Figure 2.1. EntelliGuard G Features and Characteristics ................................................................................................................. 4
STANDARD AND OPTIONAL FEATURES ....................................................................................................................................................... 5
Short Time Rating (1/2 Sec) ..................................................................................................................................................................... 5
Short Circuit/High Interruption Rating .............................................................................................................................................. 5
Two-Step Stored Energy Mechanism ................................................................................................................................................ 5
Field Installable Trip Units and Accessories ................................................................................................................................... 5
Breaker/Main Contact Status ................................................................................................................................................................ 6
Motor Operator ............................................................................................................................................................................................. 6
Ready to Close Indicator .......................................................................................................................................................................... 6
Breaker Status Indicators ........................................................................................................................................................................ 6
Carriage Position Switch .......................................................................................................................................................................... 7
IP Covers ........................................................................................................................................................................................................... 7
Bell Alarm Contact ....................................................................................................................................................................................... 8
Reliability without Compromising Protection ......................................................................................................................................... 9
Arc Flash and the EntelliGuard TU Trip Unit ............................................................................................................................................ 9
Figure 3.1. Arcing Current ...................................................................................................................................................................... 10
Selectivity with Molded case Circuit Breakers and Other Devices ............................................................................................ 10
DET-653C EntelliGuard® G Circuit Breaker Application Guide
24-May-12 Table of Contents
Above Other Power Circuit Breakers ........................................................................................................................................................ 15
Long Time Protection ................................................................................................................................................................................. 16
Thermal Long Time Overcurrent ................................................................................................................................................................ 16
Figure 3.3.
Table. 3.5.
Fuse-Shaped Steep Long Time Overcurrent ........................................................................................................................................ 17
Short Time Protection ....................................................................................................................................................................................... 19
Short Time Pickup ..................................................................................................................................................................................... 19
Short Time Bands ...................................................................................................................................................................................... 20
External Zero Sequence Input...................................................................................................................................................................... 21
Table 3.11. Max. Adjustable Instantaneous Pickup for CBs with Normal or Extended Range Option ......... 22
Table 3.12. Time Current Curves .......................................................................................................................................................
High Set Instantaneous Overcurrent (HSOIC) ...................................................................................................................................... 23
Making Current Release (MCR) ..................................................................................................................................................................... 23
Voltage Unbalance Relay ............................................................................................................................................................................... 30
Table 3.19. Relay Functions Available in EntelliGuard G CBs with EntelliGuard TUs ............................................. 30
Table 3.20. Voltage Unbalance Settings ....................................................................................................................................... 30
Thermal Characteristic: Max. and Min. Long Time Delay Bands for a 1000A Long Time Pickup ...... 16
Thermal Characteristic: Nominal Clearing and Commit Times for X Multipliers of Nominal Pickup 17
Characteristic: Max. and Min. Long Time Delay Bands for a 1000A Long Time Pickup ............. 17
Characteristic: Nominal Clearing and Commit Times for X Multipliers of Nominal Pickup ........ 18
Figure 3.5. Short Time Pickup .................................................................................................................................................... 19
Figure 3.6. Short Time Transition ............................................................................................................................................. 19
Table 3.7. Short Time Delay Bands ......................................................................................................................................... 20
Figure 3.7 Short Time Delay ....................................................................................................................................................... 20
Figure 3.8. Short I
2
t Slopes ................................................................................................................................................................................ 20
2
t (In or Out).................................................................................................................................................... 20
DET-653C EntelliGuard® G Circuit Breaker Application Guide
SECTION 4 – ACCESSORIES
24-May-12 Table of Contents
Current Unbalance Relay ................................................................................................................................................................................ 31
Table 3.21. Current Unbalance Settings ........................................................................................................................................ 31
Under Voltage Relay .......................................................................................................................................................................................... 31
Under Voltage Relay Zero-Volt Trip Enable ........................................................................................................................................... 31
Table 3.22. Under Voltage Settings .................................................................................................................................................. 31
Over Voltage Relay ............................................................................................................................................................................................. 31
Table 3.23. Over Voltage Settings ..................................................................................................................................................... 31
Power Demand Intervals ................................................................................................................................................................................. 31
Current Alarm ........................................................................................................................................................................................................ 31
Table 3.25 Input Assignments Possible .......................................................................................................................................... 32
Outputs for EntelliGuard G Circuit Breakers.......................................................................................................................................... 32
EntelliGuard Trip Unit Performance Characteristics Graphs ........................................................................................................ 33
Table 3.27. EntelliGuard Trip Unit Summary ................................................................................................................................ 33
Table 3.28. Metering Data Startup Levels for breaker with Entelliguard Trip Unit with 24 VDC ...................... 35
Table 3.29. Metering Data for breaker with Entelliguard Trip Unit without 24 VDC requires 20%
sensor current and then all metering will be available ............................................................................... 35
Figure 3.14. Long Time Circuit Breaker Characteristics ....................................................................................................... 36
Figure 3.15. Short Time Pickup and Delay Bands ..................................................................................................................... 37
Figure 3.16. Ground Fault: Multiple of Sensor ............................................................................................................................. 38
Motorized Spring Charging Unit .................................................................................................................................................................. 40
Table 4.1. Motor Operators .................................................................................................................................................................. 40
Circuit Breaker Closing Coils – Standard and Commanded ......................................................................................................... 40
Under Voltage Release with Fixed Time Delay .................................................................................................................................... 41
Time Delay Module for UVR (Externally Mounted) .............................................................................................................................. 42
Figure 4.2. Time Delay Module .......................................................................................................................................................... 42
Ready to Close Contact .................................................................................................................................................................................... 42
Table 4.8. Ready to Close Contacts (1NO) ..................................................................................................................................... 42
Table 4.15. Key Interlocks and Door Interlocks ......................................................................................................................... 44
Bell Alarm with Lockout ................................................................................................................................................................................... 47
Table 4.21. Bell Alarm Switches ......................................................................................................................................................... 47
Charging Spring Status Indicator ............................................................................................................................................................... 47
Table 4.23 Spring Charged Contact (1NO) ................................................................................................................................... 47
Table 4.25. Wiring Schematic for Block A ..................................................................................................................................... 47
Table 4.26. Wiring Schematic for Block B ..................................................................................................................................... 48
Table 4.27. Wiring Schematic for Block C ..................................................................................................................................... 48
Position Indicators ................................................................................................................................
Door Interlocks ..................................................................................................................................................................................................... 51
Table 4.32. Door Interlocks ................................................................................................................................................................... 50
Back Connected Terminations .................................................................................................................................................................... 51
Table 4.33. Back Connected Terminations for Cassette ....................................................................................................... 51
Table 4.34. Back Connected Terminations .................................................................................................................................. 53
Front Flat Terminations ................................................................................................................................................................................... 56
Table 4.35. Optional Front Flat Terminations ............................................................................................................................. 56
Table 4.37. Cluster Pad ........................................................................................................................................................................... 58
Terminations for DC Switches UL 489B .................................................................................................................................................. 59
Figure 4.35. Terminations for DC Switches UL 489B .............................................................................................................. 59
DET-653C EntelliGuard® G Circuit Breaker Application Guide
SECTION 5 – CATALOG NUMBERING GUIDE
SECTION 6 – APPLICATION DATA
SECTION 7 – PHYSICAL DATA
SECTION 8 – STANDARDS AND REFERENCES
24-May-12 Table of Contents
EntelliGuard G ANSI/UL489 Circuit Breaker Catalog Number Guide ....................................................................................... 60
EntelliGuard G Cassette Catalog Number Guide ................................................................................................................................ 68
EntelliGuard TU Trip Unit for EntelliGuard G Breaker ....................................................................................................................... 70
EntelliGuard TU Trip Unit Rating Plugs ..................................................................................................................................................... 72
Key Features .......................................................................................................................................................................................................... 73
UL1066 Low Voltage Power Circuit Breakers ............................................................................................................................. 73
UL498 Stored Energy Insulated Case Circuit Breakers .......................................................................................................... 73
IEC rated Circuit Breakers for IEC Equipment and Applications ....................................................................................... 73
All Types .......................................................................................................................................................................................................... 73
Ratings and Sizes ................................................................................................................................................................................................ 73
Short Circuit Interrupting Ratings ............................................................................................................................................................... 74
Figure 6.1. Short Circuit Rating Adjustment Equation ............................................................................................................ 74
Table 6.1. First Half-Cycle Peak at Specific Fault X/R Ratios ............................................................................................... 74
Withstand Ratings, Selective Adjustable-, RELT- and Override-Instantaneous Protection ......................................... 74
Close and Latch Ratings and Making Current Release (MCR) Instantaneous Trip............................................................ 75
Table 6.2. EntelliGuard G Circuit Breaker Close and Latch Ratings, UL489 Listed .................................................. 75
Table 6.3. EntelliGuard G Circuit Breaker Close and Latch Ratings, UL1066 Listed................................................ 75
Table 6.4. EntelliGuard G Non-Automatic Switch Close, Latch, and Withstand Ratings, UL489 Listed ....... 76
Selecting a Circuit Breaker for an Application ..................................................................................................................................... 76
Cable or Bus Size – Factor A .......................................................................................................................................................................... 76
Ambient Temperature – Factor B ............................................................................................................................................................... 77
Table 6.7. Ambient Temperature Rating – Factor B ................................................................................................................. 77
Operating Frequency – Factor C ................................................................................................................................................................. 77
Altitude – Factor D .............................................................................................................................................................................................. 77
Load Class Rating – Factor E ......................................................................................................................................................................... 77
Table 6.9. Load class Rating – Factor E .......................................................................................................................................... 78
Safety – Factor F .................................................................................................................................................................................................. 78
Other Factors that Influence Circuit Breaker Sizing 100% vs. 80% Ratings ........................................................................ 78
Table 6.10. Circuit Breaker and Trip Parameters ......................................................................................................................
Figure 7.1. Sample Dimensional Drawing: ANSI UL 489, 3Pole, Drawout, 2000A, Type E, M ............................. 79
Dimensional Drawing Index .......................................................................................................................................................................... 80
Table 7.1. Dimensional Drawing Index ........................................................................................................................................... 80
EntelliGuard G circuit breakers are the newest line of low voltage power circuit breakers (LVPCBs) evolved from the
exceptional designs and practices of GE legacy breakers. EntelliGuard G breakers offer a truly global product platform that
meets industry standards throughout the Americas, Europe and Asia (ANSI, UL, CSA, IEC, Lloyds Register of Shipping, etc.).
Breakers are available to OEMs in 3- and 4-pole designs from 400A to 6400A (IEC) with fault interruption ratings up to 150kA.
New, state-of-the-art EntelliGuard Trip Units enable the breakers with advanced technology that provides system
protection, local and remote monitoring, relaying and communications. EntelliGuard Trip Units may be supplied with either
Modbus or Profibus communications protocols. The breaker-trip unit system delivers superior circuit protection without
compromising selectivity or arc flash protection. The EntelliGuard system is yet another evolution of GE’s core competencies
in reliable electric power distribution, circuit protection and arc flash protection.
EntelliGuard G 3-pole breakers are the standard in GE AKD-20 Low Voltage Switchgear. The breakers are suitable for
280Vac, 480Vac and 600Vac applications, and they provide advanced circuit protection, limit arc fault energy and preserve
system coordination without sacrificing any of these critical functions (Table 1.1).
UL489B DC for
IEC 60947-3 IEC 68-2-52 Level 2: salt mist
CSA 22.2 NO 5.1
EntelliGuard G devices are available in all standard, 100% rated, ANSI, UL and IEC ratings in both fixed and draw-out
designs. Standard devices are also offered in 4 pole designs. No compromise (e.g., derating) is necessary in the system
protection scheme as the EntelliGuard G Neutral poles are fully rated. Front and rear access connections are available, and
all configurations can be manually or electrically operated with multiple and redundant accessories (optional) (Table 1.2).
EntelliGuard G short circuit and interrupting ratings are given in Tables 1.3 through 1.6.
4 Configurations available for 600V DC and 1000V DC with or without isolating both DC legs.
See Page 59 for Bus Bar Configurations.. Note: Bus Bars must be ordered separately.
Time Constant (L/R) = 15msec, Rated calibration temperature 50 degree C
ANSI C37 and UL 489 designs are 100% rated up to 40ºC when
applied in recommended enclosure sizes. IEC 60947 versions are
100% rated in free air up to 50ºC. IP31 enclosure/switchboard
rating is based on size, recommended up to 50ºC ambient with
rear vertical bus connection (Table 2.1).
EntelliGuard G devices can be fed from top or bottom terminals.
EntelliGuard G operates via stored energy mechanisms that can
Specified Cubicle
Minimum Specified Cubicle Ventilation - No of
be manually charged (MO) or electrically charged (EO) by the
Spring Charging Motor. Closing time is less than five cycles.
Closing and opening can be initiated remotely or via the front
cover push buttons. An Open-Close-Open cycle is possible
without recharging. (Charge after close). The breaker operating
mechanism is a trip-free mechanism and is furnished with an
integrated anti-pumping system.
EntelliGuard G devices have provisions for four accessory
operating coils. The four positions can be filled by the following
four devices: one Close Coil (CC) or one Command Close Coil (CCC),
one Shunt Trip Coil (ST), one Under Voltage Release (UVR), and the
fourth position can either be a 2nd ST Coil or a UVR. The Shunt
Trip and the UVR can also be replaced with a 120V Network
Interlock Device. The closing coil is a “one-shot” electronic closed
circuit. Shunt trip (ST) coils are continuous rated. (Note: No Red
Indicating Light on Shunt Trip) Under voltage relays (UVR) are
available with a fixed time delay (3 Cycles at down to 50% system
voltage; 1.2 Cycles below 50% system voltage). The time delay
module (TDM) is available as a shipped loose accessory for
remote installation (in equipment). Optional Coil Signaling contact
modules for the CC, CCC, ST, UVR, and NI's provide coil status
(energize/de-energize) via the secondary disconnects or trip unit
through Modbus or Profibus Comm.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
6
Coils
Breaker/Main Contact Status
Motor Operator
Electrical Closing Button
Ready to Close Indicator
Mounting Straps/Accessories
Auxiliary Switches
Interlocks
24-May-12 Section 2. Features and Characteristics
EntelliGuard G devices have provisions for four accessory
operating coils. The four positions can be filled by the following
four devices: one Close Coil (CC or CCC), one Shunt Trip Coil, one
UVR (Under Voltage Release), and the fourth position can either
be a Shunt Trip Coil or a UVR. The closing coil is a “one-shot”
electronic closed circuit. Shunt trip (ST) coils are continuous rated.
Under voltage relays (UVR) are available with a fixed time delay
(50ms at down to 50% system voltage; 20ms below 50% system
voltage). The time delay module (TDM) is available as a shippedloose accessory for remote installation (in equipment). Optional
status contact modules for the ST, CC and UVRs provide coil
status (energize/de-energize) via the secondary disconnects and
trip unit.
Heavy duty, motor/gearbox unit; easily accessible with a full
Four available designs:
Standard interlocks include:
OPEN/CLOSED, ON/OFF indication is provided on the front cover.
range of voltages.
Located on the front cover between the Open and Close button;
used to electronically close the breaker when a Command Close
Coil is selected.
Provides visible indication/readiness for close operation.
Kits are available to mount and connect fixed/stationary breakers
in either a rear connected (Vertical) or a front flat connected.
• Power rated (3NO+3NC) (Standard)
• Power rated (3NO+3NC) + low signal (Hi-Fi) (2NO+2NC)
• Power rated (8NO+8NC)
• Power rated (4NO+4NC) + low signal (Hi-Fi) (4NO+4NC)
• Drawout Breaker: prevents the breaker from being closed
unless it is in the TEST or CONNECT positions
• Drawout Breaker/Main Contacts: prevents withdrawal/removal
of the breaker unless the main contacts are OPEN. Access to the
drawout mechanism racking screw is blocked when the breaker
is CLOSED.
• Spring Discharge Interlock: Automatically discharges the
closing springs when the breaker is moved from the DISCONNECT
to the WITHDRAWN position. This prevents withdrawing a breaker
from the cubicle with the closing springs charged.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
7
Breaker Status Indicators
Rejection Feature
Through-Door Racking
Padlocking Devices
Key Interlock
Shutters
Carriage Position Switch
Lifting Beam
IP Covers
Mechanical Counter
24-May-12 Section 2. Features and Characteristics
A factory-installed rejection feature prevents mismatching
Up to four optional key interlocks are available (Kirk, Ronis,
Optional lockable shutters are available (factory installed).
Optional Lifting Beams/bars with separate slings are available for
Optional IP54 covers (protects against harmful amounts of dust
Standard Indicators include:
• The breaker status indicator shows the condition of the main
contacts (OPEN, CLOSED).
• The status of the closing springs is indicated as CHARGED or
DISCHARGED.
• The draw-out position indicator displays whether the breaker is
in the CONNECT, TEST or DISCONNECT position.
• The breaker also includes a switch that provides main contact
status indication to the POWER LEADER™ Power Management
System.
• The optional Reduced Energy Let-Through (RELT) is provided
with an ON/OFF contact closure to positively indicate whether the
RELT setting is enabled or not.
breakers and cassettes/substructures. This prevents (a) inserting
a breaker with a lower interrupting rating into a higher rated
cassette/substructure and (b) inserting a higher current rated
breaker into a lower rated cassette/substructure.
The breaker racking mechanism is accessible through the front of
the cassette and permits safely disconnecting/withdrawing the
circuit breaker without opening the door and exposing personnel
to live parts during the process.
The padlocking device is standard on breakers and allows up to
three padlocks with 1/4" to 3/8" diameter shanks to secure the
breaker in the OPEN/TRIP FREE position. A padlock provision on
the front panel of the cassette/substructure permits locking
access to the racking screw. Racking access can be locked with
the breaker in the CONNECT, TEST, DISCONNECT position with up
to three padlocks.
Profalux, Castell). Switchgear applications utilize a Kirk key
interlock mounted in the cassette. A maximum of two key
interlocks may fit in the cassette.
This optional cassette/substructure device permits local or
remote indication of the circuit breaker status (CONNECTED, TEST,
DISCONNECTED), 2NO/2NC single pole, double throw contacts are
available for each position.
all breaker sizes. A Universal Lifting Beam is also available
capable of lifting a 3 Pole Envelope 1
and splashing water) are available for all breaker sizes.
