GE PACSystems RX3i, IC694PSM001-AB, IC694ACC200-A User Manual

PACSystems* RX3i
RUN
GRID 2
GRID 1
FLT
GRID 1
2
CAL
CAL
Module Offset: -2
Module Gain: 4000H
Module Offset: -2
Module Gain: 4000H
IC694PSM001
Replacement PSM module
IC694ACC200
Replacement Terminal Assembly
IC694CBL200
One replacement 2m (6.56 ft.) interface cable
two grounding lug nuts
GFK-2748C Power Sync and Measurement System May 2014 IC694PSM001-AB and IC694ACC200-A
The PACSystems Power Sync and Measurement (PSM) system monitors two independent three-phase power grids. It incorporates advanced digital signal processor (DSP) technology to continuously pr ocess three voltage inputs and four current inputs for each grid. Measurements include RMS voltages, RMS currents, RMS power, frequency, and phase relationship between the phase voltages of both grids.
The PSM module performs calculations on each captured waveform, with the DSP processing the data in less than two-thirds of a power line cycle. The PSM module can be used with wye or delta type three-phase power systems or with single-phase power systems.
The PSM system can be used for applications such as:
Electrical power consumption monitoring and reporting  Fault monitoring  Generator control features for generator to power grid synchronization  Demand penalty cost reduction/load shedding
The PSM system consi st s of:
PSM module – A standard IC694 module that mounts in an RX3i rack. The PSM
module provides the DSP capability.
Terminal Assembly – A panel-mounted unit that provides the interface between the
PSM module and the input transformers.
Interface cables Provide the GRID 1 and GRID 2 connections between the PSM
module and the Terminal Assembly.
PSM System Features
Uses standard, user-supplied current transformers (CTs) and potential transformers
(PTs) as its input devices.
Accurately measures RMS voltage and current, power, power factor, frequency,
energy, and total three-phase 15-minute power demand.
Provides two isolated relays that close when the voltage phase relationships between
the two monitored grids are within the specified ANSI 25 limits provided by the RX3i host controller. These contacts can be used for general-purpose, lamp duty or pilot duty loads. Voltage and current ratings for these load types are provided in GFK-2749, PACSystems RX3i Power Sync and Measurement System User’s Manual.
Provides a cable monitoring function that indicates when the cables linking the PSM
module and Terminal Assembly are correctly installed.
PSM module and Terminal Assembly are easily calibrated by hardware configuration
using the Proficy* Machine Edition (PME) software.
Ordering Information
IC694PSK001 PSM System. Includes a PSM module, a Terminal Assembly and two interface cables
IC694ACC201 PSM replacement parts:
two finger guards four thumb screws one relay connector
____________________________ © 2014 General Electric Company. All Rights Reserved.
*
Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of their
respective owners.
2 RX3i Power Sync and Measurement System
Backplane Power Consumption
400 mA max. at 5 VDC
Total Power Dissipation
2.0 W max.
Isolation from Backplane
1500 VDC
RX3i system
Pilot duty: 125 VAC / 125 VDC maximum at 0.35 amp
5 ms
Frequency
30–70 Hz
Impedance
<5 milliohms
Range
0–5 A RMS (5 A nominal)
Phase difference between grids:
±180O
Voltage
0.2%
kW, kVAR, kVA
0.4%
kWH, kVARH, kVAH
0.4%
Power factor
1%
Phase angle
0.1O
Current
15 Amps continuous maximum
Voltage
690 VAC RMS
Contacts above.
GFK-2748C
Specifications
PSM Module Power Requirements
Maximum number of PSM modules per
Sync Relay Contacts
Two isolated relay outputs General purpose: 125 VAC / 125 VDC maximum at 1 amp
Switching speeds
Turn-on time Turn-off time
Measurement Specifications
Three voltage inputs per grid
Impedance: Range
Low range High range
Four current inputs per grid
Frequency 30–70 Hz
Measurement Accuracy 1
No restrictions, as long as the power supply has sufficient capacity
Lamp duty: 125 VAC / 125 VDC maximum at 1 amp
20 ms
All voltage data is scaled in 0.1 VAC units. >1 M
45–150 VAC RMS (120 VAC nominal) 120–690 VAC RMS (600 VAC CAT IV; 690 VAC CAT III)
All current data is scaled in 0.001 Amp units.
