GE EP 700T, EP 1000T, EP 2000T, EP 3000T, EP 6000T User Manual

...
--
1. SAFETY INSTRUCTIONS
Condensation may occur if the UPS is moved directly from a cold to a warm
environment. The UPS must be absolutely dry before being installed. Please allow an acclimatization time of at least two hours.
Do not install the UPS near water or in damp environment. Do not install the UPS where it would be exposed to direct sunlight or near heat. Do not block ventilation openings in the UPSs housing. Do not connect appliances or items of equipment which would overload the UPS
(e.g. laser printers, etc) to the UPS outlet sockets.
Place cables in such a way that no one can step on or trip over them.
Installation for EP 700/1000/2000/3000
Socket-outlets and socket of batteries are earthed by the input power cord, please
insert the power cord into mains socket before using of UPS.
Connect the UPS only to an earthed shockproof socket outlet. The building wiring socket outlet (shockproof socket outlet) must be easily
accessible to close to the UPS.
This is operator installable.
Installation for EP6000
UPS has provided earthed terminal, in the final installed system configuration,
equipotential earth bonding to the external UPS battery cabinets.
An integral single emergency switching device which prevents further supply to the
load by the UPS in any mode of operation should be provided in the building wiring installation.
An appropriate disconnect device as short-circuit backup protection should be
provided in the building wiring installation.
For three-phase equipment connection to an IT power system, a four-pole device
which disconnect all phase conductors and the neutral conductor should be provided in the building installation wiring.
This is permanently connected equipment , it must be installed by qualified
Please read the FOLLOWING user manual and the safety instructions before installing the unit and starting it up!
--
maintenance personnel.
Earth connection essential before connecting to the building wiring terminal.
1.2 Operation
Do not disconnect the mains cable on the UPS or the building wiring socket
(grounded shockproof socket) during operation as this would remove the ground to the UPS and of all connected loads.
The UPS output socket or output terminal block may be electrically lived even if the
UPS system is not connected to the building wiring terminal.
In order to fully disconnect the UPS, first press the Standby button, then disconnect
the mains lead.
Ensure that no liquid or other foreign objects can enter the UPS. The UPS can be operated by any individuals with no previous experience.
1.3 Maintenance, servicing and faults
The UPS operates with hazardous voltages. Repairs may be carried out only by
qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains
power supply (building wiring socket), components inside the UPS are still connected to the battery which are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the
batteries. Verify that no current is present and no hazardous voltage exists in the capacitor or BUS capacitor terminals.
Batteries must be replaced only by qualified personnel. Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the ground. Verify that no voltage is present before servicing!
Batteries have a high short-circuit current and pose a risk of shock. Take all
precautionary measures specified below and any other measures necessary when working with batteries:
remove all jewellery, wristwatches, rings and other metal objects use only tools with insulated grips and handles.
When changing batteries, replace with the same quantity and the same type of
batteries.
-3-
Do not attempt to dispose of batteries by burning them. It could cause explosion. Do not open or destroy batteries. effluent electrolyte can cause injury to the skin
and eyes. It may be toxic.
Please replace the fuse only by a fuse of the same type and of the same amperage
in order to avoid fire hazards.
Do not dismantle the UPS, except the qualified maintenance personnel.
1.4 Transport
Please transport the UPS only in the original packaging (to protect against shock
and impact).
1.5 Storage
The UPS must be stockpiled in the room where it is ventilated and dry.
--
2. DESCRIPTION OF COMMONLY USED NOTATIONS
Some or all of the following Notations may be used in this manual and may appear in your application process. Therefore, all users should be familiar with them and understand their explanations.
Notation and Explanation
Notation Explanation Notation Explanation
Alert you to pay special attention
Protective ground
Caution of high voltage
Alarm silence
Turn on the UPS
Overload indication
Turn off the UPS
Battery
Idle or shut down the UPS
Recycle
Alternating current source (AC)
Do not dispose with ordinary trash
Direct current source
Refer to manual
--
3. INTRODUCTION –EP700/1000/2000/3000/6000
This On-Line-Series is an uninterruptible power supply incorporating double-converter technology. It provides perfect protection specifically for Novell, Windows NT and UNIX servers.
