GE GTUN275EM0WW, GTUN275EM1WW, GTUN275EM2WW, GTUN275GM0WW, GTUN275GM1WW Installation Guide

...
Installation
Unitized Gas
Instructions
Questions on installation? Call: 1-800-GECARES (US}or Visit our Web site at: www.GEAppliunces.com (US).
In Canada, call 800-561-3344 or visit www.GEAppliunces.cu.
BEFOREYOU BEGIN
carefully.
IMPORTANT-Save these instructionsfor
localinspector'suse.
IMPORTANT- Observe all governing
codesandordinances.
Note to Installer - Be sure to leave these instructionswith thecustomer.
Note to Customer - Keepthese instructions with your Use and Care Book for future
reference.
Beforethe appliance isremovedfrom service or discarded, remove the washer and dryer
door.
inspectthedryerexhaustoutletandstraighten theoutlet walls if they are bent.
Service information and the wiring diagram are locatedat the accesspanel.
Do not allow childrenon or in the appliance. Close supervision of children is necessary whentheappliance isusednearchildren.
Install the dryer where the temperature is above50°F(].O°C)for satisfactory operationof thedryercontrol system.
WARNING RISK OF FIRE
, Toreducethe riskofsevereinjuryordeath,followallinstallationinstructions. . Applianceinstallationmustbeperformedbyaqualifiedinstaller. . Installtheclothesapplianceaccordingtotheseinstructionsandinaccordancewithlocal
codes.In theabsenceof localcodes,installationmustcomplywith NationalFuelGas Code,ANSIZ223.1/NFPA54ortheCanadianNaturalGasandPropaneInstallationCode,
CSAB149,1,
,CalifomiaSafeOnnkingWaterandToxicEnforcementAct.
Thisact requiresthegovernorofCaliforniato publisha listofsubstancesknowntothe statetocausecancer,birthdefectsorotherreproductiveharmandrequiresbusinesses to warn customersof potentialexposureto suchsubstances.Gasappliancescan causeminorexposureto fourof thesesubstances,namelybenzene,carbonmonoxide, formaldehydeandsoot,causedprimarilybytheincompletecombustionof naturalgas or LPfuels.Properlyadjusteddryerswillminimizeincompletecombustion.Exposureto
thesesubstancescanbeminimizedfurtherbyproperlyventingthedryertotheoutdoors. , Thisappliancemustbeexhaustedtotheoutdoors. , Useonly4"rigidmetalductingforexhaustingtheappliancetotheoutdoors. , DONOTinstalla clothesdryerwithflexibleplasticductingmaterials.Ifflexiblemetal
(semi-rigidorfoiFtype)ductisinstalled,it mustbeULlistedandinstalledinaccordance
withtheinstructionsfoundin"ConnectingTheDryerTo HouseVent"onpage8 ofthis
manual.Flexibleventingmaterialsareknowntocollapse,beeasilycrushed,andtraplint.
Theseconditionswillobstructdryerairflowandincreasetheriskoffire. , Donotinstallorstorethisapplianceinanylocationwhereitcouldbeexposedtowater
andorweather. , Savetheseinstructions.(Installers:Besuretoleavetheseinstructionswiththecustomer).
--i@
Washer/Dryer
TOOLS YOU WILL NEED
{x2I
i0" ADJUSTABLEWRENCHES _._
8"PIPEWRENCH LEVEL
SUPJOINTPUERS FLATBLADESCREWDRIVER
1/4" Nutdriver
In the state of Massachusetts:
Installation must be performed by e qualifledor licensed contractor,
plumber, or gesfltter qualified or licensed by the state.
When using bell-type gas shut-off
valves, they shell be T-handle type.
A flexible gas connector, when used, must not exceed 3 feet.
MATERIALS YOU WILL NEED
4'IDIA.METALDUCT
(RECOMMENDED) 4'IDIAMMETALELBOW
4"DIA.FLEXIBLEMETAL(SEMI-RIGID)
ULLISTEDTRANSITIONDUCT
KITWXO8XlO077(INCLUDES2ELBOWS)
4"DIA.FLEXIBLEMETAL(FOILTYPE)
(IFNEEDED)
ULLISTEDTRANSITIONDUCT
(IFNEEDED.)
