GE EntelliGuard G Application Manual

Page 1
imagination at work
EntelliGuard
®
G
Circuit Breaker
Application Guide
GE Energy
• Envelope 1, 100KAIC, 2000A and below
• Envelope 1, 65KAIC, 1200A and below
• Envelope 2, 100KAIC @ 600V rating
• UL489B DC Switch Ratings @ 600V and 1000V DC
Page 2
DET-653C EntelliGuard® G Circuit Breaker Application Guide

SECTION 1 – GENERAL INFORMATION

SECTION 2 – FEATURES AND CHARACTERISTICS

SECTION 3 – ENTELLIGUARD TU TRIP UNIT SYSTEM

24-May-12 Table of Contents
Introduction .............................................................................................................................................................................................................. 1
Table 1.1. Device Standards and References ............................................................................................................................... 1
Table 1.2. Device Ratings ........................................................................................................................................................................ 1
Table 1.3. ANSI/UL1066 Ratings .......................................................................................................................................................... 2
Table 1.4. UL489 Ratings ......................................................................................................................................................................... 2
Table 1.5. Non-Automatic Circuit Breaker – ANSI Version Ratings ................................................................................... 2
Table 1.6. Non-Automatic Circuit Breaker/Molded Case Switch – UL Version Ratings .......................................... 2
Table 1.6b UL489B Ratings .................................................................................................................................................................... 3
Figure 2.1. EntelliGuard G Features and Characteristics ................................................................................................................. 4
STANDARD AND OPTIONAL FEATURES ....................................................................................................................................................... 5
Short Time Rating (1/2 Sec) ..................................................................................................................................................................... 5
Short Circuit/High Interruption Rating .............................................................................................................................................. 5
Thermal Performance ............................................................................................................................................................................... 5
Table 2.1. Sensors Available .......................................................................................................................................................... 5
Reverse Feed .................................................................................................................................................................................................. 5
Two-Step Stored Energy Mechanism ................................................................................................................................................ 5
Field Installable Trip Units and Accessories ................................................................................................................................... 5
Coils ............................................................................................................................................................................................................ 6
Breaker/Main Contact Status ................................................................................................................................................................ 6
Motor Operator ............................................................................................................................................................................................. 6
Electrical Closing Button .......................................................................................................................................................................... 6
Ready to Close Indicator .......................................................................................................................................................................... 6
Mounting Straps/Accessories ............................................................................................................................................................... 6
Auxiliary Switches ........................................................................................................................................................................................ 6
Interlocks .......................................................................................................................................................................................................... 6
Breaker Status Indicators ........................................................................................................................................................................ 6
Rejection Feature ......................................................................................................................................................................................... 7
Through-Door Racking .............................................................................................................................................................................. 7
Padlocking Devices ..................................................................................................................................................................................... 7
Key Interlock ................................................................................................................................................................................................... 7
Shutters ............................................................................................................................................................................................................ 7
Carriage Position Switch .......................................................................................................................................................................... 7
Lifting Beam .................................................................................................................................................................................................... 7
IP Covers ........................................................................................................................................................................................................... 7
Mechanical Counter ................................................................................................................................................................................... 7
Cable Interlocks (OEM Applications Only) ........................................................................................................................................ 8
Bell Alarm Contact ....................................................................................................................................................................................... 8
Introduction ............................................................................................................................................................................................................ 9
Reliability without Compromising Protection ......................................................................................................................................... 9
Arc Flash and the EntelliGuard TU Trip Unit ............................................................................................................................................ 9
Figure 3.1. Arcing Current ...................................................................................................................................................................... 10
Selectivity with Molded case Circuit Breakers and Other Devices ............................................................................................ 10
Figure 3.2. Selectivity Curve.................................................................................................................................................................. 10
Table 3.1. EntelliGuard Selectivity Above GE Current Limiting Circuit Breakers ....................................................... 10
Table 3.2. Maximum Instantaneous Pickup Multipliers for GE Circuit Breakers ....................................................... 11
Table 3.3. Selectivity with EntelliGuard TU Trip Units in ANSI and ICCB/ Power Break II Circuit Breakers .. 13
Above Downstream Feeders ......................................................................................................................................................................... 14
The Waveform Recognition Selective Instantaneous ...................................................................................................................... 14
Table 3.4. Minimum Selective Clearing Times for an EntelliGuard G Circuit Breaker ............................................. 15
©2012 General Electric All Rights Reserved
Page 3
DET-653C EntelliGuard® G Circuit Breaker Application Guide 24-May-12 Table of Contents
Above Other Power Circuit Breakers ........................................................................................................................................................ 15
Terminology ........................................................................................................................................................................................................... 15
Long Time Protection ................................................................................................................................................................................. 16
Thermal Long Time Overcurrent ................................................................................................................................................................ 16
Figure 3.3. Table. 3.5.
Fuse-Shaped Steep Long Time Overcurrent ........................................................................................................................................ 17
Figure 3.4. Fuse Table 3.6. Fuse
Thermal Memory ................................................................................................................................................................................................. 19
Short Time Protection ....................................................................................................................................................................................... 19
Short Time Pickup ..................................................................................................................................................................................... 19
Short Time Bands ...................................................................................................................................................................................... 20
Short Time I
Ground Fault Protection .................................................................................................................................................................................. 20
Internal Residual Summation ....................................................................................................................................................................... 20
External Zero Sequence Input...................................................................................................................................................................... 21
Ground Fault Pickup Settings ....................................................................................................................................................................... 21
Table 3.9. Ground Fault Time Delay Bands .................................................................................................................................. 21
Ground Fault Time Delay Bands ................................................................................................................................................................. 21
Table 3.10. Minimum Ground Fault Pickup and Clear Time ................................................................................................ 21
Ground Fault Protection Curves ................................................................................................................................................................. 21
Figure 3.9. Ground Fault Characteristics ...................................................................................................................................... 21
Instantaneous Protection ............................................................................................................................................................................... 21
Adjustable Selective Instantaneous ......................................................................................................................................................... 22
Table 3.11. Max. Adjustable Instantaneous Pickup for CBs with Normal or Extended Range Option ......... 22
Table 3.12. Time Current Curves .......................................................................................................................................................
High Set Instantaneous Overcurrent (HSOIC) ...................................................................................................................................... 23
Making Current Release (MCR) ..................................................................................................................................................................... 23
Table 3.13. HSIOC Locations ................................................................................................................................................................ 23
Reduced Energy Let-Through (RELT) Instantaneous Trip .............................................................................................................. 23
Reduced Energy Let-Through Switch Wiring ....................................................................................................................................... 24
Figure 3.10. Integrated Switch And LED, Spring Return from “Test” to ‘Off,” Latched in “On” .......................... 24
Zone Selective Interlocking (ZSI ) ................................................................................................................................................................ 24
Table 3.14. Instantaneous ZSI on EntelliGuard TU Trip Units in ANSI EntelliGuard G Circuit Breakers ........ 25
Figure 3.11. Zone Selective Interlocked CB, Upper CB Shown “Unrestrained” ......................................................... 25
Figure 3.12. Zone Selective Interlocked CB, Upper CB Shown “Restrained” .............................................................. 25
Rating Plugs ........................................................................................................................................................................................................... 26
Figure 3.13. EntelliGuard Trip Unit Rating Plug Catalog Number Guide ...................................................................... 26
Table 3.15. Trip Rating Plug Specifications .................................................................................................................................. 27
Table 3.16. Trip Rating Plug Codes ................................................................................................................................................... 27
Table 3.17. EntelliGuard G Rating Plug Logic (UL 489,n UL 1066, IEC) ........................................................................... 28
Universal Spare Trip Unit ................................................................................................................................................................................ 28
Table 3.18. Universal Spare trip Unit Options (User-Selected) ........................................................................................... 22
Relay Functions ................................................................................................................................................................................................... 29
Protective Relays................................................................................................................................................................................................. 30
Voltage Unbalance Relay ............................................................................................................................................................................... 30
Table 3.19. Relay Functions Available in EntelliGuard G CBs with EntelliGuard TUs ............................................. 30
Table 3.20. Voltage Unbalance Settings ....................................................................................................................................... 30
Thermal Characteristic: Max. and Min. Long Time Delay Bands for a 1000A Long Time Pickup ...... 16
Thermal Characteristic: Nominal Clearing and Commit Times for X Multipliers of Nominal Pickup 17
Characteristic: Max. and Min. Long Time Delay Bands for a 1000A Long Time Pickup ............. 17
Characteristic: Nominal Clearing and Commit Times for X Multipliers of Nominal Pickup ........ 18
Figure 3.5. Short Time Pickup .................................................................................................................................................... 19
Figure 3.6. Short Time Transition ............................................................................................................................................. 19
Table 3.7. Short Time Delay Bands ......................................................................................................................................... 20
Figure 3.7 Short Time Delay ....................................................................................................................................................... 20
Figure 3.8. Short I
2
t Slopes ................................................................................................................................................................................ 20
2
t (In or Out).................................................................................................................................................... 20
22
©2012 General Electric All Rights Reserved
Page 4
DET-653C EntelliGuard® G Circuit Breaker Application Guide

SECTION 4 – ACCESSORIES

24-May-12 Table of Contents
Current Unbalance Relay ................................................................................................................................................................................ 31
Table 3.21. Current Unbalance Settings ........................................................................................................................................ 31
Under Voltage Relay .......................................................................................................................................................................................... 31
Under Voltage Relay Zero-Volt Trip Enable ........................................................................................................................................... 31
Table 3.22. Under Voltage Settings .................................................................................................................................................. 31
Over Voltage Relay ............................................................................................................................................................................................. 31
Table 3.23. Over Voltage Settings ..................................................................................................................................................... 31
Power-Reversal Relay ....................................................................................................................................................................................... 31
Table 3.24. Power-Reversal Settings ............................................................................................................................................... 31
Power-Direction Setup ..................................................................................................................................................................................... 31
Potential Transformer Primary Voltage ................................................................................................................................................... 31
Potential Transformer Connection ............................................................................................................................................................. 31
Power Demand Intervals ................................................................................................................................................................................. 31
Current Alarm ........................................................................................................................................................................................................ 31
Trip Logic Inputs ................................................................................................................................................................................................... 31
Table 3.25 Input Assignments Possible .......................................................................................................................................... 32
Outputs for EntelliGuard G Circuit Breakers.......................................................................................................................................... 32
Table 3.26. Output Configuration ...................................................................................................................................................... 32
Waveform Capture ............................................................................................................................................................................................. 32
EntelliGuard Trip Unit Performance Characteristics Graphs ........................................................................................................ 33
Table 3.27. EntelliGuard Trip Unit Summary ................................................................................................................................ 33
Table 3.28. Metering Data Startup Levels for breaker with Entelliguard Trip Unit with 24 VDC ...................... 35

Table 3.29. Metering Data for breaker with Entelliguard Trip Unit without 24 VDC requires 20%

sensor current and then all metering will be available ............................................................................... 35
Figure 3.14. Long Time Circuit Breaker Characteristics ....................................................................................................... 36
Figure 3.15. Short Time Pickup and Delay Bands ..................................................................................................................... 37
Figure 3.16. Ground Fault: Multiple of Sensor ............................................................................................................................. 38
Figure 3.17. Instantaneous, Override (HSIOC), Reduced Energy Let-Through Instantaneous (RELT) ............ 39
Introduction .......................................................................................................................................................................................................... 40
Figure 4.1. Accessory Mounting ......................................................................................................................................................... 40
Motorized Spring Charging Unit .................................................................................................................................................................. 40
Table 4.1. Motor Operators .................................................................................................................................................................. 40
Circuit Breaker Closing Coils – Standard and Commanded ......................................................................................................... 40
Table 4.2. Closing Coil Characteristics ............................................................................................................................................ 41
Command Operation Module ....................................................................................................................................................................... 41
Shunt Trip ................................................................................................................................................................................................................ 41
Table 4.3. Extended Range Shunt Trip for UL Ground Fault and ANSI DC Rating Applications ........................ 41
Status Indication Switch (Coil Signaling Contact) ............................................................................................................................... 41
Table 4.4. Coil Signaling Contact Module ...................................................................................................................................... 41
Under Voltage Release with Fixed Time Delay .................................................................................................................................... 41
Table 4.5. UVR Operating Characteristics ..................................................................................................................................... 41
Time Delay Module for UVR (Externally Mounted) .............................................................................................................................. 42
Figure 4.2. Time Delay Module .......................................................................................................................................................... 42
Table 4.6. TDM Characteristics .......................................................................................................................................................... 42
Remote Operation Coil Combination ........................................................................................................................................................ 42
Table 4.7. Remote Operation Coil Combination ......................................................................................................................... 42
Ready to Close Contact .................................................................................................................................................................................... 42
Table 4.8. Ready to Close Contacts (1NO) ..................................................................................................................................... 42
Auxiliary Switches ............................................................................................................................................................................................... 42
Table 4.9. Auxiliary Switches ................................................................................................................................................................ 42
Table 4.10. Auxiliary Switch Ratings and Secondary Disconnect Points ...................................................................... 42
Table 4.11. Power Rated (3NO/3NC) (Ref Drawing 10099230) ........................................................................................... 43
Table 4.12. Power Rated (8NO/8NC) (Ref Drawing 10099228) ........................................................................................... 43
©2012 General Electric All Rights Reserved
Page 5
DET-653C EntelliGuard® G Circuit Breaker Application Guide 24-May-12 Table of Contents
Table 4.13. Power Rated (3NO/3NC) + Low Signal (Hi-Fi) (2NO/2NC) (Ref Drawing 10099232) ........................ 43
Table 4.14. Power Rated (4NO/4NC) + Low Signal (Hi-Fi) (4NO/4NC) (Ref Drawing 10099234 ......................... 44
Circuit Breaker – Key Interlock Facility .................................................................................................................................................... 44
Table 4.15. Key Interlocks and Door Interlocks ......................................................................................................................... 44
Figure 4.3. Breaker-Mounted Key Interlock ................................................................................................................................. 44
Figure 4.4. Cassette-Mounted Key Interlock ............................................................................................................................... 44
Carriage Position Switch (TOC) .................................................................................................................................................................... 45
Table 4.16. Carriage Position Switches .......................................................................................................................................... 45
Table 4.17. Carriage Position Switch Ratings (Common NO/NC Contact Configuration ..................................... 45
Mechanical Interlocks (Cable/Rod) (OEM Applications Only) .............................................................................................. 45
Table 4.18. Mechanical Interlock (Cable/Rod) ............................................................................................................................ 45
Cables .............................................................................................................................................................................................................. 45
Table 4.19. Cables for Mechanical Interlocks ............................................................................................................................. 45
Table 4.20. Interlock Configurations ............................................................................................................................................... 46
Bell Alarm with Lockout ................................................................................................................................................................................... 47
Table 4.21. Bell Alarm Switches ......................................................................................................................................................... 47
Table 4.22. Bell Alarm Ratings (Common 1NO/NC Contact Configuration) ................................................................ 47
Charging Spring Status Indicator ............................................................................................................................................................... 47
Table 4.23 Spring Charged Contact (1NO) ................................................................................................................................... 47
Secondary Disconnects (Factory-Installed/Field Installable) ...................................................................................................... 47
Table 4.24. Block Location .................................................................................................................................................................... 47
Table 4.25. Wiring Schematic for Block A ..................................................................................................................................... 47
Table 4.26. Wiring Schematic for Block B ..................................................................................................................................... 48
Table 4.27. Wiring Schematic for Block C ..................................................................................................................................... 48
Table 4.28. Electronic Interlock .......................................................................................................................................................... 48
Table 4.29. Wiring Schematic Nomenclature Definitions .................................................................................................... 49
Ground Fault ......................................................................................................................................................................................................... 50
Table 4.30. Neutral Rogowski CTs .................................................................................................................................................... 50
Sealed Door Panel Escutcheon ................................................................................................................................................................... 50
Mechanical Operations Counter ................................................................................................................................................................. 50
Table 4.31. Miscellaneous Accessories .......................................................................................................................................... 50
Cassette/Substructure ..................................................................................................................................................................................... 50
Position Indicators ................................................................................................................................
Door Interlocks ..................................................................................................................................................................................................... 51
Table 4.32. Door Interlocks ................................................................................................................................................................... 50
Back Connected Terminations .................................................................................................................................................................... 51
Table 4.33. Back Connected Terminations for Cassette ....................................................................................................... 51
Table 4.34. Back Connected Terminations .................................................................................................................................. 53
Front Flat Terminations ................................................................................................................................................................................... 56
Table 4.35. Optional Front Flat Terminations ............................................................................................................................. 56
Table 4.36. Cluster ..................................................................................................................................................................................... 57
Table 4.37. Cluster Pad ........................................................................................................................................................................... 58
Terminations for DC Switches UL 489B .................................................................................................................................................. 59
Figure 4.35. Terminations for DC Switches UL 489B .............................................................................................................. 59
Remote Racker .............................................................................................................................................................................................. 59
Table 4.38. Remote Racker ................................................................................................................................................................ 59
Grounding/Earthing Device (IEC Only) ..................................................................................................................................................... 59
Table 4.39. Grounding/Earthing Devices (IEC Only .................................................................................................................. 59
Rejection Device .................................................................................................................................................................................................. 59
.............................................................. 50
©2012 General Electric All Rights Reserved
Page 6
DET-653C EntelliGuard® G Circuit Breaker Application Guide

SECTION 5 – CATALOG NUMBERING GUIDE

SECTION 6 – APPLICATION DATA

SECTION 7 – PHYSICAL DATA

SECTION 8 – STANDARDS AND REFERENCES
24-May-12 Table of Contents
EntelliGuard G ANSI/UL489 Circuit Breaker Catalog Number Guide ....................................................................................... 60
EntelliGuard G Cassette Catalog Number Guide ................................................................................................................................ 68
EntelliGuard TU Trip Unit for EntelliGuard G Breaker ....................................................................................................................... 70
EntelliGuard TU Trip Unit Rating Plugs ..................................................................................................................................................... 72
Introduction .......................................................................................................................................................................................................... 73
Key Features .......................................................................................................................................................................................................... 73
UL1066 Low Voltage Power Circuit Breakers ............................................................................................................................. 73
UL498 Stored Energy Insulated Case Circuit Breakers .......................................................................................................... 73
IEC rated Circuit Breakers for IEC Equipment and Applications ....................................................................................... 73
All Types .......................................................................................................................................................................................................... 73
Ratings and Sizes ................................................................................................................................................................................................ 73
Short Circuit Interrupting Ratings ............................................................................................................................................................... 74
Figure 6.1. Short Circuit Rating Adjustment Equation ............................................................................................................ 74
Table 6.1. First Half-Cycle Peak at Specific Fault X/R Ratios ............................................................................................... 74
Withstand Ratings, Selective Adjustable-, RELT- and Override-Instantaneous Protection ......................................... 74
Close and Latch Ratings and Making Current Release (MCR) Instantaneous Trip............................................................ 75
Table 6.2. EntelliGuard G Circuit Breaker Close and Latch Ratings, UL489 Listed .................................................. 75
Table 6.3. EntelliGuard G Circuit Breaker Close and Latch Ratings, UL1066 Listed................................................ 75
Table 6.4. EntelliGuard G Non-Automatic Switch Close, Latch, and Withstand Ratings, UL489 Listed ....... 76
Operations .............................................................................................................................................................................................................. 76
Table 6.5. Operational Ratings, UL489 Circuit Breakers ........................................................................................................ 76
Table 6.6. Operational Ratings, UL1066/ANSI Circuit Breakers ......................................................................................... 76
Selecting a Circuit Breaker for an Application ..................................................................................................................................... 76
Cable or Bus Size – Factor A .......................................................................................................................................................................... 76
Ambient Temperature – Factor B ............................................................................................................................................................... 77
Table 6.7. Ambient Temperature Rating – Factor B ................................................................................................................. 77
Operating Frequency – Factor C ................................................................................................................................................................. 77
Altitude – Factor D .............................................................................................................................................................................................. 77
Table 6.8. Altitude Rating – Factor D................................................................................................................................................ 77
Load Class Rating – Factor E ......................................................................................................................................................................... 77
Table 6.9. Load class Rating – Factor E .......................................................................................................................................... 78
Safety – Factor F .................................................................................................................................................................................................. 78
Other Factors that Influence Circuit Breaker Sizing 100% vs. 80% Ratings ........................................................................ 78
Table 6.10. Circuit Breaker and Trip Parameters ......................................................................................................................
78
Dimensional Drawings ..................................................................................................................................................................................... 79
Figure 7.1. Sample Dimensional Drawing: ANSI UL 489, 3Pole, Drawout, 2000A, Type E, M ............................. 79
Dimensional Drawing Index .......................................................................................................................................................................... 80
Table 7.1. Dimensional Drawing Index ........................................................................................................................................... 80
Dimensions .......................................................................................................................................................................................................... 81
Table 7.2. 3-Pole, UL/ANSI ..................................................................................................................................................................... 81
Table 7.3. 4-Pole, UL/ANSI ..................................................................................................................................................................... 81
.................................................................................................................................................................... 82
Publications .......................................................................................................................................................................................................... 85
©2012 General Electric All Rights Reserved
Page 7
DET-653C EntelliGuard® G Circuit Breaker Application Guide
1
EntelliGuard® G Power Circuit Breaker Section 1. Introduction

Table 1.1. Device Standards and References (See Section 8 for Details)

ANSI® Certified

UL® Listed

IEC® Rated

IEC® Extreme Atmospheric Conditions

Low-Voltage

Insulated Case

Circuit Breaker

IEC 68-2-1: Dry cold at -55°C

Power Circuit

Circuit Breaker

IEC 60947-1

IEC 68-2-2: Dry heat at 85°C

Breaker

UL 489

Photovoltaic

IEC 60947-2

IEC 68-2-30: Damp heat (temp. 55°C, rel. humidity 95%)

C37.13

NEMA AB1

C37.16

C37.17

C37.20

C37.50

UL 1066

NEMA SG3&5

Table 1.2. Device Ratings

Standard

Sensors Available

Envelope 1

Envelope 2

Envelope 3

ANSI/UL

400A - 2000A

400A - 3200A

3200A - 5000A

UL 489

400A - 2000A

400A - 3200A

3200A - 6000A

IEC

400A - 2000A

400A - 4000A

3200A - 6400A

24-May-12 Section 1. Introduction

EntelliGuard G circuit breakers are the newest line of low voltage power circuit breakers (LVPCBs) evolved from the exceptional designs and practices of GE legacy breakers. EntelliGuard G breakers offer a truly global product platform that meets industry standards throughout the Americas, Europe and Asia (ANSI, UL, CSA, IEC, Lloyds Register of Shipping, etc.).
Breakers are available to OEMs in 3- and 4-pole designs from 400A to 6400A (IEC) with fault interruption ratings up to 150kA. New, state-of-the-art EntelliGuard Trip Units enable the breakers with advanced technology that provides system protection, local and remote monitoring, relaying and communications. EntelliGuard Trip Units may be supplied with either Modbus or Profibus communications protocols. The breaker-trip unit system delivers superior circuit protection without compromising selectivity or arc flash protection. The EntelliGuard system is yet another evolution of GE’s core competencies in reliable electric power distribution, circuit protection and arc flash protection.
EntelliGuard G 3-pole breakers are the standard in GE AKD-20 Low Voltage Switchgear. The breakers are suitable for 280Vac, 480Vac and 600Vac applications, and they provide advanced circuit protection, limit arc fault energy and preserve system coordination without sacrificing any of these critical functions (Table 1.1).
UL489B DC for

IEC 60947-3 IEC 68-2-52 Level 2: salt mist

CSA 22.2 NO 5.1

EntelliGuard G devices are available in all standard, 100% rated, ANSI, UL and IEC ratings in both fixed and draw-out designs. Standard devices are also offered in 4 pole designs. No compromise (e.g., derating) is necessary in the system protection scheme as the EntelliGuard G Neutral poles are fully rated. Front and rear access connections are available, and all configurations can be manually or electrically operated with multiple and redundant accessories (optional) (Table 1.2).

EntelliGuard G short circuit and interrupting ratings are given in Tables 1.3 through 1.6.

©2012 General Electric All Rights Reserved
Page 8
DET-653C EntelliGuard® G Circuit Breaker Application Guide
2

Table 1.3. ANSI/UL1066 Ratings

Interrupting Rating Tier ANSI/UL1066 Devices, LVPCB

Envelope 1

Envelope 2

Envelope 3

Type

254V

508V

635V

1/2S
Withstand

400, 800,
1200

400, 800,
1600,

2000

3200

400-3200

3200

4000-

5000

S
N

65,000

65,000

65,000

65,000

X X
H

85,000

85,000

65,000

65,000

X
P

100,000

100,000

65,000

65,000

X
E

85,000

85,000

85,000

85,000

X
M

100,000

100,000

100,000

85,000

X
X
B

100,000

100,000

100,000

100,000

X
X
L

150,000

150,000

100,000

100,000

X
X

Table 1.5. Non-Automatic Circuit Breaker – ANSI Version Ratings

Envelope

Type

Amps

Rated
Interrupting

Rated Endurance

Current

Minimum
Mechanical

Minimum
Electrical

Minimum Electrical

Endurance

Endurance
at 480V

Endurance
at 600V

S
42
1 N 800
42

12,500

10,000

7,500

1 N 1600
42

12,500

10,000

7,500

1 N 2000
42

12,500

7,500

5,000

2 M 3200
65

5,000

5,000

5,000

3 B 4000
100

5,000

3,000

2,000

3 B 5000
100

5,000

2,000

1,500

Table 1.4. UL489 Ratings

Interrupting Rating Tier UL489 Devices, ICCB

Envelope 1

Envelope 2

Envelope 3

Type

240V

480V

600V

1/2S
Withstand

400­1200

400-
2000

2500-

3000

400-
3000

3000

4000

5000-
6000

S

65,000

65,000

50,000

42,000

X
N
X
X
H
X
X
P

100,000

100,000

65,000

50,000

X
M
L
24-May-12 Section 1. Introduction

65,000 65,000 50,000 50,000 X

65,000 65,000 65,000 42,000 85,000 85,000 65,000 50,000
100,000 100,000 100,000 65,000
150,000 150,000 100,000 85,000
1
800
12,500 10,000 7,500
X
X X X
X X
GE internal quality testing requirements exceeded 20,000 mechanical and electrical operations.
©2012 General Electric All Rights Reserved
Page 9
DET-653C EntelliGuard® Circuit Breaker Application Guide
3

Table 1.6. Non-Automatic Circuit Breaker/Molded Case Switch – UL Version Ratings

Envelope

Type

Amps

Short
Interrupting

Rated Endurance

Current (kA)

Minimum
Mechanical

Minimum
Electrical

Minimum Electrical

Endurance

Endurance

at 480V

Endurance
at 600V

1 S 800
42

12,500

10,000

7,500

S
42
N
1 N 1600
42

12,500

10,000

7,500

1 N 2000
42

12,500

7,500

5,000

M
B
3 B 5000
100

5,000

3,000

1,500

3 B 6000
100

5,000

1,500

1,000

Table 1.6b UL489B Ratings "Suitable for use in Photovoltaic system in accordance with article 690 of the NEC"

Envelope

Type

Amps

Short
Interrupting

Rated Endurance

Current (kA)

Minimum
Mechanical
Endurance

Minimum Electrical

Endurance
at 600V
DC

Minimum Electrical

Endurance
at 1000V
DC
2
M

800 -

3000

30

12500

500
500

Altitudes and Closing Times

Dimensions and Weights

24-May-12 Section 1. Introduction
1 1
2 3
GE internal quality testing requirements exceeded 20,000 mechanical and electrical operations.

1200

12,500 10,000 7,500
800 42 12,500 10,000 7,500

3000 65 5,000 5,000 5,000 4000 100 5,000 3,000 2,000

4 Configurations available for 600V DC and 1000V DC with or without isolating both DC legs. See Page 59 for Bus Bar Configurations.. Note: Bus Bars must be ordered separately. Time Constant (L/R) = 15msec, Rated calibration temperature 50 degree C

See Section 7, Tables 7.2 and 7.3.

See Section 7.