The double-converter principle eliminates all mains power disturbances. A rectifier converts the alternating current from the socket outlet to direct current. This direct current charges the batteries and powers the inverter. On the basis of this DC voltage, the inverter generates a sinusoidal AC voltage, which permanently supplies the loads.
Load like computers and periphery are thus powered entirely by the mains voltage. In the event of power failure, the maintenance-free batteries power the inverter.
This manual covers the UPS listed as follows. Please confirm whether it is the model you intend to purchase by performing a visual inspection of the Model No. on the rear panel of the UPS.
Model No. Type
EP 700T EP 1000T EP 2000T EP 3000T EP 6000T
Tower Model
EP 700LRT EP 1000LRT EP 2000LRT EP 3000LRT EP 6000LRT
Tower Model with Long backup time
EP 700R EP 1000R EP 2000R EP 3000R EP 6000R
Rack Model
--
4. SYSTEM DESCRIPTION – EP700/1000/2000/3000/6000
Switch Function
ON - Switch
Turn on UPS system: By pressing the ON-Switch ON the UPS system is turned on. Deactivate acoustic alarm: By pressing this switch an acoustic alarm can be deactivated.
OFF-Switch
When mains power is normal and Bypass is enable, the UPS system switches to Standby mode by pressing OFF-Switch OFF. It is then switched to Bypass and the inverter is off. At this moment, maybe the output sockets are supplied with voltage via the bypass if the mains power is available and bypass is enable.
When UPS is on battery mode, pressing OFF-Switch OFF will shutdown UPS.
EP700T/700LRT/1000T/1000LRT/2000T/2000LRT
/3000T/3000LRT/6000T/6000LRT
EP700R/1000R/2000R/3000R/6000R
--
Display Function
AC INPUT LED
The green AC INPUT LED lights up if mains voltage is applied to the UPS input. AC INPUT LED blinks when the phase and neutral conductor have been
reversed at the input of the UPS system. If AC INPUT LED and BATTERY LED light up, the mains power supply is out of
tolerance.
BATTERY LED
The orange-coloured BATTERY-LED lights up when the mains power has failed and the inverter is being powered by the batteries.
BYPASS LED
The orange-coloured BYPASS LED lights up when the UPS system is supplying voltage provided by the mains power via the bypass.
UPS ON LED
The green-coloured UPS ON LED lights up if the UPS system is supplying voltage provided by the mains power via the inverter.
ALARM LED
The red ALARM LED lights up and an acoustic warning signal is issued continuously when the UPS system is in fault condition. Press the OFF switch in order to turn off the warning tone.
Display Function
LOAD and
BATTERY
CAPACITY
LEDs(#2~#6)
(For
EP700/1000/2000
/3000)
These LEDs show the load of the UPS system if the mains power is available (normal operation): 2nd LED: 96%-108% 3rd LED: 71%-95% 4th LED: 51%-70% 5th LED: 31%-50% 6th LED: 0-30%
In the battery operation, the LEDs indicate the capacity of the batteries: 2nd LED: 100% 3rd LED: 76%-100% 4th LED: 51%-75% 5th LED: 26%-50% 6th LED: 0-25%
LOAD and
BATTERY
CAPACITY
LEDs(#2~#6)
(For EP6000)
These LEDs show the load of the UPS system if the mains power is available (normal operation): 2nd LED: 96%-105% 3rd LED: 76%-95% 4th LED: 56%-75% 5th LED: 36%-55% 6th LED: 0-35%
In the battery operation, the LEDs indicate the capacity of the batteries: 2nd LED: 81%-100% 3rd LED: 61%-80% 4th LED: 41%-60% 5th LED: 21%-40% 6th LED: 0-20%
--
5. CONNECTION AND OPERATION – EP700/1000/2000/3000
5.1 Inspection: Inspect the packaging carton and its contents for damage. Please inform
the transport agency immediately should you find signs of damage. Please keep the packaging in a safe place for future use.
