GE GFK0579B User Manual

GE Fanuc Automation
Programmable Control Products
Series 90t-70 Remote I/O Scanner
User’s Manual
GFK–0579B July 1992
Warnings, Cautions, and Notes as Used in this Publication
Warning notices are used in this publication to emphasize that hazardous voltages, currents, temperatures, or other conditions that could cause personal injury exist in this equipment or may be associated with its use.
In situations where inattention could cause either personal injury or damage to equipment, a Warning notice is used.
Caution notices are used where equipment might be damaged if care is not taken.
GFL–002
Warning
Caution
Note
Notes merely call attention to information that is especially significant to understanding and operating the equipment.
This document is based on information available at the time of its publication. While efforts have been made to be accurate, the information contained herein does not purport to cover all details or variations in hardware or software, nor to provide for every possible contingency in connection with installation, operation, or maintenance. Features may be described herein which are not present in all hardware and software systems. GE Fanuc Automation assumes no obligation of notice to holders of this document with respect to changes subsequently made.
GE Fanuc Automation makes no representation or warranty, expressed, implied, or statutory with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. No warranties of merchantability or fitness for purpose shall apply.
The following are trademarks of GE Fanuc Automation North America, Inc.
Alar m Master CIMST AR Helpmate PROMA CRO Series Six CIMPLICITY GEnet Logicmaster Series One Series 90 CIMPLICITY 90–ADS Genius Modelmaster Series Three VuMaster CIMPLICITY PowerTRA C Genius PowerTRA C ProLoop Series Five Workmaster
Copyright 1992 GE F anuc A utomation North America, Inc.
All Rights Reserved
Content of this Manual
This book is a reference to installing, configuring, and using a GE Fanuc Series 90t–70 Remote I/O Scanner (IC697BEM733).
Chapter 1. Introduction: This chapter describes the Remote I/O Scanner and other equipment that may be used with it. It discusses Geniust bus operation as it relates to the Remote I/O Scanner, and describes how the Remote I/O Scanner can be used in redundancy systems. Chapter 1 also describes configurable features of a remote drop, and explains configuration methods.
Chapter 2. Installation: Explains how to properly install the components of a remote drop, including Series 90–70 racks, a Remote I/O Scanner, and other Series 90–70 modules. Chapter 2 also explains how to complete the Genius bus connections and how to connect a programmer to the Remote I/O Scanner.
Chapter 3. Remote I/O Scanner Operation: Describes the memory and operating modes of the Remote I/O Scanner, and explains its operation. This chapter also explains how option modules such as the Programmable Coprocessor Module (PCM) could be used in a remote drop.
Preface
Chapter 4. Configuration with Logicmastert 90–70: Explains configuration steps using Release 4 of the Logicmaster 90–70 configuration software.
Chapter 5. Logicmaster 90 Operation with a Remote Drop: Explains how to set up a Logicmaster 90 programmer to communicate with a remote drop. This chapter also describes functional differences in LM90 when it communicates with a remote drop.
Chapter 6. Remote Drop Configuration with a Hand–held Monitor: Explains how to configure a remote drop using a Genius Hand–held Monitor.
Chapter 7. Monitoring and Controlling Remote Drop Data: Explains how the I/O data for a remote drop can be displayed on a Hand–held Monitor or programmer. Chapter 7 also describes how I/O circuits can be forced, toggled, or overwritten.
Chapter 8. Diagnostics and Fault Clearing: Explains how diagnostic information from a remote drop can be displayed on a Hand–held Monitor or programmer, and how faults can be cleared.
Chapter 9. Remote I/O Scanner Datagrams: Describes datagrams that can be sent to a Remote I/O Scanner. Chapter 9 also shows the format of the Remote I/O Scanner’s Report Fault datagrams.
Appendix A. Estimating the Maximum Number of Remote Drops for a Bus: Shows how to roughly estimate how many remote drops can be on a bus with one Bus Controller, one Hand–held Monitor, no Genius blocks, and no programmed communications.
Appendix B. Finding the I/O Configuration Data Total of a Remote Drop: Gives instructions for finding the amount of configuration data needed for the I/O modules in a remote drop.
iii
Preface
Appendix C. Logicmaster 90–70, Release 3, Series 90–70 PLC Configuration Instructions: Explains how to complete the PLC portion of the configuration if you are
using Release 3 of the Logicmaster 90–70 software.
Appendix D. Logicmaster 90–70, Release 3, Remote Drop Configuration Instructions:
Explains how to configure a remote drop if you are using Release 3 of the Logicmaster 90–70 software.
Related Publications
For more information, refer to these publications: Genius I/O System User’s Manual (GEK–90486–1). Reference manual for system
designers, programmers, and others involved in integrating Genius I/O products in a PLC or host computer environment. This book provides a system overview, and describes the types of systems that can be created using Genius products. Datagrams, Global Data, and data formats are defined.
Series 90–70 PLC Installation and Operation Manual (GFK–0262). This book describes the modules of a Series 90–70 PLC system, and explains system setup and operation.
Logicmaster 90–70 User’s Manual (GFK–0263). Reference manual for system operators and others using the Logicmaster 90–70 software to program, configure, monitor, or control a Series 90–70 PLC and/or a remote drop.
Logicmaster 90 Software Reference Manual (GFK–0265). Reference manual which describes program str ucture and defines program instructions for the Series 90–70 PLC.
Series Sixt
Controller, which interfaces a Genius bus to a Series Six PLC. This book describes the installation and operation of the Bus Controller. It also contains the programming information needed to interface Genius I/O devices to a Series Six PLC.
Series FiveBus Controller User’s Manual (GFK–0248). Reference manual for the Bus Controller, which interfaces a Genius bus to a Series Five PLC. This book describes the installation and operation of the Bus Controller. It also contains the programming information needed to interface Genius I/O devices to a Series Five PLC.
Genius I/O PCIM User’s Manual (GFK–0074). Reference manual for the PCIM, which interfaces a Genius bus to a suitable host computer. This book describes the installation and operation of the PCIM. It also contains the programming information needed to interface Genius I/O devices to a host computer.
Bus Controller User’s Manual (GFK–0171). Reference manual for the Bus
We Welcome Your Comments and Suggestions
At GE Fanuc automation, we strive to produce quality technical documentation. After you have used this manual, please take a few moments to complete and return the Reader’s Comment Card located on the next page.
Jeanne Grimsby
Senior technical writer
Series 90–70 Genius Bus Controller User’s Manual – July 1992iv
Contents
Chapter 1 Introduction 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Description 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Required Equipment 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts of a Remote Drop 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Genius Bus 11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Timing 12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Redundancy 14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration 18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2 Installation 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hardware Packaging 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preinstallation Check 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Grounding Procedures 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rack Installation 23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
