GE Masoneilan 469 Series, Masoneilan 496-857, Masoneilan 496-858, Masoneilan 496- Series 58, Masoneilan 496- Series 57 Instruction Manual

Page 1
Masoneilan*
496 Series
Position Transmitter and Limit Switch
ATEX Instruction Manual (Rev.B)
BHGE Data Classification: Public
Page 2
THESE INSTRUCTIONS PROVIDE THE CUSTOMER/OPERATOR WITH IMPORTANT PROJECT-SPECIFIC REFERENCE INFORMATION IN ADDITION TO THE CUSTOMER/OPERATOR’S NORMAL OPERATION AND MAINTENANCE PROCEDURES. SINCE OPERATION AND MAINTENANCE PHILOSOPHIES VARY, BHGE (BAKER HUGHES, A GE COMPANY AND ITS SUBSIDIARIES AND AFFILIATES) DOES NOT ATTEMPT TO DICTATE SPECIFIC PROCEDURES, BUT TO PROVIDE BASIC LIMITATIONS AND REQUIREMENTS CREATED BY THE TYPE OF EQUIPMENT PROVIDED.
THESE INSTRUCTIONS ASSUME THAT OPERATORS ALREADY HAVE A GENERAL UNDERSTANDING OF THE REQUIREMENTS FOR SAFE OPERATION OF MECHANICAL AND ELECTRICAL EQUIPMENT IN POTENTIALLY HAZARDOUS ENVIRONMENTS. THEREFORE, THESE INSTRUCTIONS SHOULD BE INTERPRETED AND APPLIED IN CONJUNCTION WITH THE SAFETY RULES AND REGULATIONS APPLICABLE AT THE SITE AND THE PARTICULAR REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE.
THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE MET IN CONNECTION WITH INSTALLATION, OPERATION OR MAINTENANCE. SHOULD FURTHER INFORMATION BE DESIRED OR SHOULD PARTICULAR PROBLEMS ARISE WHICH ARE NOT COVERED SUFFICIENTLY FOR THE CUSTOMER/OPERATOR'S PURPOSES THE MATTER SHOULD BE REFERRED TO BHGE.
THE RIGHTS, OBLIGATIONS AND LIABILITIES OF BHGE AND THE CUSTOMER/OPERATOR ARE STRICTLY LIMITED TO THOSE EXPRESSLY PROVIDED IN THE CONTRACT RELATING TO THE SUPPLY OF THE EQUIPMENT. NO ADDITIONAL REPRESENTATIONS OR WARRANTIES BY BHGE REGARDING THE EQUIPMENT OR ITS USE ARE GIVEN OR IMPLIED BY THE ISSUE OF THESE INSTRUCTIONS.
THESE INSTRUCTIONS ARE FURNISHED TO THE CUSTOMER/OPERATOR SOLELY TO ASSIST IN THE INSTALLATION, TESTING, OPERATION, AND/OR MAINTENANCE OF THE EQUIPMENT DESCRIBED. THIS DOCUMENT SHALL NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE WRITTEN APPROVAL OF BHGE.
2 | BHGE © 2018 Baker Hughes, a GE company. All rights reserved.
Page 3
Conversion Table
All the USCS values are converted to
metric values using the following conversion factors:
Metric values using
the following
conversion factors:
Conversion Factor
Metric Unit
in. 25.4 mm lb.
0.4535924
kg in
2
6.4516
cm
2
ft3/min
0.02831685
m3/min
gal/min
3.785412
L/min
lb/hr
0.4535924
kg/hr
psig
0.06894757
barg
ft lb
1.3558181
Nm °F
5/9 (°F-32)
°C
Note: Multiply USCS value with conversion factor to get metric value.
NOTICE!
For valve configurations not listed in this manual, please contact your local MARC or BHGE sales office for assistance.
© 2018 Baker Hughes, a GE company. All rights reserved. Masoneilan 496 Series Position Transmitter ATEX Instruction Manual | 3
Page 4
Contents
1. Instrument Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2. Numbering System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3. Technical Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
4. ATEX Intrinsic Safety Marking and Electrical Safety Parameters . . . . . . . . . . . . . . . . . . . . .8
5. ATEX Flameproof Marking and Electrical Safety Parameters. . . . . . . . . . . . . . . . . . . . . . . 10
6. Position Transmitter 496-8../. Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7. Electrical Connection, Installation and Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8. Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
9. Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
10. Special Conditions of Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
11. Special Conditions of Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Annex I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Annex II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Annex III. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4 | BHGE © 2018 Baker Hughes, a GE company. All rights reserved.
Page 5
Warning
BEFORE installing, using or carrying out any maintenance tasks associated with this instrument, READ THE INSTRUCTIONS CAREFULLY.
These instruments comply with the essential safety requirements of the European Directive ATEX 94/9/CE. It is certified to be used in Gas or Dust explosive atmospheres, groups IIA, IIB, IIC and IIIC:
Category II 1GD – zones 0, 1, 2, 20, 21 and 22 for the protection mode ia
Category II 2GD – zones 1, 2, 21 and 22 for the protection mode d and tb
They also comply with the essential safety requirements of the European Directive EMC 2004/108/EC as amended, for use within an industrial environment.
Products certified as explosion proof equipment
MUST BE:
a) Installed, put into service, used and maintained
in compliance with European and/or national and local regulations and in accordance with the recommendations contained in the relevant standards concerning potentially explosive atmospheres.
b) Used only in situations those comply with the
certification conditions shown in this document and after verification of their compatibility with the zone of intended use and the permitted maximum ambient temperature.
c) Installed, put into service and maintained by qualified
and competent professionals who have undergone suitable training for instrumentation used in areas with potentially explosive atmosphere. Such trainings are not supported by BHGE.
It is the end users responsibility to:
Verify material compatibility with the application
Ensure proper use of fall protection when working
at heights, per Safe Site Work Practices
Ensure use of proper Personal Protective Equipment
Take the appropriate actions to ensure that site personnel who are performing installation, commissioning and maintenance have been trained in proper site procedures for working with and around equipment, per Safe Site Work Practices
BHGE reserves the right to discontinue manufacture of any product or change product materials, design, or specifications without notice.