Provides local record of the cumulative number of complete
DET-653C EntelliGuard® G Circuit Breaker Application Guide
9
EntelliGuard G Power Circuit Breaker
Section 3. EntelliGuard TU Trip Unit System
Introduction
Reliability without Compromising Protection
Arc Flash and the EntelliGuard TU Trip Unit
24-May-12 Section 3. EntelliGuard TU Trip Unit System
The EntelliGuard TU Trip Unit offers optimum circuit
protection and optimum system reliability simultaneously
with little or no compromise to either of these critical
functions. Reliability and arc flash protection, in one
package, at the same time, all the time.
EntelliGuard TU series trip units are available as the
standard controller for new production EntelliGuard G
ANSI/UL 1066, UL 489 and IEC circuit breakers. EntelliGuard
TU designs are also available as direct, functional
replacements for GE's PowerBreak, PowerBreak II, WavePro,
AKR, and AK circuit breakers. EntelliGuard TU trip units are
also available in kit form for many popular non-GE and older
GE low voltage power circuit breakers (Refer to DEH-4567).
The EntelliGuard® TU technology is also available in GE's
molded case Spectra Breaker line 400A-1200A. The Spectra
MET (microEntelliGuard) includes the innovative RELT and
Zone Selective Interlocking- Instantaneous feature. New, onboard features and communications capabilities enable
equipment enhancements, improved operational
performance and life extension programs. Performance will
vary based on associated circuit breaker and equipment
conditions. All EntelliGuard TU Trip Units are Conformal
Coated for increased reliability in humid/damp
environments.
This section describes the functions as implemented in the
EntelliGuard G UL 489 and ANSI/UL 1066 circuit breakers.
References or comparisons to other GE circuit breakers are
for informational purposes only.
Reliable protection of circuits and equipment has always
been the circuit breaker’s primary mission. Providing
appropriate protection of the conductors, while preserving
selective coordination, has been the primary focus of most
system designers. However, what was acceptable in the
past is no longer the standard today.
Modern economic reality, coupled with strict regulatory
requirements, demand optimal system performance with
increased sensitivity to the inherent power system hazards
that face operating and maintenance personnel. Safety
agencies, local authorities and owner-operators demand
better personnel protection and state-of-the-art capabilities
to minimize hazards while simultaneously preserving critical
loads and system capabilities.
These requirements often seem to be, and sometimes are, in
conflict, pitting the speed and sensitivity required to improve
arc flash protection against the delays and deliberate
decision making required to maximize power system
reliability. The EntelliGuard TU, along with the EntelliGuard
family of circuit breakers, offers flexible solutions for
demanding circuit protection and circuit preservation
environments. The EntelliGuard TU is designed to provide the
utmost in system protection and reliability simultaneously,
with little or no compromise.
Reducing arc flash hazard is a primary concern in many
power system designs. The best way to ensure the lowest
possible hazard for a particular distribution system is to
consider the hazard as the system is designed and make
careful selection of the system’s topology, circuit sizes,
equipment sizes and protective devices to minimize hazard
for the operating and maintenance personnel that will need
to use the system for years to come.
The EntelliGuard TU, especially in conjunction with the
EntelliGuard G circuit breaker, provides significant flexibility
towards solving arc flash hazard problems without
excessive sacrifice of system reliability, in terms of
selectivity.
The next three to four pages are an overview of the
EntelliGuard TU's unique features enabling Arc Flash
mitigation and selectivity at the same time. When the
downstream breaker/fuse is current limiting, the Waveform
Recognition Selective Instantaneous is used to achieve lower
Instantaneous pickup settings while maintaining selectivity.
This is very effective for 250A and below devices. For Feeder
devices above 250A, the Instantaneous Zone Selective
Interlocking (I-ZSI) feature is used to achieve selectivity and
arc flash mitigation at the same time. The I-ZSI feature is
available on Spectra MET and EntelliGuard® TU in the
following breakers: EntelliGuard G, Power Break II, WavePro,
AK/AKR, and Conversion Kits. By combining the Waveform
Recognition Selective Instantaneous and I-ZSI, a system with
a 100KAIC bolted fault current can achieve a 8 cal/cm2 or
less incident energy level.
One way to lower potential incident energy is to ensure that
circuit breakers are able to interrupt using their
Instantaneous trips for all expected arcing faults. Figure 3.1
shows the expected arcing currents for 480V systems for
various arc gaps representative of switchgear (32mm),
switchboards (25mm), MCCs (25mm) and panelboards
(13mm). These values were determined using IEEE standard
1548, Guide for Performing Arc-Flash Hazard Calculations,
DET-653C EntelliGuard® G Circuit Breaker Application Guide
10
Figure 3.1. Arcing Current
Selectivity with Molded Case Circuit Breakers and Other
Devices
Figure 3.2. Selectivity Curve
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
Figure 3.1 demonstrates the wide range of possible arcing
currents predicted by the IEEE standard’s calculations. The
actual arcing currents may be lower or higher when
consideration is given to the potential error in short circuit
calculations, fault current data provided by the utility
company, and variance in the actual arcing gap or
enclosure’s geometry where the arc occurs. Of particular
concern should be the lower end of the possible range of
current that may fall below the Instantaneous pickup of a
circuit breaker or the current limiting threshold of a fuse.
Dangerous incident energy may quickly increase when
interruption time increases from a few cycles to a few
seconds, even for low arcing current.
The EntelliGuard TU trip unit’s Waveform Recognition
Selective Instantaneous provides a unique selectivity
capability. When used in conjunction with current limiting
devices downstream, the trip unit may be set low, and still
maintain significant levels of selectivity. Table 3.1 lists the
minimum instantaneous setting above specific GE circuit
breakers and the levels of selectivity achieved. Testing and
documentation of the selectivity capability of the
EntelliGuard Trip unit will be expanded as more test data
becomes available. Always consult GE Selectivity reference
publication DET-537 for the latest information or contact
your GE sales representative for up to date information.
Selectivity above current limiting fuses may also be
expected. The required minimum setting may be estimated
by examining the peak let-through curve for the fuse. Find
the peak let-through current value that is 1.41 times the
prospective RMS current. The trip unit should be set such
that the instantaneous pickup is above that peak value. The
circuit breaker and fuse may then be selective up to the
values identified in Table 3.1. The fuse and circuit breaker
combinations have not been tested so performance cannot
be guaranteed at this time; however, selectivity is expected
for arcing and bolted faults up to the values indicated in the
above selectivity table.
Protection between circuit breakers using the EntelliGuard
TU trip unit may be further improved using zone selective
interlocking. The trip unit’s unique instantaneous zone
selective interlocking which can increase selectivity for UL
489 EntelliGuard G mains while allowing to trip
instantaneously for faults within their zone of protection
allows significant selectivity and arc flash protection at the
same time.
Selectivity for an EntelliGuard TU ground fault function and a
circuit breaker below may be enhanced by the trip unit’s
selective ground fault function and zone selective
interlocking. Figure 3.2 demonstrates an 800A circuit
breaker under a 1200A ground fault set to be fully selective.
See also Tables 3.2 and 3.3.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
11
Table 3.1. EntelliGuard Selectivity Above GE Current Limiting Circuit Breakers
Load side (branch)
devices
Wavepro,
override
Record Plus G
600A
Record Plus G
400A
Record Plus G
250A
Record Plus E
250A
Record Plus E
150A
Record Plus E
100A
Record Plus E
60A
Record Plus E
30A
Record Plus
B/C
Spectra G
600A
Spectra G
400A
Spectra G
250A
Spectra F
250A
11,200A (2)
Spectra E
150A
9,600A (2)
TECL
3 & 7A
800A (1)
TECL
15A
850A (1)
TECL
30A
1,800A (1)
TECL
50A
3,800A (1)
TECL
100A
7,300A (1)
TECL
150A
11,000A (1)
TEY/TEYF
15-100A
9,900A (1)
14,000A
14,000A
14,000A
14,000A
THQL (240V)
15-60A
9,900A (1)
10,000A
10,000A
10,000A
10,000A
THHQL
(240V)
24-May-12 Section 3. EntelliGuard TU Trip Unit System
Selectivity between any line side (main)Circuit Breaker with a GE EntelliGuard TU trip unit and a load side (branch) GE current
limiting circuit breaker, and certain lighting panel type circuit breakers is determined based on the setting of the line side
EntelliGuard TU Trip. When the line side EntelliGuard TU Trip unit is set at the value defined in the table or higher the pair is
selective over the instantaneous range of the upstream CB up to the limit defined in the table below. The required settings are
independent of the line side circuit breaker type and only depend on the load side current limiting circuit breaker. The table
below identifies the values for GE's currently produced UL listed current limiting molded case circuit breakers.
Extent of selectivity will depend on line side circuit breaker type. The table below describes how that selectivity is limited by
circuit breaker type.
The table below applies at 208 through 480 Volts except where specifically limited to 240V and lower.
Line side (Main) device with EntelliGuard TU trip unit
Frame
Designation
Maximu
m Trip
(frame
or
sensor)
EntelliGuard TU
instantaneous
setting must be
> than (3)
20,350A
9,900A (1)
100A 7,190A
29,980A
PowerBreak
II, UL 489 CB
Up to short
circuit rating;
65kA, 100kA
or 150kA at
480V, and
200kA at
240V
AKR or AK,
or other
ANSI CB
without a
mechanical
Up to short
circuit rating;
65kA, 100kA
or 150kA at
480V.
EntelliGuard
G, UL489 CB
Up to
withstand
rating; 42kA,
50kA, 65kA,
85kA or
100kA at
480V
EntelliGuard
G, ANSI CB
Up to
withstand
rating; 65kA,
85kA or
100kA at
480V
Notes:
1. EntelliGuard TU must employ a 400A rating plug or larger
2. EntelliGuard TU must employ an 800A rating plug or larger
3. Any instantaneous overlap seen in time current curves when line side CB is set per table does not indicate a lack of
selectivity and may be ignored.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
12
Table 3.2. Maximum Instantaneous Pickup Multipliers for GE Circuit Breakers
Line side device with Entelliguard TU Trip Unit
PowerBreak II,
UL 489 CB
WavePro or AKR,
ANSI CB
EntelliGuard G,
ANSI/UL Std I
EntelliGuard
G, ANSI Ext I
Max Instantaneous in X
Max Instantaneous in X
800A frame
15
15
15
30
1600A frame
15
15
15
30
3000A frame
13
N/A
15
30
3200A frame
N/A
13
15
30
6000A frame
N/A
N/A
15
16 Amperes
Amperes
2000A frame, 2000A plug
30,000
30,000
30,000
60,000
2500A frame, 2500A plug
32,500
N/A
37,500
75,000
4000A frame, 4000A plug
40,000
52,000
60,000
92,000
5000A frame, 5000A plug
N/A
65,000
75,000
95,000
Maximum instantaneous is a multiple of rating plug, the above values may be lower if a smaller rating plug than
maximum for frame is used. In PB2 & WavePro CB maximum instantaneous multiplier is limited by frame rating. In
Entelliguard G the maximum Instantaneous X may be limited by circuit breaker withstand or short time rating (also
known as Icw).
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
•Instantaneous selectivity between a circuit breaker with an EntelliGuard TU trip Unit and any non-current limiting circuit breaker may be evaluated via
traditional time current curve analysis or simply multiplying the upstream instantaneous trip setting by .9 which accounts for the tolerance of the line
side circuit breaker around the nominal setting. If The EntelliGuard TU's Instantaneous zone selective interlocking capability between similarly equipped
circuit breakers is employed then selectivity up to the upstream circuit breaker's full withstand or short circuit rating is possible.
The table below identifies maximum instantaneous pickup multipliers possible for various types and sizes of GE circuit
breakers. Lower part of table identifies the maximum instantaneous pickup in amperes for various circuit breaker, sensor and
rating plug combinations.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
13
Table 3.3. Selectivity with EntelliGuard TU Trip Units in ANSI and ICCB/ Power Break II Circuit Breakers
Downstream device with
EntelliGuard TU Trip Unit
Power Break II,
UL 489 CB
WavePro or AKR,
ANSI CB
EntelliGuard G,
ANSI/UL Std I
EntelliGuard
G, ANSI Ext I
Max Instantaneous in X
Max Instantaneous in X
800A frame
15
15
15
30
1600A frame
15
15
15
30
2000A frame
15
15
15
30
3000A frame
13
N/A
15
30
3200A frame
N/A
13
15
30
4000A frame
10
10
15
23
5000A frame
N/A 7 15
19
6000A frame
(UL 489 only)
N/A
N/A
15
N/A
Amperes per above multipliers
800A frame,
800A plug
12,000
12,000
12,000
24,000
1600A plug
2000A frame,
2000A plug
30,000
30,000
30,000
60,000
3000A plug
3200A frame,
3200A plug
N/A
41,600
48,000
96,000
4000A plug
5000A frame,
5000A plug
N/A
35,000
75,000
95,000
6000A plug
24-May-12 Section 3. EntelliGuard TU Trip Unit System
Frame determines
maximum
instantaneous
pickup (X) for PB II
and WP CB.
Plug/Icw ratio
determines
maximum possible
for EntelliGuard
GCB. EntelliGuard
values shown are
more maximum
withstand tiers.
1600A frame,
3000A frame,
24,000
39,000
24,000
24,000
N/A 45,000
48,000
90,000
4000A frame,
6000A frame,
• Maximum instantaneous is a multiple of rating plug. The above values may be lower if a smaller rating plug than maximum for frame is used. In PB II &
WavePro circuit breakers, the maximum instantaneous multiplier is limited by frame rating. In EntelliGuard G, the maximum Instantaneous X may be
limited by circuit breaker withstand or short time rating (also known as Icw). The current numbers above multiplied by 0.9 provide maximum selectivity
above non-current limiting if instantaneous is adjusted to maximum and no zone selective interlocking is used.
40,000
40,000
60,000
N/A N/A 90,000
92,000
N/A
Note: For complete listing of all selectivity functionalities see publication DET-537D
DET-653C EntelliGuard® G Circuit Breaker Application Guide
14
Above Downstream Feeders
The Waveform Recognition Selective Instantaneous
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
The EntelliGuard TU trip unit has Short Time bands under
100msec designed to optimally fit above the Instantaneous
clearing times of various GE circuit breakers. Table 3.4 lists
the suggested Short Time band that may be used above
specific GE circuit breakers for the fastest coordination and
consequently fastest EntelliGuard G circuit breaker
interruption.
Also listed is the Hazard Risk Category for various available
fault currents calculated at the listed Short Time band
clearing times and Instantaneous clearing times provided by
the EntelliGuard TU trip unit’s Waveform Recognition
Selective Instantaneous and its Reduced Energy Let-Through
(RELT) Instantaneous trip. The Hazard Risk Category (HRC)
levels shown are calculated for a solidly grounded, 480V
system, 32mm arc gap, 18 in. working distance and arc in
box. Using the optimized Short Time band allows the system
to stay at HRC2 most of the time and always less than HRC4.
However, use of the RELT Instantaneous trip allows the
system to protect at HRC1 or 2 for available fault currents as
high as 90kA.
The Instantaneous algorithm in the EntelliGuard TU trip unit
will allow a large switchboard or switchgear circuit breaker
to be set low yet maintain selectivity. For example, when set
to protect the conductors to a motor control center, an 800A
feeder circuit breaker’s Instantaneous may be set as low as
8kA nominal. This should provide complete selectivity above
the typical 150A and smaller circuit breakers or fuses found
in a motor control center.
Allowing for 10% pickup tolerance in the Instantaneous
pickup of the feeder circuit breaker would indicate that the
feeder would pickup Instantaneously for arcing fault
currents approximately 9kA or higher. From Figure 3.1 it can
be seen that fault currents of 20-25kA and higher would
seem to reliably produce arcing current above 9kA in a
variety of configurations. From Table 3.4 it can be seen that
an EntelliGuard G circuit breaker clearing instantaneously
can maintain HRC1 in a system with up to 42kA available
and HRC2 in systems with up to 100kA available – excellent
arc flash protection and selectivity simultaneously!
Note: These incident energy calculations do not take into
account motor contribution or other factors that may affect
expected levels of incident energy or hazard. For a thorough
understanding of the incident energy available or HRC in a
power distribution system, an Arc Flash Study should be
conducted by engineering personnel qualified to provide
such analysis.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
15
Table 3.4. Minimum Selective Clearing Times for an EntelliGuard G Circuit Breaker Above Selected GE Circuit Breakers,
and Related HRC Levels at Various Fault Circuits
GP = General Purpose Application.
MCP = Motor Circuit Protector).
HRC = Hazard Risk Category (See NFPA 70E.
Above Other Power Circuit Breakers
Terminology
In:
X:
HSIOC:
MCR:
ICW:
ICU:
24-May-12 Section 3. EntelliGuard TU Trip Unit System
FB, FC, TEY, THQL TM, LP 0.025sec 0.08sec 2 2 2 2 3 3 3
TED, TEC TM-GP, MCP 0.025sec 0.08sec 2 2 2 2 3 3 3
TF, TJ, TK TM-GP 0.025sec 0.08sec 2 2 2 2 3 3 3
Spectra E, F, G Frame E-GP 0.025sec 0.08sec 2 2 2 2 3 3 3
Spectra K Frame E-GP 0.033sec 0.088sec 2 2 2 2 3 3 3
Spectra G, K with MVT trip AE-GP 0.025sec 0.08sec 2 2 2 2 3 3 3
Record Plus G Frame E, AE-GP 0.042sec 0.097sec 2 2 2 2 3 3 3
Record Plus E Frame E-GP 0.033sec 0.088sec 2 2 2 2 3 3 3
Power Break with MVT AE-GP 0.058sec 0.113sec 2 2 2 3 3 3 3
Instantaneous Clearing Time
RELT Clearing Time
instantaneous 0.050sec 1 1 1 2 2 2 2
RELT Instantaneous 0.042sec 1 1 1 1 2 2 2
Using the EntelliGuard TU trip unit’s unique Instantaneous
Zone Selective Interlocking (I-ZSI), the main circuit breaker
also can be set to interrupt selectively for faults in its zone
of protection. However, the pickup level must be nested to
prevent a nuisance trip at the main. Allowing for a 10%
tolerance in the pickup current of both trips, the upper
boundary of the main’s trip may be estimated at
approximately 11kA. Again, Figure 3.1 shows that
available fault currents above 25kA will generally produce
arcing currents above 11kA. Table 3.4 shows a system
with fault currents from 35kA to 100kA, the feeder and
main circuit breaker will provide protection at HRC1 or
HRC2 selectively above most circuit breakers using short
time bands. Coordinated instantaneous settings would
provide even better protection while still maintaining
selectivity with select feeder breakers. To this capability
one can add the RELT instantaneous setting that provides
more sensitive and faster protection when needed.
