Digital communications
software designed
exclusively for SVI* II ESD
About this Guide
This instruction manual applies to the following instruments and approved software:
SVI II ESD
with Firmware version
with ValVue ESD version 1.0 or greater
with a handheld communicator with DD published for SVI II ESD
The information in this manual is subject to change without prior notice.
The information contained in this manual, in whole or part, shall not be transcribed or copied without GE Oil & Gas’s written
permission.
In no case does this manual guarantee the merchantability of the PST Controller or the software or its adaptability to a spe-
cific client needs.
Please report any errors or questions about the information in this manual to your local supplier or visit
www.ge-energy.com/valves.
DISCLAIMER
THESE INSTRUCTIONS PROVIDE THE CUSTOMER/OPERATOR WITH IMPORTANT PROJECT-SPECIFIC REFERENCE INFORMATION IN ADDITION TO THE CUSTOMER/OPERATOR’S NORMAL OPERATION AND MAINTENANCE PROCEDURES. SINCE
OPERATION AND MAINTENANCE PHILOSOPHIES VARY, GE (GENERAL ELECTRIC COMPANY AND ITS SUBSIDIARIES AND
AFFILIATES) DOES NOT ATTEMPT TO DICTATE SPECIFIC PROCEDURES, BUT TO PROVIDE BASIC LIMITATIONS AND
REQUIREMENTS CREATED BY THE TYPE OF EQUIPMENT PROVIDED.
THESE INSTRUCTIONS ASSUME THAT OPERATORS ALREADY HAVE A GENERAL UNDERSTANDING OF THE REQUIREMENTS
FOR SAFE OPERATION OF MECHANICAL AND ELECTRICAL EQUIPMENT IN POTENTIALLY HAZARDOUS ENVIRONMENTS.
THEREFORE, THESE INSTRUCTIONS SHOULD BE INTERPRETED AND APPLIED IN CONJUNCTION WITH THE SAFETY RULES
AND REGULATIONS APPLICABLE AT THE SITE AND THE PARTICULAR REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE.
THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR
EVERY POSSIBLE CONTINGENCY TO BE MET IN CONNECTION WITH INSTALLATION, OPERATION OR MAINTENANCE.
SHOULD FURTHER INFORMATION BE DESIRED OR SHOULD PARTICULAR PROBLEMS ARISE WHICH ARE NOT COVERED
SUFFICIENTLY FOR THE CUSTOMER/OPERATOR'S PURPOSES THE MATTER SHOULD BE REFERRED TO GE.
THE RIGHTS, OBLIGATIONS AND LIABILITIES OF GE AND THE CUSTOMER/OPERATOR ARE STRICTLY LIMITED TO THOSE
EXPRESSLY PROVIDED IN THE CONTRACT RELATING TO THE SUPPLY OF THE EQUIPMENT. NO ADDITIONAL REPRESENTATIONS OR WARRANTIES BY GE REGARDING THE EQUIPMENT OR ITS USE ARE GIVEN OR IMPLIED BY THE ISSUE OF THESE
INSTRUCTIONS.
THESE INSTRUCTIONS CONTAIN PROPRIETARY INFORMATION OF GE, AND ARE FURNISHED TO THE CUSTOMER/OPERATOR SOLELY TO ASSIST IN THE INSTALLATION, TESTING, OPERATION, AND/OR MAINTENANCE OF THE EQUIPMENT
DESCRIBED. THIS DOCUMENT SHALL NOT BE REPRODUCED IN WHOLE OR IN PART NOR SHALL ITS CONTENTS BE DISCLOSED TO ANY THIRD PARTY WITHOUT THE WRITTEN APPROVAL OF GE.
Copyright
All software is the intellectual property of GE Oil & Gas.
The complete design and manufacture is the intellectual property of GE Oil & Gas.
*
Masoneilan
accurate at the time of publication and is subject to change without notice.
Copyright 2014 by GE Oil & Gas. All rights reserved.
PN 720002-392 Rev. G
, SVI*, and ValVue* are registered trademarks of GE Oil & Gas. All information contained herein is believed to be
Document Changes
Version/ DateChanges
C/02-2011
D/3-2013
E/9-2013
F/02-2014
G/8-2014
Added to section on DO switches configuration.
Updated Registration section updated to GE logo software
Removed references to double-acting
Fixed issues from S. Leledy.
Changed the Simplified Switch diagram in Configure I/O section.
Added Cautions about Position Low and Upper Limits.
Added text about the 4-20 retransmit galvanic isolation.
Updated the Simplified Switch diagram in Configure I/O section
and updated the text.
Updated Configure tab to add Air Loss Trip and Trip Level fields.
Update software install section to reflect 1.10.0 version.