Under certain operating conditions, the use of damaged instruments could cause a degradation of the performances of the system which may lead to personal injury or death.
Use only BHGEs Masoneilan replacement parts to ensure that the products comply with the essential safety requirements of the European Directives mentioned above.
© 2018 Baker Hughes, a GE company. All rights reserved. 496 Series Masoneilan Position Transmitter ATEX Instruction Manual | 5
Page 6
Protection
55. Weatherproof
57. Explosionproof and dust and water tight
58. Intrinsically safe and dust and water tight
Additional Function
for a Transmitter Only
1. One mechanical switch single pole double throw
2. Two mechanical switches single pole double throw
4. One proximity switch
5. Two proximity switches
6. One mechanical switch double pole double throw
7. Two mechanical switches double pole double throw
1. Instrument Operation
1.1 The 496-.58 and 496-.57 position
limit switch
Allow switching 1 or 2 electrical circuits. This function is provided by 1 or 2 micro- switch(es) or 1 or 2 proximity switch(es).
1.2 The 496-857 and 496-857/. and
496-858 or 496-858/. position transmitter
The 496 Series instrument is a non-contact opto­electronic positioner transmitter which provides a 4-20mA analog output signal proportional to the valve position. This device can be mounted both on rotary and reciprocating valves through a system of gears and (for reciprocating valves only) a linkage.
The displacement of the stem or shaft is transmitted to the opto-electronic sensor by 2 gears.
The opto-electronic sensor has the same function than a standard potentiometer and its output voltage is proportional to the rotation of its axis.
An electronic circuit amplifies this voltage to a 4-20 mA signal proportional to the angle of rotation.
This equipment has many advantages:
non electrical noise typical of potentiometer with cursor
frictionless
unlimited life
non sensitive to vibration and electrical noise
very low operating torque: 0.02 N.m
Optionally 496-857/. or 496-858/. apparatus can also be used as a limit switch to switch 1 or several electrical circuits. 1 or 2 micro- switch(es) or 1 or 2 proximity switch(es) are provided for this supplementary function.
2. Numbering System
496 - _ _ _ / _
6 | BHGE © 2018 Baker Hughes, a GE company. All rights reserved.
Type
1. One mechanical switch single pole double throw
2. Two mechanical switches single pole double throw
4. One proximity switch
5. Two proximity switches
6. One mechanical switch double pole double throw
7. Two mechanical switches double pole double throw
8. Optoelectronic position transmitter
Page 7
3. Technical Specification
Internal components for limit switch and position transmitter are mounted inside an IP66/IP67 enclosure.
Performances of position transmitter type 496-857 or 496-857/. and 496-858 or 496-858/.
Output signal: 4-20 mA (2 wires)
Acceptable span on the command axle: from 25° to 90° for rotary or reciprocating valves
Rotation: clockwise or counter clockwise
Linearity: ≤ ± 0.5% for a rotary angle of 25° to 90° (typically ± 0.3% for a rotary angle ≥ 60°)
Hysteresis: ≤ 0.1%
Dead band: 0.1%
Repeatability: ≤ 0.1%
Total drift in temperature: 0.02 %/°C or 200 ppm/°C (zero and span range)
Operating temperature range: -40°C to +80°C
Electrical characteristics and temperature range of the position transmitter with micro-switch(es) or proximity switch(es) are given in the following sections.
© 2018 Baker Hughes, a GE company. All rights reserved. 496 Series Masoneilan Position Transmitter ATEX Instruction Manual | 7
Page 8
4. ATEX Intrinsic Safety Marking and Electrical
Safety Parameters
4.1 Marking
The marking is on the serial plate stamped on the 496 cover (rep 14).
Name and address of the manufacturer: Dresser Produits Industriels S.A.S. 14110 CONDE SUR NOIREAU - FRANCE
Type designation:
496-858 for transmitter,
496-858/for transmitter with additional
function(s)
496-58 for position switches
the ” can take the values 1, 2, 4, 5.
Basic and complementary marking:
Transmitter alone or with mechanical switch(es)
(additional function):
II 1 GD
Ex ia IIC T.* Ga Tamb = -..°C à +..°C *
Ex ia IIIC T..°C* Da
– Transmitter alone or with proximity switch(es)
(additional function):
II 1G* or II 2G*
Ex ia IIC T.* Ga Tamb = -..°C à +..°C *
Position mechanical switch(es):
II 1 GD
Ex ia IIC T.* Ga Tamb = -..°C à +..°C *
Ex ia IIIC T..°C* Da
Position proximity switch(es) (additional function):
II 1G*, II 2G*
Ex ia IIC T.* Ga Tamb = -..°C à +..°C *
* Ambient temperatures ranges and surface temperatures for the temperature classifications T6, T5 and T4 are given in ANNEX I with:
– Tables 1, 2 and 3 for the transmitter alone, the
mechanical switch(es) alone and the proximity switch(es) alone.
– Tables 4 and 5 for the transmitter with mechanical
switch(es) and for the transmitter with proximity switch(es).
Serial number
Year of manufacturing
Number of notified body ••••
EC-Type examination certificate number
Warning:
AVERTISSEMENT : DANGER POTENTIEL DE CHARGES ELECTROSTATIQUES – VOIR INSTRUCTIONS
WARNING: POTENTIAL DANGER OF ELECTROSTATIC CHARGES. SEE INSTRUCTIONS
4.2 Electrical safety parameters
4.2.1 Type 496-.58
4.2.1.1 Option with 1 or 2 Micro-Switch(es)
Type identification is: 496-158 and 496-258.