©2012 General Electric All Rights Reserved
Page 10
DET-653C EntelliGuard® G Circuit Breaker Application Guide
4
EntelliGuard® G Power Circuit Breaker Section 2. Features and Characteristics

Figure 2.1. EntelliGuard G Features and Characteristics

24-May-12 Section 2. Features and Characteristics

©2012 General Electric All Rights Reserved
Page 11
DET-653C EntelliGuard® G Circuit Breaker Application Guide
5

STANDARD AND OPTIONAL FEATURES

Short Time Rating (1/2 Sec)
Short Circuit/High Interruption Rating
Thermal Performance
Reverse Feed
Two-Step Stored Energy Mechanism
Field Installable Trip Units and Accessories

Table 2.1 Enclosure Requirements

Minimum
Space (inches)
Vent Slots (a)

Frame Size

No. of Poles

W H D

Top Wall

Bottom Wall

Rear Wall

1200A (Env 1)

3P
20

16.4

16.5

12
16
-

2000A (Env 1)

3P
20

16.4

16.5

12
16
-

2000A (Env 1)

4P
22

16.4

16.5

12
16
-

3000A/3200A (Env 2)

3P
22
21

16.5

16
16
8

3000A/3200A (Env 2)

4P
25
21

16.5

20
16
8

6000A (Env 3)

3P
32
30

16.5

24
20
20

6000A (Env 3)

4P
41
30

16.5

30
24
20
24-May-12 Section 2. Features and Characteristics
42KA, 50KA, 65KA (Env 1); 85KA (Env 2), 100KA (Env 3)
65K - 150KA @ 508V and below, 65K - 100KA @ 635V
ANSI C37 and UL 489 designs are 100% rated up to 40ºC when
applied in recommended enclosure sizes. IEC 60947 versions are 100% rated in free air up to 50ºC. IP31 enclosure/switchboard rating is based on size, recommended up to 50ºC ambient with rear vertical bus connection (Table 2.1).
EntelliGuard G devices can be fed from top or bottom terminals.
EntelliGuard G operates via stored energy mechanisms that can
Specified Cubicle
Minimum Specified Cubicle Ventilation - No of
be manually charged (MO) or electrically charged (EO) by the Spring Charging Motor. Closing time is less than five cycles. Closing and opening can be initiated remotely or via the front cover push buttons. An Open-Close-Open cycle is possible without recharging. (Charge after close). The breaker operating mechanism is a trip-free mechanism and is furnished with an integrated anti-pumping system.
EntelliGuard G devices have provisions for four accessory
operating coils. The four positions can be filled by the following four devices: one Close Coil (CC) or one Command Close Coil (CCC), one Shunt Trip Coil (ST), one Under Voltage Release (UVR), and the fourth position can either be a 2nd ST Coil or a UVR. The Shunt Trip and the UVR can also be replaced with a 120V Network Interlock Device. The closing coil is a “one-shot” electronic closed circuit. Shunt trip (ST) coils are continuous rated. (Note: No Red Indicating Light on Shunt Trip) Under voltage relays (UVR) are available with a fixed time delay (3 Cycles at down to 50% system voltage; 1.2 Cycles below 50% system voltage). The time delay module (TDM) is available as a shipped loose accessory for remote installation (in equipment). Optional Coil Signaling contact modules for the CC, CCC, ST, UVR, and NI's provide coil status (energize/de-energize) via the secondary disconnects or trip unit through Modbus or Profibus Comm.
©2012 General Electric All Rights Reserved
Page 12
DET-653C EntelliGuard® G Circuit Breaker Application Guide
6
Coils
Breaker/Main Contact Status
Motor Operator
Electrical Closing Button
Ready to Close Indicator
Mounting Straps/Accessories
Auxiliary Switches
Interlocks
24-May-12 Section 2. Features and Characteristics
EntelliGuard G devices have provisions for four accessory
operating coils. The four positions can be filled by the following four devices: one Close Coil (CC or CCC), one Shunt Trip Coil, one UVR (Under Voltage Release), and the fourth position can either be a Shunt Trip Coil or a UVR. The closing coil is a “one-shot” electronic closed circuit. Shunt trip (ST) coils are continuous rated. Under voltage relays (UVR) are available with a fixed time delay (50ms at down to 50% system voltage; 20ms below 50% system voltage). The time delay module (TDM) is available as a shipped­loose accessory for remote installation (in equipment). Optional status contact modules for the ST, CC and UVRs provide coil status (energize/de-energize) via the secondary disconnects and trip unit.
Heavy duty, motor/gearbox unit; easily accessible with a full
Four available designs:
Standard interlocks include:
OPEN/CLOSED, ON/OFF indication is provided on the front cover.
range of voltages.
Located on the front cover between the Open and Close button;
used to electronically close the breaker when a Command Close Coil is selected.
Provides visible indication/readiness for close operation.
Kits are available to mount and connect fixed/stationary breakers
in either a rear connected (Vertical) or a front flat connected.
Power rated (3NO+3NC) (Standard)
Power rated (3NO+3NC) + low signal (Hi-Fi) (2NO+2NC)
Power rated (8NO+8NC)
Power rated (4NO+4NC) + low signal (Hi-Fi) (4NO+4NC)
Drawout Breaker: prevents the breaker from being closed
unless it is in the TEST or CONNECT positions
Drawout Breaker/Main Contacts: prevents withdrawal/removal of the breaker unless the main contacts are OPEN. Access to the drawout mechanism racking screw is blocked when the breaker is CLOSED.
Spring Discharge Interlock: Automatically discharges the closing springs when the breaker is moved from the DISCONNECT to the WITHDRAWN position. This prevents withdrawing a breaker from the cubicle with the closing springs charged.
©2012 General Electric All Rights Reserved
Page 13
DET-653C EntelliGuard® G Circuit Breaker Application Guide
7
Breaker Status Indicators
Rejection Feature
Through-Door Racking
Padlocking Devices
Key Interlock
Shutters
Carriage Position Switch
Lifting Beam
IP Covers
Mechanical Counter
24-May-12 Section 2. Features and Characteristics
A factory-installed rejection feature prevents mismatching
Up to four optional key interlocks are available (Kirk, Ronis,
Optional lockable shutters are available (factory installed).
Optional Lifting Beams/bars with separate slings are available for
Optional IP54 covers (protects against harmful amounts of dust
Standard Indicators include:
The breaker status indicator shows the condition of the main contacts (OPEN, CLOSED).
The status of the closing springs is indicated as CHARGED or DISCHARGED.
The draw-out position indicator displays whether the breaker is in the CONNECT, TEST or DISCONNECT position.
The breaker also includes a switch that provides main contact status indication to the POWER LEADER™ Power Management System.
The optional Reduced Energy Let-Through (RELT) is provided with an ON/OFF contact closure to positively indicate whether the RELT setting is enabled or not.
breakers and cassettes/substructures. This prevents (a) inserting a breaker with a lower interrupting rating into a higher rated cassette/substructure and (b) inserting a higher current rated breaker into a lower rated cassette/substructure.
The breaker racking mechanism is accessible through the front of
the cassette and permits safely disconnecting/withdrawing the circuit breaker without opening the door and exposing personnel to live parts during the process.
The padlocking device is standard on breakers and allows up to
three padlocks with 1/4" to 3/8" diameter shanks to secure the breaker in the OPEN/TRIP FREE position. A padlock provision on the front panel of the cassette/substructure permits locking access to the racking screw. Racking access can be locked with the breaker in the CONNECT, TEST, DISCONNECT position with up to three padlocks.
Profalux, Castell). Switchgear applications utilize a Kirk key interlock mounted in the cassette. A maximum of two key interlocks may fit in the cassette.
This optional cassette/substructure device permits local or
remote indication of the circuit breaker status (CONNECTED, TEST, DISCONNECTED), 2NO/2NC single pole, double throw contacts are available for each position.
all breaker sizes. A Universal Lifting Beam is also available capable of lifting a 3 Pole Envelope 1
and splashing water) are available for all breaker sizes.
Provides local record of the cumulative number of complete
breaker closing operations.
©2012 General Electric All Rights Reserved
Page 14
DET-653C EntelliGuard® G Circuit Breaker Application Guide
8
Cable Interlocks (OEM Applications Only)
Bell Alarm Contact
24-May-12 Section 2. Features and Characteristics
Available with or without a mechanical lockout feature, the bell
Available for fixed and draw-out breakers, these units enable
direct interlocking of EntelliGuard G circuit breakers.
alarm operates whenever the breaker trips due to a protective function (electrical fault).
©2012 General Electric All Rights Reserved
Page 15
DET-653C EntelliGuard® G Circuit Breaker Application Guide
9
EntelliGuard G Power Circuit Breaker Section 3. EntelliGuard TU Trip Unit System

Introduction

Reliability without Compromising Protection
Arc Flash and the EntelliGuard TU Trip Unit

24-May-12 Section 3. EntelliGuard TU Trip Unit System

The EntelliGuard TU Trip Unit offers optimum circuit protection and optimum system reliability simultaneously with little or no compromise to either of these critical functions. Reliability and arc flash protection, in one package, at the same time, all the time.
EntelliGuard TU series trip units are available as the standard controller for new production EntelliGuard G ANSI/UL 1066, UL 489 and IEC circuit breakers. EntelliGuard TU designs are also available as direct, functional replacements for GE's PowerBreak, PowerBreak II, WavePro, AKR, and AK circuit breakers. EntelliGuard TU trip units are also available in kit form for many popular non-GE and older GE low voltage power circuit breakers (Refer to DEH-4567). The EntelliGuard® TU technology is also available in GE's molded case Spectra Breaker line 400A-1200A. The Spectra MET (microEntelliGuard) includes the innovative RELT and Zone Selective Interlocking- Instantaneous feature. New, on­board features and communications capabilities enable equipment enhancements, improved operational performance and life extension programs. Performance will vary based on associated circuit breaker and equipment conditions. All EntelliGuard TU Trip Units are Conformal Coated for increased reliability in humid/damp environments.
This section describes the functions as implemented in the EntelliGuard G UL 489 and ANSI/UL 1066 circuit breakers. References or comparisons to other GE circuit breakers are for informational purposes only.
Reliable protection of circuits and equipment has always been the circuit breaker’s primary mission. Providing appropriate protection of the conductors, while preserving selective coordination, has been the primary focus of most system designers. However, what was acceptable in the past is no longer the standard today.
Modern economic reality, coupled with strict regulatory requirements, demand optimal system performance with increased sensitivity to the inherent power system hazards that face operating and maintenance personnel. Safety agencies, local authorities and owner-operators demand better personnel protection and state-of-the-art capabilities to minimize hazards while simultaneously preserving critical loads and system capabilities.
These requirements often seem to be, and sometimes are, in conflict, pitting the speed and sensitivity required to improve arc flash protection against the delays and deliberate decision making required to maximize power system reliability. The EntelliGuard TU, along with the EntelliGuard family of circuit breakers, offers flexible solutions for demanding circuit protection and circuit preservation environments. The EntelliGuard TU is designed to provide the utmost in system protection and reliability simultaneously, with little or no compromise.
Reducing arc flash hazard is a primary concern in many power system designs. The best way to ensure the lowest possible hazard for a particular distribution system is to consider the hazard as the system is designed and make careful selection of the system’s topology, circuit sizes, equipment sizes and protective devices to minimize hazard for the operating and maintenance personnel that will need to use the system for years to come.

The EntelliGuard TU, especially in conjunction with the EntelliGuard G circuit breaker, provides significant flexibility towards solving arc flash hazard problems without excessive sacrifice of system reliability, in terms of selectivity.

The next three to four pages are an overview of the EntelliGuard TU's unique features enabling Arc Flash mitigation and selectivity at the same time. When the downstream breaker/fuse is current limiting, the Waveform Recognition Selective Instantaneous is used to achieve lower Instantaneous pickup settings while maintaining selectivity. This is very effective for 250A and below devices. For Feeder devices above 250A, the Instantaneous Zone Selective Interlocking (I-ZSI) feature is used to achieve selectivity and arc flash mitigation at the same time. The I-ZSI feature is available on Spectra MET and EntelliGuard® TU in the following breakers: EntelliGuard G, Power Break II, WavePro, AK/AKR, and Conversion Kits. By combining the Waveform Recognition Selective Instantaneous and I-ZSI, a system with a 100KAIC bolted fault current can achieve a 8 cal/cm2 or less incident energy level.
One way to lower potential incident energy is to ensure that circuit breakers are able to interrupt using their Instantaneous trips for all expected arcing faults. Figure 3.1 shows the expected arcing currents for 480V systems for various arc gaps representative of switchgear (32mm), switchboards (25mm), MCCs (25mm) and panelboards (13mm). These values were determined using IEEE standard 1548, Guide for Performing Arc-Flash Hazard Calculations,
2002.
©2012 General Electric All Rights Reserved
Page 16
DET-653C EntelliGuard® G Circuit Breaker Application Guide
10

Figure 3.1. Arcing Current

Selectivity with Molded Case Circuit Breakers and Other Devices

Figure 3.2. Selectivity Curve

24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
Figure 3.1 demonstrates the wide range of possible arcing currents predicted by the IEEE standard’s calculations. The actual arcing currents may be lower or higher when consideration is given to the potential error in short circuit calculations, fault current data provided by the utility company, and variance in the actual arcing gap or enclosure’s geometry where the arc occurs. Of particular concern should be the lower end of the possible range of current that may fall below the Instantaneous pickup of a circuit breaker or the current limiting threshold of a fuse. Dangerous incident energy may quickly increase when interruption time increases from a few cycles to a few seconds, even for low arcing current.
The EntelliGuard TU trip unit’s Waveform Recognition Selective Instantaneous provides a unique selectivity capability. When used in conjunction with current limiting devices downstream, the trip unit may be set low, and still maintain significant levels of selectivity. Table 3.1 lists the minimum instantaneous setting above specific GE circuit breakers and the levels of selectivity achieved. Testing and documentation of the selectivity capability of the EntelliGuard Trip unit will be expanded as more test data becomes available. Always consult GE Selectivity reference publication DET-537 for the latest information or contact your GE sales representative for up to date information.
Selectivity above current limiting fuses may also be expected. The required minimum setting may be estimated by examining the peak let-through curve for the fuse. Find the peak let-through current value that is 1.41 times the prospective RMS current. The trip unit should be set such that the instantaneous pickup is above that peak value. The
circuit breaker and fuse may then be selective up to the values identified in Table 3.1. The fuse and circuit breaker combinations have not been tested so performance cannot be guaranteed at this time; however, selectivity is expected for arcing and bolted faults up to the values indicated in the above selectivity table.
Protection between circuit breakers using the EntelliGuard TU trip unit may be further improved using zone selective interlocking. The trip unit’s unique instantaneous zone selective interlocking which can increase selectivity for UL 489 EntelliGuard G mains while allowing to trip instantaneously for faults within their zone of protection allows significant selectivity and arc flash protection at the same time.
Selectivity for an EntelliGuard TU ground fault function and a circuit breaker below may be enhanced by the trip unit’s selective ground fault function and zone selective interlocking. Figure 3.2 demonstrates an 800A circuit breaker under a 1200A ground fault set to be fully selective. See also Tables 3.2 and 3.3.
©2012 General Electric All Rights Reserved
Page 17
DET-653C EntelliGuard® G Circuit Breaker Application Guide
11

Table 3.1. EntelliGuard Selectivity Above GE Current Limiting Circuit Breakers

Load side (branch)
devices

Wavepro,
override

Record Plus G

600A

Record Plus G

400A

Record Plus G

250A

Record Plus E

250A

Record Plus E

150A

Record Plus E

100A

Record Plus E

60A

Record Plus E

30A

Record Plus
B/C

Spectra G

600A

Spectra G

400A

Spectra G

250A

Spectra F

250A

11,200A (2)

Spectra E

150A

9,600A (2)

TECL

3 & 7A

800A (1)

TECL

15A

850A (1)

TECL

30A

1,800A (1)

TECL

50A

3,800A (1)

TECL

100A

7,300A (1)

TECL

150A

11,000A (1)

TEY/TEYF

15-100A

9,900A (1)

14,000A

14,000A

14,000A

14,000A

THQL (240V)

15-60A

9,900A (1)

10,000A

10,000A

10,000A

10,000A

THHQL
(240V)

24-May-12 Section 3. EntelliGuard TU Trip Unit System
Selectivity between any line side (main)Circuit Breaker with a GE EntelliGuard TU trip unit and a load side (branch) GE current limiting circuit breaker, and certain lighting panel type circuit breakers is determined based on the setting of the line side EntelliGuard TU Trip. When the line side EntelliGuard TU Trip unit is set at the value defined in the table or higher the pair is selective over the instantaneous range of the upstream CB up to the limit defined in the table below. The required settings are independent of the line side circuit breaker type and only depend on the load side current limiting circuit breaker. The table below identifies the values for GE's currently produced UL listed current limiting molded case circuit breakers.

Extent of selectivity will depend on line side circuit breaker type. The table below describes how that selectivity is limited by circuit breaker type.

The table below applies at 208 through 480 Volts except where specifically limited to 240V and lower.

Line side (Main) device with EntelliGuard TU trip unit

Frame
Designation
Maximu
m Trip (frame
or
sensor)
EntelliGuard TU
instantaneous
setting must be

> than (3)

20,350A

9,900A (1)

100A 7,190A

29,980A

PowerBreak
II, UL 489 CB
Up to short circuit rating; 65kA, 100kA
or 150kA at
480V, and
200kA at
240V
AKR or AK,
or other
ANSI CB
without a
mechanical
Up to short circuit rating; 65kA, 100kA
or 150kA at
480V.

EntelliGuard G, UL489 CB

Up to
withstand
rating; 42kA,
50kA, 65kA,
85kA or
100kA at
480V
EntelliGuard
G, ANSI CB
Up to
withstand
rating; 65kA,
85kA or
100kA at
480V

Notes:

1. EntelliGuard TU must employ a 400A rating plug or larger

2. EntelliGuard TU must employ an 800A rating plug or larger

3. Any instantaneous overlap seen in time current curves when line side CB is set per table does not indicate a lack of selectivity and may be ignored.

©2012 General Electric All Rights Reserved

15-60A 9,900A (1) 22,000A 22,000A 22,000A 22,000A

Page 18
DET-653C EntelliGuard® G Circuit Breaker Application Guide
12

Table 3.2. Maximum Instantaneous Pickup Multipliers for GE Circuit Breakers

Line side device with Entelliguard TU Trip Unit

PowerBreak II,
UL 489 CB

WavePro or AKR,
ANSI CB

EntelliGuard G,
ANSI/UL Std I

EntelliGuard G, ANSI Ext I

Max Instantaneous in X

Max Instantaneous in X

800A frame

15
15
15
30

1600A frame

15
15
15
30

3000A frame

13
N/A
15
30

3200A frame

N/A
13
15
30

6000A frame

N/A
N/A
15
16 Amperes

Amperes

2000A frame, 2000A plug

30,000

30,000

30,000

60,000

2500A frame, 2500A plug

32,500

N/A

37,500

75,000

4000A frame, 4000A plug

40,000

52,000

60,000

92,000

5000A frame, 5000A plug

N/A

65,000

75,000

95,000

Maximum instantaneous is a multiple of rating plug, the above values may be lower if a smaller rating plug than maximum for frame is used. In PB2 & WavePro CB maximum instantaneous multiplier is limited by frame rating. In Entelliguard G the maximum Instantaneous X may be limited by circuit breaker withstand or short time rating (also known as Icw).
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
Instantaneous selectivity between a circuit breaker with an EntelliGuard TU trip Unit and any non-current limiting circuit breaker may be evaluated via
traditional time current curve analysis or simply multiplying the upstream instantaneous trip setting by .9 which accounts for the tolerance of the line side circuit breaker around the nominal setting. If The EntelliGuard TU's Instantaneous zone selective interlocking capability between similarly equipped circuit breakers is employed then selectivity up to the upstream circuit breaker's full withstand or short circuit rating is possible.
The table below identifies maximum instantaneous pickup multipliers possible for various types and sizes of GE circuit breakers. Lower part of table identifies the maximum instantaneous pickup in amperes for various circuit breaker, sensor and rating plug combinations.
Frame
determines
maximum
instantaneous
pickup (X) for PB2
and WP CB.
Plug/Icw ratio
determines
maximum
possible for
EntelliGuard G
CB. EntelliGuard
values shown are
more maximum
withstand tiers.

2000A frame 15 15 15 30 2500A frame 13 N/A 15 30

4000A frame 10 10 15 23 5000A frame N/A 7 15 19

800A frame, 800A plug 12,000 12,000 12,000 24,000

1600A frame, 1600A plug 24,000 24,000 24,000 48,000

3000A frame, 3000A plug 39,000 N/A 45,000 90,000 3200A frame, 3200A plug N/A 41,600 48,000 96,000

6000A frame, 6000A plug N/A N/A 90,000 96,000

©2012 General Electric All Rights Reserved
Page 19
DET-653C EntelliGuard® G Circuit Breaker Application Guide
13

Table 3.3. Selectivity with EntelliGuard TU Trip Units in ANSI and ICCB/ Power Break II Circuit Breakers

Downstream device with EntelliGuard TU Trip Unit

Power Break II, UL 489 CB

WavePro or AKR, ANSI CB

EntelliGuard G, ANSI/UL Std I

EntelliGuard G, ANSI Ext I

Max Instantaneous in X

Max Instantaneous in X

800A frame

15
15
15
30

1600A frame

15
15
15
30

2000A frame

15
15
15
30

3000A frame

13
N/A
15
30

3200A frame

N/A
13
15
30

4000A frame

10
10
15
23

5000A frame

N/A 7 15
19

6000A frame (UL 489 only)

N/A
N/A
15
N/A Amperes per above multipliers

800A frame, 800A plug

12,000

12,000

12,000

24,000 1600A plug

2000A frame, 2000A plug

30,000

30,000

30,000

60,000 3000A plug

3200A frame, 3200A plug

N/A

41,600

48,000

96,000 4000A plug

5000A frame, 5000A plug

N/A

35,000

75,000

95,000

6000A plug
24-May-12 Section 3. EntelliGuard TU Trip Unit System
Frame determines maximum instantaneous pickup (X) for PB II and WP CB. Plug/Icw ratio determines maximum possible for EntelliGuard GCB. EntelliGuard values shown are more maximum withstand tiers.
1600A frame,
3000A frame,

24,000

39,000

24,000

24,000

N/A 45,000

48,000

90,000

4000A frame,
6000A frame,
Maximum instantaneous is a multiple of rating plug. The above values may be lower if a smaller rating plug than maximum for frame is used. In PB II &
WavePro circuit breakers, the maximum instantaneous multiplier is limited by frame rating. In EntelliGuard G, the maximum Instantaneous X may be limited by circuit breaker withstand or short time rating (also known as Icw). The current numbers above multiplied by 0.9 provide maximum selectivity above non-current limiting if instantaneous is adjusted to maximum and no zone selective interlocking is used.

40,000

40,000

60,000

N/A N/A 90,000

92,000

N/A
Note: For complete listing of all selectivity functionalities see publication DET-537D
©2012 General Electric All Rights Reserved
Page 20
DET-653C EntelliGuard® G Circuit Breaker Application Guide
14
Above Downstream Feeders
The Waveform Recognition Selective Instantaneous
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
The EntelliGuard TU trip unit has Short Time bands under 100msec designed to optimally fit above the Instantaneous clearing times of various GE circuit breakers. Table 3.4 lists the suggested Short Time band that may be used above specific GE circuit breakers for the fastest coordination and consequently fastest EntelliGuard G circuit breaker interruption.
Also listed is the Hazard Risk Category for various available fault currents calculated at the listed Short Time band clearing times and Instantaneous clearing times provided by the EntelliGuard TU trip unit’s Waveform Recognition Selective Instantaneous and its Reduced Energy Let-Through (RELT) Instantaneous trip. The Hazard Risk Category (HRC) levels shown are calculated for a solidly grounded, 480V system, 32mm arc gap, 18 in. working distance and arc in box. Using the optimized Short Time band allows the system to stay at HRC2 most of the time and always less than HRC4. However, use of the RELT Instantaneous trip allows the system to protect at HRC1 or 2 for available fault currents as high as 90kA.
The Instantaneous algorithm in the EntelliGuard TU trip unit will allow a large switchboard or switchgear circuit breaker to be set low yet maintain selectivity. For example, when set to protect the conductors to a motor control center, an 800A feeder circuit breaker’s Instantaneous may be set as low as 8kA nominal. This should provide complete selectivity above the typical 150A and smaller circuit breakers or fuses found in a motor control center.
Allowing for 10% pickup tolerance in the Instantaneous pickup of the feeder circuit breaker would indicate that the feeder would pickup Instantaneously for arcing fault currents approximately 9kA or higher. From Figure 3.1 it can be seen that fault currents of 20-25kA and higher would seem to reliably produce arcing current above 9kA in a variety of configurations. From Table 3.4 it can be seen that an EntelliGuard G circuit breaker clearing instantaneously can maintain HRC1 in a system with up to 42kA available and HRC2 in systems with up to 100kA available – excellent arc flash protection and selectivity simultaneously!
Note: These incident energy calculations do not take into account motor contribution or other factors that may affect expected levels of incident energy or hazard. For a thorough understanding of the incident energy available or HRC in a power distribution system, an Arc Flash Study should be conducted by engineering personnel qualified to provide such analysis.
©2012 General Electric All Rights Reserved
Page 21
DET-653C EntelliGuard® G Circuit Breaker Application Guide
15

Table 3.4. Minimum Selective Clearing Times for an EntelliGuard G Circuit Breaker Above Selected GE Circuit Breakers, and Related HRC Levels at Various Fault Circuits

GE Molded Case Circuit Breaker Family

Circuit
Breaker
Type

Minimum
EntelliGuard TU
Short Time Band

Clearing
Time

480V, 32mm, 24in Working Distance,
Arc in a Box - HRC @ Ibf=

35kA

42kA

50kA

60kA

75kA

90kA

100kA

-
-
TM = Thermal Magnetic. E = Electronic.
AE = Adjustable Electronic. LP = Lighting Panel Application.

GP = General Purpose Application. MCP = Motor Circuit Protector).

HRC = Hazard Risk Category (See NFPA 70E.

Above Other Power Circuit Breakers
Terminology In:
X:
HSIOC:
MCR:
ICW:
ICU:
24-May-12 Section 3. EntelliGuard TU Trip Unit System

FB, FC, TEY, THQL TM, LP 0.025sec 0.08sec 2 2 2 2 3 3 3 TED, TEC TM-GP, MCP 0.025sec 0.08sec 2 2 2 2 3 3 3 TF, TJ, TK TM-GP 0.025sec 0.08sec 2 2 2 2 3 3 3 Spectra E, F, G Frame E-GP 0.025sec 0.08sec 2 2 2 2 3 3 3 Spectra K Frame E-GP 0.033sec 0.088sec 2 2 2 2 3 3 3 Spectra G, K with MVT trip AE-GP 0.025sec 0.08sec 2 2 2 2 3 3 3 Record Plus G Frame E, AE-GP 0.042sec 0.097sec 2 2 2 2 3 3 3 Record Plus E Frame E-GP 0.033sec 0.088sec 2 2 2 2 3 3 3 Power Break with MVT AE-GP 0.058sec 0.113sec 2 2 2 3 3 3 3 Instantaneous Clearing Time RELT Clearing Time

instantaneous 0.050sec 1 1 1 2 2 2 2

RELT Instantaneous 0.042sec 1 1 1 1 2 2 2

Using the EntelliGuard TU trip unit’s unique Instantaneous Zone Selective Interlocking (I-ZSI), the main circuit breaker also can be set to interrupt selectively for faults in its zone of protection. However, the pickup level must be nested to prevent a nuisance trip at the main. Allowing for a 10% tolerance in the pickup current of both trips, the upper boundary of the main’s trip may be estimated at approximately 11kA. Again, Figure 3.1 shows that available fault currents above 25kA will generally produce arcing currents above 11kA. Table 3.4 shows a system with fault currents from 35kA to 100kA, the feeder and main circuit breaker will provide protection at HRC1 or HRC2 selectively above most circuit breakers using short time bands. Coordinated instantaneous settings would provide even better protection while still maintaining selectivity with select feeder breakers. To this capability one can add the RELT instantaneous setting that provides more sensitive and faster protection when needed.
Trip plug rating in amperes. This is the current rating of the rating plug installed in the trip unit. This is the maximum Long Time pickup a trip unit can have with a specific plug installed. A sensor can usually be applied with plugs between 37.5% or 40% to 100% of the sensor rating. Plugs are labeled in amperes.
X is a multiplier that may be applied in front of any rating value to denote a fraction of that rating. Example: The Long Time Pickup may be set at 0.5X of In.
High Set Instantaneous Overcurrent, also known as the Override. This is an Instantaneous protection setting applied near the circuit breaker’s withstand rating required to clear high magnitude faults quickly. In UL489 circuit breakers this is fixed; in UL1066 CBs the override may vary, if present at all.
Making Current Release. A setting provided with each trip unit, based on the specific circuit breaker size, used to protect the circuit against closing on high magnitude faults. The MCR function immediately trips/opens the circuit breaker if high magnitude fault current is sensed at the instant the circuit breaker is closed.
Short Circuit Withstand Rating of a particular circuit breaker in amperes. The withstand rating is defined differently within different standards, but it is always the value of current that a circuit breaker can withstand for some period of time without interrupting.
Short Circuit Interrupting Rating (ISC), or ultimate interrupting rating (ICU) in IEC terms. The maximum short­circuit interrupting rating of a circuit breaker in amperes.
©2012 General Electric All Rights Reserved
Page 22
DET-653C EntelliGuard® G Circuit Breaker Application Guide
16
Long Time Protection
Thermal Long Time Overcurrent

Figure 3.3. Thermal Characteristic: Maximum and Minimum Long Time Delay Bands for a 1000A Long Time Pickup

Breaker Type

TCC

EntelliGuard G:

DES-090

WavePro, PBII, PBI, AK, AKR, Conv Kits

DES-095

24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
The EntelliGuard TU offers two different shapes for Long Time protection curves. Each type of curve is available with 22 different time delays. The shapes may be described as
2
thermal type I
t characteristics and fuse shaped I4t lines. The nominal Long Time pickup is computed from the trip rating plug value (In) multiplied by the Long Time pickup setting. Long Time pickup setting multipliers are user settings and may range from 0.5 to 1.0 in increments of 0.05. The actual Long Time pickup is 112% of the nominal setting (Ir). 112% is to compensate for the Long Time Pickup Tolerance of ±10% that is drawing as “actual value/1+ tolerance)”. For a nominal 1000A Long Time pickup, the actual trip setting is 1120A, drawn as a vertical band between 1120/1.1 and 1120/0.9, or 1018A and 1244A.
The thermal I2t shape is similar to the typical curve of a thermal magnetic circuit breaker and matches the shape of many overcurrent devices used in industry today. The typical shape and range of settings may be seen in Figure 3.3. The range of time delays is shown in Table 3.5 at various multiples of nominal (100%) current setting. Drawn bands also include a mechanical constant time to account for circuit breaker operating and clearing time, which causes the slight widening of the band evident at the lower (right) end of the faster (lower) bands.
©2012 General Electric All Rights Reserved
Page 23
DET-653C EntelliGuard® G Circuit Breaker Application Guide
17

Table 3.4. Thermal Characteristic: Nominal Clearing and Commit Times for X Multipliers of Nominal Pickup

X=
1.5
7.2
10
12
15

Commit

Clear

Commit

Clear

Commit

Clear

Commit

Clear

Commit

Clear

Min CB

4.25

8.04

0.139

0.239

0.072

0.137

0.050

0.104

0.038

0.080

C-2

12.7

24.1

0.417

0.656

0.215

0.352

0.149

0.253

0.095

0.172

C-3

25.5

48.1

0.83

1.28

0.430

0.674

0.298

0.476

0.190

0.315

C-4

34.0

64.1

1.11

1.70

0.57

0.89

0.40

0.62

0.254

0.410

C-5

51.0

96.2

1.67

2.53

0.86

1.32

0.60

0.92

0.38

0.60

C-6

67.9

128

2.22

3.4

1.15

1.75

0.79

1.22

0.51

0.79

C-7

84.9

160

2.78

4.2

1.43

2.18

0.99

1.52

0.63

0.98

C-8
102
192

3.33

5.0

1.72

2.61

1.19

1.81

0.76

1.17

C-9
119
224

3.89

5.9

2.01

3.03

1.39

2.11

0.89

1.36

C-10

136
256

4.44

6.7

2.29

3.46

1.59

2.41

1.02

1.55

C-11

153
289

5.00

7.5

2.58

3.89

1.79

2.71

1.14

1.74

C-12

170
321

5.56

8.4

2.87

4.32

1.99

3.00

1.27

1.93

C-13

204
385

6.67

10.0

3.44

5.18

2.38

3.60

1.52

2.31

C-14

238
449

7.78

11.7

4.01

6.04

2.78

4.19

1.78

2.69

C-15

272
513

8.89

13.4

4.59

6.90

3.18

4.79

2.03

3.07

C-16

306
577

10.0

15.0

5.16

7.76

3.58

5.38

2.29

3.45

C-17

340
641

11.1

16.7

5.73

8.61

3.97

5.98

2.54

3.83

C-18

374
705

12.2

18.4

6.30

9.47

4.37

6.57

2.79

4.21

C-19

408
769

13.3

20.0

6.88

10.3

4.77

7.17

3.05

4.59

C-20

442
833

14.4

21.7

7.45

11.2

5.17

7.76

3.30

4.97

C-21

476
898

15.6

23.4

8.02

12.0

5.56

8.36

3.56

5.35

Max CB

510
962

16.7

25.1

8.60

12.9

5.96

8.95

3.81

5.73

Actual Long Time pickup is 112% of nominal pickup.
Fuse-Shaped Steep Long Time Overcurrent

Figure 3.4. Fuse Characteristic: Maximum and Minimum Long Time Delay Bands for a 1000A Long Time Pickup

Table 3.5.

