DEH065 Installation Instructions R02
Spectra Series™ Power Panelboards
Bolt-On Circuit Breaker Kits
Application
These instructions apply to bolt-on circuit breaker kits with catalog numbers AMCB6QD and AMCB4QD.
For use with circuit breaker types TQD and THQD.
For use with circuit breaker cover kits AFP2QDD and AFP3QDD.
Installation
WARNING: Danger of electrical shock or injury.
OFF
Turn switchboard before workin e Equipment is to be installed and maintained b properly trained and qualified personnel only.
In the following instructions, numbers in brackets in the text and figures refer to the items in Table 1.
1. Confirm the contents of the kit. These kits are used to install Spectra TQD and THQD circuit breakers into Spectra APNB bolt-on–style interiors. The parts included in these kits are listed in Table 1.
Item Description
1 A & C pole outer strap 2 2 2 A & C pole inner strap 2 2 3 Carriage bolt, 1/4-20 x 11/2"2 3 4 Conical spring washer, 1/4"2 3 5 Nut, 1/4-20 2 3 6 B pole strap 2 2 7 Inner mounting bracket 2 2 8 Thread-forming screw 8 8
9 Outer mounting bracket 2 2 10 Screw, 1/4-20 x 3/4"46 11 Conical spring washer, 1/4"4 6 12 Screw, #10-32 x 23/4"44 13 Lock washer, #10 4 4 14 Antiturn clip 2 3
Table 1. Parts included in kits AMCB4QD and AMCB6QD.
2. Locate the side of the interior with a 2.75-inch
reference distance. The circuit breaker straps are
mounted on the side of the panel interior bus at which the distance from the nearest vertical bus face to the inner face of the bus-support rail is 2.75 inches, as indicated in Figure 2.
ower ahead of the panelboard or
inside the
ment or removing any component.
Qty. in
AMCB4QD
Qty. in
AMCB6QD
3. Install the circuit breaker straps. For three-phase applications (kit AMCB6QD), begin installing the breaker straps with the A or C phase poles, as shown in Figures 1 and 2. Slide an antiturn clip [14] over the square shank of a carriage bolt [3]. Insert the carriage bolt assembly into the appropriate square hole in the bus, so that the pin of the antiturm clip rests on the front of the bus. Place the square holes in the inner strap [2] and outer strap [1] over the bolt so that the pin of the antiturn clip fits into the small holes on the straps. Secure the assembly to the vertical bus with a conical spring washer [4] and nut [5], leaving the connection finger tight. Repeat the process for the center pole straps [6] and the other end pole straps [1, 2].
For single-phase panels, dc applications, and phase­balancing purposes (kit AMCB4QD), Table 2 lists the possible configurations. Align the appropriate strap assemblies [1, 2, 6] with the corresponding holes in the vertical bus, as shown in Figures 1 and 2. Fasten each strap assembly loosely to the vertical bus with a carriage bolt [2], conical washer [3], and nut [4], as described for the three-phase kit. When installing any of the two-pole strap configurations in Table 2, be sure to install the straps in standard phase-rotation order. When installing a two-pole and a three-pole breaker in a double-branch assembly, arrange the straps in the typical three-pole configuration, as shown in Figure 1.
A Phase B Phase C Phase
XX
X* X*
XX
* Use for single-phase panels and dc
applications.
Table 2. Possible pole configurations with kit AMCB4QD.
4. Install the circuit breaker mounting brackets and cover supports. Attach the inner breaker mounting
brackets [7] to the panel side rails with thread­forming screws [8], as shown in Figure 1. Tighten the screws to 35 in-lb. Slide the uppermost slot on the cover supports (supplied with the breaker cover kit), with the mounting tabs oriented inward, onto the outer mounting brackets [9] until they snap into place. Cover supports can be easily removed by inserting a screwdriver blade into the slot on the underside of the mounting bracket assembly and gently prying downward while pushing the support off. Install the completed outer mounting bracket assemblies on the panel side rails with thread-forming screws [8], as shown in Figure 1. Tighten the screws to 35 in-lb.
Cover
pp
pp
Su
Figure 1. Mounting TQD and THQD circuit breakers into Spectra APNB bolt-on interiors.
Strap Mounting Side
ort
Cover
Su
ort
Figure 2. Mounting TQD and THQD circuit breakers into Spectra APNB bolt-on interiors, assembly end view.