Mechanical switch(es): type BZ-2R72-A2,
manufacturer: HONEYWELL
They are supplied by a certified power source for explosible atmospheres group IIC with the maximal characteristics:
– Constant power supply: Ui= 30V, Ii = 0.5A, Ci = 0F
and Li = 0H
– Alternative power supply: Ui= 90V, Ii = 1.4A, Ci = 0F
and Li = 0H
The wiring connection is done directly on mechanical switch(es).
4.2.1.2 Option with 1 or 2 Proximity Switch(es)
Type identification is: 496-458 and 496-558.
These detectors from PEPPERL & FUCHS are
defined as:
II 1G Ex ia IIC T6 Ga
II 2G Ex ia IIC T6 Gb
EC type examination certificate:
PTB 00 ATEX 2048 X (II1G, II2G)
PTB 00 ATEX 2049 X (II1G, II2G)
8 | BHGE © 2018 Baker Hughes, a GE company. All rights reserved.
Page 9
4. ATEX Intrinsic Safety Marking and Electrical
Variation
Ui Ii Ci
(V) (A) (nF)
Li Pi
(μH) (W)
With Micro­switch
DC Source
30 0.5 0 0 -
AC Source
Peak Value
90
1.4
0
0
-
With Proximity Switch
16 0.052
120 200
0.169
Safety Parameters (Contd)
They are supplied by a certified power source * for explosible atmospheres with the maximal characteristics:
Ui = 16V ; Ii = 0.052A ; Pi = 0.169W.
* The power source (Control circuit) must be one manufactured by Pepperl & Fuchs below:
WE 77/EX 1 or WE 77/EX 2
The wiring connection is done on one or two terminal connector type: MK 3 ; 2.5mm2 ; 380 volts ; manufacturer: WEIDMULLER or equivalent product.
4.2.1.3 Maximum Input Characteristics
4.2.2.2 Type 496-858/. :
The additional functions of position transmitters are identical to type 496-58
Maximum input characteristics at terminal block of additional function:
Variation
Ui Ii Ci
(V) (A) (nF)
Li Pi
(μH) (W)
With Micro­switch
DC Source
30 0.5 0 0
AC Source
Peak Value
90
1.4
0
0
-
With Proximity Switch
16 0.052
120 200
0.169
4.2.2 Types 496-858 and 496-858/. :
4.2.2.1 Type 496-8:
The position transmitter is connected to a linear tension source of a certified type for use in group IIC hazardous locations and its output circuit must be intrinsically safe approved per EN 60079-11.
Maximum input characteristics at terminal block:
Ui (V) Ii (A)
Ci (nF)
Li (μH)
Pi (W)
28
0.11
36 0 0.77
© 2018 Baker Hughes, a GE company. All rights reserved. 496 Series Masoneilan Position Transmitter ATEX Instruction Manual | 9
Page 10
Type
Min Max
Voltage Voltage
496-157 or 496-257 or 496-657 or
496-757
-
220V
(direct current) or
250V (alternative
current)
496-457 or
496-557
Pepperl
and Fuchs
-
16V
(direct current)
496-457 or
496-557
Télémécanique
-
58V
(direct current)
496-857/.
9.0V
(direct current)
36V
(direct current)
5. ATEX Flameproof Marking and Electrical Safety
Parameters
5.1 Marking
The marking is on the serial plate stamped on the 496 cover (rep 14).
Name and address of the manufacturer Dresser Produits Industriels S.A.S. 14110 CONDE SUR NOIREAU – FRANCE
Type designation:
496-857 for a position transmitter
496-857/for a position transmitter with
additional function(s), for a transmitter
496-57 for a position limit switch
The • can be replaced by 1, 2, 4, 5, 6 and 7.
the specific marking:
II 2 GD
the complementary marking:
Ex d IIC T6 Gb Ta –55°C, +75°C (*)
Ex tb IIIC T85°C Db IP66/IP67
– Ex d IIC T5 Gb Ta –55°C, +85°C (*)
Ex tb IIIC T100°C Db IP66/IP67
Serial number
Year of manufacturing
Number of notified body ••••
EC-Type examination certificate number
Warning:
AVERTISSEMENT : NE PAS OUVRIR SOUS TENSION
WARNING : DO NOT OPEN WHEN ENERGIZED
T cable : (**)
(*) temperature range can be reduced without
exceeding above values depending upon the type of component mounted inside the enclosure.
(**) Mandatory mention when the ambient
temperature is higher than 70°C.
T ambient T cable
70°C
75°C
75°C
80°C
80°C
85°C
85°C
90°C
5.2 Electrical safety parameter
Maximum dispersed power = 5W
Voltage supply allowable:
Warning:
AVERTISSEMENT : DANGER POTENTIEL DE CHARGES ELECTROSTATIQUES – VOIR INSTRUCTIONS
WARNING: POTENTIAL DANGER OF ELECTROSTATIC CHARGES. SEE INSTRUCTIONS
10 | BHGE © 2018 Baker Hughes, a GE company. All rights reserved.
Page 11
6. Position Transmitter 496-8../. Electrical data
Power supply:
Voltage Supply U (V)
Mini
Maxi
Flameproof
9.0V
36V
Intrinsic Safety
9.0V
28V
Lightning protection (in standard) : 1500W 10/1000µs
Output current 4-20mA (two wires)
Zc
Zero range adjustment : ±0.5mA
U
Span range adjustment : ±2.5mA
Protected against polarity inversion
Supply Voltage (V) – 9.0 (V
)
Maximum load
Zc
(Ω)
=
This means for 20mA:
Imaxi (A
)
Zc = 950 Ohm max with for an intrinsically safe loop and Zc = 1350 Ohm for Flameproof.
© 2018 Baker Hughes, a GE company. All rights reserved. 496 Series Masoneilan Position Transmitter ATEX Instruction Manual | 11
Page 12
Plug
Manufacturer
Certification
ATEX
Certificate
IECEx
Certificate
REDAPT
Ex d IIC
Ex tb IIIC
SIRA 99
ATEX
1115U
IECEx SIR
05.0042U
Others plugs if apparatus certified ATEX or IECEx
(type Cooper CAPRI CODEC).