1.Cable Tie
2 Washer Hoses
EXHAUSTHOOD
(x2)
4"DUCTCLAMPS
OR
4"SPRINGCLAMPS
PIPE
COMPOUND SOAPSOLUTION
FLEXIBLEGASLINECONNECTOR
PARTS SUPPLIED
% O
2 Rubber Washers Rubber Washers
(washers may be in water hoses)
FORLEAKDETECTION
DUCTTAPE
2 Stainer Screens
SAFETYGLASSES
GLOVES
<5
4"COVERPLATE(IFNEEDED)
(KITWEIM454)
Printedinlexico 233D1835PO01 31-16655-6 12-12 GE
Installation
nstructions
INSTALLATION REQUIREMENTS LOCATION Thisappliance must beinstalled on firm flooring to minimize vibration during spin cycle. Concrete flooring is best, but wood base is sufficient, provided floor support meets FHA standards. This appliance should not be installed on rugs or exposed to weather.
PLUMBING WATERPRESSURE- Must be 20 psi minimum to 120 psi
maximum. WATERTEIVlPERATURE- Household water heater should be
set to deliver water at 120° to 150°F (50° to 66°C) IN THE WASHERwhen hot wash is selected.
SHUTOFFVALVES-Bothhot and cold shutoffvalves (faucets) should be supplied.
DRAIN- Water may be drained into standpipe or set tub.
Discharge height MUSTNOT BE LESSTHAN 30 INCHES, and no more than 6 feet above the base of the washer.
Standpipe must be 1-!/2 inches minimum inside diameter and must be open to atmosphere.
Verify Your Gas Installation (see section 2).
Step 1
Prepare the Area and Exhaust for Installation of
Step 2
appliance (seesection 1). Check and Insure the Existing External Exhaust
Step 3
is Clean (seesection 1)and Meets Attached Installation Specifications (see section 6). Remove the Foam Shipping Pads (seesection 1).
Step 4
Move the appliance to the Desired Location.
Step 5
Levelyour appliance (seesection 8).
Step 6
Connect the Gas Supply (seesection 3) and check
Step 7
for leaks (seesection 4). Connect the External Exhaust (seesection 7).
Step 8
Connect to plumbing facilities (seesection 11).
Step 9
ELECTRICAL REQUIREMENTS
CAUTION: Before plugging in washer, read the following
electrical requirements.
CAUTION: For personal safety, do not use an extension
cord or adapter plug with this appliance. Do not, under any circumstances, cut or remove the third grounding prong from the power cord. Follow national electrical codes and ordinances. Thisappliance must besupplied with the voltage and frequency indicated on the rating plate (located at the top of the dryer front panel),and connected to an individual,
properly grounded branch circuit, protected by a 15- or 20-
amp circuit breaker or time-delay fuse. If the electric supply
provided does not meet the above requirements, call a licensed electrician.
Step 10 Connect the Power Supply (seesection 5). Step 11 Check the Operation of the Power Supply, Gas
Connections, and Venting.
Step 12 Place the Owners Manual and the Installation
Instructions in a Location Where They Will Be Noticed Bythe Owner.
For Alcove or Closet Installation see section 1:3. For Bathroom or Bedroom Installation see section 14. For Mobile or Manufactured Home see section 12.
ADJUSTING FOR ELEVATION
. Gas clothes dryers input ratings are based on sea level
operation and need not be adjusted for operation at or below 2000 ft. elevation. For operation at elevations above 2000 ft., input ratings should be reduced at a rate of 4 percent for each 1000 ft. above sea level.
. Installation must conform to local codes and ordinances
or, in their absence with the National Fuel Gas Code, ANSI Z22:3.1/NFPA54, or the Natural Gas and Propane
Installation Code,CSAB149.1.
2
L5
Installation Instructions
24" NOMINAL PRODUCT DIMENSIONS
_---'23.75"----_
Gas Inlet
(Rearview of appliance)
W(]ter Inlets
(reor)
51"
* Dimension represents door closed including handle and knobs.
NOTE:With feet set at mid position, feet can be adjusted +_.575".
27" NOMINAL PRODUCT DIMENSIONS
_------'26.7"-----_
0oolo o O
--12.5"
52.9"
W(]ter Inlets
]
36.5"
_47"_
Gas Inlet
(Rec]rview of appliance)
4.35"
_._ Drc]in outlet
i (rec]r)
_-- 3.9"
F
_--- 26.8"
* Dimension represents door closed including handle and knobs. NOTE:With feet set at mid position, feet can be adjusted +_.575".