Contents
About This Manual..................................................................................................................................................................... 19
System Requirements.............................................................................................................................................................. 21
Activating the License .....................................................................................................................................................47
Main Window............................................................................................................................................................................... 49
Editing Plant Schedule for a Selected Device.......................................................................................................54
Export to Excel .................................................................................................................................................................... 56
Connected Devices Help ........................................................................................................................................................56
Launching Set Options.................................................................................................................................................... 58
Set Options Screen............................................................................................................................................................58
Multiplexor Setup and Operation ....................................................................................................................................... 62
Configuring the Multiplexor ..........................................................................................................................................64
Launching a Device ..................................................................................................................................................................69
Selecting an Offline Device ...........................................................................................................................................71
Selecting a Connected Device.....................................................................................................................................74
Device Information ...........................................................................................................................................................75
Find by Tag ...........................................................................................................................................................................75
Right Clicking on Device Name ...........................................................................................................................................77
Working in ESDVue ................................................................................................................................................................... 82
Modes of Operation ......................................................................................................................................................... 82
ESDVue Help ................................................................................................................................................................................ 84
Help Menu.............................................................................................................................................................................84
Status Screen...................................................................................................................................................................... 91
What You Can Do on the Monitor Screen ...................................................................................................................... 93
Pressure, Pressure1 and Pressure2.......................................................................................................................... 94
Position Indicator .............................................................................................................................................................. 94
Signal ...................................................................................................................................................................................... 94
Changing the Setpoint ............................................................................................................................................................ 96
Status on the Monitor Screen .............................................................................................................................................. 98
Tag Information.......................................................................................................................................................................... 99
Monitor Context Menu ......................................................................................................................................................... 101
How to Create Reports ................................................................................................................................................ 103
View All Parameters .............................................................................................................................................................. 110
All ........................................................................................................................................................................................... 112
PST DATA ............................................................................................................................................................................ 114
What you can do on the Trend Screen ........................................................................................................................ 119
Trend Graph Features .......................................................................................................................................................... 120
Changing the Graph View .......................................................................................................................................... 120
Capture to Clipboard .................................................................................................................................................... 120
What You Can Do on the Configure Screen ............................................................................................................... 123
Changing Tag Information ................................................................................................................................................. 124
Language ................................................................................................................................................................................... 128
Pressure Units .......................................................................................................................................................................... 129
Air Action ................................................................................................................................................................................... 129
What you can do on the Calibrate Screen.................................................................................................................. 151
Auto Tune ................................................................................................................................................................................... 157
Auto Tune Diagnostic Graph ............................................................................................................................................. 162
Diagnostic Graph Color Legend .............................................................................................................................. 163
Set Graph Scale............................................................................................................................................................... 163
Show Computed Calibration Results..................................................................................................................... 170
Save to File......................................................................................................................................................................... 171
Export to Excel ................................................................................................................................................................. 173
Run Find Stops................................................................................................................................................................. 177
What you can do on the Diagnostics Screen ............................................................................................................ 185
Running a Step Test ...................................................................................................................................................... 186
Show Computed Step Results .................................................................................................................................. 199
Save to File......................................................................................................................................................................... 201
Export to Excel ................................................................................................................................................................. 203
Show Computed Extended Signature Results .................................................................................................. 217
Save to File................................................................................................................................................................................. 219
Export to Excel.......................................................................................................................................................................... 221
Loading Data from a Database............................................................................................................................... 223
Load Data from a File on Diagnostics Screen .................................................................................................. 226
What you can do on the PST Screen............................................................................................................................. 231
4. Set PST Parameters.................................................................................................................................................. 237
Changing Interval of Days.......................................................................................................................................... 238
Changing New PST Schedule.................................................................................................................................... 239
Partial Stroke Test Settings........................................................................................................................................ 242
Maximum Time................................................................................................................................................................ 244
Dwell Time ......................................................................................................................................................................... 245
Friction High Limit.......................................................................................................................................................... 245
Load Data from Database ......................................................................................................................................... 267
Load from File .................................................................................................................................................................. 273
Diagnostic Graph Color Legend .............................................................................................................................. 282
PST Context Menu .................................................................................................................................................................. 283
What you can do on the Status Screen ....................................................................................................................... 285
Active Faults.............................................................................................................................................................................. 287
Clear Current Faults............................................................................................................................................................... 294
Clear All Faults.......................................................................................................................................................................... 296
Set Fail High/Low.................................................................................................................................................................... 300
Status Fault Code List................................................................................................................................................... 300
Status Context Menu............................................................................................................................................................. 325
What you can do on the Check Screen........................................................................................................................ 327
Information Displayed on the Check Screen ............................................................................................................. 328
List of Available HART Commands ......................................................................................................................... 331
Methods to Set Up the SVI II ESD..................................................................................................................................... 335
Steps to Set Up SVI II ESD.................................................................................................................................................... 335
Run Find Stops................................................................................................................................................................. 336
Run Auto Tune.................................................................................................................................................................. 341
6Ready to Install ................................................................................................................................................................. 26
7ValVue ESD CD Browser ............................................................................................................................................... 27
9PRM Plug-In Main Screen.............................................................................................................................................28
10Install Shield Central Server........................................................................................................................................29
11PRM Central Server License Agreement............................................................................................................... 29
12PRM Central Server Destination Folder ................................................................................................................. 30
13PRM Central Server Database Directory Destination Folder....................................................................... 31
14Ready to Install ................................................................................................................................................................. 31
15PRM Central Server Dialog .......................................................................................................................................... 32
16PRM Central Server Dialog II....................................................................................................................................... 32
17PRM Central Server Dialog III...................................................................................................................................... 32
21PRM Plug-In Main Screen.............................................................................................................................................34
28Ready to Install ................................................................................................................................................................. 38
29Owner and Product Key Registration Window.................................................................................................. 39
30Applying Owner and Product Key Information.................................................................................................. 40
31Software and Mux Key Window ............................................................................................................................... 40
36Registration Email Sent Dialog.................................................................................................................................. 43
50Applying Edits to the Plant Schedule......................................................................................................................54
52Setting PST Schedule for Individual Device .........................................................................................................55
53Plant Schedule Set for Individual Device ..............................................................................................................55