Note: Please ensure that the incoming feeder is isolated and secured to prevent it from
being switched back on again.
5.2 Connection:
1) UPS Input Connection
If the UPS is connected via the power cord, please use a proper socket with protection against electric current, and pay attention to the capacity of the socket: over 7A for EP 700/1000, over 12A for EP 2000 and over 16A for EP 3000.
2) UPS Output Connection
The output of EP 700/1000/2000/3000 are socket-types only. Simply plug the load power cord to the output sockets to complete connection.
Model No. Output Socket (pcs)
EP 700 4 EP 1000 4 EP 2000 6 for Tower & 4 for Rack EP 3000 6 for Tower & 2 for Rack
3) Computer Connection:
Connect your load to the outlet sockets of the UPS system directly.
5.3 Battery Charge: Fully charge the batteries of the UPS system by leaving the UPS system connected to the mains for 1-2 hours. You may use the UPS system directly
The system may be installed and wired only by qualified electricians in accordance with applicable safety regulations!
When installing the electrical wiring, please note the rated current
of your
incoming feeder
Caution!
Do not connect equipment which would overload the UPS system (e.g. laser printers)
--
without charging it but the stored energy time may be shorter than the nominal value specified.
5.4 Turn On the UPS:
1) With utility power connecting:
Press ON button continuously for more than 1 second to turn on the UPS. Then the UPS will get into self-test status first. After having finishing the self-test, the UPS will get into the inverter mode, at this time, the AC INPUT LED, Inverter LED, and Load and Battery Capacity LEDs will light up.
2) Without utility power connecting:
Even though utility power is not connected to the UPS, the UPS still can be turned on by just simply pressing ON button continuously for more than 1 second. Then the UPS will get into self-test status first. After having finishing the self-test, the UPS will get into the inverter mode, at this time, Battery LED, Inverter LED, Load and Battery Capacity LEDs will light up.
Note: The default setting for bypass mode is no output after UPS is connecting utility
power and breaker is turned on. This can be configured by monitoring software.
5.5 Test Function:
Test the function of the UPS system by either pressing the On button or disconnecting the input of the UPS system from the power supply.
5.6 Turn Off the UPS:
1) In Inverter Mode:
Press OFF button continuously for more than 1 second to turn off the UPS. Then the UPS will get into LED self-test status first. After having finished the self-test, the UPS will get into Standby mode (or Bypass mode if Bypass enable) and the AC INPUT LED (and Bypass LED if Bypass enable) will light up. At this time, the UPS might has output (if Bypass enable). Disconnect the utility power to turn off the output.
2) In Battery Mode:
Press OFF button continuously for more than 1 second to turn off the UPS. Then the UPS will get into self-test status first. After having finished the self-test, the UPS will be turned off completely.
5.7 Audible Alarm Mute Function: If the alarm is too annoying in battery mode, you
may press ON button continuously for more than 1 second to clear it. Moreover, the alarm will be enabled when the battery is low to remind you to shutdown the load soon.
-10-
5.8 Operation Procedure of External Battery
1) Use the battery pack with voltage: 36VDC for EP 700/1000 (3 pcs of 12V batteries), 96VDC for EP 2000/3000 (8 pcs of 12V batteries). Connection of batteries more than or less than required will cause abnormality
2) One end of the external battery cord is a plug for connecting the UPS and the other end has a plug for connecting the user battery cabinet
3) (Do not connect the UPS to any load at this time). Then, connect the power cord of the UPS to supply utility power to the UPS to make the UPS operate in utility power mode.
4) Connect the plug of the external battery cord to the external battery socket on the rear panel of the UPS to complete the connection procedure and the UPS will start to charge the battery pack.
Caution!
The output sockets of the UPS system may still be electrically live even if the power
supply system has been disconnected.
