D485 Modbus to DeviceNet Converter Instruction Manual.
D485 is a registered trademark of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be
reproduced in whole or in part without the permission of GE Multilin Inc. The content of this manual is for informational use
only and is subject to change without notice.
Part numbers contained in this manual are subject to change without notice, and should therefore be verified by GE
Multilin Inc. before ordering.
General features..........................................................................................................................................1–3
Order codes....................................................................................................................................................1–4
Power connector .........................................................................................................................................2–4
Indicators and switches ........................................................................................2–5
Status indicators..........................................................................................................................................2–5
I/O data vs. explicit data..........................................................................................................................3–3
System requirements................................................................................................................................ 4–1
Information window ............................................................................................................................... 4–10
Configuration line indicator ................................................................................................................ 4–10
Example ...........................................................................................................................................................6–1
Control register (DeviceNet control system to D485).................................................................8–1
Control codes ................................................................................................................................................8–2
Status register (D485 to fieldbus control system) ........................................................................8–2
Status codes ..................................................................................................................................................8–3
Equipment and documents.................................................................................................................... 9–1
System setup ................................................................................................................................................ 9–2
Modbus user map setup ........................................................................................9–3
PQMII user map ........................................................................................................................................... 9–3
MM2 user map .............................................................................................................................................9–3
System configuration.............................................................................................9–5
GE Multilin warranty statement ........................................................................................................ 10–1
INDEX
ivD485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
GE
Grid Solutions
D485 Modbus to DeviceNet
Converter
Chapter 1: Introduction
Introduction
Getting started
INSPECTING THE
PACKAGE AND PRODUCT
CONTACT INFORMATIONFor product support, contact the information and call center as follows:
Examine the shipping container for obvious damage prior to installing this product; notify
the carrier of any damage that you believe occurred during shipment or delivery. Inspect
the contents of this package for any signs of damage and ensure that the items listed
below are included.
Remove the items from the shipping container. Be sure to keep the shipping container
should you need to re-ship the unit at a later date.
In the event there are items missing or damaged, contact the party from whom you
purchased the product. If the unit needs to be returned, please use the original shipping
container, if possible.
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE1–1
INTRODUCTION
DeviceNet
master
Slave
GE Multilin
D485 Converter
Slave
Modbus
network
DeviceNet network
OUT
IN
OUT
IN
Document conventions
DESCRIPTIONThe following conventions are used throughout this document:
•Numbered lists provide sequential steps.
•Bulleted lists provide information, not procedural steps.
•The term ‘user’ refers to the person or persons responsible for installing the D485
Modbus to DeviceNet Converter in a network.
•Hexadecimal values are written in the format 0xNNNN, where NNNN is the
hexadecimal value.
•Decimal values are represented as NNNN, where NNNN is the decimal value.
•As in all communication systems, the terms “input” and “output” can be ambiguous,
since their meaning depends on which end of the link is being referenced. The
convention in this document is that “input” and “output” are always being referenced
to the master/scanner end of the link (see illustration below).
•The term “sub-network” is interchangeably used for “Modbus network”.
Figure 1-1: Input and output definition
GLOSSARYThe following terminology is used in the D485 manual:
•Broadcaster: A protocol specific node in the sub-network scan that holds transactions
destined for all nodes.
•Command: A protocol specific transaction.
•Fieldbus: The network to which the converter is connected (DeviceNet for D485).
•Frame: A higher level series of bytes forming a complete telegram on the sub-network
(Modbus).
•Monitor: A tool for debugging the D485 and network connections.
•Node: A device in the scan list that defines the communication with a slave (GE relay)
on the Modbus sub-network.
•Scan list: List of configured slaves with transactions on the sub-network.
•Sub-network: Modbus network that logically is located on a subsidiary level with
respect to the fieldbus and to which the D485 acts as a gateway.
•Transaction: A generic building block that is used in the sub-network scan list and
1–2D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
defines the data that is sent out the sub-network.
INTRODUCTION
DeviceNet
master (PLC)
HMI
DeviceNet
slave
DeviceNet network
D485
PC for configuration
and monitoring
Multi-drop
Multi-node Modbus network
Single-node Modbus network
RS232 port
PC for configuration
and monitoring
DeviceNet slave
HMI
DeviceNet
master (PLC)
DeviceNet network
D485
About the D485 Modbus to DeviceNet Converter
APPLICATIONThe D485 Modbus to DeviceNet Converter (or D485) acts as a gateway between the
Modbus protocol and a DeviceNet network. Integration of industrial devices is enabled
without loss of functionality, control, and reliability, both when retrofitting to existing
equipment as well as when setting up new installations.