Adaptor or Reducer
Manufacturer
Certification
ATEX
Certificate
IECEx
Certificate
REDAPT
Ex d IIC
Ex tb IIIC
SIRA 99
ATEX
1115U
IECEx SIR
05.0042U
Other adaptors or reducers if apparatus certified
ATEX or IECEx (Cooper CAPRI CODEC).
7. Electrical Connection, Installation and Start-up
Comply with current national and local regulations for electrical installation work.
Must be installed and put into service in conformance with EN 60079-14 and/or national and local
regulations applicable for explosible atmospheres.
Before carrying out any work on the device, power off the instrument or make sure that the local conditions in the potentially explosive atmosphere permit – the safe opening of the cover.
Connect the wires to the instrument terminals, taking care of complying with polarities and maximum voltage allowed.
Before power up or after doing any work on the device always check the cover (12) is fully screwed, O-ring (10) is free of any damage and security screw (9) is well locked.
Note: Before installation, check that the device is undamaged. In the event of damage, inform the manufacturer
whose address is shown on the serial plate.
7.1 Conduit entry in flameproof application
The connections can be done with different variations taking into account approved manufacturer and requested approvals:
A cable entry of a certified type Ex d IIC / Ex tb IIIC
can be mounted directly on the single ¾" NPT (ANSI/ ASME B1.20.1) housing conduit connection.
For an adaptor or reducer need, these component are allowed:
For multiple cable entries (3 maximum), the adaptor Y237 “Masoneilancan be used for ATEX application only.
– If one Y237 input is not used, the conduit will be
closed by the followed plugs:
– If two Y237 inputs are not used, the Y237 must be
suppressed.
The cable entry with or without its adaptor/reducer and the Y237 with its cable entry must be installed in conformance with Annex III.
12 | BHGE © 2018 Baker Hughes, a GE company. All rights reserved.
Page 13
7. Electrical Connection, Installation and Start-up (Contd)
7.2 Electrical connection for type 496-.57 or 496-.58
The electrical cables are connected either directly
on to the micro switch(es) or to the proximity switch terminal block.
Connect the device to the earth using the earth
connections provided inside and outside the housing of the device.
Basic rule for wiring:
– Must be used in addition to local regulation for
electrical installation
Connector slot approval:
Insulation must be free of any damage along the
wires inside the housing
– Tightening must be sufficient to bring constant
contact in time without being excessive to cut or damage connection.
7.3 Electrical connection for type
496-857 or 496-857/. and 496-858 or 496-858/.
Connect the electrical cables to the position transmitter terminal block located on the printed circuit board. Respect the polarities + and – and the maximum voltage allowed.
When a position transmitter is provided with an additional function, the electrical cables are connected either directly on to the micro switch(es) or to the proximity switch terminal block.
Connect the device to the earth using the earth connections provided inside the housing and on the outside of the device.
Basic rule for wiring:
– Must be used in addition to local regulation for
electrical installation
Connector slot approval:
Insulation must be free of any damage along the
wires inside the housing
– Tightening must be sufficient to bring constant
contact in time without being excessive to cut or damage connection.
© 2018 Baker Hughes, a GE company. All rights reserved. 496 Series Masoneilan Position Transmitter ATEX Instruction Manual | 13
Page 14
7. Electrical Connection, Installation and Start-up (Contd)
7.4 Installation and start-up
7.4.1 Installation
Flameproof instrument may be installed in gas and dust explosive atmosphere of groups IIA, IIB, IIC and IIIC for the zones 1, 2, 21 and 22 with d and tb protection mode.
Intrinsically safe instrument may be installed in gas and dust explosive atmosphere of groups IIA, IIB, IIC and IIIC for zones 0, 1, 2, 20, 21 and 22 with “ia protection mode.
Nota: It is under the user responsibility to check the installation against Intrinsic safety rules taking into account entity parameters of all devices in the loop in addition of temporary one like measurement devices.
7.4.2 Start-up
– Before power up or after doing any work on the device always check the cover (12) is fully screwed,
O-ring (10) is free of any damage and security screw (9) is well locked.
– Check that the cable gland is certified for the intended use and that the electrical data are suitable for
the operating zone.
Before start up, proceed, if required, with instrument calibration as per §8 and/or ensure that all the safety instructions in the preceding paragraphs have been strictly followed.
14 | BHGE © 2018 Baker Hughes, a GE company. All rights reserved.
Page 15
8. Calibration
Before power up the device to proceed with calibration carefully read the following safety warnings.
– Comply with current national and local
regulations for electrical installation work.
– Must be installed and put into service in
conformance with EN 60079-14 and / or national and local regulations applicable for explosible atmospheres.
– Before carrying out any work on the device,
power off the instrument or make sure that the local conditions in the potentially explosive atmosphere permit- the safe opening of the cover.
– Connect the wires to the instruments
terminals, taking care of complying with polarities and maximum voltage allowed.
– Before power up or after doing any work on
the device always check the cover (12) is fully screwed, O-ring (10) is free of any damage and security screw (9) is well locked.
8.1 Calibration of rotary limit switch 496-.57 and 496-.58 equipped with micro switch(es)
The concave portion of the lever (5) must be strictly
concentric to the cam (13) when the micro-switch is actuated.
This is an important caution to make sure the lever is properly depressed when not actuated.
If not, loosen the screws (3 & 17) and slightly move the lever upwards or downwards. Tighten the screws.
Slightly loosen the cam locking screw (1) using a 3/32socket hex head wrench.
Move the plug stem to the position required to actuate the switch.
It is important to note that the cam operating the right hand micro-switch must actuate the lever (5) at the end of the counterclockwise rotation. (See detail figure below).
This makes sure the screw (2) has free the lever (5) when the valve is throttling. The remaining concave portion only ensures micro-switch actuation in case of over travel. Conversely, the cam operating the left hand micro-switch must actuate the lever (5) at the end of the clockwise rotation. (See front view below).
