GE D30 series Instruction Manual

837767A2.CDR
LISTED
52TL
IND.CONT. EQ.
E83849
GE
Digital Energy
D30 Line Distance Protection
System
UR Series Instruction Manual
D30 revision: 7.0x
Manual P/N: 1601-0116-Y2 (GEK-113664A)
GE Digital Energy
650 Markland Street
Markham, Ontario
Tel: +1 905 927 7070 Fax: +1 905 927 5098
Internet: http://www.GEDigitalEnergy.com
*1601-0116-Y2*
GE Multilin's Quality Management
System is registered to ISO
9001:2008
QMI # 005094
UL # A3775
Copyright © 2012 GE Multilin Inc. All rights reserved.
D30 Line Distance Protection System UR Series Instruction Manual revision 7.0x.
FlexLogic, FlexElement, FlexCurve, FlexAnalog, FlexInteger, FlexState, EnerVista, CyberSentry, HardFiber, Digital Energy, Multilin, and GE Multilin are trademarks or registered trademarks of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The content of this manual is for informational use only and is subject to change without notice. Part number: 1601-0116-Y2 (November 2012)
TABLE OF CONTENTS
1. GETTING STARTED 1.1 IMPORTANT PROCEDURES
1.1.1 CAUTIONS AND WARNINGS ........................................................................... 1-1
1.1.2 INSPECTION CHECKLIST ................................................................................ 1-1
1.2 UR OVERVIEW
1.2.1 INTRODUCTION TO THE UR ........................................................................... 1-2
1.2.2 HARDWARE ARCHITECTURE......................................................................... 1-3
1.2.3 SOFTWARE ARCHITECTURE.......................................................................... 1-4
1.2.4 IMPORTANT CONCEPTS ................................................................................. 1-4
1.3 ENERVISTA UR SETUP SOFTWARE
1.3.1 PC REQUIREMENTS ........................................................................................ 1-5
1.3.2 INSTALLATION.................................................................................................. 1-5
1.3.3 CONFIGURING THE D30 FOR SOFTWARE ACCESS .................................... 1-6
1.3.4 USING THE QUICK CONNECT FEATURE....................................................... 1-9
1.3.5 CONNECTING TO THE D30 RELAY .............................................................. 1-15
1.4 UR HARDWARE
1.4.1 MOUNTING AND WIRING............................................................................... 1-16
1.4.2 COMMUNICATIONS........................................................................................ 1-16
1.4.3 FACEPLATE DISPLAY.................................................................................... 1-16
1.5 USING THE RELAY
1.5.1 FACEPLATE KEYPAD..................................................................................... 1-17
1.5.2 MENU NAVIGATION ....................................................................................... 1-17
1.5.3 MENU HIERARCHY ........................................................................................ 1-17
1.5.4 RELAY ACTIVATION....................................................................................... 1-17
1.5.5 RELAY PASSWORDS..................................................................................... 1-18
1.5.6 FLEXLOGIC™ CUSTOMIZATION................................................................... 1-18
1.5.7 COMMISSIONING ........................................................................................... 1-19
2. PRODUCT DESCRIPTION 2.1 INTRODUCTION
2.1.1 OVERVIEW........................................................................................................ 2-1
2.1.2 ORDERING........................................................................................................ 2-2
2.1.3 REPLACEMENT MODULES ............................................................................. 2-6
2.2 SPECIFICATIONS
2.2.1 PROTECTION ELEMENTS ............................................................................... 2-9
2.2.2 USER PROGRAMMABLE ELEMENTS........................................................... 2-13
2.2.3 MONITORING.................................................................................................. 2-14
2.2.4 METERING ......................................................................................................2-14
2.2.5 INPUTS ............................................................................................................ 2-14
2.2.6 POWER SUPPLY ............................................................................................2-15
2.2.7 OUTPUTS ........................................................................................................ 2-16
2.2.8 COMMUNICATIONS........................................................................................ 2-17
2.2.9 INTER-RELAY COMMUNICATIONS............................................................... 2-18
2.2.10 ENVIRONMENTAL .......................................................................................... 2-18
2.2.11 TYPE TESTS ................................................................................................... 2-19
2.2.12 PRODUCTION TESTS .................................................................................... 2-19
2.2.13 APPROVALS ................................................................................................... 2-20
2.2.14 MAINTENANCE ............................................................................................... 2-20
3. HARDWARE 3.1 DESCRIPTION
3.1.1 PANEL CUTOUT ............................................................................................... 3-1
3.1.2 MODULE WITHDRAWAL AND INSERTION ..................................................... 3-6
3.1.3 REAR TERMINAL LAYOUT............................................................................... 3-8
3.2 WIRING
3.2.1 TYPICAL WIRING.............................................................................................. 3-9
3.2.2 DIELECTRIC STRENGTH ............................................................................... 3-10
3.2.3 CONTROL POWER ......................................................................................... 3-10
3.2.4 CT/VT MODULES ............................................................................................ 3-11
3.2.5 PROCESS BUS MODULES ............................................................................ 3-12
3.2.6 CONTACT INPUTS AND OUTPUTS...............................................................3-13
GE Multilin D30 Line Distance Protection System iii
TABLE OF CONTENTS
3.2.7 TRANSDUCER INPUTS/OUTPUTS.................................................................3-20
3.2.8 RS232 FACEPLATE PORT..............................................................................3-21
3.2.9 CPU COMMUNICATION PORTS.....................................................................3-21
3.2.10 IRIG-B...............................................................................................................3-24
3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS
3.3.1 DESCRIPTION .................................................................................................3-25
3.3.2 FIBER: LED AND ELED TRANSMITTERS ......................................................3-27
3.3.3 FIBER-LASER TRANSMITTERS .....................................................................3-27
3.3.4 G.703 INTERFACE...........................................................................................3-28
3.3.5 RS422 INTERFACE .........................................................................................3-31
3.3.6 RS422 AND FIBER INTERFACE .....................................................................3-33
3.3.7 G.703 AND FIBER INTERFACE ......................................................................3-33
3.3.8 IEEE C37.94 INTERFACE................................................................................3-34
3.3.9 C37.94SM INTERFACE ...................................................................................3-37
4. HUMAN INTERFACES 4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE
4.1.1 INTRODUCTION ................................................................................................4-1
4.1.2 CREATING A SITE LIST ....................................................................................4-1
4.1.3 ENERVISTA UR SETUP OVERVIEW................................................................4-1
4.1.4 ENERVISTA UR SETUP MAIN WINDOW..........................................................4-3
4.2 EXTENDED ENERVISTA UR SETUP FEATURES
4.2.1 SETTINGS TEMPLATES ...................................................................................4-4
4.2.2 SECURING AND LOCKING FLEXLOGIC™ EQUATIONS ................................4-8
4.2.3 SETTINGS FILE TRACEABILITY.....................................................................4-10
4.3 FACEPLATE INTERFACE
4.3.1 FACEPLATE.....................................................................................................4-13
4.3.2 LED INDICATORS............................................................................................4-14
4.3.3 CUSTOM LABELING OF LEDS .......................................................................4-17
4.3.4 DISPLAY...........................................................................................................4-23
4.3.5 KEYPAD ...........................................................................................................4-23
4.3.6 BREAKER CONTROL ......................................................................................4-23
4.3.7 MENUS.............................................................................................................4-24
4.3.8 CHANGING SETTINGS ...................................................................................4-26
5. SETTINGS 5.1 OVERVIEW
5.1.1 SETTINGS MAIN MENU ....................................................................................5-1
5.1.2 INTRODUCTION TO ELEMENTS......................................................................5-4
5.1.3 INTRODUCTION TO AC SOURCES..................................................................5-5
5.2 PRODUCT SETUP
5.2.1 SECURITY..........................................................................................................5-8
5.2.2 CYBERSENTRY SECURITY............................................................................5-12
5.2.3 DISPLAY PROPERTIES ..................................................................................5-18
5.2.4 CLEAR RELAY RECORDS ..............................................................................5-19
5.2.5 COMMUNICATIONS ........................................................................................5-20
5.2.6 REAL TIME CLOCK .........................................................................................5-44
5.2.7 FAULT REPORTS ............................................................................................5-49
5.2.8 OSCILLOGRAPHY ...........................................................................................5-51
5.2.9 USER-PROGRAMMABLE LEDS .....................................................................5-53
5.2.10 USER-PROGRAMMABLE SELF TESTS .........................................................5-56
5.2.11 CONTROL PUSHBUTTONS ............................................................................5-57
5.2.12 USER-PROGRAMMABLE PUSHBUTTONS....................................................5-59