P ower Supply Installation 26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Locations 27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Installation and Removal 28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field Wiring to I/O Modules 29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Multiple Racks in a Remote Drop 31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Genius Bus Connections: Single Bus Cable 32 . . . . . . . . . . . . . . . . . . . . . . . . . . .
Genius Bus Connections: Dual Bus Cables 33 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programmer Connection at the Remote I/O Scanner 35 . . . . . . . . . . . . . . . . . . .
Multidrop Connections 38 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 3 Remote I/O Scanner Operation 43 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview 43 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O Scan 44 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O Scanner Memory 45 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Transfer with the Host 46 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using Option Modules in a Remote Drop 50 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 4 Configuration with Logicmaster 90–70 53 . . . . . . . . . . . . . . . . . . . . . . .
Configuration Limits 53 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Filenames for Configuration Files 53 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using Release 3 Configuration Files with Release 4 Software 54 . . . . . . . . . . . .
“Attaching” Configuration Files 54 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring a Remote Drop 55 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configure the Modules in the Remote Drop 65 . . . . . . . . . . . . . . . . . . . . . . . . . .
Completing the Remote Drop Configuration 68 . . . . . . . . . . . . . . . . . . . . . . . . .
Displaying Configured References 71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Copying, Deleting, and Undeleting 73 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Selecting an Existing Configuration File 74 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Storing the Configuration 75 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GFK–0579B Series 90–70 Remote I?O Scanner User ’s Manual – July 1992
v
Contents
Chapter 5 Logicmaster 90 Operation with a Remote Drop 77 . . . . . . . . . . . . . . . .
Overview 77 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting Up Programmer Communications with a Remote Drop 78 . . . . . . . . .
Status Display for a Remote Drop 79 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Logicmaster 90 Software,
Programmer Differences for a Remote Drop 80 . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 6 Remote Drop Configuration
with a Hand–held Monitor 83 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview 84 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Set Up the Hand–held Monitor 86 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display the Configuration Main Menu 87 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Select the Device Number 88 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Select a Series Six or Series Five PLC Reference Address 89 . . . . . . . . . . . . . . . .
Select the Baud Rate 90 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Select Series 90–70 Data Lengths 91 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Select the Remote Drop ID 93 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display I/O Modules in Remote Drop 94 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Select Genius Bus Redundancy 95 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Select BSM Control 95 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Select CPU Redundancy 96 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Select Configuration Protection 97 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 7 Monitoring and Controlling
Remote Drop Data 99 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview 99 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Monitoring/Controlling I/O Data:
Genius Hand–held Monitor 102 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Monitoring/Controlling I/O Data:
Logicmaster 90–70 107 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Monitoring/Controlling I/O Data:
Series Six PLC or Series Five PLC 109 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Monitoring/Controlling I/O Data:
Computer 112 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 8 Diagnostics and Fault Clearing 113 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview 113 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display and Clear Faults from a Genius Hand–held Monitor 114 . . . . . . . . . . .
Display and Clear Faults from Logicmaster 90–70 116 . . . . . . . . . . . . . . . . . . . . .
Display and Clear Faults from Logicmaster 5 or Logicmaster 6 121 . . . . . . . . . .
GFK–0579B Series 90–70 Remote I?O Scanner User ’s Manual – July 1992
vi
Contents
Chapter 9 Remote I/O Scanner Datagrams 123 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Datagram Types 124 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Read Map 125 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Read Map Reply 125 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Write Map 125 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Report Fault Datagram Format 126 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix A Estimating the Number of Remote Drops for a Bus 129 . . . . . . . . . . . . .
Appendix B Finding the I/O Configuration Data Total
for a Remote Drop 131 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix C Logicmaster 90–70, Release 3:
Series 90–70 PLC Configuration
for Remote Drops 133 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview 133 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 1: Create or Select a PLC Program Folder 134 . . . . . . . . . . . . . . . . . . . . . . . .
Step 2: Add the Remote I/O Scanner to the Genius Bus 134 . . . . . . . . . . . . . . . . .
Step 3: Configure the Remote I/O Scanner 137 . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 4: Store the Configuration to the PLC 140 . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix D Logicmaster 90–70, Release 3:
Remote Drop Configuration Instructions 141 . . . . . . . . . . . . . . . . . .
Overview 141 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote Drop Configuration Summary 142 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 1: Create a Folder 143 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 2: Configure the Remote I/O Scanner 144 . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 3: Configure the Modules in the Remote Drop 148 . . . . . . . . . . . . . . . . . . . .
Step 4: Store the Configuration to the Remote Drop 150 . . . . . . . . . . . . . . . . . . .
GFK–0579B Series 90–70 Remote I?O Scanner User ’s Manual – July 1992
vii
restart lowapp ARestart oddapp: ARestarts for autonumbers that do not restart in
Î
Î
Î
Î
Î
each chapter . figure bi level 1, reset table_big level 1, reset chap_big level 1, reset1 Lowapp Alwbox restart evenap:A1app_big level 1, resetA figure_ap level 1, reset table_ap level 1, reset figure level 1, reset Figure 1. table level 1, reset Table 1. these restarts oddbox reset: 1evenbox reset: 1must be in the header frame of chapter 1. a:ebx, l 1 resetA a:obx:l 1, resetA a:bigbx level 1 resetA a:ftr level 1 resetA c:ebx, l 1 reset1 c:obx:l 1, reset1 c:bigbx level 1 reset1 c:ftr level 1 reset1 Reminders for autonumbers that need to be restarted manually (first instance will always be 4) let_in level 1: A. B. C. letter level 1:A.B.C. num level 1: 1. 2. 3. num_in level 1: 1. 2. 3. rom_in level 1: I. II. III. roman level 1: I. II. III. steps level 1:
1. 2. 3.

