DEH40392 Installation Instructions R01
Spectra Series™ Power Panelboards
Circuit Breaker Cover Kit
Catalog Number
AMCB6TEDL
Application
For use with circuit breaker type TED136 and current limiter
TEDL36 (015, 020, 030, 060, 100).
Installation
WARNING: Danger of electrical shock or i njury.
Turn OFF power ahead of the panelboard or
switchboard before working inside the equipment or
removing any component. Equipment is to be
installed and maintained by properly trained and
qualified personnel only.
In the following instructions and figures, numbers in brackets
refer to the items in Table 1.
1. Confirm the contents of the kit. These kits are for
assembling fillers for TED6-frame Spectra circuit breakers
with TEDL current limiter on Spectra APNB bolt-on style
interiors. The vertical space required is 4.125 in. (3X).
The kit contains parts for 36W, 40W, and 44W
panelboards and 40W and 45W switchboards. Choose the
appropriate filler from the kit by matching its width with
the width of the existing fillers. Discard the other filler.
Figure 1 shows all the parts included in this kit, which are
listed in Table 1.
Item Description Part # Qty.
#CM 36, 40W TEDL DB 3X
1
Filler
#CM 44, 45W TEDL DB 3X
2
Filler
3 Cover support 3X 208C1850P3 2
4 Barrier center 252B1667P1 1
5 Spacer plate TED6 w/TEDL 252B2056P8 1
6 Steel drive rivet #10 x1/2" 331A3329P2 2
Thread-forming screw,
7
10-32x
8 Instruction sheet DEH40392 1
3
/8"
Table 1. Parts list for kit AMCB6TEDL.
168D1930P3 1
168D1930P4 1
N722EP16006B6 2
Figure 1. Parts Included In the circuit breaker filler kit AMCB6TEDL.
2. Attach the barrier center to the filler. Put steel drive rivets
[6] through the clearance hole in the filler [1, 2] and align
with the appropriate holes in the barrier center [4], as
shown in Figure 2. Lightly tap the rivets with a hammer to
secure into the barrier center.
4. Attach the cover support. Slide the cover support [3] onto
the existing bracket on the circuit breaker, as shown in
Figure 4. The cover support will snap into place when it is
correctly positioned.
Figure 4. Cover support snapped onto the breaker.
Figure 2. Riveting the barrier to the filler.
3. Install the space filler. Mount the spacer plate [5] to the
side without a TED6 breaker with TEDL, as shown in
Figure 3. Units that are double branch mounted do not
require a space filler. Align the holes on the spacer plate
with the holes on the filler [1, 2] and secure with threadrolling screws [7].
Figure 3. Mounting the space filler.
5. Attach the breaker to the cover. Snap the assembled circuit
breaker cover over the flexible prongs on the filler supports,
as shown in Figure 5.
Figure 5. Breaker attached to the filler plate.
Maintenance Note : Push-on circuit breaker fillers may bend if
not removed properly. To prevent bending of the filler, pull the
upper edge of the filler off the flexible prongs, then pull the
lower edge free.
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that
may be met in connection with installation, operation, or maintenance. Should further information be desi red or should
articular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the
GE Company.