54Selecting Export to Excel .............................................................................................................................................. 56
55Accessing Connected Devices Tools Menu .........................................................................................................57
56Launching Set Options ..................................................................................................................................................58
57ValVue ESD Set Options Screen ................................................................................................................................59
58Context Menu with Mux Functions..........................................................................................................................63
61Selecting an Offline Device..........................................................................................................................................71
63File Open Window Launched at ValVue ESD ...................................................................................................... 72
64Offline dp3 Data File Default Location................................................................................................................... 73
65Offline Device Displayed at Monitor Screen........................................................................................................73
66Selecting a Connected Device...................................................................................................................................74
67Device Information Displayed....................................................................................................................................75
68Right Clicking on Connected Device .......................................................................................................................77
69Selecting the Historical View Start Date ............................................................................................................... 79
72Leaving Normal Mode Warning................................................................................................................................ 83
73Entering Normal Mode Warning...............................................................................................................................84
90View All Parameters Window.................................................................................................................................. 110
91View All Parameters - Device Tab......................................................................................................................... 111
92View All Parameters - All Tab .................................................................................................................................. 112
93View All Parameters - PST Config Tab................................................................................................................. 113
94View All Parameters - PST DATA Tab................................................................................................................... 114
95View All Parameters - CAL Tab............................................................................................................................... 115
96View All Parameters - Config Tab ......................................................................................................................... 116
97View All Parameters - DYNAMIC Tab ................................................................................................................... 117
98Trend Screen Displaying All Parameters .......................................................................................................... 119
113Setup Wizard - Setting Tag and Descriptor...................................................................................................... 135
114Tag and Descriptor Entered..................................................................................................................................... 136
115Enabling Set Air Action............................................................................................................................................... 137
137Launching Auto Tune.................................................................................................................................................. 157
143PID Values - Previous and New .............................................................................................................................. 161
146Selecting Set Graph Scale......................................................................................................................................... 163
151Selecting Load Data from Database ................................................................................................................... 166
153Selecting Load Data from File................................................................................................................................. 167
155Opening File for Additional Curve ......................................................................................................................... 168
156Selecting Calibration Record ................................................................................................................................... 169
158Selecting Show Computed Result......................................................................................................................... 170
159Auto Tune Calibration Computed Result ........................................................................................................... 170
160Selecting Save to File .................................................................................................................................................. 171
162Selecting a Folder for Saving File .......................................................................................................................... 172
163Selecting Export to Excel ........................................................................................................................................... 173
164Diagnostic Graph Data - in Excel .......................................................................................................................... 174
165Calibrate Screen Context Menu ............................................................................................................................. 175
166Selecting Run Find Stops........................................................................................................................................... 177
167Starting Run Find Stops Dialog............................................................................................................................... 178
173Valve Open Dialog........................................................................................................................................................ 182
182Running a Step............................................................................................................................................................... 189
183Loading Data for a Step ........................................................................................................................................... 189
191Selecting Load Data from Database ................................................................................................................... 195
193Selecting Load Data from File ................................................................................................................................ 196
195Opening File for Additional Curve ......................................................................................................................... 197
196Selecting Step Test Record....................................................................................................................................... 198
198Selecting Show Computed Result......................................................................................................................... 199
200Selecting Save To File ................................................................................................................................................. 201
202Selecting a Folder for Saving File .......................................................................................................................... 202
203Selecting Export to Excel........................................................................................................................................... 203
204Diagnostic Graph Data - in Excel .......................................................................................................................... 204
206Start and End Positions Error Message .............................................................................................................. 206
218Selecting Load Data from Database ................................................................................................................... 213
220Loading Extended Signature Data ....................................................................................................................... 214
221Selecting Load Data from File ................................................................................................................................ 215
223Opening File for Additional Curve ......................................................................................................................... 216
224Selecting Signature Data Record.......................................................................................................................... 216
226Selecting Show Computed Result......................................................................................................................... 218
228Selecting Save To File.................................................................................................................................................. 219
230Selecting a Folder for Saving File .......................................................................................................................... 220
231Selecting Export to Excel ........................................................................................................................................... 221
232Diagnostic Graph Data - in Excel .......................................................................................................................... 222
233Selecting Load From DB ............................................................................................................................................ 223
234Device and Data Type Displayed........................................................................................................................... 224
235Load Data from DB Tool Tip..................................................................................................................................... 225
239Opening File for Diagnostic Data .......................................................................................................................... 227
240Selecting Step Test Record....................................................................................................................................... 228
243PST Test Settings Graph............................................................................................................................................. 232
246Load from DB.................................................................................................................................................................. 235
248Extended Signature Result Window - Computed Values........................................................................... 236
249Changing Interval of Days........................................................................................................................................ 238
255Max Time Error Message........................................................................................................................................... 244
270Selecting Set Graph Scale......................................................................................................................................... 254
274Selecting Data Source................................................................................................................................................ 256
276Selecting Show Computed Result......................................................................................................................... 257
278Position and Pressure vs. Time View ................................................................................................................... 259
279Selecting Save to File.................................................................................................................................................. 260
281Selecting a Folder for Saving File .......................................................................................................................... 261
282Selecting Export to Excel........................................................................................................................................... 262
283Diagnostic Graph Data - in Excel .......................................................................................................................... 263
285Terminal Board and Pneumatic Test Progress Dialog ................................................................................ 265
286Terminal Board and Pneumatic Test Complete ............................................................................................. 265
287Load Data Selections.................................................................................................................................................. 266
288Selecting Data to Load............................................................................................................................................... 267
289Selecting Load From Database.............................................................................................................................. 268
290Launching Load Data from Database................................................................................................................ 269
291Device and Data Type Displayed .......................................................................................................................... 270
293Load Data from DB Tool Tip..................................................................................................................................... 271
295Selecting Load From File........................................................................................................................................... 273
297Opening File for Diagnostic Data.......................................................................................................................... 274
298Selecting Diagnostic Record ................................................................................................................................... 275
301Selecting Start Date for Historical View ............................................................................................................. 278
302Selecting the Historical View End Date .............................................................................................................. 279
304Selecting a Historical View Data Point................................................................................................................ 281
308Status Screen Active Faults Tab ............................................................................................................................ 287
309Status Screen General Tab....................................................................................................................................... 288
317Executing Clearing All Faults................................................................................................................................... 296
319Entering an Individual Fault..................................................................................................................................... 298
320Clearing an Individual Fault..................................................................................................................................... 299
327Check Context Menu ................................................................................................................................................... 333
328Selecting Run Find Stops........................................................................................................................................... 336
329Starting Run Find Stops Dialog............................................................................................................................... 337
335Valve Open Dialog........................................................................................................................................................ 341
3Troubleshooting ValVue ESD Used with Mux ..................................................................................................... 67
4Burst Mode Data Return............................................................................................................................................... 68
The ValVue ESD Instruction Manual is intended to help a Field Engineer install ValVue ESD, and
setup, calibrate, and test an SVI II ESD using ValVue ESD. If you experience problems that are not
documented in this guide, contact the factory or your local representative. Sales offices are
listed on the back cover of this manual.
Masoneilan's ValVue ESD software is a Human-Machine Interface (HMI) software tool that
provides a powerful interface to Masoneilan’s SVI II ESD, the Model 12300 and 12400 Digital
Level Transmitter (DLT), and other HART instruments used in a Safety Instrumented System
(SIS).
ValVue ESD is used to configure, calibrate and perform partial stroke testing and valve
diagnostics with the SVI II ESD utilizing HART communications protocol.