Chapter 1 Introduction

section level 1 1
1
This chapter describes the Series 90t–70 Remote I/O Scanner (IC697BEM733) and other equipment that may be used with it. It discusses Genius bus operation as it relates to the Remote I/O Scanner, and describes how the Remote I/O Scanner can be used in Genius redundancy systems.

Overview

The Remote I/O Scanner is an intelligent module which mounts in a remote Series 90–70 rack, and inter faces Series 90–70 modules to a Genius bus.
figure bi level 1 table_big level 1
The Genius bus connects the Remote I/O Scanner to a Bus Controller in the host PLC or computer. A dditional remote drops, Genius blocks, Bus Controllers, and Hand–held Monitors can be attached to the same bus.
a42453
S
P
C
S
A N N E R
REMOTE DROP
CPU
BUS
CONTROLLER
COMMUNICATIONS
BUS
I/O BLOCKS
HAND–HELD
MONITOR
The Remote I/O Scanner can send up to 128 bytes of inputs from input boards in its remote drop to the CPU, and can provide up to 128 bytes of outputs from the CPU to output boards in the remote drop. The amount of data transferred is configurable. Individual I/O circuits in the remote drop can be:
H
Forced and unforced from a Hand–held Monitor or the application program logic.
H
Overridden from a PLC application program.
H
Toggled from a Logicmaster 90–70 programmer.
The Remote I/O Scanner can be used in CPU redundancy (dual controller) and bus redundancy (dual bus) systems.
The Host CPU
The Remote I/O Scanner is ideally suited for use in a Series 90–70 PLC system. However, any type of PLC or computer capable of controlling a Genius bus can be used as the host. Suitable hosts include Series Six PLCs, Series Five PLCs, and computers equipped with a PCIM (P ersonal Computer Interface Module), QBIM (Q–Bus Interface Module), or a third–party GENI–based interface.
1
1

Module Description

The Series 90–70 Remote I/O Scanner consists of a single circuit board, with a hinged door which serves as a faceplate. It occupies one slot in a Series 90–70 I/O rack.
MODULE OK LED
I/O ENABLED LED
BUS B ACTIVE LED
a44761
GENIUS
HAND HELD
MONITOR
CONNECTOR
SERIAL
PORT
RS–422/485
COMPATIBLE
GENIUS
BUS
TERMINALS
MODEL 70
BEM 733
MODULE OK I/O ENABLED BUS B ACTIVE
ON = OK, ACTIVE
MODULE FUNCTION
SERIES 90–70 GENIUS BUS REMOTE I/O SCANNER
GENIUS HAND HELD MONITOR
SERIAL PORT
RS–422/485 COMPA TIBLE
SER1
SER2
SER1A
R E D
SER2A
U N D A
SER1B
N C Y
SER2B
MODULE IC697BEM733 LABEL 44A726758–110R02
SHIELD
SHIELD
OUT
SHIELD
IN A
SHIELD
OUT A
SHIELD
IN B
SHIELD
OUT B
IN
BEM 733
The Remote I/O Scanner does not require batteries; the battery holder in the faceplate is not used.
Series 90–70 Remote I/O Scanner User’s Manual – July 19922
LEDs
Module OK
I/O Enabled
Bus B Active
The Remote I/O Scanner has three LEDs that show through the transparent portion at the top of the door.
lights to indicate that the module has passed its powerup diagnostic tests. If this LED flashes, it indicates a problem, as shown in the table below . If this LED is off, there is a fatal error, which causes the Remote I/O Scanner to go to stop/faulted mode.
lights when the Remote I/O Scanner is receiving the expected output data from the CPU. If this LED flashes, it indicates either I/O data is forced, or a Device Number conflict.
if the Remote I/O Scanner is installed on a dual (redundant) bus, this LED lights if Bus B of the dual bus pair is the currently–active bus.
The following table summarizes the LED indications.
Module OK I/O Enabled Meaning
On On Normal operation
Blinking On Fault detected
On Blinking I/O data forced
Alter nate blinking Alternate blinking F ault detected, and I/O data forced
Synchronous blinking Synchronous blinking Device Number conflict
On Off Outputs not being updated from CPU Off Off No power or fatal error
1
Connectors
The front of the module has three connectors:
H
9–pin male D Connector: the upper connector. Used for attaching a Genius Hand–held Monitor.
H
15–pin female D Connector: the center connector. This connector is an RS–422 compatible RS–485 serial port. It can be used for communicating with a programmer equipped with the serial version of Logicmaster 90–70, or for connection to a multidrop communications network.
H
The connector at the bottom of the module attaches the Genius bus terminal strip. Because the terminal strip is removable, it is possible to service or replace the Remote I/O Scanner while the rest of the system is operating, without disrupting bus communications.
3Chapter 1 Introduction
1

Required Equipment

The following equipment is required to use a Remote I/O Scanner.
H
At least one Series 90–70 5–slot or 9–slot remote rack with Power Supply. A remote drop may include multiple racks and power supplies.
H
If a Genius Hand–held Monitor will be used to configure or monitor a remote drop, it must be version 4.0 (IC660HHM501G) or later.
H
If Logicmaster 90–70 configuration software will be used to configure the remote drop, it must be release 3.0 or later:
A. IC641SWP701F (3.5”, 2DD, 5.25” 2S/HD) B. IC641SWP704C (5.25” 2S/2D)
H
If the parallel version of Logicmaster 90–70 will be used with a remote drop, the remote drop must include a Bus Transmitter Module (IC697BEM713) for connection to the programmer.
H
If the remote drop will include more than one rack of modules, a Bus Transmitter Module (IC697BEM713) one or more Bus Receiver Modules (IC697BEM711), and appropriate cables are required.
H
For a Series 90–70 PLC
h
The Series 90–70 CPU firmware must be release 2.0 or later.
h
The Logicmastert 90–70 programming and configuration software must be release 3.0 or later. Catalog numbers are given above.
h
A Series 90–70 Genius Bus Controller, release 3.0 or later. The Bus Controller must be 4.0 or later for full diagnostics display from Logicmaster 90–70 (see chapter 8), or for redundancy applications.
H
For a Series Sixt PLC
h
CPU: rev. 105 or later.
h
Logicmaster 6 Programming Software: release 4.02 or later.
h
Bus Controllers: IC660CBB902 or 903, version 1.7 or later.
H
For a Series Fivet PLC
h
CPU: rev . 3.2 (catalog number with E suffix) or later.
h
Logicmaster 5 Programming Software: release 2.01 or later.
h
Bus Controller: any version
H
For a Host Computer
h
PCIM: any version
h
QBIM: any version
Series 90–70 Remote I/O Scanner User’s Manual – July 19924

