GE Industrial Solutions Spectra Series Power Panelboards 400–600 Ampere Fusible Switch User Manual

g
p
g
quip
p
y
p
WARNING: Danger of electrical shock or injury.
OFF
Turn switchboard before workin
ment or removing any component. Do
e not remove circuit other component until the power is turned OFF.
General
To comply with the National Electrical Code and Underwriters Laboratories, the Canadian Electrical Code and the Canadian Standards Association, the load center must be installed in accordance with the information included on the label on the inside of the equipment. This must also be done in accordance with the applicable local electrical codes and by a qualified electrical contractor or licensed electrician.
ower ahead of the panelboard or
inside the
rotective devices or an
GEH5550 Installation Instructions R04
Spectra Series™ Power Panelboards
400–600 Ampere Fusible Switch
Switch
Bottom
Interior
Rail
Locating
Tabs
Figure 1. Positioning the switch in the panelboard interior.
WARNING: Hazard of electrical shock or burn. Turn off before working inside.
ower supplying this equipment
Installation
Use the following instructions to install a 400–600 ampere fusible switch.
1. Position the switch. Orient the switch with the of the label facing up. Align the locating hook tabs on the bottom of the switch into the square holes in the support rails on the panelboard interior, as shown in Figure 1.
If the switch is to be used as the main switch, locate it on the interior at the extreme top or bottom position.
2. Mount the switch. Secure the switch in position on the interior rail with the two self-tapping screws provided, as shown in Figure 2. Tighten the screws to 27 in-lb.
ON side
Mounting
Screws
Figure 2. Mounting the switch to the interior rail.
3. Attach the MAIN label. If this installation is to be used as a main switch, attach the panelboard label kit, on the cover of the switch where it will be plainly visible.
4. Filler plates. Filler plate kits are included with J and T fused switches to cover the width of a 36-inch-wide enclosure. When the switch is mounted in a 44-inch­wide enclosure, order filler kit AFP10T44.
MAIN label, from the
g
These instructions do not cover all details or variations in e
quip
y
p
ma
be met in connection with installation, operation, or maintenance. Should further information be desired or should
articular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the
GE Company.
ment nor do they provide for every possible contingency that
GE Industrial Systems
General Electric Company 41 Woodford Ave., Plainville, CT 06062
GEH5550 R04 0901 © 2001 General Electric Company