Breaker Type

TCC

EntelliGuard G:

DES-091

WavePro, PBII, PBI, AK, AKR,
Conv Kits

DES-096

24-May-12 Section 3. EntelliGuard TU Trip Unit System
Algorithm will not commit below 1.5 cycles, clearing time will not be less than 0.08sec. Maximum LT curve is 15XLTPU for Envelope 1 and 2 devices, 10XLTPU for Envelope 3 devices.
The optional steeper fuse characteristic is a straight line
4
t shape for application in systems where fuses and
K=I circuit breakers are used together. Twenty-two different time bands are available in each trip unit.

Figure 3.4 displays minimum and maximum bands. Table 3.6 displays the nominal time delays for each of the 22 bands at various multiples of nominal current pickup.

Drawn bands also include a 30 ms constant time, which accounts for the slight widening evident in the time current curve at the lower (right) end of the faster (lower) time bands.

©2012 General Electric All Rights Reserved
Page 24
DET-653C EntelliGuard® G Circuit Breaker Application Guide
18

Table 3.6. Fuse Characteristic: Nominal Clearing and Commit Times for X Multipliers of Nominal Pickup

X=
1.5
7.2
10
12
15

Commit

Clear

Commit

Clear

Commit

Clear

Commit

Clear

Commit

Clear

Min Fuse

0.675

1.51

0.025

0.080

0.025

0.080

0.025

0.080

0.025

0.080

F-2

1.96

4.37

0.025

0.080

0.025

0.080

0.025

0.080

0.025

0.080

F-3

3.56

7.95

0.025

0.080

0.025

0.080

0.025

0.080

0.025

0.080

F-4

5.57

12.4

0.025

0.080

0.025

0.080

0.025

0.080

0.025

0.080

F-5

8.07

18.0

0.025

0.080

0.025

0.080

0.025

0.080

0.025

0.080

F-6

11.2

25.0

0.025

0.080

0.025

0.080

0.025

0.080

0.025

0.080

F-7

15.1

33.7

0.028

0.080

0.025

0.080

0.025

0.080

0.025

0.080

F-8

20.0

44.7

0.038

0.084

0.025

0.080

0.025

0.080

0.025

0.080

F-9

26.1

58.3

0.049

0.110

0.025

0.080

0.025

0.080

0.025

0.080

F-10

33.8

75.4

0.064

0.142

0.025

0.080

0.025

0.080

0.025

0.080

F-11

43.3

96.7

0.082

0.182

0.025

0.080

0.025

0.080

0.025

0.080

F-12

55.3

123

0.104

0.232

0.028

0.080

0.025

0.080

0.025

0.080

F-13

70.2

157

0.132

0.295

0.036

0.080

0.025

0.080

0.025

0.080

F-14

88.9

198

0.167

0.374

0.045

0.100

0.025

0.080

0.025

0.080

F-15

112
251

0.211

0.472

0.057

0.127

0.027

0.080

0.025

0.080

F-16

141
316

0.266

0.595

0.072

0.160

0.035

0.080

0.025

0.080

F-17

178
397

0.335

0.748

0.090

0.201

0.043

0.097

0.025

0.080

F-18

224
499

0.421

0.940

0.113

0.252

0.055

0.122

0.025

0.080

F-19

280
626

0.528

1.179

0.142

0.317

0.068

0.153

0.028

0.080

F-20

352
785

0.663

1.479

0.178

0.397

0.086

0.192

0.035

0.080

F-21

441
984

0.830

1.853

0.223

0.498

0.108

0.240

0.044

0.098

Max Fuse

540

1204

1.017

2.269

0.273

0.610

0.132

0.294

0.054

0.120

Actual Long Time pickup is 112% of nominal pickup.
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
Algorithm will not commit below 1.5 cycles, clearing time will not be less than 0.08sec.
• Maximum LT curve is 15XLTPU for Envelope 1 and 2 devices, 10XLTPU for Envelope 3 devices.
©2012 General Electric All Rights Reserved
Page 25
DET-653C EntelliGuard® G Circuit Breaker Application Guide
19
Thermal Memory

Short Time Protection

Short Time Pickup
Short Time Bands
Figure 3.5. Short Time Pickup

Figure 3.6. Short Time Transition

24-May-12 Section 3. EntelliGuard TU Trip Unit System
The Long Time and Short Time pickup algorithm also includes a cooling cycle that keeps track of current if it oscillates in and out of pickup range. This Thermal Memory is also active in case the circuit breaker trips on Long Time or Short Time to account for residual heating in conductors. If a circuit breaker is closed soon after a Long Time trip or Short Time trip, a subsequent trip may happen faster than indicated by the time current curve due to the residual cable Thermal Memory effect. In trips without control power, the Thermal Memory is powered from the Trip Unit battery. The cooling algorithm requires up to 14 minutes to fully reset to zero.
The EntelliGuard TU provides a wide range of Short Time
2
pickup settings, I
t characteristics and time bands to optimize selectivity while not sacrificing clearing time unnecessarily. Short Time pickup settings range from 1.5 to 12 times the Long Time pickup setting for the EntelliGuard G circuit breakers in Envelopes 1 and 2. The maximum Short Time pickup for Envelope 3 is 10 times. In Power Break, WavePro, AKR and other circuit breakers, the maximum Short Time pickup may be lower. The transition between Long Time band and Short Time function may happen at the horizontal Short Time Delay Band rather than the vertical Short Time pickup, depending on the following:
How fast or what type of Long Time band is chosen
What Short Time pickup is selected
What Short Time Delay is selected
An example of this may be seen in Figure 3.5 for the combination of Long Time Delay Band and Short Time Delay Band shown in Figure 3.6, any Short Time pickup setting larger than 6X will result in the Long Time band intersecting with the horizontal Short Time delay band rather the vertical Short Time pickup.
The EntelliGuard TU comes with a wide range of adjustable Time Delay Bands, ranging from a minimum of 25ms (clears in 80ms, 55ms for Sensing, Operating and Clearing Time) to 417ms (clears in 472ms). The bands are specially designed to pickup above various circuit breakers and trip systems to provide required selectivity while not sacrificing any more clearing time than required to provide the best possible arc flash protection.

The time bands are shown in Table 3.6 and Figure 3.7.

©2012 General Electric All Rights Reserved
Page 26
DET-653C EntelliGuard® G Circuit Breaker Application Guide
20
Table 3.7. Short Time Delay Bands

Label

Pickup

Clearing

Minimum

0.025

0.080

2nd

0.033

0.088

3rd

0.042

0.097

4th

0.058

0.113

5th

0.092

0.147

6th

0.117

0.172

7th

0.158

0.213

8th

0.183

0.238

9th

0.217

0.272

10th

0.350

0.405

Maximum

0.417

0.472

Figure 3.7. Short Time Delay

Table 3.8.

Breaker Type

TCC

EntelliGuard G:

DES-092

WavePro, PBII, PBI, AK, AKR, Conv
Kits

DES-097

Short Time I2t Slopes

Figure 3.8. Short I2t (In or Out)

Ground Fault Protection
Internal Residual Summation
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
Figure 3.8. The bands may be defined by the formula K = I where K equals 18, 8 and 2 times the nominal Long Time pickup squared. A 30msec fixed time is added to account for circuit breaker mechanical operation, clearing time and variance. Pickup tolerance is 10% of current.
2
t,
The EntelliGuard Trip Unit offers three different Short Time I2t characteristics to allow optimized settings for selectivity and fast protection whenever possible. When using the EntelliGuard Trip Unit in systems that also employ older GE
2
MVT trip units, the EntelliGuard Trip Unit’s maximum I characteristic is equal to the Short Time I
2
t characteristic in
t
the MVT trip.
The position of the I
2
t slopes varies with the Long Time pickup of the respective circuit breaker. The intersection of the Short Time pickup and the Short Time delay band with
2
t slope varies with the Short Time pickup and time
the I delay band.
The three positions for the Short Time I
2
t band are shown in
The maximum (upper) Short Time I2t band may not be used with the minimum Long Time thermal band. Use of the fuse shaped Long Time bands also inhibits use of the Short Time
2
t bands. Only the definite Short Time pickup characteristic
I may be used with the fuse shaped Long Time curves.
The EntelliGuard TU trip unit offers the ultimate in Ground Fault protection. Each trip unit may be provided with the ability to accept a neutral sensor signal and generate an internal Zero Sequence phasor for Ground Fault protection. It may also be equipped with the ability to accept a Zero Sequence phasor signal from an external Zero Sequence CT or residual summation scheme using current transformers. Either Ground Fault method may be used to provide Ground Fault trip or Ground Fault alarm. Four pole circuit breakers may also provide Ground Fault protection based on an external Zero Sequence input signal or a residual sum of all four internal sensors.
The EntelliGuard TU trip unit uses internal air core sensors for current sensing, and the signals are residually summed using advanced digital electronics. A neutral sensor may be located remotely and connected to the trip unit. The connection is limited to 10m (33ft). Due to the air core sensor’s ability to handle a wide range of primary currents without distortion, Ground Fault sensing is accurate for a wide range of phase and current inputs.
©2012 General Electric All Rights Reserved
Page 27
DET-653C EntelliGuard® G Circuit Breaker Application Guide
21
External Zero Sequence Input
Ground Fault Pickup Settings
Table 3.9. Ground Fault Time Delay Bands

Sensor

Minimum

Maximum

400
0.2

0.60

600
0.2

0.60

800
0.2

0.60

1200

0.2

0.60

1600

0.2

0.60

2000

0.2

0.60

2500

0.2

0.48

3000

0.2

0.40

3200

0.2

0.37

4000

0.2

0.30

5000

0.2

0.24

6000

0.2

0.20

Ground Fault Time Delay Bands
Table 3.10. Minimum Ground Fault Pickup and Clear Time

Setting

Power Break I & II,
AKR & WavePro

EntelliGuard G

Ground Fault Protection Curves

Figure 3.9. Ground Fault Characteristics

Instantaneous Protection
24-May-12 Section 3. EntelliGuard TU Trip Unit System
The EntelliGuard TU trip unit is able to accept input from an externally calculated Ground Fault current. The Ground Fault current may be derived using a single Zero Sequence CT or multiple phase CTs connected in a residual summation scheme. External CE marked Zero Sequence or ground return CTs are available for IEC applications, but are not UL Listed. Phase CTs used for a summation connection are UL Listed. Applications for this capability include sensing at the ground return connection for a transformer or generator as well as application in multiple source grounded systems.
All UL 489 and UL 1066 circuit breakers are limited to a maximum nominal pickup setting of 1200A per the National Electrical Code or 60% of the sensor size, whichever is lower. The minimum setting is 20% of sensor size. The available maximum settings per sensor may be seen in Table 3.8.
The EntelliGuard TU trip unit offers four different shapes for the ground fault function:
Definite time with adjustable time delay.
2
I
t slope with adjustable time delay.
4
I
t slope (fuse shaped) with adjustable time delay.
Selective double break I
The definite time and I traditional GF curve shapes. The I shape more in line with downstream fuses. GE’s unique selective double break I
2
t with adjustable time delay.
2
t characteristics provide the
2
t characteristic provides the most
4
t characteristic provides a
selective setting possible while still meeting the applicable UL and NEC standards. In many cases, an 800A circuit breaker may be used under a 1200A ground fault curve selectively (Fig. 3.9).
Ground Fault Time Delay Bands used in the EntelliGuard G circuit breakers range from 42msec to 942msec. In Power Break I, Power Break II, WavePro and AKR circuit breakers, the minimum GF Time Delay Band is 58msec and the maximum is 417msec.

The available minimum settings per circuit breaker type are shown in Table 3.9. The maximum Time Delay Band setting for all circuit breakers is 0.940sec with a 1sec clear.

The EntelliGuard TU trip unit may provide several types of Instantaneous protection, depending on the circuit breaker in which it is installed. The different types of Instantaneous protection are as follows:
• Adjustable Selective Instantaneous: Provided on Power
Break, Power Break II, WavePro, AK, AKR, Conv Kits and EntelliGuard G.
• Extended Range Adjustable Selective Instantaneous: An
available option on ANSI EntelliGuard G circuit breakers.
• High Set Instantaneous Overcurrent Trip: Provided on

Minimum pickup 0.058sec 0.042sec

Minimum clear 0.113sec 0.097sec

Maximum pick 0.417sec 0.940sec

Maximum clear 0.470sec 1.000sec

Power Break II and some EntelliGuard G circuit breakers, also called an override.
• Making Current Release (MCR): Provided on all EntelliGuard
G circuit breakers.

• Reduced Energy Let-Through Instantaneous Trip: An available option on Power Break, Power Break II, WavePro, AK, AKR, Conv Kits, and EntelliGuard G circuit breakers.

©2012 General Electric All Rights Reserved
Page 28
DET-653C EntelliGuard® G Circuit Breaker Application Guide
22
Adjustable Selective Instantaneous

Table 3.11. Maximum Adjustable Instantaneous Pick-up for EntelliGuard G Circuit Breakers with Normal or Extended Range Option

“In” (Plug
Rating, A)

Withstand Rating

42
50
65
85
100

Normal

Range

Extended

Range

Normal

Range

Extended

Range

Normal

Range

Extended

Range

Normal

Range

Extended

Range

Normal

Range

Extended

Range

150-2,000

15
N/A
15
N/A
15
30
15
30
15
30

2,200

N/A
N/A
15
N/A
15
28
15
30
15
30

2,400

N/A
N/A
15
N/A
15
25
15
30
15
30

2,500

N/A
N/A
15
N/A
15
24
15
30
15
30

3,000

N/A
N/A
15
N/A
15
20
15
26
15
30

3,200

N/A
N/A
N/A
N/A
15
19
15
25
15
29

3,600

N/A
N/A
N/A
N/A
15
17
15
22
15
26

4,000

N/A
N/A
N/A
N/A
15
15
15
20
15
23

5,000

N/A
N/A
N/A
N/A
N/A
N/A
15
16
15
19

6,000

N/A
N/A
N/A
N/A
N/A
N/A
13
N/A
N/A
N/A

Table 3.12. Time Current Curves

Breaker Type

TCC

EntelliGuard G: Selective
Instantaneous & RELT

DES-094

& RELT

DES-101

Power Break: Instantaneous

DES-099

Power Break II: Selective
Instantaneous and HSIOC (Override)

DES-100

24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System

Each of these Instantaneous trips provides optimum protection, selectivity or both as required for different applications, subject to the capabilities of the respective circuit breakers in which the trip units are installed.

The EntelliGuard TU uses an exclusive algorithm, developed by GE, to recognize the wave shape of fault current within a cycle. With the improved analysis of the fault current wave shape, the trip unit allows the circuit breaker to trip immediately yet provide superior selectivity when used above current limiting circuit breakers or fuses. In many cases, the trip unit’s Instantaneous pickup may be set quite low yet allow for complete selectivity up to the circuit breaker’s full withstand level. For a list of possible selective combinations of GE circuit breakers employing the EntelliGuard TU trip unit and various downstream overcurrent devices, see GE publication DET-537.
The EntelliGuard TU trip unit can be furnished with one of two Instantaneous adjustment ranges. The standard adjustable range may be as high as 15X the trip plug value on all UL 489 or UL 1066 circuit breakers. An optional Extended Range Adjustable Selective Instantaneous, as high as 30X, may be provided for UL 1066 Listed Low Voltage Power Circuit Breakers (LVPCBs). LVPCBs also allow for this adjustable Instantaneous trip to be turned off. The minimum adjustable Instantaneous pickup setting for all circuit breakers is 2X the trip plug rating. The available maximum pickup settings are described in Table 3.10. The maximum Instantaneous pickup is limited by the circuit breaker’s withstand rating.
The Adjustable Selective Instantaneous will clear a fault in three cycles when used in 60Hz or 50Hz applications. Zone Selective Interlocking (I-ZSI) may be used with this Instantaneous function, allowing several breakers with overlapping Instantaneous protection to be selective with each other. Because each circuit breaker is set to trip Instantaneously for faults within their respective zones of protection, fast protection and selectivity are achieved simultaneously.
The special selective Instantaneous algorithm allows any circuit breaker above current limiting devices to be set with a relatively low Instantaneous pickup and still achieve significant selectivity. The system may be able to provide Instantaneous protection for most faults, including high impedance arcing fault, while maintaining significant levels of selectivity. Figures 3.11 and 3.12 later in this document
©2012 General Electric All Rights Reserved
demonstrate the performance of the Instantaneous ZSI capability
.
Power CB: Selective Instantaneous
Page 29
DET-653C EntelliGuard® G Circuit Breaker Application Guide
23
High Set Instantaneous Overcurrent (HSIOC)
Making Current Release (MCR)

Table 3.13. HSIOC Locations

Short
Circuit Tier

Interrupting Rating (A)

UL489

Override

UL1066

Override

240V

480V

600V

UL489 I
CW

UL1066 ICW

S

65,000

65,000

50,000

42,000

50,000

42,000

None

N

65,000

65,000

65,000

42,000

65,000

42,000

None

H

85,000

85,000

65,000

50,000

65,000

50,000

65,000

P

100,000

100,000

65,000

50,000

65,000

50,000

65,000

E

85,000

85,000

85,000

N/A

85,000

N/A

None

M

100,000

100,000

100,000

65,000

85,000

65,000

85,000

B

100,000

100,000

100,000

N/A

100,000

N/A

None

L

150,000

150,000

100,000

85,000

100,000

85,000

10,000

Reduced Energy Let-Through (RELT) Instantaneous Trip
24-May-12 Section 3. EntelliGuard TU Trip Unit System
The EntelliGuard TU trip unit’s HSIOC pickup is similar to the fixed override used by other trip units and circuit breakers in the industry. In EntelliGuard G, the HSIOC setting is changed automatically by the trip unit if the normal adjustable Instantaneous is turned off (LVPCB only). When adjustable Instantaneous setting is turned off, HSIOC nominal setting becomes 98% of the circuit breaker’s Short Time withstand setting. In all other cases, in the EntelliGuard G family of circuit breakers, the HSIOC is set high enough to allow full selectivity up to the circuit breaker’s short time withstand rating.
For circuit breakers with an HSIOC trip function, the location of the HSIOC trip is shown by the line that reaches the
0.01sec axis at the bottom of the TCC. The location of that line is shown in Table 3.11. In many applications, the
EntelliGuard G circuit breaker with an EntelliGuard TU trip unit will be completely selective up to the HSIOC pickup or
This form of Instantaneous protection is provided on all EntelliGuard G circuit breakers. This function provides protection in case the circuit breaker is closed on an unusually high current. A circuit breaker that experiences 15 times (15x) or more its plug rating is possibly closing in on a fault caused by incorrectly wired conductors, forgotten grounding cables or some other type of unusual low impedance fault.
Alternatively, it is closing on a very low impedance arcing fault. In either case, there is a possibility that equipment may be damaged by the high fault current or an arc flash hazard has been inadvertently created. The MCR provides very fast protection when the circuit breaker is closed and for the first six cycles thereafter. After the six cycles have elapsed, the MCR is turned off and the circuit breaker reverts to its adjustable Instantaneous pickup and HSIOC if provided. The
MCR will clear fault current in 40msec or less. the circuit breaker’s full short circuit rating, even with the adjustable Instantaneous on.
All UL Overrides are -0% tolerance, ANSI Override pickup at -0% or -9% based on Adjustable Selective Instantaneous being on or off.
The EntelliGuard TU trip unit provides an optional second, user-adjustable, RELT Instantaneous trip, which allows a circuit breaker to be temporarily set to a more sensitive pickup to provide better protection, only when better protection is needed and some selectivity may be sacrificed. The RELT pickup is adjustable from 1.5X to 15X of plug rating, independently of the normal adjustable selective Instantaneous. It may be set higher or lower than the selective Instantaneous.
The user must make two entries at the trip unit: (1) Pickup settings (1.5-15X of the plug) and (2) ON, OFF or REMOTE. ON/OFF enables or disables the pickup setting. REMOTE allows the RELT Instantaneous pickup to be enabled via application of 24Vdc or Vac at the RELT input terminals or serial communications via the Modbus or Profibus communication port. The RELT pickup may be enabled via serial communication or remote 24V signal, but both need to be indicating “OFF” for the RELT Instantaneous pickup to be disabled. The RELT input command may be wired to a manual switch, automatic sensor or, via external logic,
When the EntelliGuard TU trip unit has the RELT
Instantaneous pickup enabled, the trip unit provides a
feedback signal via an optically isolated dry contact and
serial communication. This provides positive feedback that
the trip unit has received and reacted to the RELT Enable
command.
The EntelliGuard TU trip unit’s RELT capability provides the
ultimate in user flexibility for wiring and controlling an
alternate Instantaneous setting for temporary use to reduce
personnel hazard. The RELT Instantaneous pickup clears
fault current in 42msec or less at 60Hz.
RELT capability may be provided on a trip unit with or
without control power. If 24V is provided to the RELT input,
the trip unit will use the RELT Instantaneous trip setting.
However, without control power connected to the trip unit
permanently, indication that the trip unit is in the RELT mode
may not be reliably communicated. If reliable
communication that the trip unit is in the RELT mode is
desired, it is suggested that the trip unit be permanently
connected to 24Vdc control power.
to one or more signal sources.
©2012 General Electric All Rights Reserved
Page 30
DET-653C EntelliGuard® G Circuit Breaker Application Guide
24
Reduced Energy Let-Through Switch Wiring

Figure 3.10. Integrated Switch and LED, Spring Return from “Test” to “Off,” Latched in “On”

Zone Selective Interlocking (ZSI)
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
The RELT switch may be connected to a manually operated two-position switch, a remote sensor, or both simultaneously. The EntelliGuard TU trip unit provides a feedback capability directly from the trip so the user is able to verify that the signal was received by the trip unit and the settings have changed. Optionally, an indicating light may also be connected to the source of control power so the user knows if control power is available to change the setting. The trip unit does not require its own control power to accept a RELT input and change the Instantaneous trip pickup according to the user settings. However, if control power is available to the trip unit, the feedback signal will function immediately, rather than when the trip unit becomes self-powered through its load current (Fig. 3.10).
This configuration provides positive indication that the trip unit has
received and processed the RELT "On" signal. It Also provides a control power check. Caution: It is recommended that RELT output be wired to an appropriate annunciation when remote activation control of RELT is used.
NOTE: When using the RELT function in conjunction with remote enable/disable control, it is strongly recommended that the trip unit be provided with permanently connected control power and that the RELT status output be assigned to a trip output contact. The trip output contact should be wired to appropriately located annunciation. The trip unit will accept a command to enable the RELT instantaneous pickup setting via local HMI control, a 24Vac/dc voltage applied at the input terminals or serial communication. Regardless how the enable command is received, the trip unit will be in the RELT mode when protection is required. However, the status indicating contacts will only close if the trip unit is powered through the internal current transformers or 24Vdc control power. Lack of 24Vdc control power could provide unreliable indication of RELT status due to low load conditions on the circuit breaker.
The EntelliGuard TU trip unit’s ZSI capability differs from that found in other circuit breaker trips in two significant ways:

1. It allows independent and separate settings of the unrestrained (in zone protection) and the restrained (back up protection) bands.

2. It provides simultaneous and independent ZSI of both the Short Time and Instantaneous protection. This allows each circuit breaker to zone interlock with upper tier circuit breakers between ST band to ST band, Instantaneous to Instantaneous, or Instantaneous to Short Time.
The EntelliGuard TU trip unit's fast ZSI system is able to interlock Ground Fault, Short Time and Instantaneous. When required for feeder selectivity the main is able to be set faster than the feeder without any sacrifice in selectivity. As long as the main breaker's pickup is set above the feeder's pickup the two devices will remain selective. Each circuit breaker in a ZSI scheme allows separate user settings for the restrained (backup) and unrestrained (in zone protections) for ground fault and short time protection. For the lowest tier device in the scheme the restrained and unrestrained are set to the same values. For instantaneous protection there is only one pickup setting required.
Instantaneous protection may also be interlocked such that all circuit breakers above the one whose zone has the fault will shift from Instantaneous clearing to a 0.058msec time band. Since it is expected that faults of enough magnitude to engage the Instantaneous pickup are dangerously high, all zone selective interlocked Instantaneous trips that receive a restraint signal are shifted to the same band. Should the bottom circuit breaker fail to clear for whatever reason, quick back up protection from both ties and feeders is provided.
Short Time and Ground Fault bands for zone interlocked circuit breakers may be set to any band available to the trip. Figure 3.11 shows two circuit breakers set to protect at their unrestrained settings. Figure 3.12 shows the same two circuit breakers while a fault is detected below the lower circuit breaker in the system and after a restraint signal is received by the upper circuit breaker’s trip unit. The upper circuit breaker’s Short Time band has shifted from the user setting of 0.025sec to a user set restrained band of 0.092sec. The Instantaneous has shifted from the adjustable selective Instantaneous band clearing in 0.050sec to the fixed restrained band of 0.058sec, clearing in 0.113sec. This allows the lower circuit breaker to clear faults within their zone of protection above 7,000A RMS and 11,000A RMS respectively, clearing under 100msec, while maintaining full selectivity for faults up to 85,000A.
©2012 General Electric All Rights Reserved
Page 31
DET-653C EntelliGuard® G Circuit Breaker Application Guide
25

Table 3.14. Instantaneous ZSI on EntelliGuard TU Trip Units in ANSI EntelliGuard G Circuit Breakers

Downstream

Upstream

EntelliGuard G, ANSI CB

EntelliGuard G ANSI Low Voltage Power CB. Long Time Curves, Short Time pickup and Instantaneous
pickup must be adjusted per TCC

Frame &
Sensor

AIC Tier,
at 240 &
480V

800A

1600A

2000A

65kA
85kA
85kA
100kA
65kA
85kA
85kA
100kA
65kA
85kA
85kA
100kA

800A

N-65kA

65
65
65
65
65
65
65
65
65
65
65
65

800A

H-85kA

65
65
85
85
65
65
85
85
65
65
85
85

800A

E-85kA

65
65
85
85
65
65
85
85
65
65
85
85

800A

M-100kA

65
65
85
85
65
65
85
85
65
65
85
85

1600A

N-65kA

65
65
65
65
65
65
65
65

1600A

H-85kA

65
65
85
85
65
65
85
85

1600A

E-85kA

65
65
85
85
65
65
85
85

1600A

M-100kA

65
65
85
85
65
65
85
85

2000A

N-65kA

2000A

M-100kA

3200A

N-65kA

3200A

E-85kA

3200A

M-100kA

3200A

B-100kA

3200A

L-150kA

4000A

M-100kA

4000A

B-100kA

4000A

L-150kA

5000A

M-100kA

5000A

B-100kA

5000A

L-150kA

24-May-12 Section 3. EntelliGuard TU Trip Unit System
2000A 2000A

H-85kA

E-85kA

S-or N-
H-
E-
M- or P-
S-or N-
H-
E-
M- or P-
S-or N-
65 65 65 65 65 65 85 85 65 65 85 85 65 65 85 85
H-
E-
M- or P-

Selectivity values are shown in kA.

Note: For complete listing of all ZSI functionalities see publication DET-537.

