GE AZ61H15DAD, AZ41E15DAC AZ61H15DAD Architect and Engineering Manual

LEADERS IN
EFFICIENCY
GE ZONELINE
ARCHITECTS AND ENGINEERS DATA MANUAL
GE Zoneline packaged terminal air conditioners
®
QUICK REFERENCE
Full Specs on pages 54 and 55
ALL UNITS REQUIRE POWER CONNECTION KIT
Power Connection Kit determines resistance heat output 7000 BTUH units are not offered with 4.7 KW resistance heater
4100 series cooling with electric heat
MODEL
NUMBER
AZ41E07DAB
AZ41E09DAB
AZ41E12DAB
AZ41E15DAB
AZ41E07EAB 265 7200 12.3 580 AZ41E09EAB 265 9700 12.0 805 AZ41E12EAB 265 11800 11.1 1025 AZ41E15EAB 265 14300 10.3 1385
VOLTAGE
208 6900 12.3 560 230 7200 12.3 580 208 9600 12.0 795 230 9700 12.0 805 208 11500 11.1 1035 230 11800 11.1 1060 208 14000 10.3 1350 230 14300 10.3 1370
COOLING
(BTUH)
EER WATTS
4100 series cooling with electric heat (corrosion treated models)
MODEL
NUMBER
AZ41E07DAC
AZ41E09DAC
AZ41E12DAC
AZ41E15DAC
AZ41E07EAC 265 7200 12.3 580 AZ41E09EAC 265 9700 12.0 805 AZ41E12EAC 265 11800 11.1 1025 AZ41E15EAC 265 14300 10.3 1385
VOLTAGE
208 6900 12.3 560 230 7200 12.3 580 208 9600 12.0 795 230 9700 12.0 805 208 11500 11.1 1035 230 11800 11.1 1060 208 14000 10.3 1350 230 14300 10.3 1370
COOLING
(BTUH)
EER WATTS
Dry Air 25 4100 series cooling with electric heat
MODEL
NUMBER
AZ41E07DAP
AZ41E09DAP
AZ41E12DAP
AZ41E07EAP 265 6500 11.7 555 AZ41E09EAP 265 9200 11.5 795 AZ41E12EAP 265 11200 10 .8 1020
Specifications subject to change.
2
VOLTAGE
208 6300 11.7 535 230 650 0 11.7 555 208 8800 11.5 765 230 9200 11.5 790 208 110 00 10.8 1015 230 11200 10.8 1035
COOLING
(BTUH)
EER WATTS
4100 and 6100 Series Control Panel
QUICK REFERENCE
Full Specs on pages 54 and 55
ALL UNITS REQUIRE POWER CONNECTION KIT
Power Connection Kit determines resistance heat output 7000 BTUH units are not offered with 4.7 KW resistance heater
6100 series heat pump with backup electric heat
MODEL
NUMBER
AZ61H07DAB
AZ61H09DAB
AZ61H12DAB
AZ61H15DAB
AZ61H07EAB 265 7000 12.8 545 6200 3.9 450 AZ61H09EAB 265 9400 12.2 765 8100 3.6 655 AZ61H12EAB 265 11700 11.6 1000 10700 3.6 870 AZ61H15EAB 265 14400 10.6 1355 13500 3.3 1165
VOLTAGE
208 6900 13.0 525 6100 3.9 445 230 7100 13.0 545 6200 3.9 465 208 9100 12.2 740 8100 3.7 635 230 9400 12.2 755 8300 3.7 650 208 11600 11.6 965 10400 3.6 835 230 11700 11.6 985 10600 3.6 855 208 14200 10.6 1335 13400 3.3 1120 230 14500 10.6 1360 13500 3.3 1165
COOLING
(BTUH)
EER WATTS
HEATING
(BTUH)
COP WATTS
6100 series heat pump with backup electric heat (corrosion treated models)
MODEL
NUMBER
AZ61H07DAC
AZ61H09DAC
AZ61H12DAC
AZ61H15DAC
AZ61H07EAC 265 7000 12.8 545 6200 3.9 450 AZ61H09EAC 265 9400 12.2 765 8100 3.6 655 AZ61H12EAC 265 11700 11.6 1000 10700 3.6 870 AZ61H15EAC 265 14400 10.6 1355 13500 3.3 1165
VOLTAGE
208 6900 13.0 525 6100 3.9 445 230 7100 13.0 545 6200 3.9 465 208 9100 12.2 740 8100 3.7 635 230 9400 12.2 755 8300 3.7 650 208 11600 11.6 965 10400 3.6 835 230 11700 11.6 985 10600 3.6 855 208 14200 10.6 1330 13400 3.3 1155 230 14500 10.6 1350 13500 3.3 1190
COOLING
(BTUH)
EER WATTS
HEATING
(BTUH)
COP WATTS
6100 series heat pump with backup electric heat (models featuring ICR - internal condensate removal)
MODEL
NUMBER
AZ61H07DAD
AZ61H09DAD
AZ61H12DAD
AZ61H15DAD
AZ61H07EAD 265 6900 12.7 540 6200 3.9 455 AZ61H09EAD 265 9200 11.9 760 8200 3.6 665 AZ61H12EAD 265 11700 11.4 1015 10900 3.6 880 AZ61H15EAD 265 14300 10.4 1355 13500 3.2 1210
VOLTAGE
208 6900 12.7 530 6100 3.9 440 230 7000 12.7 550 6200 3.9 465 208 9100 11.9 750 8000 3.6 640 230 9200 11.9 760 8100 3.6 655 208 11600 11.4 960 10400 3.6 835 230 11700 11.4 980 10600 3.6 855 208 14100 10.4 1330 13400 3.2 1200 230 14300 10.4 1345 13500 3.2 1200
COOLING
(BTUH)
EER WATTS
HEATING
(BTUH)
COP WATTS
POWER CONNECTION KITS
230/208-Volt Line-Cord Connection Units
Line Cord
Kit
RAK3153A 8150/7900 2450/2360 11.0/11.6 15 RAK3203A 11200/10900 3350/3230 15.1/16.0 20 RAK3303A 16000/15450 4750/4580 21.2/22.4 30
Elect ric Heat Amps include electric heater and fan motor cur rent draw. Each Line-Cord Kit has an integral Leakage Current Detec tion and Interruptio n (LCDI) or Arc Fault Current Interrupter (AFCI) device as required by National Electrical Code (NEC) and Underwriters Labora tories (UL) for units manufac tured after August 1, 20 04.
Electric
Heat
BTUH
Electric
Heater
Watts
Electric
Heat
Amps
Min. Circuit
Protection
(Amps)
230/208-Volt Sub-Base and Direct-Connected Units
Sub-Base
Connection
Kit
RAK204D15P RAK4157 8150/7900 2450/2360 11.0/11.6 15 RAK204D20P RAK4207 11200/10900 3350/3230 15.1/16.0 20 RAK204D30P RAK4307 16000/15450 4750/4580 21.2/22.4 30
Elect ric Heat Amps include electric heater and fan motor cur rent draw. Units connec ted through sub-base do not require an LCDI or AFCI device since they are not considered to be line-cord connected. Each 230/208-volt sub-base kit consists of sub-base with appropriate receptacle for min imum circuit amp erage, chaseway to route p ower connector from sub-base to chassis, wiring to connect sub-base to building wiring and a short line cord with 9-pin connector to connect to chassis and plug into receptacle in sub-base. Short sub-b ase line cord may not be used without sub-base. Junction box for 230/208-volt cha ssis mu st be purchased separa tely. RAK4002A for 2900, 3900, 4100, and 6100 series units, RAK4002B for 5800 series units.
Direct
Electric
Heat
BTUH
Electric
Heater
Watts
Electric
Heat
Amps
Min. Circuit
Protection
265-Volt Sub-Base and Direct-Connected Units
Sub-Base
RAK204E15 RAK5172 RAK5157 8150 2460 9.6 15 RAK204E20 RAK5202 RAK5207 11550 3460 13.3 20 RAK204E30 RAK5302 RAK5307 16350 4860 18.6 30
Elect ric Heat Amps include electric heater and fan motor cur rent draw. 265-volt units are to be per manently connected i n compliance with National Ele ctrical Code and local codes a nd have a factor y-installed junction box on the chassis. Each 265-volt sub-base kit consi sts of sub-ba se with a ppropriate re ceptacle for minimum circuit amperage, chaseway to route power connector from sub-base to chassis and wiring to connect su b-base to building wiring.
265-Volt Power Connection Kit mu st be orde red separately.
Power
Connection Kit
Direct
Connection Kit
Electric Heat
BTUH
Electric Heater
Watts
Electric Heat
Amps
Min. Circuit Protection
(Amps)
Important
(Amps)
Essential Elements Ordering Overview
230/208-volt line-cord connected units — order line cord kit 230/208-volt sub-base connected units — order sub-base 265-volt units — order sub-base and power connection kit
®
ZONELINE
CHASSIS NOMENCLATURE
The Zoneline chassis is identified by a model number defining the type of unit, cooling capacity, electrical information and optional features included on the unit. When specifying or ordering the Zoneline chassis, the use of this nomenclature will assure receiving the correct unit.
EXAMPLE
AZ61H12DAD
Zoneline
packaged terminal chassis
Chassis series
41= deluxe line cool/
electric heat
61=deluxe line heat pump
Unit type
E= cooling with electric
resistance heat
H= heat pump with electric
resistance heat
Nominal cooling capacity
07=7,000 BTUH cooling 09=9,000 BTUH cooling 12=12,000 BTUH cooling 15=15,000 BTUH cooling
Voltage/Phase/ Frequency
D= 230/208-Volt,
single-phase, 60 Hz
E= 265-Volt, single-phase,
60 Hz
Universal power connection
Special Features
B=base unit C=corrosion treated D= internal
condensate removal (ICR) system (heat pump models only) (not for coastal areas)
P= Dry Air 25 (4100
Series only)
Specifications subject to change.
4
The Zoneline 4100 and 6100 Series have incorporated changes suggested by customers, along with enhancements by GE’s Technology Team and changes necessary to meet new UL and NEC requirements.
“L” shaped condenser coil.
Cross-flow blower across the product line for quieter operation.
The “Partial Open Vent Air” feature was a specific request by a customer.
“Heat Sentinel” is an enhancement developed by GE’s Technology Team to help lodging professionals welcome their guests with a moderate-temperature room and to help lower cooling costs.
Devices have been added on cord-connected units to protect against injury from unsafe power cords.
See the “Features and Benefits” section for in-depth explanation of these changes and the industry-leading features of GE Zoneline retained from the previous series.
The Deluxe 4100 Series Zoneline models include The “Dry Air 25” models, which remove 25% more moisture than other Zoneline models.
As warm, humid air is pulled through the pre-cool (front) section of the heat pipe, the heat removed from the air is absorbed by the refrigerant, causing the refrigerant to change to a gas and flow to the re-heat (rear) section of the heat pipe. The air leaving the pre-cool section of the heat pipe is cooler and at a higher relative humidity level than the room air. The pre-cooled air is further cooled as it passes through the evaporator, consequently allowing the evaporator coil to remove more moisture.
When the cold air from the evaporator comes in contact with the re-heat section of the heat pipe, the heat that was removed by the pre-cool section is added back to the air
Deluxe Dry Air 25 Models
Cooling With Resistance Heat
• Removes 25% more moisture than standard Zoneline models
• Cools and dries air in less time than standard Zoneline models
• Dry Air is a separate sealed refrigerant system — No mechanical parts — No special maintenance required
• Helps maintain lower relative humidity in rooms
• Maintains comfort at slightly higher room temperatures — Reduces operating costs — Provides comfort without
overcooling
• Corrosion treatment is standard
• Excellent choice for humid climates
• Available in 7,000, 9,000 and 12,000 BTU sizes The Dry Air 25 system, a heat pipe, is a hermetically sealed
heat transfer surface installed in a “saddlebag” configuration around the indoor (evaporator) coil of the Zoneline unit. This coil arrangement will transfer heat from the front coil of the saddlebag to the rear coil without power consumption. This assembly uses R-410A as the refrigerant and is not connected to the regular Zoneline refrigerant circuit.
and the refrigerant in the heat pipe condenses and flows back to the pre-cool (front) section. The air discharged into the room by this process is much drier, creating a more comfortable room condition.
The Dry Air 25 models center around GE’s exclusive use of the patented Dinh® Dehumidifier Heat Pipe from Heat Pipe Technology, Inc. This innovative NASA spin-off technology enables Dry Air 25 to remove 25% more moisture from the air than other leading manufacturers’ packaged terminal air conditioners. This helps maintain room comfort at a higher room temperature, reducing operating costs.
The Dry Air 25 keeps a room cool and dry, and this is the most important benefit when it comes to the occupant of the room—hotel guests, apartment residents, students. In a hot, humid climate, getting away from the humidity is just as important as getting away from the heat, and the Dry Air 25 is the perfect solution. The dehumidification of the Dry Air 25 has been verified by the same AHRI test conditions under which standard units are rated.
Specifications subject to change.