5.2.13 FLEX STATE PARAMETERS ..........................................................................5-64
5.2.14 USER-DEFINABLE DISPLAYS........................................................................5-65
5.2.15 DIRECT INPUTS/OUTPUTS ............................................................................5-67
5.2.16 TELEPROTECTION .........................................................................................5-75
5.2.17 INSTALLATION ................................................................................................5-75
5.3 REMOTE RESOURCES
5.3.1 REMOTE RESOURCES CONFIGURATION....................................................5-77
iv D30 Line Distance Protection System GE Multilin
TABLE OF CONTENTS
5.4 SYSTEM SETUP
5.4.1 AC INPUTS ...................................................................................................... 5-78
5.4.2 POWER SYSTEM............................................................................................ 5-79
5.4.3 SIGNAL SOURCES ......................................................................................... 5-80
5.4.4 BREAKERS...................................................................................................... 5-83
5.4.5 DISCONNECT SWITCHES ............................................................................. 5-87
5.4.6 FLEXCURVES™ ............................................................................................. 5-90
5.5 FLEXLOGIC
5.5.1 INTRODUCTION TO FLEXLOGIC .................................................................. 5-97
5.5.2 FLEXLOGIC™ RULES .................................................................................. 5-107
5.5.3 FLEXLOGIC™ EVALUATION........................................................................ 5-108
5.5.4 FLEXLOGIC™ EXAMPLE ............................................................................. 5-108
5.5.5 FLEXLOGIC™ EQUATION EDITOR ............................................................. 5-113
5.5.6 FLEXLOGIC™ TIMERS................................................................................. 5-113
5.5.7 FLEXELEMENTS™ ....................................................................................... 5-114
5.5.8 NON-VOLATILE LATCHES ........................................................................... 5-118
5.6 GROUPED ELEMENTS
5.6.1 OVERVIEW.................................................................................................... 5-119
5.6.2 SETTING GROUP ......................................................................................... 5-119
5.6.3 LINE PICKUP................................................................................................. 5-120
5.6.4 DISTANCE ..................................................................................................... 5-122
5.6.5 POWER SWING DETECT............................................................................. 5-137
5.6.6 LOAD ENCROACHMENT.............................................................................. 5-145
5.6.7 PHASE CURRENT ........................................................................................ 5-147
5.6.8 NEUTRAL CURRENT.................................................................................... 5-157
5.6.9 GROUND CURRENT..................................................................................... 5-164
5.6.10 NEGATIVE SEQUENCE CURRENT ............................................................. 5-167
5.6.11 VOLTAGE ELEMENTS.................................................................................. 5-174
5.7 CONTROL ELEMENTS
5.7.1 OVERVIEW.................................................................................................... 5-182
5.7.2 TRIP BUS....................................................................................................... 5-182
5.7.3 SETTING GROUPS ....................................................................................... 5-184
5.7.4 SELECTOR SWITCH..................................................................................... 5-185
5.7.5 SYNCHROCHECK......................................................................................... 5-191
5.7.6 AUTORECLOSE ............................................................................................ 5-195
5.7.7 DIGITAL ELEMENTS..................................................................................... 5-201
5.7.8 DIGITAL COUNTERS .................................................................................... 5-204
5.7.9 MONITORING ELEMENTS ........................................................................... 5-206
5.8 INPUTS AND OUTPUTS
5.8.1 CONTACT INPUTS........................................................................................ 5-216
5.8.2 VIRTUAL INPUTS.......................................................................................... 5-218
5.8.3 CONTACT OUTPUTS.................................................................................... 5-219
5.8.4 VIRTUAL OUTPUTS...................................................................................... 5-221
5.8.5 REMOTE DEVICES....................................................................................... 5-222
5.8.6 REMOTE INPUTS.......................................................................................... 5-223
5.8.7 REMOTE DOUBLE-POINT STATUS INPUTS .............................................. 5-224
5.8.8 REMOTE OUTPUTS...................................................................................... 5-224
5.8.9 RESETTING................................................................................................... 5-225
5.8.10 DIRECT INPUTS AND OUTPUTS................................................................. 5-225
5.8.11 TELEPROTECTION INPUTS AND OUTPUTS..............................................5-229
5.8.12 IEC 61850 GOOSE ANALOGS...................................................................... 5-231
5.8.13 IEC 61850 GOOSE INTEGERS..................................................................... 5-232
5.9 TRANSDUCER INPUTS AND OUTPUTS
5.9.1 DCMA INPUTS .............................................................................................. 5-233
5.9.2 RTD INPUTS.................................................................................................. 5-234
5.9.3 DCMA OUTPUTS .......................................................................................... 5-236
5.10 TESTING
5.10.1 TEST MODE .................................................................................................. 5-239
5.10.2 FORCE CONTACT INPUTS .......................................................................... 5-240
5.10.3 FORCE CONTACT OUTPUTS ...................................................................... 5-241
GE Multilin D30 Line Distance Protection System v
TABLE OF CONTENTS
6. ACTUAL VALUES 6.1 OVERVIEW
6.1.1 ACTUAL VALUES MAIN MENU.........................................................................6-1
6.2 STATUS
6.2.1 CONTACT INPUTS ............................................................................................6-3
6.2.2 VIRTUAL INPUTS ..............................................................................................6-3
6.2.3 REMOTE INPUTS ..............................................................................................6-3
6.2.4 REMOTE DOUBLE-POINT STATUS INPUTS...................................................6-4
6.2.5 TELEPROTECTION INPUTS .............................................................................6-4
6.2.6 CONTACT OUTPUTS ........................................................................................6-4
6.2.7 VIRTUAL OUTPUTS ..........................................................................................6-5
6.2.8 AUTORECLOSE.................................................................................................6-5
6.2.9 REMOTE DEVICES............................................................................................6-5
6.2.10 DIGITAL COUNTERS.........................................................................................6-6
6.2.11 SELECTOR SWITCHES ....................................................................................6-6
6.2.12 FLEX STATES....................................................................................................6-6
6.2.13 ETHERNET ........................................................................................................6-7
6.2.14 REAL TIME CLOCK SYNCHRONIZING ............................................................6-7
6.2.15 DIRECT INPUTS ................................................................................................6-8
6.2.16 DIRECT DEVICES STATUS ..............................................................................6-8
6.2.17 IEC 61850 GOOSE INTEGERS .........................................................................6-9
6.2.18 TELEPROTECTION CHANNEL TESTS.............................................................6-9
6.2.19 REMAINING CONNECTION STATUS .............................................................6-10
6.3 METERING
6.3.1 METERING CONVENTIONS ...........................................................................6-11
6.3.2 SOURCES ........................................................................................................6-14
6.3.3 SYNCHROCHECK ...........................................................................................6-17
6.3.4 TRACKING FREQUENCY................................................................................6-17
6.3.5 FLEXELEMENTS™..........................................................................................6-18
6.3.6 IEC 61580 GOOSE ANALOG VALUES ...........................................................6-18
6.3.7 TRANSDUCER INPUTS/OUTPUTS.................................................................6-19
6.4 RECORDS
6.4.1 FAULT REPORTS ............................................................................................6-20
6.4.2 EVENT RECORDS...........................................................................................6-20
6.4.3 OSCILLOGRAPHY ...........................................................................................6-21
6.4.4 BREAKER MAINTENANCE .............................................................................6-21
6.5 PRODUCT INFORMATION
6.5.1 MODEL INFORMATION...................................................................................6-22
6.5.2 FIRMWARE REVISIONS..................................................................................6-22
7. COMMANDS AND TARGETS
7.1 COMMANDS
7.1.1 COMMANDS MENU...........................................................................................7-1
7.1.2 VIRTUAL INPUTS ..............................................................................................7-1
7.1.3 CLEAR RECORDS.............................................................................................7-2
7.1.4 SET DATE AND TIME ........................................................................................7-2
7.1.5 RELAY MAINTENANCE.....................................................................................7-3
7.1.6 SECURITY..........................................................................................................7-3
7.2 TARGETS
7.2.1 TARGETS MENU ...............................................................................................7-5
