These instructions do not purport to cover all details or variations in equipment nor
provide for every possible contin
ency to be met in connection with installation,
operation, or maintenance. Should further information be desired or should particular
problems arise which are not covered sufficiently for the purchaser’s purpose, the
matter should be referred to the General Electric Company.
To the extent required the products described herein meet applicable ANSI, IEEE,
and NEMA standards; but no such assurance is
ordinances because they vary
The 469 Motor Managemen t Relay is a micropro cessor ba sed rela y design ed for the prote ction and m anagement of medium and large hor sepower motors and driven equipment. Th e 469 is equipped with six output
relays for trips, alar ms, and start blocks. Motor protection, fault diagnosti cs, power metering, and RTU functions are integrated into one ec onomical drawout package. The single-line diagram below illus trates the 469
functionality using ANSI (American National Standards Institute) device numbers.
1
Figure 1–1: SINGLE LINE DIAGRAM
Typical applications include:
•Pumps•Fans•Compressors
•Mills•Shredders•Extruders
•Debarkers•Refiners•Cranes
•Conveyors•Chillers•Crushers
•Blowers
GE Power Management469 Motor Management Relay1-1
1.1 OVERVIEW1 INTRODUCTION
Some of the protection highlig hts are detailed here; a complete list is shown below. Four assignable digital
inputs may be configured for a number of different features including tachometer or generic trip and alarm with
1
a programmable name . The thermal model inc orporates unbalance bia sing, RTD feedback, and exponent ial
cooling. In addition to the 15 standard overload curves, there is a custom curve feature and a curve specifically
designed for the starting of high inertia loads, when the acceleration time exceeds the safe stall time. A second
overload curve is pr ovided for two-speed motors. Ground fau lts or earth leakage as low as 0.25 A may be
detected using the GE Power Management 50:0.025 Ground CT. CT inputs for phase differential protection are
also provided. The 12 RTD inputs provided may be individually field programmed for different RTD types. Voltage transformer inputs allow for numerous protec tion features based on vo ltage and power quantities. F our
4 to 20 mA analog inputs ma y be used for tripping and alarm ing on any transducer input such as vibration,
pressure, flow, etc.
51Overload
86Overload Lockout
66Starts/Hour & Time Between Starts
Fault diagnostics are provided through pretrip data, event record, trace memory, and statistics. Prior to issuing
a trip, the 469 takes a snapshot of the measured parame ters and stores them with the cause of the trip. This
pre-trip data may be viewed using the key before the trip i s reset, or by accessing the
LAST TRIP DATA
actual values. The 469 event recorder stores up to 40 time and date stamped events including
NEXT
A1 STATUS /
the pre-trip data. Each time a trip occurs, the 469 stores a trace of 8 cycles pre-trip and 8 cycles post-trip for all
measured AC quantities . Trip counters record the number of occurrenc es of each type of trip. Minimum an d
maximum values for RTDs and analog inputs are also recorded. These features enable the operator to pinpoint
a problem quickly and with certainty.
Power metering is buil t into the 469 as a s tandard feature. The ta ble below outline s the metered param eters
available either through the front panel or communications ports.
The 469 is equipped with 3 fully functional and independent communications ports. The front panel RS232 port
may be used for 469 setpoint program ming , loca l interro gation or control , and upgradi ng of 469 fir mware. Th e
Computer RS485 port m ay be connecte d to a PLC, DCS , or PC based u ser interfac e program. The A uxiliary
RS485 port may be used for redundancy or simultaneous interrogat ion and/or control from a second PLC,
DCS, or PC software.
There are also four 4 to 20 mA or 0 to 1 mA (as specified with order) transducer outputs that may be assi gne d
to any measured parameter. The range of these outputs is scalable.
Additional features are outlined in the table below.