-11-
6. TROUBLE SHOOTING - EP700/1000/2000/3000
If the UPS system does not operate correctly, please attempt to solve the problem using the table below.
Problem Possible cause Remedy
No indication, no warning tone even though system is connected to mains power supply
No input voltage
Check building wiring socket outlet and input cable.
AC INPUT LED blinks
Phase and neutral conductor at input of UPS system are reversed
Rotate mains power socket by 180° or connect UPS system.
AC INPUT LED blinks and BATTERY-LED lights up
Input power and/or frequency are out of tolerance
Check input power source and inform seller if necessary
AC INPUT and BYPASS LED light up even though the power supply is available
Inverter not switched on
Press On-Switch ON
UPS ON LED lights up, and audible alarm sounding every 1 beep in every 4 seconds
Mains power supply has failed
Switching to battery mode automatically. When audible alarm sounding every second, battery capacity is low.
ALARM LED lights, warning tone once a second
Overload Remove loads from UPS output.
ALARM LED lights up, permanent warning tone
UPS fault Notify seller!
Emergency supply period shorter than nominal value
Batteries not fully charged / batteries defect
Charge the batteries for at least 3 hours and then check capacity. If the problem still persists, consult seller.
ALARM LED lights, BATTERY-LED blinks, warning tone once a second
Charger or Batteries damaged
Notify seller !
Please have the following information at hand before calling the After-Sales Service Department:
Model number, serial number
Date on which the problem occurred
Detailed description of the problem
-12-
7. MAINTENANCE - EP700/1000/2000/3000
7.1 Operation
The UPS system contains no user-serviceable parts. If the battery service life (3 - 5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case please contact seller.
7.2 Storage
If the batteries are stored in temperate 20°C~25°C, they should be charged every three months for 1-2 hours. You should shorten the charging intervals to two months at
locations subject to high temperatures.
-13-
8.TECHNICAL DATA - EP700/1000/2000/3000
8.1 Electrical specifications
INPUT
Model No. EP700 EP1000 EP2000 EP3000
Phase Single Frequency (46~54)Hz for 50Hz system & (56~64)Hz for 60Hz system Current(A) 7A 7A 12A 16A
OUTPUT
Model No. EP700 EP1000 EP2000 EP3000
Power rating(VA/W)
700/490 1000/700 2000/1400 3000/2100
Voltage
220/230/240VAC 2%
Frequency
50/60Hz ±0.2% (Battery mode)
Wave form Sine Wave
BATTERIES
Model No. EP700 EP1000 EP2000 EP3000
Number and type
3×12V 7.2Ah 3×12V 7.2Ah 8×12V 7.2Ah 8×12V 7.2Ah
8.2 Operating Environment
Operating Temperature
0 oC to 40 oC(20°C~25°C recommended)
Operating humidity < 95%
Altitude < 1000m
Storage temperature -15 oC ~ 40 oC
Note: if 1000m < Altitude < 3500m (output derating: 1% derating per 100m )
8.3 Typical stored energy time (Typical values at 25°C in minutes:)
Model No. 100 % Load 50 % Load
EP700 5 10 EP1000 5 10 EP2000 5 10 EP3000 5 10
-14-
8.4 Dimensions and weights
Model No.
Dimensions W x D x H
(mm)
Net Weight
kg
EP700T 145X400X220 14
EP700LRT 145X400X220 7
EP700R 482X420X87 15
EP1000T 145X400X220 14
EP1000LRT 145X400X220 7
EP1000R 482X420X87 15
EP2000T 192 X460X340 34.5
EP2000LRT 192 X460X340 15
EP2000R 482X420X87 9.6
EP3000T 192 X460X340 35.5
EP3000LRT 192 X460X340 16
EP3000R 482X420X87 10
Battery pack 96V Rack 482X420X87 26
-15-
9. TECHNICAL DATA – EP6000
9.1 General Specification
Model EP6000 EP6000LRT EP6000R
Battery pack
(240V)
Power Rating
(VA/W)
6000/4200
Frequency (Hz) 50/60
Voltage (176-276)VAC
Input
Current 31A max.