©2012 General Electric All Rights Reserved
Page 32
DET-653C EntelliGuard® G Circuit Breaker Application Guide
26

Figure 3.11. Zone Selective Interlocked CB, Upper CB Shown “Unrestrained”

Figure 3.12. Zone Selective Interlocked CB, Upper CB Shown “Restrained”

Universal Trip Rating Plugs

Figure 3.13. EntelliGuard Trip Unit Rating Plug Catalog Number Guide

24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
The EntelliGuard TU trip system is composed of trip units and trip rating plugs along with the sensors and wiring provided in the EntelliGuard G circuit breaker to support the trip. Rating plugs are used to lower the Long Time adjustment range of the sensor provided in the circuit breaker.
The EntelliGuard TU trip rating plugs are unique in that they can be used with multiple trip units and circuit breakers within a specific sensor range, rather than only with a single specific sensor. The trip rating plug catalog number, shown in Figure 3.13, identifies the rating as well as the minimum and maximum sensor rating the plug may be used with. Table 3.12 lists trip rating plugs available for each sensor. Table 3.13 lists the two-digit codes used within the trip rating plug catalog numbers and the sensor current ratings to which they are mapped.
©2012 General Electric All Rights Reserved
Page 33
DET-653C EntelliGuard® G Circuit Breaker Application Guide
27

Table 3.15. Trip Rating Plug Specifications

Trip Plug Catalog
Number

Plug
Rating

May Be Used With

Minimum
Sensor

Maximum
Sensor

GTP0060U0101

60A1

150A3

150A3

GTP0080U0101

80A1

150A3

200A4

GTP0100U0103

100A2

150A3

200A4

GTP0125U0103

125A1

150A3

200A4

GTP0150U0404

150A

150A3

400A

GTP0200U0404

200A

200A4

400A

GTP0225U0406

225A

400A

600A

GTP0300U0408

300A

400A

800A

GTP0350U0408

350A

400A

800A

GTP0400U0410

400A

400A

1000A

GTP0450U0612

450A

600A

1200A

GTP0500U0613

500A

600A

1250A5

GTP0600U0616

600A

600A

1600A

GTP0700U0816

700A

800A

1600A

GTP0800U0820

800A

800A

2000A

GTP0900U1020

900A

1000A

2000A

GTP1000U1025

1000A

1000A

2500A

GTP1100U1225

1100A

1200A

2500A

GTP1200U1232

1200A

1200A

3200A

GTP1500U1640

1500A

1600A

4000A

GTP1600U1640

1600A

1600A

4000A

GTP2200U2550

2200A

2500A

5000A

GTP2400U2564

2400A

2500A

6400A5

GTP2500U2564

2500A

2500A

6400A5

GTP3000U3064

3000A

3000A

6400A5

GTP3200U3264

3200A

3200A

6400A5

GTP3600U4064

3600A

4000A

6400A5

GTP4000U4064

4000A

4000A

GTP5000U5064

5000A

5000A

6400A5

GTP6000U6064

6000A

6000A

6400A5

Table 3.16. Trip Rating Plug Codes

Sensor Designation

Sensor Rating

01

150A1

02

200A2

03

225A4

04

400A

06

600A

07

630A3

08

800A

10

1000A

12

1200A

13

1250A3

16

1600A

20

2000A

25

2500A

30

3000A

32

3200A

40

4000A

50

5000A

60

6000A

64

6400A3

24-May-12 Section 3. EntelliGuard TU Trip Unit System

GTP0250U0407 250A 400A

GTP0750U0820 750A 800A 2000A

GTP1900U2050 1900A 2000A 5000A GTP2000U2050 2000A 2000A 5000A

630A5

1 Sensor available in WavePro and AKR only. 2 Sensor available in Power Break only. 3 Sensor available in IEC listed circuit breaker only. 4 Used on Conv Kits

Table 3.17 lists the plugs available for each sensor in the various circuit breakers in which the EntelliGuard TU may be installed.

1 WavePro & AKR only. EntelliGuard G min. trip plug is 150A. 2 PowerBreak only. EntelliGuard G min. trip plug is 150A. 3 WavePro & AKR only. EntelliGuard G min. sensor is 400A. 4 PowerBreak only. EntelliGuard G min. sensor is 400A. 5 IEC only sensor, UL equivalents are 600A. 6 Used on ITE and Allis Chalmers Conv Kits
©2012 General Electric All Rights Reserved

6400A5

GTP4000K40406 4000A 4000A 4000A

Page 34
DET-653C EntelliGuard® G Circuit Breaker Application Guide
28

Table 3.17. EntelliGuard G Rating Plug Logic (UL 489, UL 1066, IEC)

Breaker Frame/Sensor (A)

All

UL/ANSI

IEC
All
All

UL/ANSI

IEC
All
All
All
UL

IEC/ANSI

All
All

UL/IEC

IEC
400
600
630
800

1000

1200

1250

1600

2000

2500

3000

3200

4000

5000

6000

6400

150 200 225
225
250
250
250 300
300
300
300
350
350
350
350
400
400
400
400
400
450
450
450
450
450
500
500
500
500
500
500
600
600
600
600
600
600
600
630
630
630
630
630
630
700
700
700
700
700
750
750
750
750
750
750
800
800
800
800
800
800 900
900
900
900
900 1000

1000

1000

1000

1000

1000

1100

1100

1100

1100

1100

1200

1200

1200

1200

1200

1200

1200

1250

1250

1250

1250

1250

1250

1500

1500

1500

1500

1500

1500

1600

1600

1600

1600

1600

1600 1900

1900

1900

1900

1900

1900

2000

2000

2000

2000

2000

2000

2200

2200

2200

2200

2200

2400

2400

2400

2400

2400

2400

2400

2500

2500

2500

2500

2500

2500

2500

3000

3000

3000

3000

3000

3000

3200

3200

3200

3200

3200

3600

3600

3600

3600

4000

4000

4000

4000

5000

5000

5000

6000

6000

6400

Universal Spare Trip Unit
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
EntelliGuard G circuit breakers will accept a Universal Spare Trip Unit. This unique trip unit may be used in any EntelliGuard G circuit breaker regardless of frame size, sensor size, short circuit rating or whether the circuit breaker is listed under UL 489, ANSI/UL 1066 or IEC 947 standards. Should any circuit breaker’s trip unit fail to operate for any reason, this one universal trip unit may be used as a replacement.
Once an EntelliGuard TU trip unit, including the Universal Spare Trip Unit, is associated with a specific EntelliGuard G circuit breaker, it may only be used with that specific circuit breaker. If swapping between EntelliGuard G circuit breakers is required, a trip unit may only be swapped between circuit breakers with equal sensor ratings, short circuit ratings and standard listing. Before the circuit breaker may be used with a swapped or new trip unit, the trip unit must be mapped to the circuit breaker.
The Re-mapping procedure is done by Pressing simultaneously the "Right", "Left", and "Up" Arrow all at the same time (should be able to do with one hand). "BIM OK" will be flashing in the upper left hand corner of the LCD when this is performed. Another Method is to use Modbus Command 107 "Upload BIM" Either procedure requires the trip unit to be mounted to the breaker and control power be provided to the trip unit from permanently connected control power or a portable power supply via the front port.

Front 24VDC Power is provided by Either the GTUTK20 Test Kit or the Portable Battery Pack, TVPBP and TVPBPACC.

All Universal Trip units have the following format G1X00----­RXXXX. The middle 5 digits describe the trip unit protection options and features.
©2012 General Electric All Rights Reserved
Page 35
DET-653C EntelliGuard® G Circuit Breaker Application Guide
29

Table 3.18. Universal Spare Trip Unit Options (User-Selected)

Feature

#

Option

1

Standard (Circuit Breaker Curves)

2

Standard and Fuse Curves

1

Standard

2

Extended Range

1

None

2

Standard (Internal GF)

3

Ground Input

Arc Flash
Protection

1

No RELT

2

RELT

1

Short Time and Ground Fault

Short Time, Ground Fault and Instantaneous

1

None

2

Modbus

3

Profibus

1

Standard (ammeter)

2

Advanced (A, V, E and P)

3

Diagnostic (Advanced and WFC)

Example Universal Trip Cat#: G1X00L4T6MRXXXX
24-May-12 Section 3. EntelliGuard TU Trip Unit System
Universal Trip Units may be ordered with a limited set of options. It is suggested that they be ordered with the widest range of options used within a facility, as any unnecessary functions can always be disabled or turned off (except for Ground Fault) during set up by the user. The user-selected options for the Universal Trip Unit are listed in Table 3.18.

Long Time

Instantaneous

Ground Fault*

Zone Selective

Interlocking

2

Communications

Metering

* Mains and ties in solidly grounded multiple source substations will usually require ground input type ground fault protection. Feeders will use standard internal ground fault protection.
Description: Universal EntelliGuard TU Trip unit for a EntelliGuard G Breaker with LSIG, Zone Selective Interlocking (Short Time, Ground Fault, Instantaneous), Modbus, Full Metering, Waveform Capture, RELT and Bell Alarm with Lockout/Manual reset
©2012 General Electric All Rights Reserved
Page 36
DET-653C EntelliGuard® G Circuit Breaker Application Guide
30

Table 3.19. Relay Functions Available in EntelliGuard G Circuit Breakers with EntelliGuard TU Trip Units

Functions

Trip

Alarm

Display

Output
Contact2

Serial
Comm.

Output3

1 2 Dedicated

Protective

Voltage Unbalance

X X -

Under Voltage

X X -

Over Voltage

yes
yes
yes
yes
yes
X X -

Current Unbalance

X X -

Power Reversal

X X -

Status

Current Level Alarm, 2 Settings Available

no
yes
yes
yes
yes
X X -

Health Indication (Bad)

X X -

Health Indication (Good)

X X -
RELT ON Status
X - -

Ground Fault Alarm Status

no
no
yes
yes
yes
X X -

ZSI Output /Input

- - X

Diagnostics

Metering

Current (Phases A, B, C, N)

- - -
Voltage (Phase A, B, C)
no
no
yes
no
yes
- - -

Energy (kWh, Total)

- - -

Real Power (Watts, Per Phase and Total)

- - -

Apparent Power (Watts, Per Phase and Total)

no
no
- - -

Reactive Power

no
no
- - -
1 User set to PH-N or PH-PH.
2 Output contacts are low signal (Hi-Fi).

3 When top unit has RELT, output 1 is dedicated to RELT ON status.

Relay Functions
Protective Relays
Voltage-Unbalance Relay
Table 3.20. Voltage Unbalance Settings

Setting

Option

Voltage unbalance pickup

Adjustable from 10% to 50% in increments of 1%.

Voltage
User adjustable from 1sec to 15sec in
zero (0) will disable the relay.
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
yes yes yes yes yes yes yes yes yes yes
yes yes yes yes yes yes yes yes yes yes
no yes yes yes yes
3
Trip Target Trip Information Trip Counter Event Logging (Trips, Alarms, I/O) Waveform Capture
1
no yes yes yes yes no no yes yes yes
no no yes yes yes
no no yes no yes
no no yes no yes
no no yes no yes
no no yes no yes
no no yes no yes
no no yes no yes
no no yes no yes no no yes no yes no no
yes yes
yes yes
- - -
- - -
- - -
- - -
- - -
The EntelliGuard TU offers various protective and alarm relay functions that may be displayed on the LCD screen, assigned contact outputs or communicated serially (Table
3.19).
Protection relays may be set by the user to alarm, trip the circuit breaker or both. Alarms and trips are displayed on the local LCD trip and communicated serially. Alarms may also be assigned to one of two output contacts. The Trip Alarm settings are independently set for each relay function.
This function compares the highest or lowest phase voltage with the average of all three phases and initiates a trip if the difference exceeds the set point. The true RMS voltage is computed for each phase (Table 3.20).
unbalance delay
increments of 1sec. Setting this value to
©2012 General Electric All Rights Reserved
Page 37
DET-653C EntelliGuard® G Circuit Breaker Application Guide
31
Current Unbalance Relay

Table 3.21. Current Unbalance Settings

Item

Options

pickup
increments of 1%.
zero (0) will disable the relay.
Under Voltage Relay
Under Voltage Relay Zero-Volt Trip Enable

Table 3.22. Under Voltage Settings

Item

Options

pickup
increments of 1%.
User adjustable from 1sec to 15sec in
to zero (0) will disable the relay.
Over Voltage Relay

Table 3.23. Over Voltage Settings

Item

Options

pickup
increments of 1%.
to zero (0) will disable the relay.
Power-Reversal Relay

Table 3.24. Power-Reversal Settings

Item

Options

pickup
in increments of 10 kW.
zero (0) will disable the relay.
Power-Direction Setup
Potential Transformer Primary Voltage
Potential Transformer Connection
Power Demand Intervals
Current Alarm
Trip Logic Inputs
24-May-12 Section 3. EntelliGuard TU Trip Unit System
This function compares the true RMS current in the highest or lowest phase with the average of all three phases and
Power reversal
User adjustable from 10 kW to 1990 kW
initiates a trip if the difference exceeds the set point (Table.
3.21).

Power reversal delay setting

User adjustable from 1sec to 15sec in increments of 1sec. Setting this value to
Current unbalance
Adjustable from 10% to 50% in
This function selects the normal power flow direction for the

Current unbalance delay setting

User adjustable from 1sec to 15sec in increments of 1sec. Setting this value to
breaker, either from line to load or from load to line. This direction setup also affects the sign of the normal power metering displays.
This function measures the true RMS voltage in all phases and initiates a trip if any phase voltage drops below the set point.
The Trip Unit gets its voltage input from an externally mounted central module, called a Voltage Conditioner. The Voltage Conditioner is wired to each trip unit in a line-up. Voltage Conditioner Cat#: PLVC1G01
This function determines if the relay trips when all three­phase voltages drop to zero volts. Uses the same timing set for the Under-Voltage Relay (Table. 3.22).
Select the appropriate potential transformer connection, either line-to-line (Ph-Ph) or line-to-neutral (Ph-N).
This function sets the power demand interval, which can be
Under voltage
Adjustable from 50% to 90% in
in the range of 5min to 60min, in steps of 5min. This set­point specifies the time interval for power demand

Under voltage delay setting

increments of 1sec. Setting this value
This function measures the true RMS voltage in all phases and initiates a trip if any phase voltage exceeds the set point. See Table. 3.23.
Over voltage

Over voltage delay setting

User adjustable from 110% to 150% in
User adjustable from 1sec to 15sec in increments of 1sec. Setting this value
This function measures the direction of power flow through the breaker and initiates a trip if a sufficient magnitude of reverse power is detected (Table. 3.24).
averaging. The trip unit calculates a rolling average of breaker power over this time interval.
The Trip unit provides two types of current alarm: Current Alarm 1 and Current Alarm 2. The current alarm’s ON/OFF pickup settings are user adjustable from 0.5 to 1.0 xIn in steps of 0.05. The trip unit does not allow the current alarm OFF set-point to be set above the ON threshold. If the highest measured phase current goes above the current alarm 1 or current alarm 2 ON set-point, and then remains above the set-point for more than 60sec, the output will close if assigned to either of these alarms. If the current falls below the current alarm 1 or current alarm 2 set-point for more than 60sec, the output, if assigned to the current alarm, will open. This is a definite time function with a 60s delay and a 60sec cool down period. Both periods are fixed.
The trip unit is able to receive two hardwired input signals. Either can be a 24Vac or Vdc signal. The inputs can be assigned to three main functions:
©2012 General Electric All Rights Reserved
Reduced Let Through Energy "RELT" instantaneous
protection "ON".

Breaker "Trip"

Breaker "RESET"
Page 38
DET-653C EntelliGuard® G Circuit Breaker Application Guide
32

Table 3.25. Input Assignments Possible

Input

Assignment

Summary Description

OFF

No action taken.

TRIP

Will cause the circuit breaker to trip

Input causes the unit to use the RELT set-
via serial communications.
Output contacts remotely.
OFF

No action taken.

TRIP

Will cause the circuit breaker to trip

Output contacts remotely.
Outputs for EntelliGuard G Circuit Breakers

Table 3.26. Output Configuration

Function

Group #

Summary Description

Closes when GF alarm is activated.
Over-current trip
Over-voltage trip closes the relay.
Closes relay when Reduced Let
or 2.
Any protective
Closes relays when protective the
Exceeding current alarm pick-up
Exceeding current alarm pick-up
Health status. NO
communication
Relay contact will change state

Waveform Capture

24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
Table 3.25 shows the assignment for the inputs.

RELT

1

RESET

2

RESET

point as long as input is active. Note: RELT must be set to REMOTE at the Trip HMI or
Input causes Output Contacts (non RELT) to open. This will also clear the event information from the front screen. Enables the ability to open the Alarm
Input causes Output Contacts (non RELT) to open. This will also clear the event information from the front screen. Enables the ability to open the Alarm
Note: When RELT is Optioned, Input1 is dedicated to RELT. Contacts are rated for 30 VDC/25 VAC MAX, 1 Amp.
The number of outputs available varies by breaker. The EntelliGuard G circuit breaker has three. These outputs are relay contact outputs to secondary disconnect. Each output can be configured per Table 3.26.
When a fault has taken place, it is important to visualize the event. The Waveform Capture option included in the advanced trip unit can track and visualize any fault event. The device tracks eight cycles, four before and four after the event, with resolution of 48 samples per cycle at 60Hz and stores the results in memory. It registers events in all three phases and the neutral. After the event, the waveform is stored in COMTrade format and can be accessed by using the waveform client module of the Enervista software. When the upload into this software is complete, the tripuUnit will reset this function and be available to register the next event.

GF alarm 1

(GF, INST, LT, ST)

RELT on 7

relay

Current alarm 1 4

Current alarm 2 5

or NC may be assigned to Health OK via serial
Relays 1 or 2.
2
Relays 1 or 2.
Through Energy Instantaneous pickup setting is enabled. Relays 1
3
relay is in pickup. Relays 1 or 2.
closes relay. Relays 1 or 2.
closes relay. Relays 1 or 2.
when the Health Monitoring
6
algorithm senses a change. Relays 1 or 2.
©2012 General Electric All Rights Reserved
Page 39
DET-653C EntelliGuard® G Circuit Breaker Application Guide
33

EntelliGuard Trip Unit Performance Characteristics Graphs

Table 3.27. EntelliGuard Trip Unit Summary

Feature

Characteristic

Specification

I2T Slopes

22

I4t Slopes

22

IEEE MV (2)

no

IEC MV (2)

no

Neutral

Neutral Over Current Protection

yes

Pick Up Range

0.5-1.0 (0.05 steps x Plug

I2t Range Delays at 6 X

0.5sec – 22sec

I4t Range Delays at 6 X

0.004sec – 3.09 sec

Long Time Thermal Memory

yes

Pick Up Range

1.5-12X

ST Delay Band Range (Commit Time)

0.025sec - 0.417sec

Band Width

55msec

ST Delay Bands

11 (UL), 17 (IEC)

I2T Slopes

3

I2T Adjustment

with LT pick up

Adjustable IPU Range (3)

1.5-15X & OFF

Extended Range Adjustable IPU

1.5-30A & OFF

Making Current Release

yes

Override

yes

Alternate IPU with Remote Enable

yes (RELT IPU)

Selective Instantaneous

yes
24-May-12 Section 3. EntelliGuard TU Trip Unit System

Table 3.27 provides an overview of the trip unit features, characteristics, specifications and accuracy.

Protection Curves

Long Time PU (Ir) and Delays

Short Time Pick and Delays

Instantaneous Protection

©2012 General Electric All Rights Reserved
Page 40
DET-653C EntelliGuard® G Circuit Breaker Application Guide
34

Table 3.27. EntelliGuard Trip Unit Summary (continued)

Feature

Characteristic

Specification

Accuracy (at 100%)

Pick Up Range

0.1/0.2 – 10

-

External Zero Seq. (Gnd Return) CT
Input

1A = 100%

-

Delay Band Range

0.042/0.058-0.417/0.0917sec

-

Delay Bands

9/7/2015

-

I2t Slopes

2
-

I4t Slopes

1
-

GF Alarm Option

yes
-

Short time

yes
-

Ground Fault

yes
-

Separate ZSI Band Settings

yes
-

Instantaneous

yes
-

Current Unbalanced

10% - 50% difference between highest
steps

2%, ±0.1sec on delay

Over Voltage

110% - 115% of line voltage in 1%
Steps; 1-15sec delay in 1sec steps

2%, ±0.1sec on delay

Under Voltage

30% - 85% of line voltage in 1% Steps;
1-15 Second Delay in 1 sec steps

2%, ±0.1sec on delay

Voltage Unbalance

10% - 50% difference between highest
steps

2%, ±0.1sec on delay

Power Reversal

Line to Load OR Load to Line, From 10
to 990kW in 10kW steps

2%

Current Level (Alarm/Load
Management)

2
-

Current (A)

A, B, C & neutral

0000 Resolution, 2%

Voltage (V)

A, B, & C

0000 resolution, 2%

Real Power (kW)

A, B, C and total

000.000 resolution, 4%

Reactive Power (KVAr)

A, B, C and total

000.000 resolution, 4%

Apparent Power (kVA)

A, B, C and total

000.000 resolution, 4%

Energy (KWh)

A, B, C and total

000.000 resolution, 4%

Frequency (Hz)

yes

00 resolution, 1 cycle

Real Demand (kW)

total

000.000 resolution, 4%

Power Factor (%)

A, B, C

00 resolution, 4%

Peak Power Demand (KW)

A, B, C

000.000 resolution, 4%

Waveform Capture (COMTrade)

yes (requires PMCS)

-

Trip Operations Counter

yes
-

Temperature Monitoring

future

-

Event Log

last 10 events

-

Open Protocols (13)

Modbus RTU, Profibus DP

-

Front Port for Local Comm

yes – standard

-

Programmable Relays

4
-

Health Monitoring Relay

1
-

Universal Trip Plugs (16)

yes
-

Adjustable (20%-100%) Trip Plug

yes
-

Universal Spare Trip Unit

yes
-

Interchangeable Trip Unit

with = sensor & process

-
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System

Ground Fault Protection

Zero Selective Interlock

& lowest phase compared to average,
1% steps; 1 to 15sec delay in 1sec

Protective Relays

& lowest phase compared to average,
1% steps; 1 to 15sec delay in 1sec
Metering, Diagnostic, and
Miscellaneous Functions

Serial Comm.

I/O

Flexibility

All Settings can be performed via the front of the trip unit. Also available is Free Set-up Software downloadable from geindustrial.com Download and upload trip unit settings. Ability to download and view the waveform captured by the trip unit. Also has the ability to store settings in an Offline file and then compare it to the current settings. Requires the EntelliGuard TU Test Kit, GTUTK20.
©2012 General Electric All Rights Reserved
Page 41
DET-653C EntelliGuard® G Circuit Breaker Application Guide
35

Table 3.28. Metering Data Startup Levels for breaker with Entelliguard Trip Unit with 24 VDC

Parameter

Phase

Unit

Startup Level

Table 3.29. Accuracy as a Percent of Sensor Rating

Accuracy as a Percent of Sensor Rating

% of Sensor (A)

Accuracy - % of

20% - 50%

+/- 10%

50% – 85%

+/- 5%

85 -100%

+/- 2%

24-May-12 Section 3. EntelliGuard TU Trip Unit System

Current

Phase A,B,C,
neutral
A

Voltage Phase L1,L2,L3 V

Real Power

Reactive Power

Apparent Power

Peak Demand Power Total

Energy

Phase L1,L2,L3

and total
Phase L1,L2,L3
and total
Phase L1,L2,L3
and total
Phase A,B,C and

total

kW

kVAR

kVA
Auto-ranging from
0.00 kWH to 999mWH Auto-ranging from
0.00 kWH to 999mWH

Frequency Hz

Power Factor %

Note: Metering Data for breaker with Entelliguard Trip Unit without 24 VDC requires 20% sensor current and then all metering will be available

> 3 % Rating Plug
Current
> 15 V for all Voltage
Ranges
> 7% Rating Plug
Current or > 15 Volts
> 7% Rating Plug
Current or > 15 Volts
> 7% Rating Plug
Current or > 15 Volts
> 7% Rating Plug
Current or > 15 Volts
> 7% Rating Plug
Current or > 15 Volts
> 10% Rating Plug
Current
> 7% Rating Plug
Current or > 15 Volts
Reading

Figure 3.14 through 3.17 depict selected sensor performance characteristics.

©2012 General Electric All Rights Reserved
Page 42
DET-653C EntelliGuard® G Circuit Breaker Application Guide
36

Figure 3.14. Long Time Circuit Breaker Characteristics

24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
©2012 General Electric All Rights Reserved
Page 43
DET-653C EntelliGuard® G Circuit Breaker Application Guide
37

Figure 3.15. Short-Time Pickup and Delay Bands

24-May-12 Section 3. EntelliGuard TU Trip Unit System
©2012 General Electric All Rights Reserved
Page 44
DET-653C EntelliGuard® G Circuit Breaker Application Guide
38

Figure 3.16. Ground Fault: Multiple of Sensor

24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
©2012 General Electric All Rights Reserved
Page 45
DET-653C EntelliGuard® G Circuit Breaker Application Guide
39

Figure 3.17. Instantaneous, Override (HSIOC), Reduced Energy Let-Through Instantaneous (RELT)

24-May-12 Section 3. EntelliGuard TU Trip Unit System
©2012 General Electric All Rights Reserved
Page 46
DET-653C EntelliGuard® G Circuit Breaker Application Guide
40
EntelliGuard® G Power Circuit Breaker Section 4. Accessories

Introduction

Figure 4.1. Accessory Mounting

Motorized Spring Charging Unit
Circuit Breaker Closing Coils – Standard and Commanded
Table 4.1 Motor Operators
Envelope
Power
Consumption
Nominal Control

Voltage

IEC Range (85% to 110%)
ANSI Range
UL Range
(85% to 110%)
Cat No.
24Vdc/30Vdc
20.4V to 26.4V
-
20.4V to 26.4V
GM0124DR
48Vdc
40.8V to 52.87V
38V to 56V
40.8V to 52.87V
GM01048DR
60Vdc
51V to 66V
-
51V to 66V
GM01060DR
72Vdc
61.2V to 79.2V
-
61.2V to 79.2V
GM01072DR
110Vdc/130Vdc
106.25V to 137.5V
100V to 140V
106.25V to 137.5V
GM0111ODR
250Vdc
212.5V to 275V
200V to 280V
212.5V to 275V
GM01250DR
48Vac
40.8V to 52.87V
-
40.8V to 52.87V
GM01048AR
120Vac
102V to 132V
104V to 127V
102V to 132V
GM01120AR
240Vac
204V to 264V
208V to 254V
204V to 264V
GM01240AR
277Vac
235.5V to 304.7V
-
235.5V to 304.7V
GM01277AR
24Vdc/30Vdc
20.4V to 26.4V
-
20.4V to 26.4V
GM0224DR
48Vdc
40.8V to 52.87V
38V to 56V
40.8V to 52.87V
GM02048DR
60Vdc
51V to 66V
-
51V to 66V
GM02060DR
72Vdc
61.2V to 79.2V
-
61.2V to 79.2V
GM02060DR
110Vdc/130Vdc
106.25V to 137.5V
100V to 140V
106.25V to 137.5V
GM0211ODR
250Vdc
212.5V to 275V
200V to 280V
212.5V to 275V
GM02250DR
48Vac
40.8V to 52.87V
-
40.8V to 52.87V
GM02048AR
120Vac
102V to 132V
104V to 127V
102V to 132V
GM02120AR
240Vac
204V to 264V
208V to 254V
204V to 264V
GM02240AR
27Vac
235.5V to 304.7V
-
235.5V to 304.7V
GM02277AR
Spring charge contact is power rated only, as shown below.

AC Ratings

DC Ratings

Voltage

Amps

Voltage

Amps

AC21-15A

24V

DC21-15A

AC23-10A

110-130V

DC21-10A

AC21-10A

250V

DC21-5A

AC23-5A - -
Spring charge time = 3sec max.

24-May-12 Section 4. Accessories

A wide range of optional accessories are interchangeable across all EntelliGuard G power circuit breakers, regardless of nominal rating or envelope/frame size. As shown in Figure
4.1, each accessory incorporates easy-fit design features for quick installation, either at the factory or in the field. NOTE: Replacement accessories have an “R” at the end of the catalog number as shown in the tables. All Coils are Conformal Coated for increased reliability in humid/damp environments
The unique motor/gearbox unit is specially designed to operate with the full range of EntelliGuard G breakers. It is easily installed with three heavy-duty bolts. After a breaker close operation, the unit automatically recharges the spring and makes it ready for immediate re-close should the need arise. High speed recharging ensures that the springs are fully charged within approximately three seconds following a release. All electrically operated (EO) ANSI/UL breakers are equipped with “Spring Charged” contacts for status indication (Table 4.1).
Two, easy-to-fit, clip-on closing coil options with simple, plug-in connections are available. Both options offer electrical remote release of the spring charged closing mechanism. Both options include a standard anti-pump safety feature ensuring that the close signal must be released before further close commands are allowed. The Command Close Coil additionally provides for local breaker close and remote breaker close over communications via the EntelliGuard Trip Unit (Table 4.2).
DC – 300W
1
AC – 350VA
DC – 480W
2 and 3
AC – 560VA

110-130V

220-240V

• Recommended fuse amps: contact factory.
• Duty cycle = 2/min.
• Envelope 1 motors: running VA ~ 300VA; inrush = 2 to 3 times.
• Envelope 2 and 3 motors: running VA ~ 450VA; inrush = 2 to 3 times.
©2012 General Electric All Rights Reserved
Page 47
DET-653C EntelliGuard® G Circuit Breaker Application Guide
41

Table 4.2. Closing Coil Characteristics

Type

Power
Consumption

Nominal Control Voltage

Catalog Number

24Vdc

GCCN024DR

48Vac/dc

GCCN048R

60 to 72Vdc

GCCN060DR

110/130/120Vac

GCCN120R

220Vdc/240Vac

GCCN240R

250Vdc/277Vac

GCCN277R

Command

24Vdc

GCCC024DR

48Vac/dc

GCCC048R

60 to 72Vdc

GCCC060DR

208Vac

GCCC208AR

Command Operation Module

Shunt Trip
Table 4.3. Extended Range Shunt Trip for UL Ground Fault and ANSI DC Rating Applications.

Nominal Control Voltage

Catalog Number

24Vdc

GSTG024DR

48Vac/dc

GSTG048R

70/72Vdc

GSTG072DR

110Vdc/120 Vac

GSTG120R

125 Vdc

GSTG125DR

208 Vac

GSTG208AR

240 Vac

GSTG240R

250 Vdc/277 Vac

GSTG250R

Status Indication Switch (Coil Signaling Contact)

Table 4.4. Coil Signaling Contact Module

Type and
Configuration

Rating

Cat. No.

120Vac

6A

250Vac

6A

125Vac

0.5A

250Vdc

0.25A

AC

125Vac

0.1A

DC

30Vdc

0.1A

(1NO contact each)
Under Voltage Release (UVR) with Fixed Time Delay

Table 4.5. UVR Operating Characteristics

Power
Consumption

Nominal Control
Voltage
Catalog Number

24 Vdc

GUVT024DR

24/30Vdc

GUVT030DR

40Vdc; 48Vac/dc

GUVT048R

60Vdc

GUVTO60DR

120 Vac

208Vac

GUVT208AR

220Vdc/240Vac

GUVT240R

250Vdc/277Vac

GUVT277R

24-May-12 Section 4. Accessories
DC: 350W,
20 W (sealed)
Closing
Coil
Operated
Closing
Coil
• Duty cycle = 2/min.
• Closing coil inrush = 350VA.
AC: 350W
(inrush),
20W (sealed)
DC: 350W,
20W (sealed)
AC: 350W
(inrush),
20W (sealed)

208Vac GCCN208AR

110/130/120Vac GCCC120R

This module energizes the closing coil to cause the breaker to close whenever control power is applied to the accessory and when commanded from the breaker trip unit or breaker front panel push button (electrical closing.)