5
TABLE OF CONTENTS
Front Cover 1
Mini Specs 4100 and 6100 Series 2–3
Mini Specs Power Connection Kits and Nomenclature 4
The 4100/6100 and Dry Air 25 5
Tab le of Conte nts 6
Introduction 7
®
The Zoneline
Features and Benefits
Features Table 9
Features and Benefits 10–12
Auxiliary Control Settings 13–14
Central Desk Control 15
Remote Thermostat Control 16–18
Heat Pumps and Energy Savings 19–20
Installation and Dimensions
Application Comments 21
Case Dimensions 22
Wall Case/Sub-Base Installation 23–34
Condensate Disposal Systems 35–37
Ducted Installations 38–40
Exterior Grilles 41–42
System 8
Product Data
Electrical Connection 43
Essential Elements Ordering Overview 44
Maximum Connected Load 45
Latent System Capacity 45
Normal Yearly Operating Data 46
Schematics 47–50
Product Specifications
Suggested Bid Form Specifications 51–52
Zoneline Chassis Nomenclature/Receptacles/Sub-Bases 53
Preliminary Specifications 54–55
Complete Accessory List 56
General Installation Suggestions 57–58
Warranty 58
Alphabetical Index 59
Back Cover 60
Important Notice
Equipment used as a primary source for heating or cooling is an integral part of the building in which it is installed. Proper application is essential for satisfactory performance over a wide range of operating conditions. It is strongly recommended that a professional engineer determine proper application.
If the unit is a replacement unit, its specifications and performance may differ from those of the unit it is replacing. For that reason, we again strongly recommend that a professional engineer determine proper application.
6
INTRODUCTION
This manual is designed to provide product, performance and application information to our customers and their architects and engineers for use in selection and design of a zonal comfort control system utilizing GE Zoneline Packaged Terminal Air Conditioners (PTAC) and Packaged Terminal Heat Pumps (PTHP). GE Zoneline PTACs and PTHPs are self-contained units designed for through-the-wall installations in hotels, motels, apartments, hospitals, nursing homes, add-on rooms and many other installations.
Zoneline units provide individual room or zone control in both cooling and heating operation. There is a model for practically every application, ranging in cooling capacity from 7,200 to 14,500 BTUH and heating capacity from 6,200 to 13,500 BTUH in heat pump operation. See pages 42 and 52 for resistance heaters available.
The Deluxe Line consists of the 4100 Series with electric resistance heat, the 4100 Series Dry Air 25 Models with enhanced dehumidification for hot and humid climates and the 6100 Series heat pump. The 6100 Series heat pump features reverse-cycle defrost and simultaneous supplemental resistance heat, when needed, to maintain room comfort. Both offer tactile touch controls with digital display and optional corrosion protection.
Deluxe Line Standard Features:
• Two-fan-motor system with indoor cross-flow blower for quieter operation
• Digital Controls
—LED Temperature Display —Easy Temperature Selection —Tactile Touch Pad
• Universal Heaters
• Heat Sentinel
• “L” Coil Design Condenser
• 3-Position Vent Door
• Freeze Sentinel
• Indoor Coil Frost Control
• Central Desk Control Interface
• Remote Thermostat Control Interface
• Random Restart
• Electronic Temperature Limiting
• “Smart Fan” Fan Cycle/Continuous Control
• Transfer Fan Interface
• Reverse Cycle Defrost and Simultaneous Supplemental Resistance Heat on Heat Pumps
• Quick Heat Recovery
Deluxe Line Optional Features:
• Corrosion Protection
• Internal Condensate Removal (on 6100 Series Heat Pump without Corrosion Protection)
NOTE: Dry Air 25 models include all the standard features of the
4100 Series plus standard corrosion protection.
Advantages of the GE Zoneline System:
• Flexible Application
— May be installed from flush to finished floor,
to 3" from the ceiling — 7,200 to 14,500 BTUH units in same physical size — Deluxe 4100 and 6100 Series may be ducted to
condition more than one room — Compatible with Class 2 remote thermostat control — Compatible with 2-wire CDC or many Energy
Management Systems
• Economical Installation — No ductwork necessary — No mechanical equipment rooms or pipes required
for heating/cooling units — Replacement units fit existing 42"-wide by 16"-high
wall cases
• Quiet Operation — Indoor cross-flow blower
• Energy-Saving Operation — Units in unoccupied areas may be turned off — Designed for efficient cooling operation — EERs from
10.3 to 13.0 — Efficient heat pump units — COPs from 3.3 to 3.9 — Extended heat pump operation without sacrificing
room comfort
• Ease of Maintenance — Permanently lubricated fan motors — Upfront lift-out interchangeable filters — Slide-out chassis for easy access for cleaning or if
service is required
• Reverse Cycle Heat Pump Operation The 6100 Series heat pumps utilize the unique GE PTAC
heat pump operation to ensure a comfortable room. The logic used by the units is the same logic used by central system heat pumps to provide greater savings.
Specifications subject to change.
7
THE ZONELINE® SYSTEM
The typical Zoneline installation consists of the wall case (or sleeve), chassis, power cord and exterior grille. Some installations may use a sub-base for support of the unit or for ease of electrical connections. Each of the components should be the standard products offered by GE, or, in the case of the exterior grille, approved by GE Applications Engineering. Use of components not specifically designed or approved for use with the Zoneline unit can result in unsatisfactory operation and can be the cause of failure not covered by the warranty.
Components of the Zoneline System
Typical Installation
Chassis
Room Cabinet
(Deluxe Series shown)
Wall Case RAB71A (Steel-Insulated) RAB77A4 (SMC — Molded) Wall Case Options (See pages 22-23)
RAG67 (shown) Grille Options (See page 41)
Power Connection Kit (required on all units) Line Cord Kit shown See pages 43-44
Power Supply Cord
Optional Accessories of the Zoneline System
Chaseway
RAK204D20P Sub-Base (shown)
Power Supply Cord (included with certain 208V/230V sub-bases)
See pages 23 and 33 for information on electrical sub-bases and chaseway. See pages 38-40 for information on ducted installations.
8
RAK6052 Duct Adapter
RAK601/602 Duct Extension, Register and Trim Flange
ZONELINE FEATURES
Resistance heat Heat pump
AZ
41 Series
Cooling EER range (230 Volts/265 Volts) 10.6 - 12.8 11.3 - 12.2 10.8 - 13.2 Heating COP range (230 Volts/265 Volts) N/A N/A 3.3 - 4.0 Refrigerant type R-410A R-410A R-410A Cross-flow (tangential) blower Standard Standard Standard Enhanced dehumidification Optional Standard — Heat pump with resistance heat back-up Standard Heat pump with supplemental resistance heat Standard Staged heating 3-Stage*** Universal heaters - UPC** Standard Standard Standard Tactile touch-pad controls with LED Standard Standard Standard Touch control set-up features Standard Standard Standard Highly featured microcomputer controls Standard Standard Standard Electric resistance heat lock-out (above 46°F) Standard Automatic emergency heat Standard Standard Standard Heat pump defrost system Reverse cycle High-temperature operation protection Standard Quick heat recovery Standard Heat boost Selectable Separate indoor & outdoor
motors — permanently lubricated 2-speed outdoor fan Standard Standard Standard Indoor fan speed settings Hi/Low Hi/Low Hi/Low "Fan Only" setting—2-speed Hi/Low Hi/Low Hi/Low "Cool & Heat Only" settings Hi/Low/Auto Hi/Low/Auto Hi/Low/Auto “SmartFan” fan cycle control Standard Standard Standard Auto power recovery Standard Standard Standard Automatic compressor restart delay Standard Standard Standard Freeze Sentinel (41F) Standard Standard Standard Heat Sentinel (85F) Standard Standard Standard Automatic indoor frost control Standard Standard Standard Temperature limiting Electronic 7-step Electronic 7-step Electronic 7-step Solid-state thermostat Standard Standard Standard Remote thermostat compatibility Standard Standard Standard Central Desk Control compatibility Standard Standard Standard 2-position discharge grille 50º/40º Standard Standard Standard Upfront filter (interchangeable) Standard Standard Standard 3-position manual air vent control Standard Standard Standard Sleep function Standard Standard Standard Transfer fan connections Standard Standard Standard Ducted installation capability Optional Optional Optional Corrosion-treated chassis Optional Standard Optional Internal condensate removal (ICR)* Optional
*Not for use in corrosive environments **UPC — Universal Power Cord Connection (see pages 43 and 53). *** Two-stage heating if using remote thermostat 265-volt units must be connected in a manner to meet National Electrical Code and all local codes.
AC AC DC
AZ
41 Dry Air 25
AZ
61 Series
Specifications subject to change.
9
FEATURES AND BENEFITS
Standard Physical Dimensions
GE has maintained the same dimensions since 1961 — 42" wide x 16" high x 13-3/4" deep — making replacement of older units easy.
Weather-Protected Electrical Components
Vital electrical components are protected from the weather by locating them on the indoor side of the weather barrier.
Weather-Resistant “Superseal”
Properly installed unit in undistorted case keeps air leakage to a minimum.
7 CFM air infiltration with 25 MPH wind on ICR units — even less on units without ICR
Industry specification is 19 CFM of air infiltration
Heater Sizes to Meet Room Requirements
All units are equipped with a universal heater
the resistance heat output is determined by power connection kit.
230/208-volt — Line-Cord Connected Units
2.4/2.32 KW with RAK3153A — 15-amp circuit
3.3/3.20 KW with RAK3203A — 20-amp circuit
4.7/4.53 KW with RAK3303A — 30-amp circuit
230/208-volt - Sub-Base Connected Units
2.4/2.32 KW with RAK204D15P — 15-amp circuit
3.3/3.20 KW with RAK204D20P — 20-amp circuit
4.7/4.53 KW with RAK204D30P — 30-amp circuit
265-volt
2.4 KW with RAK5172 — 15-amp circuit
3.4 KW with RAK5202 — 20-amp circuit
4.8 KW with RAK5302 — 30-amp circuit
Automatic Emergency Heat
Automatically uses electric resistance heat if the heat pump output is not sufficient to maintain selected room temperature.
Reverse Cycle Heat Pump Defrost System
Standard on all Zoneline 6100 Series heat pumps
Enables heat pump to operate at lower temperatures when other systems switch to more expensive electric resistance heat.
See pages 18 and 19 for discussion of heat pump operation and defrost systems.
High-Temperature Heat Pump Operation Protection
Automatically protects the compressor if heat pump is operated with high outdoor temperatures.
Power to the outdoor fan is turned off if the indoor coil gets too hot during heat pump operation to prevent damage to the compressor.
Quick Heat Recovery – Heat Pump Units
When the unit operation is changed from STOP or COOL to HEAT, the electric resistance heaters are used to warm the room to the thermostat set point. This provides faster room temperature increase for greater guest comfort.
Fan Motors – Permanently Lubricated
All units have two fan motors for quiet operation and maximum operating efficiency.
Motors are permanently lubricated to reduce maintenance and totally enclosed to keep dirt and water out of the motor windings.
Unit Controls
4100 and 6100 Series — touch pad controls with digital
readout of temperature set point
Highly Featured Microprocessor Controls
Microprocessor controls are programmed to interface with the temperature sensors to maximize comfort conditions for the room occupant and provide outstanding features.
Thermistors are used to sense small changes in temperature to give excellent room control and allow the microprocessor to monitor and react to changing conditions.
Electric Resistance Heat Lock-Out
To maximize the savings of the heat pump operation, the Zoneline® heat pumps do not utilize the resistance heater when the outdoor temperature is above 46°F during normal operation. The resistance heat is used in the Quick Heat Recovery feature.
10
Outdoor Fan
The unit automatically selects the most efficient speed for the outdoor fan. The operating sound level is lower when the outdoor fan can operate in low speed, yet there are situations where it must operate in high speed. The unit changes the fan speed automatically.
Indoor Fan Speed Selections – HIGH/LOW
Unit may be operated in HIGH HEAT or LOW HEAT or HIGH COOL or LOW COOL.
FEATURES AND BENEFITS (cont)
Fan-Only Setting – HIGH/LOW
The unit provides the option of selecting either HIGH or LOW speed for Fan-Only operation.
Fan-Cycle Switch – “SmartFan”
Unique “SmartFan” allows unit to operate fan continuously in cooling operation and fan cycle in heating to provide better guest comfort. Eliminates complaint of cold-air draft during the heating season.
Eliminates the need for changing fan-cycle switch seasonally.
“SmartFan” settings are controlled via the auxiliary control setting push button.
Compressor Random Restart
In the event of a power failure, all compressors attempting to restart immediately when power is restored can result in a power surge that can cause another power interruption.
The microprocessors in the Zoneline units have a random restart logic system that prevents all units from starting at the same time.
Rotary Compressor
Provides smoother operation for quiet, dependable service. GE has used rotary compressors since 1961.
Compressor Restart Delay
Zoneline units are designed to provide a minimum of three minutes of compressor-off time to allow refrigerant pressures to equalize before restarting to prevent compressor damage.
Zoneline units are also designed to provide a minimum of three minutes of compressor-run time to prevent room occupant disturbance due to short-cycling of the air conditioner.
Freeze Sentinel
Detects low room temperature and turns on heater to help protect against damage caused by freezing room temperature.
Heater turns on at 41°F and warms indoor thermistor temperature to 46°F and shuts off.
Freeze Sentinel may be turned off by dip switch on auxiliary control.
Heat Sentinel
The property owner may choose to activate the Heat Sentinel feature on the Zoneline unit. If the Heat Sentinel is activated and room temperature reaches 85°F (even when the unit is in the “STOP” setting), the unit will automatically start in air conditioning operation and will shut off when the room temperature reaches 80°F. This will help dehumidify the air and lower high temperatures so the guest will not be entering an extremely hot room.
Indoor Coil Frost Control
Prevents indoor coil from freezing and causing complaints due to lack of cooling. Frost can form on the indoor coil when the unit is operated in cooling when outdoor temperatures are low. The unit automatically shuts the compressor off until the indoor coil temperature warms to the point where frosting will no longer occur.
Trans fer Fan Inter face
24 VAC terminals are provided to operate a relay to control a fan mounted in a wall to move conditioned air into another space. The electrical power for the operation of the transfer fan itself is not provided by the Zoneline unit. Transfer fans and their controlling relays are field supplied.