Parts of a Remote Drop

Together, a Remote I/O Scanner and the modules it serves make up a remote drop on the Genius bus. The remote drop may consist of one to eight Series 90–70 racks.
1
P S
S
B
C
T
A
M N N E R
GENIUS BUS
RACK 0
REMOTE DROP
PSB
RACK 7
R
M
RACK 1
P
B
S
R
M
UP TO 50 FEET
NOTE:
ALL RACKS MUST BE AT THE SAME GROUND POTENTIAL
PSB
RACK 6
R
M
a44875
Multiple R acks
When there are multiple racks, the Remote I/O Scanner must be located in the first rack (rack 0). To link multiple racks in a remote drop, a Bus T ransmitter (IC697BEM713) Module in rack 0 is connected to a Bus Receiver Module (IC697BEM711) in the first expansion rack. Additional racks are also linked via Bus Receiver Modules.
All racks in a remote drop must be at the same ground potential.
Distance Between R acks in a Remote Drop
The maximum total cable length from the first Bus Transmitter to the last Bus Receiver in a remote drop is 50 feet (15 meters). Since none of the daisy–chained signals (all at the same ground potential) are broken at a rack, any rack can be independently powered–down without affecting the operation of the rest of the system.
Data Quantities
Regardless of the number of racks used for a remote drop, the maximum amount of data for a remote drop is 128 bytes of inputs and 128 bytes of outputs (8 discrete points represent one byte and 1 analog channel uses 2 bytes).
5Chapter 1 Introduction
1
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Series 90–70 Racks
Any of the following racks can be used in a remote drop:
H
5–slot, panel mount rack (IC697CHS750).
H
9–slot, panel mount rack (IC697CHS790).
H
9–slot, rack mount rack (IC697CHS791).
Each of these racks has an additional, wider slot for a P ower Supply. Rack sizes may be mixed in a system installation to suit the requirements of your application.
The rack–mount Series 90–70 rack has flanges on the front for mounting on 19–inch standard instrument rack hardware. The panel–mount racks have rear flanges for mounting on electrical panels.
WITH OPTIONAL VME J2
BACKPLANE KIT
1.00
(25.4)
CONNECTOR
FOR POWER SUPPLY
SPACER
(QTY.4)
SIDE VIEW
I/O TERMINAL RESTRAINING
STRAP
7.25
(184)
9.14
(232)
CABLE
ENTRANCE
FROM
BOTTOM
REMOVABLE
I/O
TERMINAL
BLOCK
Î
Î
Î
Î
Î
HINGED
DOOR
11.50 (292)
6.75
(172)
=
(19)
3.00 (76)
1.50 (38)
2.24 (57)
.34
(8.64)
.75
ОООООООООООО
ОООООООООООО
Î
GND
STUD
ОООООООООООО
Î
ОООООООООООО
Î
ОООООООООООО
Î
ОООООООООООО
Î
ОООООООООООО
Î
ОООООООООООО
DIMENSIONS FOR 5 SLOT RACK
12.60
19.00 (320)
(483)
18.11 (460)
Î
Î
Î
Î
Î
Î
FRONT VIEW
11.71 (297)
17.04 (433)
10.64 (270)
.25 DIA. (TYPICAL)
DIMENSIONS IN INCHES, MILLIMETERS ARE IN PARENTHESIS
Series 90–70 racks do not require a fan for cooling as long as sufficient space is left around the rack when it is mounted.
GND
STUD
a42984
Series 90–70 Remote I/O Scanner User’s Manual – July 19926
Series 90–70 Power Supplies
These Series 90–70 Power Supplies can be used in a remote drop:
H
IC697PWR710, 120/240 VAC input, +5 VDC output, 55 Watts (shown below)
H
IC697PWR711, 120/240 VAC input, +5 VDC, +12 VDC, –12 VDC output, 100 Watts
H
IC697PWR721, 24VDC input, +5 VDC, +12 VDC, –12 VDC output, 90 Watts
H
IC697PWR731, 125VDC input, +5 VDC, +12 VDC, –12 VDC output, 60 Watts
a42818
LED
MODEL 70
PWR 710
POWER SUPPLY MODULE
INPUT
OUTPUT
BRANCH CIRCUIT FUSING MUST BE PROVIDED EXTERNALLY
RECOMMENDED TIGHTENING TORQUE 1,5Nm (15kg cm)
ON
OFF
L1
N
SHORT FOR 120 OPEN FOR 240
120/240VAC 50/60HZ
1.5/0.8A 5V
11A
120
SELECT
INPUT
L1
240
L2
WARNING
EVEN IF THE POWER SUPPLY
IS SWITCHED OFF, HAZARDOUS
VOLTAGES FROM USER FIELD
WIRING MAY STILL BE PRESENT
ON THE I/O TERMINAL BOARDS
AS WELL AS THE POWER
SUPPLY TERMINAL BOARD.
CARE SHOULD BE TAKEN WHEN
HANDLING THE POWER SUPPLY
AND I/O MODULES AS WELL AS
ANY WIRING CONNECTED TO
THEM IN ORDER TO PREVENT
PERSONAL INJURY.
WARNING
DO NOT REMOVE OR INSERT
MODULES WITH POWER APPLIED.
PERSONAL INJURY, SYSTEM
MALFUNCTION AND/OR DAMAGE
TO THE EQUIPMENT MAY OCCUR.
1
MODULE IC697PWR710 LABEL 44A726758–501
Power supply selection will depend on the input power and load requirements of the application. Load specifications for Series 90–70 modules are listed on page 9.
AC power supplies mount in the leftmost slot of a Series 90–70 rack. DC power supplies can be mounted on the side of the rack or used as freestanding modules. The DC power supplies require a power supply adapter, which installs in the power supply slot and is connected to the power supply by a short cable.
7Chapter 1 Introduction
1
Powering Two Racks from a Single Power Source
Except for the 125VDC supply, each of these power supplies can be used to power two racks if the total current requirement for both racks does not exceed the power supply’s load capacity. The rack that does not contain the Power Supply must not have a load greater than 5.2 amps.
Connection from the rack with the power supply to the second rack is made through a cable (catalog number IC697CBL700) three feet (one meter) in length, which is terminated at both ends with 9–pin D–connectors. This cable car ries both +5 volt power and control signals (power sequencing signals only) to the second rack.
INSTALL CABLE
SO THAT THE
INDICATED END
IS SUPPLYING
POWER
TWO
RACK
POWER
CABLE
123456789
POWER SUPPLY
FACE
PLATE
a42134
FIRST RACK
SECOND
RACK
Series 90–70 Remote I/O Scanner User’s Manual – July 19928
Series 90–70 Modules for a Remote Drop
The table below lists modules that can be placed in a remote drop, and gives their catalog numbers, I/O capacities, and loads.
1
Module Catalog
Number
IC697BEM733 Remote I/O Scanner 0.80 IC697BEM713 Bus T ransmitter Module 1.40 IC697BEM711 Bus Receiver Module 0.80
IC697MDL240 16 120 V A C Isolated, Input, 16 points 0.25 IC697MDL241 16 240 V A C Isolated, Input, 16 points 0.25 IC697MDL250 32 120 VAC Input, 32 point 0.35 IC697MDL650 32 24 VDC Input, 32 point 0.30 IC697MDL651 32 Input module, negative logic, TTL 0.525 IC697MDL652 32 12 VDC Pos/Neg Logic Input, 32 points 0.30 IC697MDL653 32 24 VDC Pos/Neg Logic Input, 32 points 0.30 IC697MDL654 32 48 VDC Pos/Neg Logic Input, 32 points 0.30 IC697MDL340 16 120 VAC Output, 16 point 0.25 IC697MDL341 16 120/240 V A C Isolated 2A Output, 16 points 0.25 IC697MDL350 32 120 VAC Output, 32 point 0.50 IC697MDL740 16 24/48 VDC Output, 16 point 0.25 IC697MDL750 32 24/48 VDC Output, 32 point 0.15 IC697MDL752 32 12 VDC 0.5A Output, 32 points 0.50 IC697MDL753 32 5/48 VDC 0.5A Neg Logic Output, 32 points 0.50 IC697MDL940 16 Relay Output 16 points 0.75
IC697ALG230 8 Analog Input Base Converter 0.80 IC697ALG440 16 Analog Input Current Expander 0.40 IC697ALG441 16 Analog Input Voltage Expander 0.40 IC697ALG320 4 High Level Analog Output, V oltage/Current 1.66
I/O Points
or
Channels
Module Description
Discrete Modules
Analog Modules
Load in
Amps at
+5 VDC
Option Modules
IC697PCM711 Programmable Coprocessor Module 1.00 IC697GDC701 Graphics Display Coprocessor Module 1.20 IC697ADC701 Alphanumeric Display Coprocessor Module 1.00
Remote Drop Capacity
The maximum number of I/O and option modules that can be installed in a remote drop is 63, which requires eight 9–slot racks. There are two limits that cannot be exceeded when locating modules in a remote drop:
H
There must not be too many option modules in a remote drop. See “Option Modules”, below .
H
The configuration data for all the I/O modules in a remote drop must not add up to more than 4500 bytes. This amount of configuration data will not be reached in any remote drop where all I/O modules are included in the Remote I/O Scanner’s configured I/O map. However, it is possible to have I/O modules in a remote drop configured to use references outside the I/O map, as explained in chapter 3. If the drop will have some modules configured outside the Remote I/O Scanner’s I/O map, refer to appendix B.
9Chapter 1 Introduction
1
Analog Modules: The maximum number of analog input modules that can provide input data to the host is 8; however, there may be additional modules in the remote drop configured outside the Remote I/O Scanner’s I/O map. The maximum number of analog input modules that can be configured for a remote drop is 29. Similarly, while the maximum number of analog output modules that can receive output data from the host is 16, as many as 54 can be configured for a remote drop.
Option Modules: A remote drop with seven or fewer racks can contain up to 18 GDS (Graphics Display Coprocessor), or ADS (Alphanumeric Display Coprocessor) modules, or up to 9 PCM (Programmable Coprocessor) modules with daughterboards. Each PCM/daughterboard combination counts as two option modules against the total of 18. The following table shows how many GDS and/or ADS modules can be used with 0 to 9 PCMs.
Total Option Modules in a Remote Drop
Number of PCMs and
Daughterboards
0 18 1 16 2 14 3 12 4 10 5 8 6 6 7 4 8 2 9 0
Number of GDS and/
or ADS Modules
If there are 8 racks in the remote drop, one less PCM with daughterboard, or two less GDS or ADS modules are permitted.
Analog Expanders: A remote drop can accommodate up to one analog input module with eight expander modules. However, the maximum number of expanders that can pass inputs to the CPU is three, due to the Remote I/O Scanner’s 128–byte input data limit. If an analog module and three expanders were used, no additional input modules (either analog or discrete) could communicate with the host from the remote drop.
Modules Not Supported: A remote drop cannot have any I/O module interrupts, or bus controllers or other modules that depend on COMREQ instructions for their operations.
Third–party VME modules cannot be used in a remote drop.
Series 90–70 Remote I/O Scanner User’s Manual – July 199210