Using ValVue ESD you can:
Monitor SVI II ESD Operation
Quickly Set Up the SVI II ESD
Advanced SVI II ESD Set Up
Calibrate the SVI II ESD
Configure or Run Partial Stroke Test (PST)
Check the SVI II ESD Status
Perform Diagnostics on SVI II ESD
System Requirements
Listed below are the hardware and software requirements for the computer used with ValVue
ESD:
Hardware
Processor:PC with minimum 1 GHz Intel Pentium or compatible
6. Click the accept radio button, click Next and the Choose Destination Location screen
appears (Figure 12).
Figure 12PRM Central Server Destination Folder
NOTEClick Change to open the Choose Folder screen to navigate to and
designate a non-default folder.
7. Click Next and the screen appears (Figure 13).
CAUTIONClick Change to open the Choose Folder screen to navigate to and
designate a non-default folder. Make a note of this machine and
folder share name, ValVue ESD DATABASE as it is required when
installing the PRM PLUG-IN ValVue.The installer also creates a data
source for the database. If the database already exists, the
installer updates the tables as necessary. No existing data is lost.
This installs the plug-in and the client software and a database. Install this application on
every computer on which PRM Client is installed after PRM Central is installed for the
particular PRM server. This application does not require registration.
To install the software:
1. Insert the CD into computer CD drive and the CD browser launches (Figure 19).
8. Navigate to the desired folder, click OK and Next and the screen appears (Figure 26).
CAUTIONUse the same folder as with the ValVue ESD DATABASE.The
installer also creates a data source for the database. If the
database already exists, the installer updates the tables as
necessary. No existing data is lost.
When you start ValVue ESD for the first time the registration window launches. ValVue ESD
software must be registered to activate the permanent installation. ValVue ESD can be used
without registration for 60 days. Registration allows the factory to keep track of all of ValVue
ESD users so that we can notify you of any changes or important information about new
software features and updates. A registration card is included with the installation CD.
The software package contains a serial number. Keep a record of the serial number in a
secure location. Do not discard the registration card. To register your software, you must
launch the ValVue to obtain an installation ID number, then contact the factory by mail,
telephone, email or Fax, and provide your name, company’s name, contact information, the
CD-ROM serial number, and the installation ID number from the ValVue ESD login display.
Contact information is provided on the registration card that is part of the software package.
Your serial number is located on the ValVue ESD package and on the enclosed sticker. Place
the serial number sticker on the detachable card included with the Registration Instruction
card and store the card in a secure location. You need the serial number to move ValVue ESD
to a different computer.
The Software Registration Center provides you with software keys that you enter the next
time you run the program. Contact the factory for a new software key if you are moving
ValVue ESD to a different computer or, if you do not have a serial number.
To register ValVue ESD:
1. Start ValVue ESD either by clicking on the desktop icon or using the Start programs
selection. When you start ValVue ESD, the registration window appears (Figure 29).
Figure 29Owner and Product Key Registration Window
5. Enter your name and the name of your company. You are now ready to contact the
factory with this information, to obtain your software keys.
There are four methods shown on the Registration Instruction Card:
6. Click Save to File to save your registration file. A Windows browser appears (Figure 34).
7. Navigate to the desired folder, name the registration information (.txt) file and click Save.
Figure 34Save Registration Information
A dialog appears (Figure 35).
8. Email the registration information by clicking Yes.
42 | =GE Oil & Gas
Figure 35Registration File Saved Dialog
ValVue ESD launches your email service and automatically attaches the registration and
Masoneilan’s Software Registration Center.
9. Click Send to email the registration.
If your email program fails to start, contact the software registration center using the
email address, phone number, address, or fax number given on the registration card
(contained with the ValVue ESD cd).
A dialog indicating the email has been sent appears (Figure 36).
After you have sent the registration info, you are provided with software keys for ValVue ESD
and optional features (when applicable).
Once you have your key, to enable the program:
1. Start ValVue ESD.
2. Choose Help > View Registration.
3. Enter the Product Key (if not already entered).
Figure 36Registration Email Sent Dialog
4. Click OK. On the 2nd registration screen, enter the software key returned by the factory
(Figure 37).
Figure 37Entering Software Key
5. Enter the software key, if applicable, by clicking on the screen under the Unlock Keys field
and the field becomes active. Enter the Mux software key.
You receive a licensing file in response from the factory (Figure 43).
Activating the License
To activate the license:
1. Select Help > Software License and Figure 44 appears.
Figure 43Licensing File
2. Click Load Licensing File. The software is licensed and the licensed number of tags
appear at the top of the ESD Licensing tool and the number is greyed out in the Number of Tags drop down list.
After you have successfully started ValVue ESD the main window appears (Figure 45), divided
into two tabs:
Connected Devices - Lists all connected devices in the SIS found during initial scan or
re-scan.
Plant Schedule - Provides access to view the next scheduled PST, edit schedule and
synchronize devices
Each tab has an associated screen and functions. The Connected Devices screen appears on
startup and lists all scanned, available devices on the selected COM port. When Load Device Listfrom Database on Startup option is enabled (see “Using a Device List File” on page 60) ValVue
ESD does not re-scan the port.
Figure 45ValVue ESD Main Window - Connected Devices
When you start ValVue ESD the main window displays the scanned, connected devices and
may also display an icon (Figure 46), located to the left of the device name.
Figure 46ValVue ESD Main Window with Disconnected Device Icon
There are four possible icons:
Connected - indicates that the device is connected to the SIS and is available for
running ValVue ESD.
Disconnected - indicates that the device is disconnected from the SIS and is only
available offline.
Status - indicates that there is more device status information available on the
Status screen.
Unlicensed - indicates that there is no ValVue ESD license available. In this case
you are not able to launch ValVue ESD for the selected device.
When you select the Plant Schedule tab the Plant Schedule screen appears (Figure 47). The
Plant Schedule tab indicates when the last PST (Partial Stroke Test) was executed and when
the next PST is scheduled to occur. You can also edit the plant PST schedule, synchronize the
current device, synchronize all devices in the SIS (Safety Integrated System) and export all
schedule data to an Excel file.
Use the Plant Schedule tab to edit the schedule for when PST (Partial Stroke Test) is executed
for the SIS (Safety Integrated System). You can edit the schedule for an individually selected
device or you can edit the PST schedule for all devices connected to the plant.