7.2.2 TARGET MESSAGES ........................................................................................7-5
7.2.3 RELAY SELF-TESTS .........................................................................................7-5
8. SECURITY 8.1 USER ACCOUNTS
8.1.1 OVERVIEW ........................................................................................................8-1
8.1.2 ENABLING THE SECURITY MANAGEMENT SYSTEM....................................8-1
8.1.3 ADDING A NEW USER ......................................................................................8-1
8.1.4 MODIFYING USER PRIVILEGES......................................................................8-2
8.2 CYBERSENTRY
8.2.1 OVERVIEW ........................................................................................................8-4
vi D30 Line Distance Protection System GE Multilin
TABLE OF CONTENTS
8.2.2 SECURITY MENU ............................................................................................. 8-6
9. THEORY OF OPERATION 9.1 DISTANCE ELEMENTS
9.1.1 INTRODUCTION................................................................................................ 9-1
9.1.2 PHASOR ESTIMATION ..................................................................................... 9-1
9.1.3 DISTANCE CHARACTERISTICS ...................................................................... 9-2
9.1.4 MEMORY POLARIZATION................................................................................ 9-6
9.1.5 DISTANCE ELEMENTS ANALYSIS.................................................................. 9-7
9.2 PHASE DISTANCE APPLIED TO POWER TRANSFORMERS
9.2.1 DESCRIPTION................................................................................................. 9-11
9.2.2 EXAMPLE ........................................................................................................ 9-14
9.3 GROUND DIRECTIONAL OVERCURRENT
9.3.1 DESCRIPTION................................................................................................. 9-16
9.3.2 EXAMPLE ........................................................................................................ 9-16
9.4 SERIES COMPENSATED LINES
9.4.1 DESCRIPTION................................................................................................. 9-18
9.5 FAULT LOCATOR
9.5.1 FAULT TYPE DETERMINATION..................................................................... 9-21
10. APPLICATION OF
SETTINGS
A. FLEXANALOG AND
FLEXINTEGER PARAMETERS
B. MODBUS
COMMUNICATIONS
10.1 APPLICATION GUIDELINES
10.1.1 INTRODUCTION.............................................................................................. 10-1
10.1.2 IMPACT OF MEMORY POLARIZATION......................................................... 10-1
10.1.3 HIGH SET OVERCURRENT ELEMENTS .......................................................10-1
10.2 DISTANCE ELEMENTS (STEPPED DISTANCE SCHEME)
10.2.1 PHASE DISTANCE.......................................................................................... 10-2
10.2.2 GROUND DISTANCE ...................................................................................... 10-3
10.3 SERIES COMPENSATED LINES
10.3.1 INTRODUCTION.............................................................................................. 10-6
10.3.2 DISTANCE ....................................................................................................... 10-6
10.3.3 GROUND DIRECTIONAL OVERCURRENT ................................................... 10-7
10.3.4 HIGH-SET PHASE OVERCURRENT ..............................................................10-7
10.4 PHASE DISTANCE THROUGH POWER TRANSFORMERS
10.4.1 PHASE DISTANCE PROTECTION ................................................................. 10-8
10.4.2 EXAMPLE ........................................................................................................10-9
A.1 PARAMETER LISTS
A.1.1 FLEXANALOG ITEMS ....................................................................................... A-1
A.1.2 FLEXINTEGER ITEMS .................................................................................... A-10
B.1 MODBUS RTU PROTOCOL
B.1.1 INTRODUCTION................................................................................................B-1
B.1.2 PHYSICAL LAYER.............................................................................................B-1
B.1.3 DATA LINK LAYER............................................................................................B-1
B.1.4 CRC-16 ALGORITHM........................................................................................B-2
B.2 MODBUS FUNCTION CODES
B.2.1 SUPPORTED FUNCTION CODES ...................................................................B-3
B.2.2 READ ACTUAL VALUES OR SETTINGS (FUNCTION CODE 03/04H) ...........B-3
B.2.3 EXECUTE OPERATION (FUNCTION CODE 05H) ...........................................B-4
B.2.4 STORE SINGLE SETTING (FUNCTION CODE 06H).......................................B-4
B.2.5 STORE MULTIPLE SETTINGS (FUNCTION CODE 10H) ................................B-5
B.2.6 EXCEPTION RESPONSES...............................................................................B-5
GE Multilin D30 Line Distance Protection System vii
TABLE OF CONTENTS
B.3 FILE TRANSFERS
B.3.1 OBTAINING RELAY FILES VIA MODBUS........................................................ B-6
B.3.2 MODBUS PASSWORD OPERATION............................................................... B-8
B.4 MEMORY MAPPING
B.4.1 MODBUS MEMORY MAP ................................................................................. B-9
B.4.2 DATA FORMATS............................................................................................. B-69
C. IEC 61850
COMMUNICATIONS
C.1 OVERVIEW
C.1.1 INTRODUCTION ............................................................................................... C-1
C.1.2 COMMUNICATION PROFILES......................................................................... C-1
C.2 SERVER DATA ORGANIZATION
C.2.1 OVERVIEW ....................................................................................................... C-2
C.2.2 GGIO1: DIGITAL STATUS VALUES.................................................................C-2
C.2.3 GGIO2: DIGITAL CONTROL VALUES.............................................................. C-2
C.2.4 GGIO3: DIGITAL STATUS AND ANALOG VALUES FROM RECEIVED GOOSE
DATAC-2
C.2.5 GGIO4: GENERIC ANALOG MEASURED VALUES.........................................C-2
C.2.6 MMXU: ANALOG MEASURED VALUES .......................................................... C-3
C.2.7 PROTECTION AND OTHER LOGICAL NODES............................................... C-3
C.3 SERVER FEATURES AND CONFIGURATION
C.3.1 BUFFERED/UNBUFFERED REPORTING........................................................C-5
C.3.2 FILE TRANSFER...............................................................................................C-5
C.3.3 TIMESTAMPS AND SCANNING....................................................................... C-5
C.3.4 LOGICAL DEVICE NAME ................................................................................. C-5
C.3.5 LOCATION ........................................................................................................ C-5
C.3.6 LOGICAL NODE NAME PREFIXES.................................................................. C-6
C.3.7 CONNECTION TIMING.....................................................................................C-6
C.3.8 NON-IEC 61850 DATA...................................................................................... C-6
C.3.9 COMMUNICATION SOFTWARE UTILITIES.....................................................C-6
C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE
C.4.1 OVERVIEW ....................................................................................................... C-7
C.4.2 GSSE CONFIGURATION..................................................................................C-7
C.4.3 FIXED GOOSE..................................................................................................C-7
C.4.4 CONFIGURABLE GOOSE ................................................................................ C-7
C.4.5 ETHERNET MAC ADDRESS FOR GSSE/GOOSE ........................................ C-10
C.4.6 GSSE ID AND GOOSE ID SETTINGS............................................................C-10
C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
C.5.1 OVERVIEW ..................................................................................................... C-11
C.5.2 CONFIGURING IEC 61850 SETTINGS .......................................................... C-12
C.5.3 ABOUT ICD FILES .......................................................................................... C-13
C.5.4 CREATING AN ICD FILE WITH ENERVISTA UR SETUP..............................C-17
C.5.5 ABOUT SCD FILES......................................................................................... C-17
C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP........................... C-20
C.6 ACSI CONFORMANCE
C.6.1 ACSI BASIC CONFORMANCE STATEMENT ................................................ C-22
C.6.2 ACSI MODELS CONFORMANCE STATEMENT............................................C-22
C.6.3 ACSI SERVICES CONFORMANCE STATEMENT ......................................... C-23
C.7 LOGICAL NODES
C.7.1 LOGICAL NODES TABLE ...............................................................................C-26
D. IEC 60870-5-104
COMMUNICATIONS
D.1 IEC 60870-5-104 PROTOCOL
D.1.1 INTEROPERABILITY ........................................................................................ D-1
D.1.2 POINT LIST .......................................................................................................D-9
E. DNP COMMUNICATIONS E.1 DEVICE PROFILE DOCUMENT
viii D30 Line Distance Protection System GE Multilin
TABLE OF CONTENTS
E.1.1 DNP V3.00 DEVICE PROFILE ..........................................................................E-1
E.1.2 IMPLEMENTATION TABLE............................................................................... E-4
E.2 DNP POINT LISTS
E.2.1 BINARY INPUT POINTS....................................................................................E-8
E.2.2 BINARY AND CONTROL RELAY OUTPUT...................................................... E-9
E.2.3 COUNTERS .....................................................................................................E-10
E.2.4 ANALOG INPUTS ............................................................................................E-11
F. MISCELLANEOUS F.1 CHANGE NOTES
F.1.1 REVISION HISTORY ......................................................................................... F-1
F.1.2 CHANGES TO THE MANUAL ...........................................................................F-2
F.2 ABBREVIATIONS
F.2.1 STANDARD ABBREVIATIONS ....................................................................... F-13
F.3 WARRANTY
F.3.1 GE MULTILIN WARRANTY ............................................................................. F-17
GE Multilin D30 Line Distance Protection System ix
TABLE OF CONTENTS
x D30 Line Distance Protection System GE Multilin
1 GETTING STARTED 1.1 IMPORTANT PROCEDURES
NOTE
1 GETTING STARTED 1.1IMPORTANT PROCEDURES
Read this chapter to help guide you through the initial setup of your new D30 Line Distance Protection System.