Energizing the shunt trip (ST), via local or remote input, will instantaneously activate the circuit breaker mechanism, ensuring a rapid open operation. The shunt trip is continuously rated and does not require an auxiliary switch in series with the coil. The shunt trip is a straightforward, field installable accessory available in wide range of voltages. See Table 4.3.
A plug-in module is available to provide status indication via the secondary disconnects and trip unit. Coil Signaling Contacts are available for closing coils, shunt trips and under voltage releases (Table 4.4). Contact is mounted on top of the Accessory Device. One of the low signal (Hi-Fi) contacts is always wired to the tip Unit.
AC
1 Power rated +
1 Low signal (Hi-Fi)
DC

GCSP1R

(1NO contact each)
2 Low signal (Hi-Fi)

AC 125Vac 0.1A GCSP2R

The UVR instantaneously activates the circuit breaker trip mechanism when the source voltage drops below the low voltage threshold. The UVR is also a simple, field installable device. NOTE: This accessory acts as a permissive; it is a no­voltage/no-close device. The circuit breaker cannot be closed (manually or electrically) unless the undervoltage release coil is energized above the required threshold. The undervoltage release with fixed time delay is specifically intended for applications where a delay period (ride-through) is required due to potential voltage events. The delays are 50msec when system voltage drops to 50% and 20msec when system voltage drops below 50% (Table 4.5).
Pickup range = 55%-110%.
• Duty cycle = 2/min.
• Inrush = 480A (ac), 480W (dc).
• Holding = 60VA (ac), 50W (dc).
©2012 General Electric All Rights Reserved
DC: 350W,
2 W (sealed)
AC: 350W

110 Vdc/130 Vdc;

(inrush),
20W (sealed)
Duty cycle = 2/min.
Inrush = 350VA (ac), 350W (dc).
Holding = 60VA (ac), 50W (dc).

GUVT120R

Page 48
DET-653C EntelliGuard® G Circuit Breaker Application Guide
42

Time Delay Module (TDM) for UVR (Externally Mounted)

Figure 4.2. Time Delay Module

Table 4.6 TDM Characteristics

Nominal Control Voltage
Catalog No.

48Vdc

GTDM048D

48Vac

GTDM048A

60Vdc

GTDM060D

125Vdc

GTDM120D

120Vac

GTDM120A

208Vac

GTDM208A

240Vdc

GTDM240D

240Vac

GTDM240A

250Vdc

GTDM250D

277Vac

GTDM277A

Remote Operation Coil Combination

Table 4.7. Remote Operation Coil Combination

Combination

Coil Position on Fascia (from left)

1 2 3
4
1
-

shunt

CC
UV 2 shunt

shunt

CC
UV 3 shunt
UV
CC
UV
Ready To Close Contact

Table 4.8. Ready To Close Contacts (1 NO)

Rating

Description

Catalog
Number

high fidelity/secondary
disconnect

power rated/secondary
disconnect

Auxiliary Switches

Table 4.9. Auxiliary Switches

Contact Configuration

Cat. No.

Power rated (3NO+3NC)

GAUX3R

(2NO+2NC)

Power rated (8NO+8NC)

GAUX6R

(4NO+4NC)

Table 4.10. Auxiliary Switch Ratings and Secondary Disconnect Points

Contact Configuration

Power
Rated

Hi-Fi

Cat. No.

Power rated (3NO+3NC)

A14 - A25,
B17 - B26
Power rated (4NO+4NC) +

(4NO+4NC)*

A14 - A25,
B25 - B26
24-May-12 Section 4. Accessories
The de-energized operation of the Undervoltage release can be delayed. This optional, externally mounted module has an adjustable time delay of 0 sec to 3 sec. The device can be implemented to prevent undesired breaker tripping due to momentary voltage interruptions and is connected in series with the Undervoltage release. The time delay is in addition to the time delay from the breaker mounted UVR accessory. The time delay module starts counting at 50% of rated voltage (Fig. 4.2 and Table 4.6).
These contacts, as shown in Table 4.8, indicate that the following conditions are met and the circuit breaker can be closed:
The circuit breaker is open.
The closing springs are charged.
The circuit breaker in not locked/interlocked in open
position.
There is no standing closing signal.
There is no standing opening signal.
Each breaker accepts a maximum of four coils in the combinations shown in Table 4.7. The four positions can be filled by the following four devices: one Close Coil, one Shunt, one UVR, and the final fourth position can either be a Shunt Trip or a UVR. All coils are mounted from the front and snap onto the mechanism after the fascia is removed.
All Coils are
Conformal Coated for increased reliability in humid/damp environments.
120Vac 6A
AC

250Vac 6A - GRTC2R

125Vdc 0.5A

DC

250Vdc 0.25A high fidelity/trip unit GRTC3R

GRTC2R

GRTC1R

Auxiliary switches indicate breaker main contact position. They change their state in the same time sequence as the breaker main contacts. See Tables 4.9 and 4.10 for available combinations and ratings, and Tables 4.11 through 4.14 for contact information.
Power rated (3NO+3NC) + low signal (Hi-Fi)

Power rated (4NO+4NC) + low signal (Hi-Fi)

GAUX5R

GAUX8R

A14 - A25 N/A GAUX3R

Power rated (3NO+3NC) + low signal (Hi-Fi) (2NO+2NC)

Power rated (8NO+8NC)*

A14 - A25

B4 - B13,
B10 - B13,
B23 - B26
N/A GAUX6R

GAUX5R

©2012 General Electric All Rights Reserved
low signal (Hi-Fi)

*Options are not available for side mounted sec disc blocks.

High Fidelity refers to gold-plated contacts. Use for signal level outputs
(10mA min to 100mA max., 8Vdc to 30Vdc, 125Vac.
B12 - B13,
B4 - B11,
B17 - B24

GAUX8R

Page 49
DET-653C EntelliGuard® G Circuit Breaker Application Guide
43

Table 4.11. Power Rated (3NO/3NC) (Ref Drawing 10099230)

Normally Open

Normally Closed

Switch Contact

Secondary
Disconnect

Connector

Switch Contact

Secondary
Disconnect

Connector

1
A25
3
A19

Power
Rated

2
A24 4 A18 5 A23 7 A17 6 A22 8 A16 9 A21
11
A15
10
A20
12
A14
Table 4.12. Power Rated (8NO/8NC) (Ref Drawing 10099228)

Normally Open

Normally Closed

Switch Contact

Secondary
Disconnect

Connector

Switch Contact

Secondary
Disconnect

Connector

1
A25
3
A19

Power
Rated

2
A24 4 A18 5 A23 7 A17 6 A22 8 A16 9 A21
11
A15
10
A20
12
A14
13
B26
15
B13
14
B25
16
B12
17
B24
19
B11
18
B23
20
B10
21
B22
23
B9
22
B21
24
B8
25
B20
27
B7
26
B19
28
B6
29
B18
31
B5
30
B17
32
B4
Table 4.13 Power Rated (3NO/3NC) Low Signal (Hi-Fi) (2NO/2NC) (Ref Drawing 10099232)

Normally Open

Normally Closed

Switch Contact

Secondary
Disconnect

Connector

Switch Contact

Secondary
Disconnect

Connector

1
A25

Power
Rated

5
A23
6
A22
9
A21
13
B26

Hi-Fi

14
B25
17
B24
18
B23
24-May-12 Section 4. Accessories
PL1
PL1
PL3
PL4
PL2
PL2
PL5
PL7
PL8
PL6
3 A19
2 A24
PL3
10 A20
PL1
PL2
©2012 General Electric All Rights Reserved
4 A18 7 A17
8 A16 11 A15 12 A14
15 B13 16 B12 19 B11
20 B10
PL6
PL4
PL5
Page 50
DET-653C EntelliGuard® G Circuit Breaker Application Guide
44
Table 4.14. Power Rated (4NO/4NC) + Low Signal (Hi-Fi) (4NO/4NC) (Ref Drawing 10099234)

Normally Open

Normally Closed

Switch Contact

Secondary
Disconnect

Connector

Switch Contact

Secondary
Disconnect

Connector

1
A25
3
A19

Power
Rated

2
A24 4 A18 5 A23 7 A17 6 A22 8 A16 9 A21
11
A15
10
A20
12
A14
13
B26
15
B13
14
B25
16
B12
17
B24
19
B11

Hi-Fi

18
B23
20
B10
21
B22
23
B9
22
B21
24
B8
25
B20
27
B7
26
B19
28
B6
29
B18
31
B5
30
B17
32
B4
Circuit Breaker - Key Interlock Facility
Table 4.15. Key Interlocks and Door Interlocks
Description
Catalog Number
(breaker mounted)
(breaker mounted)
(cassette mounted)
(cassette mounted)
Door interlock (left side)
GLHD
Door interlock (right side)
GRHD

Figure 4.3. Breaker-Mounted Key Interlock

A
A Key interlock mounting locations

Figure 4.4. Cassette-Mounted Key Interlock

A
A Key interlock mounting locations
24-May-12 Section 4. Accessories
PL1
PL2
PL4
PL3
15A max. current, 440V max.
This option supplies factory-installed key interlock mounting provisions (baseplates and mechanism) on the front of the breaker fascia. Key interlocks ensure that a circuit breaker cannot be closed unless the dedicated key has been inserted and secured within the lock. Circuit breakers accept ready-to-fit interlocking device kits such as Castell, Ronis, Kirk and Profalux for installation between related, separate circuit breakers. NOTE: Locks and keys are not supplied by GE. Please order separately from your local supplier (Table 4.15 and Figs. 4.3 and 4.4).
PL5
PL6
PL8
PL7
Kirk Keys for Fixed Breaker: CN22. Kirk Keys for Cassette:
KCAMXXX105 (Extended), KCAMXXX11S (Withdrawn). S indicates that the key designation (A,B, etc.) is to be stamped on the lock and the key.
Ronis: Type 1104B lock with standard key, 1/4 in. turn to
trap the key, compulsory spindle size.
For drawout breaker applications, key interlocks can be
mounted in the cassette.
Baseplate and mechanism for Ronis locks
Baseplate and mechanism for Kirk Key locks
Mechanism for Ronis key cassette interlock
Mechanism for Kirk key cassette interlock
©2012 General Electric All Rights Reserved
GBRONR
GBKRKR
GCRONR
GCKRKR
Page 51
DET-653C EntelliGuard® G Circuit Breaker Application Guide
45
Carriage Position Switch (TOC)

Table 4.16. Carriage Position Switches

Switch Configuration

Catalog Number

1 NO/NC switch per position
GCPS1R
Set of 2 NO/NC switches per position
GCPS2R
Set of 6 NO/NC switches per position
GCPS3R

Table 4.17. Carriage Position Switch Ratings (Common NO/NC Contact Configuration)

Ratings

120Vac

6A

250Vac

6A

125Vac

0.5A

250Vac

0.25A

Cassette/Substructure
Mechanical Interlocks (Cable/Rod) (OEM Applications Only)

Table 4.18. Mechanical Interlock (Cable/Rod)

Interlock
Type
Number of

Cables

Required
Breaker Type
Poles
Catalog
Number
3
GI2WADR
4
GI3WADR
3
GI2FADR
4
GI3FADR
3
GI2WBR
4
GI3WBR
3
GI2FBR
4
GI3FBR
3
GI2WCR
4
GI3WCR
3
GI2FCR
4
GI3FCR
Type D
3
GI2WDTR
4
GI3WDTR
fixed
3
GI2FDTR
Cables

Table 4.19. Cables for Mechanical Interlocks

Length

Catalog Number

Meters

Inches

1

39.4

GCB1

1.6
63

GCB2

2

78.7

GCB3

2.5

98.4

GCB4

3

118.1

GCB5

3.5

137.8

GCB6

4

157.5

GCB7

24-May-12 Section 4. Accessories
Available as an option for mounting within the base of the cassette/substructure, the carriage position switch provides six single-pole changeover contacts (single pole, double throw) for local or remote electrical indication of the circuit breaker status: CONNECTED, TEST and DISCONNECTED. The DISCONNECTED position is indicated only when minimum isolating distances between contacts on both the main and auxiliary circuits have been achieved. This option is in addition to the mechanical indicators, which are fitted as standard. When installed, the carriage switch is IP2X protected. For use with drawout breakers/cassettes Tables
4.16 and 4.17).
2 Way –
Type A
1 from 3
Type B
2 from 3
Type C
2
6
6
withdrawable
fixed
withdrawable
fixed
withdrawable
fixed
AC
DC
The drawout mechanism allows the breaker to be racked in four distinct positions (CONNECTED, TEST, DISCONNECTED, WITHDRAWN).
Available for fixed and draw-out circuit breakers, these units enable the direct interlocking of EntelliGuard G circuit breakers, either mounted side-by-side or stacked. The interlocking mechanisms are connected by a specially designed cable or rod in a 1 from 2, 1 from 3, and 2 from 3 configuration, and any mix of current ratings/pole configurations can be accommodated Table 4.18).
1 from 3
Way –
Contact factory for availability.
4
withdrawable

Standard cable lengths are shown in Table 4.19. (Cables ordered separately. Please contact our technical customer service department if longer length is required.)

Contact factory for availability.

Mechanical interlocks can be fitted to electrical systems and can link two and/or three circuit breakers. Any nominal rating, frame size, number of poles or type (fixed pattern or draw-out) can be interlocked.

©2012 General Electric All Rights Reserved
Page 52
DET-653C EntelliGuard® G Circuit Breaker Application Guide
46

Table 4.20. Interlock Configurations

Typical Circuit

Interlock Configuration

Possible Combinations

Type A

B1
B2 O O 1 O O 1

Type B

B1
B2
B3 O O O 1 O O O 1 O O O 1

Type C

B1
B2
B3 O O O 1 O O
O O 1
O 1 O 1 1 O O 1 1 1 O
1
third breaker from closing.

Type D

B1
B2
B3
O O O
1 O O O O
1
1 O 1
O 1 O
24-May-12 Section 4. Accessories

1 from 2 interlock 2 cable configuration Interlocking between two circuit breakers

One normal power supply One generator (emergency) supply

1 from 3 interlock 6 cable configuration Interlocking among three circuit breakers

Three power supplies (generator or transformers) feeding the same busbar but parallel operation is prevented.

Available on request.

B1 can close only if B2 is open. B2 can close only if B1 is open.

Only 1 of 3 breakers can be closed.

Contact factory for availability.

2 from 3 interlock 6 cable configuration Interlocking among three circuit breakers

Two bus sections can be powered by single transformer (bus tie breaker closed) or both transformers (bus tie breaker open).

Available on request.

1 from 3 interlock 6 cable configuration Interlocking between three circuit breakers

Two normal power supplies cannot be connected in parallel. One power supply may assist the priority circuit.

Available on request.

• Any two from three breakers can be closed.
• Any one from three breakers can be closed.
Two breakers must be closed to prevent the
• B1 and/or B3 can be closed only if B2 is open.
• B2 can only be closed if B1 and B2 are both
open.
©2012 General Electric All Rights Reserved
Page 53
DET-653C EntelliGuard® G Circuit Breaker Application Guide
47
Bell Alarm with Lockout

Table 4.21. Bell Alarm Switches

Switch Configuration

Cat. No.

One single pole, double throw switch (1-Form C contact)

GBAT1R

Table 4.22. Bell Alarm Ratings (Common 1 NO/NC Contact Configuration)

Ratings

120Vac

6A

250Vac

6A

125Vac

0.5A

250Vac

0.25A

Charging Spring Status Indicator
Table 4.23. Spring Charged Contact (1 NO)
Ratings
Catalog Number

120Vac

6A

250Vdc

0.25A

Secondary Disconnects (Factory-installed/Field Installable)
Table 4.24. Secondary Disconnect Block Locations
Top Disconnect
Block B
Block A
Side Disconnect Block A
Block B
Table 4.25. Wiring Schematic for Block-A (Three Layer Secondary Disconnect with Basic GTU and Basic Accessories)
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
A13
RTC NO
RTC NO
UV2
UV2

Max. Current (I)

14.8A

14.8A

10A
10A

1.9A

1.9A

1.9A

1.9A

1.9A

1.9A

1.9A

1.9A

1.9A

Max. Voltage (V)

440V

440V

240V

240V

440V

440V

440V

440V

440V

440V

440V

440V

440V

A14
A15
A16
A17
A18
A19
A20
A21
A22
A23
A24
A25
A26

Max. Current (I)

15A
15A
15A
15A
15A
15A
15A
15A
15A
15A
1A
15A
-

Max. Voltage (V)

A27
A28
A29
A30
A31
A32
A33
A34
A35
A36
A37
A38
A39

Max. Current (I)

Max. Voltage (V)

25Vac
25Vac
25VAC
25Vac
24-May-12 Section 4. Accessories
The Bell Alarm provides remote indication that the circuit breaker has opened because of an electrical fault. The Lockout feature is integral to the trip unit. When a Bell Alarm is supplied with the breaker, the Trip Unit dial is set and locked to the manual position. In order to re-close the breaker, the Lockout button must be pushed in/reset on the Trip Unit 1-Form C contact (Tables 4.21 and 4.22).
AC
DC
Factory-installed on the motor, this auxiliary switch indicates that the circuit breaker is charged and is standard with the spring-charging motor (Table 4.23).
AC
DC
250Vac 6A 125Vdc 0.5A

GSCC1R

Inputs and outputs to the circuit breaker are wired through secondary disconnects located on either the top or the side (Envelope 1 only) of the breaker. The plug-style secondary disconnects engage mating disconnects in the breaker cubicle when the breaker is in the TEST or CONNECT position. Up to 78 points are available so that all breaker accessories can be wired to dedicated disconnect points (Tables 4.24 through 4.29). Block B is ordered separate for cassettes, Cat. No. GSDWTR.
circuit breaker/cradle
viewed from the front

Motor Motor

NC3 NC3 NC2 NC2 NC1 NC1 NO3 NO3 NO2 NO2 NO1 NO1 -

440V 440V 440V 440V 440V 440V 440V 440V 440V 440V 440V 440V -

O/P1a O/P1b O/P2a O/P2b 24 V+ 24 V- BA NC BA NO BA COM N-RC- N-RC+ Eleg-CT Eleg-CT

1A 1A 1A 1A <500mA <500mA 10A 10A 10A <50mA <50mA 5A 5A
30Vdc/
30Vdc/
Spr NO/
30Vdc/
Spr NO/
30Vdc/
ST1 ST1 UV1 UV1 CC COM CC IMM CC CMD

30V 30V 240V 240V 240V 480mV 480mV 2V 2V

ST2/
ST2/
©2012 General Electric All Rights Reserved
Page 54
DET-653C EntelliGuard® G Circuit Breaker Application Guide
48
Table 4.26. Wiring Schematic for Block-B (Three Layer Secondary Disconnect to be Added for GTU with Full I/O and Additional Accessory Signals)
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
B11
B12
B13
NC7
NC7

Max. Current (I)

<50mA

<50mA

<50mA

10A/15A

10A/15A

10A/15A

10A/15A

15A

15A
15A
15A
15A
15A
B14
B15
B16
B17
B18
B19
B20
B21
B22
B23
B24
B25
B26
NO7

Max. Current (I)

15A
15A
15A

Max. Voltage (V)

440V

440V

440V

440V

B27
B28
B29
B30
B31
B32
B33
B34
B35
B36
B37
B38
B39

out+

out-

in+
in-
GND
ISO

Volt-IN

Max. Current (I)

<50mA

<50mA

<50mA

<50mA

<500mA

<500 mA

<50mA

<50mA

<50mA

<500mA

<50mA

<50mA

<50mA

Max. Voltage (V)

Table 4.27. Wiring Schematic for Block-C (Internal to the breaker, not used by customer.) (Two Layer Intermediate Secondary Disconnect at the Top for the Side Mounted Secondary Disconnect.)
C1
C2
C3
C4
C5
C6
C7
C8
C9
C10
C11
C12
C13
C14
C15
C16
C17
C18
C19
C20
C21

ST2/

ST2/

C22
C23
C24
C25
C26
C27
C28
C29
C30
C31
C32
C33
C34
C35
C36
C37
C38
C39
C40
C41
C42
Spr
Table 4.28. Electronic Interlock

Network Interlock Connections

Network Interlock Status Switch

24-May-12 Section 4. Accessories

Max. Voltage (V)

INPUT1 INPUT2

30Vdc/

25Vac

RELT

INPUT

30Vdc/

25Vac

COM -
COM

30Vdc/

25Vac

<50mA <500mA -

5V 0.1V -

ZSI
ZSI
ZSI
I/P

ST1 NO/

NC8

240V/

440V

CC NO/

NO8

10A/

/

240V

ZSI

ST1 COM/

NC8

240V/

440V

CC COM/

NO8

10A/

240V/

ISO
UV1
NO/

240V/

440V

ST2 NO/

UV2 NO/

NO7

10A/

240V/

5V
UV1
COM/
240V/

440V

NC6 NC6 NC5 NC5 NC4 NC4

440V 440V 440V 440V 440V 440V

ST2 COM/

UV2
COM/
NO6 NO6 NO5 NO5 NO4 NO4
10A/15A 15A 15A 15A 15A 15A 15 A
240V/

TX EN 1 RX TX

440V 440V 440V 440V 440V 440V

GND

Volt-A Volt-B Volt-C

28Vdc 28Vdc 30Vdc 30Vdc 0.1V 5V 5V 5V 5V 0.1V 1.76V 1.76V 1.76V

BA
BA
BA
ST1
ST1
UV1
UV1
CC
CC
UV2
UV2
NC
Spr NO/
RTC NO
NO
COM
NO
NO/
ST1 ST1 UV1 UV1
RTC
NO
COM
NO
COM
CC
COM
NO
CC
IMM
COM
CC
CMD
NO
ST2/
UV2
NO5 NO5 NO4 NO4 NC3 NC3 NC2 NC2 NC1 NC1
COM
ST2/
NC5 NC5 NC4 NC4 NO3 NO3 NO2 NO2 NO1 NO1
UV2
A5 A6 A7 A8 B4 B5 B6

NI TRIP NI TRIP NI RESET NI RESET NI NC NI NO NI COM

1.9A 1.9A 1.9A 1.9A 10A 10A 10A

240V 240V 240V 240V 240V 240V 240V

©2012 General Electric All Rights Reserved
Page 55
DET-653C EntelliGuard® G Circuit Breaker Application Guide
49
Table 4.29. Wiring Schematic Nomenclature Definitions
Pin

Nomenclature

Description

Pin

Nomenclature

Description

A1

Motor

B1

Input 1

relay input to trip unit

A2

Motor

B2

Input 2

relay input to trip unit

A3

SPR NO/RTC NO

B3

I/P COM

relay input to trip unit

A4

SPR NO/RTC NO

B4

ST1 NO/NC8

A5
ST1
B5

ST1 COM/NC8

A6
ST1
B6

UV1 NO/NC7

A7
UV1
B7

UV1 COM/NC7

A8
UV1
B8
NC6

(CC or CCC)

control power (CCC)
A11

CC CMD

closing coil close signal (CCC)

B11
NC5
A12

ST2/UV2

voltage release 2
B12
NC4
A13

ST2/UV2

B13
NC4
A14
NC3
B14

RELT

RELT signal output

A15
NC3
B15
COM

trip unit communication

A16
NC2
B16 - -
A17
NC2
B17

CC NO/NO8

open contact 8
A18
NC1
B18

CC COM/NO8

NO/NO7
COM/NO7
A21
NO3
B21
NO6
A22
NO2
B22
NO6
A23
NO2
B23
NO5
A24
NO1
B24
NO5
A25
NO1
B25
NO4
A26 - -
B26
NO4
A27

O/P1a

relay output 1 from trip unit

B27

ZSI out+

A28

O/P1b

relay output 1 from trip unit

B28

ZSI out-

A29

O/P2a

relay output 2 from trip unit

B29

ZSI in+

A30

O/P2b

relay output 2 from trip unit

B30

ZSI in-

A31

24 V+

B31

ISO GND

A32

24 V-

B32
A33

BA NC

B33
A34

BA NO

A35

BA COM

GND
A37

N-RC+

B37

Volt-A

A38

Eleg-CT

B38

Volt-B

A39

Eleg-CT

B39

Volt-C

24-May-12 Section 4. Accessories

power input to motor operator

spring charge status contact/ ready to close signaling contact

power input to shunt trip 1

under voltage release 1

shunt trip 1 signaling contact/normally open contact 8

under voltage release 1 signaling contact/normally closed contact 7

A9 CC COM

A10 CC IMM

A19 NC1 B19
A20 NO3

closing coil neutral wire-common

closing coil (CC), continuous
power input to shunt trip 2/under

normally closed contact 3

normally closed contact 2

normally closed contact 1

normally open contact 3

normally open contact 2

normally open contact 1

B9 NC6
B10 NC5
B20
ST2 NO/UV2
ST2 COM/UV2

normally closed contact 6

normally closed contact 5

normally closed contact 4

closing coil signaling contact/normally

shunt trip 2 signaling contact/under voltage release 2 signaling contact/ normally open contact 7

normally open contact 6

normally open contact 5

normally open contact 4

A36 N-RC-

©2012 General Electric All Rights Reserved

auxiliary power supply to trip unit

bell alarm switch

neutral Rogowski coil

earth leg CT (multi-source ground fault)

B34 B35
B36

5V Iso TX EN 1 RX TX

Voltage Input

GF zone selective interlock output

GF zone selective interlock input

trip unit communication

ground point for voltage input to trip unit

system phase voltage signals

Page 56
DET-653C EntelliGuard® G Circuit Breaker Application Guide
50
Ground Fault
Neutral Rogowski

Table 4.30. Neutral Rogowski CTs
(Encased with Terminal Screws)

Envelope

Current Rating

Cat. No.

400 A

G04HNRCE

600/630 A

G07HNRCE

800 A

G08HNRCE

1000 A

G10HNRCE

1200/1250 A

G13HNRCE

1600 A

G16HNRCE

2000 A

G20HNRCE

400 A

G04MNRCE

600/630 A

G07MNRCE

800 A

G08MNRCE

1000

G10MNRCE

1200/1250 A

G13MNRCE

1600 A

G16MNRCE

2000 A

G20MNRCE

2500 A

G25MNRCE

3000/3200 A

G32HNRCE

4000 A

G32MNRCE

3

3000/3200 A (1600 A x 2)

G32LNRCE

4000 A (2000 A x 2)

G32LNRCE

5000 A (2000 A x 2)

G50LNRCE

6000/6400 A (3200 A x 2)

G64LNRCE

Table 4.30a. Neutral Rogowski CTs (Loose Rogowski Coil
and mounting hardware)

Envelope

Current Rating

Cat. No.

400 A

G04HNRC

600/630 A

G07HNRC

800 A

G08HNRC

1000 A

G10HNRC

1200/1250 A

G13HNRC

1600 A

G16HNRC

2000 A

G20HNRC

400 A

G04MNRC

600/630 A

G07MNRC

800 A

G08MNRC

1000

G10MNRC

1200/1250 A

G13MNRC

1600 A

G16MNRC

2000 A

G20MNRC

2500 A

G25MNRC

3000/3200 A

G32HNRC

4000 A

G32MNRC

3

3000/3200 A (1600 A x 2)

G32LNRC

4000 A (2000 A x 2)

G40LNRC

5000 A (2000 A x 2)

G50LNRC

6000/6400 A (3200 A x 2)

G64LNRC

Sealed Door Panel Escutcheon

Mechanical Operations Counter

Table 4.31. Miscellaneous Accessories

Description

Cat. No.

IP54 Door Panel - Withdrawable Type

GF54D

IP54 Door Panel - Fixed Pattern

GW54D

Mechanical Operations Counter

GMCNR

ACB Lifting Truck

ACBLIFT

Door Interlocks
Table 4.32. Door Interlocks

Mounting

Catalog Number

Right mounted

GRHD

Left mounted

24-May-12 Section 4. Accessories

The EntelliGuard TU Trip Unit provides a non-core CT input for zero sequence or residual summation current. The expected ratio is 1A = 100%.

The Neutral Rogoswki CT’s are used to measure the Neutral Current and is required when Internal Ground Fault is selected on the trip unit. There are two types available:

1. Encased with Terminal Screws: The Rogowski coil is
encased with two terminal screws. No additional mounting hardware is required as the encasing is molded to the mounting dimensions. Table 4.30
2. Loose Rogowski Coil with separate mounting
hardware: The coil and mounting hardware are separate. The coil comes with the two wire leads for connection to a terminal block. Table 4.30a
1
2
1
An optional complete IP54 front door panel is available when a higher degree of protection is needed (Table 4.31).
Used with either manual or motor charged circuit breakers, the counter provides an accurate record of the cumulative number of complete breaker closing operations (Table 4.31).
2
Contact factory for availability.
See Table 4.32.
©2012 General Electric All Rights Reserved

GLHD

Page 57
DET-653C EntelliGuard® G Circuit Breaker Application Guide
51
Table 4.33. Back Connected Terminations for Cassette

Envelope
Size

Description

Type

Catalog Number

Drawing

Qty.

1

Up to 1600 A

3 Pole

4 Pole

200 A

3 Pole

4 Pole

2

Up to 1600 A

3 Pole

4 Pole

24-May-12 Section 4. Accessories

GBB216TBBC3

GBB216TBBC4

GBB220TBBC3

6
8
6

GBB220TBBC4

GBB216TBBC3

GBB216TBBC4

8
6
8
©2012 General Electric All Rights Reserved
Page 58
DET-653C EntelliGuard® G Circuit Breaker Application Guide
52
2

Up to 2000 A

3 Pole

4 Pole

3000A UL

3 Pole

4 Pole

3200A ANSI

3 Pole (Top Side)
3 Pole (Bottom Side)
4 Pole (Top Side)
24-May-12 Section 4. Accessories

GBB220TBBC3

GBB220TBBC4

GBB230TBBC3

GBB230TBBC4

6
8
6
8
©2012 General Electric All Rights Reserved

GBB232TBC3

GBB232BBC3

GBB232TBC4

6
6
8
Page 59
DET-653C EntelliGuard® G Circuit Breaker Application Guide
53
2

4 Pole (Bottom Side)

3

6000A

3 Pole (Top Side)

3 Pole (Bottom Side)

4 Pole (Top Side)
4 Pole (Bottom Side)
Table 4.34. Back Connected Terminations

Envelope
Size

Description

Type

Catalog Number

Drawing

Qty.

