GE VersaMax IC200ALG630 User Manual

VersaMax* Analog Input, 16-Bit Thermocouple Module
1
1234567 831
ANALOG INPUT 16BIT THERMOCOUPLE 7CH
OK
Module Characteristics
Channels
Seven thermocouple or millivolt inputs
Module ID
FFFF9804
Isolation:
User input to logic (optical) and to frame ground
Group to group Channel to channel
250VAC continuous; 1500VAC for 1 minute
Not applicable None
LED indicators
OK LED: Green indicates backplane power is present. Amber indicates module fault.
Backplane current consumption
5V output: 125mA maximum. 3.3V output: 125mA maximum.
External power supply
None
Thermal derating
None
Diagnostics
Open Thermocouple, over/under range, and high/low alarm, thermistor fault (reported as internal fault).
Input Characteristics
Thermocouple types
J, K, T, S, R, none (used for mV inputs)
Spans (+/–)
19.5mV, 39mV, 78.125mV, 156.25mV, 312.5mV, 625mV
Converter resolution
15 bits + sign
Cold junction compensation
If used, reference junction temperature is measured at thermocouple termination using a precision thermistor, or supplied by system, or by fixed configuration value.
Cold junction temperature error
+/–0.25 degree Celsius (local measurement). To reduce temperature transients, thermocouple terminations should not be installed in the same cabinet as heat dissipation assemblies.
Conformity error
+/–0.3 degree Celsius, +/–0.5 degree Fahrenheit.
Accuracy, at 25° C on voltage measurement: on temp. measurement:
+/–0.2% +/- 3 degrees Celsius.
Temperature sensitivity (0° to 60°C)
+/–0.004% of reading, +/–1.5µV per ° Celsius referred to input
Normal mode rejection
60dB, at 50/60 Hz, 100% span
Common mode rejection
120 dB at 50/60Hz, 100 ohm imbalance
Common mode voltage
3 VDC maximum
Maximum voltage between channels
50V Normal mode voltage
5 VDC maximum
Scan time
60 Hz: approximately 60 milliseconds per point 50 Hz: approximately 70 milliseconds per point.
IC200ALG630
October 2016 GFK-1700L
Product Description
The IC200ALG630 Analog Input Thermocouple Module is an intelligent module that accepts seven independent thermocouple or millivolt inputs.
The module receives power from the backplane power supply. No external power source is required.
Each input channel can be configured to report millivolts ranges as 1/100 of millivolts, or thermocouple inputs as linearized temperature in tenths of degrees Celsius or Fahrenheit, with or without cold junction compensation.
The module automatically performs A/D calibration at powerup. Automatic calibration is then repeated periodically to compensate for changes in the ambient temperature. New calibration values are filtered into the current calibration values.
Host Interface
The Analog Input Thermocouple Module uses the following data types:
7 words of analog input data.  7 optional words of analog output data.
The module exchanges data in the same manner as other types of I/O modules: it provides all its input data when requested.
Diagnostics
The Analog Input Thermocouple Module performs diagnostics and provides the following information.
Alarm faults are reported if the processed value for a channel
exceeds its configured alarm limit.
Over/underrange faults are reported if the millivolt value for an
input exceeds the limits of its span.
Open circuit is checked every time a thermocouple input is read
(unless Open TC checking is disabled). If the circuit is open, a fault is reported and the input defaults to the configured channel default.
Thermistor fault will be reported as Internal fault in the I/O Fault
table.
A thermistor fault occurs if the calculated temperature value from the thermistor is less than -10 °C or greater than +75 °C.
LED Indicators
The green OK LED is on when backplane power is present to the module. If this LED is amber, it indicates a module fault.
Preinstallation Check
Carefully inspect all shipping containers for damage. If any equipment is damaged, notify the delivery service immediately. Save the damaged shipping container for inspection by the delivery service. After unpacking the equipment, record all serial numbers. Save the shipping containers and packing material in case it is necessary to transport or ship any part of the system.
VersaMax* Analog Input, 16-Bit Thermocouple Module
2
Thermocouple
or Millivolt
Inputs
Thermocouple
or Millivolt
Inputs
Install Optional
Thermistors Here
Thermocouple
Inputs
Thermocouple
Inputs
Built-In Thermistors
Located Here
CHS014
Number
Connection
Number
Connection
A1
Channel 1 (+)
B1
No connection
A2
Channel 1 (-)
B2
Shield
A3
Channel 2 (+)
B3
No connection
A4
Channel 2 (-)
B4
Shield
A5
Channel 3 (+)
B5
No connection
A6
Channel 3 (-)
B6
Shield
A7
Channel 4 (+)
B7
No connection
A8
Channel 4 (-)
B8
Shield
A9
(Thermistor (+))
B9
No connection
A10
(Thermistor (-))
B10
Shield
A11
Channel 5 (+)
B11
No connection
A12
Channel 5 (-)
B12
Shield
A13
Channel 6 (+)
B13
No connection
A14
Channel 6 (-)
B14
Shield
A15
Channel 7 (+)
B15
No connection
A16
Channel 7 (-)
B16
No connection
A17
No connection
B17
No connection
A18
No connection
B18
No connection
1234567891112131415161718
10
AI 1
AI 2
AI 3
AI 5
AI 6
AI 7
Thermistor
AI 4
A
Note: only for thermocouple carrier
IC200ALG630
October 2016 GFK-1700L
Installation Instructions
The preferred installation technique is to mount the Thermocouple Module on a Connector-style I/O Carrier and connect thermocouples to an Interposing Thermocouple Carrier as shown below. The Interposing Thermocouple-style I/O Carrier provides both box-style wiring terminals and a built-in thermistor for Local Cold Junction Compensation. It connects to the Connector-Style Carrier via a cable as shown. This allows the thermocouple connections to be located away from the I/O modules in the system. Each TC terminal on the Interposing Thermocouple Carrier accommodates one solid or stranded AWG #14 (avg. 2.1mm2 cross section) to AWG #22 (avg. 0.36mm2 cross section) wire, or two wires up to AWG #18 (avg. 0.86mm2 cross section).
However, it is also possible to mount the Thermocouple Module on one of the terminal-style carriers (box-style, spring-style, or barrier-style) and provide Local Cold Junction Compensation by using a kit that includes the correct type of thermistor, as described in the I/O Modules User Manual. Both methods are shown below. The thermistor kit must be installed on the A9 and A10 terminals of the carrier.
If the module will only be used to measure millivolt inputs, not thermocouple inputs, it can be mounted on any type of I/O Carrier. The thermistor terminals A9 and A10 cannot be used as millivolt input terminals.
Installation in Hazardous Locations
EQUIPMENT LABELED WITH REFERENCE TO CLASS I,
GROUPS A, B, C & D, DIV. 2 HAZARDOUS LOCATIONS IS SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C, D OR NON-HAZARDOUS LOCATIONS ONLY
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2;
WARNING - EXPLOSION HAZARD - WHEN IN HAZARDOUS
LOCATIONS, TURN OFF POWER BEFORE REPLACING OR WIRING MODULES; AND
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS.
Field Wiring Terminals
The terminal assignments shown below are the same for all carriers.
Wiring Connections for Carriers with Two Rows of Terminals:
Loading...
+ 3 hidden pages