Voltage 240VDC
Battery
Current 24A max
Voltage 220/230/240VAC
Output
Current 27A
Dimension (WxDxH)
mm
260x570x717 260x570x717
482.6X600X130 (3U)
482.6X600X130 (3U)
Net Weight (kg) 90 35 18.3 64.2
9.2 Electrical Performance
Input
Model Voltage Frequency Power Factor
EP6000 Single-phase
(46~54)Hz for 50Hz system (56~64)Hz for 60Hz system
>0.98 (Full load)
Output
Voltage
Regulation
Power Factor
Frequency
tolerance.
Distortion Overload capacity
Current
crest ratio
±2%
0.7 lag
Synchronized 46-54Hz in Line mode (AC mode)
±0.1% of normal frequency in Battery mode
THD<3% Full load (Linear Load)
105%-
130% load transfers
to bypass mode after 10 seconds
>130% load transfers to bypass mode after 1 second and shutdown the output after 1 minute
3:1
maximum
-16-
9.3 Operating Environment
Temperature Humidity Altitude Storage temperature
0°C~40°C
<95% <1000m
-15°C~40°C
Note: Output power is derated when UPS is above 1000m as following:
Altitude (M) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Derating Power 100% 95% 91% 86% 82% 78% 74% 70% 67%
-17-
10. INSTALLATION - EP6000
10.1 Unpacking and Inspection
1) Unpack the packaging and check the package contents. The shipping package contains:
l An UPS l An user manual l A communication cable (RS232) l A communication cable (USB) l A Software CD l SNMP card (optional) l Battery cable (long backup time model battery pack only)
2) Inspect the appearance of the UPS to see if there is any damage during
transportation. Do not turn on the unit and notify the carrier and seller immediately if there is any damage or lacking of some parts.
10.2 Input and output power cords and protective earth ground installation
1. Notes for installation
1) The UPS must be installed in a location with good ventilation, far away from water, inflammable gas and corrosive agents.
2) Ensure the air vents on the front and rear of the UPS are not blocked. Allow at least 0.5m of space on each side.
3) Condensation may occur if the UPS is unpacked in a very low temperature environment. In this case it is necessary to wait until the UPS is fully dried inside before proceeding installation and use. Otherwise there are hazards of electric shock.
2. Installation
Installation and wiring must be performed in accordance with the local electric code and the following instructions by professional person.
For safety, please cut off the mains power switch before installation.The battery breaker also needs to be cut off if it is a long backup time model (LRT model) or Rack model (R model).
1) Open the terminal block cover located on the rear panel of the UPS, please refer to the appearance diagram.
2) It is recommended to select the UL1015 10AWG(6mm2) wire or other insulated wire which complies with AWG Standard for the UPS input and
-18-
output wirings.
Note: Do not use the wall receptacle as the input power source for the UPS, as its
rated current is less than the UPSs maximum input current. Otherwise the receptacle may be burned and destroyed.
3) Connect the input and output wires to the corresponding input and output terminals according to the following diagram.
Note: you must make sure that the input and output wires and the input and
output terminals are connected tightly.
4) It is recommended to select the UL1015 10AWG(6mm2) green wire with yellow ribbon for protective earth ground wire.
5) After having completed the installation, make sure the wiring is correct.
6) Please install the leak current protective breaker at the output power distribution panel of the UPS if necessary.
7) To connect the load with the UPS, please turn off all the loads first, then perform the connection and finally turn on the loads one by one.
8) No matter the UPS is connected to the utility power or not, the output of the UPS may have electricity. The parts inside the unit may still have hazardous voltage after turning off the UPS. To make the UPS have no output, power off the UPS, and then disconnect the utility power supply.
9) Suggest charging the batteries for 8 hours before use. After connection, turn the input breaker in the ON position, the UPS will charge the batteries automatically. You can also use the UPS immediately without charging the batteries first, but the backup time may be less than the standard value.