Table 1–1: METERING AND ADDITIONAL FEATURES
METERINGADDITIONAL FEATURES
VoltageDrawout case (for ease of maintenance/testing)
Current and amps demandReduced voltage starting control for single transition
Real power, kW demand, kW power consumptionTrip coil supervision
Apparent power and kVA demandFlash memory for easy firmware upda tes
Reactive power, kvar demand, kvar consumption/
generation
Frequency
Power Factor
RTD
Speed in RPM with a key phasor input
User-programmable analog inputs
1
GE Power Management469 Motor Management Relay1-3
1.1 OVERVIEW1 INTRODUCTION
1.1.2 ORDER INFORMATION
1
All 469 features are standard; there are no options. The phase CT secondaries, control power, and analog output range must be specified at the time of order. The 469 differential CT inputs are field programmable for CTs
with 1 A or 5 A secondaries. There are two gr ound CT inputs, one for the GE Power Manageme nt 50:0.025
core balance CT and one for a ground CT with a 1 A or 5 A secondary, also field programmable. The VT inputs
will accommodate VTs in either a delta or wye configuration. The output relays are always non-failsafe with the
exception of the serv ice relay. The 469PC software is p rovided with each unit. A metal dem o case may be
ordered for demonstration or testing purposes.
469
469Basic unit
Additional access ories are listed in the following section.
•469PC
DEMO:
•
SR 19-1 PANEL:
•
SR 19-2 PANEL:
•
SCI MODULE:
•
Phase CT:
•
HGF3, HGF5, HGF8:
•
Software:
***
P1
P5
LO
HI
A1
A20
Provided free with each relay
Metal Carry Case in which 469 unit may be mounted
Single cutout 19" panel
Dual cutout 19" panel
RS232 to RS485 converter box designed for harsh industrial environments
50, 75, 100, 150, 200, 250, 300, 350, 400, 500, 600, 750, 1000
For sensitive ground detection on high resistance grounded systems.
1A phase CT secondaries
5A phase CT secondaries
DC: 25-60 V; AC: 20-48 V @ 48-62 Hz
DC: 90-300 V; AC: 70-265 V @ 48-62 Hz
0-1 mA analog outputs
4-20 mA analog outputs
Figure 1–3: 469 ORDER CODES
1.1.3 OTHER ACCESSORIES
•469
•469
•
1" Collar:
3" Collar:
Optional Mounting Kit:
For shallow switchgear, reduces the depth of the relay by 1 #3/8"
For shallow switchgear, reduces the depth of the relay by 3"
Additional mounting support 1819-0030
1-4469 Motor Management RelayGE Power Management
1 INTRODUCTION1.2 SPECIFICATIONS
1.2 SPECIFICATIONS1.2.1 469 SPECIFICATIONS
POWER SUPPLY
Options:LO / HI (must be specified with order)
Range:LO:DC: 20 to 60 V DC
AC: 20 to 48 V AC at 48 to 62 Hz
HI:DC: 90 to 300 V DC
AC: 70 to 265 V AC at 48 to 62 Hz
Power:45 VA (max), 25 VA typical
Proper operation time without supply voltage: 30 ms
PHASE CURRENT INPUTS
CT Primary:1 to 5000 A
CT Secondary: 1 A or 5 A (must be specified with order)
Burden:Less than 0.2 VA at rated load
Conversion Range: 0.05 to 20 × CT
Accuracy:at < 2 x CT: ± 0.5% of 2 × CT
at ≥ 2 x CT: ± 1% of 20 × CT
CT Withstand:1 second @ 80 × rated current
2 seconds @ 40 × rated current
continuous @ 3 × rated current
GROUND CURRENT INPUTS
CT Primary:1 to 5000 A
CT Secondary:1 A or 5 A (setpoint)
Burden:< 0.2 VA at rated load for 1 A or 5 A
< 0.25 VA for 50:0.025 @ 25 A
Conversion Range: 0.02 to 1 × CT primary Amps
Accuracy:± 0.5% of 1 × CT for 5 A
± 0.5% of 5 × CT for 1 A
± 0.125 A for 50:0.025
CT Withstand:1 second @ 80 × rated current
2 seconds @ 40 × rated current
continuous @ 3 × rated current
DIFFERENTIAL PHASE CURRENT INPUTS
CT Primary:1 to 5000A
CT Secondary: 1 A or 5 A (setpoint)
Burden:Less than 0.2 VA at rated load
Conversion Range: 0.02 to 1 × CT
Accuracy:±0.5% of 1 × CT for 5 A
±0.5% of 5 × CT for 1 A
CT Withstand:1 second @ 80 × rated current
2 seconds @ 40 × rated current
continuous @ 3 × rated current
VOLTAGE INPUTS
VT Ratio:1.00 to 150.00:1 in steps of 0.01
VT Secondary:273 V AC (full scale)
Conversion Range: 0.05 to 1.00 × full scale
Accuracy:±0.5% of full scale
Max. Continuous:280 V AC
Burden:> 500 kΩ
(isolated with analog inputs and outputs)
Range:–50 to +250°C
Accuracy:±2°C
Lead Resistance:25 Ω Max per lead for Pt and Ni type
3 Ω Max per lead for Cu type
No Sensor:>1000 Ω
Short/Low Alarm: < –50°C
TRIP COIL SUPERVISION
Applicable Voltage: 20 to 300 V DC / V AC
Trickle Current:2 to 5 mA
ANALOG CURRENT INPUTS
Current Inputs:0 to 1 mA, 0 to 20mA or 4 to 20 mA
(setpoint)
Input Impedance: 226 Ω ±10%
Conversion Range: 0 to 21 mA
Accuracy:±1% of full scale
Type:passive
Analog Input Supply: +24 V DC at 100 mA max.