Electronic Temperature Limiting
Seven independent programmable heating temperature limits and seven independent programmable cooling temperature limits.
Heating Temperature Limits
65 70 72 74 76 78 80 85
Lowest
Cool
60 64 66 68 70 72 74 76
Limits are set via the auxiliary control setting push button.
Cooling Temperature Limits
Highest
Heat
Remote Control Capability with Wall-Mounted Thermostat
See pages 16–18.
Central Desk Control Capability
See page 15.
Energy Management System Interface with Load-Shedding Option
All units have a switch via the auxiliary control setting to allow the indoor fan to continue operating if the unit is connected to an energy management system that shuts off compressor or heater operation. By allowing the indoor fan to run when the heater or compressor is shut off by the energy management system, the guest is less likely to realize the operation of the unit has been altered. This helps reduce peak energy demand loads without disturbing the room occupant.
Reversible Indoor Air Louvers
Allows air to be directed into room at 40º or 50º angle to provide better air distribution.
Angle is changed by removing room front and screws holding louver in place, and rotating louver section.
11
FEATURES AND BENEFITS (cont)
Up-Front Air Filters
Two interchangeable up-front filters, easy to remove and reinstall, may be cleaned without opening or removing the room front.
Clean filters by brushing, vacuuming or back­flushing under faucet or shower head.
Concealed Manual Vent Control
Open ventilation doors on GE Zoneline® Packaged Ter minal Air Con ditione rs and Heat Pumps allow outside air to enter the room through a screen-covered opening in the weather barrier that separates the indoor and outdoor sections of the unit.
A concealed lever, located along the left side of the unit under the front cover, is used to open and close the vent door.
The 3-position manual vent door control may be closed, partially open or fully open. Positive vent door closure prevents accidental opening and unwanted air infiltration.
Vent CFM High Speed
Unit Full Open Partial Open
7000 50 40
9000 70 45
12000 75 45
15000 75 45
CFM ratings at 230 and 265 volts.
For each CFM of air to enter the room, an equal amount of air must be removed through exhaust fans in the bathroom or roof tops. Greater amounts of air will be introduced (from chart shown above) depending on the size of the exhaust fan.
Outside ambient air entering the room through this screened vent opening is not conditioned. This unconditioned air becomes mixed with the conditioned air that is circulated by the indoor fan. This air mixture generates an additional heat load/heat loss that causes the unit to run longer and may translate into higher operating costs.
Zoneline vent openings are not intended to be the source of make-up air for building ventilation systems due to the additional heating or cooling loads generated.
Corrosion Protection (Optional)
4100 and 6100 Series units may be ordered with special protection to better withstand damage from salt air and salt water in seacoast or other corrosive areas.
Corrosion protection is standard on the Dry Air 25 models.
Heat pump units with ICR are not available with corrosion protection and should not be installed in seacoast or other corrosive environments.
Units installed in corrosive areas should use the RAB77 wall sleeve and be examined/cleaned more frequently than normal installations.
Internal Condensate Removal (ICR)
See page 35 for a discussion of the Internal Condensate Removal system available on 6100 Series heat pumps.
Enhanced Dehumidification
Moisture removal is an important function of an air conditioner. People are more comfortable at higher temperatures when the humidity level is relatively low. Air conditioners operate with less energy consumption when the room temperatures are set higher.
The GE Zoneline 4100 Series with the Dry Air 25 heat pipe application removes 25% more moisture than the base 4100 Series unit .
The GE Zoneline Dry Air 25 chassis is the only PTAC available with the application of the patented Dinh® Dehumidifier Heat Pipe under license from Heat Pipe Technology, Inc.
Customers who are using the Dry Air 25 report a fresher­smelling room as a result of the lower humidity levels, as well as lower operating costs.
Locking Door Kit
RAK8023 — A door with a lock that replaces the standard
control cover door to prevent unauthorized changing of control settings is offered as an accessory.
12
AUXILIARY CONTROL—AUX SET BUTTON
Press “AUX SET”
First Digit
Second Digit
Press “Mode”
Press
/
Smart Fan
HEAT COOL
Load Shedding
Sentinel
HEAT COOL
Constant Fan
Temperature
Limit
HEAT COOL
Class 2 Mode
Duct Mode
All I2R Mode
Boost Heat
0: 60F-85F 1: 64F-85F 2: 66F-85F 3: 68F-85F 4: 70F-85F 5: 72F-85F 6: 74F-85F 7: 76F-85F
0: 60F-65F 1: 60F-70F 2: 60F-72F 3: 60F-74F 4: 60F-76F 5: 60F-78F 6: 60F-80F 7: 60F-85F
HEAT
COOL
– Off
–On
– Off
–On
– Cycle
– Continue
(AZ61 Only)
(AZ61 Only)
The auxiliary control push button is located behind the room cabinet, below the control panel. The auxiliary controls come preset to the modes most desired by customers. However, the owner is responsible for ensuring the auxiliary controls are set to the desired function. There are 9 different modes that can be set using the auxiliary set button.
To change modes:
• Press the STOP button.
• Press AUX SET (“AU” appears on the display).
• Press the MODE button on the control pad until the first digit in the display shows the number corresponding to the mode you are choosing and the correct HEAT/COOL LED is lit.
• Press the UP or DOWN arrow to change the mode setting selection (second digit in the display).
• Press the MODE button to move to the next feature or the AUX SET button to exit the set up process.
Auxiliary Set Button
Access Cover
Press “AUX SET”
First Digit
Press “Mode”
Smart Fan
Load Shedding
Sentinel
Constant Fan
Temperature
Limit
Class 2 Mode
Duct Mode
All I2R Mode
(AZ61 Only)
Boost Heat
(AZ61 Only)
HEAT COOL
HEAT COOL
HEAT COOL
Press /
Second Digit
– Cycle
– Off
COOL
0: 60F-85F 1: 64F-85F 2: 66F-85F 3: 68F-85F 4: 70F-85F 5: 72F-85F 6: 74F-85F 7: 76F-85F
– Off
HEAT
0: 60F-65F 1: 60F-70F 2: 60F-72F 3: 60F-74F 4: 60F-76F 5: 60F-78F 6: 60F-80F 7: 60F-85F
– Continue
–On
–On
AUXILIARY CONTROL SETTINGS
Mode 1—Smart Fan—Cooling/Heating
The default setting for Mode 1 is as follows: Cooling: Continuous (ON) Heating: Cycle (OFF)
* Note: In cyclic Cooling Mode, the indoor fan will activate occasionally
to verify air temperature in the room. In cyclic Heating Mode, the fan will continue to operate for 90 seconds after the heating function has stopped in order to increase unit efficiency.
Mode 2—Load Shedding (Central Desk Control) The default setting for Mode 2 is OFF. This feature is active only if the unit is connected to a CDC and the CDC has control. When this mode is on, only the indoor fan can be turned ON or OFF with the unit controls. When this mode is off, all operation is disabled except Heat/Freeze Sentinel (Mode 3).
Press “SET”
First Digit
Press “Mode”
HEAT COOL
Press “Mode”
HEAT COOL
Press “Mode”
Second Digit
Press
Press
Press
/
Smart Fan Cool – Cycle*
Smart Fan Cool – Continue
/
Smart Fan Heat – Cycle*
Smart Fan Heat – Continue
/
Load Shedding – Off
Load Shedding – On
13
AUXILIARY CONTROL SETTINGS (cont)
Mode 3—Freeze Sentinel/Heat Sentinel
The default settings for Mode 3 are: Heat Sentinel is off Freeze Sentinel is on. When Freeze Sentinel is activated, it automatically provides heat without user interface. This helps to prevent plumbing damage by turning the heater and indoor fan ON at 41ºF and OFF at 46ºF. When Heat Sentinel is activated, it automatically provides cooling without user interface. This helps to prevent an excessively hot room by turning the air conditioner ON at 85ºF and OFF at 80ºF.
NOTE: These functions are active whenever the unit is plugged in, even if the unit is in the STOP position.
Mode 4—Constant ON Fan The default setting for Mode 4 is OFF.
Mode 5—Temperature Limiting The default setting for Mode 5 is as follows: Cool: 2 (66ºF to 85ºF) Heat: 5 (60ºF to 78ºF)
Temperature limits—Cool Temperature limits—Heat
0 = 60°F to 85°F 0 = 60°F to 65°F 1 = 64°F to 85°F 1 = 60°F to 70°F 2 = 66°F to 85°F 2 = 60°F to 72°F 3 = 68°F to 85°F 3 = 60°F to 74°F 4 = 70°F to 85°F 4 = 60°F to 76°F 5 = 72°F to 85°F 5 = 60°F to 78°F 6 = 74°F to 85°F 6 = 60°F to 80°F 7 = 76°F to 85°F 7 = 60°F to 85°F
Mode 6—Remote Thermostat – Class 2 The default setting for Mode 6 is OFF. Setting this mode to ON will allow the unit to operate with a Class 2 Remote Control Wall Thermostat.
Mode 7—Duct Mode The default setting for Mode 7 is OFF. This setting is used when the unit is installed using a duct adapter kit. If the unit is ducted, the Duct Mode needs to be set to ON. This increases the fan speed to ensure proper circulation.
Mode 8—All-Electric Heat (AZ6100 only) The default setting for Mode 8 is OFF. This electric heat option functions only on the 6100 model. When this option is ON, heat pump operation is locked out, causing the unit to provide only electric resistance heat.
Mode 9—Heat Boost (AZ6100 only) The default setting for Mode 9 is OFF. When Heat Boost is ON and outer temperatures are between 25ºF and 46ºF, heat pump-only operation is locked out. This setting is used to provide supplementary heat to the heat pump operation by electric resistance heat in conditions where the heat pump-only operation is not sufficient to maintain a consistent, comfortable room temperature.
NOTE: Heat Boost option should NOT be used with remote thermostat operation. This will cause the unit to switch to resistance heat when the outdoor temperature is 46ºF.
14
Press “Mode”
HEAT
COOL
Press “Mode”
HEAT COOL
Press “Mode”
Press “Mode”
HEAT COOL
Press “Mode”
HEAT COOL
Press “Mode”
Press “Mode”
Press “Mode”
Press “Mode”
Press
Press
Press
Press
Press
Press
Press
Press
Press
/
Freeze Sentinel – Off
Freeze Sentinel – On
/
Heat Sentinel – Off
Heat Sentinel – On
/
Constant Fan – Off
Constant Fan – On
/
Temperature Limit Cool
0: 60F-85F 1: 64F-85F 2: 66F-85F 3: 68F-85F 4: 70F-85F 5: 72F-85F 6: 74F-85F 7: 76F-85F
/
Temperature Limit Heat
0: 60F-65F 1: 60F-70F 2: 60F-72F 3: 60F-74F 4: 60F-76F 5: 60F-78F 6: 60F-80F 7: 60F-85F
/
Class 2 Mode – Off
Class 2 Mode – On
/
Duct Mode – Off
Duct Mode – On
/
ALL 12R Mode – Off
ALL 12R Mode – On
/
Boost Heat – Off
Boost Heat – On
CENTRAL DESK CONTROL
Unit #2
Unit #1
Unit #3
CDC Terminals
on Zoneline unit
Some installations may want to govern the ability of the unit to operate from a control device remote to the unit or even remote to the room in which the unit is located. The general term given to systems such as this is Central Desk Control (CDC). The most common installation of this type of system is a switch mounted at the registration desk and, upon guest check-in, a button is pushed or a switch is moved to allow the air conditioner to operate. Likewise, when the guest checks out, the device is put into the “OFF” position so the unit will not operate while the room is vacant.
It is not necessary that the controlling device be located at a central desk to employ a device that will control the unit operation. For instance, in some resort areas, devices are connected to sliding glass doors and opening the door causes a contact to close, turning the air conditioner off. This prevents energy being wasted by operating the air conditioner when warm, humid air is entering the room. Some systems operate by motion sensors or heat-sensing detectors mounted in the room. These types of systems determine occupant presence in the room and allow the unit to operate; if no one is in the room the device signals the air conditioner to turn off.
®
Zoneline
models offer load-shedding capabilities on units connected to Central Desk Control systems. For more information on the models’ load-shedding feature, see page 11.
There is a wide variety of devices available, each with its own benefits and constraints. While GE does not offer components that are external to the unit for a Central Desk Control system, GE Zoneline units are compatible with most CDC and energy management systems. Zoneline units
provide a 24 VAC circuit that powers the Central Desk Control system and no external power is needed.
All Zoneline 4100 and 6100 Series units are compatible with simple on/off 2-wire Central Desk Control systems. Consult with the provider of the energy management system to be sure it is compatible with GE Zoneline units. Zoneline units have standard connectors factory-installed to provide a CDC interface that permits the unit to be connected to most of the energy management systems. The devices connected to the Zoneline units require no power supply or transformers external to the unit.
Important CDC Comments (all series applicable)
4. Recommended wire size must be followed as a minimum requirement.
Wire Size #AWG Maximum Allowable Length
#22 600 Ft. #20 900 Ft. #18 1500 Ft. #16 2000 Ft.
Freeze Sentinel and Heat Sentinel remain operational when the unit is connected to a CDC system. Even if the unit is turned “OFF” at the central location, if the sensor at the unit detects the low or high limit temperature, the unit will automatically turn on until it reaches the preset shutdown temperature (46°F heating, 80°F cooling).
Connecting the Zoneline unit to a CDC system does not eliminate the ability to connect the unit to a remote thermostat. Once the circuit is “opened,” and control of the unit removed from the CDC system, the selected controls—either the unit­mounted control or the remote thermostat—govern the operation of the unit.
Please see page 57 for installation recommendations for the Central Desk Control wiring.