L
_------ 30.85"------_
3
Installation Instructions
Minimum Clearance Other Than Alcove or Closet Installation
Minimum clearance to combustible surfaces and for air opening are: 0 in. clearance both sides and rear.Consideration
must be given to provide adequate clearance for installation and service.
I-_ PREPARING FOR INSTALLATION
OF NEW APPLIANCE
NEW HONE OR REMODELING FAUCETS/ DRAIN STANDPIPE/ELECTRICAL LOCATIO N
DISCONNECTING GAS
TURNGAS SHUT-OFFVALVEI_ DISCONNECTANDDISCARDOLD,_._,
TOTHEOFF ___ FLEXIBLEGASCONNECTORAND
POS,T,ON OLDTRANS,T,ONDUCT,NG
MATERIAL.REPLACEWITHNEW CSA(AGA)APPROVEDFLEXIBLE
GASLINECONNECTORANDUL APPROVEDTRANSITIONDUCT.
WARNING - NEVERREUSEOLD
FLE×IBLE CONN ECTORS.
Theuse of old flexible connectors can cause leaks and personal injury. Always use new flexible connectors
when installing gas appliances.
REMOVING LINT FROM WALL EXHAUST OPENING
Removeand discard existing plastic or metal foil transition duct and replace with ULlisted transition duct.
_j WALL
INTERNAL_t_,].DUCT _ CHECKTHATEXHAUST OPENING -'_-_ \ G "'.. HOODDAPIPEROPENS
TILTTHEAPPLIANCE
SIDEWAYSAND REMOVE
THE FOAMSHIPPINGPADS
BYPULLINGATTHESIDES
AND BREAKINGTHEMAWAY
FROMTHEAPPLIANCELEGS.
BESURETOREMOVEALL OF THE FOAMPIECESAROUND THE LEGS.
After the machine is in the home, remove remaining packing material/
carton from washer.
DO NOT REMOVE SHIPPING ROD AT
THISTIME.
Removestyrofoam block. Removethe
bag containing theWasher hosesand parts parts from tub. Put styrofoam
block back in tub opening to hold tub in placeduring the rest of installation.
Hove washer close to final position. Make sure there is at least a 24"
clearance on right side of washer to
remove shipping bar.PULLSHIPPING BAROUT USINGYELLOWPLASTIC
HANDLE. Keep bar so it can be reinstalled if washer is ever moved
again.
StyrofoamBlock
ANDCLOSESFREELY.
II
and Parts
Yellow
" Plastic
/ Handle
I-_ GAS REQUIREMENTS
WARNING
, Installation must conform to local codes and
ordinances, or in their absence, with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CSA
B1491
. Thisgas dryerisequippedwitha Valve& Burner
Assembly foruse onlywith naturalgas Using conversion kit WE25M73 for 24" Models or
WE25M74 for 27" Models,your localservice organizationcan convertthisdryerforuse with
propane (LP)gas ALL CONVERSIONS MUST BE MADE BY PROPERLY TRAINED AND QUALIFIED
PERSONNEL AND IN ACCORDANCE WITH LOCAL
CODES AND ORDINANCE REQUIREMENTS
Theappliancemustbedisconnectedfromthegassupply pipingsystemduringanypressuretestingofthatsystem
ata testpressureinexcessof05 PSI(34KPa)
The appliancemustbe isolatedfromthegassupply pipingsystembyclosingtheequipmentshutoffvalve
duringanypressuretestingofthegassupplypipingof testpressureequaltoorlessthan05 PSI(34KPa)
Note: 24" Gas supply connection has a flexible hose thus dimensions will vary.
Right side of
Laundry Center
12"--_
Locate spigots, " drain standpipe s3" |
and electrical plug | in this area
!
27" GASSUPPLYCONNECTION
_ .................. _|
!
FLOOR
3"
4
Installation Instructions
GAS SUPPLY
, A 1/8-in.National Pipe Taper thread plugged tapping,
accessible for test gauge connection, must be installed immediately upstream of the gas supply connection to
the dryer, Contact your local gas utility should you have
questions on the installation of the plugged tapping.
. Supply line isto be 1/2-in. rigid pipe and equipped with
an accessible shut-off within 6 ft. of, and in the same room with the dryer.
,Use pipe thread sealer compound or Teflon tape
appropriate for natural or LPgas.