Trip plug rating in amperes. This is the current rating of
the rating plug installed in the trip unit. This is the
maximum Long Time pickup a trip unit can have with a
specific plug installed. A sensor can usually be applied
with plugs between 37.5% or 40% to 100% of the sensor
rating. Plugs are labeled in amperes.
X is a multiplier that may be applied in front of any
rating value to denote a fraction of that rating. Example:
The Long Time Pickup may be set at 0.5X of In.
High Set Instantaneous Overcurrent, also known
as the Override. This is an Instantaneous protection
setting applied near the circuit breaker’s withstand rating
required to clear high magnitude faults quickly. In UL489
circuit breakers this is fixed; in UL1066 CBs the override
may vary, if present at all.
Making Current Release. A setting provided with
each trip unit, based on the specific circuit breaker size,
used to protect the circuit against closing on high
magnitude faults. The MCR function immediately
trips/opens the circuit breaker if high magnitude fault
current is sensed at the instant the circuit breaker is
closed.
Short Circuit Withstand Rating of a particular circuit
breaker in amperes. The withstand rating is defined
differently within different standards, but it is always the
value of current that a circuit breaker can withstand for
some period of time without interrupting.
Short Circuit Interrupting Rating (ISC), or ultimate
interrupting rating (ICU) in IEC terms. The maximum shortcircuit interrupting rating of a circuit breaker in amperes.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
16
Long Time Protection
Thermal Long Time Overcurrent
Figure 3.3. Thermal Characteristic: Maximum and
Minimum Long Time Delay Bands for a 1000A Long Time
Pickup
Breaker Type
TCC
EntelliGuard G:
DES-090
WavePro, PBII, PBI, AK, AKR, Conv Kits
DES-095
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
The EntelliGuard TU offers two different shapes for Long
Time protection curves. Each type of curve is available with
22 different time delays. The shapes may be described as
2
thermal type I
t characteristics and fuse shaped I4t lines.
The nominal Long Time pickup is computed from the trip
rating plug value (In) multiplied by the Long Time pickup
setting. Long Time pickup setting multipliers are user
settings and may range from 0.5 to 1.0 in increments of 0.05.
The actual Long Time pickup is 112% of the nominal setting
(Ir). 112% is to compensate for the Long Time Pickup
Tolerance of ±10% that is drawing as “actual value/1+
tolerance)”. For a nominal 1000A Long Time pickup, the
actual trip setting is 1120A, drawn as a vertical band
between 1120/1.1 and 1120/0.9, or 1018A and 1244A.
The thermal I2t shape is similar to the typical curve of a
thermal magnetic circuit breaker and matches the shape of
many overcurrent devices used in industry today. The typical
shape and range of settings may be seen in Figure 3.3. The
range of time delays is shown in Table 3.5 at various
multiples of nominal (100%) current setting. Drawn bands
also include a mechanical constant time to account for
circuit breaker operating and clearing time, which causes
the slight widening of the band evident at the lower (right)
end of the faster (lower) bands.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
17
Table 3.4. Thermal Characteristic: Nominal Clearing and Commit Times for X Multipliers of Nominal Pickup
X=
1.5
7.2
10
12
15
Commit
Clear
Commit
Clear
Commit
Clear
Commit
Clear
Commit
Clear
Min CB
4.25
8.04
0.139
0.239
0.072
0.137
0.050
0.104
0.038
0.080
C-2
12.7
24.1
0.417
0.656
0.215
0.352
0.149
0.253
0.095
0.172
C-3
25.5
48.1
0.83
1.28
0.430
0.674
0.298
0.476
0.190
0.315
C-4
34.0
64.1
1.11
1.70
0.57
0.89
0.40
0.62
0.254
0.410
C-5
51.0
96.2
1.67
2.53
0.86
1.32
0.60
0.92
0.38
0.60
C-6
67.9
128
2.22
3.4
1.15
1.75
0.79
1.22
0.51
0.79
C-7
84.9
160
2.78
4.2
1.43
2.18
0.99
1.52
0.63
0.98
C-8
102
192
3.33
5.0
1.72
2.61
1.19
1.81
0.76
1.17
C-9
119
224
3.89
5.9
2.01
3.03
1.39
2.11
0.89
1.36
C-10
136
256
4.44
6.7
2.29
3.46
1.59
2.41
1.02
1.55
C-11
153
289
5.00
7.5
2.58
3.89
1.79
2.71
1.14
1.74
C-12
170
321
5.56
8.4
2.87
4.32
1.99
3.00
1.27
1.93
C-13
204
385
6.67
10.0
3.44
5.18
2.38
3.60
1.52
2.31
C-14
238
449
7.78
11.7
4.01
6.04
2.78
4.19
1.78
2.69
C-15
272
513
8.89
13.4
4.59
6.90
3.18
4.79
2.03
3.07
C-16
306
577
10.0
15.0
5.16
7.76
3.58
5.38
2.29
3.45
C-17
340
641
11.1
16.7
5.73
8.61
3.97
5.98
2.54
3.83
C-18
374
705
12.2
18.4
6.30
9.47
4.37
6.57
2.79
4.21
C-19
408
769
13.3
20.0
6.88
10.3
4.77
7.17
3.05
4.59
C-20
442
833
14.4
21.7
7.45
11.2
5.17
7.76
3.30
4.97
C-21
476
898
15.6
23.4
8.02
12.0
5.56
8.36
3.56
5.35
Max CB
510
962
16.7
25.1
8.60
12.9
5.96
8.95
3.81
5.73
•
•
• Actual Long Time pickup is 112% of nominal pickup.
Fuse-Shaped Steep Long Time Overcurrent
Figure 3.4. Fuse Characteristic: Maximum and Minimum
Long Time Delay Bands for a 1000A Long Time Pickup
Table 3.5.
Breaker Type
TCC
EntelliGuard G:
DES-091
WavePro, PBII, PBI, AK, AKR,
Conv Kits
DES-096
24-May-12 Section 3. EntelliGuard TU Trip Unit System
Algorithm will not commit below 1.5 cycles, clearing time will not be less than 0.08sec. Maximum LT curve is 15XLTPU for Envelope 1 and 2 devices, 10XLTPU for Envelope 3 devices.
The optional steeper fuse characteristic is a straight line
4
t shape for application in systems where fuses and
K=I
circuit breakers are used together. Twenty-two different
time bands are available in each trip unit.
Figure 3.4 displays minimum and maximum bands. Table 3.6
displays the nominal time delays for each of the 22 bands at
various multiples of nominal current pickup.
Drawn bands also include a 30 ms constant time, which
accounts for the slight widening evident in the time current
curve at the lower (right) end of the faster (lower) time bands.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
19
Thermal Memory
Short Time Protection
Short Time Pickup
Short Time Bands
Figure 3.5. Short Time Pickup
Figure 3.6. Short Time Transition
24-May-12 Section 3. EntelliGuard TU Trip Unit System
The Long Time and Short Time pickup algorithm also
includes a cooling cycle that keeps track of current if it
oscillates in and out of pickup range. This Thermal Memory is
also active in case the circuit breaker trips on Long Time or
Short Time to account for residual heating in conductors. If a
circuit breaker is closed soon after a Long Time trip or Short
Time trip, a subsequent trip may happen faster than
indicated by the time current curve due to the residual cable
Thermal Memory effect. In trips without control power, the
Thermal Memory is powered from the Trip Unit battery. The
cooling algorithm requires up to 14 minutes to fully reset to
zero.
The EntelliGuard TU provides a wide range of Short Time
2
pickup settings, I
t characteristics and time bands to
optimize selectivity while not sacrificing clearing time
unnecessarily. Short Time pickup settings range from 1.5 to
12 times the Long Time pickup setting for the EntelliGuard G
circuit breakers in Envelopes 1 and 2. The maximum Short
Time pickup for Envelope 3 is 10 times. In Power Break,
WavePro, AKR and other circuit breakers, the maximum
Short Time pickup may be lower. The transition between
Long Time band and Short Time function may happen at the
horizontal Short Time Delay Band rather than the vertical
Short Time pickup, depending on the following:
• How fast or what type of Long Time band is chosen
• What Short Time pickup is selected
• What Short Time Delay is selected
An example of this may be seen in Figure 3.5 for the
combination of Long Time Delay Band and Short Time Delay
Band shown in Figure 3.6, any Short Time pickup setting
larger than 6X will result in the Long Time band intersecting
with the horizontal Short Time delay band rather the vertical
Short Time pickup.
The EntelliGuard TU comes with a wide range of adjustable
Time Delay Bands, ranging from a minimum of 25ms (clears
in 80ms, 55ms for Sensing, Operating and Clearing Time) to
417ms (clears in 472ms). The bands are specially designed
to pickup above various circuit breakers and trip systems to
provide required selectivity while not sacrificing any more
clearing time than required to provide the best possible arc
flash protection.
The time bands are shown in Table 3.6 and Figure 3.7.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
20
Table 3.7. Short Time Delay Bands
Label
Pickup
Clearing
Minimum
0.025
0.080
2nd
0.033
0.088
3rd
0.042
0.097
4th
0.058
0.113
5th
0.092
0.147
6th
0.117
0.172
7th
0.158
0.213
8th
0.183
0.238
9th
0.217
0.272
10th
0.350
0.405
Maximum
0.417
0.472
Figure 3.7. Short Time Delay
Table 3.8.
Breaker Type
TCC
EntelliGuard G:
DES-092
WavePro, PBII, PBI, AK, AKR, Conv
Kits
DES-097
Short Time I2t Slopes
Figure 3.8. Short I2t (In or Out)
Ground Fault Protection
Internal Residual Summation
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
Figure 3.8. The bands may be defined by the formula K = I
where K equals 18, 8 and 2 times the nominal Long Time
pickup squared. A 30msec fixed time is added to account for
circuit breaker mechanical operation, clearing time and
variance. Pickup tolerance is 10% of current.
2
t,
The EntelliGuard Trip Unit offers three different Short Time I2t
characteristics to allow optimized settings for selectivity and
fast protection whenever possible. When using the
EntelliGuard Trip Unit in systems that also employ older GE
2
MVT trip units, the EntelliGuard Trip Unit’s maximum I
characteristic is equal to the Short Time I
2
t characteristic in
t
the MVT trip.
The position of the I
2
t slopes varies with the Long Time
pickup of the respective circuit breaker. The intersection of
the Short Time pickup and the Short Time delay band with
2
t slope varies with the Short Time pickup and time
the I
delay band.
The three positions for the Short Time I
2
t band are shown in
The maximum (upper) Short Time I2t band may not be used
with the minimum Long Time thermal band. Use of the fuse
shaped Long Time bands also inhibits use of the Short Time
2
t bands. Only the definite Short Time pickup characteristic
I
may be used with the fuse shaped Long Time curves.
The EntelliGuard TU trip unit offers the ultimate in Ground
Fault protection. Each trip unit may be provided with the
ability to accept a neutral sensor signal and generate an
internal Zero Sequence phasor for Ground Fault protection.
It may also be equipped with the ability to accept a Zero
Sequence phasor signal from an external Zero Sequence CT
or residual summation scheme using current transformers.
Either Ground Fault method may be used to provide Ground
Fault trip or Ground Fault alarm. Four pole circuit breakers
may also provide Ground Fault protection based on an
external Zero Sequence input signal or a residual sum of all
four internal sensors.
The EntelliGuard TU trip unit uses internal air core sensors
for current sensing, and the signals are residually summed
using advanced digital electronics. A neutral sensor may be
located remotely and connected to the trip unit. The
connection is limited to 10m (33ft). Due to the air core
sensor’s ability to handle a wide range of primary currents
without distortion, Ground Fault sensing is accurate for a
wide range of phase and current inputs.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
21
External Zero Sequence Input
Ground Fault Pickup Settings
Table 3.9. Ground Fault Time Delay Bands
Sensor
Minimum
Maximum
400
0.2
0.60
600
0.2
0.60
800
0.2
0.60
1200
0.2
0.60
1600
0.2
0.60
2000
0.2
0.60
2500
0.2
0.48
3000
0.2
0.40
3200
0.2
0.37
4000
0.2
0.30
5000
0.2
0.24
6000
0.2
0.20
Ground Fault Time Delay Bands
Table 3.10. Minimum Ground Fault Pickup and Clear Time
Setting
Power Break I & II,
AKR & WavePro
EntelliGuard G
Ground Fault Protection Curves
Figure 3.9. Ground Fault Characteristics
Instantaneous Protection
24-May-12 Section 3. EntelliGuard TU Trip Unit System
The EntelliGuard TU trip unit is able to accept input from an
externally calculated Ground Fault current. The Ground Fault
current may be derived using a single Zero Sequence CT or
multiple phase CTs connected in a residual summation
scheme. External CE marked Zero Sequence or ground
return CTs are available for IEC applications, but are not UL
Listed. Phase CTs used for a summation connection are UL
Listed. Applications for this capability include sensing at the
ground return connection for a transformer or generator as
well as application in multiple source grounded systems.
All UL 489 and UL 1066 circuit breakers are limited to a
maximum nominal pickup setting of 1200A per the National
Electrical Code or 60% of the sensor size, whichever is lower.
The minimum setting is 20% of sensor size. The available
maximum settings per sensor may be seen in Table 3.8.
The EntelliGuard TU trip unit offers four different shapes for
the ground fault function:
• Definite time with adjustable time delay.
2
• I
t slope with adjustable time delay.
4
• I
t slope (fuse shaped) with adjustable time delay.
• Selective double break I
The definite time and I
traditional GF curve shapes. The I
shape more in line with downstream fuses. GE’s unique
selective double break I
2
t with adjustable time delay.
2
t characteristics provide the
2
t characteristic provides the most
4
t characteristic provides a
selective setting possible while still meeting the applicable
UL and NEC standards. In many cases, an 800A circuit
breaker may be used under a 1200A ground fault curve
selectively (Fig. 3.9).
Ground Fault Time Delay Bands used in the EntelliGuard G
circuit breakers range from 42msec to 942msec. In Power
Break I, Power Break II, WavePro and AKR circuit breakers,
the minimum GF Time Delay Band is 58msec and the
maximum is 417msec.
The available minimum settings per circuit breaker type are
shown in Table 3.9. The maximum Time Delay Band setting
for all circuit breakers is 0.940sec with a 1sec clear.
The EntelliGuard TU trip unit may provide several types of
Instantaneous protection, depending on the circuit breaker
in which it is installed. The different types of Instantaneous
protection are as follows:
• Adjustable Selective Instantaneous: Provided on Power
Break, Power Break II, WavePro, AK, AKR, Conv Kits and
EntelliGuard G.
• Extended Range Adjustable Selective Instantaneous: An
available option on ANSI EntelliGuard G circuit breakers.
• High Set Instantaneous Overcurrent Trip: Provided on
Minimum pickup 0.058sec 0.042sec
Minimum clear 0.113sec 0.097sec
Maximum pick 0.417sec 0.940sec
Maximum clear 0.470sec 1.000sec
Power Break II and some EntelliGuard G circuit breakers,
also called an override.
• Making Current Release (MCR): Provided on all EntelliGuard
G circuit breakers.
• Reduced Energy Let-Through Instantaneous Trip: An
available option on Power Break, Power Break II, WavePro,
AK, AKR, Conv Kits, and EntelliGuard G circuit breakers.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
22
Adjustable Selective Instantaneous
Table 3.11. Maximum Adjustable Instantaneous Pick-up for EntelliGuard G Circuit Breakers with Normal or Extended
Range Option
“In” (Plug
Rating, A)
Withstand Rating
42
50
65
85
100
Normal
Range
Extended
Range
Normal
Range
Extended
Range
Normal
Range
Extended
Range
Normal
Range
Extended
Range
Normal
Range
Extended
Range
150-2,000
15
N/A
15
N/A
15
30
15
30
15
30
2,200
N/A
N/A
15
N/A
15
28
15
30
15
30
2,400
N/A
N/A
15
N/A
15
25
15
30
15
30
2,500
N/A
N/A
15
N/A
15
24
15
30
15
30
3,000
N/A
N/A
15
N/A
15
20
15
26
15
30
3,200
N/A
N/A
N/A
N/A
15
19
15
25
15
29
3,600
N/A
N/A
N/A
N/A
15
17
15
22
15
26
4,000
N/A
N/A
N/A
N/A
15
15
15
20
15
23
5,000
N/A
N/A
N/A
N/A
N/A
N/A
15
16
15
19
6,000
N/A
N/A
N/A
N/A
N/A
N/A
13
N/A
N/A
N/A
Table 3.12. Time Current Curves
Breaker Type
TCC
EntelliGuard G: Selective
Instantaneous & RELT
DES-094
& RELT
DES-101
Power Break: Instantaneous
DES-099
Power Break II: Selective
Instantaneous and HSIOC (Override)
DES-100
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
Each of these Instantaneous trips provides optimum
protection, selectivity or both as required for different
applications, subject to the capabilities of the respective
circuit breakers in which the trip units are installed.
The EntelliGuard TU uses an exclusive algorithm, developed
by GE, to recognize the wave shape of fault current within a
cycle. With the improved analysis of the fault current wave
shape, the trip unit allows the circuit breaker to trip
immediately yet provide superior selectivity when used
above current limiting circuit breakers or fuses. In many
cases, the trip unit’s Instantaneous pickup may be set quite
low yet allow for complete selectivity up to the circuit
breaker’s full withstand level. For a list of possible selective
combinations of GE circuit breakers employing the
EntelliGuard TU trip unit and various downstream
overcurrent devices, see GE publication DET-537.
The EntelliGuard TU trip unit can be furnished with one of
two Instantaneous adjustment ranges. The standard
adjustable range may be as high as 15X the trip plug value
on all UL 489 or UL 1066 circuit breakers. An optional
Extended Range Adjustable Selective Instantaneous, as high
as 30X, may be provided for UL 1066 Listed Low Voltage
Power Circuit Breakers (LVPCBs). LVPCBs also allow for this
adjustable Instantaneous trip to be turned off. The minimum
adjustable Instantaneous pickup setting for all circuit
breakers is 2X the trip plug rating. The available maximum
pickup settings are described in Table 3.10. The maximum
Instantaneous pickup is limited by the circuit breaker’s
withstand rating.
The Adjustable Selective Instantaneous will clear a fault in
three cycles when used in 60Hz or 50Hz applications. Zone
Selective Interlocking (I-ZSI) may be used with this
Instantaneous function, allowing several breakers with
overlapping Instantaneous protection to be selective with
each other. Because each circuit breaker is set to trip
Instantaneously for faults within their respective zones of
protection, fast protection and selectivity are achieved
simultaneously.