CDC Terminal Location and Typical Wiring
See page 16 for location of CDC terminals on unit.
Example of Common Busing
NOT PERMITTED
INCORRECT Common Busing
Normally Open
Switch -
Unit Operational
1. When the switching device closes the circuit of the CDC conductors, the unit operation stops.
2. Do not use a common bus (at the unit or at the switch panel) in the wiring. Both wires comprising the circuit must connect to the unit connectors and to the controlling switch. Running one wire from one unit to another unit is common busing and may damage internal components or cause erratic operation of the system.
3. A 24-volt transformer is contained within the Zoneline unit. No external voltage may be applied to the unit through the CDC terminals. (Voltage on the CDC conductors is 24 volt s AC.)
Typical Wiring
(All Wiring Shown Is Field Supplied)
15
REMOTE THERMOSTAT CONTROL
R
GL
GH
B
Y
W
C
Common White — Heater Yellow — Compressor Black — Not Used On 4100 Green — High-Speed Fan Green — Low-Speed Fan Red — 24V AC CDC Terminal
CDC
In some installations, control of the operation of the unit at a location remote from the unit itself may be desired. A unit mounted high in the wall or over a door, for instance, where the unit-mounted controls are inaccessible, can be connected to a wall-mounted thermostat. Other installations may use remote thermostat control for design or performance enhancement. The unit is connected to the thermostat by low-voltage wiring which permits the operation of the unit to be selected and the temperature sensed at the thermostat.
Important Notes: Remote thermostat wiring should NOT be run through the wall case. Thermostat wiring should exit the wall below the unit and enter the unit between room cabinet and chassis. Wire molding may be used to hide thermostat wiring. If a sub-base is used, the thermostat wiring may be concealed by the sub-base. Thermostat wiring should NOT be run parallel to line voltage wires since induced current may cause erratic operation.
®
All Zoneline
4100 and 6100 Series units are adaptable to Class 2 remote low-voltage thermostats. The only additional field-supplied components are the remote thermostat and wiring necessary to connect it.
The controls on the unit are not functional when the remote control function is used.
RAK806 Universal Control Cover Label
When a Zoneline unit is using a remote thermostat control, the RAK806 Universal Control Cover Label is recommended. The RAK806 is only available in a package of 10 labels. The label is placed over the control panel to direct the user to the wall thermostat for operation of the Zoneline unit.
The remote thermostat-Class 2 option (Mode 6 in the auxiliary control setting) must be turned ON to enable remote thermostat control. Refer to installation instructions packaged with the chassis.
Please see page 57 for installation recommendations for the remote thermostat wiring. Compatibility of other thermostats considered for use with GE Zoneline units is the responsibility of the customer.
The control voltage on the remote control conductors is 24 volts AC. The AC voltage may not be compatible with some solid-state thermostats.
The fan speed for the 4100 Series in remote thermostat operation is selected by the connection of the fan wire from the thermostat to either the HIGH or LOW terminal on the unit. See the sketch of the unit terminals below for the location of the HIGH and LOW fan-speed terminals. Operating the unit in low fan speed reduces the operating sound level of the unit.
Freeze Sentinel and Heat Sentinel remain operational if the unit is connected to a remote thermostat. The unit may be connected to a Central Desk Control (CDC) system and controlled with a remote thermostat when the CDC system has the unit in operation. See page 15 for additional information on the CDC system.
Unit temperature-limiting settings are not functional when unit is connected to a remote thermostat.
Field Wiring Terminal
R — 24V AC GL — Low-Speed Fan GH — High-Speed Fan B — Not Used on 4100 Y — Compressor W — Heater C — Common
Resistance Heat Models
The Zoneline 4100 resistance heat units may be connected to a single-stage thermostat designed for use with cooling with electric heat systems. GE offers two thermostats compatible with the 4100 Series unit.
RAK164D2 — a solid-state digital thermostat requiring five connection wires.
16
RAK164P2 — a solid-state digital programmable thermostat requiring five connection wires.
REMOTE THERMOSTAT CONTROL (cont)
R
GL
GH
B
Y
W
C
Common White — Heater Yellow — Compressor Black — Reversing Valve Green — High-Speed Fan Green — Low-Speed Fan Red — 24V AC CDC Terminal
CDC
Heat Pump Models
The Zoneline 6100 Series heat pump units may be connected to a single-stage cooling/two-stage heating thermostat designed for use with heat pump systems. GE offers two thermostats compatible with the 6100 series units:
RAK148D2 — solid-state digital thermostat requiring six connection wires.
Please see page 57 for installation recommendations for the remote thermostat wiring. Compatibility of other thermostats considered for use with the GE Zoneline unit is the responsibility of the customer.
The control voltage on the remote control conductors is 24 VAC. The remote thermostat-Class 2 option (Mode 6 in the
auxiliary control setting) must be turned ON to enable remote thermostat control. Refer to installation instructions packaged with the chassis.
The fan speed for the 6100 Series in remote thermostat operation is selected by the connection of the fan wire from the thermostat to either the HIGH or LOW terminal on the unit. See the sketch of the unit terminals for the location of the HIGH and LOW fan speed terminals. Operating the unit in low fan speed reduces the operating sound level of the unit.
RAK148P2 — solid-state digital programmable thermostat requiring six connection wires.
Feature Heat Pump Electric Heat
Indoor frost control Yes Yes Freeze Sentinel Yes Yes Heat Sentinel Yes Yes Auto fan speed No No Electronic
temperature limiting No No Switch to resistance
heat based on indoor temperature
Switch to resistance heat based on outdoor temperature Yes N/A
Reverse cycle defrost Yes N/A Simultaneous
resistance heat with heat pump No N/A
Resistance heat lockout Yes N/A
“Smart Fan” fan cycle
Central Desk Control Yes Yes
Determined by remote thermostat N/A
Fan ON/AUTO set on remote thermostat
Fan ON/AUTO set on remote thermostat
When connected to a remote thermostat, indoor air­temperature sensing is shifted from the unit to the remote thermostat. For this reason, the units will operate slightly differently when connected to a remote thermostat. The above chart shows the unit operation when connected to a remote thermostat.
The Heat Boost option should NOT be used with remote thermostat operation since this will cause the unit to switch to resistance heat when outdoor temperatures are below 46ºF.
Field Wiring Terminal
R — 24V AC GL — Low-Speed Fan GH — High-Speed Fan B — Reversing Valve Y — Compressor W — Heater C — Common
17
REMOTE THERMOSTAT CONTROL (cont)
Remote Thermostat Control Selection Chart For Zoneline® Packaged Terminal Units
Zoneline Series Thermostat Model Type Function Low-Voltage Conductors
4100 RAK164D2 Di git al
RAK164P2 Digital Programmable 5
6100 RAK14 8D2 Dig ital
RAK148P2 Digital Programmable 6
Thermostat wire size – up to 60 feet AWG20 – up to 66 feet AWG18
For remote thermostat operation follow the steps below:
1. Turn on the unit and ensure it is working properly
BEFORE proceeding.
2. Unplug the unit or disconnect power and remove
the room cover.
3. Connect the thermostat wiring per the appropriate
diagram/colors for your model.
4. Plug the unit back in or reconnect power.
5. Press the AUX SET button once. The letters AU will
appear in the display.
6. Press the MODE button until the number “6” appears
in the left hand digit.
7. Press the UP arrow once so the top half of the right
hand digit is lit.
8. Press the AUX SET button to exit the setup function.
9. Replace the room cover.
Cooling and Heating
Single-Stage Cooling –
2-Stage Heating
5
6
See pages 13 and 14 for full instructions on using the Auxiliary Controls Feature.
18
HEAT PUMPS AND ENERGY SAVINGS
• GE Zoneline heat pumps are designed to provide cost-efficient heat pump operation while monitoring room conditions to maintain comfort.
The units employ a logic system monitoring both outdoor and indoor temperatures to determine the heat source, thus increasing energy savings by operating longer in the heat pump mode.
Heat pumps save energy and cost less to operate than units with electric resistance heaters as the only heat source. Just as the EER of an air conditioner is an indication of the efficiency of the unit, COP (Coefficient of Performance) is the indication of the efficiency of the heat pump. This relative efficiency of a heat pump compares the unit to electric resistance heat. If a unit has a COP of 3.0, it means the unit will produce three times as much heat at rating conditions for the same electrical input wattage used for electric resistance heat.
The compressor is used in heat pump operation just as in air conditioning operation. In heat pump operation, the hot refrigerant gas is directed to the indoor coil rather than to the outdoor coil. Room air that circulates over the indoor coil gains heat from the coil rather than losing heat to the coil as during cooling operation.
As the outdoor temperature falls, the heat pump cannot extract as much heat from the outdoor air to raise the temperature of the indoor air. For this reason, all packaged terminal heat pumps also have electric resistance heaters as backup to heat pump operation. At some point, the heat pump is unable to provide sufficient heat to adequately warm the room. Many Packaged Terminal Heat Pumps cease heat pump operation and change to more expensive resistance heat at some pre-determined outdoor temperature to compensate for the inability of the heat pump to maintain room temperature. This point, called the “switchover point,” is usually at an outdoor temperature where savings from heat pump operation may still be realized if the unit is designed to maintain room comfort at the lower outdoor temperatures.
Balance Point
An important consideration in the selection of a heat pump unit is the “balance point” of the installation. Virtually every room is unique—with different insulation, different sizes and types of windows, different types of construction and different directional exposures. All these variables, as well as geographical location, must be considered in order to determine the balance point, the point at which the heat pump is unable to produce enough heat to compensate for the heat loss of the room or area being heated. For these reasons, a consulting engineer should be engaged to calculate the heat loss and specify the heat pump unit required.
The Zoneline 6100 series heat pump units—with highly featured microprocessor controls—react to the indoor temperature as well as the outdoor temperature in determining the heat source to provide comfortable room conditions and energy savings. This determination of the heat source based on the indoor temperature helps provide a more comfortable room.
19
HEAT PUMPS AND ENERGY SAVINGS (cont)
Heat Pump Operation — Zoneline® 6100 Series
Heat sources: Heat pump, heat pump and simultaneous electric resistance heat, or electric resistance heat.
Zoneline heat pumps employ a highly featured microprocessor control system interfaced with thermistors to accurately measure indoor air temperature, outdoor air temperature, indoor coil temperature and outdoor coil temperature. This system allows the microprocessor to precisely and predictably react to changing conditions in order to provide a very advanced packaged terminal heat pump operating system.
Zoneline heat pumps are designed to help ensure a comfortable room. When “HEAT” is selected, the unit will determine if the room air is warm enough to satisfy the thermostat setting. If the temperature at the unit sensor is below the desired temperature, the electric resistance heater will be utilized to warm the room to the point where the thermostat is satisfied. This feature is designed to allow the temperature of an unoccupied room to be maintained at an energy-saving level without inconveniencing the room occupant. Once the thermostat has been satisfied, the resistance heater will turn off and the heat pump will operate (as shown below in the Heat Source Logic chart) until the thermostat calls for heat again. The unit will operate in this manner even if connected to a Central Desk Control.
Zoneline Heat Pump Heat Source Logic
ROOM
TEMPERATURE
VS. THERMOSTAT
SET POINT
Less Than
1.8°F Below
1.8°F to 2.7°F Below
More than 2.7°F
Below
Above
46°F
Heat Pump Heat Pump*
Heat Pump
Heat Pump
Between 46°F
and 25°F
Heat Pump +
Supplemental
Heater
Full Resistance
Heat
Below
25°F
Full Resistance
Heat
Full Resistance
Heat
Full Resistance
Heat
An option is provided in the auxiliary controls (Mode 8) to allow the unit to operate only in resistance heat. The use of this option significantly increases the cost for heating.
Heat pump defrost — Zoneline 6100 Series
Zoneline heat pumps utilize a reverse-cycle, demand­defrost system to extend heat pump operation and increase savings from extended operation. The microprocessor
determines the need for defrosting by criteria based on continuous compressor running time, outdoor air temperature, outdoor coil temperature and the rate of temperature change of the outdoor coil. When defrosting is required, the unit reverses the flow of refrigerant to direct the hot gas into the outdoor coil to melt the frost buildup. Before and after the reverse-cycle defrosting, the unit shuts off the compressor to allow the refrigerant pressures to equalize throughout the system. This eliminates the possibility of a loud reversing noise. During these periods of pressure equalization, the full resistance heat capacity of the unit is activated to help ensure room comfort conditions during the defrost cycle. The unit remains in the defrost cycle for a minimum of two minutes up to a maximum of nine minutes. The defrost cycle terminates when the outdoor coil reaches a temperature of 68°F or the maximum time has been reached.
Heat pump condensate
Zoneline 6100 Series heat pumps may be ordered with a factory-installed Internal Condensate Removal (ICR) system to minimize the amount of condensate water draining from the unit during heat pump operation. The ICR system has proven to be an effective means of minimizing the amount of heat pump condensate dripping from the unit. However, if the requirements of a particular installation will allow no dripping of condensate water from the wall case, the installation of an internal or external drain system is recommended. See page 35 for more information on heat pump condensate.
Units with ICR may not be installed in seacoast or other corrosive environments.
The Heat Boost option feature utilizes the supplemental simultaneous heater at the same time as heat pump operation when the outdoor temperature is below 46°F, regardless of the indoor air temperature**. The chart above indicates the heat source of the heat pump under various indoor and outdoor conditions. The unit is designed to provide heat pump savings without sacrificing room comfort.
The Quick Heat Recovery feature is not affected by the Heat Source Logic shown in the chart above. For more information about the Quick Heat Recovery feature, see page 9. The full heat output of the resistance heater is dependent upon circuit amperage and the power connection kit used. See pages 4 and 43–44 for information on power connection kits and available heater capacities.