Current 0.2%
Frequency 0.01 Hz
Terminal Assembly Input Terminal Ratings
Sync Relay contacts 150 VAC/VDC at 1 Amp Resistive, maximum
Note: Actual contact ratings depend on load type. Refer to Sync Relay
1
In the presence of severe conducted RF interference (IEC 61000-4-6, 10 volts) accuracy could be degraded by ±2% of full
scale.
RX3i Power Sync and Measurement System 3
%I
80 bits
%Q
32 bits
%AI
64 words
A complete data exchange between the PSM and RX3i occurs during each controller scan. Refer to GFK-2749, the section s, System Operation and PSM Status Flags.
ANSI 25 – Generator and Public Grid Synchronization
ANSI 27 – Under-voltage Protection
ANSI 32 – Reverse Power Protection
ANSI 47 –Voltage Phase Sequence Protection
ANSI 59 – Over-voltage Protection
ANSI 60 – Voltage (Current) Imbalance Protection
ANSI 81U – Under-frequency Protection
ANSI 81O – Over-frequency Protection
Four-wire three phase wye systems: 3 PTs and 3 CTs plus Neutral CT (optional)
Three-wire single phase systems: 120/240 (2 PTs and 2 CTs)
GFK-2748C
RX3i CPU Memory Requirement for Automatic Data Exchange
%AQ 2 words
Data Exchange Time Between RX3i CPU and PSM
Minimum scan time is 3.5 ms per PSM module in the backplane. Minimum data update rate is one power line period.
ANSI Protective Functions
ANSI 50 – Instantaneous Over-current Protection
Power Measurement Configurations
Three-wire three phase delta systems: 2 PTs and 2 CTs Three independent single phase systems: 1 PT and 1 CT for each phase
Operating Environment
Enclosure mounting Required. PSM module and Terminal Assembly must be installed in a
NEMA/UL Type 1 enclosure or an IP20 rating providing at least a pollution degree 2 environment.
When this system is installed in an area designated as Class 1 Zone 2 in Europe, compliance with the ATEX Directive requires an enclosure with a minimum rating of IP54.
For product standards, general operating sepcifications, and installation requirements, refer to GFK-2749, PACSystems RX3i Power Sync and Measurement System User’s Manual.
Installation in Hazardous Locations
The following information is for products bearing the UL marking for Hazardous Areas, or ATEX marking for explosive
atmospheres:
Class 1 Division 2 Groups ABCD
This equipment shall be installed in an ultimate enclosure suitable for the environment that is only accessible with the use of a tool.
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations, or nonhazardous locations only.
EXPLOSION HAZARD - Substitution of components may impair suitability for class I, division 2.
4 RX3i Power Sync and Measurement System
GFK-2748C
When in hazardous locations, turn off power before replacing or wiring modules; and DO NOT connect or disconnect equipment unless power has been switched off or the area is known
to be nonhazardous.
ATEX Zone 2
This product must be mounted in an enclosure certified in accordance with EN60079-15 for use in Zone 2, Group IIC and rated IP54. The enclosure shall only be able to be opened with the use of a tool .
Quick Reference Guide
HIGH VOLTAGE; HIGH CURRENT
DO NOT TOUCH the connectors or wiring after powering up the PSM system. Hazardous voltages exist, and death or injury may result.
The Terminal Assembly frame ground connection must always be installed and must be installed before any other wiring is attached.
To reduce risk of electric shock or damage to the attached CTs, always open or disconnect all voltage circuits and apply the shorting bar connections to the current inputs before installing or servicing the connections to the Terminal Assembly.
Never disconnect the GRID 1 or GRID 2 field wiring while power is present. Personal injury or equipment damage may result. Finger guards must be installed on the Terminal Assembly before energizing the field wiring.
User Supplied Equipment
The user must supply the following components depending upon the application. This equipment includes:
5 Amp current transformers  Potential transformers for all installations  1 Amp fuses for each of the voltage leads connected to the Terminal Assembly.  1 Amp fuse for the common or return line for the voltage lead on the Terminal Assembly.  A CT shorting block for each current transformer (CT) connection used on the Terminal Assembly when used with
external CTs.