Figure 1-2: Typical applications
Features
GENERAL FEATURES•DIN-rail mountable
•Save/load configuration in flash
•CE, UL, and cUL marked
MODBUS NETWORK•RS232/RS422/RS485 communications
•Multi-drop or single-node configurations possible
•Modbus RTU Master mode
DEVICENET INTERFACE
FEATURES
•Supports up to 50 commands
•Configuration via EnerVista P485/D485 Setup software
•Complete DeviceNet adapter functionality (profile no. 12 group 2 only server)
•Group two only server
•MAC ID and baud rate configuration via on-board switches
•Polled, Change of State (COS), and Bit Strobed I/O
•Explicit messaging
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE1–3
INTRODUCTION
ORDER CODESThe following table illustrates the order codes for the D485 Modbus to DeviceNet
Ordering
Converter.
Table 1–1: D485 order codes
D485 – *
Base unitD485|D485 Modbus to DeviceNet Converter
CWith configuration cable
XNo configuration cable
Specifications
MECHANICALHOUSING
Plastic housing with snap-on connection to DIN-rail, protection class IP20
DIMENSIONS
L x W x H:120 mm × 75 mm × 27 mm
(4.72-in × 2.95-in × 1.06-in)
PROTECTION CLASS
Protection class:IP20
ELECTRICAL
CHARACTERISTICS
POWER SUPPLY
Power:24 V ±10% (for use in class 2 circuits)
POWER CONSUMPTION
Maximum power consumption: 280 mA on 24 V
Typically power consumption: approximately 100 mA
COMMUNICATIONSBAUD RATES
Baud rate (DeviceNet)125, 250, and 500 kbps
Baud rate (Modbus)1200, 2400, 4800, 9600, 19200, 38400, and 57600 bps
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE2–3
INSTALLATION
51
69
(female)
51
69
(female)
NOTE
12
Figure 2-5: Configuration cable (PC end)
MODBUS CONNECTORThe Modbus connector is indicated as C in Figure 2-1: D485 electrical connections on page
2–2. This connector is used to connect the D485 to the serial network. Based on the
configuration selected in the EnerVista P485/D485 Setup software, the corresponding
signals are activated.
Figure 2-6: Modbus connector
Table 2–4: Modbus connector pin assignments
PinDescriptionRS232RS422RS485
1+5V output (50mA max)
2RS232 Rx
3RS232 Tx
4Not connected
5Ground
6RS422 Rx +
7RS422 Rx –
8RS485 + / RS422 Tx+
9RS485 – / RS422 Tx–
POWER CONNECTORThe power connector is indicated as D in Figure 2-1: D485 electrical connections on page
2–4D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
2–2. Use this connector to apply power to the D485.
Pin 1: +24 V DC;
Pin 2: ground
Use 60/75 or 75°C copper (CU) wire only. The terminal tightening torque must be between
5 to 7 lbs-in (0.5 to 0.8 nm).
Figure 2-7: Power connector
Mechanical installation
11
22
ONOFF
1
3
5
2
4
6
DIN-RAIL MOUNTINGThe DIN-rail connector is internally connected to the D485.
Figure 2-8: Mounting the D485 to the DIN-rail
To snap the D485 on, first press the D485 downwards (1) to compress the spring on the
DIN-rail connector, then push the D485 against the DIN-rail as to make it snap on (2)
To snap the D485 off, push the D485 downwards (1) and pull it out from the DIN-rail (2), as
to make it snap off from the DIN-rail.
INSTALLATION
Indicators and switches
STATUS INDICATORSThe status indicators for the D485 Modbus to DeviceNet Converter are indicated below.
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE2–5
Figure 2-9: D485 status indicators
INSTALLATION
8
7
6
5
4
3
2
1
Table 2–5: D485 status indicators
NumberDescriptionStateStatus
1Network status OffNot powered / not online
GreenLink OK, online, connected
Green flashingOnline, not connected
RedCritical link failure
Red flashingConnection timeout
2Module statusOffNo power to device
GreenDevice operational
Green flashingData size larger than configured
RedUnrecoverable fault
Red flashingMinor fault
3Not used--
4Not used--
5Modbus
status *
6Device statusOffPower off
* This LED turns green when all transactions have been active at least once. This includes any
transactions using “change of state” or “change of state on trigger”. If a timeout occurs on a
transaction, this LED will turn red.