You can save or create a comma separated value file (.csv) of the Plant Schedule data and
export the file to Excel. With the Excel file you can perform schedule analysis and export the
data to other formats. To export a plant schedule to Excel:
Click Export to Excel (Figure 54).
ESDVue launches Microsoft Excel and displays the plant schedule data, as Excel values.
Connected Devices Help
Launch Help from the Connected Devices screen, either by clicking Help at the bottom right
corner of the screen, or by selecting Help from the Help menu and help appears starting at the
Connected Devices content.
Master Mode - select Primary or Secondary Master
Use Multiplexor - enable/disable Multiplexor feature
OK - saves changes and opens the Connected Devices screen
Cancel - cancels any changes you have made to the Options parameters and opens
the Connected Devices screen
Figure 57ValVue ESD Set Options Screen
Interval Between CyclesPatrolling is the time at which ValVue ESD searches for connected
devices. ValVue ESD searches through all connected devices. Each
time a search through all connected devices is executed is considered a cycle. You can set the interval time between cycles; i.e. when
one patrolling cycle has been completed how long ValVue ESD waits
to start another patrolling cycle. To change the interval between
patrolling cycles click in the field and change the number (in seconds).
Interval Between DevicesPatrolling is the time at which ValVue ESD searches for connected
devices. ValVue ESD searches through all connected devices. Each
time a search through all connected devices is executed is considered a cycle. You can set the patrolling interval time between
devices within a cycle; i.e. when one device has been recognized
how long ValVue ESD waits to patrol for the next device. To change
the patrolling interval between devices click in the field and change
the number (in seconds).
Using a Device List FileThe device list can be saved in a file to eliminate rescanning each
time Connect is selected. This is useful only with multiplexors. Unless
Load Device List from Database on Startup is selected as an option,
the device addresses file used is temporary and is rescanned each
time the program is restarted. If selected, you can select a file to
save the device list. This file is read when the program is started and
the list displayed. Select New File to change the file or create a new
one.
Com Port SelectionSelect the COM Port on your PC that is connected to the HART
modem. If you’re not sure about the COM port the modem is connected to, go to the Windows Device Manager to locate the Com
Port number assigned to the PC.
MultidropWhen more than one device is connected to a loop or if polling
addresses other than 0 have been assigned to devices, select Allow Multidrop. ValVue ESD supports HART devices, including SVI and SVI
II, SVI II ESDs, and HDLTs with non-zero polling addresses and supports multiple SVI and SVI II and SVI II ESDs on the same loop for split
ranging, for example. If the box is unchecked, ValVue ESD looks for
devices only at polling address 0. When in multidrop mode, even if a
device is found at polling address 0, ValVue ESD polls addresses up to
15.
Master ModeValVue ESD can send commands to a HART device as a primary mas-
ter or as a secondary master. HART is a Master-Slave communication
protocol, where the slave (field device) replies to commands sent by
the master. The HART protocol allows for a device to communicate
simultaneously with two masters, as long as they are different Masters. One being a Primary Master and the other being a Secondary
Master. A Primary Master is defined as a host (or interface) which is
connected permanently with a slave, such as a control system. A
Secondary Master is a host (or interface) connected temporarily to
the slave (like a handheld or laptop computer) and that is not part of
the control system.
When used with a multiplexor, operation is allowed when a second
HART master, such as a DCS system, is communicating. The ValVue
ESD program must be configured to match the configuration of the
multiplexor. If the multiplexor is a primary master, ValVue ESD must
also be configured to be a primary master.
Mux OptionThe Use Multiplexor option allows you to select multiplexor opera-
tion. If the Use Multiplexor control is checked then the MUX Setup,
and MUX reset controls are added to the Connected Devices page
context (right click) menu.
Check Use Multiplexor and set a baud rate that is equal to
the baud rate set on the multiplexor hardware with DIP
switches.
NOTESettings in the Options page for ValVue ESD must agree with the
MUX configuration settings that are also shown. The Mux
configuration can have originated in other applications.
NOTEDo not check Use Multiplexor unless ValVue ESD is connected to
Multiplexor hardware.
The MTL multiplexor supports baud rates of 9600, 19200, and
38400. You must set a baud rate that matches the
configuration of the hardware.
After the options are selected, select OK to accept the
changes and exit to Connected Devices page or select
Cancel to discard the changes.
ValVue ESD supports the MTL HART multiplexor allows you to monitor and operate many SVI II
ESD PST controllers from a single computer.
The MTL 4840 HART maintenance system is a widely used multiplexor for communicating with
HART instruments. Connected to a computer serial port with an RS232/RS485 converter, the
multiplexor is capable of supporting up to 31 nodes, each with the capability of supporting up
to 16 sub nodes. Each sub node can control 16 loops. Therefore, the multiplexor provides the
potential to communicate with a maximum of 7936 HART loops, i.e., 31 (nodes) x 16 (sub
nodes) x 16 (loops) using one computer interface. Additionally, the multiplexor supports the
multidrop connection of HART devices on a single loop. Therefore, using the multidrop feature
it is possible to expended capacity of a system beyond 7936 HART devices.
For more information regarding the MTL multiplexor, refer to the manufacturer’s documents.
Using the multiplexor capability of ValVue ESD and the MTL multiplexor, monitoring and
communicating with many SVI’s and other HART devices is possible. After start-up and login to
the ValVue ESD program, the Connected Devices screen appears and provides options to
setup the multiplexor.
Use of the optional multiplexor ValVue ESD software requires an additional license and
registration. Contact your local representative for licensing assistance. A 60 day trial of the
multiplexor option is provided without licensing.
Selecting Mux Setup
To select the Mux Setup function:
1. Check Use Multiplexor and select the baud rate and node in the ValVue ESD Set Options
(see “Mux Option” on page 61) return to the Connected Devices page.
2. Right-click on the Connected Devices page and select Mux Setup (Figure 58).
1. Select MUX Setup from the context menu to setup the nodes used on the MTL multiplexor.
The Connected Devices page appears and prompts for the nodes to be configured.
2. Type a number between 1 and 31 for the desired node, e.g. 1 for node 1 and select OK. The
node address must match the DIP switch setting on the MUX hardware.
The Multiplexor Setup dialog appears (Figure 59).
3. Set the Master Mode: Primary or Secondary Master.
NOTEValVue ESD must be configured to be the same type of master as
The multidrop option substantially increases the time required to scan each node of the Mux.