Installation
Enclosures
The Terminal Assembly and PSM module are considered open equipment (having live electrical parts that may be accessible to users) and must be installed in a protective enclosure or incorporated into other assemblies manufactured to provide safety. As a minimum, the enclosure or assembl ies shall prov ide a degree of protection against solid object s up to 12 mm (for example, fingers). For Non Hazardous environments, this equates to a NEMA/UL Type 1 enclosure or an IP20 rating providing at least a pollution degree 2 environment.
The enclosure must be able to adequately dissipate t he heat generated by all components mounted inside so that no components overheat. Heat dissipation is also a factor in determining the need for enclosure cooling options such as fans and air conditioning.
Installing the PSM Module
RX3i Power Sync and Measurement System 5
1
GRID 1 Operation: 0 = disabled, 1 = enabled
GRID 1 Voltage Selection: 0 = low voltage range (120VAC), 1 = high voltage range (600VAC)
bit to a value that does not match the physical configuration will result in erroneous power system
3
GRID 1 Grid Operational Mode: 0 = single phase, 1 = three-phase
GRID 1 Connection mode:
• In three-phase mode: 0 = WYE system configuration, 1 = DELTA system configuration
GRID 1 PTA measurement: 0 = GRID 1 PTA not connected, 1 = GRID 1 PTA connected
GRID 1 CTA measurement: 0 = GRID 1 CTA not connected, 1 = GRID 1 CTA connected
GRID 1 PTB measurement: 0 = GRID 1 PTB not connected, 1 = GRID 1 PTB connected
GRID 1 CTB measurement: 0 = GRID 1 CTB not connected, 1 = GRID 1 CTB connected
GRID 1 PTC measurement: 0 = GRID 1 PTC not connected, 1 = GRID 1 PTC connected
GFK-2748C
The PSM module must be installed in a main (CPU) rack in an RX3i system. For system-level installation information, refer to GFK-2314, PACSystems RX3i System Manual. The IC694PSM001 Module can be hot-swapped in an RX3i backplane.
Installing the Terminal Assembly
The Terminal Assembly must be securely installed on a rigid, conductive, 12 – 14 gauge steel panel using four user supplied M4 - M5 or #8 - #10 SAE bolts. The Terminal Assembly should be mounted near the host controller rack containing the PSM module, close enough to accommodate the 2 meter interface cables provided.
For detailed installation and power system connection instructions, refer to GFK-2749, PACSystems RX3i Power Sync and Measurement Module User's Manual.
Configuration
The PSM module is configured using the Proficy Machine Edition programming software. For compatible versions, refer to page 12.
Configuration parameters are used to set nominal values for Grid 1 and Grid 2 voltage, current and frequency, and to calibrate the PSM system for specific Potential Transformer and Current Transformer gains, increasing the accuracy of the measured values. Configuration parameters are also used to set ANSI device threshold and delay values.
A Mode Control register, consisting of 32 bits in %Q memory, selects operational and measurement modes. This application must apply initial values to these bits and can change them while the PSM is running.
The application can change a single configuration parameter in run mode by modifying the two-word Parameter Write register in %AQ memory.
Mode Control Bits
The RX3i CPU sends 32 %Q bits of Mode Control data to the PSM module every sweep. The application logic must apply initial values to these bits on the first RX3i scan. The application can change these settings during operation to modify
measurement modes in response to changing conditions.
%Q Bit
Offset
If disabled, the PSM module does no measurements for the GRID1 (power grid) inputs. Note: Both grid control offset bits (Q1 and Q17) must be enabled in order for the PSM module to operate as a 2-source synchronizer.
2
Caution: The voltage range is determined by the physical connections in the power system. Changing this
measurements. Note: Do not change this value in while in RUN mode.
4
Works with the Grid Operational Mode setting to determine system type.
• In single phase mode: 0 = Three single phases ,1 = Three-wire, single phase (120/240) using PTA and PTB
5
The PSM module reconstructs the missing variable. Refer to Reconstructed Variables in GFK-2749.
6
The PSM module reconstructs the missing variable. Refer to Reconstructed Variables in GFK-2749.
7
The PSM module reconstructs the missing variable. Refer to Reconstructed Variables in GFK-2749.
8
The PSM module reconstructs the missing variable. Refer to Reconstructed Variables in GFK-2749.
9
The PSM module reconstructs the missing variable. Refer to Reconstructed Variables in GFK-2749.
Function
Loading...
+ 9 hidden pages