GTX65EBSJ
22 1/2"
27 3/4"
26"
4"
1 3/4"
3 1/4"
4 1/4"
37 1/2"
46"
27"
5"
Power Cord 4 1/2"
11 3/4"
GE Appliances 6.1 Cu. Ft. Capacity Aluminized Alloy Drum Electric Dryer with HE Sensor Dry
DIMENSIONS AND INSTALLATION INFORMATION (IN INCHES)
ELECTRIC DRYER RATING:
24 0V 5600W 24A 60Hz
208V 4400W 22A 60Hz
EXHAUST OPTION: 4-way rear, right, left and bottom.
CIRCUIT REQUIREMENTS: An individual, properly-grounded branch circuit,
protected by a 30-amp circuit breaker or a time-delay fuse, is required.
NOTE: Dryer wall outlet must be located within 36" of service cord entry and
acessible when dryer is mounted in position.
INSTALLAT ION INFO RMATION: For complete information, see installation
instructions packed with your dryer.
SPECIAL INSTALLATION REQUIREMENTS
ALCOVE OR CLOSET INSTALLATION:
- If your dryer is approved for installation in an alcove or closet, it will be stated on a label on the
dryer back.
- The dryer MUST be exhausted to the outside.
- Minimum clearances between dryer cabinet and adjacent walls or other surfaces are: 0"
either side; 1" front, top and rear.
- Closet doors must be louvered or otherwise ventilated and must contain a minimum of 60
sq. in. of open area equally distributed. If this closet contains both a washer and a dryer,
doors must contain a minimum of 120 sq. in. of open area equally distributed.
- No other fuel-burning appliance shall be installed in the same closet with a gas dryer.
BATHROOM OR BEDROOM INSTALLATION:
- The dryer MUST be exhausted to the outdoors.
- The installation must conform with the local codes, or in the absence of local codes, with
the National Electric Code and National Fuel Gas Code, ANSI Z223 for gas dryers.
MINIMUM CLEARANCES OTHER THAN ALCOVE OR CLOSET INSTALLATION:
- Minimum clearances to combustible surfaces are: 0" both sides; 1" rear.
DRYER EXHAUSTING INFORMATION :
- Use metal duct only, vertical and horizontal ducting.
SIDE VIEW REAR VIEW
POWER CORD LOCATIONS
BACK VI EW
For answers to your Monogram, GE Café™ Series, GE Profile™ Series or
GE Appliances product questions, visit our website at geappliances.com
or call GE Answer Center® Service, 800.626.2000.
Listed by
Underwriters
Laboratories
Speci fication Revised 9/16
GTX65EBSJ
GE Appliances 6.1 Cu. Ft. Capacity Aluminized Alloy Drum
Electric Dryer with HE Sensor Dry
FOR COMPLETE INFORMATION, SEE INSTALLATION INSTRUCTIONS PACKED WITH
YOUR DRYER.
DUCTING MATERIALS:
For best performance, this dryer should be vented with 4" diameter all rigid metal exhaust duct.
If rigid metal duct cannot be used, then UL-listed flexible metal (semi-rigid) ducting can be used
(Kit WX08X10077). In special installations, it may be necessary to connect the dryer to the house
vent using a flexible metal (foil-type) duct. A UL-listed flexible metal (foil-type) duct may be used
ONLY in installations where rigid metal or flexible metal (semi-rigid) ducting cannot be used
AND where a 4" diameter can be maintained throughout the entire length of the transition duct.
Please see installation instruction packed with your dryer for complete instructions when using
flexible metal (foil type) ducting.
EXHAUST LENGTH CALCULATION:
1. Determine the number of 90° turns needed for your installation. If you exhaust to the side or
bottom of dryer, add one turn.
2. The maximum length of 4" rigid (aluminum or galvanized) duct which can be tolerated is shown
in the table. A turn of 45° or less may be ignored. Two 45° turns within the duct length should
be treated as a 90° elbow. A turn over 45° should be treated as a 90° elbow.
Dryers must be exhausted to the outside.
CAUTION: For personal safety do not terminate exhaust into a chimney, under any enclosed
house floor (crawl space), or into an attic, since the accumulated lint could create a fire hazard or
moisture could cause damage. Never terminate the exhaust into a common duct or plenum with a
kitchen exhaust, since the combination of lint and grease could create a fire hazard.
Exhaust ducts should be terminated in a dampered wall cap to prevent back drafts, bird nesting,
etc. The wall cap must also be located at least 12" above the ground or any other obstruction with
the opening pointed down.
FOR MORE INFORMATION ON VENTING KITS AND ACCESSORIES, PLEASE CALL
1-800-GE-CARES.
DRYER EXHAUSTING INFORMATION—
USE METAL DUCT ONLY VERTICAL AND
HORIZONTAL DUCTING
BEST PERFORMANCE
Maximum length
A
Number
of 90°
Domestic dryer models
Long Vent 6.1-7.4 cu. ft.
capacity electric & gas
(GTD33, GTD42, GTD45,
GTD65, GTX22, GTX33, GTX42
and GTX65)
For every extra 90° elbow, reduce the allowable vent system
length by 10 ft.
Two 45° elbows will be treated like one 90° elbow.
For the side exhaust installations, add one 90° elbow to the chart.
When calculating the total vent system length, you must add all
the straight portions and elbows of the system (including the
transition duct.
of 4" dia rigid
metal duct
Exhaust hood type
A
turns
0 120 ft. 90 ft.
1 100 f t. 75 ft.
2 85 ft. 65 ft.
3 70 ft. 55 ft.
4 60 f t. 45 ft.
5 55 ft. 35 ft.
4"
opening
opening
B
2-1/2"
Speci fication Revised 9/16