To meet the above requirement when only one micro-switch is provided (type 496-158) it may be necessary to change the location of the micro-switch.
Rotate the cam (13) until the micro-switch is actuated. Lock the cam (13) tightening the screw (1).
Fine tune adjustment with screw (2). Use a 1/16 socket hex head wrench. The screw (2) must come out the cam enough to properly depress the lever (5).
Strictly follow safety instructions under §7.4 before putting into service.
© 2018 Baker Hughes, a GE company. All rights reserved. 496 Series Masoneilan Position Transmitter ATEX Instruction Manual | 15
Page 16
8. Calibration (Contd)
1 6 9 10 11 12 8
13
A
8
2
13
3
4
3
17
7
15
5
14
18
5
16
B
Parts List
Rep.
Designation
Rep.
Designation
Rep. Designation
1
Adjusting screw
8
Snap ring
2
Adjusting screw
9
Safety screw
16
Insulating
3
Screw (1 micro switch)
10 (1)
Oring
17
Screw (second micro switch)
4
Micro switch
11
Axis 18
Washer
5
Lever
12
Cover
19 (2)
Spacer (Not shown)
6
Housing
13
Cam A
Contact point for the left micro switch
7 (1)
O ring
14
Serial plate
B
Contact point for the right micro switch
(1) Recommended spare parts
(2) Only for 496-2 model
16 | BHGE © 2018 Baker Hughes, a GE company. All rights reserved.
Page 17
8. Calibration (Contd)
Rep.
Designation
Rep.
Designation
33
Arm
34
Proximity switch
8.2 Calibration of rotary limit switch 496-.57 and 496-.58 equipped with proximity switch(es)
8.2.1 Type 496-4
Actuate the valve to the desired triggering position
and check the sense of rotation when the arm leaves the proximity sensor.
The figure below shows the location of the proximity
sensor and of the arm when triggering as a function of the sense of rotation.
Slowly move the arm towards the proximity sensor
until it triggers. Triggering occurs when the arm overlaps approximately 1/3 of the proximity switch.
Strictly follow safety instructions under §7.4 before
putting into service.
34 34
33
8.2.2 Type 496-5
During adjustment make sure that the proximity switch with the red spot is triggered by the arm with the red spot.
Adjustment of the first proximity switch
The first switch is adjusted at the beginning of
the stroke.
– Check what will be the sense of rotation when the
valve is actuated. Figure (b, c) below shows the proximity sensor and the arm assigned to the first triggering point for a given the sense of rotation.
– Slowly move the arm towards the proximity switch
until it triggers.
Adjustment of the second proximity switch
The second switch is adjusted at the end of the
actuator stroke.
– Immobilize the first arm previously adjusted and
slowly move the second arm towards the second proximity sensor until it triggers.
– Make sure the first proximity switch is still
correctly adjusted.
Strictly follow safety instructions under §7.4 before putting into service.
a
A
B
b
B
c
Rep.
Designation
Rep.
Designation
A
Red spot
B
First triggering point
© 2018 Baker Hughes, a GE company. All rights reserved. 496 Series Masoneilan Position Transmitter ATEX Instruction Manual | 17
Page 18
8. Calibration (Contd)
8.2.3 Air-gap adjustment
Air-gap between the proximity switch and the arm is factory adjusted. If new adjustment is required proceed as follows:
Loosen the proximity sensor nut (37A), located on the front of the bracket (36).
Unscrew a few turns the locknut (37B) located on the back of the bracket.
Position the arm above the proximity sensor and push the shaft end (11) towards the outside of the housing so as to eliminate the longitudinal play.
Hold in position the proximity sensor and screw the nut (37A). Adjust air gap to 0,3 mm using a shim
Tighten the lock nut (37B).
6 9 10 11 12 8 30 37A
8
31
32
33
3
36
7
15
25
14
3
24
34 37B 19
Parts List
Rep.
Designation
Rep.
Designation
Rep.
Designation
3
Screw
12
Cover
31
Snap ring
6
Housing
14
Serial plate
32
Washer
7 (1)
O-ring
33
Arm 8 Snap ring
19
Spacer
34
Proximity sensor
9
Safety screw
24
Terminal block
35 (2)
Spacer (Not shown)
10 (1)
O-ring
25
Terminal block
36
Sensor bracket
11
Axis
30
Spacer
37
Nut
(1) Recommended spare parts (2) Only for 496-4 model
18 | BHGE © 2018 Baker Hughes, a GE company. All rights reserved.
Page 19
8. Calibration (Contd)
Masoneilan
8.3 Calibration of position transmitter 496-858 or 496-858/
Action
The action sense of the valve (open or closed valve, compared to the 4 - 20 mA of the loop signal), determines the position of the connector 3 points of the optoelectronic sensor on one of the two connectors of electronic circuit A or B.
The operation rule is: for a clockwise rotation of the pinion of the control shaft (view cover side), the output current increases (420 mA) when the connector of the optoelectronic sensor is connected in A and decreases when connected in B.
A B
C
Z S
- PN:
+
Linkage adjustment
When mounted on reciprocating valves, adjust the turnbuckle to get the instrument lever perpendicular to the plug stem at mid-travel.
Position transmitter adjustment
– Position the connector 3 points on connector A
or B in function of the chosen action.
– Preset mid travel the zero adjustment (Z)
if necessary *.
– Preset mid travel the span adjustment (S) if
necessary **.
– Configure the switch C (see annex II) on the
rotation angle of the control axle.
– Position the valve to the origin of travel that should
correspond to the minimum of the signal (4 mA).
– Install a milliamp meter in series in the loop and
power up the instrument.
– Rotate the primary pinion on the control axle to
get an output signal around 4 mA
– Fine tune-up of the 4 mA signal with the zero
potentiometer (Z).
– Full stroke the valve to the rated travel and
adjust the output signal to 20 mA with the span potentiometer (S).