Response Time: ≤ 100 ms
COMMUNICATIONS PORTS
RS232 Port:1, Front Panel, non-isolated
RS485 Ports:2, Isolated together @ 36 V
Baud Rates:RS485: 300, 1200, 2400, 4800, 9600,
19200
RS232: 9600
Parity:None, Odd, Even
Protocol:Modbus® RTU / half duplex
pk
1
GE Power Management469 Motor Management Relay1-5
1.2 SPECIFICATIONS1 INTRODUCTION
ANALOG CURRENT OUTPUT
Type:Active
1
Range:4 to 20 mA, 0 to 1 mA
(must be specified with order)
Accuracy:±1% of full scale
4 to 20 mA maximu m load: 1200 Ω
0 to 1 mA maximum load: 10 kΩ
Isolation:36 Vpk
(Isolated with RTDs and Analog Inputs)
4 Assignable Outputs:
phase A current
phase B current
phase C current
3 phase average current
ground current
phase AN (AB) voltage
phase BN (BC) voltage
phase CN (CA) voltage
3 phase average voltage
hottest stator RTD
hottest bearing RTD
hottest other RTD
RTD # 1 to 12
Power factor
3 phase Real power (kW)
3 phase Apparent power (kVA)
3 phase Reactive power (kvar)
Thermal Capacity Used
Relay Lockout Time
Current Demand
kvar Demand
kW Demand
kVA Demand
Motor Load
Torque
OVERLOAD / STALL PROTECTION /
THERMAL MODEL
Overload Curves:15 Standard Overload Curves, Custom
Curve, Voltage Dependent Custom
Curve for high inertia starting (all curves
time out against average phase current)
Curve Biasing:Phase Unbalance
Hot/Cold Curve Ratio
Stator RTD
Running Cool rate
Stopped Cool Rate
Line Voltage
Overload Pickup: 1.01 to 1.25 (for service factor)
Pickup Accuracy: as per Phase Current Inputs
Timing Accuracy: ±100 ms or ±2% of total time
Elements:Trip and Alarm
OUTPUT RELAYS
Configuration:6 Electromechanical Form C
Contact Material: silver alloy
Operate Time:10 ms
Max ratings for 100000 operations:
VOLTAGEMAKE/CARRYBREAK MAX.
DC
RESISTIVE
DC
INDUCTIVE
L/R=40ms
AC
RESISTIVE
AC
INDUCTIVE
P.F.=0.4
CONTINUOUS
30 V10 A30 A10A300 W
125 V10 A30 A0.5 A62.5 W
250 V10 A30 A0.3 A75 W
30 V10 A30 A5A150 W
125 V10 A30 A0.25 A31.3 W
250 V10 A30 A0.15 A37.5 W
120 V10 A30 A10 A2770 VA
250 V10 A30 A10 A2770 VA
120 V10 A30 A4 A480 VA
250 V10 A30 A3 A750 VA
0.2s
LOAD
TERMINALS
Low Voltage (A, B, C, D terminals): 12 AWG max.