1.1.1 CAUTIONS AND WARNINGS

Before attempting to install or use the device, review all safety indicators in this document to help prevent injury, equipment damage, or downtime.
The following safety and equipment symbols are used in this document.
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Indicates practices not related to personal injury.

1.1.2 INSPECTION CHECKLIST

1. Open the relay packaging and inspect the unit for physical damage.
2. View the rear nameplate and verify that the correct model has been ordered and delivered.
1
Figure 1–1: REAR NAMEPLATE (EXAMPLE)
3. Ensure that the following items are included:
• Instruction manual (if ordered)
• GE EnerVista™ CD (includes the EnerVista UR Setup software and manuals in PDF format)
• Mounting screws
For product information, instruction manual updates, and the latest software updates, visit the GE Digital Energy website at
http://www.gedigitalenergy.com
If there is any noticeable physical damage, or any of the contents listed are missing, please contact GE Digital Energy immediately.
GE DIGITAL ENERGY CONTACT INFORMATION AND CALL CENTER FOR PRODUCT SUPPORT:
GE Digital Energy 650 Markland Street Markham, Ontario Canada L6C 0M1
TELEPHONE: Worldwide +1 905 927 7070
Europe/Middle East/Africa +34 94 4854 88 54 North America toll-free 1 800 547 8629
FAX: +1 905 927 5098 EMAIL: multilin.tech@ge.com HOME PAGE: http://www.gedigitalenergy.com/multilin
.
GE Multilin D30 Line Distance Protection System 1-1
1.2 UR OVERVIEW 1 GETTING STARTED