– Check the zero and span calibration compared
to the valve stroke. Repeat the zero and span calibration operations if necessary.
* In case of problem of Zero adjustment due to
the physical limits of the potentiometer, turn of 5 turns in the reverse direction that desired and turn the primary pinion to obtain an output current nearest to 4 mA.
** In case of problem of span adjustment due to
the physical limits of the potentiometer, turn of 5 turns in the reverse direction that desired and configure the switch C (see annex II) for a higher or lower angle than that basis.
Adjustment of micro-switch(es) or proximity
switch(es)
Refer to paragraph §8.1 or §8.2 to adjust micro­switches or proximity switch(es).
Strictly follow safety instructions under §7.4 before putting into service.
© 2018 Baker Hughes, a GE company. All rights reserved. 496 Series Masoneilan Position Transmitter ATEX Instruction Manual | 19
Page 20
8. Calibration (Contd)
9 10 11 8 12 23 111 44 110
7
8 220
221
44
6
114
46
222
114
14
F
View F
Vue
108
106
105
101 102 103 104
38 42
107
Parts List
Rep. Designation Rep. Designation Rep. Designation
6
housing
38
spacer
106
Grower washer
7
O-ring
42
electronic card
107
stirrup
8
circlips
44
washer
108
washer
9
CHC screw
46
card support
110
screw
10
O-ring
101
ground screw (inside)
111
spring washer
11
shaft
102
Grower washer
114
CHC screw
12
cover
103
stirrup
220
detector set
14
serial plate
104
washer
221
detector support
23
pinion
105
ground screw (outside)
222
screw
20 | BHGE © 2018 Baker Hughes, a GE company. All rights reserved.
Page 21
9. Maintenance
– Before carrying out any work on the device,
power off the instrument or make sure the local conditions are free of potentially explosive atmosphere for safe opening of the cover.
– These operations must be done in
conformance with EN 60079-17 and / or national and local regulations applicable for explosible atmospheres.
– Before power up or after doing any work
on the device always check the cover (12) is fully screwed, O-ring (10) is free of any damage and security screw (9) is well locked.
Check that no part of the 496 is damaged.
In the event of damage replace the defective parts with genuine manufacturers replacement part.
Pay particular attention to the following:
Check device, mechanical link and general aspect.
Check the cable gland and the electrical
connections.
– Check the condition of the O-ring (10) of
cover (12) and O-ring (7) of the shaft (11).
– Make sure that shaft (11) is not worn out
or damaged.
– If the shaft (11) must be removed, make sure the
original circlips (8) is put back in place. Check that neither the housing nor the shaft are damaged.
Instruments installed in zones 20, 21 and 22 must be cleaned to prevent any dust build up on the walls. See instruction §11.1 b&c for safe cleaning.
10. Special Conditions of Work
Based on 94/9/EC directive, a training session must be followed by person usually recognized to use apparatus in explosible atmospheres.
This training session is not supported par Dresser Produits Industriels S.A.S.
© 2018 Baker Hughes, a GE company. All rights reserved. 496 Series Masoneilan Position Transmitter ATEX Instruction Manual | 21
Page 22
11. Special Conditions of Use
11.1 For Intrinsic Safety and Flameproof Types 496-.58, 496-858 and 496-858/. and
Types 496- .57, 496-857 and 496-857/.
a. It is under the user responsibility to check once
a year the gasket and in the event of damage to replace the defective parts with manufacturers replacement parts only.
b. For use in dusty hazardous areas, the user will have
to proceed to a cleaning regularly the different sides of the enclosure to avoid the deposits of dusts, the maximum thickness must be <5 mm. This cleaning will be done using recommendations defined in §c.
For safe operation, this can be done only if the local conditions around the device are free of potentially explosive atmosphere.
c. To avoid any spark due to electrostatic discharges, it
is requested to follow the instructions of EN TR50404. For example, the user will proceed a cleaning of the device and mainly the plastic label with a wet rag to. For safe operation, this can be done only if
the local conditions around the device are free of potentially explosive atmosphere.
d. The user will have to check the temperature
increase on the 496 head coming from the mechanical part in contact with the 496 housing or through the process thermal radiation be less or equal than the temperature classification allowed. This must be done in conformance with EN 60079-14 and/or national and local regulations applicable for explosible atmospheres.
e. The final user during the 496 installation on site must
show the protection mode used on the serial plate removing the tears off tabs or putting a cross in the dedicated area. This is a requirement only for multi protection marking. The label here on the right is shown for example only and not representative to the 496 label.
22 | BHGE © 2018 Baker Hughes, a GE company. All rights reserved.
Page 23
11.
Special Conditions of Use (Contd.)
T ambient
T cable
70°C
75°C
75°C
80°C
80°C
85°C
85°C
90°C
11.2 Intrinsically safe apparatus: Types 496-.58, 496-858 and 496-858/.
The cable entry must have a protection level at least equal to IP6X according to EN 60529 standards.
For the 496 housing with aluminum material, the user will have to determine the use of the device for group II category 1 (zone 0) against potential
inflammable source causing by sparks in the event of impact or friction.
The voltage supply connected on each 496 connectors must be certified for use in group IIC and the loop intrinsic safety approved. The entity parameters of the voltage supply must be compatible with the entity parameters of the 496 described §4.2.
11.3 Explosion proof apparatus:
Types 496-.57, 496-857 and 496-857/.
When the ambient temperature is higher than 70°C, the user will have to choose a cable entry and a cable compatible with the data of the table below:
The cable entry must have a degree of protection at least equal to IP66/67.
Use only the following greases for the explosion­proof gaskets, shaft, cover threads, cable gland and plug for Y237:
Type
Manufacturer
SI 33
ORAPI
GRAPHENE 702
ORAPI
MOLYKOTE 111 COMPOUND
MOLYKOTE®
MULTILUB
MOLYKOTE®
GRIPCOTT NF
MOLYDAL
All mechanical parts coupled with the limit switch or transmitter and likely to generate a spark or a hot surface will have to be the object, on behalf of the user, an analysis of the risks in agreement with the Directive 94/9/CE. The user will have to follow the conformity module adapted to the zone in which it will be installed.