, You must usewith this dryer a flexible metal connector
listed ANSI Z21.24 / CSA 6.10. The length of the connector shall not exceed 3 ft.
, Connect flexible metal connector to dryer and gas
supply.
, Open shut-off valve.
RECONNECTING GAS
Listed connector ANSI Z21.24 / CSA6.10
24"
NEW METAL _.. _ _k_>4/ '_
FLEXIBLEGAS
INLET FROM
APPLIANCE
LINECONNECTOR
/
BACK OF
APPLIANCE
2a" & 27"
27"
APPLYPIPECOMPOUND
TOTHEADAPTORAND
APPLIANCEGASINLET.
TIGHTENTHEFLEXIBLEGASLINETO
THEADAPTORUSING2ADJUSTABLE
WRENCHES.
APPLY PIPE COMPOUND TO
APPLIANCE INLET
24"
FLARE
/8" NPT INLET
FROM APPLIANCE
27"ONLY
ELBOW
27" ONLY
ADAPTOR
27" ONLY
NEW METAL
FLEXIBLE GAS
LINE CONNECTOR
ADAPTOR
SHUT-OFF VALVE
ITEHS NOT SUPPLIED
NPT PIPE PLUG
FOR CHECKING GAS INLET PRESSURE
AT LEAST 1/2"
FLOOR
Note: The connector and fittings are designed for use only on the original installation and are not to be reused for another appliance or at another location. Keepflare end of adaptor free of grease, oil and thread sealant. CAUTION: Use adopters as shown. Connector nuts must
not be connected directly to pipe threads.
;HTEN THE FLEXIBLE GAS
LINE TO THE APPLIANCE
INLET USING 2 ADJUSTABLE
WRENCHES.
24" & 27"
_ APPLY PIPECOMPOUND
TIGHTEN ALL CONNECTIONS USING TWO
ADJUSTABLE WRENCHES. DO NOT OVERTORQUE GAS CONNECTIONS!
TO ALL MALE THREADS
24" & 27"
5
Installation Instructions
[-4]LEAK TEST
I WARNING: NEVER USE AN OPEN
FLAME TO TEST FOR GAS LEAKS.
ENSURE PROPERGROUND EXISTSBEFOREUSE.
OPEN
GASVALVE.
Check oil connections for leaks with soapy solution or equivalent. Apply soap solution. Bubbles indicate leaks. Leak test solution
must not contain ammonia which could cause damage to the brass fittings, tfleak are found, close valve retighten thejaint and repeat the soap test.
[_ELECTRICAL CONNECTION INFORMATION
WARNING - TO REDUCE THE
RISK OF FIRE, ELECTRICAL SHOCK,
AND PERSONAL INJURY:
. DO NOT USEAN EXTENSIONCORDOR AN ADAPTER
PLUGWITH THISAPPLIANCE. Dryer must be electrically grounded in accordance
with local codes and ordinances, or in the absence of local codes, in accordance with the NATIONAL
ELECTRICALCODE,ANSI/NFPANO.70.
ELECTRICAL REQUIREMENTS
This appliance must be supplied with 120V, 60Hz, and connected to u properly grounded brunch circuit,
protected by u 15- or 20- amp circuit breaker or time- delay fuse. If electrical supply provided does not meet the above specifications, it is recommended that a licensed electrician install an approved outlet.
, WARNING - THIS DRYER IS
EQUIPPED A THREE-PRONG (GROUNDING) PLUG FOR 'fOUR PROTECTION AGAINST
SHOCK HAZARD AND SHOULD BE PLUGGED DIRECTLY INTO A PROPERLY GROUNDED
THREE-PRONG RECEPTACLE. DO NOT CUT OR REMOVE THE GROUNDING PRONG FROM THIS PLUG.
GROUNDING INSTRUCTIONS
This appliance must be grounded. In the event of
malfunction or breakdown, grounding will reduce the risk of electric shock by providing u path of least resistance of electric current. This appliance is equipped with a cord having an equipment-grounding conductor and a grounding plug. The plug must be plugged into an appropriate outlet that isproperly installed and grounded in accordance with all local codes and ordinances.
WARN IN G - Improper connectionofthe
equipment-grounding conductor can result in a risk of electric shock. Check with a qualified electrician or serviceman if you are in doubt as to whether the appliance is properly grounded.