High Voltage (E, F, G, H terminals): #8 ring lug, 10 AWG
wire standard
PHASE SHORT CIRCUIT
Pickup Level:4.0 to 20.0 × CT primary in steps of 0.1
of any one phase
Time Delay:0 to 1000 ms in steps of 10
Pickup Accuracy: as per Phase Current Inputs
Timing Accuracy: +50 ms
Elements:Trip
MECHANICAL JAM
Pickup Level:1.01 to 3.00 × FLA in steps of 0.01 of any
one phase, blocked on start
Time Delay:1 to 30 s in steps of 1
Pickup Accuracy: as per Phase Current Inputs
Timing Accuracy: ±0.5 s or ±0.5% of total time
Elements:Trip
UNDERCURRENT
Pickup Level:0.10 to 0.95 × CT primary in steps of
0.01 of any one phase
Time Delay:1 to 60 s in steps of 1
Block From Start: 0 to 15000 s in steps of 1
Pickup Accuracy: as per Phase Current Inputs
Timing Accuracy: ±0.5 s or ±0.5% of total time
Elements:Trip and Alarm
1-6469 Motor Management RelayGE Power Management
1 INTRODUCTION1.2 SPECIFICATIONS
CURRENT UNBALANCE
Unbalance:I2/I1 if I
I
2/I1
Range:0 to 100% UB in steps of 1
Pickup Level:4 to 40% UB in steps of 1
Time Delay:1 to 60 s in steps of 1
Pickup Accuracy: ±2%
Timing Accuracy: ±0.5 s or ± 0.5% of total time
Elements:Trip and Alarm
× I
avg
avg
> FLA
/FLA if I
avg
< FLA
GROUND INSTANTANEOUS
Pickup Level:0.1 to 1.0 × CT primary in steps of 0.01
Time Delay:0 to 1000 ms in steps of 10
Pickup Accuracy: as per Ground Current Input
Timing Accuracy: +50 ms
Elements:Trip and Alarm
PHASE DIFFERENTIAL INSTANTANEOUS
Pickup Level:0.05 to 1.0 × CT primar y i n st eps of 0.01
of any one phase
Time Delay:0 to 1000 ms in steps of 10
Pickup Accuracy: as per Phase Differential Current Inputs
Timing Accuracy: +50 ms
Elements:Trip
ACCELERATION TIMER
Pickup:transition of no phase current to > over-
load pickup
Dropout:when current falls below overload pickup
Time Delay:1.0 to 250.0 s in steps of 0.1
Timing Accuracy: ±100 ms or ± 0.5% of total time
Elements:Trip
JOGGING BLOCK
Starts/Hour:1 to 5 in steps of 1
Time Between Starts: 1 to 500 min.
Timing Accuracy: ±0.5 s or ± 0.5% of total time
Elements:Block
RESTART BLOCK
Time Delay:1 to 50000 s in steps of 1
Timing Accuracy: ±0.5 s or ± 0.5% of total time
Elements:Block
RTD
Pickup:1 to 250°C i n steps of 1
Pickup Hysteresis:2°C
Time Delay:3 s
Elements:Trip and Alarm
UNDERVOLTAGE
Pickup Level:
Motor Starting: 0.60 to 0.99 × Rated in steps of 0.01
Motor Running:0.60 to 0.99 × Rated in steps of 0.01
of any one phase
Time Delay:0.1 to 60.0 s in steps of 0.1
Pickup Accuracy: as per Voltage Inputs
Timing Accuracy: <100 ms or ±0.5% of total time
Elements:Trip and Alarm
OVERVOLTAGE
Pickup Level:1.01 to 1.10 × Rated in steps of 0.01 of
any one phase
Time Delay:0.1 to 60.0 s in steps of 0.1
Pickup Accuracy: as per Voltage Inputs
Timing Accuracy: ±100 ms or ±0.5% of total time
Elements:Trip and Alarm
VOLTAGE PHASE REVERSAL
Configuration:ABC or ACB phase rotation
Timing Accuracy: 500 to 700 ms
Elements:Trip
FREQUENCY
Required Voltage:> 30% of full scale in Phase A
Overfrequency Pickup: 25.01 to 70.00 in steps of 0.01
Underfrequency Pickup: 20.00 to 60.00 in steps of 0.01
Accuracy:±0.02 Hz
Time Delay:0.1 to 60.0 s in steps of 0.1
Timing Accuracy: <100 ms or ±0.5% of total time
Elements:Trip and Alarm
REDUCED VOLTAGE START
Transition Level: 25 to 300% FLA in steps of 1
Transition Time: 1 to 250 s in steps of 1
Transition Control: Current, Timer, Current and Timer
REMOTE SWITCH
Configurable:Assignable to Digital Inputs1 to 4
Timing Accuracy: 100 ms max.