The special selective Instantaneous algorithm allows any
circuit breaker above current limiting devices to be set with
a relatively low Instantaneous pickup and still achieve
significant selectivity. The system may be able to provide
Instantaneous protection for most faults, including high
impedance arcing fault, while maintaining significant levels
of selectivity. Figures 3.11 and 3.12 later in this document
demonstrate the performance of the Instantaneous ZSI
capability
.
Power CB: Selective Instantaneous
Page 29
DET-653C EntelliGuard® G Circuit Breaker Application Guide
23
High Set Instantaneous Overcurrent (HSIOC)
Making Current Release (MCR)
Table 3.13. HSIOC Locations
Short
Circuit Tier
Interrupting Rating (A)
UL489
Override
UL1066
Override
240V
480V
600V
UL489 I
CW
UL1066 ICW
S
65,000
65,000
50,000
42,000
50,000
42,000
None
N
65,000
65,000
65,000
42,000
65,000
42,000
None
H
85,000
85,000
65,000
50,000
65,000
50,000
65,000
P
100,000
100,000
65,000
50,000
65,000
50,000
65,000
E
85,000
85,000
85,000
N/A
85,000
N/A
None
M
100,000
100,000
100,000
65,000
85,000
65,000
85,000
B
100,000
100,000
100,000
N/A
100,000
N/A
None
L
150,000
150,000
100,000
85,000
100,000
85,000
10,000
Reduced Energy Let-Through (RELT) Instantaneous Trip
24-May-12 Section 3. EntelliGuard TU Trip Unit System
The EntelliGuard TU trip unit’s HSIOC pickup is similar to the
fixed override used by other trip units and circuit breakers in
the industry. In EntelliGuard G, the HSIOC setting is changed
automatically by the trip unit if the normal adjustable
Instantaneous is turned off (LVPCB only). When adjustable
Instantaneous setting is turned off, HSIOC nominal setting
becomes 98% of the circuit breaker’s Short Time withstand
setting. In all other cases, in the EntelliGuard G family of
circuit breakers, the HSIOC is set high enough to allow full
selectivity up to the circuit breaker’s short time withstand
rating.
For circuit breakers with an HSIOC trip function, the location
of the HSIOC trip is shown by the line that reaches the
0.01sec axis at the bottom of the TCC. The location of that
line is shown in Table 3.11. In many applications, the
EntelliGuard G circuit breaker with an EntelliGuard TU trip
unit will be completely selective up to the HSIOC pickup or
This form of Instantaneous protection is provided on all
EntelliGuard G circuit breakers. This function provides
protection in case the circuit breaker is closed on an
unusually high current. A circuit breaker that experiences 15
times (15x) or more its plug rating is possibly closing in on a
fault caused by incorrectly wired conductors, forgotten
grounding cables or some other type of unusual low
impedance fault.
Alternatively, it is closing on a very low impedance arcing
fault. In either case, there is a possibility that equipment may
be damaged by the high fault current or an arc flash hazard
has been inadvertently created. The MCR provides very fast
protection when the circuit breaker is closed and for the first
six cycles thereafter. After the six cycles have elapsed, the
MCR is turned off and the circuit breaker reverts to its
adjustable Instantaneous pickup and HSIOC if provided. The
MCR will clear fault current in 40msec or less.
the circuit breaker’s full short circuit rating, even with the
adjustable Instantaneous on.
• All UL Overrides are -0% tolerance, ANSI Override pickup at -0% or -9% based on Adjustable Selective Instantaneous being on or off.
The EntelliGuard TU trip unit provides an optional second,
user-adjustable, RELT Instantaneous trip, which allows a
circuit breaker to be temporarily set to a more sensitive
pickup to provide better protection, only when better
protection is needed and some selectivity may be
sacrificed. The RELT pickup is adjustable from 1.5X to 15X
of plug rating, independently of the normal adjustable
selective Instantaneous. It may be set higher or lower than
the selective Instantaneous.
The user must make two entries at the trip unit: (1) Pickup
settings (1.5-15X of the plug) and (2) ON, OFF or REMOTE.
ON/OFF enables or disables the pickup setting. REMOTE
allows the RELT Instantaneous pickup to be enabled via
application of 24Vdc or Vac at the RELT input terminals or
serial communications via the Modbus or Profibus
communication port. The RELT pickup may be enabled via
serial communication or remote 24V signal, but both need
to be indicating “OFF” for the RELT Instantaneous pickup
to be disabled. The RELT input command may be wired to
a manual switch, automatic sensor or, via external logic,
When the EntelliGuard TU trip unit has the RELT
Instantaneous pickup enabled, the trip unit provides a
feedback signal via an optically isolated dry contact and
serial communication. This provides positive feedback that
the trip unit has received and reacted to the RELT Enable
command.
The EntelliGuard TU trip unit’s RELT capability provides the
ultimate in user flexibility for wiring and controlling an
alternate Instantaneous setting for temporary use to reduce
personnel hazard. The RELT Instantaneous pickup clears
fault current in 42msec or less at 60Hz.
RELT capability may be provided on a trip unit with or
without control power. If 24V is provided to the RELT input,
the trip unit will use the RELT Instantaneous trip setting.
However, without control power connected to the trip unit
permanently, indication that the trip unit is in the RELT mode
may not be reliably communicated. If reliable
communication that the trip unit is in the RELT mode is
desired, it is suggested that the trip unit be permanently
DET-653C EntelliGuard® G Circuit Breaker Application Guide
24
Reduced Energy Let-Through Switch Wiring
Figure 3.10. Integrated Switch and LED, Spring Return
from “Test” to “Off,” Latched in “On”
Zone Selective Interlocking (ZSI)
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
The RELT switch may be connected to a manually operated
two-position switch, a remote sensor, or both
simultaneously. The EntelliGuard TU trip unit provides a
feedback capability directly from the trip so the user is able
to verify that the signal was received by the trip unit and the
settings have changed. Optionally, an indicating light may
also be connected to the source of control power so the user
knows if control power is available to change the setting.
The trip unit does not require its own control power to
accept a RELT input and change the Instantaneous trip
pickup according to the user settings. However, if control
power is available to the trip unit, the feedback signal will
function immediately, rather than when the trip unit
becomes self-powered through its load current (Fig. 3.10).
• This configuration provides positive indication that the trip unit has
received and processed the RELT "On" signal. It Also provides a control
power check. Caution: It is recommended that RELT output be wired to
an appropriate annunciation when remote activation control of RELT is
used.
NOTE: When using the RELT function in conjunction with
remote enable/disable control, it is strongly recommended
that the trip unit be provided with permanently connected
control power and that the RELT status output be assigned
to a trip output contact. The trip output contact should be
wired to appropriately located annunciation. The trip unit will
accept a command to enable the RELT instantaneous pickup
setting via local HMI control, a 24Vac/dc voltage applied at
the input terminals or serial communication. Regardless how
the enable command is received, the trip unit will be in the
RELT mode when protection is required. However, the status
indicating contacts will only close if the trip unit is powered
through the internal current transformers or 24Vdc control
power. Lack of 24Vdc control power could provide unreliable
indication of RELT status due to low load conditions on the
circuit breaker.
The EntelliGuard TU trip unit’s ZSI capability differs from that
found in other circuit breaker trips in two significant ways:
1. It allows independent and separate settings of the
unrestrained (in zone protection) and the restrained
(back up protection) bands.
2. It provides simultaneous and independent ZSI of both
the Short Time and Instantaneous protection. This
allows each circuit breaker to zone interlock with upper
tier circuit breakers between ST band to ST band,
Instantaneous to Instantaneous, or Instantaneous to
Short Time.
The EntelliGuard TU trip unit's fast ZSI system is able to
interlock Ground Fault, Short Time and Instantaneous. When
required for feeder selectivity the main is able to be set
faster than the feeder without any sacrifice in selectivity. As
long as the main breaker's pickup is set above the feeder's
pickup the two devices will remain selective. Each circuit
breaker in a ZSI scheme allows separate user settings for
the restrained (backup) and unrestrained (in zone
protections) for ground fault and short time protection. For
the lowest tier device in the scheme the restrained and
unrestrained are set to the same values. For instantaneous
protection there is only one pickup setting required.
Instantaneous protection may also be interlocked such that
all circuit breakers above the one whose zone has the fault
will shift from Instantaneous clearing to a 0.058msec time
band. Since it is expected that faults of enough magnitude
to engage the Instantaneous pickup are dangerously high,
all zone selective interlocked Instantaneous trips that
receive a restraint signal are shifted to the same band.
Should the bottom circuit breaker fail to clear for whatever
reason, quick back up protection from both ties and feeders
is provided.
Short Time and Ground Fault bands for zone interlocked
circuit breakers may be set to any band available to the trip.
Figure 3.11 shows two circuit breakers set to protect at their
unrestrained settings. Figure 3.12 shows the same two
circuit breakers while a fault is detected below the lower
circuit breaker in the system and after a restraint signal is
received by the upper circuit breaker’s trip unit. The upper
circuit breaker’s Short Time band has shifted from the user
setting of 0.025sec to a user set restrained band of 0.092sec.
The Instantaneous has shifted from the adjustable selective
Instantaneous band clearing in 0.050sec to the fixed
restrained band of 0.058sec, clearing in 0.113sec. This allows
the lower circuit breaker to clear faults within their zone of
protection above 7,000A RMS and 11,000A RMS respectively,
clearing under 100msec, while maintaining full selectivity for
faults up to 85,000A.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
26
Figure 3.11. Zone Selective Interlocked CB, Upper
CB Shown “Unrestrained”
Figure 3.12. Zone Selective Interlocked CB, Upper CB
Shown “Restrained”
Universal Trip Rating Plugs
Figure 3.13. EntelliGuard Trip Unit Rating Plug Catalog
Number Guide
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
The EntelliGuard TU trip system is composed of trip units and
trip rating plugs along with the sensors and wiring provided
in the EntelliGuard G circuit breaker to support the trip.
Rating plugs are used to lower the Long Time adjustment
range of the sensor provided in the circuit breaker.
The EntelliGuard TU trip rating plugs are unique in that they
can be used with multiple trip units and circuit breakers
within a specific sensor range, rather than only with a single
specific sensor. The trip rating plug catalog number, shown
in Figure 3.13, identifies the rating as well as the minimum
and maximum sensor rating the plug may be used with.
Table 3.12 lists trip rating plugs available for each sensor.
Table 3.13 lists the two-digit codes used within the trip rating
plug catalog numbers and the sensor current ratings to
which they are mapped.
1 Sensor available in WavePro and AKR only.
2 Sensor available in Power Break only.
3 Sensor available in IEC listed circuit breaker only.
4 Used on Conv Kits
Table 3.17 lists the plugs available for each sensor in the
various circuit breakers in which the EntelliGuard TU may be
installed.
1 WavePro & AKR only. EntelliGuard G min. trip plug is 150A.
2 PowerBreak only. EntelliGuard G min. trip plug is 150A.
3 WavePro & AKR only. EntelliGuard G min. sensor is 400A.
4 PowerBreak only. EntelliGuard G min. sensor is 400A.
5 IEC only sensor, UL equivalents are 600A.
6 Used on ITE and Allis Chalmers Conv Kits
DET-653C EntelliGuard® G Circuit Breaker Application Guide
28
Table 3.17. EntelliGuard G Rating Plug Logic (UL 489, UL 1066, IEC)
Breaker Frame/Sensor (A)
All
UL/ANSI
IEC
All
All
UL/ANSI
IEC
All
All
All
UL
IEC/ANSI
All
All
UL/IEC
IEC
400
600
630
800
1000
1200
1250
1600
2000
2500
3000
3200
4000
5000
6000
6400
150 200 225
225
250
250
250 300
300
300
300
350
350
350
350
400
400
400
400
400
450
450
450
450
450
500
500
500
500
500
500
600
600
600
600
600
600
600
630
630
630
630
630
630
700
700
700
700
700
750
750
750
750
750
750
800
800
800
800
800
800 900
900
900
900
900 1000
1000
1000
1000
1000
1000
1100
1100
1100
1100
1100
1200
1200
1200
1200
1200
1200
1200
1250
1250
1250
1250
1250
1250
1500
1500
1500
1500
1500
1500
1600
1600
1600
1600
1600
1600 1900
1900
1900
1900
1900
1900
2000
2000
2000
2000
2000
2000
2200
2200
2200
2200
2200
2400
2400
2400
2400
2400
2400
2400
2500
2500
2500
2500
2500
2500
2500
3000
3000
3000
3000
3000
3000
3200
3200
3200
3200
3200
3600
3600
3600
3600
4000
4000
4000
4000
5000
5000
5000
6000
6000
6400
Universal Spare Trip Unit
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
EntelliGuard G circuit breakers will accept a Universal Spare
Trip Unit. This unique trip unit may be used in any
EntelliGuard G circuit breaker regardless of frame size,
sensor size, short circuit rating or whether the circuit breaker
is listed under UL 489, ANSI/UL 1066 or IEC 947 standards.
Should any circuit breaker’s trip unit fail to operate for any
reason, this one universal trip unit may be used as a
replacement.
Once an EntelliGuard TU trip unit, including the Universal
Spare Trip Unit, is associated with a specific EntelliGuard G
circuit breaker, it may only be used with that specific circuit
breaker. If swapping between EntelliGuard G circuit breakers
is required, a trip unit may only be swapped between circuit
breakers with equal sensor ratings, short circuit ratings and
standard listing. Before the circuit breaker may be used with
a swapped or new trip unit, the trip unit must be mapped to
the circuit breaker.
The Re-mapping procedure is done by Pressing
simultaneously the "Right", "Left", and "Up" Arrow all at the
same time (should be able to do with one hand). "BIM OK"
will be flashing in the upper left hand corner of the LCD
when this is performed. Another Method is to use Modbus
Command 107 "Upload BIM" Either procedure requires the
trip unit to be mounted to the breaker and control power be
provided to the trip unit from permanently connected
control power or a portable power supply via the front port.
Front 24VDC Power is provided by Either the GTUTK20 Test
Kit or the Portable Battery Pack, TVPBP and TVPBPACC.
All Universal Trip units have the following format G1X00----RXXXX. The middle 5 digits describe the trip unit protection
options and features.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
29
Table 3.18. Universal Spare Trip Unit Options
(User-Selected)
Feature
#
Option
1
Standard (Circuit Breaker Curves)
2
Standard and Fuse Curves
1
Standard
2
Extended Range
1
None
2
Standard (Internal GF)
3
Ground Input
Arc Flash
Protection
1
No RELT
2
RELT
1
Short Time and Ground Fault
Short Time, Ground Fault and
Instantaneous
1
None
2
Modbus
3
Profibus
1
Standard (ammeter)
2
Advanced (A, V, E and P)
3
Diagnostic (Advanced and WFC)
Example Universal Trip Cat#: G1X00L4T6MRXXXX
24-May-12 Section 3. EntelliGuard TU Trip Unit System
Universal Trip Units may be ordered with a limited set of
options. It is suggested that they be ordered with the widest
range of options used within a facility, as any unnecessary
functions can always be disabled or turned off (except for
Ground Fault) during set up by the user. The user-selected
options for the Universal Trip Unit are listed in Table 3.18.
Long Time
Instantaneous
Ground Fault*
Zone Selective
Interlocking
2
Communications
Metering
* Mains and ties in solidly grounded multiple source substations will usually
require ground input type ground fault protection. Feeders will use standard
internal ground fault protection.
Description: Universal EntelliGuard TU Trip unit for a
EntelliGuard G Breaker with LSIG, Zone Selective Interlocking
(Short Time, Ground Fault, Instantaneous), Modbus, Full
Metering, Waveform Capture, RELT and Bell Alarm with
Lockout/Manual reset
The EntelliGuard TU offers various protective and alarm relay
functions that may be displayed on the LCD screen,
assigned contact outputs or communicated serially (Table
3.19).
Protection relays may be set by the user to alarm, trip the
circuit breaker or both. Alarms and trips are displayed on the
local LCD trip and communicated serially. Alarms may also
be assigned to one of two output contacts. The Trip Alarm
settings are independently set for each relay function.
This function compares the highest or lowest phase voltage
with the average of all three phases and initiates a trip if the
difference exceeds the set point. The true RMS voltage is
computed for each phase (Table 3.20).
DET-653C EntelliGuard® G Circuit Breaker Application Guide
31
Current Unbalance Relay
Table 3.21. Current Unbalance Settings
Item
Options
pickup
increments of 1%.
zero (0) will disable the relay.
Under Voltage Relay
Under Voltage Relay Zero-Volt Trip Enable
Table 3.22. Under Voltage Settings
Item
Options
pickup
increments of 1%.
User adjustable from 1sec to 15sec in
to zero (0) will disable the relay.
Over Voltage Relay
Table 3.23. Over Voltage Settings
Item
Options
pickup
increments of 1%.
to zero (0) will disable the relay.
Power-Reversal Relay
Table 3.24. Power-Reversal Settings
Item
Options
pickup
in increments of 10 kW.
zero (0) will disable the relay.
Power-Direction Setup
Potential Transformer Primary Voltage
Potential Transformer Connection
Power Demand Intervals
Current Alarm
Trip Logic Inputs
24-May-12 Section 3. EntelliGuard TU Trip Unit System
This function compares the true RMS current in the highest
or lowest phase with the average of all three phases and
Power reversal
User adjustable from 10 kW to 1990 kW
initiates a trip if the difference exceeds the set point (Table.
3.21).
Power reversal
delay setting
User adjustable from 1sec to 15sec in
increments of 1sec. Setting this value to
Current unbalance
Adjustable from 10% to 50% in
This function selects the normal power flow direction for the
Current unbalance
delay setting
User adjustable from 1sec to 15sec in
increments of 1sec. Setting this value to
breaker, either from line to load or from load to line. This
direction setup also affects the sign of the normal power
metering displays.
This function measures the true RMS voltage in all phases
and initiates a trip if any phase voltage drops below the set
point.
The Trip Unit gets its voltage input from an externally
mounted central module, called a Voltage Conditioner. The
Voltage Conditioner is wired to each trip unit in a line-up.
Voltage Conditioner Cat#: PLVC1G01
This function determines if the relay trips when all threephase voltages drop to zero volts. Uses the same timing set
for the Under-Voltage Relay (Table. 3.22).