20
* If the Heat Boost switch (auxiliary setting #9) is “ON”, the supplemental
simultaneous heater will be used with heat pump operation. Simultaneous supplemental heater: 1.0 KW @ 230 V;
0.8 KW @ 208V; 1.0 KW @ 265V.
** Heat Boost option only applies to systems controlled at the
unit. Heat Boost option should NOT be used with remote thermostat operation since this will cause the unit to switch to resistance heat when outdoor temperatures are below 46°F.
APPLICATION COMMENTS
Use and Care Manual and installation instructions are shipped with Zoneline units. It is important that any air conditioning system be properly sized and applied in order to achieve the desired temperature and humidity levels in the space to be conditioned. Zoneline units are designed primarily to provide heating and cooling with the additional benefit that during operation in the cooling mode, the units also remove some moisture from the conditioned space. The following are some brief application comments on undersizing, oversizing, heating, wall coverings, and air infiltration: all are important in the proper matching of the heating/air conditioning system to the building structure.
Undersizing: If an air conditioner is undersized (cooling capacity is less than required for a specific application), the unit will typically not be able to cool the space down to the desired temperature (thermostat set point), nor be able to remove enough moisture from the air. The result could be a warm and humid or warm and dry conditioned space.
Oversizing: If an air conditioner is oversized (cooling capacity is greater than required for the specific application), the unit will typically cool the space down to the desired temperature (thermostat set point) too quickly. The compressor then begins to cycle on and off. Dehumidification only takes place when the compressor is operating in the cooling mode. A typical result in a hot/humid climate could be a cool but excessively humid space.
Heating: Undersizing can result in not being able to maintain the desired temperature level within the conditioned space.
Wall Covering: Use of a non-permeable wall covering (some paints, some wallpapers, and other types of coverings) which severely restricts passage of air or water vapor can cause a severe moisture problem. Typical results could be staining of room surfaces, wall damage, as well as mold and mildew growth in hot/humid climates.
Air Infiltration: Excessive air infiltration can magnify problems associated with undersizing or oversizing of an air conditioner unit and can be the root cause of insufficient cooling, dehumidification or heating. Some sources of air infiltration include vents, gaps around windows and doors, and improperly sealed floor, ceiling and wall joints.
Recommendation: For the above reasons it is strongly recommended that a professional engineer be retained to match the Zoneline unit with the building structure.
High Wall Mount: For units mounted high in the wall, the discharge louvers should be at a setting that provides the most horizontal air discharge. Recommended installation is at least 3" below the ceiling. In installations where units are close to the ceiling, the greatest horizontal discharge angle can be obtained by removing the discharge grille from the room cabinet.
Supply Air Throw: One Zoneline unit should not be required to do a job obviously requiring two or more units. Units should be located around large rooms according to calculated loads or in such fashion as to achieve balanced air distribution in all parts of the room. The single unit in the “Incorrect” illustration below obviously cannot condition the entire room. Add a second unit as shown in the “Correct” illustration.
INCORRECT
OVER 40 FT.
CORRECT
OVER 40 FT.
Air Distribution
Zoneline packaged terminal air conditioners and heat pumps discharge air from the top of the unit through reversible two-position discharge louvers. Unit discharge louvers are reversed by removing the room cabinet from the unit, removing seven screws that hold the louver section in place, removing the louver section and rotating it end for end, reinstalling the louver section in the room cabinet with the seven screws, and reinstalling the room cabinet on the unit. The unit is shipped from the factory with the discharge louvers at an angle of 50° off vertical. In the alternate position, the louvers will be at an angle of 40° off vertical.
All room cabinets return air through the front of the unit.
50°
40°
40°50°
21
CASE DIMENSIONS
RAB71A WALL CASE
16"
Additional Wall Case Depths
42"
A
13-
3/4"
1-1/2" TYP
1/2" SQ. HOLE (2 REQ'D.)
1/4" DIA
1/2"
2-55/64"
9-41/64"
RAB7116 - 16" RAB7124 - 24" RAB7128 - 28" RAB7131 - 31"
4"
WALL OPENING 16-1/4" MIN. x 42-1/4" MIN.
RAB77AA WALL CASE
WALL OPENING 16-1/2" MIN. x 42-3/8" MIN.
WALL CASE WITH CHASSIS INSTALLED
13-7/8"
16-1/4"
RAB71A = 13-3/4" RAB77A4 = 13-7/8"
1-1/2"
34"
1/2" SQ. HOLE
(2 REQ'D.)
36"
RAB71A = 42" RAB77A4 = 42-1/8"
TOP VIEW
21"
19"
8"
1/2" DIA. HOLE (2 REQ'D.)
42-1/8"
2-7/8"
9/16"
6"
GRILLE
INSIDE
1/2" DIA. (3 REQ'D.)
7-1/8"
RAB71A = 20-7/8" RAB77A4 = 21"
SIDE
VIEW
GRILLE
RAB71A = 16" RAB77A4 = 16-1/4"
OUTSIDE
42"
ROOM
CABINET
ROOM
CABINET
WALL CASE WITH SUB-BASE
3-1/2"
*SHOWN WITH ACCESS COVERS REMOVED. NOTE: CAUTION - REMOVE KNOCKOUTS FROM INSIDE OUT.
12-3/4" 12" 9-3/8"
FRONT VIEW*
13"
KNOCKOUTS (ENCLOSURE) 4 REAR; 4 BOTTOM
SEE PAGE 33 FOR KNOCKOUT LOCATION DIMENSIONS.
LEVELING SCREW
1-7/16"
2-1/2"
3" MIN. ADJUSTABLE TO 5" MAX.
1-5/16"
Installation instructions packed with wall case. See page 26 for additional information concerning outdoor weather panel and case stiffener.
22
SIDE VIEW
FINISHED FLOOR
2-3/8" MIN.
INTERIOR WALL
WALL CASE
A choice of wall cases is available for Zoneline® units. RAB71A — This insulated case is constructed of heavy-
gauge galvanized steel and finished with a baked-enamel finish for protection and appearance. Design of the case provides for support of the chassis and free draining of any water entering the wall case. A petroleum microcrystalline wax is applied at critical points of fabrication to seal against moisture. The dimensions of the RAB71A wall case are 42" wide by 16" high by 13-3/4" deep, the same dimensions as the original wall case for GE Zoneline units built in 1961. The RAB71A wall case is also available in depths other than the standard depth. It is available on special order as: RAB7116
– 16" deep; RAB7124 – 24" deep; RAB7128 – 28" deep; and RAB7131 – 31" deep. All these special-order deep wall cases
are insulated and have sheet-metal dividers, or splitters, to prevent the recirculation of condenser discharge air.
RAB77A4 — This non-insulated wall case is molded from fiberglass-reinforced polyester compound. This SMC (Sheet-Molded Compound) wall case offers outstanding strength, durability, color retention, water integrity and corrosion resistance. The dimensions of the RAB77A4 wall case are 42-1/8" wide by 16-1/4" high by 13-7/8" deep.
• Both wall cases are of universal design, accepting all Zoneline chassis of current design as well as all GE Zoneline chassis produced since 1961.
• Drain holes are provided in the rear of the wall case to permit excessive cooling condensate water, heat pump condensate or precipitation entering the wall case to drain freely. A drain kit may be connected to the wall case to control any water draining from the wall case. See page
36 for information on RAD10 Drain Kit.
RAK901L — For installations where the wall case extends into the room, RAK901L is an insulation kit that can be used with the RAB77 or any existing non-insulated wall case to minimize the possibility of condensation forming on the indoor side of the case during the winter.
SUB-BASE
The sub-base is an optional accessory for the Zoneline unit and is presented with the wall case information since deciding whether or not to use a sub-base in the installation is a factor in the location of the wall opening. National Electrical Code® (NEC) requires that air conditioning units connected to voltages in excess of 250 volts be “permanently connected.” There are also some installations where units connected to voltage sources under 250 volts may also need to be “permanently connected.” If you are in doubt about the requirements for a particular installation, consult Article 440 of the NEC or the local electrical inspector. These requirements are designed to protect personal safety and should be strictly followed. Although NEC is cited here as a reference, all electrical wiring and installations must conform to any and all local electrical codes and regulations.
“Permanent connection” generally means wiring to the unit must be contained in an enclosed “chaseway,” where access to the wiring connections is more restrictive than a normal line cord plugged into a receptacle. NEC requirements may be met by using flexible or rigid conduit to contain the wiring between the unit and a junction box that contains the wiring connections. The conduit is connected to the unit and to the junction box with connectors to hold the conduit in place. The junction box may be located in the floor or the wall of the structure, but only approved connectors may be used outside the unit or the junction box. The sub-base is UL junction box for permanent connection of a Zoneline unit.
Using a sub-base in an installation requiring permanent connection provides a convenient, consistent location for unit wiring to be connected to building wiring. The use of a sub-base is not required, but the convenience and the improved aesthetics it offers make the use of a sub-base a viable means of permanent connection.
RAK204U — The RAK204U Series of sub-bases provides a variety of designs that fit the site needs and are available for use with Zoneline PTAC/PTHP units. The RAK204U will most likely be used for support of the wall case and unit. The RAK204U is the same physically as the other sub-bases except there is no receptacle installed. Receptacles and wiring can be field installed and, by using the RAK205CW chaseway and the RAK4002A junction box, perform the same function as any of the other sub-base kits by selecting the correct receptacle and installing it in the interior mounting plate inside the RAK204U.
208/230-volt receptacles can also be mounted in the cover plate for easy access when direct-connect wiring is not required. 265-volt units are to be “Permanently (or Direct) Connected” and the external receptacle (when wiring is not enclosed in a chaseway) does not meet this requirement. A knockout for a fuseholder or a disconnect is also provided in the cover plate.
RAK204U — No receptacle, no wiring; will accept any 15-, 20-, 30-amp receptacle and wiring. No chaseway is included. RAK205CW chaseway must be ordered separately.
The 230/208-volt sub-bases below include a short, sub-base power connection kit. Since sub-base connected units are not considered to be line-cord connected, a Leakage Current Detection and Interruption or Arc Fault Current Interrupter device is not necessary.
The junction box (RAK4002A for 4100 and 6100 Series units) that mounts on the chassis of 230/208-volt sub-base connected units must be purchased separately.
RAK204D15P 208/230-volt 15-amp receptacle. Receptacle is NEMA6-20R with 18" of #12AWG wires attached to the receptacle. Short power connection kit included. Chaseway included.
RAK204D20P 208/230-volt 20-amp receptacle. Receptacle is NEMA6-20R with 18" of #12AWG wires attached to the receptacle. Short power connection kit included. Chaseway included.
®
listed as a
23
SUB-BASE (cont)
RAK204D30P 208/230 volt 30-amp receptacle. Receptacle
is NEMA6-30R with 18" of #12AWG wires attached to the receptacle. Short power connection kit included. Chaseway included.
The junction box (RAK4002A for 4100 and 6100 Series units) that mounts on the chassis of 230/208 volt sub-base connected units must be purchased separately.
Sub-bases for the 265-volt units: RAK204E15 265-volt 15-amp receptacle. Receptacle is
NEMA7-15R with 18" of #12AWG wires attached to the receptacle. Chaseway included.
RAK204E20 265-volt 20-amp receptacle. Receptacle is NEMA7-20R with 18" of #12AWG wires attached to the receptacle. Chaseway included.
RAK204E30 265-volt 30-amp receptacle. Receptacle is NEMA7-30R with 18" of #12AWG wires attached to the receptacle. Chaseway included.
The junction box for 265-volt units is shipped with the chassis since all 265-volt units are to be “permanently (or direct) connected.”
The power connection kit is not included There are separate internal compartments to permit
separation of low-voltage (Class 2) connections from line­voltage connections as required by National Electrical Code (NEC). Conduit containing building wiring enters the sub-base through knockouts located in the rear or bottom of the sub­base and is not accessible when the wall case is installed.
The sub-base attaches to the RAB71A wall case with two clips (field-assembled) that are screwed into pre-drilled holes in the bottom front flange of the wall case. It attaches to the RAB77A4 wall case with clips that fit over molded ribs without requiring the use of screws into the wall case. (See page 34 for illustration.) Since the sub-base extends under the wall case, clearance from the inner edge of the wall case to the finished wall must be 2-3/8" or greater. The sub-base has four leveling legs and adjustable side channels to enable the area under the wall case to be enclosed. Clearance from the bottom edge of the wall case to the finished floor must be between 3" and 5".
The sub-base may be used as support for the chassis and wall case in installations where the wall is of insufficient thickness to provide secure mounting of the wall case.
WALL CASE INSTALLATION DATA
General
of installation. The unit may be installed high in the wall and these installations usually require a remote thermostat and are discussed on pages 16 and 17.
Regardless of the installation, there are several things to consider when selecting a location for installing the unit. For instance, drapery location could interfere with air discharge, and placement of furniture may have an impact on the performance of the unit. The following information is intended to minimize installation problems and assure you of trouble-free installation.
Refer to page 22 for required wall opening dimensions. Minimum recommended interior and exterior case projections for standard wall thicknesses are shown in the drawings in this manual. The case may be installed flush with the finished indoor wall. Special attention must be paid to room-side case projection when the unit is installed in a ducted application as shown on pages 39 and 40.