Genius Bus

1
The Genius bus is an industrially–hardened Local–Area–Network (LAN). It passes I/O (control) data and background information (datagrams) between the Remote I/O Scanner and a Genius bus controller. The communicated data is protected from environmental interference and corruption in several ways. Each byte is triply–encoded during transmission, and each message is checksummed with a cyclic redundancy check (CRC). Embedded intelligence at either end also checks for correct message length and type.
A Genius bus can support up to 32 devices. Each remote drop counts as one device on the bus, regardless of the number or type of modules it includes. A bus can serve any mix of remote drops, I/O blocks, Bus Controllers and Hand–held Monitors, provided the bus scan time does not exceed 400mS. Typical busses reserve one location for a Bus Controller and one for a Hand–held Monitor, leaving 30 for additional devices. The illustration below shows a Bus Controller in a Series 90–70 PLC connected to a Genius bus with I/O blocks and two single–rack remote drops.
PSC
P U
Bus Type
Bus Termination Baud Rate
7500 FEET WITH 16 DEVICES, AT 38.6K BAUD
B C
3500 FEET WITH 32 DEVICES, AT 153.6K BAUD EXT.
MAXIMUM BUS LENGTH
90–70 REMOTE RACK
S
I
I
I
C
/
/
/
A
O
O
O N N E R
90–70 REMOTE RACK
S
I
I
I
C
/
/
/
A
O
O
O N N E R
a44669
I
I
I
I
/
/
/
/
O
O
O
O
I
I
I
I
/
/
/
/
O
O
O
O
Daisy–chained bus cable; single twisted pair plus shield or Twinax. Fiber optics cable and modems can also be used.
75, 100, 120, or 150 ohm resistor at both ends of electrical bus cable. Configurable. 153.6 Kbaud standard, 153.6 Kbaud extended,
76.8Kbaud, or 38.4 Kbaud.
Maximum Bus Length
Maximum Number of Devices
7500 feet at 38.4 Kbaud, 4500 feet at 76.8 Kbaud, 3500feet at 153.6 Kbaud extended, 2000 feet at 153.6 Kbaud, standard. Maximum length at each baud rate also depends on cable type. The Genius I/O System User’s Manual pro vides a complete list of cable types, show­ing corresponding bus lengths and baud rates. Greater bus lengths are possible using sections of fiber optics cable with modems.
32 devices at 153.6 Kbaud standard, 153.6 Kbaud extended, or 76.8 Kbaud. 16 devices at 38.4 Kbaud. Includes Bus Controller and Hand– held Monitor.
11Chapter 1 Introduction
1
Total Amount of Input and
Total Amount of Input and Output Data for