Select the appropriate potential transformer connection,
either line-to-line (Ph-Ph) or line-to-neutral (Ph-N).
This function sets the power demand interval, which can be
Under voltage
Adjustable from 50% to 90% in
in the range of 5min to 60min, in steps of 5min. This setpoint specifies the time interval for power demand
Under voltage
delay setting
increments of 1sec. Setting this value
This function measures the true RMS voltage in all phases
and initiates a trip if any phase voltage exceeds the set
point. See Table. 3.23.
Over voltage
Over voltage delay
setting
User adjustable from 110% to 150% in
User adjustable from 1sec to 15sec in
increments of 1sec. Setting this value
This function measures the direction of power flow through
the breaker and initiates a trip if a sufficient magnitude of
reverse power is detected (Table. 3.24).
averaging. The trip unit calculates a rolling average of
breaker power over this time interval.
The Trip unit provides two types of current alarm: Current
Alarm 1 and Current Alarm 2. The current alarm’s ON/OFF
pickup settings are user adjustable from 0.5 to 1.0 xIn in
steps of 0.05. The trip unit does not allow the current alarm
OFF set-point to be set above the ON threshold. If the
highest measured phase current goes above the current
alarm 1 or current alarm 2 ON set-point, and then remains
above the set-point for more than 60sec, the output will
close if assigned to either of these alarms. If the current falls
below the current alarm 1 or current alarm 2 set-point for
more than 60sec, the output, if assigned to the current
alarm, will open. This is a definite time function with a 60s
delay and a 60sec cool down period. Both periods are fixed.
The trip unit is able to receive two hardwired input signals.
Either can be a 24Vac or Vdc signal. The inputs can be
assigned to three main functions:
DET-653C EntelliGuard® G Circuit Breaker Application Guide
32
Table 3.25. Input Assignments Possible
Input
Assignment
Summary Description
OFF
No action taken.
TRIP
Will cause the circuit breaker to trip
Input causes the unit to use the RELT set-
via serial communications.
Output contacts remotely.
OFF
No action taken.
TRIP
Will cause the circuit breaker to trip
Output contacts remotely.
Outputs for EntelliGuard G Circuit Breakers
Table 3.26. Output Configuration
Function
Group #
Summary Description
Closes when GF alarm is activated.
Over-current trip
Over-voltage trip closes the relay.
Closes relay when Reduced Let
or 2.
Any protective
Closes relays when protective the
Exceeding current alarm pick-up
Exceeding current alarm pick-up
Health status. NO
communication
Relay contact will change state
Waveform Capture
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
Table 3.25 shows the assignment for the inputs.
RELT
1
RESET
2
RESET
point as long as input is active. Note: RELT
must be set to REMOTE at the Trip HMI or
Input causes Output Contacts (non RELT)
to open. This will also clear the event
information from the front screen.
Enables the ability to open the Alarm
Input causes Output Contacts (non RELT)
to open. This will also clear the event
information from the front screen.
Enables the ability to open the Alarm
Note: When RELT is Optioned, Input1 is dedicated to RELT.
Contacts are rated for 30 VDC/25 VAC MAX, 1 Amp.
The number of outputs available varies by breaker. The
EntelliGuard G circuit breaker has three. These outputs are
relay contact outputs to secondary disconnect. Each output
can be configured per Table 3.26.
When a fault has taken place, it is important to visualize the
event. The Waveform Capture option included in the
advanced trip unit can track and visualize any fault event.
The device tracks eight cycles, four before and four after the
event, with resolution of 48 samples per cycle at 60Hz and
stores the results in memory. It registers events in all three
phases and the neutral. After the event, the waveform is
stored in COMTrade format and can be accessed by using
the waveform client module of the Enervista software. When
the upload into this software is complete, the tripuUnit will
reset this function and be available to register the next
event.
GF alarm 1
(GF, INST, LT, ST)
RELT on 7
relay
Current alarm 1 4
Current alarm 2 5
or NC may be
assigned to Health
OK via serial
Relays 1 or 2.
2
Relays 1 or 2.
Through Energy Instantaneous
pickup setting is enabled. Relays 1
DET-653C EntelliGuard® G Circuit Breaker Application Guide
34
Table 3.27. EntelliGuard Trip Unit Summary (continued)
Feature
Characteristic
Specification
Accuracy (at 100%)
Pick Up Range
0.1/0.2 – 10
-
External Zero Seq. (Gnd Return) CT
Input
1A = 100%
-
Delay Band Range
0.042/0.058-0.417/0.0917sec
-
Delay Bands
9/7/2015
-
I2t Slopes
2
-
I4t Slopes
1
-
GF Alarm Option
yes
-
Short time
yes
-
Ground Fault
yes
-
Separate ZSI Band Settings
yes
-
Instantaneous
yes
-
Current Unbalanced
10% - 50% difference between highest
steps
2%, ±0.1sec on delay
Over Voltage
110% - 115% of line voltage in 1%
Steps; 1-15sec delay in 1sec steps
2%, ±0.1sec on delay
Under Voltage
30% - 85% of line voltage in 1% Steps;
1-15 Second Delay in 1 sec steps
2%, ±0.1sec on delay
Voltage Unbalance
10% - 50% difference between highest
steps
2%, ±0.1sec on delay
Power Reversal
Line to Load OR Load to Line, From 10
to 990kW in 10kW steps
2%
Current Level (Alarm/Load
Management)
2
-
Current (A)
A, B, C & neutral
0000 Resolution, 2%
Voltage (V)
A, B, & C
0000 resolution, 2%
Real Power (kW)
A, B, C and total
000.000 resolution, 4%
Reactive Power (KVAr)
A, B, C and total
000.000 resolution, 4%
Apparent Power (kVA)
A, B, C and total
000.000 resolution, 4%
Energy (KWh)
A, B, C and total
000.000 resolution, 4%
Frequency (Hz)
yes
00 resolution, 1 cycle
Real Demand (kW)
total
000.000 resolution, 4%
Power Factor (%)
A, B, C
00 resolution, 4%
Peak Power Demand (KW)
A, B, C
000.000 resolution, 4%
Waveform Capture (COMTrade)
yes (requires PMCS)
-
Trip Operations Counter
yes
-
Temperature Monitoring
future
-
Event Log
last 10 events
-
Open Protocols (13)
Modbus RTU, Profibus DP
-
Front Port for Local Comm
yes – standard
-
Programmable Relays
4
-
Health Monitoring Relay
1
-
Universal Trip Plugs (16)
yes
-
Adjustable (20%-100%) Trip Plug
yes
-
Universal Spare Trip Unit
yes
-
Interchangeable Trip Unit
with = sensor & process
-
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
Ground Fault Protection
Zero Selective Interlock
& lowest phase compared to average,
1% steps; 1 to 15sec delay in 1sec
Protective Relays
& lowest phase compared to average,
1% steps; 1 to 15sec delay in 1sec
Metering, Diagnostic, and
Miscellaneous Functions
Serial Comm.
I/O
Flexibility
All Settings can be performed via the front of the trip unit. Also available is Free Set-up Software downloadable from
geindustrial.com Download and upload trip unit settings. Ability to download and view the waveform captured by the trip
unit. Also has the ability to store settings in an Offline file and then compare it to the current settings. Requires the
EntelliGuard TU Test Kit, GTUTK20.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
40
EntelliGuard® G Power Circuit Breaker
Section 4. Accessories
Introduction
Figure 4.1. Accessory Mounting
Motorized Spring Charging Unit
Circuit Breaker Closing Coils – Standard and Commanded
Table 4.1 Motor Operators
Envelope
Power
Consumption
Nominal Control
Voltage
IEC Range (85% to 110%)
ANSI Range
UL Range
(85% to 110%)
Cat No.
24Vdc/30Vdc
20.4V to 26.4V
-
20.4V to 26.4V
GM0124DR
48Vdc
40.8V to 52.87V
38V to 56V
40.8V to 52.87V
GM01048DR
60Vdc
51V to 66V
-
51V to 66V
GM01060DR
72Vdc
61.2V to 79.2V
-
61.2V to 79.2V
GM01072DR
110Vdc/130Vdc
106.25V to 137.5V
100V to 140V
106.25V to 137.5V
GM0111ODR
250Vdc
212.5V to 275V
200V to 280V
212.5V to 275V
GM01250DR
48Vac
40.8V to 52.87V
-
40.8V to 52.87V
GM01048AR
120Vac
102V to 132V
104V to 127V
102V to 132V
GM01120AR
240Vac
204V to 264V
208V to 254V
204V to 264V
GM01240AR
277Vac
235.5V to 304.7V
-
235.5V to 304.7V
GM01277AR
24Vdc/30Vdc
20.4V to 26.4V
-
20.4V to 26.4V
GM0224DR
48Vdc
40.8V to 52.87V
38V to 56V
40.8V to 52.87V
GM02048DR
60Vdc
51V to 66V
-
51V to 66V
GM02060DR
72Vdc
61.2V to 79.2V
-
61.2V to 79.2V
GM02060DR
110Vdc/130Vdc
106.25V to 137.5V
100V to 140V
106.25V to 137.5V
GM0211ODR
250Vdc
212.5V to 275V
200V to 280V
212.5V to 275V
GM02250DR
48Vac
40.8V to 52.87V
-
40.8V to 52.87V
GM02048AR
120Vac
102V to 132V
104V to 127V
102V to 132V
GM02120AR
240Vac
204V to 264V
208V to 254V
204V to 264V
GM02240AR
27Vac
235.5V to 304.7V
-
235.5V to 304.7V
GM02277AR
• Spring charge contact is power rated only, as shown below.
AC Ratings
DC Ratings
Voltage
Amps
Voltage
Amps
AC21-15A
24V
DC21-15A
AC23-10A
110-130V
DC21-10A
AC21-10A
250V
DC21-5A
AC23-5A - -
• Spring charge time = 3sec max.
24-May-12 Section 4. Accessories
A wide range of optional accessories are interchangeable
across all EntelliGuard G power circuit breakers, regardless
of nominal rating or envelope/frame size. As shown in Figure
4.1, each accessory incorporates easy-fit design features for
quick installation, either at the factory or in the field. NOTE:
Replacement accessories have an “R” at the end of the
catalog number as shown in the tables. All Coils are
Conformal Coated for increased reliability in humid/damp
environments
The unique motor/gearbox unit is specially designed to
operate with the full range of EntelliGuard G breakers. It is
easily installed with three heavy-duty bolts. After a breaker
close operation, the unit automatically recharges the spring
and makes it ready for immediate re-close should the need
arise. High speed recharging ensures that the springs are
fully charged within approximately three seconds following
a release. All electrically operated (EO) ANSI/UL breakers are
equipped with “Spring Charged” contacts for status
indication (Table 4.1).
Two, easy-to-fit, clip-on closing coil options with simple,
plug-in connections are available. Both options offer
electrical remote release of the spring charged closing
mechanism. Both options include a standard anti-pump
safety feature ensuring that the close signal must be
released before further close commands are allowed. The
Command Close Coil additionally provides for local breaker
close and remote breaker close over communications via
the EntelliGuard Trip Unit (Table 4.2).
DC – 300W
1
AC – 350VA
DC – 480W
2 and 3
AC – 560VA
110-130V
220-240V
• Recommended fuse amps: contact factory.
• Duty cycle = 2/min.
• Envelope 1 motors: running VA ~ 300VA; inrush = 2 to 3 times.
• Envelope 2 and 3 motors: running VA ~ 450VA; inrush = 2 to 3 times.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
41
Table 4.2. Closing Coil Characteristics
Type
Power
Consumption
Nominal Control
Voltage
Catalog
Number
24Vdc
GCCN024DR
48Vac/dc
GCCN048R
60 to 72Vdc
GCCN060DR
110/130/120Vac
GCCN120R
220Vdc/240Vac
GCCN240R
250Vdc/277Vac
GCCN277R
Command
24Vdc
GCCC024DR
48Vac/dc
GCCC048R
60 to 72Vdc
GCCC060DR
208Vac
GCCC208AR
Command Operation Module
Shunt Trip
Table 4.3. Extended Range Shunt Trip for UL Ground Fault
and ANSI DC Rating Applications.
Nominal Control Voltage
Catalog Number
24Vdc
GSTG024DR
48Vac/dc
GSTG048R
70/72Vdc
GSTG072DR
110Vdc/120 Vac
GSTG120R
125 Vdc
GSTG125DR
208 Vac
GSTG208AR
240 Vac
GSTG240R
250 Vdc/277 Vac
GSTG250R
Status Indication Switch (Coil Signaling Contact)
Table 4.4. Coil Signaling Contact Module
Type and
Configuration
Rating
Cat. No.
120Vac
6A
250Vac
6A
125Vac
0.5A
250Vdc
0.25A
AC
125Vac
0.1A
DC
30Vdc
0.1A
(1NO contact each)
Under Voltage Release (UVR) with Fixed Time Delay
Table 4.5. UVR Operating Characteristics
Power
Consumption
Nominal Control
Voltage
Catalog
Number
24 Vdc
GUVT024DR
24/30Vdc
GUVT030DR
40Vdc; 48Vac/dc
GUVT048R
60Vdc
GUVTO60DR
120 Vac
208Vac
GUVT208AR
220Vdc/240Vac
GUVT240R
250Vdc/277Vac
GUVT277R
24-May-12 Section 4. Accessories
DC: 350W,
20 W (sealed)
Closing
Coil
Operated
Closing
Coil
• Duty cycle = 2/min.
• Closing coil inrush = 350VA.
AC: 350W
(inrush),
20W (sealed)
DC: 350W,
20W (sealed)
AC: 350W
(inrush),
20W (sealed)
208Vac GCCN208AR
110/130/120Vac GCCC120R
This module energizes the closing coil to cause the breaker
to close whenever control power is applied to the accessory
and when commanded from the breaker trip unit or breaker
front panel push button (electrical closing.)
Energizing the shunt trip (ST), via local or remote input, will
instantaneously activate the circuit breaker mechanism,
ensuring a rapid open operation. The shunt trip is
continuously rated and does not require an auxiliary switch
in series with the coil. The shunt trip is a straightforward,
field installable accessory available in wide range of
voltages. See Table 4.3.
A plug-in module is available to provide status indication via
the secondary disconnects and trip unit. Coil Signaling
Contacts are available for closing coils, shunt trips and under
voltage releases (Table 4.4). Contact is mounted on top of the
Accessory Device. One of the low signal (Hi-Fi) contacts is
always wired to the tip Unit.
AC
1 Power rated +
1 Low signal (Hi-Fi)
DC
GCSP1R
(1NO contact each)
2 Low signal (Hi-Fi)
AC 125Vac 0.1A GCSP2R
The UVR instantaneously activates the circuit breaker trip
mechanism when the source voltage drops below the low
voltage threshold. The UVR is also a simple, field installable
device. NOTE: This accessory acts as a permissive; it is a novoltage/no-close device. The circuit breaker cannot be
closed (manually or electrically) unless the undervoltage
release coil is energized above the required threshold. The
undervoltage release with fixed time delay is specifically
intended for applications where a delay period (ride-through)
is required due to potential voltage events. The delays are
50msec when system voltage drops to 50% and 20msec
when system voltage drops below 50% (Table 4.5).
DET-653C EntelliGuard® G Circuit Breaker Application Guide
42
Time Delay Module (TDM) for UVR (Externally Mounted)
Figure 4.2. Time Delay Module
Table 4.6 TDM Characteristics
Nominal Control Voltage
Catalog No.
48Vdc
GTDM048D
48Vac
GTDM048A
60Vdc
GTDM060D
125Vdc
GTDM120D
120Vac
GTDM120A
208Vac
GTDM208A
240Vdc
GTDM240D
240Vac
GTDM240A
250Vdc
GTDM250D
277Vac
GTDM277A
Remote Operation Coil Combination
Table 4.7. Remote Operation Coil Combination
Combination
Coil Position on Fascia (from left)
1 2 3
4
1
-
shunt
CC
UV 2 shunt
shunt
CC
UV 3 shunt
UV
CC
UV
Ready To Close Contact
Table 4.8. Ready To Close Contacts (1 NO)
Rating
Description
Catalog
Number
high fidelity/secondary
disconnect
power rated/secondary
disconnect
Auxiliary Switches
Table 4.9. Auxiliary Switches
Contact Configuration
Cat. No.
Power rated (3NO+3NC)
GAUX3R
(2NO+2NC)
Power rated (8NO+8NC)
GAUX6R
(4NO+4NC)
Table 4.10. Auxiliary Switch Ratings and Secondary
Disconnect Points
Contact Configuration
Power
Rated
Hi-Fi
Cat. No.
Power rated
(3NO+3NC)
A14 - A25,
B17 - B26
Power rated (4NO+4NC) +
(4NO+4NC)*
A14 - A25,
B25 - B26
24-May-12 Section 4. Accessories
The de-energized operation of the Undervoltage release can
be delayed. This optional, externally mounted module has an
adjustable time delay of 0 sec to 3 sec. The device can be
implemented to prevent undesired breaker tripping due to
momentary voltage interruptions and is connected in series
with the Undervoltage release. The time delay is in addition to
the time delay from the breaker mounted UVR accessory. The
time delay module starts counting at 50% of rated voltage
(Fig. 4.2 and Table 4.6).
These contacts, as shown in Table 4.8, indicate that the
following conditions are met and the circuit breaker can be
closed:
• The circuit breaker is open.
• The closing springs are charged.
• The circuit breaker in not locked/interlocked in open
position.
• There is no standing closing signal.
• There is no standing opening signal.
Each breaker accepts a maximum of four coils in the
combinations shown in Table 4.7. The four positions can be
filled by the following four devices: one Close Coil, one Shunt,
one UVR, and the final fourth position can either be a Shunt
Trip or a UVR. All coils are mounted from the front and snap
onto the mechanism after the fascia is removed.
All Coils are
Conformal Coated for increased reliability in humid/damp
environments.
120Vac 6A
AC
250Vac 6A - GRTC2R
125Vdc 0.5A
DC
250Vdc 0.25A high fidelity/trip unit GRTC3R
GRTC2R
GRTC1R
Auxiliary switches indicate breaker main contact position.
They change their state in the same time sequence as the
breaker main contacts. See Tables 4.9 and 4.10 for available
combinations and ratings, and Tables 4.11 through 4.14 for
contact information.