In walls thicker than 13-1/2" for line-cord-connected units and 11-1/8" for sub-base installations, it may be necessary to install a field-fabricated case extension or use one of the special-order RAB71 deep wall cases. Such extensions must be carefully flashed and sealed both to the wall case and to the wall to ensure water integrity. This is necessary to ensure that any water entering the wall case, either from operation of the unit or from other sources, such as rain storms or from washing the exterior of the building, will drain from the case without the possibility of capillary action drawing the water into either the room or the wall cavity. In an installation where the case is recessed less than 3" from the outside surface, flashing and sealing may be all the modification necessary. In such an installation, the sides and top of the wall opening must be waterproof to prevent moisture from seeping into and damaging the walls. See pages 31 and 32 for suggested detail. Since the installation of a case extension requires a considerable amount of attention, we recommend using one of the deep wall cases if the standard case is not of sufficient depth.
Mounting an outdoor grille or louver section to the building face may cause a space between the outdoor coil and the louver section. Air splitters, aligned with the ends of the outdoor coil, must be installed between the outdoor coil inlet and outlet air streams. Gaps between the outdoor coil and the louver section may allow condenser air recirculation and affect the operation of the unit. See page 41 for requirements for custom louvers.
Generally, Zoneline® units are installed 3" to 5" above the floor (flush to finished floor installation is possible) as near to the center of the room as possible; underneath a window or a glass panel is typical. Normal installation of the wall case allows installation flexibility; from flush with the finished interior wall to a minimum of 1/4" of the wall case extending beyond the finished exterior of the building. Special consideration must be given to installations where the wall case does not extend a minimum of 1/4" beyond the finished exterior wall. See pages 31 and 32 for information on this type
24
The wall case should be level from side to side and from level to 1/4 bubble tilt to the outdoors. The condensate disposal system in the unit is designed to dissipate the condensate water generated during cooling operation in accordance with AHRI standards and actually uses this water for maximum unit efficiency. A level unit will also ensure proper performance of the Internal Condensate Removal (ICR) system optional on heat pump units.
WALL CASE INSTALLATION DATA (cont)
MASONRY WALL CONSTRUCTION
For new construction, early planning with the architect is necessary. Unit location, electrical connection locations and wall openings of the proper dimensions are essential to avoid the necessity of rework, fillers, framing, moving electrical outlets and other expensive modifications.
For existing construction it is important that carpentry, masonry and electrical work be performed by competent, qualified personnel. Since installations in existing construction may involve removal of building material from the structure, locating the wall case must be done correctly.
ARCHITECTURAL WINDOW/ LOUVER INSTALLATION
Many installations utilize an architectural window/louver combination to enhance the exterior appearance of the building. The exterior grille for the air conditioner is built as an integral part of the window frame. An internal drain system is highly recommended for these installations (see page
37). When this type of installation is made, there must be
provision in the grille work for condensate water to drain to the exterior (including the overflow relief drain holes) and not be routed back into the interior of the building or into the wall cavity. Failure to allow for the drainage of condensate water can cause extensive damage to structural components.
The problems associated with the lack of condensate drain consideration often show up shortly after the air conditioners are turned on in a new building. New buildings that have been virtually wide-open during construction have a significant amount of moisture in the air and in the building components that the air conditioners start removing as they operate. The free area in the louver section must also comply with the requirements shown on page 42.
The wall case should be anchored to the architectural window/louver section to reduce air infiltration and excessive vibration of the chassis and wall case during unit operation. Field-fabricated and -installed case angles are the recommended method of securing the wall case to the window/louver framework.
WINDOW, CURTAIN AND PANEL
The wall case should be installed during construction and lintels should be used to support the blocks above the wall case. The wall case will not support the concrete block. The installation instructions show how the wall case must be secured to the masonry and caulked. Do not remove the cardboard stiffener supplied with the wall case until ready to install the chassis. (See page 30 for details of installation in masonry wall)
For existing masonry construction, wall openings must be made by removing concrete blocks to achieve the proper­size opening. Consult the builder, architect or owner to determine the necessity for lintels to support the block above the wall case.
Anchor bolts are normally required to secure the case to the wall and shims may be required to prevent distortion of the wall case when securing the wall case to the wall. Field­supplied case angles can be used to position and secure the wall case to the wall and to cover oversized wall openings.
BRICK, FRAME, STUCCO AND SHINGLE CONSTRUCTION
For new construction, the opening for the wall case should be framed and the wall case inserted into the opening during construction. Lintels should be used when the building material is heavy and is not self-supporting (such as brick). The wall case will fit an opening of six courses of standard brick or five courses of jumbo brick. Wall framing in this type construction is normally on 16" centers and the wall case will fit a framed opening spanning three 16" O.C. 2" x 4" stud spaces.
For existing construction, the indoor and outdoor wall will need to be cut out, allowing for clearances of 1/8" on all sides of the wall case. Work should begin on the inside wall. Cut the correct dimensions and mark (using drill holes) the outside wall from each corner of the inside cutout. Studding that interferes with the opening must be removed and a suitable frame constructed to secure the wall case and provide adequate support for case and chassis.
As shipped, the RAB71A Series or RAB77A4 is ready for installation.
WALL CONSTRUCTION
With this type of construction, provision for support of the unit, other than by the wall itself, is often required. Such support may be in the form of wood or metallic material of the proper thickness to maintain a level case. This additional support should be located both near the wall and at the front of the wall case. Sub-base (RAK204 Series) with four leveling legs provides an excellent support for the unit in this type of installation. (See page 29 for details of this type of installation.)
In existing construction, common practice is to remove a pane of glass, metal, wood, or other construction material and build a frame around the wall case. Similar filler panel material may be installed around the case for appearance and weather seal.
25
PREPARATION OF THE WALL CASE
CASE ANGLES
FOR ALL TYPES OF CONSTRUCTION
Do not remove the stiffener from inside the wall case or the weather closure panel from the outside face of the wall case until the outdoor grille and chassis are ready to be installed.
Installation of Wall Case in Wall Opening
1. Position the wall case into the wall. The room-side edge of the RAB71A or RAB77A4 wall case should be at least flush with the finished wall for line-cord installations and permanent-connection installations when no sub-base is used, and should project into the room at least 2-3/8" when a sub-base is used. The outside edge of the wall case should extend at least 1/4" beyond the outside wall. This is necessary for proper caulking, to prevent sealing the drain holes in the rear flange of the wall case, and to facilitate the installation of an accessory drain, if used. If the minimum exterior dimensions are not met, refer to pages 31 and 32.
The wall case should be level from side to side and from level to 1/4 bubble tilt to the outdoors. The condensate disposal system in the unit is designed to dissipate the condensate water generated during cooling operation in accordance with AHRI standards and actually uses this water for maximum unit efficiency. A level unit will also ensure proper performance of the Internal Condensate Removal (ICR) system optional on heat pump units.
In some installations, such as curtain walls, window walls, or where the structural material of the wall is insufficient to support or fasten wall case, case angles may be used. Case angles are pieces of steel or other material of similar structural strength that are formed to a 90° angle, with holes to fasten the case angle to the wall case and to the structural component of the wall surrounding the wall case.
The following describes the procedure when field-fabricated and -installed case angles are applied.
1. Position case angles around top and sides of wall case at the desired location. Position case angles vertically on each side of wall case to provide a level installation.
2. Mark wall case through holes in case angles. The lowest hole on the sides of the wall case must be a minimum of 2" above the bottom of the case.
3. For RAB71A wall case, drill 5/32" diameter holes at locations marked on wall case in Step 2, and assemble angles to wall case using #10 x 1/2" self-tapping screws. For RAB77A4 wall case, follow the same procedure except use a #10 x 1/2" bolt, washer and nut to attach case angles to case. Install screws or bolts from inside wall case.
4. Do not drill any holes in bottom of wall case. Do not distort wall case.
5. Do not use case angles for a lintel.
2. The wall case should be secured to the wall at both sides. Use a minimum of two screws or other fastening device on each side. (See Figure 2 on page 27.) Mark the wall case on each side 2" from the bottom and 2" from the top at a point where basic wall structure is located. Drill wall case and use fasteners appropriate for wall construction. All holes for fasteners in the side of the wall case must be at least 2" up from the bottom of the wall case. Never locate screws or put other holes in the bottom of the wall case. The ONLY exception is when an RAD10 drain kit is installed to connect to an internal drain system. (See page 37 for RAD10 drain kit information.)
If the wall opening is greater than the case dimensions,
spacers must be used on the sides between the wall case and the wall support structure to prevent distorting the wall case.
3. Caulk or gasket the entire opening on the outside between the wall case and exterior wall surface (four sides) to provide total water and air seal.
4. Caulk or gasket room-side opening between wall case and interior wall surface (four sides). Openings beneath or around the wall case can allow outdoor air to leak into the room, resulting in increased operating costs and improper room temperature control.
Care should be taken in location of electrical supply entry in relationship to wall sleeve to assure access to receptacle or junction box once unit is installed.
• Refer to page 44 for maximum power cord length.
• Permanently connected units close to finished floor
must allow for conduit clearance.
26
HEADER
LINTEL
MOUNTING
SCREW HOLE
Framing detail for this construction is as
shown in Figure 1. Note use of lintel under
first course of brick above the Zoneline
case. Do not use the case as a lintel.
Mounting screw holes shown are to be
made by the installer.
BOLT
ANCHOR
EXPANSION
BOLT
MOLLY
OR TOGGLE
Choice of attachment devices
through both ends of case or the
top. Mounting screw holes and
attachment devices by installer.
FASTENING WALL CASE
MAIN STUDS
JACK STUD
HEADER – 4" x 4" OR
2 - 2" x 4" ON EDGE
NO HOLES PERMITTED
IN BOTTOM OF CASE
(EXCEPTION -RAD10
DRAIN KIT)
WOOD
SCREW
NO HOLES PERMITTED IN
BOTTOM OF CASE
(EXCEPTION - RAD10
DRAIN KIT)
2" MIN.
Note: Do not remove the stiffener
support from inside the wall case
until the chassis is to be installed.
MAIN STUD
JACK STUD
FRAMING FOR WALL CASE
FINISHED FLOOR
CRIPPLE
JACK STUD
SUB-FLOOR
Figure 1 Figure 2
27
THIS DIMENSION
42-1/4" MIN. (RAB71A)
42-3/8" MIN. (RAB77A4)
ADJUSTABLE FRAMING TO SECURE
MAIN STUD
JACK STUDS
16-1/4" MIN. RAB71A
16-1/2" MIN. RAB77A4
Brick Veneer and Frame Construction
1/4"
CAULK*
GRILLE
OUTDOOR
RAB71A 16"
RAB77A4 16-1/4"
*Caulk around
perimeter of wall
case all four sides
where it joins the
building - Interior
and Exterior.
WALL SECTION – DETAILED SIDE VIEW
BY INSTALLER
MOUNTING SCREWS
LINTEL
2-3/8"
CAULK*
RAB71A 13-3/4"
RAB77A4 13-7/8"
20-7/8" (RAB71A)
21" (RAB77A4)
Sub-Base Connected
GRILLE
OUTDOOR
Frame and Brick Veneer Installation
STEEL LINTEL
CAULK*
2" MIN.
WALL CASE
SIDE CHANNEL
ROOM
CABINET
1-5/16"
CAULK*
3-11/16"
3" MIN.
5" MAX.
RAG60 1/4"
1/4"
MIN.
SUB-BASE
RAG61, 62, 63 1-3/8"
FINISHED FLOOR
RAG67 1-1/4"
CAULK*
(RAK204)
CARPET
OR TOP OF
(ALTERNATE ENTRY)
POWER SUPPLY CONDUIT
CONDUIT
RAB71A 16"
RAB71A 13-3/4"
RAB77A4 13-7/8"
MOUNTING SCREWS
20-7/8" (RAB71A)
21" (RAB77A4)
BY INSTALLER
RAB77A4 16-1/4"
WALL CASE
2" MIN.
POWER SUPPLY
Cord-set connected
(BY OTHERS)
CAULK*
28
ROOM
CABINET
CAULK*
WALL RECEPTACLE
OR TOP OF
FINISHED FLOOR
CARPET
*Caulk around perimeter of wall case all four sides
where it joins the building - Interior and Exterior.
16"
3" MIN.
5" MAX.
16"
RAB71A
ROOM
16-1/4"
RAB77A4
CABINET
(RAK204)
SUB-BASE
FLOOR
LEVELING LEG
CONDUIT
POWER SUPPLY
(ALTERNATE ENTRY)
Sub-Base ConnectedCord-Set Connected
SIDE
CHANNEL
GASKET
(FIELD
SUPPLIED)
WALL OR
WINDOW
WITH RAG61-63
RAB71A 22-1/4"
CASE ANGLE (FIELD SUPPLIED)
Gasket and
caulk around
RAB77A4 22-3/8"
perimeter of
wall case all
four sides
where it joins
the building
RAB71A 21-1/8"
RAB77A4 21-1/4"
WITH RAG60
WALL CASE
GRILLE
OUTDOOR
16"
WALL SECTION – DETAILED SIDE VIEW
ROOM
CABINET
RECEPTACLE
(BY OTHERS)
16"
RAB71A
Window, 2" curtain or panel wall installation with RAG rear grille extended beyond outer wall surface
Gasket and
CASE ANGLE (FIELD SUPPLIED)
caulk around
perimeter of
wall case all
four sides
where it joins
the building
RAB71A 22-1/4"
RAB77A4 22-3/8"
WITH RAG61-63
RAB71A 21-1/8"
RAB77A4 21-1/4"
WITH RAG60
16-1/4"
RAB77A4
OUTDOOR
WALL CASE
GRILLE
USE NO
SCREWS IN
CASE
BOTTOM OF
FLOOR
FIELD SUPPLIED
MIN. 2 SUPPORTS
29
SIDE VIEW OF
ALTERNATE
HIGH MOUNT
With conduit
16" RAB71A
CAULK*
power supply.