The shaft joint tolerance is lower than one defined by the standard EN 60079-1. It must be respected with a maximum radial gap of 0.133mm.
The length of explosion-proof gaskets is greater than the one defined in the sheet of EN 60079-1.
The minimal temperature of the cable is indicated on the serial plate.
When the ambient temperature is lower than -20°C, the user will have to choose a cable entry and a cable compatible with the ambient temperature specified on the marking plate.
© 2018 Baker Hughes, a GE company. All rights reserved. 496 Series Masoneilan Position Transmitter ATEX Instruction Manual | 23
Page 24
Annex I
Table 1 Min and Max Ambient Temperatures (°C)
Type 496-858
Ci
Li
1G/2G/1D
1G/2G
1D
nF
µH
MIN
T6
T5
T4
T85°C
T100°C
Transmitter
30 0 -40
70
80
80
70
80
Table 2 Min and Max Ambient Temperatures (°C)
Type 496-158 and 496-258
Ci
Li
1G/2G/1D
1G/2G
1D
nF
µH
MIN
T6
T5
T4
T85°C
T100°C
BZ-2R-72-A2
0 0 -55
80
80
80
70
80
Table 3 Min and Max Ambient Temperatures (°C)
Type 496-458 and 496-558
Ci
Li
1G/2G
1G
2G
1D
nF
µH
MIN
T6
T5
T4
T6
T5
T4
T85°C
T100°C
NJ2-11-N-G
30
50
-25
45
57
81
62
77
81
NJ2-11-SN-G
50
150
-40
45
57
81
62
77
81
NJ2-12GK-N
45
50
-25
51
66
80
NJ2-12GK-SN
50
150
-40
34
46
74
51
66
80
NJ2-12GM-N
30
50
-25
45
57
81
62
77
81
NCB2-12GM35 NO
90
100
-25
45
57
81
62
77
81
NJ3-18-GK-S1N
70
200
-25
34
46
74
51
66
80
NJ4-12GK-N
45
50
-25
51
66
80
NJ4-12GK-SN
70
150
-50
34
46
74
51
66
80
NJ5-18GK-N
70
50
-25
34
46
74
51
66
80
NJ5-18GK-SN
120
200
-40
34
46
74
51
66
80
NJ5-18GM-N
70
50
-25
45
57
81
62
77
81
NJ5-30GK-S1N
100
200
-25
34
46
74
51
66
80
NCB5-18GM40 NO
95
100
-25
45
57
81
62
77
81
24 | BHGE © 2018 Baker Hughes, a GE company. All rights reserved.
Page 25
Annex I (Contd)
Table 5 Min and Max Ambient Temperatures (°C)
Type 496-858/4 and 496-858/5
Ci
Li
1G/2G
1G
2G
1D
nF
µH
MIN
T6
T5
T4
T6
T5
T4
T85°C
T100°C
Transmitter+NJ2-11-N-G
30
50
-25
45
57
80
62
77
80
Transmitter+NJ2-11-SN-G
50
150
-40
45
57
80
62
77
80
Transmitter+NJ2-12GK-N
45
50
-25
51
66
80
Transmitter+NJ2-12GK-SN
50
150
-40
34
46
74
51
66
80
Transmitter+NJ2-12GM-N
30
50
-25
45
57
80
62
77
80
Transmitter+NCB2-12GM35 NO
90
100
-25
45
57
80
62
77
80
Transmitter+NJ3-18-GK-S1N
70
200
-25
34
46
74
51
66
80
Transmitter+NJ4-12GK-N
45
50
-25
51
66
80
Transmitter+NJ4-12GK-SN
70
150
-40
34
46
74
51
66
80
Transmitter+NJ5-18GK-N
70
50
-25
34
46
74
51
66
80
Transmitter+NJ5-18GK-SN
120
200
-40
34
46
74
51
66
80
Transmitter+NJ5-18GM-N
70
50
-25
45
57
80
62
77
80
Transmitter+NJ5-30GK-S1N
100
200
-25
34
46
74
51
66
80
Transmitter+NCB5-18GM40 NO
95
100
-25
45
57
80
62
77
80
Table 4 Min and Max Ambient Temperatures (°C)
Type 496-858/1 and 496-858/2
Ci
Li
1G/2G/1D
1G/2G
1D
nF
µH
MIN
T6
T5
T4
T85°C
T100°C
Transmitter + BZ-2R-72-A2
30 0 -40
70
80
80
70
80
Not Applicable
© 2018 Baker Hughes, a GE company. All rights reserved. 496 Series Masoneilan Position Transmitter ATEX Instruction Manual | 25
Page 26
Annex II
Switch Configuration According to the Rotation Angle of the Control Axle
24° and
< 30°
30° and
< 36°
36° and
< 42°
42° and
<48°
48° and
< 54°
≤54° and
< 62°
62° and
<70°
70° and
< 80°
≤80° and
90°
Concerned Apparatus
87/88 strokes ½to 0,8
37/38 strokes ½to ¾
Sigma F stroke ¾”
Varimax
67/68 stroke 5”
Camflex
Varipak
3100
87/88
strokes 1to 2,5
37/38 strokes 1to 4
Sigma F strokes 1,5to 2
67/68 stroke 6”
67/68 stroke 8:
Minitork
Ball
26 | BHGE © 2018 Baker Hughes, a GE company. All rights reserved.