1

Up to 1600 A

3 Pole

4 Pole

24-May-12 Section 4. Accessories

GBB232BBC4

GBB360TBC3

GBB360BBC3

GBB360TBC4

8
6
6
8

GBB360BBC4

GBB116TBB3

GBB116TBB4

8
6
8
©2012 General Electric All Rights Reserved
Page 60
DET-653C EntelliGuard® G Circuit Breaker Application Guide
54
1

200 A

3 Pole

4 Pole

2

Up to 2000 A

3 Pole

4 Pole

3000A UL

3 Pole

4 Pole

3200A ANSI

3 Pole (Top Side)
3 Pole (Bottom Side)
24-May-12 Section 4. Accessories

GBB120TBB3

GBB120TBB4

GBB220TBB3

GBB220TBB4

GBB230TBB3

6
8
6
8
6
©2012 General Electric All Rights Reserved

GBB230TBB4

8

GBB232TBB3

GBB232BBB3

6
6
Page 61
DET-653C EntelliGuard® G Circuit Breaker Application Guide
55
2

4 Pole (Top Side)

4 Pole (Bottom Side)

3

Up to 4000 A

3 Pole

4 Pole

6000A

3 Pole (Top Side)

3 Pole (Bottom Side)

4 Pole (Top Side)
4 Pole (Bottom Side)
24-May-12 Section 4. Accessories

GBB232TBB4

GBB232BBB3

GBB340TBB3

GBB340TBB4

8
8
6
8

GBB360TBB3

GBB360BBB3

GBB360TBB4

GBB360BBB4

6
6
8
8
©2012 General Electric All Rights Reserved
Page 62
DET-653C EntelliGuard® G Circuit Breaker Application Guide
56

Front Flat Terminations

Table 4.35. Optional Front Flat Terminations

Description

Catalog
Number

Drawing

Qty.

Env1 800 - 2000A, Type N&H, Flat Front UL489 Env3 4000-6000A Flat Front UL Fixed 4 Pole
24-May-12 Section 4. Accessories

The EntelliGuard G Fixed mounted breaker comes standard with Back Connected Terminations. Optional Front Flat terminations are available for front access mounting (Table 4.35).

Fixed 3 Pole Breaker Bus Bar Terminations (Top/Bottom)

Env1 800 - 2000A, Type N&H, Flat Front UL489 Fixed 4 Pole Breaker Bus Bar Terminations (Top/Bottom)

Env2 800A - 3000A Flat Front UL489 Fixed 3 Pole Breaker Bus Bar Terminations (Top/Bottom)

Env2 800A - 3000A Flat Front UL489 Fixed 4 Pole Breaker Bus Bar Terminations (Top/Bottom)

GBB1TBF3

GBB1TBF4

GBB2TBF3

GBB2TBF4

3
4
3
4

Env3 4000-6000A Flat Front UL Fixed 3 Pole Breaker Bus Bar Terminations (Top/Bottom)

Breaker Bus Bar Terminations (Top/Bottom)
Note: Please visit GE Energy's website for information regarding terminations for DC switches UL 489B.
©2012 General Electric All Rights Reserved

GBB3TBF3

GBB3TBF4

3
4
Page 63
DET-653C EntelliGuard® G Circuit Breaker Application Guide
57
Table 4.36. Cluster

Envelope

Description

Catalog Number

Drawing

Qty.

1
2
3
24-May-12 Section 4. Accessories

36 finger (95x20 mm) Qty 1 G20NCLS

36 finger (95x20 mm) Qty 1 G20MCLS*

36 finger (95x15 mm) Qty 1 G32ECLS

1
1
1

36 finger (95x15 mm) Qty 1 G64LCLS

1
* GE AKD20 Envelope 2 breakers with Characters 5 & 6 = ED or MD, regardless of amperage size, all use GBB232TBD Cluster Pad Assemblies and G32ECLS Finger Clusters
©2012 General Electric All Rights Reserved
Page 64
DET-653C EntelliGuard® G Circuit Breaker Application Guide
58
Table 4.37. Cluster Pad

Envelope

Description

Catalog Number

Drawing

Qty.

1
2
3
24-May-12 Section 4. Accessories

Cluster Pad ( set per phase) GBB120TBD

Cluster Pad ( single cluster) 2000A GBB220TBD*

Cluster Pad ( double cluster) 2500A-3200A GBB232TBD

Cluster Pad GBB360TBD

2
2
2
2
* GE AKD20 Envelope 2 breakers with Characters 5 & 6 = ED or MD, regardless of amperage size, all use GBB232TBD Cluster Pad Assemblies and G32ECLS Finger Clusters
©2012 General Electric All Rights Reserved
Page 65
DET-653C EntelliGuard® G Circuit Breaker Application Guide
59
Figure 4.35. Terminations for DC Switches UL 489B
Remote Racker

Table 4.38.

Description
Catalog #
Remote Racker
EGGRRLV
Grounding/Earthing Device (IEC Only)

Table 4.39. Earthing Devices (IEC only)

Envelope

Current Rating

Poles

400 to 1600/3P

3

400 to 1600/4P

4

2000/3P

3

2000/4P

4

400 to 4000/3P

3

400 to 4000/4P

4 3 3200 to 6300/3P
3

3200 to 6300/4P

4
Rejection Device
24-May-12 Section 4. Accessories
The remote racking operator allows the user to move a draw out circuit breaker between the CONNECT and DISCONNECT positions via an electric racking gear head motor and the Cassette housing the breaker. The remote racking operator requires 115VAC, 60Hz control power. A control box connected to the operator with a thirty-foot chord permits control from a remote location.
All EntelliGuard G circuit breakers can be fitted with a grounding/earthing device, which has a short circuit rating equal to the breaker withstand rating. This permits either the feeder cables or the busbar to be safely grounded and locked during system maintenance operations (Table 4.36).
1
2
A factory-installed rejection feature prevents mismatching breakers and cassettes/substructures. This prevents (a) inserting a breaker with a lower rating into a higher rated cassette/substructure and (b) inserting a higher rated breaker into a lower rated cassette/substructure. Mis­insertion Interlock catalog number is GREPM.
©2012 General Electric All Rights Reserved
Page 66
DET-653C EntelliGuard® G Circuit Breaker Application Guide
60
EntelliGuard® G Power Circuit Breaker Section 5. Catalog Numbering Guide
EntelliGuard G ANSI/UL489 Circuit Breaker Catalog Number Guide

Sample

G A 16 M 1 H E R X 5 R A X X L4 X 6
V
Digit 1 2
3&4 5 6 7 8 9 10
11
12
13
14
15

16&17

18
19
20

Digit 1 – Circuit Breaker Family

Device Series/Line

Code

EntelliGuard G Breaker/Switch

G

Digit 2 – Device & Type

Breaker/Switch Type, Secondary Mounting

Envelope 1

Envelopes 2 & 3

Side

Top
Top
Breaker

UL489 Circuit Breaker

B U B
(ANSI Switch)
(UL Switch)

Digits 3 & 4 – Current Rating/Sensors

Current Sensor
Rating (A)

Circuit Breaker

Switches*

ANSI

UL489

ANSI

UL489

400
04
04 - -
600
-
06 - -
800
08
08
08
08

1000

-
10 - -

1200

-
12 - 12

1600

16
16
16
16

2000

20
20
20
20

2500

-
25 - 25

3000

-
30 - 30

3200

32 - 32
-

4000

40
40
40
40

5000

50
50
50
50

6000

-
60 - 60

24-May-12 Section 5. Catalog Numbering Guide

Circuit Breaker Family

ANSI/UL1066 Circuit
ANSI Non-auto CB

Breaker Switch Type

Current Rating Sensors

Short Circuit Withstand Rating

A N A
C M C
UVR

Mounting

Spring Charge Motor

Shunt Trip

Closing Devices

2nd Shunt Trip, 2nd UVR

Contact
Auxiliary Switch, Coil Signaling
Bell Alarm, Mechanical Counter,
Device
Trip Annunciation

Mechanical Interlock

Key Interlock and Padlock
Overcurrent Protection Ground
ZSI
Fault

Rating Plug

Communications
Advanced Features and
UL489 Non-auto CB
Top = Top Mounted Secondary Disconnects (TSD).
Side = Side Mounted Secondary Disconnects (SSD). (Available on Envelope
1 only.)
N, U, M, S characters are for Envelope 1 only with top mounted
secondary disconnects (TSD).
When ordering codes A, B, C, D, Side Secondary Disconnects (SSD) are
supplied as standard on Envelope 1.
Codes N, U, M, S are not valid for Envelopes 2 & 3.
Envelope 1 (Type N and H, 400A - 2000A).
DC Ratings; trip unit not included. DC Rated Circuit Breakers require
external control devices (e.g., Type 37 or Type 76 DC Relays).
Side Secondary Disconnects are specifically intended for 5-High ("high
density") equipment designs.
With Side Mounted Disconnects (SSD), the following aux switches are not
valid (In Digit 12); Auxiliary Switch, 8 NO+8 NC (Power Rated) or Aux. Switch, 4 NO/4 NC (Power Rated) + 4 NO/4 NC low signal (Hi-Fi).
D S D

*Switches (Digit 2 = M, S, C, D) do not have current Sensors or a trip unit.

©2012 General Electric All Rights Reserved
Page 67
DET-653C EntelliGuard® G Circuit Breaker Application Guide
61

Digit 5- EntelliGuard G Short Circuit and Interrupting Ratings

Interrupting Rating Tier ANSI/UL1066 Devices, LVPCB

Envelope 1

Envelope 2

Envelope 3

C o d e

254V

580V

635V

1/2S

Withstand

HSIOC

Override

No.1

Overrride
WI

C o d e

400-
1200

400-200

3200

400-

3200

3200

4000-
5000

S
S
N
N
H
H
X
P*
P
E
E
X
M
M
X X
B
B
L
L

Interrupting Rating Tier UL489 Devices ICCB

Envelope 1

Envelope 2

Envelope 3

240V

480V

600V

1/2S

HSIOC

Override

Overrride
WI

400-
1200

400-200

2500-

3000

400-
3000

3000

4000-
6000

Withstand
No.1
S
S
N
N
H
H
P*
P
M
M
X
L
L

Close and Latch ratings (MCR set accordingly)

UL/ANSI 1 UL/ANSI 2 UL/ANSI 3
S N H M E L IEC 1

IEC 2

IEC 3

ANSI Non-Automatic Switches

30 Cycle Withstand Ratings

Envelope 1

Envelope 2

Envelope 3

254V

580V

635V

800-2000

800-3200

3200-5000

N
N
M
M
X
B
B

UL489 Non-Automatic Switches

Envelope 1

Envelope 2

Envelope 3

240V

480V

600V 800-2000

800-3000

3000-6000

N
N
M
M
X
B
B
24-May-12 Section 5. Catalog Numbering Guide

65,000 65,000 50,000 50,000 50,000 49,000 53,500

65,000 65,000 65,000 65,000 None None None

85,000 85,000 65,000 65,000 65,000 63,700 69,500

100,000 100,000 65,000 65,000 65,000 63,700 69,550

85,000 85,000 85,000 85,000 None None None

100,000 100,000 100,000 85,000 85,000 83,800 90,950

100,000 100,000 100,000 100,000 None None None

150,000 150,000 100,000 100,000 100,000 98,000 107,000

65,000 65,000 50,000 42,000 42,000 N/A 44,940

65,000 65,000 65,000 42,000 42,000 N/A 44,940

85,000 85,000 65,000 50,000 50,000 N/A 53,500

100,000 100,000 65,000 50,000 50,000 N/A 53,500

100,000 100,000 100,000 65,000 65,000 N/A 69,550

150,000 150,000 100,000 85,000 85,000 N/A 90,950

X
X X
X
X
X
X
X X
X X
X
X X
X
X
X
42,000 65,000

100,000

42,000 42,000 42,000

42,000 42,000 42,000

65,000 65,000 65,000

100,000 100,000 100,000

42,000 42,000 42,000

65,000 65,000 65,000

150,000 150,000 100,000

* P available only as 3-pole.
UL/ANSI CB MCR setting determined based on Envelope only. For
Retrofill's (A = 17,000, B = 33,000, N = 42,000)

50,000 50,000 65,000 65,000

100,000

Note: Non-automatic switches are provided with
no internal sensing or tripping mechanism and
cannot be applied above their respective withstand
levels. If a non-automatic device is required at
ratings above the available switches is required, it
is recommended that a circuit breaker set with
maximum setting be employed using external
control or protection as required by the
application.

100,000

Notes: Override has 7 % pick up tolerance. Nominal setting is 98% of lcw if no other instantaneous is on, or 107% of lcw if any other instantaneous is
on. UL 489 CB always has other instantaneous protection on. MCR set at
78% Close and Latch rating with -10% tolerance. -6000A UL 489 CB is
100% rated as stationary and 80% rated draw-out.
X
X
X
X
©2012 General Electric All Rights Reserved
Page 68
DET-653C EntelliGuard® G Circuit Breaker Application Guide
62

Digit 6 – Mounting Type Poles

Designation

Mounting

Poles

Code

1
2
3
4
5
6
D
F

Digit 7 – Spring Charging Motor

Spring Charging Motor (EO)

Code

24/30Vdc

A

48Vdc

B

60Vdc

C

72Vdc

D

110/130Vdc

E

250Vdc

F

48Vac

G

120Vac

H

240Vac

J

277Vac

K

Blank/none*

X

Digit 8 – Closing Devices

Closing Coil Type

Code

A
B

48Vac/dc

C

60 – 72Vdc

D
E

208Vac

F
G
H

24Vdc

M

30Vdc

N
P

60 – 72 Vdc

Q
R
S

220Vdc; 240Vac

T

Blank/none

X
SELECT ONE DEVICE ONLY.

Digit 9 – Shunt Trip 1

Extended Range Shunt Trip (ANSI/UL)*

Code

M
P
Q

110/125Vdc; 120Vac

R

208Vac

S

220Vdc; 240Vac

T
V
X
SELECT ONE DEVICE ONLY.
24-May-12 Section 5. Catalog Numbering Guide
3

drawout

OEM

stationary

4, right

4, left

3

4, right

4, left

GE Equipment

Right, Left indicates the location of the fourth pole, typically used to
switch the neutral.
Stationary and drawout breakers come with back connected
terminations. Optional front flat terminations are available. See page 40.
P type circuit breaker available only in 3-pole.

drawout 3

stationary 3

DC
AC
*An "X" (Blank/None) denotes a Manually Operated device (MO) Spring Charge Contact, GSCC1, included with all Motor Operators.
When a Spring Charging Motor is selected, a Closing Device must be
selected from Closing Devices for Digit 8, and a Shunt Trip Device must be selected from Shunt Trip 1 Devices for Digit 9.
Shunt Trip 1 with a coil voltage different from the Spring Charge Motor
may be user-selected.
24Vdc 30Vdc

Closing Coil (CC)*

110Vdc/130Vdc; 120Vac

220Vdc; 240Vac 250Vdc; 277Vac

Command Operated Closing Coil (CCC)**

48Vac/dc

110Vdc/130Vdc; 120Vac 208Vac
*The Closing Coil (CC) permits either local or remote release of the spring charged closing mechanism by electrical operation. **The Command Operated Closing Coil (CCC) includes an additional anti-pumping safety feature to ensure that the electrical closing signal must be released before further closure is attempted, a shut off is initiated if the closing signal is maintained.
Manual button through breaker cover is included as standard
assembly.
When a Spring Charging Motor is selected (Digit 7), a Closing Device
must be selected from Closing Devices for Digit 8, and a Shunt Trip Device must be selected from Shunt Trip 1 Devices for Digit 9.
24Vdc 48Vac/dc 70 – 72Vdc

250Vdc; 277 Vac Blank/none

*The Extended Range Shunt Trip is specifically intended and required for UL ANSI Ground Fault applications. The pick up range is 55-110% of the ST coil voltage.
When a motor is selected from the Spring Charging Motor (Digit 7)
a Shunt Trip 1 must be selected.
©2012 General Electric All Rights Reserved
Page 69
DET-653C EntelliGuard® G Circuit Breaker Application Guide
63

Digit 10 – Under Voltage Release (UVR)

UVR with Fixed Time Delay *

Code

24Vdc

1

30Vdc

2
3
4
5

208Vac

6

220Vdc; 240Vac

7

250Vdc; 277Vac

8
X
SELECT ONE DEVICE ONLY.

Digit 11 – 2nd Shunt Trip or UVR

Type

Code

24Vdc

1

30Vdc

2

48Vac/dc

3

60 - 72Vdc

4

110Vdc/130Vdc; 120Vac

5

208Vac

6

220Vdc; 240Vac

7

250Vdc; 277Vac

8

24Vdc

M

48Vac/dc

P

70 - 72Vdc

Q

110/125Vdc; 120Vac

R

208Vac

S

240Vac

T

250Vdc

V

Blank/none

X
SELECT ONE DEVICE ONLY.
24-May-12 Section 5. Catalog Numbering Guide
48Vac/dc 60-72Vdc 110/130Vdc; 120Vac

Blank/none

*The UVR Shunt Trip with Fixed Time Delay is specifically intended for applications where a delay period ('ride- through') is required due to potential voltage events. The design delays are 50msec when system voltage drops to 50% and 20 msec when system voltage drops below 50%.
An optional External UVR Time Delay Module is available in a 1 - 3sec delay.

2nd UVR with Fixed Time Delay **

2nd Extended Range Shunt Trip (ANSI/UL)*

*The Extended Range Shunt Trip is specifically intended and required for UL ANSI Ground Fault applications. The pick up range is 55-110% of the ST coil voltage. **The UVR with Fixed Time Delay is specifically intended for applications where a delay period ('ride- through') is required due to potential voltage events. The design delays are 50msec when system voltage drops to 50% and 20msec when system voltage drops below 50%.
An optional External UVR Time Delay Module is available in a 1 - 3sec
delay.
©2012 General Electric All Rights Reserved
Page 70
DET-653C EntelliGuard® G Circuit Breaker Application Guide
64

Digit 12 – Auxiliary Switch

Contact Configuration

Code

2

Auxiliary Switch, 8NO+8NC (Power Rated)***

4

Aux. Switch, 3NO/3NC (Power Rated) + 2NO/2NC low signal (Hi-Fi)

6

Aux. Switch, 4NO/4NC (Power Rated) + 4NO/4NC low signal (Hi-Fi)***

8

CSC, PR, (1 NO on SD) - Close Coil or CCC

A

CSC, Hi-Fi via Trip Unit - Close Coil or CCC**

B

CSC, PR, (1 NO on SD) - 1st Shunt Trip

C

CSC, Hi-Fi via Trip Unit - 1st Shunt Trip **

D

CSC, PR, (1 NO on SD) - 1st UVR

E

CSC, Hi-Fi via Trip Unit - 1st UVR**

F

CSC, PR, (1 NO on SD) - 2nd ST or 2nd UVR

G

CSC, Hi-Fi via Trip Unit - 2nd ST or 2nd UVR**

H

CSC, PR, (1 NO on SD) - Close Coil or CCC

J

CSC, Hi-Fi via Trip Unit - Close Coil or CCC**

K

CSC, PR, (1 NO on SD) - 1st Shunt Trip

L

CSC, Hi-Fi via Trip Unit - 1st Shunt Trip**

M

CSC, PR, (1 NO on SD) - 1st UVR

N

CSC, Hi-Fi via Trip Unit - 1st UVR**

P

CSC, PR, (1 NO on SD) - 2nd ST or 2nd UVR

Q

CSC, Hi-Fi via Trip Unit - 2nd ST or 2nd UVR**

R
(Power Rated)

CSC, PR, (1 NO on SD) - All Installed Devices

S

CSC, Hi-Fi via Trip Unit - All Installed Devices**

T

CSC, PR, (1 NO on SD) - All Installed Devices

U

CSC, Hi-Fi via Trip Unit - All Installed Devices**

V
CCC CSC Hi-Fi PR SD
24-May-12 Section 5. Catalog Numbering Guide

Auxiliary Switch, 3NO+3NC (Power Rated)* STANDARD/INCLUDED

Auxiliary Switch, 3NO+3NC (Power Rated)

Aux. Switch, 3NO/3NC (PR) + 2NO/2NC Low Signal (Hi-Fi)

Auxiliary Switch, 3NO+3NC

Aux. Switch, 3NO/3NC (PR) + 2NO/2NC Low Signal (Hi-Fi)

= Command Operated Close Coil
= Coil Signaling Contact
= High Fidelity = Power Rated = Secondary Disconnect
*The 3NO/3NC scheme is STANDARD (INCLUDED, CODE 2) and is wired to Secondary Disconnect Block A, all other selections require Secondary Disconnect Block B. **In order to output the Coil Signaling status Hi-Fi via trip unit (options B, D, F, H, K, M, P,R, T, and V) a communications package must be selected in Advanced Features (Digit 19; options 2, 3, 6, 7, 8, 9). This option requires Secondary Disconnect Block B. **If a UL or ANSI Switch is selected in Digit 2 (C, D, M, S), the Hi-Fi via Trip Unit options are not valid (options B, D, F, H, K, M, P, R, T, V). ***For Side-mounted Secondary Disconnect Blocks, all options are available EXCEPT options 4 and 8.
The term “Hi-Fi” refers to gold-plated contacts used for signal level outputs (10mA minimum - 100mA maximum, 5-30Vdc, 125Vac).
If no devices were selected in Digit 8, 9, 10, 11 (Codes = "X"), then Options A - V are invalid.
Options A-V are only valid if the corresponding device to be monitored by the Coil Signaling Contact (CSC) is selected in digits 8, 9, 10, 11.
©2012 General Electric All Rights Reserved
Page 71
DET-653C EntelliGuard® G Circuit Breaker Application Guide
65

Digit 13 – Bell Alarm/Trip Annunciation

Bell Alarm and Trip Annunciation

Code

A
B
C
1
2

RTC Signal Rated (Hi-Fi) Contacts through Trip Unit**

3

BACL and RTC Power Rated Contacts on SD*

D

BACL and RTC Signal Rated (Hi-Fi) Contacts on SD*

E

BACL and RTC Signal Rated (Hi-Fi) through Trip Unit**

F

BACL, MOC and RTC Power Rated on SD*

G

BACL, MOC and RTC Signal Rated on SD*

H
Unit**
J K
L
M
X
BACL = Bell Alarm Contact with Lockout RTC = Ready To Close Contacts
Hi-Fi = High Fidelity SD = Secondary Disconnect
**In order to output the RTC contact output via Trip Unit (options 3, F, J, M) a communications pac (Code 19/Step 16); this requires Secondary Disconnect Block B. **If a UL or ANSI Switch is selected, the (Hi valid (Options 3, F, J, M). **RTC Through the Trip Unit is not a valid option for Switches. Bell Alarm Contact with Lockout comes with the Trip Enabled.

Digit 14 – Key Interlock

Key Interlock (Breaker Mounted)

Code

Castell Key Interlock

C

Kirk Key Interlock

K

Ronis Key Interlock

R
L
Device
1 2
3

Blank/none

X
• Locks and Keys are NOT Supplied by GE.

Digit 15 – Mechanical Interlocks

Mechanical Interlocks

Code

Blank/None DEFAULT

X

Mechanical Interlock - Type A

1

Mechanical Interlock - Type B

2

Mechanical Interlock - Type C

3

Mechanical Interlock - Type D

4
• Contact factory for availability.
24-May-12 Section 5. Catalog Numbering Guide
Bell Alarm Contact (1NO/1NC) with Lockout (BACL) Mechanical Operations Counter (MOC) Bell Alarm Contact (1NO/1NC) with Lockout and MOC RTC Power Rated Contacts on SD* RTC Signal Rated (Hi-Fi) Contacts on SD*
BACL, MOC and RTC Signal Rated (Hi-Fi) through Trip
MOC and RTC Power Rated on SD* MOC and RTC Signal Rated on SD* MOC and RTC Signal Rated (Hi-Fi) through Trip Unit** Blank/none
kage must be selected in Advanced Features
-Fi Through Trip Unit) is not
Unit set to Manual LO
The term “Hi-Fi” refers to gold-plated contacts use for signal level
outputs (10mA minimum - 100mA maximum, 5-30Vdc, 125vac).
Option "B", “I”, “2”, “3”, “K”, “L”, “M”, and “X” are the only valid options
when a Switch is selected in Digit 2.
Pushbutton Padlock Device Castell Key Interlock and Push Button Padlock
Kirk Key Interlock and Push Button Padlock Device Ronis Key Interlock and Push Button Padlock Device
This option provides factory installed interlocking devices for
installation between separate circuit breakers (baseplates and mechanism). This safeguard ensures that a circuit breaker cannot be closed unless the dedicated key has been inserted and secured within the lock.
If selecting a Draw Out Breaker (Digit 6), consider putting the Key
Interlock on the Cassette versus the breaker. This enables the ability to swap breakers without having to change the key interlocks.
©2012 General Electric All Rights Reserved
Some installations use multiple power sources that are required to supply
energy simultaneously, alternately, or, in a specified sequence. EntelliGuard G Circuit Breakers can be used to interconnect these sources and be electrically and mechanically interlocked to provide the necessary transition and protection. Mechanical Interlocks are available for fixed and draw out circuit breakers. The interlocks enable directly interlocking breakers that are mounted side by side or in vertical stacks. The interlocks consist of two components: (A) The factory-installed bracket fitted to the breaker (fixed breakers) or the cassette (drawout breakers), and (B) The field-installable interconnecting cables available in lengths of 1.0, 1.6, 2.0,
2.5, 3.0, 3.5 and 4.0m (ordered separately). Refer to Section 4 for interlocking schemes.
Page 72
DET-653C EntelliGuard® G Circuit Breaker Application Guide
66

Digits 16 & 17 – Overcurrent Protection Package

Type

Over Current (OC) Protection Package

Code

LSI
L3
LSIG
L4
LSIGA
L5
LSIC
L6
LSICA
L7
LSIGDA*
L8
LSIGCDA*
L9
LSH
LC
LSHG
LD
LSHGA
LE
LSHC
LF
LSHCA
LG
LSHGDA*
LH
LSHGCDA*
LK
FROM 1/1/12: INCLUDED IN L TYPE TRIP UNITS
JSI
J3
JSIG
J4
JSIGA
J5
JSIC
J6
JSICA
J7

JSIGDA* (S, G, A all switchable) (I, switchable ANSI only)

J8
JSIGCDA*
J9
JSH
JC
JSHG
JD
JSHGA
JE
JSHC
JF
JSHCA
JG
JSHGDA*
JH
JSHGCDA*
JK
XX
A C application: Zero Sequence Input of 1A = 100%) D G H I J L S CA GA GDA, GCDA = Ground Fault Trip and Ground Fault Alarm (all switchable, not UL Listed)
*Function Combination is NOT UL Listed.
Option "XX" is the only valid option when a Switch is selected in Digit 2.
24-May-12 Section 5. Catalog Numbering Guide
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only)

Standard Range Instantaneous

EntelliGuard G ANSI/UL OC Protection with Fuse Settings

Extended Range Adjustable Instantaneous

Standard Range
EntelliGuard G
Instantaneous
ANSI/UL OC Protection with Fuse Settings

Extended Range Adjustable Instantaneous

NONE - (For Switch Only)

= Ground Fault, External Ground Fault, Alarm only
= External CT for ground fault detection (AKD20 application: input from external summing CTs, used for multiple source ground fault detection. OEM
= Defeatable/Switchable Ground Fault, not UL Listed = Ground Fault Protection (GFP, 3-wire or 4-wire, internal summing) = Extended Range Adjustable Instantaneous, (IOC, 2x-30x), not available in UL489 version of EntelliGuard G or any Legacy CB
= Standard Range Adjustable Instantaneous, (IOC, 2x-15x)
= Long Time (L, I2T) + Fuse Settings (I4T) = Long Time (I2T, all trip unit)
= Short Time (Switchable if Instantaneous (I) protection is enabled)
= External Ground Fault Alarm Only
= Ground Fault Alarm Only
(S, switchable) (I, switchable ANSI only) (G, Alarm Only)
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only) (C, Alarm Only)
(S, G, A switchable) (I, switchable ANSI only)
(S, G, C, A all switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only) (G, Alarm Only)
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only) (C, Alarm Only)
(S, G, A switchable) (I, switchable ANSI only)
(S, G, C, A all switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only) (G, Alarm Only)
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only) (C, Alarm Only)
(S, G, C, A all switchable) (I, switchable ANSI only)
(S, switchable) (H, switchable ANSI only)
(S, switchable) (H, switchable ANSI only)
(S, switchable) (H, switchable ANSI only) (G, Alarm Only)
(S, switchable) (H, switchable ANSI only)
(S, switchable) (H, switchable ANSI only) (C, Alarm Only)
(S, G, A all switchable) (H, switchable ANSI only)
(S, G, C, A all switchable) (H, switchable ANSI only)
©2012 General Electric All Rights Reserved
Page 73
DET-653C EntelliGuard® G Circuit Breaker Application Guide
67

Digit 18 – Zone Selective Interlocking (ZSI)

Zone Selective Interlocking

Code

Z

Z + IOC or HIOC ZSI; user selectable

T
X

Digit 19 – Advanced Features and Communications

Advanced Features and Communications

Code

Reduced Energy Let-Through (RELT)

1

Modbus Protocol + RELT

2
3

Monitoring + RELT, NO Communication

4

Monitoring + Relay Package + RELT

5

Monitoring + Data Acquisition, Modbus Protocol + RELT

6

Monitoring + Data Acquisition, Profibus Protocol + RELT

7

Monitoring + Data Acquisition + Relay Package, Modbus + RELT

8

Monitoring + Data Acquisition + Relay Package, Profibus + RELT

9

None

X

Digit 20 – Rating Plug

Rating Plug

Catalog Number

Code

150

GTP0150U0104

B

1100

GTP1100U1225

R

1900

GTP1900U2050

W

2500

GTP2500U2564

2

6000

GTP6000U6064

8
X
24-May-12 Section 5. Catalog Numbering Guide

ZSI, Short time and GF; user selectable

Blank/none

ZSI selections require Secondary Disconnect Block B and 24Vdc control
power. Control power recommended for instantaneous ZSI.