OffPower off
Green, flashingInitializing and not running
GreenRunning
RedStopped or subnet error, or timeout
Red/green
Invalid or missing configuration
alternating
GreenInitializing
Green flashingRunning
Red flashingIf the device status LED is flashing in a
sequence starting with one or more red
flashes, note the sequence pattern and
contact GE Multilin
CONFIGURATION
SWITCHES
The configuration switches are used to set the DeviceNet MAC ID and baud rate settings.
Normally, these switches are covered by a plastic hatch. Note that the node address can
not be changed during runtime, i.e. the D485 requires a reset for any changes to have
effect. Recycle the power supply to reset the module.
2–6D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
Figure 2-10: D485 configuration switches
INSTALLATION
NOTE
The DeviceNet MAC ID and baud rate switches are set according to the following tables.
Table 2–6: Baud rate settings
Baud rateSwitch 1Switch 2
125 kbpsOFFOFF
250 kbpsOFFON
500 kbpsONOFF
ReservedONON
Table 2–7: MAC ID settings
MAC IDSwitch 3Switch 4Switch 5Switch 6Switch 7Switch 8
0OFFOFFOFFOFFOFFOFF
1OFFOFFOFFOFFOFFON
2OFFOFFOFFOFFONOFF
3OFFOFFOFFOFFONON
↓↓↓↓↓↓↓
63ONONONONONON
When removing the hatch, avoid touching the circuit boards and components. Exercise
caution when using tools to open the hatch.
DEVICENET
CONFIGURATION TOOL
DEVICENET NETWORK
TERMINATION
LINKSAdditional information about the DeviceNet fieldbus system can be found at http://
DeviceNet installation procedure
Each device on a DeviceNet network is associated with a ESD file, which contains all
necessary information about the device. This file is used by the DeviceNet configuration
tool during configuration of the network. The file is available for download at the GE
Multilin website at http://www.GEmultilin.com
It is necessary to import the ESD file in the DeviceNet configuration tool in order to
incorporate the D485 as a slave in the DeviceNet network. The properties for the D485
must then be configured from the DeviceNet configuration tool. This includes setting up
the node address, input/output data areas and DeviceNet baud rate.
•Node address: The node address in the DeviceNet configuration tool should be set to
match the one selected using the on board configuration switches of the D485 (see
Configuration switches on page 2–6).
•Setting up input/output data areas: To establish the connection with the master, the
D485 mus be configured for correct I/O sizes.
•Baud rate: The DeviceNet network baud rate should match the D485 baud rate
setting.
If the D485 is the last node on a DeviceNet network, it is necessary to use a DeviceNet
network termination resistor of 120 ohms between the CAN L and CAN H terminals.
www.odva.org.
(the ESD file is named ‘D485.ESD’).
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE2–7
INSTALLATION
Troubleshooting
DESCRIPTIONProblem during configuration upload/download. The Config Line LED turns red.
•Serial communication failed – try again.
The serial port seems to be available, but it is not possible to connect to the D485.
•The serial port may be in use by another application. Exit EnerVista P485/D485 Setup
and close all other applications including the ones in the system tray and try again.
•Select another serial port and try again.
Poor performance.
•Right click ‘Modbus Network’ in the Navigation window and select ‘Modbus Network
Status’ to see status/diagnostic information about the sub network. If the D485
reports very many retransmissions, check your cabling and/or try a lower baud rate
setting for the sub network (if possible).
•Is the Modbus Network Monitor in EnerVista P485/D485 Setup active? The Modbus
network monitor has a negative influence on the overall performance of the D485,
and should only be used when necessary.
•Is the Node Monitor in EnerVista P485/D485 Setup active? The node monitor has a
negative influence on the overall performance of the D485, and should only be used
when necessary.
2–8D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
GE
Grid Solutions
D485 Modbus to DeviceNet
Converter
Chapter 3: Data Exchange
Data Exchange
Overview
DESCRIPTIONData from the fieldbus (DeviceNet) and the sub network (Modbus) is stored in an internal
memory buffer. This is a easy method for data exchange where the fieldbus control
system simply reads and writes data to pre-defined memory locations, and the serial sub
network also use the same internal memory buffer to read and write data.