Timing

A fully–loaded (128 input bytes and 128 output bytes) remote drop adds at least 20mS to the bus scan. The table below shows the bus scan time contribution, at each baud rate, for remote drops with a total of 16, 32, 64, 128, and 256 bytes (fully–loaded), when the Remote I/O Scanner receives outputs from only one bus controller at a time.
Contribution time in mS at each baud rate *
Remote Drop
16 bytes 2.09 2.16 3.83 7.16 32 bytes 3.24 3.31 6.12 11.74 64 bytes 5.52 5.60 10.69 20.89 128 bytes 10.10 10.17 19.85 39.20 256 bytes (fully–loaded) 19.25 19.32 38.15 75.80
* See below to calculate the exact scan time contribution for the application.
153.6 Kb std
153.6 Kb ext
76.8 Kb 38.4 Kb
Estimating Bus Scan Time for Remote I/O Drops
The scan time contribution for a remote drop depends on its I/O data usage. Follow the procedure below to estimate the the scan time contribution of a remote drop. (Each analog channels is 2 bytes. Eight discrete points are one byte).
1. Find the total number of input bytes and output bytes. number of input bytes = ________
number of output bytes = ________ total bytes = ________
2. With this total, calculate a scan time contribution using the formula below that
corresponds to the Genius bus baud rate.
Formula for 153.6 Kbaud Standar d:
0.943mS + (0.0715 x total bytes) = ________ mS
Formula for 153.6 Kbaud Extended:
1.015mS + (0.0715 x total bytes) = ________ mS
Formula for 76.8 Kbaud:
1.538mS + (0.143 x total bytes) = ________ mS
Formula for 38.4 Kbaud:
2.583mS + (0.286 x total bytes) = ________ mS
Other devices on the bus, including the Bus Controller, Hand–held Monitor, and I/O blocks also add to the bus scan time. The Genius I/O System Manual (Volume 1) shows how to calculate bus scan time based on the devices actually present.
Series 90–70 Remote I/O Scanner User’s Manual – July 199212

Number of R emote Drops on a Bus

The number of remote drops on a bus depends on the baud rate and the total number of I/O points in the remote drops.
Since the maximum Genius bus scan time is 400mS, and the bus scan time contribution of one fully–loaded remote drop is 20mS, only twenty fully–loaded remote drops are supported on a single bus that operates at 153.6 Kbaud. If remote drops are not fully–loaded, more may be used on a bus operating at these baud rates.
If some remote drops are not fully–loaded, more than the maximum number given below can be used. The table in appendix A will help you estimate the total number of remote drops and data bytes that can be accommodated on a bus that has one Bus Controller, one Genius Hand–held Monitor, no datagrams or Global Data communications, and no Genius I/O blocks. The Genius I/O System User’s Manual explains how to calculate the bus scan time for a specific bus.
Maximum Number of Drops per Baud Rate
153.6K baud extended: Up to 20 fully–loaded drops, or up to 30 drops with the total
number of I/O bytes less than the limits listed in the table.
1
153.6K baud standard: Up to 20 fully–loaded drops, or up to 30 drops with the total
number of I/O bytes less than the limits listed in the table.
76.8K baud: Up to 10 fully–loaded drops, or up to 30 drops with the total number of
I/O bytes less than the limits listed in the table.
38.4K baud: Up to 5 fully–loaded drops, or up to 14 drops with the total number of
I/O bytes less than the limits listed in the table.
13Chapter 1 Introduction
1