1.2UR OVERVIEW 1.2.1 INTRODUCTION TO THE UR

1
Historically, substation protection, control, and metering functions were performed with electromechanical equipment. This equipment was gradually replaced by analog equipment, most of which emulated the single-function approach of their elec­tromechanical precursors. Both technologies required expensive cabling and auxiliary equipment to produce functioning systems.
Recently, digital electronic equipment has begun to provide protection, control, and metering functions. Initially, this equip­ment was either single function or had very limited multifunction capability, and it did not significantly reduce the cabling and auxiliary equipment required. However, recent digital relays are multifunctional, reducing cabling and auxiliaries signifi­cantly. These devices also transfer data to central control facilities and software using electronic communications. The functions performed have become so broad that many users now prefer the term Intelligent Electronic Device (IED).
It is obvious to station designers that the amount of cabling and auxiliary equipment installed can be even further reduced, to 20% to 70% of levels common in 1990, and achieve large cost reductions. This requires placing even more functions within the IEDs.
Users of power equipment are also interested in reducing cost by improving power quality and personnel productivity, and in increasing system reliability and efficiency. These objectives are realized through software that is used to perform func­tions at both the station and supervisory levels. The use of these systems is growing rapidly.
High-speed communication is required to meet the data transfer rates required by modern automatic control and monitoring systems. Very high speed communications are required to perform protection signaling with a performance target response time for a command signal between two IEDs, from transmission to reception, of less than 3 milliseconds. This has been established by the IEC 61850 standard.
IEDs with such capabilities also provide significantly more power system data than was available, enhanced operations and maintenance, and permit the use of adaptive system configuration for protection and control systems. This new generation of equipment is easily incorporated into automation systems, at both the station and enterprise levels. The GE Multilin Uni­versal Relay (UR) series meets these goals.
1-2 D30 Line Distance Protection System GE Multilin
1 GETTING STARTED 1.2 UR OVERVIEW

1.2.2 HARDWARE ARCHITECTURE

a) UR BASIC DESIGN
The UR is a digital-based device containing a central processing unit (CPU) that handles multiple types of input and output signals. The UR device can communicate over a local area network (LAN) with an operator interface, a programming device, or another UR device.
Figure 1–2: UR CONCEPT BLOCK DIAGRAM
The CPU module contains firmware that provides protection elements in the form of logic algorithms, as well as program­mable logic gates, timers, and latches for control features.
Input elements accept a variety of analog or digital signals from the field. The UR isolates and converts these signals into logic signals used by the relay.
Output elements convert and isolate the logic signals generated by the relay into digital or analog signals that can be used to control field devices.
1
b) UR SIGNAL TYPES
The contact inputs and outputs are digital signals associated with connections to hard-wired contacts. Both ‘wet’ and ‘dry’ contacts are supported.
The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include signals generated by the local user interface. The virtual outputs are outputs of FlexLogic™ equations used to customize the device. Virtual outputs can also serve as virtual inputs to FlexLogic equations.
The analog inputs and outputs are signals that are associated with transducers, such as Resistance Temperature Detec- tors (RTDs).
The CT and VT inputs refer to analog current transformer and voltage transformer signals used to monitor AC power lines. The UR-series relays support 1 A and 5 A CTs.
The remote inputs and outputs provide a means of sharing digital point state information between remote UR-series devices. The remote outputs interface to the remote inputs of other UR-series devices. Remote outputs are FlexLogic oper­ands inserted into IEC 61850 GSSE and GOOSE messages.
The direct inputs and outputs provide a means of sharing digital point states between a number of UR-series IEDs over a dedicated fiber (single or multimode), RS422, or G.703 interface. No switching equipment is required as the IEDs are con­nected directly in a ring or redundant (dual) ring configuration. This feature is optimized for speed and intended for pilot­aided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis.
GE Multilin D30 Line Distance Protection System 1-3
1.2 UR OVERVIEW 1 GETTING STARTED
c) UR SCAN OPERATION
The UR-series devices operate in a cyclic scan fashion. The device reads the inputs into an input status table, solves the
1
logic program (FlexLogic equation), and then sets each output to the appropriate state in an output status table. Any result­ing task execution is priority interrupt-driven.
Figure 1–3: UR-SERIES SCAN OPERATION

1.2.3 SOFTWARE ARCHITECTURE

The firmware (software embedded in the relay) is designed in functional modules that can be installed in any relay as required. This is achieved with object-oriented design and programming (OOD/OOP) techniques.
Object-oriented techniques involve the use of objects and classes. An object is defined as “a logical entity that contains both data and code that manipulates that data”. A class is the generalized form of similar objects. By using this concept, one can create a protection class with the protection elements as objects of the class, such as time overcurrent, instanta­neous overcurrent, current differential, undervoltage, overvoltage, underfrequency, and distance. These objects represent completely self-contained software modules. The same object-class concept can be used for metering, input/output control, software interface, communications, or any functional entity in the system.
Employing OOD/OOP in the software architecture of the D30 achieves the same features as the hardware architecture: modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection, transformer protection, distance protection) is constructed by combining objects from the various functional classes. This results in a common interface across the UR series.

1.2.4 IMPORTANT CONCEPTS

As described above, the architecture of the UR-series relays differ from previous devices. To achieve a general understand­ing of this device, some sections of Chapter 5 are quite helpful. The most important functions of the relay are contained in “elements”. A description of the UR-series elements can be found in the Introduction to elements section in chapter 5. Examples of simple elements, and some of the organization of this manual, can be found in the Control elements section of chapter 5. An explanation of the use of inputs from CTs and VTs is in the Introduction to AC sources section in chapter 5. A description of how digital signals are used and routed within the relay is contained in the Introduction to FlexLogic section in chapter 5.
1-4 D30 Line Distance Protection System GE Multilin
1 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE

1.3ENERVISTA UR SETUP SOFTWARE 1.3.1 PC REQUIREMENTS

The faceplate keypad and display or the EnerVista UR Setup software can be used to communicate with the relay. The EnerVista UR Setup software interface is the preferred method to edit settings and view actual values because the com­puter monitor can display more information in a simple comprehensible format.
The following minimum requirements must be met for the EnerVista UR Setup software to properly operate on a computer:
Pentium class or higher processor (Pentium II 300 MHz or higher recommended)
Windows 95, 98, 98SE, ME, NT 4.0 (Service Pack 4 or higher), 2000, XP
Internet Explorer 4.0 or higher
128 MB of RAM (256 MB recommended)
200 MB of available space on system drive and 200 MB of available space on installation drive
Video capable of displaying 800 x 600 or higher in high-color mode (16-bit color)
RS232 and/or Ethernet port for communications to the relay
The following qualified modems have been tested to be compliant with the D30 and the EnerVista UR Setup software:
US Robotics external 56K FaxModem 5686
US Robotics external Sportster 56K X2
PCTEL 2304WT V.92 MDC internal modem

1.3.2 INSTALLATION

After ensuring the minimum requirements for using EnerVista UR Setup are met (previous section), install the EnerVista UR Setup from the GE EnerVista CD. Or download the UR EnerVista software from http://www.gedigitalenergy.com/multilin and install it.
1. Insert the GE EnerVista CD into your CD-ROM drive.
2. Click the Install Now button and follow the installation instructions to install the EnerVista software.
3. When installation is complete, start the EnerVista Launchpad application.
4. Click the IED Setup section of the Launch Pad window.
1
5. In the EnerVista Launch Pad window, click the Add Product button and select the appropriate product, shown as fol­lows. Select the "Web" option to ensure the most recent software release, or select "CD" if you do not have a web con-
GE Multilin D30 Line Distance Protection System 1-5
1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED
nection, then click the Add Now button to list software items for the product. EnerVista Launchpad then obtains the software from the Internet or CD and automatically starts the installation program.
1
6. Select the complete path, including the new directory name, where the EnerVista UR Setup is to be installed.
7. Click on Next to begin the installation. The files are installed in the directory indicated, and the installation program automatically creates icons and adds EnerVista UR Setup to the Windows start menu.
8. Click Finish to complete the installation. The UR-series device is added to the list of installed IEDs in the EnerVista Launchpad window, as shown.