Do not modify the plug provided with the appliance. If it
will not fit the outlet, have a proper outlet installed by a
qualified electrician.
_-I EXHAUST INFORMATION
I WARNING - IN CANADA AND IN THE
UNITED STATES,THE REQUIRED EXHAUST DUCT DIAMETER IS 4 IN (102ram). DO NOT USE DUCT LONGER THAN SPECIFIED IN THE EXHAUST
LENGTH TABLE. Using exhaust longer than specified length will:
Increase the drying times and the energy cost. Reducethe dryer life.
Accumulate lint, creating a potential fire hazard.
The correct exhaust installation is YOUR
RESPONSIBILITYoProblems due to incorrect installation
are not covered by the warranty.
Remove and discard existing plastic or metal foil
transition duct and replace with ULlisted transition duct. The MAXIMUM ALLOWABLEduct length and number of
bends of the exhaust system depends upon the type of duct, number of turns, the type of exhaust hood (wall cap), and all conditions noted below. The maximum duct
length for rigid metal duct isshown in the table below.
6
Installation instructions
EXHAUST INFORMATION (CONT.)
27" DRYEREXHAUSTLENGTH
RECOMMENDED MAXIMUM LENGTH
Exhaust Hood Types
Recommended
No. of 900 Rigid Rigid
Elbows Metal Metal
O 56 Feet 42 Feet
i 48 Feet 34 Feet 2 40 Feet 26 Feet 3 32 Feet 18 Feet
Use only for short
run installations
24" DRYEREXHAUSTLENGTH
RECOMMENDED MAXIMUM LENGTH
Exhaust Hood Types
Recommended Use only for short
No. of 900 Rigid Rigid
Elbows Metal Metal
O 45 Feet 56 Feet
i 53 Feet 26 Feet 2 24 Feet 16 Feet
run installations
, For every extra 90° elbow, reduce the allowable vent
system length by 10ft.
, Two 45°elbows will be treated likeone 90°elbow. Forthe
sideexhaust installations,add one 90° elbow to the chart.
, The total vent system length includes all the straight
portions and elbows of the system (transition duct included).
EXHAUST SYSTEM CHECK LIST
HOOD ORWALL CAP , Terminate in a manner to prevent back drafts or entry
of birds or other wildlife.
, Termination should present minimal resistance to
the exhaust air flow and should require little or no maintenance to prevent clogging.
, Never install u screen in or over the exhaust duct. This
could cause lint build up.
, Wall cups must be installed at least 12 in.above ground
level or any other obstruction with the opening pointed down.
SEPARATIONOFTURNS For best performance, separate all turns by at least 4
ft. of straight duct, including distance between lust turn
and exhaust hood.
TURNS OTHERTHAN 90°
, One turn of 450 or less may be ignored. , Two 450 turns should be treated us one 900 turn.
, Each turn over 450 should be treated as one 900 turn. SEALINGOFJOINTS
, Alljoints should be tight to avoid leaks. The mule end of
each section of duct must point away from the dryer.
, Do not assemble the ductwork with fasteners that
extend into the duct. They will serve as a collection point for lint.
, Duct joints can be made air and moisture-tight by
wrapping the overlapped joints with duct tape.
, Horizontal runs should slope down toward the outdoors
1/4 inch per foot
INSULATION Duct work that runs through an unheated urea or is
near air conditioning should be insulated to reduce condensation and lint build-up.
P-JEXHAUST CONNECTION
, WARNING - TO REDUCE THE
RISK OF FIRE OR PERSONAL INJURY:
, This apliancce must be exhausted to the outdoors. , Use only 4" rigid metal ducting for the home exhaust
duct.
, Use only 4" rigid metal or UL-listed flexible metal
(semi-rigid or foil-type) duct to connect the dryer to the home exhaust duct. It must be installed
in accordance with the instructions found in "Connecting The Dryer To House Vent" on page 8 of
this manual.
, Donot terminate exhaust inu chimney, uwall, uceiling,
gas vent, crawl space, attic, under an enclosed floor, or in any other concealed space of u building. The accumulated lint could create a potential fire hazard.
, Never terminate the exhaust into a common duct
with u kitchen exhaust system. A combination of grease and lint creates mpotential fire hazard.
, Do not use duct longer than specified in the exhaust
length table. Longer ducts can accumulate lint, creating u potential fire hazard.
, Never install u screen in or over the exhaust duct. This
will cause lint to accumulate, creating mpotential fire hazard.