Power rated (3NO+3NC) + low signal (Hi-Fi)
Power rated (4NO+4NC) + low signal (Hi-Fi)
GAUX5R
GAUX8R
A14 - A25 N/A GAUX3R
Power rated (3NO+3NC) +
low signal (Hi-Fi)
(2NO+2NC)
DET-653C EntelliGuard® G Circuit Breaker Application Guide
44
Table 4.14. Power Rated (4NO/4NC) + Low Signal (Hi-Fi) (4NO/4NC) (Ref Drawing 10099234)
Normally Open
Normally Closed
Switch Contact
Secondary
Disconnect
Connector
Switch Contact
Secondary
Disconnect
Connector
1
A25
3
A19
Power
Rated
2
A24 4 A18 5 A23 7 A17 6 A22 8 A16 9 A21
11
A15
10
A20
12
A14
13
B26
15
B13
14
B25
16
B12
17
B24
19
B11
Hi-Fi
18
B23
20
B10
21
B22
23
B9
22
B21
24
B8
25
B20
27
B7
26
B19
28
B6
29
B18
31
B5
30
B17
32
B4
Circuit Breaker - Key Interlock Facility
Table 4.15. Key Interlocks and Door Interlocks
Description
Catalog Number
(breaker mounted)
(breaker mounted)
(cassette mounted)
(cassette mounted)
Door interlock (left side)
GLHD
Door interlock (right side)
GRHD
Figure 4.3. Breaker-Mounted Key Interlock
A
A Key interlock mounting locations
Figure 4.4. Cassette-Mounted Key Interlock
A
A Key interlock mounting locations
24-May-12 Section 4. Accessories
PL1
PL2
PL4
PL3
• 15A max. current, 440V max.
This option supplies factory-installed key interlock
mounting provisions (baseplates and mechanism) on the
front of the breaker fascia. Key interlocks ensure that a
circuit breaker cannot be closed unless the dedicated key
has been inserted and secured within the lock. Circuit
breakers accept ready-to-fit interlocking device kits such
as Castell, Ronis, Kirk and Profalux for installation
between related, separate circuit breakers. NOTE: Locks
and keys are not supplied by GE. Please order separately
from your local supplier (Table 4.15 and Figs. 4.3 and 4.4).
PL5
PL6
PL8
PL7
• Kirk Keys for Fixed Breaker: CN22. Kirk Keys for Cassette:
KCAMXXX105 (Extended), KCAMXXX11S (Withdrawn). S
indicates that the key designation (A,B, etc.) is to be
stamped on the lock and the key.
• Ronis: Type 1104B lock with standard key, 1/4 in. turn to
trap the key, compulsory spindle size.
• For drawout breaker applications, key interlocks can be
Available as an option for mounting within the base of the
cassette/substructure, the carriage position switch provides
six single-pole changeover contacts (single pole, double
throw) for local or remote electrical indication of the circuit
breaker status: CONNECTED, TEST and DISCONNECTED. The
DISCONNECTED position is indicated only when minimum
isolating distances between contacts on both the main and
auxiliary circuits have been achieved. This option is in
addition to the mechanical indicators, which are fitted as
standard. When installed, the carriage switch is IP2X
protected. For use with drawout breakers/cassettes Tables
4.16 and 4.17).
2 Way –
Type A
1 from 3
Type B
2 from 3
Type C
2
6
6
withdrawable
fixed
withdrawable
fixed
withdrawable
fixed
AC
DC
The drawout mechanism allows the breaker to be racked in
four distinct positions (CONNECTED, TEST, DISCONNECTED,
WITHDRAWN).
Available for fixed and draw-out circuit breakers, these units
enable the direct interlocking of EntelliGuard G circuit
breakers, either mounted side-by-side or stacked. The
interlocking mechanisms are connected by a specially
designed cable or rod in a 1 from 2, 1 from 3, and 2 from 3
configuration, and any mix of current ratings/pole
configurations can be accommodated Table 4.18).
1 from 3
Way –
• Contact factory for availability.
4
withdrawable
Standard cable lengths are shown in Table 4.19. (Cables
ordered separately. Please contact our technical customer
service department if longer length is required.)
• Contact factory for availability.
Mechanical interlocks can be fitted to electrical systems and
can link two and/or three circuit breakers. Any nominal
rating, frame size, number of poles or type (fixed pattern or
draw-out) can be interlocked.
Table 4.25. Wiring Schematic for Block-A (Three Layer Secondary Disconnect with Basic GTU and Basic Accessories)
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
A13
RTC NO
RTC NO
UV2
UV2
Max. Current (I)
14.8A
14.8A
10A
10A
1.9A
1.9A
1.9A
1.9A
1.9A
1.9A
1.9A
1.9A
1.9A
Max. Voltage (V)
440V
440V
240V
240V
440V
440V
440V
440V
440V
440V
440V
440V
440V
A14
A15
A16
A17
A18
A19
A20
A21
A22
A23
A24
A25
A26
Max. Current (I)
15A
15A
15A
15A
15A
15A
15A
15A
15A
15A
1A
15A
-
Max. Voltage (V)
A27
A28
A29
A30
A31
A32
A33
A34
A35
A36
A37
A38
A39
Max. Current (I)
Max. Voltage (V)
25Vac
25Vac
25VAC
25Vac
24-May-12 Section 4. Accessories
The Bell Alarm provides remote indication that the circuit
breaker has opened because of an electrical fault. The
Lockout feature is integral to the trip unit. When a Bell Alarm
is supplied with the breaker, the Trip Unit dial is set and
locked to the manual position. In order to re-close the
breaker, the Lockout button must be pushed in/reset on the
Trip Unit 1-Form C contact (Tables 4.21 and 4.22).
AC
DC
Factory-installed on the motor, this auxiliary switch indicates
that the circuit breaker is charged and is standard with the
spring-charging motor (Table 4.23).
AC
DC
250Vac 6A
125Vdc 0.5A
GSCC1R
Inputs and outputs to the circuit breaker are wired through
secondary disconnects located on either the top or the side
(Envelope 1 only) of the breaker. The plug-style secondary
disconnects engage mating disconnects in the breaker
cubicle when the breaker is in the TEST or CONNECT position.
Up to 78 points are available so that all breaker accessories
can be wired to dedicated disconnect points (Tables 4.24
through 4.29). Block B is ordered separate for cassettes, Cat.
No. GSDWTR.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
48
Table 4.26. Wiring Schematic for Block-B
(Three Layer Secondary Disconnect to be Added for GTU with Full I/O and Additional Accessory Signals)
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
B11
B12
B13
NC7
NC7
Max. Current (I)
<50mA
<50mA
<50mA
10A/15A
10A/15A
10A/15A
10A/15A
15A
15A
15A
15A
15A
15A
B14
B15
B16
B17
B18
B19
B20
B21
B22
B23
B24
B25
B26
NO7
Max. Current (I)
15A
15A
15A
Max. Voltage (V)
440V
440V
440V
440V
B27
B28
B29
B30
B31
B32
B33
B34
B35
B36
B37
B38
B39
out+
out-
in+
in-
GND
ISO
Volt-IN
Max. Current (I)
<50mA
<50mA
<50mA
<50mA
<500mA
<500 mA
<50mA
<50mA
<50mA
<500mA
<50mA
<50mA
<50mA
Max. Voltage (V)
Table 4.27. Wiring Schematic for Block-C (Internal to the breaker, not used by customer.)
(Two Layer Intermediate Secondary Disconnect at the Top for the Side Mounted Secondary Disconnect.)
The EntelliGuard TU Trip Unit provides a non-core CT input
for zero sequence or residual summation current. The
expected ratio is 1A = 100%.
The Neutral Rogoswki CT’s are used to measure the Neutral
Current and is required when Internal Ground Fault is
selected on the trip unit. There are two types available:
1. Encased with Terminal Screws: The Rogowski coil is
encased with two terminal screws. No additional
mounting hardware is required as the encasing is
molded to the mounting dimensions. Table 4.30
2. Loose Rogowski Coil with separate mounting
hardware: The coil and mounting hardware are
separate. The coil comes with the two wire leads
for connection to a terminal block. Table 4.30a
1
2
1
An optional complete IP54 front door panel is available
when a higher degree of protection is needed (Table 4.31).
Used with either manual or motor charged circuit breakers,
the counter provides an accurate record of the cumulative
number of complete breaker closing operations (Table 4.31).
DET-653C EntelliGuard® G Circuit Breaker Application Guide
56
Front Flat Terminations
Table 4.35. Optional Front Flat Terminations
Description
Catalog
Number
Drawing
Qty.
Env1 800 - 2000A, Type N&H, Flat Front UL489
Env3 4000-6000A Flat Front UL Fixed 4 Pole
24-May-12 Section 4. Accessories
The EntelliGuard G Fixed mounted breaker comes standard with Back Connected Terminations. Optional Front Flat
terminations are available for front access mounting (Table 4.35).
Fixed 3 Pole Breaker Bus Bar Terminations
(Top/Bottom)
Env1 800 - 2000A, Type N&H, Flat Front UL489
Fixed 4 Pole Breaker Bus Bar Terminations
(Top/Bottom)
Env2 800A - 3000A Flat Front UL489 Fixed 3
Pole Breaker Bus Bar Terminations
(Top/Bottom)
Env2 800A - 3000A Flat Front UL489 Fixed 4
Pole Breaker Bus Bar Terminations
(Top/Bottom)
GBB1TBF3
GBB1TBF4
GBB2TBF3
GBB2TBF4
3
4
3
4
Env3 4000-6000A Flat Front UL Fixed 3 Pole
Breaker Bus Bar Terminations (Top/Bottom)
Breaker Bus Bar Terminations (Top/Bottom)
Note: Please visit GE Energy's website for information regarding terminations for DC switches UL 489B.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
57
Table 4.36. Cluster
Envelope
Description
Catalog
Number
Drawing
Qty.
1
2
3
24-May-12 Section 4. Accessories
36 finger (95x20 mm) Qty 1 G20NCLS
36 finger (95x20 mm) Qty 1 G20MCLS*
36 finger (95x15 mm) Qty 1 G32ECLS
1
1
1
36 finger (95x15 mm) Qty 1 G64LCLS
1
* GE AKD20 Envelope 2 breakers with Characters 5 & 6 = ED or MD, regardless of amperage size, all use GBB232TBD Cluster Pad Assemblies
and G32ECLS Finger Clusters
DET-653C EntelliGuard® G Circuit Breaker Application Guide
58
Table 4.37. Cluster Pad
Envelope
Description
Catalog
Number
Drawing
Qty.
1
2
3
24-May-12 Section 4. Accessories
Cluster Pad ( set per phase) GBB120TBD
Cluster Pad ( single cluster) 2000A GBB220TBD*
Cluster Pad ( double cluster) 2500A-3200A GBB232TBD
Cluster Pad GBB360TBD
2
2
2
2
* GE AKD20 Envelope 2 breakers with Characters 5 & 6 = ED or MD, regardless of amperage size, all use GBB232TBD Cluster Pad Assemblies
and G32ECLS Finger Clusters
DET-653C EntelliGuard® G Circuit Breaker Application Guide
59
Figure 4.35. Terminations for DC Switches UL 489B
Remote Racker
Table 4.38.
Description
Catalog #
Remote Racker
EGGRRLV
Grounding/Earthing Device (IEC Only)
Table 4.39. Earthing Devices (IEC only)
Envelope
Current Rating
Poles
400 to 1600/3P
3
400 to 1600/4P
4
2000/3P
3
2000/4P
4
400 to 4000/3P
3
400 to 4000/4P
4 3 3200 to 6300/3P
3
3200 to 6300/4P
4
Rejection Device
24-May-12 Section 4. Accessories
The remote racking operator allows the user to move a draw
out circuit breaker between the CONNECT and DISCONNECT
positions via an electric racking gear head motor and the
Cassette housing the breaker. The remote racking operator
requires 115VAC, 60Hz control power. A control box
connected to the operator with a thirty-foot chord permits
control from a remote location.
All EntelliGuard G circuit breakers can be fitted with a
grounding/earthing device, which has a short circuit rating
equal to the breaker withstand rating. This permits either the
feeder cables or the busbar to be safely grounded and
locked during system maintenance operations (Table 4.36).
1
2
A factory-installed rejection feature prevents mismatching
breakers and cassettes/substructures. This prevents (a)
inserting a breaker with a lower rating into a higher rated
cassette/substructure and (b) inserting a higher rated
breaker into a lower rated cassette/substructure. Misinsertion Interlock catalog number is GREPM.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
62
Digit 6 – Mounting Type Poles
Designation
Mounting
Poles
Code
1
2
3
4
5
6
D
F
Digit 7 – Spring Charging Motor
Spring Charging Motor (EO)
Code
24/30Vdc
A
48Vdc
B
60Vdc
C
72Vdc
D
110/130Vdc
E
250Vdc
F
48Vac
G
120Vac
H
240Vac
J
277Vac
K
Blank/none*
X
Digit 8 – Closing Devices
Closing Coil Type
Code
A
B
48Vac/dc
C
60 – 72Vdc
D
E
208Vac
F
G
H
24Vdc
M
30Vdc
N
P
60 – 72 Vdc
Q
R
S
220Vdc; 240Vac
T
Blank/none
X
SELECT ONE DEVICE ONLY.
Digit 9 – Shunt Trip 1
Extended Range Shunt Trip (ANSI/UL)*
Code
M
P
Q
110/125Vdc; 120Vac
R
208Vac
S
220Vdc; 240Vac
T
V
X
SELECT ONE DEVICE ONLY.
24-May-12 Section 5. Catalog Numbering Guide
3
drawout
OEM
stationary
4, right
4, left
3
4, right
4, left
GE Equipment
• Right, Left indicates the location of the fourth pole, typically used to
switch the neutral.
• Stationary and drawout breakers come with back connected
terminations. Optional front flat terminations are available. See page 40.
• P type circuit breaker available only in 3-pole.
drawout 3
stationary 3
DC
AC
*An "X" (Blank/None) denotes a Manually Operated device (MO) Spring
Charge Contact, GSCC1, included with all Motor Operators.
• When a Spring Charging Motor is selected, a Closing Device must be
selected from Closing Devices for Digit 8, and a Shunt Trip Device must
be selected from Shunt Trip 1 Devices for Digit 9.
• Shunt Trip 1 with a coil voltage different from the Spring Charge Motor
may be user-selected.
24Vdc
30Vdc
Closing Coil
(CC)*
110Vdc/130Vdc; 120Vac
220Vdc; 240Vac
250Vdc; 277Vac
Command
Operated
Closing Coil
(CCC)**
48Vac/dc
110Vdc/130Vdc; 120Vac
208Vac
*The Closing Coil (CC) permits either local or remote release of the spring
charged closing mechanism by electrical operation.
**The Command Operated Closing Coil (CCC) includes an additional
anti-pumping safety feature to ensure that the electrical closing signal
must be released before further closure is attempted, a shut off is
initiated if the closing signal is maintained.
• Manual button through breaker cover is included as standard
assembly.
• When a Spring Charging Motor is selected (Digit 7), a Closing Device
must be selected from Closing Devices for Digit 8, and a Shunt Trip
Device must be selected from Shunt Trip 1 Devices for Digit 9.
•
24Vdc
48Vac/dc
70 – 72Vdc
250Vdc; 277 Vac
Blank/none
*The Extended Range Shunt Trip is specifically intended and required
for UL ANSI Ground Fault applications. The pick up range is 55-110%
of the ST coil voltage.
• When a motor is selected from the Spring Charging Motor (Digit 7)
DET-653C EntelliGuard® G Circuit Breaker Application Guide
63
Digit 10 – Under Voltage Release (UVR)
UVR with Fixed Time Delay *
Code
24Vdc
1
30Vdc
2
3
4
5
208Vac
6
220Vdc; 240Vac
7
250Vdc; 277Vac
8
X
SELECT ONE DEVICE ONLY.
Digit 11 – 2nd Shunt Trip or UVR
Type
Code
24Vdc
1
30Vdc
2
48Vac/dc
3
60 - 72Vdc
4
110Vdc/130Vdc; 120Vac
5
208Vac
6
220Vdc; 240Vac
7
250Vdc; 277Vac
8
24Vdc
M
48Vac/dc
P
70 - 72Vdc
Q
110/125Vdc; 120Vac
R
208Vac
S
240Vac
T
250Vdc
V
Blank/none
X
SELECT ONE DEVICE ONLY.
24-May-12 Section 5. Catalog Numbering Guide
48Vac/dc
60-72Vdc
110/130Vdc; 120Vac
Blank/none
*The UVR Shunt Trip with Fixed Time Delay is specifically intended for
applications where a delay period ('ride- through') is required due to
potential voltage events. The design delays are 50msec when system
voltage drops to 50% and 20 msec when system voltage drops below
50%.
• An optional External UVR Time Delay Module is available in a 1 - 3sec
delay.
•
2nd UVR with Fixed
Time Delay **
2nd Extended
Range Shunt Trip
(ANSI/UL)*
*The Extended Range Shunt Trip is specifically intended and required for UL
ANSI Ground Fault applications. The pick up range is 55-110% of the ST coil
voltage.
**The UVR with Fixed Time Delay is specifically intended for applications
where a delay period ('ride- through') is required due to potential voltage
events. The design delays are 50msec when system voltage drops to 50%
and 20msec when system voltage drops below 50%.
• An optional External UVR Time Delay Module is available in a 1 - 3sec
Aux. Switch, 3NO/3NC (PR) + 2NO/2NC
Low Signal (Hi-Fi)
Auxiliary Switch, 3NO+3NC
Aux. Switch, 3NO/3NC (PR) + 2NO/2NC
Low Signal (Hi-Fi)
= Command Operated Close Coil
= Coil Signaling Contact
= High Fidelity
= Power Rated
= Secondary Disconnect
*The 3NO/3NC scheme is STANDARD (INCLUDED, CODE 2) and is wired to Secondary Disconnect Block A, all other selections require Secondary Disconnect
Block B.
**In order to output the Coil Signaling status Hi-Fi via trip unit (options B, D, F, H, K, M, P,R, T, and V) a communications package must be selected in Advanced
Features (Digit 19; options 2, 3, 6, 7, 8, 9). This option requires Secondary Disconnect Block B.
**If a UL or ANSI Switch is selected in Digit 2 (C, D, M, S), the Hi-Fi via Trip Unit options are not valid (options B, D, F, H, K, M, P, R, T, V).
***For Side-mounted Secondary Disconnect Blocks, all options are available EXCEPT options 4 and 8.
• The term “Hi-Fi” refers to gold-plated contacts used for signal level outputs (10mA minimum - 100mA maximum, 5-30Vdc, 125Vac).
• If no devices were selected in Digit 8, 9, 10, 11 (Codes = "X"), then Options A - V are invalid.