1.3.3 CONFIGURING THE D30 FOR SOFTWARE ACCESS

a) OVERVIEW
The user can connect remotely to the D30 through the rear RS485 port or the rear Ethernet port with a computer running the EnerVista UR Setup software. The D30 can also be accessed locally with a laptop computer through the front panel RS232 port or the rear Ethernet port using the Quick Connect feature.
To configure the D30 for remote access via the rear RS485 port, see the Configuring Serial Communications section.
1-6 D30 Line Distance Protection System GE Multilin
1 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE
To configure the D30 for remote access via the rear Ethernet port, see the Configuring Ethernet Communications sec-
tion. An Ethernet module must be specified at the time of ordering.
To configure the D30 for local access with a laptop through either the front RS232 port or rear Ethernet port, see the
Using the Quick Connect Feature section.
b) CONFIGURING SERIAL COMMUNICATIONS
Before starting, verify that the serial cable is properly connected to the RS485 terminal on the back of the device. The face­plate RS232 port is intended for local use and is not described in this section; see the Using the Quick Connect Feature section.
A GE Multilin F485 converter (or compatible RS232-to-RS485 converter) is required. Refer to the F485 instruction manual for details.
1. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or
online from http://www.gedigitalenergy.com/multilin
2. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.
3. Click the Device Setup button to open the Device Setup window and click the Add Site button to define a new site.
4. Enter a site name in the “Site Name” field. Optionally add a short description of the site along with the display order of
devices defined for the site. In this example, we use “Location 1” as the site name. Click the OK button when complete. The new site appears in the upper-left list in the EnerVista UR Setup window.
5. Click the Device Setup button, then select the new site to re-open the Device Setup window.
6. Click the Add Device button to define the new device.
7. Enter a name in the "Device Name” field and a description (optional) of the site.
8. Select “Serial” from the Interface drop-down list. This displays a number of interface parameters that must be entered
for serial communications.
). See the Software Installation section if not already installed.
1
Figure 1–4: CONFIGURING SERIAL COMMUNICATIONS
9. Enter the relay slave address, COM port, baud rate, and parity settings from the
MUNICATIONS
GE Multilin D30 Line Distance Protection System 1-7
 SERIAL PORTS menu in their respective fields.
SETTINGS PRODUCT SETUP  COM-
1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED
10. Click the Read Order Code button to connect to the D30 device and upload the order code. If a communications error
1
occurs, ensure that the EnerVista UR Setup serial communications values entered in the previous step correspond to the relay setting values.
11. Click the OK button when the relay order code has been received. The new device is added to the Site List window (or Online window) located in the top left corner of the main EnerVista UR Setup window.
The device has now been configured for RS232 communications. Proceed to the Connecting to the D30 section to begin communication.
c) CONFIGURING ETHERNET COMMUNICATIONS
Before starting, verify that the Ethernet network cable is properly connected to the Ethernet port on the back of the relay. To setup the relay for Ethernet communications, you define a Site, then add the relay as a Device at that site.The computer and UR device must be on the same subnet.
1. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or online from http://www.gedigitalenergy.com/multilin
2. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.
3. Click the Device Setup button to open the Device Setup window, then click the Add Site button to define a new site.
4. Enter the desired site name in the “Site Name” field. If desired, a short description of site can also be entered along with the display order of devices defined for the site. In this example, we use “Location 2” as the site name. Click the OK button when complete.
5. The new site appears in the upper-left list in the EnerVista UR Setup window. Click the Device Setup button then select the new site to re-open the Device Setup window.
6. Click the Add Device button to define the new device.
7. Enter the desired name in the “Device Name” field and a description (optional) of the site.
8. Select “Ethernet” from the Interface drop-down list. This displays a number of interface parameters that must be entered for proper Ethernet functionality.
). See the Software Installation section for installation details.
Figure 1–5: CONFIGURING ETHERNET COMMUNICATIONS
9. Enter the relay IP address specified in the
ADDRESS in the “IP Address” field.
1-8 D30 Line Distance Protection System GE Multilin
SETTINGS PRODUCT SETUP  COMMUNICATIONS  NETWORK IP
1 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE
10. Enter the relay slave address and Modbus port address values from the respective settings in the SETTINGS PROD-
UCT SETUP  COMMUNICATIONS  MODBUS PROTOCOL menu.
11. Click the Read Order Code button to connect to the D30 device and upload the order code. If an communications
error occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay setting values.
12. Click OK when the relay order code has been received. The new device is added to the Site List window (or Online
window) located in the top left corner of the main EnerVista UR Setup window.
The Site Device has now been configured for Ethernet communications. Proceed to the Connecting to the D30 section to begin communications.