, Do not assemble ductwork with any fasteners that
extend into the duct. Thesefasteners can accumulate
lint, creating mpotential fire hazard. , Do not obstruct incoming or exhausted air. , Provide an access for inspection and cleaning of
the exhaust system, especially at turns and joints.
Exhaust system shall be inspected and cleaned at
least once year.
THIS DRYER COMES READY FOR REAR
EXHAUSTING. IF SPACE IS LIMITED, USE
THE INSTRUCTIONS IN SECTION 9 TO
EXHAUST DIRECTLY FROM THE SIDES OR BOTTOM OF THE CABINET.
CSA(AGA}APPROVED NEWFLEXIBLEGAS For straight line installation, connect
EXTERNALDUCT
OPENING
DUCTTAPEOR
DUCTCLAMP
4" METALDUCTCUT
TO PROPERLENGTH
LINECONNECTOR the drger exhaust to the external
GAS clamp.
INLET PIPE
DUCTTAPEOR DUCTCLAMP
exhaust hood using duct tape or
7
Installation Instructions
STANDARD REAR EXHAUST
(Vented above floor level}
U
ELBOW HIGHLY
RECOMMENDED
ECOMMENDED ONFIGURATION
O MINIMIZE XHAUSTBLOCKAGE
NOTE: ELBOWS WILL PREVENT DUCT KINKING AND COLLAPSING
[8]LEVELING AND STABILIZING YOUR
APPLIANCE
_.__E LEVEL
LEVEL
FRONT-TO-BACK.
2LEVELINGLEGS
Level and stabilizing your appliance
1. Carefully move the appliance to its final location. Gently rock the appliance into position. It is important not to damage the rubber leveling legs when moving your appliance to its final location. Damage legs can increase appliance vibration. It may be helpful to spray window cleaner on the floor to help move your appliance to its final position.
Note: do not usewasher cover to lift the unit.
2. To ensure the appliance is level and solid on all four legs, tilt the appliance forward so the rear legs are off the ground. Gently set the appliance back down to allow the rear legs to self adjust.
2
-TO-SIDE
3.With the appliance in its final position, place a level on top of back part of the washer lid and check it side to side, then check front to back. Screw the front leveling
legs up or down to ensure the appliance is resting solid on all four legs (no rocking or the appliance should exist), turn the lock nuts on each leg up toward the base of the unit and snug with a wrench.
Note: Keep the leg extension at minimum to prevent excessive vibration. The farther out legs are extended, the
more the unit will vibrate.
CONNECTING THE DRYER TO HOUSE VENT
RIGIDMETALTRANSITIONDUCT
Forbest drying performance,a rigid metal transition duct is recommended.
Rigidmetaltransitions ducts reducethe risk of crushing and kinking.
UL-LISTEDFLEXIBLEMETAL(SEMI-RIGID)TRANSITIONDUCT
tf rigidmetal ductcannotbeused,thenUL-listedflexiblemetal (semi-rigid)ductingcan beused(KitWX08X10077).
Never install flexible metal duct in walls, ceilings, floors or otherenclosedspaces.
Formanyapplications,installingelbowsat boththe dryer and
thewall ishighly recommended(seeillustrationsonpage 9). Elbowsallowthe dryerto sit closeto the wallwithout kinking and or crushing the transition duct, maximizing drying performance.
Avoidrestingthe duct on sharpobjects.
UL-LISTEDFLEXIBLEMETAL(FOIL-TYPE}TRANSITIONDUCT
tn special installations,it may be necessaryto connect the dryerto the housevent usinga flexiblemetal (foiltype)duct. AUL-listedflexiblemetal (foil-type)ductmaybe usedONLYin installations where rigid metal or flexible metal (semi-rigid) ducting cannot be usedAND where a 4" diameter can be maintained throughout the entire length of the transition
duct.
tn Canadaand the United States,onlythe flexible metal(foil-
type) ducts that comply with the "Outline for ClothesDryer
TransitionDuctSubject2158A"shallbeused.
Total length of flexible metal duct should not exceed 8 feet
(2.4m).
Avoidrestingthe duct on sharpobjects.
Forbestdryingperformance:
1.Slideoneendof the duct overthe clothesdryeroutletpipe.
2.Securetheduct with a clamp.