Page 27
Annex
Ill
CABLE GLAND ACCESSORIES MOUNTING
ON
ATEX
and
IECEx
INSTRUMENTS
WITH CABLE
ENTRY
CERTIFIED Ex d IIC , Ex tb IIIC
Taper
threaded joints in conformance
with ANSI ASME
Bl.20.1:
5
threads provided
on
each
part
WITH ADAPTOR or
REDUCER
CERTIFIED Ex d IIC , Ex tb IIIC
Taper threaded joints in conformance with ANSI ASME
B1.20.1:
5
threads provided
on
each
part
Cemented with •LOCTITE FREINFILET
FORT•
or
equivalent product with similar
efficiency
Y237 ADAPTOR CABLE GLAND ACCESSORIES MOUNTING
ON
ATEX INSTRUMENTS
ONLY
CABLE
ENTRY
ADAPTOR or
REDUCER
HOUSING
CERTIFIED II 2 GO
Ex d IIC Ex
tb
IIIC
CABLE
ENTRY
CERTIFIED II 2 GO
Ex d IIC Ex
tb
IIIC
ADAPTOR
or
REDUCER
CERTIFIED II 2 GO
Ex
d IIC
Ex
tb I I
IC
NOTE : A
PLUG
CAN NOT
BE
MOUNTED
ON AN
ADAPTOR
OR REDUCER
PLUG
HOUSING
CERTIFIED II
2
GO
Ex d I
IC
PLUG
CERTIFIED II
2
GO
Ex d I
IC
Ex
tb
IIIC
A:
Taper threaded joints in conformance with ANSI ASME
Bl.20.1:
S
threads provided
on
each
part
Cemented with •LOCTITE FREINFILET
FORT•
or
equivalent product with similar
efficiency
B :
Taper threaded joints in conformance
Ex
tb IIIC
ONLY ONE PLUG
ALLOWED
B
The
plug
and
the cable
entries
can
be lubricated with
greases specified in paragraph •special conditions
of use•
with ANSI ASME
Bl.20.1:
5
threads provided
on
each
part
Cylindrical thread
joints
In conformance with ISO
965-1/3
Effecti
ve threads
engaged
≥ 5
Depth
of
engagement
8 mm
C:
Taper threaded
joints
in conformance with ANSI ASME Bl.20.1:
5
threads provided
on
each
port
Cylindrical thread
joints
in conformance
with
ISO
965-1/3
Effecti
ve threads
engaged
≥ 5
Depth
of
engagement
8 mm
Cemented with •LOCTITE FREINFILET
FORT•
or
equivalent product with similar
efficiency.
DWG N° 720017989 REV.A
© 2018 Baker Hughes, a GE company. All rights reserved. 496 Series Masoneilan Position Transmitter ATEX Instruction Manual I 27
Page 28
DIRECT SALES OFFICE LOCATIONS
AUSTRALIA Brisbane Phone: +61-7-3001-4319 Fax: +61-7-3001-4399
Perth Phone: +61-8-6595-7018 Fax: +61-8-6595-7299
ITALY Phone: +39-081-7892-111 Fax: +39-081-7892-208
JAPAN Tokyo Phone: +81-03-6871-9008 Fax: +81-03-6890-4620
SOUTH AFRICA Phone: +27-11-452-1550 Fax: +27-11-452-6542
SOUTH & CENTRAL AMERICA AND THE CARIBBEAN Phone: +55-12-2134-1201 Fax: +55-12-2134-1238
Melbourne KOREA
SPAIN
Phone:
+61-3-8807-6002
Phone:
+82-2-2274-0748
Phone:
+34-93-652-6430
Fax:
+61-3-8807-6577
Fax:
+82-2-2274-0794
Fax:
+34-93-652-6444
BELGIUM MALAYSIA UNITED ARAB EMIRATES
Phone:
+32-2-344-0970
Phone:
+60-3-2161-0322
Phone:
+971-4-8991-777
Fax:
+32-2-344-1123
Fax:
+60-3-2163-6312
Fax:
+971-4-8991-778
BRAZIL Phone: +55-11-2146-3600 Fax: +55-11-2146-3610
CHINA Phone: +86-10-5738-8888 Fax: +86-10-5918-9707
FRANCE Courbevoie Phone: +33-1-4904-9000 Fax: +33-1-4904-9010
GERMANY Ratingen Phone: +49-2102-108-0 Fax: +49-2102-108-111
INDIA Mumbai Phone: +91-22-8354790 Fax: +91-22-8354791
New Delhi Phone: +91-11-2-6164175 Fax: +91-11-5-1659635
MEXICO Phone: +52-55-3640-5060
THE NETHERLANDS Phone: +0031-15-3808666
RUSSIA Veliky Novgorod Phone: +7-8162-55-7898 Fax: +7-8162-55-7921
Moscow Phone: +7 495-585-1276 Fax: +7 495-585-1279
SAUDI ARABIA Phone: +966-3-341-0278 Fax: +966-3-341-7624
SINGAPORE Phone: +65-6861-6100 Fax: +65-6861-7172
UNITED KINGDOM Wooburn Green Phone: +44-1628-536300 Fax: +44-1628-536319
UNITED STATES Jacksonville, Florida Phone: +1-904-570-3409
Deer Park, Texas Phone: +1-281-884-1000 Fax: +1-281-884-1010
Houston, Texas Phone: +1-281-671-1640 Fax: +1-281-671-1735
bhge.com
*Denotes a trademark of Baker Hughes, a GE company LLC. Other company names and product names used in this document are the registered trademarks or trademarks of their respective owners.
© 2018 Baker Hughes, a GE company LLC - All rights reserved.
Baker Hughes, a GE company, LLC and its affiliates (“BHGE”) provides this information on an “as is” basis for general information purposes and believes it
to be accurate as of the date of publication. BHGE does not make any representation as to the accuracy or completeness of the information and makes no warranties of any kind, specific, implied or oral, to the fullest extent permissible by law, including those of merchantability and fitness for a particular purpose or use. BHGE hereby disclaims any and all liability for any direct, indirect, consequential or special damages, claims for lost profits, or third party claims arising from the use of the information, whether a claim is asserted in contract, tort, or otherwise. The BHGE logo is a trademark of Baker Hughes, a GE company LLC. GE and the GE monogram are trademarks of the General Electric Company used under trademark license.
GEA31058B 09/2018
Loading...