Multiplexor Options Setup Dialog
Use this procedure to setup Multiplexor options.
1. Right-click in the Connected Devices page and select Set Options.
the multiplexor. Use both the Options setup and Mux setup
screens to check and compare the selection. Both can be primary
or both can be secondary.
2. Check the Use Multiplexor box on the Options page.
3. Select which communication serial port the computer uses for the HART communication
channel. Once selected in the Options dialog, this selection overrides any selection on the
command line that starts the program.
4. Select the baud rate to match that set with dip switches on the multiplexor hardware.
The device list is automatically saved to the device database. This file is read whenever the
program is started and the saved device list appears. This is particularly useful for a
multiplexor connected to many devices and saves the time required to re-scan.
Tag This is a user-entered value of up to 7 characters, used to identify the
MTL multiplexor node in the system. The tag appears in Device List
box in Connected Devices page.
DescriptorA description with up to 15 characters for the MTL multiplexor node.
Retry CountThe number of times the multiplexor retries sending a command to a
Hart device before returning with an error. The valid range for this
number is 0 to 5. The recommended number is ‘3’.
Preamble CountA device using the HART protocol sends a short string of characters
at the beginning of each communication to wake up the other
device. This string is called a preamble. The number of preambles
prefixed to each Hart command sent to a device varies from device
to device. The valid range is 2 to 20. Recommended values for this
parameter are 3 to 5 when using the Mux. ValVue ESD allows for a
user-configured Mux preamble count.
Scan Age TimeThe length of time in seconds that scan data remains valid. An error
is returned when the scan data requested is older than the time
when the data was last updated. This parameter set s this time for
other applications that use the multiplexor. ValVue ESD does not
support the scanning feature.
Multiplexor Master ModeValVue ESD Options must be set to use the same mode as the multi-
plexor. Other applications that use the multiplexor or other HART
masters can require a special selection. See the multiplexor documentation for further information.
Search MethodWhen building a device list, the multiplexor can use one of three
methods:
Polling Address 0 only - This method looks only at polling
address 0 for each loop. Any devices on a loop with a
non-zero polling address are not found.
Mux Reset
One Device - For each loop, all polling addresses are searched
until a device is found. The multiplexor does not continue the
search on a loop after the first device is found.
Multidrop - For each loop, polling address 0 is checked. If a
device is found, no further search is performed on that loop. If
no device is found at polling address 0, polling addresses 1 15 are searched and any devices found are added to the
device list.
Select Mux Reset to issue a reset command to a node of the multiplexor. This function is
enabled and used only in the multiplexor configuration of the program. You are prompted for
the node that is to be reset. When reset, the multiplexor node re-scans all of the devices
connected to it and depending on the multiplexor options set for the multiplexor, can take
some time to complete. If hardware has been added to the Mux or connected to different Mux
channels a rescan must be performed before the ValVue ESD re-scan can be used.
The Mux Reset is necessary when adding or removing HART devices on a Mux network. This
function updates the Mux’s Look Up Table utilized by ValVue ESD to map devices.
The MTL multiplexor has the capability to continually scan the connected Hart devices to
report the results. ValVue ESD does not use this feature, but the option is provided to configure
the multiplexor as needed by other applications.
The multiplexor can be used to request information about HART devices. Select the MUX Reset
popup menu function to issue a reset command to a node of the multiplexor. You are
prompted for the node that is to be reset. When it is reset, the multiplexor node re-scans all of
the devices connected to the node (this hardware rescan is different from the re-scan done by
ValVue ESD from the Re-scan popup menu function). Depending upon the options set for the
multiplexor, this can take a while to complete. No communication can be done with devices on
the selected node until the reset is completed. After the reset is finished, select Re-scan popup
menu function to build a device list.
A device list is arranged in the order found on the multiplexor’s channels. This list can be very
long if there are many connected devices. To find a device by its tag, select the Find by Tag
button to open a text entry dialog. Enter a tag name to allow ValVue ESD to search the device
list for a device with a matching tag. If found, the device is selected and the window scrolled
so that its line is visible.
NOTEThe Mux hardware re-scan is different from the re-scan performed
by ValVue ESD from the Re-scan button. No communication
between ValVue ESD and any device takes place on the node until
the reset is completed. This can take several minutes, depending
on MUX loading.
Selecting the Re-scan popup menu function causes ValVue ESD to build a new device list. All
nodes are checked. If there are a large number of devices connected to the multiplexor, this
function can take some time to complete. When the re-scan is completed, you can optionally
save the device list to a file so that rescanning is not necessary every time ValVue ESD is
started.
Table 3 lists some of the problems, causes, and corrective actions you may encounter when
setting up ValVue ESD used with a multiplexor (Mux).
Table 3Troubleshooting ValVue ESD Used with Mux
ProblemCauseCorrective Action
No devices foundBoth ValVue ESD and AMS are
connected to the Mux
The Mux is configured for AMS
communication
Baud rate setting does not
match setting
HART converter (RS-232 to
RS485) not working properly.
Expected device is not found in
Connected Devices list
Devices all have the same tag
name in Connected Devices
MuxUse Set Options in ValVue ESD to match the set-
Check for loose wires
Check for power cabling
between converter and Mux
Device was added after the
Mux performed its last scan
ValVue ESD and Mux are not
configured as the same type of
master
Connect ValVue ESD to the device with a
modem. If the installation is fundamentally safe
connect the input to the MTL 4046P Isolator. In a
general purpose system, connect directly to the
device wires.
Reconfigure the Mux for Cornerstone communications mode with MTL provided software.
ting in the Mux. Refer to the dip switch setting
on the MUX.
Check configuration of converter. Refer to the
manufacturer's instructions.
Click the Reset Mux button to update or power
off/on the Mux.
Set Mux and ValVue ESD so both are Primary
Master or both are Secondary Master.
The Burst Mode is a mode where the HART device continuously sends out data without being
polled for such data, by a Master. This mode is useful only for devices that are passive (i.e. not
a HART master), such as a HART to Analog converter (SPA from Moore Industries, Tri-Loop by
Rosemount). It is not necessary to set the burst mode to allow communications with a control
system since the control system is a master capable of polling the device. Turning on Burst
mode in cases where it is not required will affect the communication bandwidth.