• Options A-V are only valid if the corresponding device to be monitored by the Coil Signaling Contact (CSC) is selected in digits 8, 9, 10, 11.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
65
Digit 13 – Bell Alarm/Trip Annunciation
Bell Alarm and Trip Annunciation
Code
A
B
C
1
2
RTC Signal Rated (Hi-Fi) Contacts through Trip Unit**
3
BACL and RTC Power Rated Contacts on SD*
D
BACL and RTC Signal Rated (Hi-Fi) Contacts on SD*
E
BACL and RTC Signal Rated (Hi-Fi) through Trip Unit**
F
BACL, MOC and RTC Power Rated on SD*
G
BACL, MOC and RTC Signal Rated on SD*
H
Unit**
J
K
L
M
X
BACL = Bell Alarm Contact with Lockout
RTC = Ready To Close Contacts
Hi-Fi = High Fidelity
SD = Secondary Disconnect
**In order to output the RTC contact output via Trip Unit (options 3, F, J,
M) a communications pac
(Code 19/Step 16); this requires Secondary Disconnect Block B.
**If a UL or ANSI Switch is selected, the (Hi
valid (Options 3, F, J, M).
**RTC Through the Trip Unit is not a valid option for Switches. Bell Alarm
Contact with Lockout comes with the Trip
Enabled.
•
•
Digit 14 – Key Interlock
Key Interlock (Breaker Mounted)
Code
Castell Key Interlock
C
Kirk Key Interlock
K
Ronis Key Interlock
R
L
Device
1
2
3
Blank/none
X
•
•
• Locks and Keys are NOT Supplied by GE.
Digit 15 – Mechanical Interlocks
Mechanical Interlocks
Code
Blank/None DEFAULT
X
Mechanical Interlock - Type A
1
Mechanical Interlock - Type B
2
Mechanical Interlock - Type C
3
Mechanical Interlock - Type D
4
•
• Contact factory for availability.
24-May-12 Section 5. Catalog Numbering Guide
Bell Alarm Contact (1NO/1NC) with Lockout (BACL)
Mechanical Operations Counter (MOC)
Bell Alarm Contact (1NO/1NC) with Lockout and MOC
RTC Power Rated Contacts on SD*
RTC Signal Rated (Hi-Fi) Contacts on SD*
BACL, MOC and RTC Signal Rated (Hi-Fi) through Trip
MOC and RTC Power Rated on SD*
MOC and RTC Signal Rated on SD*
MOC and RTC Signal Rated (Hi-Fi) through Trip Unit**
Blank/none
kage must be selected in Advanced Features
-Fi Through Trip Unit) is not
Unit set to Manual LO
The term “Hi-Fi” refers to gold-plated contacts use for signal level
Option "B", “I”, “2”, “3”, “K”, “L”, “M”, and “X” are the only valid options
when a Switch is selected in Digit 2.
Pushbutton Padlock Device
Castell Key Interlock and Push Button Padlock
Kirk Key Interlock and Push Button Padlock Device
Ronis Key Interlock and Push Button Padlock Device
This option provides factory installed interlocking devices for
installation between separate circuit breakers (baseplates and
mechanism). This safeguard ensures that a circuit breaker cannot be
closed unless the dedicated key has been inserted and secured
within the lock.
If selecting a Draw Out Breaker (Digit 6), consider putting the Key
Interlock on the Cassette versus the breaker. This enables the ability
to swap breakers without having to change the key interlocks.
Some installations use multiple power sources that are required to supply
energy simultaneously, alternately, or, in a specified sequence.
EntelliGuard G Circuit Breakers can be used to interconnect these sources
and be electrically and mechanically interlocked to provide the necessary
transition and protection. Mechanical Interlocks are available for fixed and
draw out circuit breakers. The interlocks enable directly interlocking
breakers that are mounted side by side or in vertical stacks. The interlocks
consist of two components: (A) The factory-installed bracket fitted to the
breaker (fixed breakers) or the cassette (drawout breakers), and (B) The
field-installable interconnecting cables available in lengths of 1.0, 1.6, 2.0,
2.5, 3.0, 3.5 and 4.0m (ordered separately). Refer to Section 4 for
interlocking schemes.
Page 72
DET-653C EntelliGuard® G Circuit Breaker Application Guide
66
Digits 16 & 17 – Overcurrent Protection Package
Type
Over Current (OC) Protection Package
Code
LSI
L3
LSIG
L4
LSIGA
L5
LSIC
L6
LSICA
L7
LSIGDA*
L8
LSIGCDA*
L9
LSH
LC
LSHG
LD
LSHGA
LE
LSHC
LF
LSHCA
LG
LSHGDA*
LH
LSHGCDA*
LK
FROM 1/1/12:
INCLUDED IN L
TYPE TRIP
UNITS
JSI
J3
JSIG
J4
JSIGA
J5
JSIC
J6
JSICA
J7
JSIGDA* (S, G, A all switchable) (I, switchable ANSI only)
J8
JSIGCDA*
J9
JSH
JC
JSHG
JD
JSHGA
JE
JSHC
JF
JSHCA
JG
JSHGDA*
JH
JSHGCDA*
JK
XX
A
C
application: Zero Sequence Input of 1A = 100%)
D
G
H
I
J
L
S
CA
GA
GDA, GCDA = Ground Fault Trip and Ground Fault Alarm (all switchable, not UL Listed)
*Function Combination is NOT UL Listed.
• Option "XX" is the only valid option when a Switch is selected in Digit 2.
24-May-12 Section 5. Catalog Numbering Guide
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only)
Standard Range
Instantaneous
EntelliGuard G
ANSI/UL OC
Protection with
Fuse Settings
Extended Range
Adjustable
Instantaneous
Standard Range
EntelliGuard G
Instantaneous
ANSI/UL OC
Protection with
Fuse Settings
Extended Range
Adjustable
Instantaneous
NONE - (For Switch Only)
= Ground Fault, External Ground Fault, Alarm only
= External CT for ground fault detection (AKD20 application: input from external summing CTs, used for multiple source ground fault detection. OEM
= Defeatable/Switchable Ground Fault, not UL Listed
= Ground Fault Protection (GFP, 3-wire or 4-wire, internal summing)
= Extended Range Adjustable Instantaneous, (IOC, 2x-30x), not available in UL489 version of EntelliGuard G or any Legacy CB
= Standard Range Adjustable Instantaneous, (IOC, 2x-15x)
= Long Time (L, I2T) + Fuse Settings (I4T)
= Long Time (I2T, all trip unit)
= Short Time (Switchable if Instantaneous (I) protection is enabled)
DET-653C EntelliGuard® G Circuit Breaker Application Guide
67
Digit 18 – Zone Selective Interlocking (ZSI)
Zone Selective Interlocking
Code
Z
Z + IOC or HIOC ZSI; user selectable
T
X
Digit 19 – Advanced Features and Communications
Advanced Features and Communications
Code
Reduced Energy Let-Through (RELT)
1
Modbus Protocol + RELT
2
3
Monitoring + RELT, NO Communication
4
Monitoring + Relay Package + RELT
5
Monitoring + Data Acquisition, Modbus
Protocol + RELT
6
Monitoring + Data Acquisition, Profibus
Protocol + RELT
7
Monitoring + Data Acquisition + Relay Package,
Modbus + RELT
8
Monitoring + Data Acquisition + Relay Package,
Profibus + RELT
9
None
X
Digit 20 – Rating Plug
Rating Plug
Catalog Number
Code
150
GTP0150U0104
B
1100
GTP1100U1225
R
1900
GTP1900U2050
W
2500
GTP2500U2564
2
6000
GTP6000U6064
8
X
24-May-12 Section 5. Catalog Numbering Guide
ZSI, Short time and GF; user selectable
Blank/none
• ZSI selections require Secondary Disconnect Block B and 24Vdc control
power. Control power recommended for instantaneous ZSI.
Profibus Protocol + RELT
• .All Advanced Feature selections require Secondary Disconnect Block B
and 24Vdc control Power.
• Option "X" is the only valid option when a Switch is selected in Digit 2.
• RELT = Reduced Energy Let Through, requires dedicated input and output
on the CB Monitoring = Advanced Metering.
• Data Acquisition = Waveform Capture and Harmonic Analysis .
• In order to output the Coil Signaling status HiFi via trip unit (Digit 12,
Options B, D, F, H, K, M, P, R, T, and V) a communications package must
be selected in Advanced Features (Digit 19; options 2, 3, ,7, 8, 9). This
option requires Secondary Disconnect Block B.
• In order to output the RTC contact output via Trip Unit (Digit 13; Options
3, F, J, M) a communications package must be selected in Advanced
Features (Code 19/Step 16); this requires Secondary Disconnect Block B.
200 GTP0200U0204 C
225 GTP0225U0306 D
250 GTP0250U0407 E
300 GTP0300U0408 F
350 GTP0350U0408 G
400 GTP0400U0410 H
450 GTP0450U0612 I
500 GTP0500U0613 J
600 GTP0600U0616 K
700 GTP0700U0816 M
750 GTP0750U0820 N
800 GTP0800U0820 O
900 GTP0900U1020 P
1000 GTP1000U1025 Q
1200 GTP1200U1232 S
1500 GTP1500U1640 U
1600 GTP1600U1640 V
2000 GTP2000U2050 Y
2200 GTP2200U2550 Z
2400 GTP2400U2564 1
Notes: Non-automatic switches are provided
with no internal sensing or tripping mechanism
and cannot be applied above their respective
withstand levels. If a non-automatic device is
required at ratings above the available
switches is required, it is recommended that a
circuit breaker set with maximum settings be
employed using external control or protection
as required by the application.
X
X
X X
OEM Cassette – 3 Pole
OEM Cassette – 4 Pole
* P version available only in 3 pole.
** GE Equipment cassette designed specifically for AKD20 Switchgear.
= External CT for ground fault detection (AKD20 application: input from external summing CTs, used for multiple source ground fault detection. OEM
Application: Zero Sequence Input of 1A = 100%).
= Defeatable/Switchable Ground Fault NOT UL Listed.
= Ground Fault Protection (GFP, 3-wire or 4-wire, internal summing).
= Extended Range Adjustable Instantaneous, (IOC, 2x-30x), Only for ANSI EntelliGuard G.
= Standard Range Adjustable Instantaneous, (IOC, 2x-15x).
= Long Time (L, I2t) + Fuse Settings (I4t).
= Long Time (I2t, all trip unit).
= Short Time (Switchable if Instantaneous (I) protection is enabled).
DET-653C EntelliGuard® G Circuit Breaker Application Guide
73
EntelliGuard® G Power Circuit Breaker
Section 6. Application Data
Introduction
Key Features
UL1066 Low Voltage Power Circuit Breakers
UL489 Stored Energy Insulated Case Circuit Breakers
IEC Rated Circuit Breakers for IEC Equipment and
Applications
All Types
Ratings and Sizes
24-May-12 Section 5. Catalog Numbering Guide
The EntelliGuard G family of circuit breakers and related
switching devices is a truly global line of protection and
switching devices. It was designed from the ground up to
provide reliable protection and operation in a wide range of
power distribution systems. Combined with the EntelliGuard
TU family of trip devices, EntelliGuard G circuit breakers
provide superior protection and reliability with a maximum
of flexibility and a minimum of compromise for your power
protection and switching needs.
This section provides an overview of the circuit breaker’s
capability under UL 489 and UL 1066 standards.
There are three product families:
• 800-5000A frames in three physical sizes.
• 400-5000A sensors with rating plugs as low as 150A and
trip settings as low as 75A.
•Short circuit ratings as high as 150kA at 480V (tested at
508V).
• Withstand capability and selectivity as high as 100kA
• Continuously adjustable selective instantaneous as high
as 30X the circuit breaker’s rating.
• 800-6000A frames in three physical sizes.
• 400-6000A sensors with rating plugs as low as 150A and
trip settings as low as 75A.
• Short circuit ratings as high as 150kA at 480V.
• Withstand capability and selectivity as high as 100kA.
• Continuously adjustable selective instantaneous to 15X
on all but the largest circuit breakers.
•Draw-out and stationary mounted, 100% rated in most
sizes.
• 800-6400A frames in three physical sizes.
• 400-6400A sensors adjustable to 20% of sensor size.
• Short circuit ratings as high as 150kA at 440V, 100kA at
690V, 80kA at 1000V.
• Rated breaking capacity 100%, Ics = Icu for all frames.
• Withstand capability and selectivity as high as 100kA for
1sec.
•Continuously adjustable selective instantaneous as high
as 30X the circuit breaker’s rating.
• Stationary mounting capability with rear or front
• Draw-out mounting with cassette and automatic shutter
• Complete closed door operation capability – UL489,
• 3 and 4 pole configurations with the neutral on either
• Suitable for UL1008 transfer switch applications
• Alternate, settable and remote controllable
• Industry’s only fully controllable ZSI restrained and
• Industry’s only fully selective instantaneous trip with
• Field installable accessories with labels that may be
• Easily accessible terminal contacts at the top or side of
• Advanced protection algorithms that allow maximum
• Trip curves and algorithms to optimally accommodate
The EntelliGuard G family of overcurrent devices is available
in 3 or 4 pole versions, in 3 physical sizes referred to as
“envelopes” 1, 2 and 3. Four pole versions may have the
neutral on the right- or left-most pole. The envelope and the
number of poles are the main determinants for physical size
and the space the device will require when installed in
equipment or enclosures.
The circuit breakers and switches are further divided into
“frame” sizes. The frame sizes follow the guidelines defined
connections.
mechanism.
ANSI or IEC.
electrically operated circuit breakers, suitable for fast
throw-over or generator paralleling applications
to rack circuit breakers in and out while standing outside
the arc flash boundary.
side.
instantaneous pickup with positive feedback.
unrestrained settings.
selectivity enhancing ZSI capability.
seen through the circuit breaker’s escutcheon.
circuit breaker for use by installer – permanently labeled,
color coded and interlocked with harnesses for fast,
efficient, mistake-proof wiring.
selectivity and protection at the same time with
minimized need to sacrifice protection to get system
reliability or visa versa.
downstream fuses, older slower power circuit
breakers, ultra fast current limiting devices or other
EntelliGuard circuit breakers without sacrificing any
more protection than absolutely necessary to achieve
significant selectivity.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
74
Short Circuit Interrupting Ratings
Figure 6.1. Short Circuit Rating Adjustment Equation
Table 6.1. First Half-Cycle Peak at Specific Fault X/R
Ratios (excerpted from UL489)
Power Factor
X/R ratio
Maximum Peak at 1/2
Cycle
17%
5.8
2.26
18%
5.5
2.23
19%
5.2
2.21
20%
4.9
2.18
100%
0.0
1.41
Withstand Ratings, Selective Waveform Recognition-,
RELT- and Override-Instantaneous Protection
24-May-12 Section 6. Application Data
under the applicable UL, IEC and ANSI standards as shown in
the various ratings tables. Switchgear equipment is typically
sized to match the frame ratings and physical size.
Switchboards may be sized to match the installed circuit
breaker’s sensor rating.
Equipment cubicles or device mounting provisions are
normally mechanically interlocked such that equivalent
frames may be installed within a specific cubicle or space.
When exchanging circuit breakers for maintenance
purposes, care should be exercised so that there is no
attempt to install a circuit breaker with a rating higher than
what the equipment was designed to accommodate, even if
the physical size seems similar.
The EntelliGuard G family of UL devices is available with short
circuit ratings as high as 150kA at 480V, and withstand
ratings as high as 100kA. UL1066 and ANSI C32 ratings are
based on various tests performed at rated voltage plus 6%.
Hence it is common to see low voltage circuit breakers listed
as suitable for 254, 508 and 635V. Any UL 1066 listed device
must be tested at these higher voltages if listed at the
normal nominal voltage of 240, 480 and 600V. UL489 circuit
breakers are tested at the nominal voltage. Both circuit
breakers are subject to dielectric testing after interrupting
faults to ensure the ability to sustain voltage.
Short circuit interrupting ratings are a measurement of the
circuit breaker’s ability to interrupt a particular value of fault
current at a maximum power factor (also expressed as X/R
ratio). For fault currents above 20,000A RMS, UL489 circuit
breakers are tested at 20% power factor and UL1066 circuit
breakers are tested at 15% power factor. When fault
currents have power factors lower (higher X/R) than the test
power factor, the circuit breaker’s short circuit rating must
be adjusted to compensate for the fault’s lower PF. The
adjustment is performed as shown in Figure 6.1. Table 6.2
shows various asymmetrical peak ratios for various power
factors and X/R ratios. A power factor of 100% yields a
symmetrical fault and hence the peak over RMS ratio is 1.41.
Consider a system where the fault current has an X/R ratio
of 10 and the calculated RMS value is 92,000. A circuit
breaker with a stated interrupting capability of 100,000 is
being considered. Since the fault’s X/R ratio is higher than
the UL489 rating at 4.9, the circuit breaker’s rating, 100kA,
must be multiplied by 2.18/2.46 (from Table 6.1). The ratio
is .89. Hence, the circuit breaker must be considered as if it
is only rated for 89,000A. The UL489 100kA rated circuit
breaker is not suitable for the application because its derated 89kA rating is below the available fault current of
92kA.
Consider an equivalent UL1066 circuit breaker tested at an
X/R ratio of 6.6. The UL1066 circuit breaker must be derated by 2.31/2.46, which yields 0.94. The UL1066 circuit
breaker is then de-rated to 0.94 times 100kA. The UL1066
circuit breaker is rated higher than the available fault
current of 92kA and hence could be considered for the
application.
Instantaneous adjustment capability for any circuit
breaker is intrinsically connected to the circuit breaker’s
withstand rating and the trip system’s sensing methods. In
the case of the EntelliGuard G family of circuit breakers,
high withstand ratings allow for a broad range of
instantaneous trip options. The trip system relies on high
accuracy air core sensors not encumbered by the
saturation concerns associated with iron core sensors
used in many other trip systems. This allows the
DET-653C EntelliGuard® G Circuit Breaker Application Guide
75
Close and Latch Ratings and Making Current Release
(MCR) Instantaneous Trip
Table 6.2. EntelliGuard G Circuit Breaker Close and Latch
Ratings, UL489 Listed
Envelope
Amps
Type
Close and Latch
Rating (kA)
1
800 - 2000
S, N, H, P
42
Table 6.3. EntelliGuard G Circuit Breaker Close and Latch
Ratings, UL1066 Listed
Envelop
e
Amps
Type
Close and Latch
Rating (kA)
1
800 - 2000
S, N, H, P
42
2
800 - 3000
N, E, M
65
M, B
85
24-May-12 Section 6. Application Data
EntelliGuard trip system to take full advantage of the
circuit breaker’s withstand rating, providing adjustable
settings and full selectivity right up to the circuit breaker’s
high withstand level. EntelliGuard G circuit breakers, in
conjunction with EntelliGuard TU trip units with GE’s unique
“selective instantaneous” algorithm, allow selectivity
capability as high as 100kA with instantaneous on, and set
at surprisingly low values. The EntelliGuard family of
devices provides multiple solutions for your selectivity and
protection problems.