3.Withthe dryerinits permanentposition,extendthe ductto
its full length.Allow 2" of ductto overlap the exhaustpipe. Cutoffand removeexcessduct. Keepthe duct asstraight aspossiblefor maximumairflow.
/4.Securetheductto the exhaustpipewith the otherclamp.
8
DO NOT _
EXCESSIVE
EXHAUST
USE
Installation instructions
DO
ELBOW HIGHLY RECOMMENDED
DON'T
EXHAUST TO LEFT OR RIGHT SIDE OF
CABINET
, For side ducting, remove the knockout (ONLY1).Rotate
elbow sections so that the opening points to the side.
Preassemble 4" elbow with 4" duct. Use only 4" UL
approved rigid metal for ducting inside the dryer.
, Insert duct assembly through the side opening and
connect to the internal elbow.
WARNING- Be sure not to pullor damage
the electrical wires inside the dryer when inserting the duct.
4" ULapproved rigid metal
I IIAPPLIANCE I II°NFLEXIBLE
o
[-_ 24" MODELS ONLY:
DRYER EXHAUST TO RIGHT, LEFT OR BOTTOM CABINET
_WARNING - BEFOREPERFORMING
THIS EXHAUST INSTALLATION, BE SURE TO DISCON NECTTH EAPPLIANCE FROM
ITS ELECTRICAL SUPPLY. PROTECT
YOUR HANDS AND ARMS FROM SHARP
EDGES WHEN WORKING INSIDE THE CABINET. BE SURE TO WEAR GLOVES.
For downward venting, rotate elbow sections so that elbow points downward
DUCT
TAPE
Apply duct tape as shown on the joint between the dryer
internal duct and the straight duct pipe.
WARNING-
Internal duct joints must be
R secured with tape, otherwise
they may separate and cause
a safety hazard.
27" MODELS ONLY: DRYER EXHAUST TO RIGHT, LEFT OR
BOTTOM CABINET
WARNING -BEFOREPERFORMING
THIS EXHAUST INSTALLATION, BE SURE TO DISCON NECTTH EAPPLIANCE FROM
ITS ELECTRICAL SUPPLY. PROTECT
YOUR HANDS AND ARMS FROM SHARP
EDGES WHEN WORKING INSIDE THE CABINET. BE SURE TO WEAR GLOVES.
i
REMOVE DESIRED KNOCKOUT (ONLY1)
FLO0
JJ
!
For downward venting, rotate elbow
sectionsm, so that elbow points downward.
9
Installation instructions
EXHAUST TO LEFT OR RIGHT SIDE OF CABINET
, Rotate elbow sections so that the opening points to the
side to which you want to vent. Preassemble 4" elbow
with 4" duct, Use only 4" UL approved rigid metal for
ducting inside the dryer.
, Connect duct assembly to the internal elbow.
WARNING- Besure not to pull or damage the
electrical wires inside the dryer when inserting the duct.
, Apply duct tape as shown on the joint between the
dryer internal duct and the straight duct pipe.
, STANDPIPEDIAMETER- The standpipe diameter must
be 1-1/2" minimum. There MUST be an air gap around the drain hose in the standpipe. A snug fit can cause a siphoning action. SIPHON BREAKKIT- For a drain facility less than 33" high, the hose, coupling and clamps provided in the machine must be used and, in addition, a siphon break
MUST be installed on the back of the machine. Use
Siphon Break Kit WH/49X228 and follow instructions in the kit.
[ ]CONNECTING TO PLUMBING
FACILITIES
WARNING-
Internal duct joints must be
H secured with tape, otherwise
they may separate and cause a safety hazard.
PLUMBING INFORMATION WATER
[ -ISU PPL¥ REQUIREMENTS
, HOTAND COLD WATERFAUCETS- Must be within 42"
of the appliance water inlet hose connections. The faucets must be 3/4" garden hose-type so inlet hoses
can be connected. WATER PRESSURE- Must be between 10 and 120
pounds per square inch with a maximum unbalance pressure, hot vs. cold flowing, of 10 pounds per square
inch. WATERTEMPERATURE- Water heater should be set to deliver 140° to 150°F (60° to 66°C) in the washer when
HOTwash is selected.
, SHUT-OFFVALVES- Both hot and cold water shut-off
valves (faucets) should be supplied.
LOCATION- Do not install appliance in an area where the temperature will fall below freezing. If appliance
is stored or transported in freezing temperatures, be sure all water from the fill and drain systems has been
removed.