Elements:Trip and Alarm
SPEED SWITCH
Configurable:Assignable to Digital Inputs1 to 4
Time Delay:1.0 to 250.0 s in steps of 0.1
Timing Accuracy: 100 ms max.
Elements:Trip
LOAD SHED
Configurable:Assignable to Digital Inputs1 to 4
Timing Accuracy: 100 ms max.
Elements:Trip
1
GE Power Management469 Motor Management Relay1-7
1.2 SPECIFICATIONS1 INTRODUCTION
PRESSURE SWITCH
Configurable:Assignable to Digital Inputs1 to 4
1
Time Delay:0.1 to 100.0 s in steps of 0.1
Block From S tart: 0 to 5000 s in steps of 1
Timing Accuracy: ±100 ms or ±0.5% of total time
Elements:Trip and Alarm
VIBRATION SWITCH
Configurable:Assignable to Digital Inputs1 to 4
Time Delay:0.1 to 100.0 s in steps of 0.1
Timing Accuracy: ±100 ms or ±0.5% of total time
Elements:Trip and Alarm
DIGITAL COUNTER
Configurable:Assignable to Digital Inputs1 to 4
Counting Frequency: ≤ 50 times a second
Range:0 to 1 000 000 000
Elements:Alarm
TACHOMETER
Configurable:Assignable to Digital Inputs1 to 4
RPM Measurement: 100 to 7200 RPM
Duty Cycle of Pulse: > 10%
Elements:Trip and Alarm
GENERAL PURPOSE SWITCH
Configurable:Assignable Digital Inputs1 to 4
Time Delay:0.1 to 5000.0 s in steps of 0.1
Block From S tart: 0 to 5000 s in steps of 1
Timing Accuracy: ±100 ms or ±0.5% of total time
Elements:Trip and Alarm
POWER FACTOR
Range:0.01 lead or lag to 1.00
Pickup Level:0.99 to 0.05 in steps of 0.01, Lead & Lag
Time Delay:0.2 to 30.0 s in steps of 0.1
Block From S tart: 0 to 5000 s in steps of 1
Pickup Accuracy: ±0. 02
Timing Accuracy: ±100 ms or ±0.5% of total time
Elements:Trip and Alarm
3 PHASE REAL POWER
Range:0 to ±99999 kW
Underpower Pickup: 1 to 25000 kW in steps of 1
Time Delay:1 to 30 s in steps of 1
Block From Start: 0 to 15000 s in steps of 1
Pickup Accuracy:
±1% of × 2 × CT × VT × VT
±1.5% of × 20 × CT × VT × VT
3
3
full scale
full scale
at I
avg
at I
< 2 × CT
> 2 × CT
avg
Timing Accuracy: ±0.5 s or ±0.5% of total time
Elements:Trip and Alarm
3 PHASE APPARENT POWER
Range:0 to 65535 kVA
Accuracy:
±1% of × 2 × CT × VT × VT
±1.5% of × 20 × CT × VT × VT
3
3
full scale
full scale
@ I
avg
@ I
< 2 × CT
> 2 × CT
avg
3 PHASE REACTIVE POWER
Range:0 to ±99999 kvar
Pickup Level:±1 to 25000 kvar in steps of 1
Time Delay:0.2 to 30.0 s in steps of 0.1
Block From Start: 0 to 5000 s in steps of 1
Pickup Accuracy:
±1% of × 2 × CT × VT × VT
±1.5% of × 20 × CT × VT × VT
3
3
full scale
full scale
@ I
avg
@ I
< 2 × CT
> 2 × CT
avg
Timing Accuracy: ±100ms or ± 0.5% of total time
Elements:Trip and Alarm
OVER TORQUE
Pickup Level:1.0 to 999999.9 Nm/ft·lb in steps of 0.1;
torque unit is selectable under torque
setup
Time Delay:0.2 to 30.0 s in steps of 0.1
Pickup Accuracy: ±2.0%
Time Accuracy: ±100 ms or 0.5% of total time
Elements:Alarm (INDUCTION MOTORS ONLY)
Ambient Operating Temperature: –40°C to +60°C
Ambient Storage Temperature: –40°C to +80°C
Humidity:Up to 90%, noncondensing.