A
16-1/8" RAB77A4
*Caulk around
perimeter of wall case
all four sides where it
joins the building -
Interior and Exterior.
CAULK*
1/4" (See note 1)
Manufacturer Required
Minimum Installation Clearance
A
Dimension
A
0" Minimum
Allow For Electrical Wiring 0" Min. (See page 27)
B
C
3" Minimum
0" Minimum 2" Recommended
See pages 38-39 for ducted application.
E
D
NOTE:
C
CAULK*
1. FOR OUTSIDE FLUSH MOUNTING SEE PAGE 35 FOR DRAIN INSTALLATION.
MAX. WALL THICKNESS
D
13-1/8"
ADJACENT WALL
LINTEL
E
CAULK*
ROOM
INSIDE
RAB71A 13-3/4"
RAB77A4 13-7/8"
7-1/8"
CABINET
CAULK*
CONDUIT
FIELD
SUPPLIED
B
FRONT VIEW
FINISH FLOOR
WALL CASE INSTALLATION – CORD-SET CONNECTED
RAB71A 13-3/4"
RAB77A4 13-7/8"
are also applicable to other types of construction
Example: block and veneer – dimensional data and comments
CASE
RAB71A 42"
RAB77A4 42-1/8"
CAULK*
FINISHED
EXTERIOR WALL
CAULK*
FINISHED
EXTERIOR
WALL
27-1/4"
TOP VIEW
2-1/2"
ROOM CABINET
D
*Caulk around perimeter of wall case all four sides
where it joins the building - Interior and Exterior.
ADJACENT WALL
ROOM CABINET
WALL OPENING
16-1/4" x 42-1/4" MIN. FOR RAB71A
16-1/2" x 42-3/8" MIN. FOR RAB77A4
ELECTRICAL RECEPTACLE (BY OTHERS).
FLUSH MOUNTED.
See page 44 for line cord length.
30
CAULK*
1/4" MIN.
CASE
ALL 4
CAULK*
SEE DETAIL
SECTION A-A
EXT.
EXTENSION
SIDES
FLASHING
WALL -
ANY
CONSTRUCTION
RAB71A/77A4ROOM
SECTION A-A
*Caulk around perimeter of wall case all four sides
where it joins the building - Interior and Exterior.
CABINET
should be non-ferrous metals. Minimal acceptable
material: Galvanized G-90 painted.
5. Suggested materials for case extension and flashing
CAULK*
D
AS REQ'D.
6-1/4" ± 1/4"
CAULK*
ALL 4 FLANGES
WALL CASE
BASEPAN/FLANGE DESIGN
SHOWING SEALANT LOCATIONS.
CUT DRAIN SLOTS
IN BOTH FLANGES
(FOUR REQUIRED)
TO MATCH DRAIN
HOLES IN RAB71A/77A4
ALL 4
SIDES
WALL
FLANGES AND
DRAIN HOLE
LOCATIONS
SAME AS ON
WALL CASE
METAL CASE EXTENSION FOR WALLS DEEPER THAN 13-1/8" (11-1/8" WITH SUB-BASE)
1" WIDE
45° DRIP LIP
SEALANT - ALL
FOUR (4) FLANGES
procedures described for a standard installation. See
diagrams below. The assembly should be sealed or
caulked to the wall around all four sides both outdoors
and indoors.
NOTE: The wall case/extension assembly should
prior to installation in the wall opening. A quality-
grade sealant should be applied to all four (4) butting
flanges. Use bolts and nuts or oversized self-tapping
screws (driven from the wall case to the extension)
to attach the two assemblies. Clean all drain holes of
excess sealant. The assembly must be free draining.
2. The wall case and extension should be connected
the flashing and wall as shown in section A-A below.
3. Install flashing, using a quality-grade sealant between
4. Install the wall case/extension assembly following
be level.
10-5/8" ± 1/4"
1-1/2"
(4 SIDES)
EXTENSION
(FIELD
SUPPLIED)
Field fabricated – GE recommends the use of one of the deeper RAB71 wall cases offered as special order items.
13-3/4" + D"
2" MIN.
units can be installed in walls of greater depth
®
Zoneline
WALL CASE
RAB71A/77A4
SPLITTER BETWEEN
AIR INTAKE AND
DISCHARGE
depth “D” should allow for a minimum outdoor
projection of 1/4". This allows for room cabinet
clearance to the finished wall and ample surfaces
to apply sealant or caulking for a tight weather seal
between the completed wall case/extension assembly
and the wall opening. It is recommended that the
extension be painted and corner and lap joints be
than the wall case. Where the case recession is less than
3" and where it is possible to waterproof the exposed
sides and top of the opening, the suggested procedure
is to apply a flashing to the bottom of the wall case as
shown on page 32. Where waterproofing is questionable
or not possible, or for installations in walls of greater
depth, the following is a suggested application
procedure. It involves the field fabrication of a case
extension. Since the wall case is a water-bearing
container, the extension likewise must also be water-
bearing and the connection between the two must be
watertight. The case extension must contain splitters
to prevent recirculation of the outdoor air circuit.
1. The case extension is field fabricated. The extension
additionally sealed with a quality-grade sealant.
FLASHING (FIELD SUPPLIED)
31
GRILLE
OUTDOOR
B
FLASHING
CAULK*
CASE
1" WIDE 45° DRIP LIP
*Caulk around perimeter of wall case all four sides
where it joins the building - Interior and Exterior.
B
A
D
C
A
DIMENSIONS:
A. DISTANCE FROM GRILLE OR CASE TO OUTSIDE SURFACE OF WALL PLUS 2" TO 4"
(TO INSERT UNDER CASE).
B. 1" DRIP LIP (MINIMUM)
C. 42" PLUS - SUFFICIENT TO FIT SNUGGLY UNDER AND UP AROUND THE CASE.
D. 2" MINIMUM
(CAUTION: WHEN CAULKING DO NOT BLOCK DRAIN HOLES IN CASE OR GRILLE.)
IF GRILLE IS TO BE MOUNTED TO WALL SURFACE "A" SPLITTERS MUST BE USED. (SEE PAGE 30.)
ALTERNATE – CASE RECESSION LESS THAN 3" WITH SIDES AND TOP OF WALL OPENING WATERPROOF, FLASHING ON BOTTOM ONLY
For an installation that will
provide better protection
against water infiltration, GE
recommends the use
of one of the deeper RAB71A
Series wall cases offered
as special-order items.
(See page 22.)
32
1/4" (See note 1)
Manufacturer Required
Minimum Installation Clearance
A
Dimension
2-3/8" Minimum
3" Min. (5" MAX.)
0" Minimum 2" Recommended
See pages 38-39 for ducted application.
B
C
D
NOTE:
1. FOR OUTSIDE FLUSH MOUNTING SEE PAGE 32 FOR
FLASHING INSTALLATION.
RAB71A 13-3/4"
RAB77A4 13-7/8"
MAX. WALL THICKNESS
RAB71A 16"
SIDE VIEW
WITH WALL
CASE SHOWN
IN PLACE
11-1/8"
RAB77A4 16-1/4"
*Caulk around
perimeter of
wall case all
INTERIOR
WALL
four sides
where it joins
the building
- Interior and
Exterior.
A
C
CAULK*
MOUNTING SCREWS
AND HOLES BY
FINISHED FLOOR
INSTALLER
7/8"
13-3/4"
D
SEE NOTE
LEFT SIDE
RAB71A 16"
RAB77A4 16-1/4"
2-3/8" MIN. CASE
EDGE TO FINISHED
WALL
CABINET
ROOM
3-11/16"
CAULK*
B
CAULK*
LEVELING SCREWS
(2) SUB-BASE BODY
(2) SIDE EXTENSIONS
FINISHED FLOOR
CONDUIT ENTRY
(ALTERNATES)
SIDE VIEW
RAB71/77A4 WALL CASE INSTALLATION - RAK204 SERIES SUB-BASE CONNECTED
1-1/2"
1-5/16" 2-3/8"
LEVELING SCREW
LEVELING SCREW
3" MIN.
ADJUSTABLE
TO 5"
are also applicable to other types of construction
8.80"
10.30"
KNOCKOUT SIZE
SMALL 7/8" DIA.
LARGE 1-1/8" DIA.
TOP VIEW
Example: frame and brick veneer - dimensional data and comments
42"
FRONT VIEW
KNOCKOUTS
(ENCLOSURE)
4 REAR; 4 BOTTOM
*SHOWN WITH ACCESS COVERS REMOVED.
NOTE: CAUTION - REMOVE KNOCKOUTS FROM INSIDE OUT.
LEVELING SCREW
2-3/8"
MIN.
FINISHED
INTERIOR
WALL
BACK VIEW
5.15" 7.70" 18.86" 1.5"
5.15" 7.70"
RECOMMEND 2" TO
INTERIOR ADJACENT
WALL BOTH SIDES.
D
12-3/4" 12-7/8" 13"
WALL
INTERIOR
ADJACENT
33
CASE
MOLDED
TYPE “E”
SUB-BASE
MOUNTING CLIP
RAB71A
USE WITH
RAB77A4
USE WITH
CHASEWAY OPTION
(Shown Without Chassis and Wall Case for Installation Location Only.)
RAK4002B
NOTE: TYPE “E”
MOUNTING CLIP MUST
BE USED WITH MOLDED
CASE.
TYPE
TYPE “A” TYPE “B” TYPE “C”
“D”
TYPE
“E”
6 REQ’D. 2 REQ’D. 8 REQ’D.
SCREW
GREEN
SCREW
GROUND
RAB71A/77A4 Wall Case
(TYPE “C”)
METAL CASE
6"
TYPE “A”
TYPE “D”
SCREW CLIP
TO SECURE
SIDE CHANNELS
SCREW
TYPE “C”
RAK204 SERIES SUB-BASE INSTALLATION AND ELECTRICAL DATA
ACCESS PLATES
NOTE: IF METAL CASE DOES NOT HAVE SCREW HOLES, 5/32" DIA. HOLES MUST
BE DRILLED 6" FROM EACH SIDE IN FRONT FLANGE. (SEE INSERT).
SCREW
TYPE “C”
5/32" DIA. HOLE (SEE NOTE)
FOR SECURING TYPE “D”
CLIPS TO SLEEVE USING
TYPE “A” SCREWS
6"
TYPE “B” SCREW
SCREW
TYPE “A”
Electrical wiring may enter the sub-base through any of the knockout holes provided in the sub-base.
Knockout holes in the sub-base access plate may accommodate a receptacle, which allows the use of a power cord (if permitted by code for the particular installation).
SIDE CHANNELS ARE ADJUSTABLE
FROM 13-3/4" TO 2-3/8" IN LENGTH
BY BREAKING OFF SECTIONS OF SIDE
CHANNELS.
34
A knockout for a circuit breaker, fuseholder or a disconnect is also provided. See pages 23 and 24 for description of electrical contents of these sub-bases.
CONDENSATE DISPOSAL SYSTEMS
Cooling Condensate
Air conditioners produce condensate water as a result of lowering the humidity of the area being conditioned. When the indoor coil temperature is below the dew point, moisture in the air condenses into water droplets on the coil. This water drains to a pan located under the indoor coil and is routed through the barrier (the partition separating the indoor and outdoor sides of the unit) to the base pan on the outdoor side. It is then picked up and dispersed against the outdoor coil, which is hot when the unit is in the air conditioning mode. The water is evaporated into the atmosphere by contact with the hot outdoor coil. This evaporation process also helps lower the temperature of the outdoor coil and improves the operating efficiency of the unit.
Slinger Ring Systems
Packaged terminal units employ various means of dispersing the condensate water. One of the most popular, and most effective, means is by the use of a “slinger ring.” A slinger ring is a ring around the circumference of the outdoor fan. The design of the unit positions the slinger ring very close to the bottom of the base pan so water in the base pan is lifted by the rotating ring. Water picked up by the slinger ring will be dispersed into the air stream and deposited on the hot outdoor coil where it evaporates.
All Zoneline® Series packaged terminal air conditioners and packaged terminal heat pumps utilize a slinger ring for cooling condensate disposal.
Certification Test Requirements
AHRI (Air Conditioning, Heating & Refrigerating Institute) requires that all certified packaged terminal air conditioners and packaged terminal heat pumps pass a cooling condensate disposal test. One stipulation of the AHRI test is that “the test start with condensate collection pan brimful.” In order to pass the AHRI Condensate Disposal Test the unit must operate continuously for four hours without condensed water blowing, dripping, or running off the unit casing during the test or after the unit has been turned off. Under extremely high outdoor humidity conditions or extreme operating conditions, such as exceptionally high air infiltration (a door or window left open while the unit is running, for instance) it is possible for any air conditioner to be unable to dissipate all the cooling condensate generated.
All Zoneline Series packaged terminal air conditioners and packaged terminal heat pumps meet the condensate disposal requirements of AHRI standards 310 and 380.
Heat Pump Condensate
During the operation of a unit in the heat pump, or “reverse cycle,” mode, the outdoor coil becomes the cold coil and the indoor coil becomes the hot coil due to reversing the flow of the refrigerant. When the temperature of the outdoor coil is below the dew point, condensation will form on the outdoor coil just as it does on the indoor coil during cooling operation. Since the dew point is humidity- as well as temperature­related, there may be more condensate on days when the relative humidity is high.
Heat Pump Condensate Disposal
Since the outdoor coil is cold during heat pump operation, the condensate water cannot be deposited on the outdoor coil because the water would cause frost to form on the coil. This frost would block the airflow through the coil. Rather than allow this problem to occur, heat pump units must dispose of the condensate in another manner.