DRAIN REQUIREMENTS
, DRAINRATE- The drain or standpipe must be capable
of accepting a discharge at the rate of 16 gallons per
minute.
, DRAINHEIGHT- The drain height must be 33" minimum
and 96" maximum.
If not installed, install rubber washer in one end of hot water
hose. Thread hot water hose onto connection labeled H at top rear of washer. Handtighten, plus an additional 1/8 turn
with pliers.
Ifnot installed, install rubber washer in one end of coldwater
hose. Thread cold water hoseonto connection labeled Cat top rear of washer. Handtighten, plus an additional 1/8 turn
with pliers.
Moveappliance as closeto final location as possible,leaving
room for you to make water, drain, electrical and vent connections to your home.
NOTE: If longer drain hose is required, order drain hose
extension kit, GE part number WH/49X301.Connectadditional
drain hose (contained in kit) to original hose with hose clamp
(contained in kit).
Insertfree endofdrain hoseinto
drain opening ofyour home up to drain hose stopper (do not
removehosestopperitprevents
siphoning). If water valves and drain are built into wall, fasten
drain hoseto oneofwater hoses with cable tie provided (ribbed
side on inside).Ifyour drains is a standpipe, fasten drain hose to standpipe with cable tie
provided.
10
Installation instructions
_-2]MOBILE OR MANUFACTURED HOME
INSTALLATION
, Installation MUST conform to the MANUFACTURED
HOME CONSTRUCTION & SAFETY STANDARD,
TITLE 24, PART 32-80 or, when such standard is not
applicable, with AMERICAN NATIONAL STANDARD FORMOBILEHOME, ANSi/NFPA NO. 501B.
, The appliance MUST be vented to the outdoors with
the termination securely fastened to the mobile home structure.
, Thevent MUSTNOTbe terminated beneath a mobile or
manufactured home.
, Thevent duct material MUSTBEMETAL.
KIT 14-D346-33 MUST be used to attach the appliance securelyto the structure.
Thevent MUSTNOTbeconnected to anyother duct, vent,or chimney.
, Do not use sheet metal screws or other fastening
devices which extend into the interior of the exhaust vent.
Provideanopening with a freearea of at least 25 sq.in.for introductionof outsideairinto thedryer room.
ALCOVE OR CLOSET INSTALLATION
DOOR VENTILATION OPENING (27" MODELS)
A minimum of 120 square inches of opening, equally divided at top and bottom, is required. Air openings are
required to be unobstructed when a door is installed. A Iouvered door with equivalent air openings for the full length of the door is acceptable.
z: :::n::
Sq.In.
27" Model
Mli i o%.,n.
When louvers or registers are placed in door openings, the free air openings of the louvers or registers must equal 120 square inches.
DOOR VENTILATION OPENING (24" MODELS)
A minimum of 72 square inches of opening is required. Air openings are required to be unobstructed when a door is
installed. A Iouvered door with equivalent air openings for
the full length of the door is acceptable.
, If your appliance isapproved for installation in an alcove
or closet, it will be stated on a label on the appliance back.
Thedryer MUSTbevented to theoutdoors.Seethe EXHAUST INFORMATIONsection.
Donot install this appliance with less than the minimum
clearances shown above.
Thecloset shouldbe vented to the outdoors to prevent gas
pocketingin caseofa gasleakinthe supplyline.
Nootherfuel-burning applianceshall beinstalledinthesame
closetwith the appliance.
CONSIDERATION MUST BE GIVEN TO PROVIDE ADEQUATE CLEARANCES FOR INSTALLATION
AND SERVICE.
, WARNING: DONOTINSTALLTHIS
APPLIANCE IN A CLOSET WITH A SOLID DOOR.
24" Model
/o/
H II J'ii'J;4 Sq. In.
I'l HT
When louvers or registers are placed in door openings, the free air openings of the louvers or registers must equal 72 square inches.
[Z4]BATHROOM OR BEDROOM INSTALLATION
, The appliance MUST be vented to the outdoors. See
EXHAUSTINFORMATIONsection 6 & 7.
, The installation must conform with local codes or,
in the absence of local codes, with the NATIONAL
ELECTRICALCODE,ANSI/NFPA NO. 70 and NATIONAL
FUELGASCODE,ANSIZ223.
11
Loading...
+ 25 hidden pages