GE IC695CMM002CA-EJ, IC695CMM004-EJ, IC695CMM002-EJ, IC695CMM004CA-EJ, IC695CMM004LT-EJ Important Product Information

Important Product Information
PACSystems* RX3i
IC695CMM002-EJ and IC695CMM002CA-EJ
GFK-2461N
Serial Communications Modules
April 2018
PACSystems* RX3i Serial Communications modules expand the serial communications capabilities of the RX3i system.
Serial Communications module IC695CMM002 provides two independent, isolated serial ports. Serial Communications module IC695CMM004, illustrated at right, provides four independent, isolated serial ports. Up to six Serial Communications modules can be located in the main PACSystems RX3i backplane1.
The IC695CMM00xCA modules are the conformal-coated versions of the IC695CMM00x modules. The IC695CMM004LT version is for low temperature applications (-40°C).
Each port can be configured for MODBUS Master, MODBUS Slave, CCM Slave, DNP3 Master, DNP3 Slave, or Serial I/O protocol. If any port is configured for DNP3 Master or Slave, the other ports on the module can only be configured for DNP3 Master or Slave.
For modules with firmware version 1.32 or later, half-duplex flow control can be configured using Machine Edition Release 5.90, SP1, SIM 6 or later. Otherwise, flow control defaults to full-duplex.
Additional module features include:
Port-to-port isolation and port-to-backplane isolation
RS-232, RS-485/422 communication, software-selected
Hardware handshake: RTS/CTS, RFR/CTS for RS-232
Selectable Baud Rates: 1200, 2400, 4800, 9600, 19.2K, 38.4K, 57.6K, 115.2K
Module fault status reporting (Watchdog, Ram Fail, Flash Fail)
Module identity and status reporting, including LED status indicators
Meets CE, UL/CUL 508 and 1604, and ATEX requirements
Flash memory for future upgrades
These modules must be located in an RX3i Universal Backplane. RX3i Serial Communications can be hot-inserted and removed following the
instructions in the most recent version of the PACSystems RX3i System Manual, GFK-2314.
For complete installation information, please refer to RX3i and Series 90-30 Installation and Maintenance Requirements document, GFK-2975.
Figure 1: CMM004 Front
View
© 2007-2018 General Electric Company. All Rights Reserved. *Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of their respective owners.
1
Not compatible with Rackless CPUs, such as CPE400.
RX3i Serial Communications Modules
2
GFK-2461N
Release Information
Release 2.02 is a new firmware release implementing a unique system ID for each module to support future RX3i expansion. No change in functionality, performance, or compatibility.
Release History
Release
Firmware
Version
Upgrade Kit
Comments
IC695CMM002-EJ IC695CMM004-EJ
2.02
2.02
41G2459-FW01-000-A2 41G2460-FW01-000-A2
This FW change implements a unique system ID for each module to support future RX3i expansion. No change in functionality, performance, or compatibility.
IC695CMM002-EH IC695CMM004-EH
2.01
2.01
41G2459-FW01-000-A1 41G2460-FW01-000-A1
This FW change fixes a bug in the RS232 serial ASCII communication mode.
IC695CMM002-EG IC695CMM004-EG
2.00
2.00
41G2459-FW01-000-A0 41G2460-FW01-000-A0
This HW/FW change addresses a component obsolescence issue and meets EU RoHS compliance.
IC695CMM002-DF IC695CMM004-DF
1.34
N/A
This change updated compliance markings on the packaging.
IC695CMM002-CF IC695CMM004-CF
1.34
N/A
This change addresses a component obsolescence issue. No change in functionality, performance or compatibility.
IC695CMM002-BF IC695CMM004-BF
1.34
N/A
Label change only. No change in functionality, performance or compatibility.
IC695CMM002-AF IC695CMM004-AF
1.34
44A753277-G06 44A753278-G06
Adds DNP3.0 Master and Slave Unsolicited Reporting functionality. The release also adds the ability to configure the DNP3.0 Slave Analog Input Event Variation and fixes three issues in the DNP3.0 firmware
IC695CMM002-AE IC695CMM004-AE
1.32
44A753277-G05 44A753278-G05
See GFK-2461E for new features and problems resolved.
IC695CMM002-AD IC695CMM004-AD
1.30
44A753277-G04 44A753278-G04
Supports Serial Protocol Language (SPL) scripting. Corrects DNP3 Slave Bit Write issue. Please refer to M050803 - IC695CMM002_004 Product Safety Bulletin for more information.
IC695CMM002-AC IC695CMM004-AC
1.20
44A753277-G03 44A753278-G03
Supports DNP3 Master and DNP3 Slave Protocol
IC695CMM002-AB IC695CMM004-AB
1.10
44A753277-G02 44A753278-G02
Supports CCM Slave Protocol
IC695CMM002-AA IC695CMM004-AA
1.00
N/A
Initial Release
Upgrades
The following upgrade kits may be downloaded from http://www.geautomation.com/support:
Kit Name
IC695CMM002 Kit #
IC695CMM004 Kit #
Notes
FW v2.02 kit
41G2459-FW01-000-A2
41G2460-FW01-000-A2
CMM00x Versions -DF or earlier can only use v1.xx firmware. They cannot be updated to v2.xx firmware due to HW design differences.
FW v2.01 kit
41G2459-FW01-000-A1
41G2460-FW01-000-A1
FW v2.00 kit
41G2459-FW01-000-A0
41G2460-FW01-000-A0