1.3.4 USING THE QUICK CONNECT FEATURE

a) USING QUICK CONNECT VIA THE FRONT PANEL RS232 PORT
Before starting, verify that the serial cable is properly connected from the computer to the front panel RS232 port with a straight-through 9-pin to 9-pin RS232 cable.
1. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or
online from http://www.gedigitalenergy.com/multilin
2. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.
3. Click the Quick Connect button to open the Quick Connect dialog box.
). See the Software Installation section if not already installed.
1
4. Select the Serial interface and the correct COM Port, then click Connect.
5. The EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named
“Quick Connect” and displays them at the upper-left of the screen. Expand the sections to view data directly from the D30 device.
Each time that the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communi­cations to the D30 device. This ensures that configuration of the EnerVista UR Setup software matches the D30 model number.
b) USING QUICK CONNECT VIA THE REAR ETHERNET PORTS
To use the Quick Connect feature to access the D30 from a computer through Ethernet, first assign an IP address to the relay from the front panel keyboard.
1. Press the MENU key until the SETTINGS menu displays.
2. Navigate to the
3. Enter an IP address, for example “1.1.1.1,” and select the ENTER key to save the value.
4. In the same menu, select the
5. Enter a subnet IP address, for example “255.0.0.0,” and press the ENTER key to save the value.
SETTINGS PRODUCT SETUP  COMMUNICATIONS  NETWORK IP ADDRESS setting.
SUBNET IP MASK setting.
GE Multilin D30 Line Distance Protection System 1-9
1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED
842799A1.CDR
END 1 END 2 Pin Wire color Diagram Pin Wire color Diagram
1 White/orange 1 White/green 2 Orange 2 Green
3 White/green 3 White/orange 4 Blue 4 Blue 5 White/blue 5 White/blue 6 Green 6 Orange 7 White/brown 7 White/brown 8 Brown 8 Brown
1
2
3
4
5
6
7
8
Next, use an Ethernet cross-over cable to connect the computer to the rear Ethernet port. In case you need it, the figure shows the pinout for an Ethernet cross-over cable.
1
Figure 1–6: ETHERNET CROSS-OVER CABLE PIN LAYOUT
Now, assign the computer an IP address compatible with the relay’s IP address.
1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con­nections window.
2. Right-click the Local Area Connection icon and select Properties.
1-10 D30 Line Distance Protection System GE Multilin
1 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE
3. Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button.
4. Click the “Use the following IP address” box.
5. Enter an IP address with the first three numbers the same as the IP address of the D30 relay and the last number dif-
ferent (in this example, 1.1.1.2).
6. Enter a subnet mask equal to the one set in the D30 (in this example, 255.0.0.0).
7. Click the OK button to save the values.
Before continuing, test the Ethernet connection.
1. Open a Windows console window by selecting Start > Run from the Windows Start menu and typing “cmd”.
2. Type the following command, substituting the IP address of 1.1.1.1 with yours:
C:\WINNT>ping 1.1.1.1
3. If the connection is successful, the system returns four replies similar to the following:
Pinging 1.1.1.1 with 32 bytes of data:
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255 Reply from 1.1.1.1: bytes=32 time<10ms TTL=255 Reply from 1.1.1.1: bytes=32 time<10ms TTL=255 Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 4, Lost = 0 (0% loss),
Approximate round trip time in milliseconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
4. Note that the values for time and TTL vary depending on local network configuration.
5. If the following sequence of messages appears when entering the
C:\WINNT>ping 1.1.1.1 command:
1
GE Multilin D30 Line Distance Protection System 1-11
1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED
Pinging 1.1.1.1 with 32 bytes of data:
1
Request timed out. Request timed out. Request timed out. Request timed out.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milliseconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
verify the physical connection between the D30 and the laptop computer, and double-check the programmed IP address in the
PRODUCT SETUP  COMMUNICATIONS  NETWORK IP ADDRESS setting, then repeat step 2.
6. If the following sequence of messages appears when entering the
Pinging 1.1.1.1 with 32 bytes of data:
Hardware error. Hardware error. Hardware error. Hardware error.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milliseconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
verify the physical connection between the D30 and the laptop computer, and double-check the programmed IP address in the
PRODUCT SETUP  COMMUNICATIONS  NETWORK IP ADDRESS setting, then repeat step 2.
7. If the following sequence of messages appears when entering the
Pinging 1.1.1.1 with 32 bytes of data:
Destination host unreachable. Destination host unreachable. Destination host unreachable. Destination host unreachable.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milliseconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
verify the IP address is programmed in the local computer by entering the ipconfig command in the command window.
C:\WINNT>ipconfig
Windows 2000 IP Configuration
Ethernet adapter <F4FE223E-5EB6-4BFB-9E34-1BD7BE7F59FF>:
Connection-specific DNS suffix. . :
IP Address. . . . . . . . . . . . : 0.0.0.0
Subnet Mask . . . . . . . . . . . : 0.0.0.0
Default Gateway . . . . . . . . . :
Ethernet adapter Local Area Connection:
Connection-specific DNS suffix . :
IP Address. . . . . . . . . . . . : 1.1.1.2
Subnet Mask . . . . . . . . . . . : 255.0.0.0
Default Gateway . . . . . . . . . :
C:\WINNT>
It can be necessary to restart the computer for the change in IP address to take effect (Windows 98 or NT).
C:\WINNT>ping 1.1.1.1 command:
C:\WINNT>ping 1.1.1.1 command:
1-12 D30 Line Distance Protection System GE Multilin
1 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE
Before using the Quick Connect feature through the Ethernet port, disable any configured proxy settings in Internet Explorer.
1. Start the Internet Explorer software.
2. Select the Tools > Internet Options menu item and click the Connections tab.
3. Click on the LAN Settings button to open the following window.
4. Ensure that the “Use a proxy server for your LAN” box is not checked.
If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon­nected from the D30 relay.
1. Start the Internet Explorer software.
2. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.
3. Click the Quick Connect button to open the Quick Connect dialog box.
1
4. Select the Ethernet interface and enter the IP address assigned to the D30, then click the Connect button. The
EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named “Quick Connect” and displays them at the upper-left of the screen.
5. Expand the sections to view data directly from the D30 device.
Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communica­tions to the D30. This ensures that configuration of the EnerVista UR Setup software matches the D30 model number.
When direct communications with the D30 via Ethernet is complete, make the following changes:
1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con-
nections window.
2. Right-click the Local Area Connection icon and select the Properties item.
3. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button.
GE Multilin D30 Line Distance Protection System 1-13
1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED
4. Set the computer to “Obtain a relay address automatically” as shown.
1
If this computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been discon­nected from the D30 relay.
AUTOMATIC DISCOVERY OF ETHERNET DEVICES
The EnerVista UR Setup software can automatically discover and communicate to all UR-series IEDs located on an Ether­net network.
Using the Quick Connect feature, a single click of the mouse triggers the software to automatically detect any UR-series relays located on the network. The EnerVista UR Setup software then proceeds to configure all settings and order code options in the Device Setup menu. This feature allows the user to identify and interrogate all UR-series devices at a loca­tion.
1-14 D30 Line Distance Protection System GE Multilin
1 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE
842743A3.CDR
Communications status indicators:
Green = OK Red = No communications UR icon = report is open
Quick action hot links
Expand the site list by double-clicking or selecting the +/– box.
NOTE

1.3.5 CONNECTING TO THE D30 RELAY

1. Open the Display Properties window through the Site List tree as shown. The Display Properties window opens with a
status indicator on the lower left of the EnerVista UR Setup window.
1
2. If the status indicator is red, verify that the Ethernet network cable is properly connected to the Ethernet port on the
back of the relay and that the relay has been properly setup for communications (steps A and B earlier).
If a relay icon appears in place of the status indicator, than a report (such as an oscillography or event record) is open. Close the report to re-display the green status indicator.
3. The Display Properties settings can now be edited, printed, or changed.
See chapter 4 in this manual or the EnerVista UR Setup Help File for information about the using the EnerVista UR Setup software interface.
QUICK ACTION HOT LINKS
The EnerVista UR Setup software has several quick action buttons to provide instant access to several functions that are often performed when using D30 relays. From the online window, users can select the relay to interrogate from a pull-down window, then click the button for the action they want to perform. The following quick action functions are available:
View the D30 event record
View the last recorded oscillography record
View the status of all D30 inputs and outputs
View all of the D30 metering values
View the D30 protection summary
Generate a service report
GE Multilin D30 Line Distance Protection System 1-15
1.4 UR HARDWARE 1 GETTING STARTED