Table 4 provides a summary of the data returned from the Burst mode (HART Command #3
equivalent to Process-Vars-Current).
Table 4Burst Mode Data Return
VariableDescriptionUnits/Range
SVI II ESD (firmware 312)
PV (Primary Variable)Valve position0-100%
SV (Secondary Variable)Actuator Net Pressure0-150 psig
TV (Tertiary Variable)Not used (Future)
QV (Quaternary Variable)Not used (Future)
Use this procedure to configure a burst mode.
1. Select the intended device from the Connected Devices page.
2. Right-click on the gray background of the window to pop up a context menu.
3. Select the Burst Mode Control dialog.
4. Select the desired command.
5. Select OK.
NOTEWhen burst mode is enabled, ValVue ESD DOES NOT allow the
detailed device view to open communications to the device.
ValVue ESD opens the Connected Devices connection window (Figure 60), searches for
connected devices and lists those devices. To stop the searching process, select Stop. The list
includes offline device files and live devices. Scanning can take a few seconds if multidrop is
selected. When a Multiplexor is used, the process can take a longer time, depending upon
how many devices are connected.
The Connected Devices window is the interface tool for ValVue ESD and devices operating
ESDVue. Once a connected device has been selected and launched, ESDVue initiates the
selected device.
NOTEValVue ESD is the main interface for connected devices. Once a
connected device is selected and launched the software tool for a
device is called ESDVue.
There is on offline mode available in ValVue ESD to work with a disconnected Masoneilan
HART devices.
The offline options serve two purposes:
When SVI II ESD Offline is selected, you are prompted to select a dump file with a dp3
extension that contains configuration and calibration data used for running the SVI II ESD.
Viewing configuration, calibration and diagnostic data, for SVI II ESD using a dump file
(.dp3).
Learning the features and functions of both SVI II ESD and ValVue ESD when they are
After the initial device scan executed when you launch ValVue ESD, the Connected Devices
screen automatically appears and shows any devices found connected during the scan.
Notice in Figure 61 that the offline device was found.
To select and activate the device:
1. Either:
Click on the device name to highlight and then click on Select (Figure 61).
or
Double-click on the device name
Figure 61Selecting an Offline Device
OR
Right-click on the device name and select Launching ESDVue (Figure 62).
2. Select a dump file as a simulated device. The dump files are installed with ValVue ESD in
the same location as the program file: e.g. C:\Program Files\DFC\ValVue ESD/Data. The
default location for SVI II ESD file Open window is shown in Figure 63.
After you have successfully logged into ValVue ESD the software automatically scans the SIS
(Safety Integrated System) for any devices that are connected to the system. The connected
devices that are found during the scan appear as shown in Figure 66.
To activate a connected device:
1. Click on the name of the device for activation (Figure 66).
2. Click Select.
ValVue ESD launches the selected device and the Monitor screen appears.
When you start ValVue ESD the software scans all the devices connected to the controlling
computer. As ValVue ESD executes scanning the software also checks the status of each
connected device. The status information is shown when you click on the name of a device
and appears in a tool tip format (Figure 67).
Figure 67Device Information Displayed
Find by Tag
To find a device by its tag name:
1. Select Find by Tag to open a text box.
2. Enter a tag name.
3. Select OK.
The software searches for a device with a matching tag. When found, the device is selected.
1. Select Re-Scan on the Connected Devices screen. In the:
Direct-connect configuration of ValVue ESD all polling addresses are checked if the
options allow multidrop.
Multiplexor configuration, all nodes are checked. If there are a large number of devices
connected to the multiplexor, this function takes time to complete.
The rescan is completes.
2. Save the device list to a file so that rescanning is not necessary every time ValVue ESD is
started. If there is only one device on the loop, select Stop when it has been found to save
scan time.
When you right-click on a connected device name on the main ValVue ESD screen (Figure 68),
you can perform several functions particular to the selected device:
Launching ESDVue - launches ValVue ESD
Historical View - launches a historical performance view of the selected device
View Latest PST - launches the graph representing the most recent PST (Partial Stroke
Testing) of the selected device
Figure 68Right Clicking on Connected Device
Launching ValVue ESD
There are three ways to launch ValVue ESD:
Right-click on the device name (in the list of connected devices) from the main ValVue
ESD screen.
Select the device on the ValVue ESD main screen and then click Select at the bottom
right of the screen.
Double-click the device name on the main screen.
1. Right-click the device name in the Connected Devices tab.
2. Select Historical View and the PST Historical View window appears (Figure 69).
3. Select the Device ID from the drop down list.
4. Select the Start and End Dates for the PST data to view.
Changing the Historical View Start and End Dates
The Historical View start and end date field is set up as mm/dd/yyyy. There are two methods
for changing the PST schedule date field. You can click on each parameter of the date field;
i.e. mm, or dd, or yyyy, and change each individual parameter or you access the calendar in
the drop down of the date field.
To change the start date schedule for the next PST:
1. Click in each parameter (mm-dd-yy-hh-mm) of the date field and highlight the text.
2. Either:
Type over the old value with the new value for each parameter.
OR
a.Click in the drop down, located at the right of PST schedule date field and access the
date calendar (Figure 69).
b.Using the arrow key on the calendar, change the month, if necessary and drag the
mouse and select the correct date within the month by clicking on it.
After you have selected the connected device ValVue ESD launches and the device appears in
the first ESDVue Monitor screen (Figure 71). ESDVue is a series of tabs, with each tab named
according to their function.
ValVue ESD is the main interface for connected devices. Once a connected
device is selected and launched the software tool for a device is called ESDVue.
ESDVue is set up as a typical Windows program, with tabs, menus, dialogs, windows and
toolbars. After logging into ValVue ESD the currently selected device appears in ESDVue’s Monitor screen. You can either perform operations on the Monitor screen or select another tab
to display another ESDVue screen.
Toolbar
The toolbar at the top of every ESDVue screen has two menu items: Tools and Help.
Modes of Operation
The SVI II ESD has three modes of operation:
“Normal Operation”
“Manual Operation ”
“Setup”
Normal Operation
In Normal mode, the SVI II ESD responds to the input signal and positions the ESD valve
accordingly.