Profibus Protocol + RELT

.All Advanced Feature selections require Secondary Disconnect Block B
and 24Vdc control Power.
Option "X" is the only valid option when a Switch is selected in Digit 2.
RELT = Reduced Energy Let Through, requires dedicated input and output
on the CB Monitoring = Advanced Metering.
• Data Acquisition = Waveform Capture and Harmonic Analysis .
In order to output the Coil Signaling status HiFi via trip unit (Digit 12,
Options B, D, F, H, K, M, P, R, T, and V) a communications package must be selected in Advanced Features (Digit 19; options 2, 3, ,7, 8, 9). This option requires Secondary Disconnect Block B.
In order to output the RTC contact output via Trip Unit (Digit 13; Options
3, F, J, M) a communications package must be selected in Advanced Features (Code 19/Step 16); this requires Secondary Disconnect Block B.

200 GTP0200U0204 C 225 GTP0225U0306 D 250 GTP0250U0407 E 300 GTP0300U0408 F 350 GTP0350U0408 G 400 GTP0400U0410 H 450 GTP0450U0612 I 500 GTP0500U0613 J 600 GTP0600U0616 K 700 GTP0700U0816 M 750 GTP0750U0820 N 800 GTP0800U0820 O 900 GTP0900U1020 P

1000 GTP1000U1025 Q

1200 GTP1200U1232 S 1500 GTP1500U1640 U 1600 GTP1600U1640 V

2000 GTP2000U2050 Y 2200 GTP2200U2550 Z 2400 GTP2400U2564 1

3000 GTP3000U3064 3 3200 GTP3200U3264 4 3600 GTP3600U4064 5 4000 GTP4000U4064 6 5000 GTP5000U5064 7

Rating plug not required/non auto switch

• See Section 3 for further details on rating plugs and sensors.
Option "X" is the only valid option when a switch is selected in Digit 2.
©2012 General Electric All Rights Reserved
Page 74
DET-653C EntelliGuard® G Circuit Breaker Application Guide
68
EntelliGuard G Cassette Catalog Number Guide

Sample

G A 16 M 2
S
Digit 1 2
3&4 5 6
7

Digit 1 – Cassette Family

Device Series/Line

Code

EntelliGuard G Breaker/Switch

G

Digit 2 – Cassette Device & Type

Cassette Type, Secondary Mounting

Envelope 1

Envelopes 2 & 3

Side

Top
Top
Breaker

UL489 Circuit Breaker

B U B
(ANSI Switch)
(UL Switch)

Digit 3 & 4 – Cassette Current Rating

Current Rating (A)

Circuit Breaker

ANSI

UL489

800
08
08

1600

16
16

2000

20
20
3000 - 30

3200

32
-

5000

50
-
6000 - 60
24-May-12 Section 5. Catalog Numbering Guide
Circuit Breaker Cassette
ANSI/UL1066 Circuit
ANSI Non-auto CB
UL489 Non-auto CB
Family

# of Poles

Shutters

Current Rating

Breaker Switch Type

A N A
C M C
D S D

Cassette AIC Rating

Select Current Rating equal to or the next higher of the Circuit Breaker or
Switch Current Rating
Top = Top Mounted Secondary Disconnects (TSD).
Side = Side Mounted Secondary Disconnects (SSD). (Available on Envelope
1 only.)
N, U, M, S characters are for Envelope 1 only with top mounted
secondary disconnects (TSD).
When ordering codes A, B, C, D, Side Secondary Disconnects (SSD) are
supplied as standard on Envelope 1.
Codes N, U, M, S are not valid for Envelopes 2 & 3.
Envelope 1 (Type N and H, 400A - 2000A).
DC Ratings; trip unit not included. DC Rated Circuit Breakers require
external control devices (e.g., Type 37 or Type 76 DC Relays).
Side Secondary Disconnects are specifically intended for 5-High ("high
density") equipment designs.
With Side Mounted Disconnects (SSD), the following aux switches are not
valid (In Digit 12); Auxiliary Switch, 8 NO+8 NC (Power Rated) or Aux. Switch, 4 NO/4 NC (Power Rated) + 4 NO/4 NC low signal (Hi-Fi).
©2012 General Electric All Rights Reserved
Page 75
DET-653C EntelliGuard® G Circuit Breaker Application Guide
69

Digit 5 – Cassette Envelope Size

Interrupting Rating Tier ANSI/UL1066 Devices, LVPCB

Envelope 1
Envelope 2
Envelope 3
240V
480V
600V
1/2S
Withstand
HSIOC
Override
No. 1
Override
WI
400-2000
3200
400-
3200
3200
4000-
5000
S
S
N

65,000

65,000

65,000

65,000

none

none

none

N
X X
H

85,000

85,000

65,000

65,000

65,000

63,700

69,500

H
X
P*
P
E

85,000

85,000

85,000

85,000

none

none

None

E
X
M

100,000

100,000

85,000

85,000

85,000

83,800

90,950

M
X Use B
B
B
L

150,000

150,000

100,000

100,000

100,000

98,000

107,000

L
X X

Interrupting Rating Tier UL489 Devices ICCB

Envelope 1
Envelope 2
Envelope 3
240V
480V
600V
1/2S
Withstand
HSIOC
Override
No. 1
Override
WI
400-2000
2500-
3000
400-
3000
3000
4000
5000-
6000
S

65,000

65,000

50,000

42,000

42,000

N/A

44,940

S
X
N

65,000

65,000

65,000

42,000

42,000

N/A

44,940

N
X X
H

85,000

85,000

65,000

50,000

50,000

N/A

53,500

H
X X
P*

100,000

100,000

65,000

50,000

50,000

N/A

53,500

P
X
M

100,000

100,000

85,000

65,000

65,000

N/A

69,550

M
X X
Use L
L

150,000

150,000

100,000

85,000

85,000

N/A
90,950
L
X X X

ANSI Non-Automatic Switches

30 Cycle Withstand Ratings

Envelope 1
Envelope 2
Envelope 3
240V
480V
600V
800-2000
800-3200
3200-5000
N

42,000

42,000

42,000

N
X
M

65,000

65,000

65,000

M
X
B

100,000

100,000

100,000

B
X

UL489 Non-Automatic Switches

Envelope 1
Envelope 2
Envelope 3
240V
480V
600V
800-2000
800-3000
3000-6000
N

42,000

42,000

42,000

N
X
M

65,000

65,000

65,000

M
X
B

100,000

100,000

100,000

B
X

Digit 6 - Cassette Type & Number of Poles

Device Series/Line

Code

2
5

GE Equipment Cassette – 3 Pole**

7

Digit 7 - Shutter

Shutters with Locks

Code

Shutter and Shutter Lock - Factory Installed

S

None

X

Loose Cassette Parts – Field Installed

GCPS1R

GCPS2R

1 Kirk Key Interlock Cam for Cassette

GCKRKR

1 Ronis Key Interlock Cam for Cassette

GCRONR

Mounted

GSDWTR

Mounted

GSDWSR

24-May-12 Section 5. Catalog Numbering Guide

65,000 65,000 50,000 50,000 50,000 49,000 53,500

100,000 100,000 65,000 65,000 65,000 63,700 69,550
100,000 100,000 100,000 100,000 none none none
Notes: Non-automatic switches are provided with no internal sensing or tripping mechanism and cannot be applied above their respective withstand levels. If a non-automatic device is required at ratings above the available switches is required, it is recommended that a circuit breaker set with maximum settings be employed using external control or protection as required by the application.
X
X
X X
OEM Cassette – 3 Pole OEM Cassette – 4 Pole
* P version available only in 3 pole. ** GE Equipment cassette designed specifically for AKD20 Switchgear.
These cassettes are NOT available for OEMs.
©2012 General Electric All Rights Reserved
Carriage Position Switch - 1 NO/1NC Carriage Position Switch - 2 NO/2NC
Secondary Disconnect Block B, 39 Pole - Top
Secondary Disconnect Block B, 39 Pole - Side
Secondary Disconnect Block B is required when:
ONE SELECTIVE INTERLOCKING" options are selected in
- Any "Z
breaker/trip unit Catalog Digit 18.
y "ADVANCED FEATURES" are selected in breaker/trip unit Catalog
- An
Digit 19.
- A COIL SIGNALING CONTACT OPTION is selected, Digit 12.
EADY TO CLOSE signal via the trip unit is selected, Digit 13.
- A R
- An
y of the following OPTIONAL Aux. Contact Switches are selected in
Digit 12: 8NO
/NC POWER RATED
3NO/NC POWER RATED + 2NO/NC Hi-Fi 4NO/NC POWER RATED + 4NO/NC Hi-Fi
Page 76
DET-653C EntelliGuard® G Circuit Breaker Application Guide
70
EntelliGuard TU Trip Unit for EntelliGuard G Breakers

Sample

GG M 16
L4 X 6 A XXXX

Digit

1&2 3 4&5
6&7 8 9
10

11-14

Manual Auto Trip Reset

Digit 1 & 2 – Trip Unit Form/Family

Circuit Breaker Type

Code

Power Break 1 (UL)

GA

Power Break 2 (UL)

GB

AKR (ANSI)

GC

WP (ANSI)

GW

Mpact Low (IEC)

GL

Mpact 24-48V (IEC)

GH

Mpact 120-240V (IEC)

GQ

Entelliguard G ACB (ANSI)

GG

Entelliguard G ACB (UL)

GU

Entelliguard G ACB (IEC)

GT

EntelliGuard G Universal Spare Trip

G1

Type A Conversion Kits (ANSI)

G2

Entelliguard G Switch (IEC)

G3

Digit 4 & 5 – Sensor Rating

Sensor Rating

Code

UNIV*

00
400
04

600**

06
800
08

1000**

10

1200**

12

1600

16

2000

20

2500**

25

3000**

30

3200***

32

4000

40

5000

50

6000**

60

Digit 3 – EntelliGuard G Frame Rating

Code

240V

480V

600V

1/2S Withstand

HSIOC

Override No 1

Override WI

Interrupting Rating Tier, ANSI/UL1066 Devices LVPCB

S

65,000

65,000

50,000

50,000

50,000

49,000

53,500

N

65,000

65,000

65,000

65,000

none

none

none

H

85,000

85,000

65,000

65,000

65,000

63,700

69,550

P

100,000

100,000

65,000

65,000

65,000

63,700

69,500

E

85,000

85,000

85,000

85,000

none

none

none

M

100,000

100,000

85,000

85,000

85,000

83,300

90,950

B

100,000

100,000

100,000

100,000

none

none

none

L

150,000

150,000

100,000

100,000

100,000

98,000

107,000

Interrupting Rating Tier, UL489 Devices ICCB

S

65,000

65,000

50,000

42,000

42,000

N/A

44,940

N

65,000

65,000

65,000

42,000

42,000

N/A

44,940

H

85,000

85,000

65,000

50,000

50,000

N/A

53,500

P

100,000

100,000

65,000

50,000

50,000

N/A

53,500

M

100,000

100,000

85,000

65,000

65,000

N/A

69,550

L

150,000

150,000

100,000

85,000

85,000

N/A

90,950

24-May-12 Section 5. Catalog Numbering Guide

Frame Rating

Sensor Rating

EntelliGuard Trip Unit Form

Overcurrent Ground Fault
ZSI
Protection

Adv. Features and Comm.

Future Use

This Application Guide documents the EntelliGuard TU Trip Unit for
EntelliGuard G Circuit Breakers.
GE Legacy ANSI, UL Circuit Breakers are documented in DEH-4567.

*Universal Spare Trip Unit. **UL only. ***ANSI only.

Refer to GEH-4567 for other circuit breaker types.
Codes E and B are for ANSI EntelliGuard G circuit breakers only.
©2012 General Electric All Rights Reserved
Page 77
DET-653C EntelliGuard® G Circuit Breaker Application Guide
71

Digits 6 & 7 – Overcurrent Protection Package (for EntelliGuard® G Breakers)

Type

Over Current (OC) Protection Package

Code

LSI (S, switchable) (I, switchable ANSI only)

L3

LSIG (S, switchable) (I, switchable ANSI only)

L4

LSIGA (S, switchable) (I, switchable ANSI only) (G, alarm only)

L5

LSIC (S, switchable) (I, switchable ANSI only)

L6

LSICA (S, switchable) (I, switchable ANSI only) (C, alarm only)

L7

LSIGDA* (S, G, A switchable) (I, switchable ANSI only)

L8

LSIGCDA* (S, G, C, A all switchable) (I, switchable ANSI only)

L9

LSH (S, switchable) (I, switchable ANSI only)

LC

LSHG (S, switchable) (I, switchable ANSI only)

LD

LSHGA (S, switchable) (I, switchable ANSI only) (G, alarm only)

LE

LSHC (S, switchable) (I, switchable ANSI only)

LF

LSHCA (S, switchable) (I, switchable ANSI only) (C, alarm only)

LG

LSHGDA* (S, G, A switchable) (I, switchable ANSI only)

LH

LSHGCDA* (S, G, C, A all switchable) (I, switchable ANSI only)

LK
FROM 1/1/12: INCLUDED IN L TYPE TRIP UNITS

JSI (S, switchable) (I, switchable ANSI only)

J3

JSIG (S, switchable) (I, switchable ANSI only)

J4

JSIGA (S, switchable) (I, switchable ANSI only) (G, Alarm Only)

J5

JSIC (S, switchable) (I, switchable ANSI only)

J6

JSICA (S, switchable) (I, switchable ANSI only) (C, Alarm Only)

J7

JSIGDA* (S, G, A all switchable) (I, switchable ANSI only)

J8

JSIGCDA* (S, G, C, A all switchable) (I, switchable ANSI only)

J9

JSH (S, switchable) (H, switchable ANSI only)

JC

JSHG (S, switchable) (H, switchable ANSI only)

JD

JSHGA (S, switchable) (H, switchable ANSI only) (G, Alarm Only)

JE

JSHC (S, switchable) (H, switchable ANSI only)

JF

JSHCA (S, switchable) (H, switchable ANSI only) (C, Alarm Only)

JG

JSHGDA* (S, G, A all switchable) (H, switchable ANSI only)

JH

JSHGCDA* (S, G, C, A all switchable) (H, switchable ANSI only)

JK

None (for switch only)

XX
A C
D G H I J L S GA CA GDA, GCDA
24-May-12 Section 5. Catalog Numbering Guide

Standard Range Instantaneous

EntelliGuard G ANSI/UL OC Protection with Fuse Settings

Extended Range Adjustable Instantaneous

Standard Range

EntelliGuard G ANSI/UL OC Protection with Fuse Settings

Instantaneous
= Ground Fault, External Ground Fault, Alarm only.
= External CT for ground fault detection (AKD20 application: input from external summing CTs, used for multiple source ground fault detection. OEM
Application: Zero Sequence Input of 1A = 100%).
= Defeatable/Switchable Ground Fault NOT UL Listed. = Ground Fault Protection (GFP, 3-wire or 4-wire, internal summing). = Extended Range Adjustable Instantaneous, (IOC, 2x-30x), Only for ANSI EntelliGuard G.
= Standard Range Adjustable Instantaneous, (IOC, 2x-15x).
= Long Time (L, I2t) + Fuse Settings (I4t). = Long Time (I2t, all trip unit).
= Short Time (Switchable if Instantaneous (I) protection is enabled).
= Ground Fault Alarm only. = External Ground Fault Alarm only.
* Function combination is NOT UL Listed.
©2012 General Electric All Rights Reserved

Extended Range Adjustable Instantaneous

= Ground Fault Trip and Ground Fault Alarm (all switchable, Not UL Listed).
Page 78
DET-653C EntelliGuard® G Circuit Breaker Application Guide
72

Digit 8 – Zone Selective Interlocking (ZSI)

Zone Selective Interlocking

Code

Z
T
X
D

Digit 9 – Advanced Features and Communications

Advanced Features & Communications

Code

Reduced Energy Let-Through (RELT)

1

Modbus Protocol + RELT

2

Profibus Protocol + RELT

3

Monitoring + RELT, NO Communication

4

Monitoring + Relay Package + RELT

5

Monitoring + Data Acquisition, Modbus Protocol + RELT

6

Monitoring + Data Acquisition, Profibus Protocol + RELT

7
Modbus + RELT
8
Monitoring + Data Acquisition + Relay Package,
9

None

X

Digit 10 – Manual/Auto Trip Reset

Manual Auto Trip Reset

Code

Manual Lockout

M

Auto Reset/Reclose

A

Auto/Manual Lockout (Selectable)

S

None (Defaults to Auto Reset/Reclose)

X

Digit 11 – Factory or Field Installed

Manual Auto Trip Reset

Code

F
R
EntelliGuard TU Trip Unit Rating Plugs (see page 20)

Sample

GTP
1600 U 16
40

Digit

1,2,3,4

5,6,7,8

9

10,11

12,13

24-May-12 Section 5. Catalog Numbering Guide
ZSI, Short time and GF; user selectable Z + IOC or HIOC ZSI; user selectable Blank/None
ALL ZSI selections require Secondary Disconnect Block B and 24Vdc
control power.
Control power recommended for instantaneous ZSI.
Monitoring + Data Acquisition + Relay Package,
Profibus + RELT
When Bell Alarm with Lockout is selected on the EntelliGuard G Circuit
Breaker, then Code M must be selected.
• X is only valid on GE Legacy Circuit Breakers and Conversion Kits.
M is valid on EntelliGuard G Breakers when a Bell Alarm is selected.
A is valid on EntelliGuard G Breakers when a Bell Alarm is not selected.
• S is IEC Only
Factory Installed Trip Unit (Original) Replacement Trip Unit (shipped loose)
Plug
All Advanced Feature selections require Secondary Disconnect Block B
and 24Vdc control Power.
• RELT = Reduced Energy Let Through.
• Monitoring = Advanced Metering.
Data Acquisition = Waveform Capture and Harmonic Analysis.
plug (4000A)
(Rating in Amperes)
EntelliGuard Trip Unit Rating
Universal Trip Unit Rating Plug

Universal Trip Plug

this plug (1600A)
Smallest Sensor that accepts
Largest Sensor that accepts this
©2012 General Electric All Rights Reserved
Page 79
DET-653C EntelliGuard® G Circuit Breaker Application Guide
73
EntelliGuard® G Power Circuit Breaker Section 6. Application Data

Introduction

Key Features
UL1066 Low Voltage Power Circuit Breakers
UL489 Stored Energy Insulated Case Circuit Breakers
IEC Rated Circuit Breakers for IEC Equipment and Applications
All Types
Ratings and Sizes
24-May-12 Section 5. Catalog Numbering Guide
The EntelliGuard G family of circuit breakers and related switching devices is a truly global line of protection and switching devices. It was designed from the ground up to provide reliable protection and operation in a wide range of power distribution systems. Combined with the EntelliGuard TU family of trip devices, EntelliGuard G circuit breakers provide superior protection and reliability with a maximum of flexibility and a minimum of compromise for your power protection and switching needs.

This section provides an overview of the circuit breaker’s capability under UL 489 and UL 1066 standards.

There are three product families:
800-5000A frames in three physical sizes.
400-5000A sensors with rating plugs as low as 150A and
trip settings as low as 75A.
Short circuit ratings as high as 150kA at 480V (tested at
508V).
Withstand capability and selectivity as high as 100kA
Continuously adjustable selective instantaneous as high
as 30X the circuit breaker’s rating.
800-6000A frames in three physical sizes.
400-6000A sensors with rating plugs as low as 150A and
trip settings as low as 75A.
Short circuit ratings as high as 150kA at 480V.
Withstand capability and selectivity as high as 100kA.
Continuously adjustable selective instantaneous to 15X
on all but the largest circuit breakers.
Draw-out and stationary mounted, 100% rated in most
sizes.
800-6400A frames in three physical sizes.
400-6400A sensors adjustable to 20% of sensor size.
Short circuit ratings as high as 150kA at 440V, 100kA at
690V, 80kA at 1000V.
Rated breaking capacity 100%, Ics = Icu for all frames.
Withstand capability and selectivity as high as 100kA for
1sec.
Continuously adjustable selective instantaneous as high
as 30X the circuit breaker’s rating.
Stationary mounting capability with rear or front
Draw-out mounting with cassette and automatic shutter
Complete closed door operation capability – UL489,
Two-step stored energy mechanism for manual or
Remote racking device allowing maintenance personnel
3 and 4 pole configurations with the neutral on either
Suitable for UL1008 transfer switch applications
Alternate, settable and remote controllable
Industry’s only fully controllable ZSI restrained and
Industry’s only fully selective instantaneous trip with
Field installable accessories with labels that may be
Easily accessible terminal contacts at the top or side of
Advanced protection algorithms that allow maximum
Trip curves and algorithms to optimally accommodate
The EntelliGuard G family of overcurrent devices is available in 3 or 4 pole versions, in 3 physical sizes referred to as “envelopes” 1, 2 and 3. Four pole versions may have the neutral on the right- or left-most pole. The envelope and the number of poles are the main determinants for physical size and the space the device will require when installed in equipment or enclosures.
The circuit breakers and switches are further divided into “frame” sizes. The frame sizes follow the guidelines defined
connections.
mechanism.
ANSI or IEC.
electrically operated circuit breakers, suitable for fast throw-over or generator paralleling applications
to rack circuit breakers in and out while standing outside the arc flash boundary.
side.
instantaneous pickup with positive feedback.
unrestrained settings.
selectivity enhancing ZSI capability.
seen through the circuit breaker’s escutcheon.
circuit breaker for use by installer – permanently labeled, color coded and interlocked with harnesses for fast, efficient, mistake-proof wiring.
selectivity and protection at the same time with minimized need to sacrifice protection to get system reliability or visa versa.
downstream fuses, older slower power circuit breakers, ultra fast current limiting devices or other EntelliGuard circuit breakers without sacrificing any more protection than absolutely necessary to achieve significant selectivity.
©2012 General Electric All Rights Reserved
Page 80
DET-653C EntelliGuard® G Circuit Breaker Application Guide
74
Short Circuit Interrupting Ratings
Figure 6.1. Short Circuit Rating Adjustment Equation
Table 6.1. First Half-Cycle Peak at Specific Fault X/R Ratios (excerpted from UL489)

Power Factor

X/R ratio

Maximum Peak at 1/2
Cycle

17%
5.8

2.26

18%
5.5

2.23

19%
5.2

2.21

20%
4.9

2.18

100%

0.0

1.41

Withstand Ratings, Selective Waveform Recognition-, RELT- and Override-Instantaneous Protection

24-May-12 Section 6. Application Data
under the applicable UL, IEC and ANSI standards as shown in the various ratings tables. Switchgear equipment is typically sized to match the frame ratings and physical size. Switchboards may be sized to match the installed circuit breaker’s sensor rating.
Equipment cubicles or device mounting provisions are normally mechanically interlocked such that equivalent frames may be installed within a specific cubicle or space. When exchanging circuit breakers for maintenance purposes, care should be exercised so that there is no attempt to install a circuit breaker with a rating higher than what the equipment was designed to accommodate, even if the physical size seems similar.
The EntelliGuard G family of UL devices is available with short circuit ratings as high as 150kA at 480V, and withstand ratings as high as 100kA. UL1066 and ANSI C32 ratings are based on various tests performed at rated voltage plus 6%. Hence it is common to see low voltage circuit breakers listed as suitable for 254, 508 and 635V. Any UL 1066 listed device must be tested at these higher voltages if listed at the normal nominal voltage of 240, 480 and 600V. UL489 circuit breakers are tested at the nominal voltage. Both circuit breakers are subject to dielectric testing after interrupting faults to ensure the ability to sustain voltage.
Short circuit interrupting ratings are a measurement of the circuit breaker’s ability to interrupt a particular value of fault current at a maximum power factor (also expressed as X/R ratio). For fault currents above 20,000A RMS, UL489 circuit breakers are tested at 20% power factor and UL1066 circuit breakers are tested at 15% power factor. When fault currents have power factors lower (higher X/R) than the test power factor, the circuit breaker’s short circuit rating must be adjusted to compensate for the fault’s lower PF. The adjustment is performed as shown in Figure 6.1. Table 6.2 shows various asymmetrical peak ratios for various power factors and X/R ratios. A power factor of 100% yields a symmetrical fault and hence the peak over RMS ratio is 1.41.
CB’s Test Peak = Derate Ratio Fault Peak

5% 20.0 2.63 6% 16.6 2.59 7% 14.3 2.55 8% 12.5 2.52 9% 11.7 2.50

9% 11.1 2.49 10% 10.0 2.46 11% 9.0 2.42 12% 8.3 2.39 13% 7.6 2.36 14% 7.1 2.34 15% 6.6 2.31 16% 6.2 2.28

Consider a system where the fault current has an X/R ratio of 10 and the calculated RMS value is 92,000. A circuit breaker with a stated interrupting capability of 100,000 is being considered. Since the fault’s X/R ratio is higher than the UL489 rating at 4.9, the circuit breaker’s rating, 100kA, must be multiplied by 2.18/2.46 (from Table 6.1). The ratio is .89. Hence, the circuit breaker must be considered as if it is only rated for 89,000A. The UL489 100kA rated circuit breaker is not suitable for the application because its de­rated 89kA rating is below the available fault current of 92kA.
Consider an equivalent UL1066 circuit breaker tested at an X/R ratio of 6.6. The UL1066 circuit breaker must be de­rated by 2.31/2.46, which yields 0.94. The UL1066 circuit breaker is then de-rated to 0.94 times 100kA. The UL1066 circuit breaker is rated higher than the available fault current of 92kA and hence could be considered for the application.
Instantaneous adjustment capability for any circuit breaker is intrinsically connected to the circuit breaker’s withstand rating and the trip system’s sensing methods. In the case of the EntelliGuard G family of circuit breakers, high withstand ratings allow for a broad range of instantaneous trip options. The trip system relies on high accuracy air core sensors not encumbered by the saturation concerns associated with iron core sensors used in many other trip systems. This allows the
©2012 General Electric All Rights Reserved
Page 81
DET-653C EntelliGuard® G Circuit Breaker Application Guide
75

Close and Latch Ratings and Making Current Release (MCR) Instantaneous Trip

Table 6.2. EntelliGuard G Circuit Breaker Close and Latch Ratings, UL489 Listed

Envelope

Amps

Type

Close and Latch
Rating (kA)

1

800 - 2000

S, N, H, P

42

Table 6.3. EntelliGuard G Circuit Breaker Close and Latch Ratings, UL1066 Listed

Envelop
e

Amps

Type

Close and Latch
Rating (kA)

1

800 - 2000

S, N, H, P

42
2

800 - 3000

N, E, M

65

M, B

85
24-May-12 Section 6. Application Data
EntelliGuard trip system to take full advantage of the circuit breaker’s withstand rating, providing adjustable settings and full selectivity right up to the circuit breaker’s high withstand level. EntelliGuard G circuit breakers, in conjunction with EntelliGuard TU trip units with GE’s unique “selective instantaneous” algorithm, allow selectivity capability as high as 100kA with instantaneous on, and set at surprisingly low values. The EntelliGuard family of devices provides multiple solutions for your selectivity and protection problems.
Low Voltage Power Circuit Breakers (LVPCBs) listed to UL1066 have defined fault current withstand currents. EntelliGuard G UL489 Insulated Case Circuit Breakers also have substantial withstand ratings. The stated withstand current (Icw) allows the instantaneous protection of LVPCBs to be turned off or set at very high values, and it’s what allows the short time bands of both types of circuit breakers to be delayed as much as 0.5sec. EntelliGuard G UL1066 LVPCBs with EntelliGuard TU trip units are available with two different instantaneous adjustment ranges to take full advantage of this capability.
The standard instantaneous adjustment range is 2-15X, adjustable in 1/2X increments on all UL 489 and UL1066 circuit breakers. EntelliGuard TU trips offer, for UL1066 LVPCBs only, an extended Instantaneous adjustment range that allows the instantaneous pickup to be continuously adjusted up to 30X, adjustable in 1X increments above 15X the rating plug. The maximum adjustable pickup setting is limited to approximately 95% of the circuit breaker’s withstand rating, or 30X trip plug current rating, whichever is lower.
The EntelliGuard G’s wide range of instantaneous adjustability allows for maximum flexibility in providing the settings that are required for selectivity or for optimum protection. Its capability is limited by its withstand rating and the instantaneous override. An instantaneous override is used in some circuit breakers to ensure that, if a fault exceeds the circuit breakers withstand capability, the circuit breaker trips quickly. In all UL489 EntelliGuard circuit breakers, the override protection is designed such that selectivity up to 100% of the stated circuit breaker’s withstand rating is possible.
In UL1066 LVPCBs, maximum selective capability is achieved by using the adjustable instantaneous algorithm, even if it is set at maximum. When the adjustable instantaneous is enabled, regardless of setting, the override protection is set so that it will not trip for faults below the circuit breaker’s withstand rating. If the adjustable instantaneous is disabled (turned off), then the override automatically adjusts downward by approximately 9%. This lowers the maximum
selective capability to 91% of the circuit breaker’s withstand rating. The EntelliGuard G LVPCB may be selective up to the full withstand current with adjustable instantaneous on and 91% of withstand rating with adjustable instantaneous off.
The EntelliGuard TU trip unit also offers a second adjustable instantaneous trip called the Reduced Energy Let-Through (RELT) instantaneous pickup. This trip offers a faster algorithm suitable for application as alternate instantaneous pickup setting for temporary use when faster and more sensitive instantaneous protection is desired. The RELT setting is determined by the user and may be adjusted from
1.5X to 15X rating plug. Once set, the RELT function may be enabled or disabled locally at the trip unit or remotely via a 24Vac/dc signal, or serial communications.
When the trip unit receives a RELT enable command, it issues a feedback signal indicating the RELT setting is now active. The user may connect the RELT enable input to any 24Vac/dc source, such as a manual switch, automatic sensor, or both. The feedback signal may be connected to any desired signaling means with the proper ratings. For further details see Section 3 of this application guide.
EntelliGuard G circuit breakers have defined close and latch ratings as shown in Tables 6.2 through 6.4. The close and latch rating is a measurement of the circuit breaker’s ability to close and latch closed on a fault. This value must be high enough to allow a circuit breaker to handle large transient inrush currents associated with certain types of loads, such as energy efficient motors or large capacitor banks.