10) If it is necessary to connect the inductance load such as a monitor or a laser printer to the UPS, the start-up power should be used for calculating the capacity of the UPS, as its start-up power consumption is too big when it is started.
Input and output Terminal Block wiring diagram of EP6000
-19-
10.3 Operating procedure for connecting the long backup time model UPS with the external battery
1) The nominal DC voltage of external battery pack is 240VDC. Each battery pack
consists of 20 pieces of 12V maintenance free batteries in series. To achieve longer backup time, it is possible to connect multi-battery packs, but the principle of same voltage, same type should be strictly followed.
2) The connector of the external battery cable is used to plug into the external
battery socket of the UPS, the other end of the external battery cable is used to connect with the external battery pack(s). The procedure of installing battery pack should be complied with strictly. Otherwise you may encounter the hazardous of electric shock.
a) Set the battery pack breaker in OFF position. b) You must connect the external battery cable to the battery first, if you
connect the cable to the UPS first, you may encounter the hazardous of electric shock. Then connect the other end to UPS.
3) To complete the connection by plugging the connector of the external battery cable into the external battery socket of the UPS. Do not attempt to connect any loads to the UPS now. You should connect the input power wire to the right position first. And then set the breaker of the battery pack in the ON position. After that set the input breaker in the ON position. The UPS begins to charge the battery packs at the time.
-20-
11. OPERATION AND OPERATING MODE – EP6000
It is easy to operate the equipment. Please read through this manual and operate according to the instructions in it.
Please refer to the appendix 2 for the meaning of the LED indicators.
11.1 Turn on the UPS with utility power supplied (in Line mode/AC mode)
1).After you make sure that the power supply connection is correct, set the bypass
breaker in the UPS position and input breaker in the ON position first. At this time the fan rotates, and the UPS operates in Bypass mode or in Standby mode.
2) To power on the UPS by simply pressing the ON button continuously for more
than 1 second.
3) When being powered on, the UPS will perform self-diagnosis, with the
load/battery level LEDs turned on and then off one after another in ascending order. A few seconds later, the UPS ON LED is turned on, the UPS is already running in Utility Power mode. If the utility power is abnormal, the UPS will operate in battery mode without output interruption of the UPS.
11.2. Turn on the UPS with no utility power supplied (in Battery mode)
1).For long back up time model (LRT model), please make sure that the battery
breaker is in ON position.
2) Press the ON button continuously for more than 1 second to power on the UPS.
3) During the course of starting up, the UPS has the same action as if it is connected
to utility power except that the utility power LED is not turned on and the battery LED is turned on instead.
11.3 Turn off the UPS with utility power supplied (in Line mode/AC mode)
1) Press the OFF button continuously for more than 1 second to turn off the inverter of the UPS immediately.
2) When being powered off, the UPS will perform self-diagnosis, the Load/Battery level LEDs will be turned on and then off one after another in ascending order, then the UPS ON LED will be turned off. The UPS will be working in Standby mode. But if Bypass is enable, bypass LED will be turned on and the UPS will be working in Bypass mode.
3) Upon completion of the above to turn UPS off, output of electric current of the UPS may be still present (Bypass mode). In order to cut off the output from the UPS, simply cut off the utility power supply and the UPS will perform self-diagnosis, finally no any display is shown on the display panel and no voltage
-21-
output is available from the UPS output.
11.4 Turn off the UPS with no utility power supplied (in Battery mode)
1) Press the OFF button continuously for more than 1 second to power off the UPS.
2) When being powered off, the UPS will perform self-diagnosis, the Load/Battery level LEDs will be turned on and then off one after another in ascending order. Finally no any display is shown on the display panel and no voltage is available from the UPS output.
Suggestions: Please turn off the connected loads before turning on the UPS and
turn on the loads one by one after the UPS is working in INV mode. Turn off all of the connected loads before turning off the UPS.