In configurations where the safety function is triggered by current, when the input signal
current:
Falls below 5.6mA, the SVI II ESD de-energizes the ESD valve.
Rises above 14mA, the SVI II ESD energizes the ESD valve.
In configurations where the safety function is triggered by a discrete 0 - 24Vdc signal, when
the input signal voltage falls:
Falls below 3V, the SVI II ESD de-energizes the ESD valve.
Rises above 18V, the SVI II ESD energizes the ESD valve.
Manual Operation
In Manual mode, the valve does not respond to the input signal. Instead it remains stable in
one position, which is the position that the valve was in when manual mode was entered or a
new position selected using the HART or pushbutton interface. However, the Shutdown
function is activated if the signal is less than 5.6 mA (ASD) or 3 Vdc (A/DSD and DSD).
Setup
In the Setup mode, you can set calibration and configuration parameters. Additionally, you
can run response time tests, step response tests, and valve signatures.
However, if a process was running at the onset of the trip condition, the valve may also go to
where it was before the process started, or stay at the de-energized stop. This is not true for
Normal mode.
In failsafe and low power the valve must stay at the de-energized stop.
Change Mode
Use the Change Mode button on all ESDVue screens to change the operating SVI II ESD mode.
When selected, you can change the SVI II ESD mode to any of three operating modes:
NOTEIf the device is tripped, in Normal, Manual and Setup modes the
setpoint and the control mode are not affected by a device trip,
and as soon as the trip condition is removed (which includes Latch
if configured) the valve goes back to the state prior to the trip.
Normal - In this mode the SVI II ESD responds to the input signal and positions the
valve accordingly (indicator green).
Manual - in this mode the valve does not respond to the input signal. Instead it remains
stable in one position which is the position that the valve was in when manual mode
was entered or a new position selected by you (by changing the setpoint in the Monitor
screen).
Setup - In this mode you can set calibration and configuration parameters.
Additionally, you can run response time tests, step response tests, and PST controller
signatures (indicator yellow).
Whenever you leave the Normal mode, a warning appears (Figure 72).
1. Click OK to continue the mode change.
Figure 72Leaving Normal Mode Warning
Whenever you return to Normal mode, a warning appears (Figure 73).
From the Monitor screen (Figure 74), you can view the basic functions of the SVI II ESD
including tag and identification, input signal, setpoint, position, and status. You can also
change the SVI II ESD mode of operation and perform setup and command functions.
The Calibrate screen (Figure 77) displays the current PST controller’s calibration parameters
and provides the ability to adjust them in the Setup mode.
The PST controller Characteristics displayed on the Monitor screen consist of:
Signal (mA) - Indicates the input analog signal expressed in mA.
Position (%) - Indicates the actual valve position in % of valve opening. 0% is always
closed and 100% is open.
Pressure (pressure units) - The SVI II ESD continuously monitors the actuator pressure.
It is displayed according to the configured units (psi, bar, or kpa).
I/P Current - the current in mA generated by the I/P.
Pressure1 (pressure units) - Actuator pressure when Single Acting.
Pressure2 (pressure units) - Has no value when Single Acting.
Supply (pressure units) - Pressure generated by the air supply.
Pilot Pres (pressure units) - pressure generated by the I/P.
Pressure, Pressure1 and Pressure2
If your unit is single acting, Pressure and Pressure1 both have the same value, the actuator
pressure.
Position Indicator
The Position Indicator shows the valve position graphically. The indicator consists of three
parts:
The upper part contains an indicator showing the value of the input signal. In Normal
The center green bar shows the valve position where % = Valve Open. The numerical
The lower part contains an indicator (thumb) showing the valve setpoint. In operating
Signal
mode this is the position setpoint.
WARNINGIf operating in manual mode, this is the position that the valve
moves to if returning operation to normal mode.
valve position is shown in the center.
mode, this is the same as the signal. In manual mode it is the valve setpoint. You can
drag the thumb to change the valve setpoint. While dragging, the number in the center
bar shows the manual setpoint for use when you release the thumb.
94 | =GE Oil & Gas
Indicates the input analog signal expressed in % of the configured signal range.
Indicates the actual valve position in % of valve opening. 0% is always closed and 100% is
open. Because the travel of a valve may exceed its nominal travel, positions greater than
100% are possible.
In NORMAL mode, the setpoint is the target position based on the characterized input. In
MANUAL mode, it is the target position to which the SVI II ESD is controlling the valve. Change
the manual setpoint by dragging the lower thumb on the position indicator.
Prior to changing the position indicator ESDVue must be in Manual mode; click on Change
Mode and select Manual. There are three ways to change the position indicator:
Entering the setpoint value in the Setpoint dialog.
Dragging the position indicator.
Left-clicking on either side of the position indicator modifies the setpoint by 5%.
The SVI II ESD tracks operation and provides several health indicators. When there is a fault
code available in the SVI II ESD, this box contains (Figure 85) Additional Status Available. The
fault codes can be retrieved by:
1. Clicking the Check tab.
2. Selecting Read Status from the Send Command drop down list.
3. Clicking Send.
The status block also contains other status codes returned by HART. These include
Configuration Changed, Device malfunction, and Variable out of limits.
98 | =GE Oil & Gas
Figure 85Monitor Screen - Additional Status Available
The Tag Information on the Monitor screen displays the following items:
Tag
Descriptor
Message
Date
Assembly Number
This data appears at the same location on the Monitor, Configure and Calibrate screens but
can only be changed on the Configure screen (See “Changing Tag Information” on page 124).
PST/ESD Information
The Monitor screen contains status information on SVI II ESD's Partial Stroke Testing (PST) and
on the Emergency Shutdown Device (ESD) function. The PST/ ESD status fields are:
New PST - indicates when a new PST has been executed
New ESD Event - indicates whether there is a new ESD status event
PST in Progress - indicates whether a PST is in progress or not
ESD Tripped - indicates whether the Safety function has been tripped or not
ESD Type - indicates the type of SVI II ESD device: ASD, DSD, A/DSD - See “ESD Types”
on page 100.
Device Busy
Communication/No Communication - indicates if the SVI II ESD is in communication
with the Safety System
If the Status field is colored red, that status field is current.