Refer to Figure 3-1: Data exchange overview on page 3–2 for additional details.
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE3–1
DATA EXCHANGE
The PLC exchanges data
via the DeviceNet network
between its internal input
area and the input area
of the D485
DeviceNet network
The PLC exchanges data
via thenetwork
between its internal output
area and the output area
of the D485
DeviceNet
The data in the input area of
the D485 contains data received
from nodes on the Modbus
sub-network (sent in to the D485
from the sub-network)
The data in the output area of the
D485 contains data received from
In this case, it is the CT PRIMARY
setting of the PQMII meter
(sent out from the D485 to the sub-network).
DeviceNet
0x00000x02000x0400
Input data areaOutput data areaGeneral data area
Modbus sub-network
Current IaCT PRIMARY
Internal memory buffer
of the D485
PLC memory
I/O inputs
I/O outputs
Current Ia
CT PRIMARY
Modbus slave (e.g. PQMII)
CT PRIMARY setting
Current Ia actual value
INTERNAL MEMORY
BUFFER STRUCTURE
The internal memory buffer can be seen as a memory space with three different types of
data; input data, output data and general data.
•Input data: This is data that should be sent to the fieldbus. The D485 can handle up to
512 bytes of input data.
•Output data: this is data recieved from the fieldbus. The D485 can handle up to 512
bytes of output data.
•General data: This data cannot be accessed from the fieldbus, and is used for
transfers between nodes on the sub-network, or as a general “scratch pad” for data.
The D485 can handle up to 1024 bytes of general data.
Figure 3-1: Data exchange overview
3–2D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
DATA EXCHANGE
Internal memory buffer
Output data
(up to 512 bytes)
Input data
(up to 512 bytes)
Sub network
Fieldbus
General data
1024 bytes
Connection object
Explicit data
Assembly
object
Message router
object
DeviceNet
object
Identity
object
I/O connections
Explicit
messages
Link layer
D485 internal memory buffer
DeviceNet network
General data
(Not available on
the fieldbus)
Input data
I/O data
Explicit data
Output data
I/O data
Figure 3-2: Internal memory buffer
Data exchange on the fieldbus interface is based on the standard DeviceNet objects, and
five vendor specific objects. The vendor specific objects can be used to access the different
memory areas. However, most applications requires only the standard DeviceNet objects.
For a complete description of the available objects, please refer to DeviceNet object implementation on page 3–6.
I/O DATA VS. EXPLICIT
DATA
The input and output areas can hold two types of data:
•I/O data: This data is sent/recevied upon change of value, polling or cyclically.
Figure 3-3: D485 memory structure
•Explicit data: This data is updated on request from another node on the fieldbus.
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE3–3
The amount of data that should be treated as I/O data is determined by the ‘I/O Sizes’
parameter in the EnerVista P485/D485 Setup software. The remainder will be treated as
explicit data. By default (that is, when using ‘automatic’ I/O sizes), all data is treated as I/O
data.
DATA EXCHANGE
Input data areaOutput data area
50 bytes
462 bytes
(512 – 50 = 462)
60 bytes
452 bytes
(512 – 60 = 462)
I/O data (input)
I/O data (input)
Explicit data
(input)
Explicit data
(output)
For example, when using an input I/O size of 50 and an output I/O size of 60, the input and
output data areas will be allocated as follows:
Figure 3-4: I/O data area example
Memory Map
MEMORY LOCATIONSWhen configuring the sub-network, use the memory locations shown below:
AddressContentsAccess
0x0000 to 0x0001Status registerread/write
0x0002 to 0x01FFInput data arearead/write
0x0200 to 0x0201Control registerread only
0x0202 to 0x03FFOutput data arearead only
0x0400 to 0x07FBGeneral data arearead/write
•Status register (0x0000 to 0x0001): If enabled, this register occupies the first two
bytes in the input data area. For more information, see Control and status registers on
page 8–1.
•Input data area (0x002 to 0x01FF): This area holds data that should be sent to the
fieldbus (see the status and control registers).
•Control register (0x0200 to 0x0201): If enabled, these register occupies the first two
bytes in the output data area. For more information, see Control and status registers
on page 8–1.