Redundancy

The Remote I/O Scanner can be used with CPU redundancy, bus redundancy, or both. The suitability of redundancy features for any system depends on the requirements of the application. For Series 90–70 PLC CPUs that are release 3 and earlier, some types of redundancy are not supported.
CPU Redundancy
Genius devices are considered to be controlled by the Bus Controller that sends them outputs. In CPU redundancy, two Bus Controllers on the same bus can send control outputs at the same time. The Bus Controllers must use Device Numbers 30 and 31.
BUS
CONTROLLER
(DEVICE 30)
BUS
CONTROLLER
(DEVICE 31)
S
P
C
S
A N N E R
REMOTE DROP
a44876
Both Bus Controllers automatically receive inputs and fault reports from all devices on the bus that have been configured as being in “CPU Redundancy“ mode.
How the two sets of outputs are handled by devices that receive them depends on whether the devices are set up for Hot Standby or Duplex redundancy. Both are explained below . If the remote drop contains any analog modules, the only form of CPU
redundancy permitted is Hot Standby .
Hot Standby CPU Redundancy
A device configured to be in Hot Standby redundancy mode is normally controlled by the Bus Controller assigned to Device Number 31. If no outputs are available from that Bus Controller for a period of three bus scans, the device accepts outputs from the Bus Controller assigned to Device Number 30. If outputs are not available from either Bus Controller, outputs go to their configured defaults or hold their last state. In Hot Standby redundancy, Device Number 31 always has priority, so that when that Bus Controller is on–line, it has control of the outputs.
Duplex CPU Redundancy
A device configured to be in Duplex redundancy mode compares the outputs it receives from the two bus controllers, to determine whether they match. If corresponding outputs are the same, the device sets the output to that state. If corresponding outputs are not the same, the device sets the output to its configured ON or OFF Duplex Default State. If either Bus Controller stops sending outputs to a device, its outputs are directly controlled by the remaining device. Only discrete devices
can operate in Duplex redundancy mode; do not use Duplex mode if the analog drop contains any analog modules.
Series 90–70 Remote I/O Scanner User’s Manual – July 199214
1
Genius Bus Redundancy
In Genius bus redundancy, there are two bus cables each connected to a Bus Controller. The device communicates on only one bus at a time. Before the alternate bus can be use for communications, a bus switchover must occur and the device must “log in“ with the Bus Controller(s) on the alternate bus. Bus switching can be handled by a Bus Switching Module attached to a Genius block, or by a Remote I/O Scanner (IC697BEM733 rev. B or later) which contains a built–in bus switching relay. Bus Switching Modules and Remote I/O Scanners are the only devices that can be directly connected to redundant bus cables.
Bus Stubs Connect Other Devices to a Dual Bus
Other Genius devices, such as I/O blocks and additional Remote I/O Scanners, can be interfaced to a dual bus by short lengths of unterminated cable called a bus stubs. Typical arrangements are shown on the following pages. Up to seven devices can be installed on a bus stub (plus the device that is connected to the dual bus). Each device on a bus stub counts toward the total of 32 devices on the Genius bus.
The total length of all bus stubs on a bus should be 100 feet or less. Within each 20% section of the actual bus length, the total maximum stub length is 20 feet. This can be divided into shorter stubs, provided that the total length in each 20% of the bus is 20 ft. or less.
a44976
20% 20% 20% 20% 20%
10’ 10’
20’
COMBINED = 100 FEET MAXIMUM
= REMOTE I/O SCANNER OR BUS SWITCHING MODULE
20’
20’
For example, for a trunk cable 3000 ft. long, 20% of the trunk cable length is 600 ft. Therefore, 20 ft. of bus stub cable can be located within any 600 ft. section of the bus. There might be two 10 ft. stubs with up to 8 devices each, or four 5 ft. stubs, with fewer devices on each.
15Chapter 1 Introduction
1
Redundant Bus Configuations
Many different redundant bus configurations are possible. Three basic ways of using a Remote I/O Scanner with a redundant bus are described below.
H
A Remote I/O Scanner can be installed directly on both cables of the dual bus pair. The Remote I/O Scanner is configured to operate as a bus switching device in
addition to performing its normal remote drop functions. Here, two single–rack remote drops are installed on a dual bus. The Remote I/O
Scanner in each remote drop would be set up as a bus switching device.
a44974
BUS A
BUS B
RACK 0
P
S
S
C A N N E R
P S
RACK 0
S C A N N E R
A bus stub may be connected to a Remote I/O Scanner that is configured as a bus switching device, allowing up to seven additional devices to utilize its bus switching action. Devices on a bus stub are independent Genius devices. When bus switching is controlled by a Remote I/O Scanner , as shown below, the devices on the bus stub are not part of the remote drop. Their data does not count toward the remote drop’s data total.
a44878 RACK 0 RACK 0
P
BUS A
S
S
C
A N N
E R
P
S
S
C A N N E R
BUS B
BUS
STUB
UP TO 7 ADDITIONAL DEVICES
Series 90–70 Remote I/O Scanner User’s Manual – July 199216
H
A Remote I/O Scanner can be located on a bus stub. The bus switching device to which the bus stub is connected can be another Remote I/O Scanner, as shown below, or a Genius block with a Bus Switching Module attached.
In this example, there are two remote drops installed directly on a dual bus. A third remote drop and some Genius blocks are installed on a bus stub connected to one of the Remote I/O Scanners. That Remote I/O Scanner acts as the bus switching device. A remote drop on a bus stub can accommodate up to 128 bytes of inputs and 128 bytes of outputs, and may include expansion racks.
1
RACK 0
P
S
S
C A N N E R
BUS A
BUS B
P
BUS
STUB
H
Finally, a remote drop can be located on just one bus of a redundant bus pair, if
S
RACK 0
S C A N N E R
P S
RACK 0
S C A N N E R
a44880
bus redundancy is not needed for the modules in that remote drop. In this example, the remote drop on the right is connected to both Bus A and Bus
B; the remote drop on the left, which contains non–critical I/O modules, is connected to Bus A only.
RACK 0
RACK 0
a44877
BUS A
BUS B
P
S
S
C A N N E R
P
S
S
C A N N E R
17Chapter 1 Introduction
1

Configuration

A remote drop can be fully configured using Logicmaster 90–70, or automatically configured using a Genius Hand–held Monitor. Differences between the two methods are explained below. Optionally, a previously–configured remote drop can be reconfigured using datagrams.
Remote Drop Configuration with Logicmaster 90–70
Logicmaster 90–70, release 3.0 or later can be used to configure a remote drop for any type of host. Either serial or parallel Logicmaster can be used. For serial Logicmaster, the connection to the remote drop can be direct, or via a multidrop network. Direct
connection or a Hand–held Monitor is needed to configure the SNP ID of the remote drop, before multidrop communications with it are possible.
Logicmaster 90–70 release 4.01 or later, which provides reference checking through the use of a common folder, is preferred for configuring a Series 90–70 PLC with remote drops. Chapter 4 explains how to configure a remote drop using Logicmaster 90–70 software which is Release 4 or later.
Appendixes C and D give instructions for configuration using Release 3 Logicmaster 90–70 software.
Remote Drop Configuration with a Genius Hand–held Monitor
A Genius Hand–held Monitor , version 4.0 (IC660HHM501G) or later, can be used to configure a remote drop that does not include Analog Expander modules. If Analog Expanders are present, Logicmaster 90 must be used for configuration.
The I/O modules in the remote drop cannot be individually configured with a Hand–held Monitor; they will operate in default mode. HHM configuration instructions are given in chapter 6.
Configuring a Remote Drop using Datagrams
The configuration of a remote drop can be completed or changed by sending it datagrams, as shown in the table on the following page. The Write Map datagram will supply Series 90–70 data types and lengths, and a Series 90–70 SNP ID for the remote drop.
Series 90–70 Remote I/O Scanner User’s Manual – July 199218

Configurable Features

The following table summarizes configuration options for a remote drop, and compares them to the PLC configuration required with a remote drop. The remote drop can be configured, or reconfigured, using Logicmaster 90–70 or a Genius Hand–held Monitor, or datagrams. If the configuration is not protected, as explained on the next page, a reconfiguration will replace part or all of an existing configuration, regardless of the configuration method originally used.
Remote Drop Configuration
Configuration Item
Logicmaster
90–70
Hand–held
Monitor
Datagrams
1
Device Number (SBA) Series 90–70 References Data Lengths Series Six/Series Five References Baud Rate
Bus Controller Options:
Input Default Outputs Enabled
I/O Module Options:
Input Filter Time Outputs Default V oltage/Current Range Analog Expander Modules PCM*, GDS*, ADS*
Genius Options:
BSM Controller * BSM Present * Timeout Select * CPU Redundancy * Duple x Default * Configuration Protection
SNP P ort Options:
SNP ID W rite Map Baud Rate Stop Bits Modem TT Idle Time
n[ n
n[ n
n[ n n[ n
n
n n
n n n n n
n n n n n n n n n n
] n
n n n n n
W rite Map W rite Map
Remote I/O Scanner Sweep Control:
Programmer Window Communications Window
[
with release 3 software, PLC configuration must match the remote drop configuration.
Only for a new Remote I/O Scanner , for which no Series Six/Series Five reference has been entered. * Not approved for use with Remote I/O Scanner version IC697BEM733A;
upgrade to IC697BEM733B or later .
]
Automatically supplied.
n n n n
19Chapter 1 Introduction
1