Altitude:Up to 2000 m
Pollution Degree: 2
It is recommended that the 469 be powered up
at least once per year to prevent deterioration
NOTE
of electrolytic capacitors in the power supply.
PRODUCTION TESTS
Thermal Cycling: Operational test at ambient, reducing to
–40°C and then increasing to 60°C
Dielectric Strength: 2.0 kV for 1 minute from relays, CTs,
VTs, power supply to Safety Ground
DO NOT CONNECT FILTER GROUND TO
SAFETY GROUND DURING TEST!
WARNING
TYPE TESTS
Dielectric Strength: Per IEC 255-5 and ANSI/IEEE C37.90
2.0 kV for 1 minute from relays, CTs,
VTs, power supply to Safety Ground
DO NOT CONNECT FILTER GROUND TO
SAFETY GROUND DURING TEST
WARNING
Insulation Resistance: IEC255-5 500 V DC, from relays,
CTs, VTs, power supply to Safety
Ground
DO NOT CONNECT FILTER GROUND TO
SAFETY GROUND DURING TEST
WARNING
Transients:ANSI C37.90.1 Oscillatory (2.5kV/1MHz)
ANSI C37.90.1 Fast Rise (5kV/10ns)
Ontario Hydro A-28M-82
IEC255-4 Impulse/High Frequency Dis-
turbance, Class III Level
Impulse Test:IEC 255-5 0.5 Joule 5 kV
RFI:50 MHz/15 W Transmitter
EMI:C37.90.2 Electromagnetic Interference
Cycle
Vibration:Sinusoidal Vibration 8.0 g for 72 hrs.
PACKAGING
Shipping Box: 12” × 11” × 10” (W × H × D)
30.5cm × 27.9cm × 25.4cm
Shipping Weight: 17 lbs Max / 7.7 kg
1
BATTERY BACKUP
Used only when no control power to relay.
Life expectancy is ≥ 10 ye ars wi th n o co ntro l po wer to relay
CASE
Fully drawout (automatic CT shorts)
Seal provision
Dust tight door
Panel or 19" rack mount
IP Class:IP20-X
CERTIFICATION
ISO: Manufactured under an ISO9001 registered system.
UL: UL approved
CSA: CSA approved
CE: Conforms to EN 55011/CISPR 11, EN 50082-2
Conforms to IEC 947-1,1010-1
GE Power Management469 Motor Management Relay1-9
2 INSTALLATION2.1 MECHANICAL
2 INSTALLATION 2.1 MECHANICAL2.1.1 DESCRIPTION
The 469 is packaged in the standard GE Power Management SR series arrangement, which consists of a drawout unit and a co mpanion fixed case. The case provides mechanical protection to the unit and is used to
make permanent con nections to al l external e quipment. The only electric al components mounted in the case
are those required to c onnect the unit to the external wiring. Connections in th e case are fitted with mechanisms required to al low the sa fe r em ov al of th e rel ay uni t fr om an ene rg ized panel (for example, automatic CT
shorting). The unit is mechanically held in the case by pins on the locking handle that cannot be fully lowered to
the locked position unt il the elec trical con nections ar e complete ly mated. A ny 469 can b e install ed in any 46 9
case, except for c ustom man ufactured un its that a re clearl y identifie d as suc h on both case and unit, and are
equipped with an index pin keying mechanism to prevent incorrect pairings.
No special ventilatio n requirements need to be observed duri ng the installation of the unit. The 469 c an be
cleaned with a damp cloth.
2
Figure 2–1: DIMENSIONS
To prevent unauthorized re moval of th e drawou t unit, a wire lead seal ca n be ins talled in the s lot provi ded on
the handle. With this seal in place, the drawout unit cannot be removed. A passcode or setpoint access jumper
can be used to prevent entry of setpoints but allow monitoring of actual values. If access to the front panel controls must be restricted, a separate seal can be installed on the cover to prevent it from being opened.
Hazard may result if the product is not used for its intended purpose.