11.5. Backup time for the standard model
The backup time of the long backup time model is dependent on the external battery pack capacity and the load level as well as other factors.
The backup time of standard model may vary from different load level. Please refer to the following:
Backup time of EP6000
-22-
12. TROUBLE SHOOTING - EP6000
Problem Possible cause Solution
The #1 ALARM LED and the #6 LED are turned on, the buzzer beeps continuously.
The UPS transfers to fault mode due to internal overheat.
Make sure the UPS is not overloaded; the air vents are not blocked and the ambient temperature is not too high. Wait for 10 minutes for the UPS to cool down before turning on again. If failed, please contact the distributor or service center.
The #1 ALARM LED and the #2 and #5 LED are turned on, and the buzzer beeps continuously.
The UPS output is short circuited.
Remove all the loads. Turn off the UPS. Ensure that the load is not failed or the UPS has no internal faults before turning it on again. If failed, please contact the distributor or service center.
The #1 ALARM LED and the #4 LED are turned on, the UPS beeps continuously.
The UPS transfers to fault mode due to its internal fault.
Please contact the distributor or service center.
The #1 ALARM LED and the #5 LED are turned on, the UPS beeps continuously.
The UPS transfers to fault mode due to its internal fault.
Please contact the distributor or service center.
The AC INPUT LED flashes.
The voltage or frequency of the utility power is out of the input range of the UPS.
The UPS is running in battery mode. To save your data and close the application program. Make sure the utility power is within the input voltage or frequency range permitted by the UPS.
The #1 ALARM LED and the #2 LED are turned on, the UPS beeps continuously.
The UPS is overloaded or the load equipment is faulty.
Check the loads and remove all no-critical equipment. Recalculate the load power and reduce the number of loads connected to the UPS. Check that the loads are not failed.
The #1 ALARM LED is turned on, and the BATTERY LED is flashed, the buzzer beeps every second.
The charger of the UPS is defective.
Please contact the distributor or service center.
BATTERY LED flashes
Battery low or battery not connected.
Check the battery. If the battery is damaged, please contact the distributor or service center.
The utility power is normal, but the UPS can not turn in line mode
Maintain switch loose Please contact the distributor or service center. Battery not yet been fully
charged.
Keep UPS connected to utility power persistently for more than 10 hours to recharge the batteries again.
UPS overloaded.
Check the loads and remove the non-critical equipment.
Battery discharging time diminishes
Battery aged.
Replace the batteries. Please contact the distributor to obtain the parts and replacement service.
The ON button is pressed too briefly.
Press the ON button for more than 1 second.
The UPS is not connected to the battery or the battery pack voltage is too low.
Check the battery or recharge the battery.
The UPS cannot power on after pressing the ON button
UPS fault. Please contact the distributor or service center.
When you contact the service center, please provide the following information:
Model No. and the serial No. of the UPS
The date when the problem arose
Complete description of the problem, including the LED display, alarm warning, and power
condition and load capacity. If your UPS is a long backup time model, you may also provide the battery information.
-23-
13.NOTES FOR BATTERY DISPOSAL AND BATTERY REPLACEMENT
1) Before disposing of batteries, remove conductive object such as necklace, wrist
watches and rings.
2) If it is necessary to replace any connection cables, please purchase the original
materials from the authorized distributors or service centers, so as to avoid overheat or spark resulting in fire due to insufficient capacity.
3) Do not dispose of batteries or battery packs in a fire, they may explode.
4) Do not open or mutilate batteries, released electrolyte is highly poisonous and
harmful to the skin and eyes.
5) Do not short the positive and negative of the battery electrode, otherwise, it may
result in electric shock or fire.
6) Make sure that there is no voltage before touching the batteries. If the battery
circuit is not isolated from the input potential circuit, there may be hazardous voltage between the battery terminals and the ground.
7) Even though the input breaker is disconnected, the components inside the UPS are
still connected with the batteries, and there are potential hazardous voltages. Therefore, before any maintenance and repairs work is carried out, switch off the breaker of the battery pack or disconnect the jumper wire of connection between the batteries.