Low Voltage Power Circuit Breakers (LVPCBs) listed to
UL1066 have defined fault current withstand currents.
EntelliGuard G UL489 Insulated Case Circuit Breakers also
have substantial withstand ratings. The stated withstand
current (Icw) allows the instantaneous protection of
LVPCBs to be turned off or set at very high values, and it’s
what allows the short time bands of both types of circuit
breakers to be delayed as much as 0.5sec. EntelliGuard G
UL1066 LVPCBs with EntelliGuard TU trip units are
available with two different instantaneous adjustment
ranges to take full advantage of this capability.
The standard instantaneous adjustment range is 2-15X,
adjustable in 1/2X increments on all UL 489 and UL1066
circuit breakers. EntelliGuard TU trips offer, for UL1066
LVPCBs only, an extended Instantaneous adjustment range
that allows the instantaneous pickup to be continuously
adjusted up to 30X, adjustable in 1X increments above 15X
the rating plug. The maximum adjustable pickup setting is
limited to approximately 95% of the circuit breaker’s
withstand rating, or 30X trip plug current rating, whichever is
lower.
The EntelliGuard G’s wide range of instantaneous
adjustability allows for maximum flexibility in providing the
settings that are required for selectivity or for optimum
protection. Its capability is limited by its withstand rating and
the instantaneous override. An instantaneous override is
used in some circuit breakers to ensure that, if a fault
exceeds the circuit breakers withstand capability, the circuit
breaker trips quickly. In all UL489 EntelliGuard circuit
breakers, the override protection is designed such that
selectivity up to 100% of the stated circuit breaker’s
withstand rating is possible.
In UL1066 LVPCBs, maximum selective capability is achieved
by using the adjustable instantaneous algorithm, even if it is
set at maximum. When the adjustable instantaneous is
enabled, regardless of setting, the override protection is set
so that it will not trip for faults below the circuit breaker’s
withstand rating. If the adjustable instantaneous is disabled
(turned off), then the override automatically adjusts
downward by approximately 9%. This lowers the maximum
selective capability to 91% of the circuit breaker’s withstand
rating. The EntelliGuard G LVPCB may be selective up to the
full withstand current with adjustable instantaneous on and
91% of withstand rating with adjustable instantaneous off.
The EntelliGuard TU trip unit also offers a second adjustable
instantaneous trip called the Reduced Energy Let-Through
(RELT) instantaneous pickup. This trip offers a faster
algorithm suitable for application as alternate instantaneous
pickup setting for temporary use when faster and more
sensitive instantaneous protection is desired. The RELT
setting is determined by the user and may be adjusted from
1.5X to 15X rating plug. Once set, the RELT function may be
enabled or disabled locally at the trip unit or remotely via a
24Vac/dc signal, or serial communications.
When the trip unit receives a RELT enable command, it
issues a feedback signal indicating the RELT setting is now
active. The user may connect the RELT enable input to any
24Vac/dc source, such as a manual switch, automatic
sensor, or both. The feedback signal may be connected to
any desired signaling means with the proper ratings. For
further details see Section 3 of this application guide.
EntelliGuard G circuit breakers have defined close and latch
ratings as shown in Tables 6.2 through 6.4. The close and
latch rating is a measurement of the circuit breaker’s ability
to close and latch closed on a fault. This value must be high
enough to allow a circuit breaker to handle large transient
inrush currents associated with certain types of loads, such
as energy efficient motors or large capacitor banks.
EntelliGuard G circuit breakers are provided with values that
are high relative to the circuit breaker’s load carrying
capacity. The trip system provides a type of instantaneous
protection called a Making Current Release (MCR) to provide
more sensitive protection when closing. Should the trip
system measure higher current than the MCR setting, it is
very likely that the circuit breaker has been closed on a
bolted fault, or low impedance, arcing fault. If that is the
case, the MCR instantaneous will provide very fast
protection, minimizing damage and hazard.
EntelliGuard G circuit breakers are designed to provide
long life, even in operationally difficult environments.
However, different standards have different ways of
measuring and qualifying circuit breaker operations,
hence slightly different numbers may apply to similar
circuit breakers when defined within the context of
different standards. Tables 6.5 and 6.6 describe the
endurance parameters for the circuit breaker family.
1
1
3
Per industry standards, operations are listed based on no
maintenance during the testing. However, if some
maintenance is done of some of the current carrying parts
and arc chute, then over 20,000 electrical and mechanical
operations are possible.
There are six application factors to consider in selecting
current rating for a circuit breaker. These are:
1. Size of the cable or bus used in the line and load
connections.
2. Actual installed ambient temperature.
3. System operating frequency.
4. Altitude of the installation.
5. Type of loading of the protected circuit.
6. Design safety factor.
The following simple relationship combines these six
application factors into a single equation:
CR Required circuit breaker current rating, amps
IA Actual load current, amps
A Cable or bus sizing factor
B Ambient temperature rating factor
C Frequency rating factor
D Altitude rating factor
E Load class rating factor
F Safety factor
The thermal design of a circuit breaker takes into account
the ability of the line and load cables or buses to act as
heat sinks. For UL489 Listed circuit breakers, UL has
assigned specific cable or bus sizes for each current
rating. Generally, these assignments are coordinated with
specific conductor temperature ratings. When using a
conductor with an increased temperature rating, the
higher rating decreases both the cross-sectional area and
its ability to conduct heat from the circuit breaker. If an
DET-653C EntelliGuard® G Circuit Breaker Application Guide
77
Ambient Temperature – Factor B
Table 6.7. Ambient Temperature Rating - Factor B
Ambient
Temperature, °C 1
Maximum Wire
Insulating Rating °C 2
Factor B
25
75
1
50
105
1
60
125
1.1
70
125
1.15
Operating Frequency – Factor C
Altitude – Factor “D”
Table 6.8. Altitude Rating – Factor D
Altitude
Factor D
Feet
Meters
100 - 6,000
30 - 1,800
1
6,001 - 10,000
1,801 - 3,000
1.04
>10,001
>3,001
1.08
Load Class Rating – Factor E
24-May-12 Section 6. Application Data
EntelliGuard G circuit breaker is used with cables directly
connected, contact your GE application engineer for
information to ensure proper cabling information. Cable
with insulation ratings above 75°C may be used, providing
it is sized to 75°C ampacity per the NEC or other applicable
codes.
Ambient temperatures have a wide effect on the rating of
the breaker-cable system. While the internal sensing and
tripping circuitry in EntelliGuard TU trip units are ambient
insensitive, high-ambient temperatures may cause
internal components to exceed operating temperature
limits. Low temperatures substantially increase the
current-carrying capabilities of the breaker-cable system
until other limiting factors occur (e.g., lubrication problems
or mechanical binding of internal parts due to differential
contraction). The ambient temperature around an
EntelliGuard G breaker should not be less than -20°C nor
exceed 70°C.
Ambient temperature always refers to the temperature of
the air immediately surrounding the breaker and not the
temperature of the air outside the breaker’s enclosure.
Room or outside air temperatures only establish the
thermal floor to which all other heating is added.
To convert breaker ambient from room ambient, it is
necessary to know the temperature rise within the
equipment housing the breaker. Temperature rise is a
function of several variables, including heating caused by
other equipment, ventilation, solar heating, factors relating
to group mounting and the free surface area of the
breaker’s enclosure. Once the device’s ambient
temperature is determined, select Factor B from Table 6.7.
40 90 1
1 Average air temperature over a 24-hour period outside the breaker’s
insulated case, but inside the enclosure.
2 Cable (wire) must be based on 75°C current rating per Table 3 10-16,
current National Electrical Code.
All UL EntelliGuard circuit breakers may be applied at their
published ratings on 50Hz and 60Hz power systems. At
nominal system frequencies less than 50Hz but above
direct current, digital solid-state trip may become
inaccurate. On direct current systems, digital solid-state
trip units are completely inoperative. EntelliGuard G circuit
breakers may be used on DC applications, but EntelliGuard
TU trip units may not.
System operating frequencies above 60Hz may change
the performance and ratings of circuit breakers by heating
metallic parts and significantly reducing interrupting
capacity. EntelliGuard TU trip units are not suitable for
applications at 400Hz.
For operating frequencies of both 50Hz and 60Hz, the
operating frequency rating Factor C = 1.00. For operating
frequencies other than 50Hz and 60Hz, contact your GE
applications engineer.
EntelliGuard G UL circuit breakers are designed for
operation at altitudes from sea level to 6000ft (1800m).
Reduced air densities at altitudes above 6000ft affect the
ability of the circuit breaker to both transfer heat and
interrupt short circuits. Determine the altitude of the
breaker’s installation, and select the altitude rating - factor
D from Table 6.8.
The type of load and its duty cycle must be considered in
the application of EntelliGuard G circuit breakers. Loads
such as capacitors and electromagnets require a
substantial and continuous de-rating factor if the breaker
is normally used to switch the load. With loads such as
resistance welders, the breaker’s continuous current rating
must be no less than 125% of the welder’s 100% dutycycle rating.
In general, circuit breakers are intended for the protection
of insulated cable. Where a circuit breaker is intended to
protect load equipment, prudent engineering practices call
for obtaining factory review and concurrence with the
selection of a specific protective device. Load class
selection Factor E for typical applications are listed in
Table 6.9.
DET-653C EntelliGuard® G Circuit Breaker Application Guide
78
Table 6.9. Load Class Rating – Factor E
Load Type
Factor E
Single Motor Branch Circuit Protection (Normal
Duty)*
Single Motor Branch Circuit Protection (Heavy
Duty)*
Safety – Factor F
Other Factors that Influence Circuit Breaker Sizing 100%
vs. 80% Ratings
Table 6.10. Circuit Breaker and Trip Parameters
Adjustment or Capability
Abbreviation
Trip Designation
Setting or Range
Short Time Pickup
STPU
STPU
1.5X - 12X of the LTPU
24-May-12 Section 6. Application Data
Switching Electromagnets 1.5
1.5
Switching Capacitors 1.5
1.75
All Other load Types (Normal Duty) 1
*Use this factor to either plugging duty or starting more than 25 times per
hour, where the rms current cannot be easily calculated.
A safety factor is used to provide a design margin between
the rating of a circuit breaker and the derived operating
current using all of the applicable selection factors. A
safety factor of at least 10% is often used to ensure the
circuit breaker is adequately sized. In addition it may be
useful to consider future growth.
All EntelliGuard G circuit breakers are 100% rated except
for the 6000A stationary mounted UL 489 circuit breaker.
Circuit breakers that are 100% rated are not required to be
sized at 125% of the expected load. However, it is
recommended that a safety factor, as described above,
always be considered when selecting overcurrent device
sizes.
An important consideration may be the circuit breaker’s
desired selective and protection performance within the
context of the system where it is installed. Certain settings
are functions of the trip plugs, others of the sensors. In
Table 3.14 you will find the sensors available on a per
frame basis. Table 3.12 identifies the trip rating plugs
available for each sensor. Table 6.10 identifies the
relationship between specific circuit breakers and trip
parameters.
Trip Current Rating Plug In In ~37.5-100% of sensor
Long Time Pickup LTPU LTPU Plug x pickup setting
Instantaneous Pickup IPU I 2X -15 or 30X of the trip current rating plug
Maximum Achievable Selectivity = Icw N/A Function of the withstand rating
Ground Fault Pickup GF GF 20-60% sensor, <1200A
Override Pickup HSIOC N/A Function of the withstand rating
Making Current Release MCR N/A Function of the close and latch rating
DET-653C EntelliGuard® G Circuit Breaker Application Guide
82
EntelliGuard® G Power Circuit Breaker
Section 8. Standards and References
Underwriters Laboratories® (UL)
National Electrical Manufactures Association (NEMA)
Canadian Standards Association (CSA)
Institute of Electrical and Electronics Engineers (IEEE)
American National Standard Institute (ANSI)
24-May-12 Section 7. Physical Data
UL 489 and UL 489-SB2 - Standard for Molded Case Circuit
Breakers and Circuit Breaker Enclosures
UL 1066 - Standard for Safety Low-Voltage AC and DC
Power Circuit Breakers Used in Enclosures
Order from:
UL Publication Stock
333 Pfingsten Road
Northbrook, IL 60062 USA
AB-1/2002 Standards Publication - Molded Case Circuit
Breakers and Molded Case Switches
SG3/1995 - Standards and Ratings for the Application of
Low-Voltage Power Circuit Breakers
SG5/1995 – Power Switchgear Assemblies
Order from:
NEMA Publication
155 East 44th Street
New York, NY 10017 USA
CSA 22.2 NO 5.1 – Standards for Branch Circuit Protection
Order from:
Canadian Standards Association
178 Rexdale Blvd.
Rexdale, Ontario, Canada M9WR3
IEEE 693 – Recommended Practices for Seismic Design of
Substations
Order from:
IEEE
345 East 47th Street,
New York, NY 10017 USA
ANSI C37.13/1990 - Low-Voltage AC Power Circuit Breaker
Used in Enclosures (600-Volt Insulation Class)
ANSI C37.16/2000 - Recommendations for Low Voltage
Power Circuit Breakers and AC Power Circuit Protectors,
Preferred Ratings, Related Requirements, and Application
ANSI C37.17/1990 - American National Standard for Trip
Devices for AC and General Purpose DC Low Voltage
Power Circuit Breakers
ANSI C37.20.1/2000 - Metal-Enclosed Low-Voltage Power
Circuit
Breaker Switchgear
ANSI C37.50/1989 (R1995) – Test Procedures for LowVoltage AC
Power Circuit Breakers Used in Enclosures
ANSI/IEEE C37.90.1/1993 - IEEE Standard Surge Withstand
Capability (SWC) Tests for Protective Relays and Relay
Systems
ANSI/IEEE C37.90.2/1993 - Withstand Capability of Relay
Systems to Radiated Electromagnetic Interference from
Transceiver
Order from:
ANSI
11 West 42nd Street,
New York, NY 10036 USA
DET-653C EntelliGuard® G Circuit Breaker Application Guide
83
International Electrotechnical Committee (IEC)
National Electrical Code®
American Society for Testing and Materials (ASTM)
Military Standard (MIL-STD)
Seismic Qualifications to All Major Building Code
Standards
Other
American Society for Testing and Materials (ASTM)
Military Standard (MIL-STD)
24-May-12 Section 8. Standards and References
IEC 60947-1 (Ed. 4/2004) - Electrical Equipment for Low
Voltage, High Power Switching Equipment (Also applies to
Electromagnetic Compatibility
IEC 60947-2 (Ed. 4/2006) - Electrical Equipment for Low
Voltage, High Power Switching Equipment (Also applies to
Electromagnetic Compatibility
IEC 60947-3 (Ed. 4, Am 1, Am 2/2002) - Electrical
equipment for Low voltage, high power switching
equipment (Also applies to Electromagnetic Compatibility
IEC 68-2-1 (Am 1/1993) – Environmental Testing
Standards/Dry Cold at –55°C Operational Temperature
IEC 68-2-2 (Am 1/1993) – Environmental Testing
Standards/Dry Heat at +85°C Operational Temperature
IEC 68-2-30 - (Am 1/1985) – Environmental Testing
Standards/Operational Temperature and Humidity (temp.
+55°C, rel. humidity 95%)
IEC 68-2-52 Level 2 - (Am 1/1996) – Environmental Testing
Standards/Salt Mist-Corrosion
IEC 801-2 2nd Edition 1991-04 - Electromagnetic
Compatibility for
Industrial-Process, Measurement and Control Equipments
Part 2: Electrostatic Discharge Requirements
Order from:
Bureau Central de la Commission
Electrotechnique Internationale
3 rue de Varamb’e
Geneve, SUISSE
Order from:
National Fire Protection Association
Batterymarch Park
Quincy, MA 02269 USA
ASTM B117-73 (Reapproved 1979)
Standard Method of Salt Spray (Fog) Testing
Order from:
ASTM
1916 Race Street
Philadelphia, PA 19103 USA
MIL-STD-810E - Environmental Test Methods and
Engineering Guidelines
Order from:
Defense Printing Service
700 Robbins Avenue, Bldg. 4D
Philadelphia, PA 19111-5094 USA
IBC - International Building Code
UBC - Uniform Building Code
BOCA – Building Officials and Code Administrators
CBC – California Building Code
SBC – Standard Building Code
IEC Environmental: 68-2-1,-2,-3,-6,-11,-14,-14,-27,-29,-30,31
IEC Environmental: 721
Lloyds Register of Shipping, Germanischer Lloyds, ABS
(American Bureau of Shipping)
European ROHS Directives
GE Consumer & Industrial Engineering Test Procedures
(ETPs) and Standing Instructions (S.I.s) Standing
Instructions (S .I .s): S.I. 900001S001 - Program Technical
Review Discipline
ASTM B117-73 (Reapproved 1979)
Standard Method of Salt Spray (Fog) Testing
Order from:
ASTM
1916 Race Street
Philadelphia, PA 19103 USA
MIL-STD-810E - Environmental Test Methods and
Engineering Guidelines
Order from:
Defense Printing Service
700 Robbins Avenue, Bldg. 4D
Philadelphia, PA 19111-5094 USA
DET-653C EntelliGuard® G Circuit Breaker Application Guide
84
Seismic Qualifications to All Major Building Code
Standards
Other
24-May-12 Section 8. Standards and References
IBC - International Building Code
UBC - Uniform Building Code
BOCA – Building Officials and Code Administrators
CBC – California Building Code
SBC – Standard Building Code
IEC Environmental: 68-2-1,-2,-3,-6,-11,-14,-14,-27,-29,-30,31
IEC Environmental: 721
Lloyds Register of Shipping, Germanischer Lloyds, ABS
(American Bureau of Shipping)
European ROHS Directives
GE Consumer & Industrial Engineering Test Procedures
(ETPs) and Standing Instructions (S.I.s) Standing
Instructions (S .I .s): S.I. 900001S001 - Program Technical
Review Discipline