WARNING
Figure 2–2: SEAL ON DRAWOUT UNIT
GE Power Management469 Motor Management Relay2-1
2.1 MECHANICAL2 INSTALLATION
2.1.2 PRODUCT IDENTIFICATION
Each 469 unit and c ase are e qui ppe d wi th a p er man ent lab el . T his l abe l i s ins tal led on t he l eft s i de (when facing the front of the relay) of both unit and case. The case label details which units can be installed.
2
The case label details the following info r mation:
•MODEL NUMBER
•MANUFACTURE DATE
•SPECIAL NOTES
The unit label details the following information:
•MODEL NUMBER
•TYPE
•SERIAL NUMBER
•MANUFACTURE DATE
•PHASE CURRENT INPUTS
•SPECIAL NOTES
•OVERVOLTAGE CATEGORY
•INSULATION VOLTAGE
•POLLUTION DEGREE
•CONTROL POWER
•OUTPUT CONTACT RATING
Figure 2–3: CASE AND UNIT IDENTIFICATION LABELS
2-2469 Motor Management RelayGE Power Management
2 INSTALLATION2.1 MECHANICAL
2.1.3 INSTALLATION
The 469 case, alone or adj acen t to anothe r SR ser ies u nit, ca n be instal led in the p anel of a stand ard 19-i nch
rack (see the diagr am below for panel cutout d imensions). Provision must b e made when mounting for the
front door to swing open without interference to, or from, adjacent equipment. Normally the 469 unit is mounted
in its case when shipped fr om the fa ctory, and should be removed befo re mou nting the case in the supp ortin g
panel. Unit withdrawal is described in the next section.
Double Cutout Panel
Single Cutout Panel
2
Figure 2–4: SINGLE AND DOUBLE 469 CUTOUT PANELS
After the mounting hole in the panel has been prepared, slide the 469 case into the panel from the front. Applying firm pressure on the front to ensur e the front be zel fits snugl y against the fr ont of the panel , bend out the
pair of retaining tabs (to a horizontal po sition) from each side of the case as shown below. The case is no w
securely mounte d, read y for panel wiring. If additional sup port i s de si red, the SR optional mounting kit may b e
ordered.
Figure 2–5: BEND UP MOUNTING TABS
GE Power Management469 Motor Management Relay2-3
2.1 MECHANICAL2 INSTALLATION
2.1.4 UNIT WITHDRAWAL AND INSERTION
TURN OFF CONTROL POWER BEFORE DRAWING OUT OR RE-INSERTING THE RELAY TO
PREVENT MALOPERATION!
CAUTION
2
CAUTION
To remove the unit from the case:
1. Open the cover by grasping the center of the right side and then pulli ng the cover, which will rotate about
2. Release the locking latch, located below the locking handle, by pressing upward on the latch with the tip of
If an attempt is made to install a unit into a non-matching case, the mechanica l key will prevent full insertion of the unit. Do not apply strong force in the following step or damage may
result.
the hinges on the left.
a screwdriver.
Figure 2–6: PRESS LATCH TO DISENGAGE HANDLE
3. While holding the latch raised, grasp the locking handle in the center and pull firmly, rotating the handle up
from the bottom of the unit until movement ceases.
Figure 2–7: ROTATE HANDLE TO STOP POSITION
2-4469 Motor Management RelayGE Power Management
2 INSTALLATION2.1 MECHANICAL
4. Once the handle is released from the locking mechan ism, the unit ca n freely slide ou t of the case whe n
pulled by the handle. It may sometimes be necessary to adjust the handle position slightly to free the unit.
2
Figure 2–8: SLIDE UNIT OUT OF CASE
To insert the unit into the case:
1. Raise the locking handle to the highest position.
2. Hold the unit immediately in front of the case and align the rolling guide pins (near the hinges of the locking
handle) to the guide slots on either side of the case.
3. Slide the unit into the case until the guide pi ns on th e unit have engaged the guid e slots on either si de of
the case.
4. Grasp the locking handle fr om the ce nter and pre ss down firm ly, rotating the handle from the ra ised posi-
tion toward the bottom of the unit.
5. When the unit is fully inserted, the latch will be heard to click, locking the handle in the final position.
No special ventilation requirements need to be observed during the installation of the unit.
The unit does not require cleaning.