8) Batteries contain hazardous voltage and current. Battery maintenance such as the
battery replacement must be carried out by qualified personnel. No other persons should handle the batteries.
-24-
14. BATTERY MAINTENANCE
l This series UPS doesnt requires much maintenance. The battery used for
standard models are value regulated sealed lead-acid maintenance free battery. The only requirement is to charge the UPS regularly so as to maximize the expected life of the battery. When being connected to the utility power, whether the UPS is turned on or not, the UPS keeps charging the batteries and also offers the protective function of overcharging and over-discharging.
l The UPS should be charged once every 4 to 6 months if it has not been used for a
long time.
l In hot regions, the battery should be charged and discharged every 2 months. The
standard charging time should be at least 12 hours.
l Under normal conditions, the battery life lasts 3 to 5 years. In case if the battery is
found not in good condition, earlier replacement should be made. Battery replacement should be performed by qualified personnel.
l Replace batteries with the same number and same type of batteries. l Do not replace the battery individually. All the batteries should be replaced at the
same time following the instructions of the battery supplier.
l Normally, the batteries should be charged and discharged once every 4 to 6
months. Charging should begin after the UPS shuts down automatically in the course of discharging, the standard charging time for the standard UPS should be at least 12 hours.
-25-
15. OPERATING MODE FOR ALL MODELS
15.1 Utility power mode
The display panel in utility power mode is shown in the following diagram. The AC input LED and the UPS ON LED are turned on. The load level LEDs will be turned on in accordance with the load capacity connected.
1) The battery LED is turned on and the AC INPUT LED flashes, it indicates the voltage or frequency of the utility power has exceeded the normal range, the UPS operates in battery mode.
2) If output overloaded, the load level LEDs will be turned on and alarm will keep twice every second. You should get rid of some unnecessary loads one by one to decrease the loads connected to the UPS less than 90% of its nominal power capacity.
Note: Please follow the following steps to connect the generator
l Activate the generator and wait until the operation is stable before supplying
power of the generator to the UPS (be sure that the UPS is in idle mode, no load). Then turn on the UPS according to the start-up procedure. After the UPS is turned on, then the loads can be connected to the UPS one by one.
l The power capacity of the AC generator should be at least twice of the UPS
capacity.
15.2 Battery mode
The display panel in battery mode is shown in the following diagram Fig.15.2. The battery LED and the UPS ON LED are turned on. The displayed number of the battery level LEDs will be turned on in accordance with the battery capacity. Note that the load level LEDs in utility power mode will indicate the level of the battery capacity in battery mode instead.
1) When the UPS is running in battery mode, the buzzer beeps once every 4 seconds. If the ON button on the front panel is pressed for more than 1 second again, the buzzer will stop beeping (in silence mode). Press the ON button once
The utility power mode
-26-
again for more than 1 second to resume the alarm function.
2) When the battery capacity decreases, the number of the battery capacity LEDs turned on will be reduced. If the battery voltage descends to the alarm level, the buzzer will beep once every second to remind the users of insufficient battery capacity and the UPS is soon going to shut down automatically. Then the load operations should be carried out promptly and the loads should be eliminated one by one.
15.3 Bypass mode
The display panel in bypass mode is shown in the following diagram Fig 15.3. The AC INPUT LED and the bypass LED are turned on. The displayed number of the load LEDs will be turned on in accordance with the load capacity connected. The UPS will beep once every 2 minutes in bypass mode.
The AC INPUT LED flashes, it shows that the voltage or frequency of the utility power has exceeded the normal range of the UPS.
1Other indications on the display panel are
the same in utility mode.
2The UPS does not have the backup
function when it is in bypass mode. The power used by the load is supplied from the utility power via internal filter.
15.4 Abnormality mode
In case the fault LED is turned on when the UPS is in use, it shows that the UPS is operating in abnormal mode.
Battery mode diagram
UPS bypass mode diagram
Loading...
+ 89 hidden pages