•Output data area (0x0202 to 0x03FF): This area holds data received from the fieldbus.
Data cannot be written to this area.
•General data Area (0x0400 to 0x07FB): This data cannot be accessed from the
fieldbus, and should be used for transfers between nodes on the Modbus subnetwork, or as a general “scratch pad” for data.
3–4D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
DATA EXCHANGE
Node
Transaction
Transaction
Message frame
Byte
WordDataCRCByte
Frame objects
Message frame
ByteWordDataCRCByte
Frame objects
Message frame
Byte
WordDataCRCByte
Frame objects
Protocol configuration
DESCRIPTIONIn order to be able to communicate on the Modbus sub-network, the D485 must be
supplied with a description of the required sub-net protocol. To accomplish this, the
EnerVista P485/D485 Setup software features a flexible protocol-programming system,
allowing the D485 to interpret and exchange data with almost any serial device on the
Modbus sub-network.
COMMUNICATION MODEThe D485 supports the Modbus Master communication mode. In this mode, the D485 is
setup to use the Modbus RTU protocol and implements a Modbus master for data
exchange between the fieldbus and one or more devices on the sub-network. Refer to
Chapter 5 for additional details.
PROTOCOL BUILDING
BLOCKS
A description of the building blocks used to describe the sub-net protocol is shown below.
Figure 3-5: Modbus protocol blocks
•Node: In the D485, a node holds all transactions and parameters for a particular
device on the sub network.
•Transaction: Transactions contains messages to be transmitted on the sub-network.
A transaction consists of one or more message frames (see figure above), and has a
few general parameters to specify how and when the transaction should be used on
the sub-network.
•Commands: A command is a pre-defined transaction that has been stored in a list in
the EnerVista P485/D485 Setup software. This improves readability as well as
simplifying common operations by allowing transactions to be stored and reused.
•Message frame: The message frame contains a description of what is actually
transmitted on the sub-network and consists of frame objects (see figure above).
•Frame object: Frame objects are used to compose a message frame. Frame objects
include fixed values, dynamic values retrieved from a specified memory location in
the D485, or strings.
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE3–5
DATA EXCHANGE
DeviceNet object implementation
OVERVIEWDeviceNet requires some mandatory objects; these are implemented as well as some
vendor specific objects. The following objects are implemented:
Table 3–1: Mandatory objects
Object nameClassPage
Identity object01h3-6
Message router object02h3-7
DeviceNet object03h3-7
Assembly object04h3-8
Connection object05h3-8
Acknowledge handler object2Bh3-10
Table 3–2: Vendor specific object
Object nameClassPage
I/O data input mapping objectA0h3-11
I/O data output mapping objectA0h3-11
Diagnostic objectAAh3-12
Parameter data input mapping objectB0h3-12
Parameter data output mapping objectB1h3-13
IDENTITY OBJECT
(CLASS 01H)
Services:
Class services: Get Attribute Single
Instance services: Get Attribute Single
Table 3–3: Class attributes for identity object 01h
Attr.Access NameTypeValueDescription
1GetRevisionUINT0001hRevision 1
Table 3–4: Instance attributes for identity object 01h
3–8D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
Table 3–13: Attributes for instance 2 for connection object 05h
Attr.Access NameTypeValueDescription
1GetStateUSINTN/A0 = Non existent
2GetInstance typeUSINT0I/O connection
1 = Configuring
3 = Established
4 = Timeout
Table 3–14: Attributes for instance 3 for connection object 05h
Attr.Access NameTypeValueDescription
1GetStateUSINTN/A0 = Non existent
2GetInstance typeUSINT0I/O connection
1 = Configuring
3 = Established
4 = Timeout
Table 3–15: Attributes for instance 4 for connection object 05h
Attr.Access NameTypeValueDescription
1GetStateUSINTN/A0 = Non existent
2GetInstance typeUSINT0I/O connection
3GetTransport class
trigger
4GetProduced
connection ID
5GetConsumed
connection ID
6GetInitial
communication
characteristics
7GetProduced
connection size
8GetConsumed
connection size
9Get/Set Expected packet
rate
12GetWatchdog
timeout action
13GetProduced
connection path
length
14GetProduced
connection path
15GetConsumed
connection path
length
16GetConsumed
connection path
BYTEN/ADefines the behavior of the
UINTN/ACAN ID for transmission
UINTN/ACAN ID for reception
BYTE0Fh (no ACK) Produces over message group 1.