2 800 - 3000 N, H, M 65

3 4000 - 6000

M 85
L 100

3 4000 - 6000

L 100
©2012 General Electric All Rights Reserved
Page 82
DET-653C EntelliGuard® G Circuit Breaker Application Guide
76

Table 6.4. EntelliGuard G Non-Automatic Switch Close, Latch, and Withstand Ratings, UL489 Listed

Envelope

Amps

Type

Close and Latch
Rating (kA)

1

800 - 2000

N
42

Operations

Table 6.5. Operational Ratings, UL 489 Circuit Breakers

Envelope

Frame

Mechanical
Operations

Electrical
Operations
at 508V

Electrical
Operations
at 635V

800-1600A

12500

10000

7500

2000A

12500

7500

5000 2 800A

12500

5000

5000

1600-3000A

5000

5000

5000

3000-4000A

5000

3000

2000 3 5000A

5000

2000

1500

6000A

5000

1500

1000

Table 6.6. Operational Ratings, UL1066/ANSI Circuit Breakers

Envelope

Frame

Mechanical
Operations

Electrical
Operations
at 508V

Electrical
Operations
at 635V

800-1600A

12500

10000

7500

2000A

12500

7500

5000 2 800A

12500

5000

5000

1600-3200A

5000

5000

5000

3200- 4000A

5000

3000

2000

5000A

5000

2000

1500

Selecting a Circuit Breaker for an Application
CR = IA x A x B x C x D x E x F
Cable or Bus Size – Factor A
24-May-12 Section 6. Application Data

2 800-3000 M 65 3 4000 - 6000 B 100

EntelliGuard G circuit breakers are provided with values that are high relative to the circuit breaker’s load carrying capacity. The trip system provides a type of instantaneous protection called a Making Current Release (MCR) to provide more sensitive protection when closing. Should the trip system measure higher current than the MCR setting, it is very likely that the circuit breaker has been closed on a bolted fault, or low impedance, arcing fault. If that is the case, the MCR instantaneous will provide very fast protection, minimizing damage and hazard.
EntelliGuard G circuit breakers are designed to provide long life, even in operationally difficult environments. However, different standards have different ways of measuring and qualifying circuit breaker operations, hence slightly different numbers may apply to similar circuit breakers when defined within the context of different standards. Tables 6.5 and 6.6 describe the endurance parameters for the circuit breaker family.
1
1
3

Per industry standards, operations are listed based on no maintenance during the testing. However, if some maintenance is done of some of the current carrying parts and arc chute, then over 20,000 electrical and mechanical operations are possible.

There are six application factors to consider in selecting current rating for a circuit breaker. These are:

1. Size of the cable or bus used in the line and load
connections.

2. Actual installed ambient temperature.

3. System operating frequency.

4. Altitude of the installation.

5. Type of loading of the protected circuit.

6. Design safety factor.

The following simple relationship combines these six application factors into a single equation:
CR Required circuit breaker current rating, amps IA Actual load current, amps A Cable or bus sizing factor B Ambient temperature rating factor C Frequency rating factor D Altitude rating factor E Load class rating factor F Safety factor
The thermal design of a circuit breaker takes into account the ability of the line and load cables or buses to act as heat sinks. For UL489 Listed circuit breakers, UL has assigned specific cable or bus sizes for each current rating. Generally, these assignments are coordinated with specific conductor temperature ratings. When using a conductor with an increased temperature rating, the higher rating decreases both the cross-sectional area and its ability to conduct heat from the circuit breaker. If an
©2012 General Electric All Rights Reserved
Page 83
DET-653C EntelliGuard® G Circuit Breaker Application Guide
77
Ambient Temperature – Factor B

Table 6.7. Ambient Temperature Rating - Factor B

Ambient
Temperature, °C 1

Maximum Wire
Insulating Rating °C 2

Factor B

25
75
1
50
105
1
60
125
1.1
70
125

1.15

Operating Frequency – Factor C
Altitude – Factor “D”

Table 6.8. Altitude Rating – Factor D

Altitude

Factor D

Feet

Meters

100 - 6,000

30 - 1,800

1

6,001 - 10,000

1,801 - 3,000

1.04

>10,001

>3,001

1.08

Load Class Rating – Factor E

24-May-12 Section 6. Application Data
EntelliGuard G circuit breaker is used with cables directly connected, contact your GE application engineer for information to ensure proper cabling information. Cable with insulation ratings above 75°C may be used, providing it is sized to 75°C ampacity per the NEC or other applicable codes.
Ambient temperatures have a wide effect on the rating of the breaker-cable system. While the internal sensing and tripping circuitry in EntelliGuard TU trip units are ambient insensitive, high-ambient temperatures may cause internal components to exceed operating temperature limits. Low temperatures substantially increase the current-carrying capabilities of the breaker-cable system until other limiting factors occur (e.g., lubrication problems or mechanical binding of internal parts due to differential contraction). The ambient temperature around an EntelliGuard G breaker should not be less than -20°C nor exceed 70°C.
Ambient temperature always refers to the temperature of the air immediately surrounding the breaker and not the temperature of the air outside the breaker’s enclosure. Room or outside air temperatures only establish the thermal floor to which all other heating is added. To convert breaker ambient from room ambient, it is necessary to know the temperature rise within the equipment housing the breaker. Temperature rise is a function of several variables, including heating caused by other equipment, ventilation, solar heating, factors relating to group mounting and the free surface area of the breaker’s enclosure. Once the device’s ambient temperature is determined, select Factor B from Table 6.7.
40 90 1

1 Average air temperature over a 24-hour period outside the breaker’s insulated case, but inside the enclosure. 2 Cable (wire) must be based on 75°C current rating per Table 3 10-16, current National Electrical Code.

All UL EntelliGuard circuit breakers may be applied at their published ratings on 50Hz and 60Hz power systems. At nominal system frequencies less than 50Hz but above direct current, digital solid-state trip may become inaccurate. On direct current systems, digital solid-state
trip units are completely inoperative. EntelliGuard G circuit breakers may be used on DC applications, but EntelliGuard TU trip units may not.

System operating frequencies above 60Hz may change the performance and ratings of circuit breakers by heating metallic parts and significantly reducing interrupting capacity. EntelliGuard TU trip units are not suitable for applications at 400Hz.

For operating frequencies of both 50Hz and 60Hz, the operating frequency rating Factor C = 1.00. For operating frequencies other than 50Hz and 60Hz, contact your GE applications engineer.

EntelliGuard G UL circuit breakers are designed for operation at altitudes from sea level to 6000ft (1800m). Reduced air densities at altitudes above 6000ft affect the ability of the circuit breaker to both transfer heat and interrupt short circuits. Determine the altitude of the breaker’s installation, and select the altitude rating - factor D from Table 6.8.
The type of load and its duty cycle must be considered in the application of EntelliGuard G circuit breakers. Loads such as capacitors and electromagnets require a substantial and continuous de-rating factor if the breaker is normally used to switch the load. With loads such as resistance welders, the breaker’s continuous current rating must be no less than 125% of the welder’s 100% duty­cycle rating.
In general, circuit breakers are intended for the protection of insulated cable. Where a circuit breaker is intended to protect load equipment, prudent engineering practices call for obtaining factory review and concurrence with the selection of a specific protective device. Load class selection Factor E for typical applications are listed in Table 6.9.
©2012 General Electric All Rights Reserved
Page 84
DET-653C EntelliGuard® G Circuit Breaker Application Guide
78
Table 6.9. Load Class Rating – Factor E

Load Type

Factor E

Single Motor Branch Circuit Protection (Normal Duty)*

Single Motor Branch Circuit Protection (Heavy Duty)*

Safety – Factor F

Other Factors that Influence Circuit Breaker Sizing 100% vs. 80% Ratings

Table 6.10. Circuit Breaker and Trip Parameters

Adjustment or Capability

Abbreviation

Trip Designation

Setting or Range

Short Time Pickup

STPU

STPU

1.5X - 12X of the LTPU

24-May-12 Section 6. Application Data

Switching Electromagnets 1.5

1.5

Switching Capacitors 1.5

1.75

All Other load Types (Normal Duty) 1

*Use this factor to either plugging duty or starting more than 25 times per hour, where the rms current cannot be easily calculated.
A safety factor is used to provide a design margin between the rating of a circuit breaker and the derived operating current using all of the applicable selection factors. A safety factor of at least 10% is often used to ensure the circuit breaker is adequately sized. In addition it may be useful to consider future growth.
All EntelliGuard G circuit breakers are 100% rated except for the 6000A stationary mounted UL 489 circuit breaker. Circuit breakers that are 100% rated are not required to be sized at 125% of the expected load. However, it is recommended that a safety factor, as described above, always be considered when selecting overcurrent device sizes.
An important consideration may be the circuit breaker’s desired selective and protection performance within the context of the system where it is installed. Certain settings are functions of the trip plugs, others of the sensors. In Table 3.14 you will find the sensors available on a per frame basis. Table 3.12 identifies the trip rating plugs available for each sensor. Table 6.10 identifies the relationship between specific circuit breakers and trip parameters.

Trip Current Rating Plug In In ~37.5-100% of sensor Long Time Pickup LTPU LTPU Plug x pickup setting

Instantaneous Pickup IPU I 2X -15 or 30X of the trip current rating plug Maximum Achievable Selectivity = Icw N/A Function of the withstand rating Ground Fault Pickup GF GF 20-60% sensor, <1200A Override Pickup HSIOC N/A Function of the withstand rating Making Current Release MCR N/A Function of the close and latch rating

©2012 General Electric All Rights Reserved
Page 85
DET-653C EntelliGuard® Circuit Breaker
79
EntelliGuard® G Power Circuit Breaker Section 7. Physical Data

Dimensions and Weights

Figure 7.1. Sample Dimensional Drawing

24-May-12 Section 7. Physical Data

To download detailed dimensional drawings like those shown in Figure 7.1, visit www.geindustrial.com.

©2012 General Electric All Rights Reserved
Page 86
DET-653C EntelliGuard® G Circuit Breaker Application Guide
80

Table 7.1 provides an index of drawings.

Table 7.1. Drawing Index

Description

Mounting Location of Secondary Disconnect

Assembly #

400 - 1600A, Type N & H, 3-pole, draw-out, ANSI/UL

Side

10101387

400 - 1600A, Type E & M, 3-pole, draw-out, ANSI/UL

Top

10101422

2000A, Type N & H, 3-pole, draw-out, ANSI/UL

Side

10101388

2000A, Type E & M, 3-pole, draw-out, ANSI/UL

Top

10101391

2500 - 3200A, Type N, E & M, 3-pole, draw-out, ANSI

Top

10101393

2500 - 3000A, Type N, H & M, 3-pole, draw-out, UL

Top

10101392

3000 - 6000A, Type B, M & L, 3-pole, draw-out, ANSI/UL

Top

10101397

400 - 1600A, Type N & H, 3-pole, fixed, ANSI/UL

Top

10101389

400 - 2000A, Type E & M, 3-pole, fixed, ANSI/UL

Top

10101394

2000A, Type N & H, 3-pole, fixed, ANSI/UL

Top

10101390

2500 - 3200A, Type N, E & M, 3-pole, fixed, ANSI

Top

10101396

2500 - 3000A, Type N, H & M, 3-pole, fixed, UL

Top

10101395

3000 - 4000A, Type B, M & L, 3-pole, fixed, ANSI/UL

Top

10101399

5000 - 6000A, Type M, B & L, 3-pole, fixed, ANSI/UL

Top

10101398

400 - 2000A, Type N & H, 3-pole, front access, UL

Top

10101452

3000A, Type E & M, 3-pole, front access, UL

Top

10101453

6000A, Type B & L, 3-pole, front access, UL

Top

10101454

400 - 1600A, Type N & H, 4-pole, draw-out, ANSI/UL

Side

10101456

400 - 1600A, Type E & M, 4-pole, draw-out, ANSI/UL

Top

10101471

2000A, Type N & H, 4-pole, draw-out, ANSI/UL

Side

10101457

2000A, Type E & M, 4-pole, draw-out, ANSI/UL

Top

10101462

2500 - 3200A, Type N, E & M, 4-pole, draw-out, ANSI

Top

10101464

2500 - 3000A, Type N, H & M, 4-pole, draw-out, UL

Top

10101463

3000 - 6000A, Type B, M & L, 4-pole, draw-out, ANSI/UL

Top

10101458

400 - 1600A, Type N & H, 4-pole, fixed, ANSI/UL

Top

10101460

400 - 2000A, Type E & M, 4-pole, fixed, ANSI/UL

Top

10101465

2000A, Type N & H, 4-pole, fixed, ANSI/UL

Top

10101461

2500 - 3200A, Type N, E & M, 4-pole, fixed, ANSI

Top

10101467

2500 - 3000A, Type N, H & M, 4-pole, fixed, UL

Top

10101466

3000 - 4000A, Type B, M & L, 4-pole, fixed, ANSI/UL

Top

10101468

5000 - 6000A, Type M, B & L, 4-pole, fixed, ANSI/UL

Top

10101469

400 - 2000A, Type N & H, 4-pole, front access, UL

Top

10101474

3000A, Type E & M, 4-pole, front access, UL

Top

10101475

6000A, Type B & L, 4-pole, front access, UL

Top

10101476

Door Cutout Detail for a Fixed Breaker

n/a

10101498

Door Cutout Detail for a Drawout Breaker

n/a

10101499

400 - 1600A, Type N & H, 3-pole, draw-out, ANSI/UL, Top Mounted Secondary Disconnects

Top
10101848 Mounted Secondary Disconnects

400 - 1600A, Type N & H, 4-pole, draw-out, ANSI/UL, Top Mounted Secondary Disconnects

Top
10101850 Mounted Secondary Disconnects
24-May-12 Section 7. Physical Data
2000A, Type N & H, 3-pole, draw-out, ANSI/UL, Top
2000A, Type N & H, 4-pole, draw-out, ANSI/UL, Top
Note: For latest drawings (including those for Type S and P), visit www.geindustrial.com
©2012 General Electric All Rights Reserved

Top 10101849

Top 10101851

Page 87
DET-653C EntelliGuard® G Circuit Breaker Application Guide
81
Table 7.2. 3-pole, UL/ANSI

Type

Design

Width

Depth

Height

Weight

in.
mm
in.
mm
in.
mm

lbs.

kg

Fixed breaker – back connected

13.50

343

17.17

436

17.40

442

136.7

62

Drawout breaker - Moving portion

13.07

332

16.34

415

17.24

438

149.9

68

Cassette/substructure

13.50

343

20.83

529

17.44

443

110.2

50

Fixed breaker – back connected

16.14

410

17.17

436

15.98

406

136.7

62

Drawout breaker - Moving portion

15.35

390

16.34

415

15.83

402

149.9

68

Cassette/substructure

15.83

402

20.83

529

15.98

406

110.2

50

Fixed breaker – back connected

17.17

436

17.17

436

17.40

442

165.3

75

Drawout breaker - Moving portion

17.01

432

16.34

415

17.24

438

176.4

80

Cassette/substructure

17.44

443

20.83

529

17.44

443

114.6

52

Fixed breaker – back connected

17.17

436

22.17

563

17.40

442

253.5

115

Drawout breaker - Moving portion

17.01

432

16.34

415

17.24

438

209.4

95

Cassette/substructure

17.44

443

26.14

664

17.44

443

231.5

105

Fixed breaker – back connected

17.17

436

22.17

563

17.40

442

275.6

125

Drawout breaker - Moving portion

17.01

432

16.34

415

17.24

438

209.4

95

Cassette/substructure

17.44

443

26.14

664

17.44

443

246.9

112

Envelope 3, Up to 4000A, ANSI/UL

Fixed breaker – back connected

28.98

736

17.17

436

17.40

442

286.6

130

Envelope 3, Up to 5000A ANSI/6000A UL

Fixed breaker – back connected

28.98

736

22.17

563

17.40

442

463.0

210

Drawout breaker - Moving portion

28.82

732

16.34

415

17.24

438

330.7

150

Cassette/substructure

29.25

743

26.14

664

17.44

443

396.8

180
Table 7.3. 4-pole, UL/ANSI

Type

Design

Width

Depth

Height

Weight

in.
mm
in.
mm
in.
mm

lbs.

kg

Fixed breaker – back connected

17.44

443

17.17

436

17.40

442

180.8

82

Drawout breaker - Moving portion

17.01

432

16.34

415

17.24

438

198.4

90

Cassette/substructure

17.44

443

20.83

529

17.44

443

143.3

65

Fixed breaker – back connected

20.08

510

17.17

436

15.98

406

180.8

82

Drawout breaker - Moving portion

19.29

490

16.34

415

15.83

402

198.4

90

Cassette/substructure

19.76

502

20.83

529

15.98

406

143.3

65

Fixed breaker – back connected

22.28

566

17.17

436

17.40

442

220.5

100

Drawout breaker - Moving portion

22.13

562

16.34

415

17.24

438

242.5

110

Cassette/substructure

22.56

573

20.83

529

17.44

443

154.3

70

Fixed breaker – back connected

22.28

566

22.17

563

17.40

442

330.7

150

Drawout breaker - Moving portion

22.13

562

16.34

415

17.24

438

275.6

125

Cassette/substructure

22.56

573

26.14

664

17.44

443

308.6

140

Fixed breaker – back connected

22.28

566

22.17

563

17.40

442

363.8

165

Drawout breaker - Moving portion

22.13

562

16.34

415

17.24

438

275.6

125

Cassette/substructure

22.56

573

26.14

664

17.44

443

330.7

150

Envelope 3, Up to 4000A, ANSI/UL

Fixed breaker – back connected

38.03

966

22.17

563

17.40

442

385.8

175

Envelope 3, Up to 5000A ANSI/6000A UL

Fixed breaker – back connected

38.03

966

22.17

563

17.40

442

617.3

280

Drawout breaker - Moving portion

37.87

962

16.34

415

17.24

438

440.9

200

Cassette/substructure

38.31

973

26.14

664

17.44

443

529.1

240
24-May-12 Section 7. Physical Data
Dimensions & Weights

Envelope 1, Top Mounted, UL/ANSI

Envelope 1, Side Mounted, UL/ANSI

Envelope 2, Up to 2000A, UL/ANSI

Envelope 2, Up to 3000A, UL

Envelope 2, Up to 3200A, ANSI

Envelope 3, All Ratings

Envelope 1, Top Mounted, UL/ANSI

Envelope 1, Side Mounted, UL/ANSI

Envelope 2, Up to 2000A, UL/ANSI

Envelope 2, Up to 3000A, UL

Envelope 2, Up to 3200A, ANSI

Envelope 3, All Ratings

©2012 General Electric All Rights Reserved
Page 88
DET-653C EntelliGuard® G Circuit Breaker Application Guide
82
EntelliGuard® G Power Circuit Breaker Section 8. Standards and References
Underwriters Laboratories® (UL)
National Electrical Manufactures Association (NEMA)
Canadian Standards Association (CSA)
Institute of Electrical and Electronics Engineers (IEEE)
American National Standard Institute (ANSI)
24-May-12 Section 7. Physical Data
UL 489 and UL 489-SB2 - Standard for Molded Case Circuit Breakers and Circuit Breaker Enclosures UL 1066 - Standard for Safety Low-Voltage AC and DC Power Circuit Breakers Used in Enclosures
Order from: UL Publication Stock 333 Pfingsten Road Northbrook, IL 60062 USA
AB-1/2002 Standards Publication - Molded Case Circuit Breakers and Molded Case Switches SG3/1995 - Standards and Ratings for the Application of Low-Voltage Power Circuit Breakers SG5/1995 – Power Switchgear Assemblies
Order from: NEMA Publication 155 East 44th Street New York, NY 10017 USA
CSA 22.2 NO 5.1 – Standards for Branch Circuit Protection
Order from: Canadian Standards Association 178 Rexdale Blvd. Rexdale, Ontario, Canada M9WR3
IEEE 693 – Recommended Practices for Seismic Design of Substations
Order from: IEEE 345 East 47th Street, New York, NY 10017 USA
ANSI C37.13/1990 - Low-Voltage AC Power Circuit Breaker Used in Enclosures (600-Volt Insulation Class) ANSI C37.16/2000 - Recommendations for Low Voltage Power Circuit Breakers and AC Power Circuit Protectors, Preferred Ratings, Related Requirements, and Application ANSI C37.17/1990 - American National Standard for Trip Devices for AC and General Purpose DC Low Voltage Power Circuit Breakers ANSI C37.20.1/2000 - Metal-Enclosed Low-Voltage Power Circuit Breaker Switchgear ANSI C37.50/1989 (R1995) – Test Procedures for Low­Voltage AC Power Circuit Breakers Used in Enclosures ANSI/IEEE C37.90.1/1993 - IEEE Standard Surge Withstand Capability (SWC) Tests for Protective Relays and Relay Systems ANSI/IEEE C37.90.2/1993 - Withstand Capability of Relay Systems to Radiated Electromagnetic Interference from Transceiver
Order from: ANSI 11 West 42nd Street, New York, NY 10036 USA
©2012 General Electric All Rights Reserved
Page 89
DET-653C EntelliGuard® G Circuit Breaker Application Guide
83
International Electrotechnical Committee (IEC)
National Electrical Code®
American Society for Testing and Materials (ASTM)
Military Standard (MIL-STD)
Seismic Qualifications to All Major Building Code Standards
Other
American Society for Testing and Materials (ASTM)
Military Standard (MIL-STD)
24-May-12 Section 8. Standards and References
IEC 60947-1 (Ed. 4/2004) - Electrical Equipment for Low Voltage, High Power Switching Equipment (Also applies to Electromagnetic Compatibility
IEC 60947-2 (Ed. 4/2006) - Electrical Equipment for Low Voltage, High Power Switching Equipment (Also applies to Electromagnetic Compatibility
IEC 60947-3 (Ed. 4, Am 1, Am 2/2002) - Electrical equipment for Low voltage, high power switching equipment (Also applies to Electromagnetic Compatibility IEC 68-2-1 (Am 1/1993) – Environmental Testing Standards/Dry Cold at –55°C Operational Temperature IEC 68-2-2 (Am 1/1993) – Environmental Testing Standards/Dry Heat at +85°C Operational Temperature IEC 68-2-30 - (Am 1/1985) – Environmental Testing Standards/Operational Temperature and Humidity (temp. +55°C, rel. humidity 95%) IEC 68-2-52 Level 2 - (Am 1/1996) – Environmental Testing Standards/Salt Mist-Corrosion IEC 801-2 2nd Edition 1991-04 - Electromagnetic Compatibility for Industrial-Process, Measurement and Control Equipments Part 2: Electrostatic Discharge Requirements
Order from: Bureau Central de la Commission Electrotechnique Internationale 3 rue de Varamb’e Geneve, SUISSE
Order from: National Fire Protection Association Batterymarch Park Quincy, MA 02269 USA
ASTM B117-73 (Reapproved 1979) Standard Method of Salt Spray (Fog) Testing
Order from: ASTM 1916 Race Street Philadelphia, PA 19103 USA
MIL-STD-810E - Environmental Test Methods and Engineering Guidelines
Order from: Defense Printing Service 700 Robbins Avenue, Bldg. 4D Philadelphia, PA 19111-5094 USA
IBC - International Building Code UBC - Uniform Building Code BOCA – Building Officials and Code Administrators CBC – California Building Code SBC – Standard Building Code
IEC Environmental: 68-2-1,-2,-3,-6,-11,-14,-14,-27,-29,-30,­31 IEC Environmental: 721 Lloyds Register of Shipping, Germanischer Lloyds, ABS (American Bureau of Shipping) European ROHS Directives GE Consumer & Industrial Engineering Test Procedures (ETPs) and Standing Instructions (S.I.s) Standing Instructions (S .I .s): S.I. 900001S001 - Program Technical Review Discipline
ASTM B117-73 (Reapproved 1979) Standard Method of Salt Spray (Fog) Testing
Order from: ASTM 1916 Race Street Philadelphia, PA 19103 USA
MIL-STD-810E - Environmental Test Methods and Engineering Guidelines
Order from: Defense Printing Service 700 Robbins Avenue, Bldg. 4D Philadelphia, PA 19111-5094 USA
©2012 General Electric All Rights Reserved
Page 90
DET-653C EntelliGuard® G Circuit Breaker Application Guide
84
Seismic Qualifications to All Major Building Code Standards
Other
24-May-12 Section 8. Standards and References
IBC - International Building Code UBC - Uniform Building Code BOCA – Building Officials and Code Administrators CBC – California Building Code SBC – Standard Building Code
IEC Environmental: 68-2-1,-2,-3,-6,-11,-14,-14,-27,-29,-30,­31 IEC Environmental: 721 Lloyds Register of Shipping, Germanischer Lloyds, ABS (American Bureau of Shipping) European ROHS Directives GE Consumer & Industrial Engineering Test Procedures (ETPs) and Standing Instructions (S.I.s) Standing Instructions (S .I .s): S.I. 900001S001 - Program Technical Review Discipline
©2012 General Electric All Rights Reserved
Page 91
DET-653C EntelliGuard® G Circuit Breaker Application Guide
85

EntelliGuard® G Publications

www.geelectrical.com
Publications
Pub #

EntelliGuard® G IOM

DEH-41304

Time Current Curves: EntelliGuard® TU Trip Unit for EntelliGuard® G; Long-Time Circuit Breaker Characteristics

Characteristics

Time Current Curves: EntelliGuard® TU Trip Unit for EntelliGuard® G; Short-Time Pickup and Delay Bands

Time Current Curves: EntelliGuard® TU Trip Unit for EntelliGuard® G; Ground Fault

DES-093

Time Current Curves: EntelliGuard® TU Trip Unit for EntelliGuard® G; Instantaneous, Override (HSIOC), Reduced Energy Let-Through Instantaneous (RELT)

UL Component Recognized Series Connected Ratings and CSA Certified Series Rated Combinations

Undervoltage Release User Manual

DEH-41361

Time Delay Module User Manual

DEH-41362

Closing Coil User Manual

DEH-41363

Motor Operator User Manual

DEH-41366

Electrical Close Switch

DEH-41374

Spring Charge Contact

DEH-41375

Castell Lock Kit

DEH-41376

Door Interlock User Manual

DEH-41377

Cassette Ronis Lock User Manual

DEH-41380

Contact Wear Indicator User Manual

DEH-41382

Wall Mounting Kit

DEH-41383

IP54 Door

DEH-41384

Escutcheon Kit

DEH-41386

Arcing Contacts Assembly

DEH-41390

Racking Handle

DEH-41392

Cluster Contacts User Manual

DEH-41394

Cluster Pliers Assembly

DEH-41395

Secondary Disconnects - Drawout

DEH-41401

CT Mounting for External Ground Fault

DEH-41402

Position Switch Kit

DEH-41403

Back Connected Terminations

DEH-41404

Front Connected Terminations

DEH-41405

Time Delay Module

DEH-41406

Key Interlock Kit - Breaker Mounted

DEH-41407

Door Interlock Kit

DEH-41408

Bell Alarm w/ Lockout

DEH-41409

Undervoltage Device

DEH-41410

Shunt Trip

DEH-41411

Remote Close Accessory Close Coil

DEH-41412

Motor Operator

DEH-41413

Pushbutton Padlock Device

DEH-41414

Aux Switch

DEH-41415

Operations Counter

DEH-41416

Secondary Disconnects - Fixed

DEH-41417

Command Close Coil

DEH-41418

Ready To Close (RTC)

DEH-41419

Coil Signaling Contacts

DEH-41420

Continued on next page

24-May-12 Section 8. Standards and References
To download publications like those shown below, visit
Time Current Curves: EntelliGuard® TU Trip Unit for EntelliGuard® G; Long-Time Fuse-Like
.

DES-090

DES-091

DES-092

DES-094

DET-008

©2012 General Electric All Rights Reserved
Page 92
DET-653C EntelliGuard® G Circuit Breaker Application Guide
86
Publications
Pub #

DEH-41430

DEH-41431

DEH-41433

DEH-41434

DEH-41437

DEH-41439

DEH-41440

DEH-41441

DEH-41442

DEH-41443

DEH-41444

DEH-41445

Contact Wear Indicator

DEH-41446

DEH-41447

DEH-41448

DEH-41449

DEH-41450

Mechanical Interlocks (Fixed)

DEH-41451

Mechanical Interlocks (Drawout)

DEH-41455

Cassette Interlock User Manual

DEH-41459

Clusters

DEH-41460

Network Interlock Device ( NI)

DEH-41461

Flat Front Termination ANSI/UL

DEH-41463

Remote Racking Operator

DEH-41467

Key Interlock Casste Mounted

DEH-41500

CVCB Coil Signal Status

DEH-41517

Neutral Sensor Kit – Rogowski

DEH-41387

24 Vdc Power Supply

GEH-6492

Arc Chute Kit

DEH-41389

Earthing Device Kit

DEH-41379

EntelliGuard TU Rating Plugs

DEH-41318

EntelliGuard TU Test Kit

DEH-4568

EntelliGuard TU Trip Unit IOM

DEH-4567

24-May-12 Section 8. Standards and References

Back Connected Terminations for Cassette

Back Connected Terminations for Cassette

Cluster pad Assembly

©2012 General Electric All Rights Reserved
Page 93
DET-653C EntelliGuard® G Circuit Breaker Application Guide
87

NOTES:

24-May-12 Section 8. Standards and References
©2012 General Electric All Rights Reserved
Page 94
EntelliGuard, WavePro and PowerBreak are registered trademarks of the General Electric Company.
GE Energy 41 Woodford Avenue Plainville, CT 06062
www.geindustrial.com
imagination at work
DET-653C (05/12)
Loading...