1.4UR HARDWARE 1.4.1 MOUNTING AND WIRING

1
See Chapter 3: Hardware for mounting and wiring instructions.

1.4.2 COMMUNICATIONS

The EnerVista UR Setup software communicates to the relay via the faceplate RS232 port or the rear panel RS485 / Ether­net ports. To communicate via the faceplate RS232 port, a standard straight-through serial cable is used. The DB-9 male end is connected to the relay and the DB-9 or DB-25 female end is connected to the computer COM2 port as described in the CPU communications ports section of chapter 3.
Figure 1–7: RELAY COMMUNICATION OPTIONS
To communicate through the D30 rear RS485 port from a computer RS232 port, the GE Multilin RS232/RS485 converter box is required. This device (catalog number F485) connects to the computer using a straight-through serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the D30 rear communications port. The converter terminals (+, –, GND) are connected to the D30 communication module (+, –, COM) terminals. See the CPU communica- tions ports section in chapter 3 for details. The line is terminated with an R-C network (that is, 120 , 1 nF) as described in the chapter 3.

1.4.3 FACEPLATE DISPLAY

All messages are displayed on a backlit liquid crystal display (LCD) to make them visible under poor lighting conditions. While the keypad and display are not actively being used, the display defaults to user-defined messages. Any high-priority event-driven message automatically overrides the default message and appears on the display.
1-16 D30 Line Distance Protection System GE Multilin
1 GETTING STARTED 1.5 USING THE RELAY

1.5USING THE RELAY 1.5.1 FACEPLATE KEYPAD

Display messages are organized into pages under the following headings: actual values, settings, commands, and targets. The MENU key navigates through these pages. Each heading page is divided further into logical subgroups.
The MESSAGE keys navigate through the subgroups. The VALUE keys increment or decrement numerical setting values when in programming mode. These keys also scroll through alphanumeric values in the text edit mode. Alternatively, val­ues can be entered with the numeric keypad.
The decimal key initiates and advances to the next character in text edit mode or enters a decimal point.
The HELP key can be pressed at any time for context-sensitive help messages.
The ENTER key stores altered setting values.

1.5.2 MENU NAVIGATION

Press the MENU key to select a header display page (top-level menu). The header title appears momentarily followed by a header display page menu item. Each press of the MENU key advances through the following main heading pages:
Actual values
Settings
Commands
Targets
User displays (when enabled)

1.5.3 MENU HIERARCHY

1
The setting and actual value messages are arranged hierarchically. The header display pages are indicated by double scroll bar characters (), while sub-header pages are indicated by single scroll bar characters (). The header display pages represent the highest level of the hierarchy and the sub-header display pages fall below this level. The MESSAGE UP and DOWN keys move within a group of headers, sub-headers, setting values, or actual values. Continually pressing the MESSAGE RIGHT key from a header display displays specific information for the header category. Conversely, contin­ually pressing the MESSAGE LEFT key from a setting value or actual value display returns to the header display.
HIGHEST LEVEL LOWEST LEVEL (SETTING
VALUE )
 SETTINGS  PRODUCT SETUP
 SETTINGS  SYSTEM SETUP
The relay is in the default “Not Programmed” state when it leaves the factory. When powered up successfully, the Trouble LED is on and the In Service LED off. The relay in the “Not Programmed” state blocks signaling of any output relay. These conditions remain until the relay is explicitly put in the “Programmed” state.
Select the menu message
RELAY SETTINGS: Not Programmed
SETTINGS PRODUCT SETUP  INSTALLATION RELAY SETTINGS
PASSWORD SECURITY
ACCESS LEVEL: Restricted

1.5.4 RELAY ACTIVATION

1. To put the relay in the “Programmed” state, press either of the VALUE keys once and then press ENTER. The face-
plate Trouble LED turns off and the In Service LED turns on.
GE Multilin D30 Line Distance Protection System 1-17
1.5 USING THE RELAY 1 GETTING STARTED
NOTE
The settings for the relay can be programmed manually (see Chapter 5) via the faceplate keypad or remotely via the EnerVista UR Setup software (see the EnerVista UR Setup help file).
1

1.5.5 RELAY PASSWORDS

It is recommended that passwords be set for each security level and assigned to specific personnel. There are two user security access levels, COMMAND and SETTING.
1. COMMAND
The COMMAND access level restricts the user from making any settings changes, but allows the user to perform the fol­lowing operations:
Operate breakers via faceplate keypad
Change state of virtual inputs
Clear event records
Clear oscillography records
Operate user-programmable pushbuttons
2. SETTING
The SETTING access level allows the user to make any changes to any of the setting values.
See the Changing Settings section in Chapter 4 for complete instructions on setting security-level passwords.

1.5.6 FLEXLOGIC™ CUSTOMIZATION

FlexLogic equation editing is required for setting user-defined logic for customizing the relay operations. See the FlexLogic section in Chapter 5.
1-18 D30 Line Distance Protection System GE Multilin
1 GETTING STARTED 1.5 USING THE RELAY

1.5.7 COMMISSIONING

The D30 requires minimal maintenance after it is commissioned into service. Since the D30 is a microprocessor-based relay, its characteristics do not change over time. As such, no further functional tests are required.
The D30 performs a number of continual self-tests and takes the necessary action in case of any major errors (see the Relay Self-tests section in chapter 7). However, it is recommended that D30 maintenance be scheduled with other system maintenance. This maintenance can involve in-service, out-of-service, or unscheduled maintenance.
In-service maintenance:
1. Visual verification of the analog values integrity, such as voltage and current (in comparison to other devices on the
corresponding system).
2. Visual verification of active alarms, relay display messages, and LED indications.
3. LED test.
4. Visual inspection for any damage, corrosion, dust, or loose wires.
5. Event recorder file download with further events analysis.
Out-of-service maintenance:
1. Check wiring connections for firmness.
2. Analog values (currents, voltages, RTDs, analog inputs) injection test and metering accuracy verification. Calibrated
test equipment is required.
3. Protection elements setting verification (analog values injection or visual verification of setting file entries against relay
settings schedule).
4. Contact inputs and outputs verification. This test can be conducted by direct change of state forcing or as part of the
system functional testing.
5. Visual inspection for any damage, corrosion, or dust.
6. Event recorder file download with further events analysis.
7. LED Test and pushbutton continuity check.
Unscheduled maintenance, such as a disturbance causing system interruption:
1. View the event recorder and oscillography or fault report for correct operation of inputs, outputs, and elements.
If it is concluded that the relay or one of its modules is of concern, contact GE Multilin for service.
1
GE Multilin D30 Line Distance Protection System 1-19
1
1.5 USING THE RELAY 1 GETTING STARTED
1-20 D30 Line Distance Protection System GE Multilin