01h (ACK)Produces over message group 1.
UINTN/ANumber of bytes transmitted
UINT0Number of bytes received across
UINT0Timing associated with this
USINTN/A0 = Transition to the timed
UINT0006hNumber of bytes in the produced
EPATH20 04 24 66
30 03h
UINT0004hNumber of bytes in the
EPATH20 2B 24
01h
1 = Configuring
3 = Established
4 = Timeout
connection
Does not consume.
Consumes over message group
2.
across this connection
this connection
connection
out state
1 = Auto delete
2 = Auto reset
3 = Deferred delete
connection path attribute
Application object producing
data on this connection
consumed connection path
length attribute
Specifies the applica tion object(s)
that are to receive the data
consumed by this connection
object
DATA EXCHANGE
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE3–9
DATA EXCHANGE
ACKNOWLEDGE
HANDLER OBJECT
(CLASS 2BH)
Services:
Class services: Get Attribute Single
Instance services: Get Attribute Single, Set Attribute Single
Table 3–16: Class attributes for acknowledge handler object 2Bh
Attr.Access NameTypeValueDescription
1GetRevisionUINT0001hRevision 1
2GetMax. instanceUINT0001hMaximum instance number
Table 3–17: Instance attributes for acknowledge handler object 2Bh
Attr.Access NameTypeValueDescription
1Get/Set Acknowledge
timer
2Get/Set Retry limitUSINT1Number of ACK time-outs before
3Get/Set Producing
connection
Instance
4GetAcknowledge list
size
5GetAcknowledge listArray of
6GetData with
acknowledge path
list size
7GetData with
acknowledge path
list
UINT20Time (in ms) to wait for
UINT4Connection instance – contains
Byte---Maximum number of members
USINT
Byte---Maximum number of members
Array of
USINT
N/AList of active connection instance
N/AList of connection instance/
acknowledge before re-sending.
retry limit reached event
the path of the producing I/O
application object which will be
notified of acknowledge handler
events
in acknowledge list (0 = dynamic)
which are receiving
acknowledgements.
in data with acknowledge path
list (0=dynamic)
consuming application object
pairs.
3–10D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
DATA EXCHANGE
I/O DATA INPUT
MAPPING OBJECT
(CLASS A0H)
This vendor-specific object provides I/O input data mapping information. The number of
existing attributes depends on which attributes are initialized in the module through the
EnerVista P485/D485 Setup software.
Services:
Class services: Get Attribute All
Instance services: Get Attribute Single, Set Attribute Single
Table 3–18: Class attributes for I/O data input mapping object A0h
Attr.Access NameTypeValueDescription
1GetRevisionUINT0001hRevision 1
Table 3–19: Instance attributes for I/O data input mapping object A0h, instance 01h
Attr.Access NameTypeValueDescription
1GetInput 1Array of
USINT
2GetInput 2Array of
USINT
3GetInput 3Array of
USINT
4GetInput 4Array of
USINT
5GetInput 5Array of
USINT
6GetInput 6Array of
USINT
---Data that is read
---Data that is read
---Data that is read
---Data that is read
---Data that is read
---Data that is read
I/O DATA OUTPUT
MAPPING OBJECT
(CLASS A1H)
This vendor-specific object provides I/O output data mapping information. The number of
existing attributes depends on which attributes are initialized in the module through the
EnerVista P485/D485 Setup software.
Services:
Class services: Get Attribute All
Instance services: Get Attribute Single, Set Attribute Single
Table 3–20: Class attributes for I/O data output mapping object A1h
Attr.Access NameTypeValueDescription
1GetRevisionUINT0001hRevision 1
Table 3–21: Instance attributes for I/O data output mapping object A1h, instance 01h
Attr.Access NameTypeValueDescription
1Get/Set Output 1Array of
USINT
2Get/Set Output 2Array of
USINT
3Get/Set Output 3Array of
USINT
4Get/Set Output 4Array of
USINT
5Get/Set Output 5Array of
USINT
6Get/Set Output 6Array of
USINT
---Data that is read or written
---Data that is read or written
---Data that is read or written
---Data that is read or written
---Data that is read or written
---Data that is read or written
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE3–11
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.