Configuration Protection

After configuring a Remote Drop, it is important to prevent inadvertent change while the system is in operation. For this reason, Logicmaster 90–70 automatically protects any configuration you download to a Remote I/O Scanner.
A configuration done with a Hand–held Monitor should be protected as described in chapter 6.
Any Hand–held Monitor used with the system while it is operating should be set up to prevent undesirable configuration changes:
Protect These Remote Drop Fea -
tures
Device Number (SBA) Change Block ID Disabled Reference Address Data Lengths (%I, %Q, %AI, %AQ) Remote Drop ID Module Options: Output Defaults
Input Filter T ime V oltage Range Baud Rate Change Block Baud Disabled Configuration Protection
Redundancy Options *
By Setting this HHM Option
Change Block Config Disabled
* Not available with Remote I/O Scanner version IC697BEM733A.
To prevent access to restricted HHM configuration options, remove the HHM key.
Caution
If configuration protection is removed from the Remote I/O Scanner and the Hand–held Monitor’s Change Block ID option is ENABLED, the HHM’s automatic configuration capability can overwrite any existing I/O configuration, including one created using Logicmaster 90–70, or downloaded using a Write Map datagram.
This automatic reconfiguration will also set any module options (see the table above) back to their defaults.
Series 90–70 Remote I/O Scanner User’s Manual – July 199220

Chapter 2 Installation

section level 1 1
2
This chapter describes procedures for installing the racks and modules in a remote drop, grounding equipment, connecting the Genius bus, completing SNP connections, and attaching a programmer.

Hardware Packaging

Each Series 90–70 rack is shipped in its own carton, without a power supply. The power supply and all of the Series 90–70 modules are shipped in individual boxes. When multiple modules are included in one shipment, individual module boxes are packaged either two, five or ten boxes to a carton.
Verify that all components of the system have been received and that they agree with your order. If the items received do not agree with your order, call Programmable Control Customer Service, toll free, in Charlottesville, V A at 1–800–432–7521. A Customer Service representative will assist you.
figure bi level 1 table_big level 1

Preinstallation Check

Carefully inspect all shipping containers for damage during shipping. If any part of the system is damaged, notify the carrier immediately. The damaged shipping container should be saved as evidence for inspection by the carrier.
As the consignee, it is your responsibility to register a claim with the carrier for damage incurred during shipment. However , GE F anuc will fully cooperate with you, should such action be necessary.
After unpacking the Series 90–70 PLC racks, modules, and other equipment, record all serial numbers. Serial numbers are required if you should need to contact Product Service during the warranty period of the equipment. Complete all software product registration cards, and return them to to GE Fanuc.
All shipping containers and all packing material be saved should it be necessary to transport or ship any part of the system.
21
2

System Grounding Procedures

All components of a control system and the devices it is controlling must be properly grounded.
H
Ground conductors should be connected in a tree fashion with branches routed to a central earth ground point. This ensures that no ground conductor carries current from any other branch. This method is shown in the figure shown below.
H
Ground conductors should be as short and as large in size as possible. Braided straps or ground cables (typically green insulation with a yellow tracer – AWG #12 or larger) can be used to minimize resistance. Conductors must always be large enough to carry the maximum short circuit current of the path being considered.
SERIES 90–70
PLC CABINET
PROGRAMMING
DEVICE
RACK
RACK
MOTOR DRIVES
AND
OTHER
ELECTRICAL
CONTROL
EQUIPMENT
a42942
MACHINERY
EARTH
GROUND
CENTRAL
GROUND POINT
NOTE
SIGNAL AND POWER
CONNECTIONS
NOT SHOWN
Series 90–70 Remote I/O Scanner User’s Manual – July 199222

Rack Installation

Î
Î
Install the rack(s) in the orientation shown below. The illustration shows a 9–slot rack, but a 5–slot rack could be used.
Series 90–70 PLC racks may be rack or panel mounted, depending on version ordered. Rack dimensions for installation purposes are shown below.
The Series 90–70 rack does not require a fan as long as sufficient space is left around the rack for cooling airflow .
WITH OPTIONAL VME J2
BACKPLANE KIT
1.00
(25.4)
SPACER
(QTY.4)
=
9.14 (232)
7.25
(184)
CONNECTOR
FOR POWER SUPPLY
SIDE VIEW
I/O TERMINAL
RESTRAINING
STRAP
DIMENSIONS FOR 5 SLOT RACK
CABLE
ENTRANCE
FROM
BOTTOM
REMOVABLE
I/O
TERMINAL
BLOCK
Î
Î
Î
Î
HINGED
DOOR
DIMENSIONS IN INCHES, MILLIMETERS ARE IN PARENTHESIS
12.60
6.75
(172)
2.24 (57)
6.00
**
(152.4)
.45 (11)
*
.75 (19)
GROUND
STUD
SUPPLY
19.00 (483)
123456789POWER
(320)
18.11 (460)
11.71 (297)
17.04 (433)
FRONT VIEW
ALLOW SUFFICIENT HORIZONTAL CLEARANCE FOR ACCESS TO GROUND STUDS
*
AT EACH END OF THE RACK. IF THE EXTENSION CABLE IS USED, ALLOW APPROXIMATELY 6 INCH HORIZONTAL
**
CLEARANCE ON THE LEFT SIDE OF THE RACK FOR ACCESS TO THE CONNECTOR. ALLOWANCE FOR COOLING ( If REQUIRED FOR ADDITIONAL COOLING, RACK FAN
***
ASSEMBLY (IC697ACC721 IS AVAILABLE. )
10.64 (264)
*
GROUND
STUD
.25 DIA.
(TYPICAL)
2
10.47 (266)
a42139
6.00
***
(152.4)
11.50 (292)
6.00
***
(152.4)
23Chapter 2 Installation
Loading...
+ 124 hidden pages