CAUTION
GE Power Management469 Motor Management Relay2-5
2
2.1 MECHANICAL2 INSTALLATION
2.1.5 TERMINAL LOCATIONS
Figure 2–9: TERMINAL LAYOUT
2-6469 Motor Management RelayGE Power Management
2 INSTALLATION2.1 MECHANICAL
T able 2–1: 469 TERMINAL LIST
A01RTD #1 HOTD21ASSIGNABLE SW. 03
A02RTD #1 COMPE NSATIOND22ASSIGNABLE SW. 04
A03RTD RETURND23SWITCH COMMON
A04RTD #2 COMPENSATIOND24SWITCH +24 V DC
A05RTD #2 HOTD25COMPUTER RS485 +
A06RTD #3 HOTD26COMPUTER RS485 –
A07RTD #3 COMPENSATIOND27COMPUTER RS485 COMMON
A08RTD RETURNE01R1 TRIP NC
A09RTD #4 COMPE NSATIONE02R1 TRIP NO
A10RTD #4 HOTE03R2 AUXILIARY COMMON
A11RTD #5 HOTE04R3 AUXILIARY NC
A12RTD #5 COMPE NSATIONE05R3 AUXILIARY NO
A13RTD RETURNE06R4 ALARM COMMON
A14RTD #6 COMPENSATIONE07R5 BLOCK START NC
A15RTD #6 HOTE08R5 BLOCK START NO
A16A NALO G OUT COMMON –E09R6 SERVICE COMMON
A17ANALOG OUT 1 +E10not used
A18ANALOG OUT 2 +E11COIL SUPERVISION +
A19ANALOG OUT 3 +E12469 DRAWOUT INDICATOR
A20ANALOG OUT 4 +F01R1 TRIP COMMON
A21ANALOG SHIELDF02R2 AUXILIARY NO
A22ANALOG INPUT 24 V DC POWER SUPPLY +F03R2 AUXILIARY NC
A23ANALOG INPUT 1 +F04R3 AUXILIARY COMMON
A24ANALOG INPUT 2 +F05R4 ALARM NO
A25ANALOG INPUT 3 +F06R4 ALARM NC
A26ANALOG INPUT 4 +F07R5 BLOCK START COMMON
A27A NALOG INPUT COMMON –F08R6 SERVICE NO
B01RTD SHIELDF09R6 SERVICE NC
B02AUXILIARY RS485 +F10not used
B03AUXILIARY RS485 –F11COIL SUPERVISION –
B04A UXILIARY RS485 COMMONF12469 DRAWOUT INDICATOR
C01ACCESS +G01PHASE VT NEUTRAL
C02ACCESS –G02PHASE A VT
C03469 UNDER TEST +G03DIFFERENTIAL A CT
C04469 UNDER TEST –G04DIFFERENTIAL B CT
D01RTD #7 HOTG05DIFFERENTIAL C CT
D02RTD #7 COMPENSATIONG06PHASE A CT
D03RTD RETURNG0 7PHASE B CT
D04RTD #8 COMPENSATIONG08PHASE C CT
D05RTD #8 HOTG091A/5A GROUND CT
D06RTD #9 HOTG1050:0.025 GROUND CT
D07RTD #9 COMPENSATIONG11FILTER GROUND
D08RTD RETURNG1 2SAFETY GROUND
D09RTD #10 COMPENSATIONH01PHASE B VT
D10RTD #10 HOTH02PHASE C VT
D11RTD #11 HOTH03DIFFEREN TIAL A CT
D12RTD #11 COMPENSATIONH04DIFFERENTIAL B CT
D13RTD RETURNH05DIFFERENTIAL C CT
D14RTD #12 COMPENSATIONH06PHASE A CT
D15RTD #12 HOTH07PHASE B CT
D16STARTER STATUSH08PHASE C CT
D17EMERGENCY RESTARTH091A/5A GROUND CT
D18REM OT E RESETH1050:0.025 GROUND CT
D19ASSIGNABLE SW. 01H11CONTROL POWER –
D20ASSIGNABLE SW. 02H12CONTROL POWER +
•
•
•
•
•
•
•
•
•
•
•
2
GE Power Management469 Motor Management Relay2-7
2.2 ELECTRICAL2 INSTALLATION
2.2 ELECTRICAL2.2.1 TYPICAL WIRING DIAGRAM
2
Figure 2–10: TYPICAL WIRING DIAGRAM
2-8469 Motor Management RelayGE Power Management
Loading...
+ 281 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.