Temperature-Activated Drain Valve
The most widely used method of disposing of heat pump condensate is with a temperature-activated drain valve. This is a device mounted in the base pan of a heat pump unit with a bellows that expands on temperature rise and contracts with temperature drop. A shaft with a rubber plug on the end is connected
to the bellows. When the outdoor temperature remains above a certain temperature, the bellows is expanded and the plug fits tightly into a hole in the bottom, or base pan, of the unit. When the plug is blocking the hole, as it should be during cooling operation, the condensate water is contained in the base pan. At temperatures when heating is required, the bellows contracts, the rubber plug is retracted from the hole and the heat pump condensate water is allowed to drain into the wall case. The valve is fully open at approximately 45°F.
Drain Kits
Although the Zoneline units are designed to dissipate most of the condensate generated during normal cooling operation, there may be times when abnormal operating conditions cause more condensate than the unit can dissipate. Heat pumps also generate condensate that the unit may not be designed to dissipate. For these reasons, if condensate dripping from the wall case is objectionable, an internal or external drain system should be installed. See pages 36 and 37 for information covering the drain systems and the RAD10 kit available to connect to the wall case.
Internal Condensate Removal (ICR) System
GE has developed an Internal Condensate Removal (ICR) system for packaged terminal heat pumps. This system has been offered as an option on Zoneline packaged terminal Heat Pumps since 1982, and thousands of them are in use. During heat pump operation, the ICR system utilizes a small pump to lift the water from the base pan and pump it into a collector tray positioned above the indoor coil. The water drains from the collector tray and drips onto the warm indoor coil where it is evaporated into the room atmosphere. If an excess amount of water is pumped to the indoor side, it is routed back to the outdoor portion of the base pan.
The ICR system has proven to be an effective means of minimizing the amount of heat pump condensate dripping from the unit. However, if the restrictions of a particular installation will allow absolutely no drippage of condensate water from the wall case, the installation of an internal or external drain system is recommended.
Units with ICR may not be installed in seacoast or other corrosive environment applications.
35
NOTE: SHADED PARTS AND
SCREWS ARE INCLUDED
WITH RAD10 DRAIN
KIT. USE EITHER THE
90° ELBOW TUBE OR
THE STRAIGHT TUBE
DEPENDING UPON
Alternate
6" long, 1/2"
O.D. straight
copper tube.
CABINET
THE REQUIREMENTS
OF THE PARTICULAR
INSTALLATION.
TYPICAL INSTALLATION
WALL CASE ROOM
CASE ANGLES (FIELD SUPPLIED)
REAR
GRILLE
90° ELBOW
Caulk around
perimeter of
wall case all
four sides
where it joins
the building.
DRAIN TUBE
FLOOR
FIELD SUPPLIED
MIN. 2 SUPPORTS
"
3"
4
CASE
PROJECTION
BEYOND WALL
WALL CASE WITH RAD10 DRAIN KIT
External Drain. See page 37 for internal drain.
“B”
SCREWS
“A”
PLASTIC
METAL
SEE PAGE 37 NOTE #6
SQUARE DRAIN HOLES
1/2" O.D. 90° ELBOW DRAIN TUBE
NEOPRENE SPONGE GASKET
STEEL MOUNTING PLATE
USE TYPE “A” SCREW FOR METAL CASE (RAB71A)
AND TYPE “B” SCREW FOR MOLDED CASE (RAB77A4)
WATER DRAINAGE - Precipitation entering the unit through the outdoor louver may not be removed entirely by the
condensate removal system. The base pan flange is designed to allow excess water, either condensate water or
precipitation, to flow into the wall case and drain through two drain holes in the rear of the wall case. If there is more
water in the wall case than can be drained through these holes it will drain through the three overflow drain holes.
These drain holes must not be blocked when mounting or caulking the wall case.
For those installations where water draining from the drain holes is objectionable or where positive drainage is desired,
the RAD10 drain kit is available with either a 90° elbow or a 6" straight tube to be used either to connect to a field-
supplied drain line or to allow the water to drip free rather than drain down the surface of the building.
NOTE: Drain kit using either the 90° elbow tube or the straight tube may be installed without modification when using
RAG60 exterior grille. Drain kit using the 90° elbow tube may be installed without modification when using RAG61
through RAG63 exterior grilles. Modification must be made to the RAG61 through RAG63 exterior grilles when using the
straight tube. Modification must be made to the RAG67 grille if using either the 90° elbow tube or the straight tube (see
installation instructions with the RAG67 grille).
36
SEE DETAIL
BELOW
HOLES
SEE NOTE 6
SQUARE DRAIN
OVERFLOW RELIEF DRAIN
WALL CASE WITH RAD10 DRAIN KIT
Internal Drain. See page 36 for external drain.
condensate to an internal drain system in the building.
wall. It may be located anywhere on the room-side portion except for sub-base installations.
For these the drain should be at least 3" from the indoor edge of the case so as to adequately
1. The RAD10 drain kit is installed in the bottom of the wall case when it is desired to drain
NEOPRENE SPONGE GASKET
STEEL MOUNTING PLATE
GASKET
USE TYPE “A” SCREW FOR METAL CASE (RAB71)
AND TYPE “B” SCREW FOR MOLDED CASE (RAB77A4)
INCLUDED WITH RAD10 DRAIN
KIT. THE 90° ELBOW TUBE IS
RECOMMENDED FOR INTERNAL
DRAIN INSTALLATION.
NOTE: SHADED PARTS AND SCREWS
“B”
PLASTIC
DETAIL
clear the sub-base.
2. The drain kit is mounted on the bottom of the wall case prior to installation of the case in the
3. A template is furnished with the kit for locating the necessary three holes in the case bottom
CABINET BOTTOM
TUBE
—two to provide a securing means and one to provide a drain hole for the 1/2" OD tubing
(see details at left).
4. A tube or hose 1/2" I.D. (obtained locally) must be installed on the drain tube and connected to
1/2" OD
the internal drain system in the building.
5. With the RAD10 the two square drain holes in the bottom outer flange of the wall case are
COVER
one 1/4" diameter hole located 3/4" above case bottom provide overflow drainage to
the outdoors when wind-driven rain enters the chassis.
sealed by the gaskets and mounting plates shown above.
6. Two 1/2" diameter holes located 1/4" above the case bottom in the bottom outer flange and
PLATE
USE TYPE “A” SCREWS FOR BOTH RAB71A AND RAB77A4
SCREWS
“A”
NUT
METAL
(MOLDED CASE (RAB77A4) ONLY)
37
DUCTED INSTALLATIONS
4100 and 6100 Series Zoneline® units may be used in ducted installations.
With a ducted installation it is possible to condition the air in two areas that have a common wall separating them. A special adapter mounts on the wall case and a transition piece directs the air from the unit into the adapter. Instructions for mounting the adapter to the wall case are included with the duct adapter. The adapter contains a grille that allows air from the unit to be discharged into the primary room and the adapter connects to a duct extension that allows the air to flow to the adjoining room. Ducting a unit may allow a single unit to be used rather than a separate unit in each room, providing a means of reducing initial equipment cost. The duct may extend a total of 15 feet (with a field-fabricated insulated duct extension) in one direction, either to the right or to the left of the unit. A baffle installed in the discharge duct of the adapter is provided from the factory to provide approximately 35% air discharge into the primary room (room in which the unit is installed) and 65% into the secondary (adjacent) room. To increase the amount of air discharged into the primary room, the damper may be modified by removing the discharge grille on top of the adapter and folding over (or cutting off) the scored section of damper to provide approximately a 50/50 split. Completely removing the discharge damper will result in approximately 75% air discharge into the primary room and 25% into the secondary room.
The installation of the wall case and sub-base, if used, is the same for units being ducted as for free-standing units. The duct adapter support bracket overlaps the wall case by 1" and the bracket and mounting screws add approximately 3/8" (3/16" on each side) to the width of the wall case. If less than 1" of the wall case projects into the room it will be necessary to allow for the additional width in the opening for the wall case. The duct adapter mounting brackets should be mounted prior to installing the case in the wall.
Refer to pages 39 and 40 for drawings of ducted installations. Prior to the installation of the transition from the room cabinet
to the adapter, it will be necessary to remove the discharge grille from the room cabinet. Instructions for this modification are included with the duct adapter.
Duct Extension, Mounting Collar and Register RAK601
Mounting Collar and Supply Register RAK602 —These
components are included in the Duct Extension Kit RAK601. They may be ordered separately for installations where two duct extensions are made from one RAK601.
DUCTED APPLICATION CONSIDERATIONS
When designing a ducted application, some application considerations to be made include:
1. Do not exceed the 15-foot-length maximum for the duct extension. Field-supplied duct extension must be completely insulated with minimum of 1/2" insulation
2. The duct must be a straight run. Turns or bends in the duct extension create air pressure drops that the unit is not designed to overcome.
3. Turn the “Duct Mode” on in the auxiliary control settings (Mode 7). This increases the fan speed to ensure proper circulation.
4. Minimum recommended clearance between the unit and the adjacent wall is 2".
5. Provisions for return air must be made to allow air circulation from secondary room. Doors in both secondary and primary rooms may be undercut or a return grille may be installed through a common wall.
6. When calculating the heat gain/heat loss take both areas into consideration.
REPLACEMENTS OF EXISTING DUCTED UNITS
Since the design of the Zoneline chassis has changed over the years to provide better performance and appearance, some of the components used in ducted applications have changed. Select the proper components from the information below. The best procedure in determining the correct kit is to measure the existing duct extension cross section.
NEW DUCTED INSTALLATIONS
Components
Duct Adapter RAK6052 — The duct adapter is secured
to each side of the wall case and requires the drilling of mounting holes in the wall case during installation. A template for the hole location is in the installation instructions. By securing the duct adapter to the wall case, the chassis retains the slide-out feature for servicing after the transition piece is removed.
Duct Extension RAK601 — This kit contains a 44"-long insulated duct, a register mounting collar, and an air supply register. It can be secured to the duct adapter at either end of the adapter. This duct may be cut at any dimension and used in two applications providing the sum of the two duct lengths necessary does not exceed the 44" length. Even in single applications, the mounting flange must be cut off one end of the duct to accept the collar and supply register.
38
Duct Adapter RAK6052
Flat-Top Discharge Units (Zoneline Units Built Prior to 1988)
Existing Duct Extension Cross-Section Measurements: 8-3/8" height x 6-1/2" width
Duct Adapter RAK7012 — This duct adapter will allow the
replacement of a new chassis (4100 or 6100 Series unit) into an existing ducted application. This adapter will align properly with the duct extension and will eliminate the need to modify the wall opening. In order to minimize replacement costs, some of the components of the old duct adapter must be removed and used in the new installation. Consult the Installation Instructions of the RAK7012 before removing and discarding the old duct adapter. (See notes on page 58.)
Slope-Front Discharge Units (AZ series models)
Existing Duct Extension Cross-Section Measurements: 7-3/32" height x 6-1/2" width
Duct Transition RAK7022 — This duct transition will allow the
replacement of a new slope-front discharge Zoneline chassis (4100 or 6100 Series unit) into a previous-design slope-front ducted installation. (See notes on page 58.)
8" high
44"
RAK601
44" LENGTH
7-3/8"
wide
RECOMMENDED
MINIMUM
CLEARANCE
2" TO SIDE WALL
DUCT ADAPTER EXTENSION HAS 1/2" INSULATION
RAK6052
ADAPTER
TRANSITION
DUCTED APPLICATION (AZ2500/2800/2900/3500/3800/3900/4100/6100 SERIES)
collar, and discharge grille. Duct extension must be cut to required length. Two ducted
installations may be made from one kit if the combined ducted length is less than 44".
RAK602 kit contains mounting collar, discharge grille and mounting hardware
necessary for second installation.
Maximum duct extension length is 15'. Duct extension must be field fabricated for
installations where length of duct exceeds length of RAK601 (44"). Field-fabricated
duct extension must be insulated to prevent condensation from forming on exterior.
Duct extension may not contain bends or turns.
Notes:
1. RAK6052 kit includes duct adapter, transition and mounting hardware.
2. RAK601 duct extension may be installed at either end of the RAK6052 duct adapter.
electrical installation requirements.
3. Ducted units may need to be permanently connected. Check local code for specific
4. Duct extension kit RAK601 contains 44" duct extension, discharge grille mounting
5. Filler strip (field supplied) actual width depends upon wall case projection into room.
A flush installation to finished wall (i.e., no filler strip) can be made.
room. Doors in both secondary and primary rooms may be undercut or a return grille
may be installed through common wall.
6. Unit must be installed to provide at least a 2" clearance between side of unit and wall.
7. Provisions for return air must be made in order to allow air circulation from secondary
8. For replacement of previous-design units, see pages 38 and 58.
39
Caulk around
perimeter of
wall case all
four sides
where it joins
the building
- Interior and
Exterior.
RAG60 - 1/4"
RAG61-63 - 1-3/8"
RAG67 - 1-1/4"
MIN.
2-3/8"*
1/4"
MAX.
CAULK
CAULK
WALL CASE
CAULK
CAULK
FILLER STRIP (SEE NOTE 5 ON PAGE 39)
RAK
204
3-11/16"
Sub-Base Installation
6-1/2" 11-1/8"
RAK6052
ADAPTER
7-3/32"
TRANSITION
2-29/32"
16-1/8"
ROOM
CABINET
3" MIN.
FLOOR
FINISHED
5" MAX.
*2-3/8" min. when installed with RAK204.
See page 39 for all notes
RAG60 - 1/4"
RAG61-63 - 1-3/8"
RAG67 - 1-1/4"
MAX.
12-3/4"
ANY CONSTRUCTION
1/4"
MIN.
CAULK
CAULK
3/4" MIN.
WALL TO
CASE EDGE
CAULK*
WALL CASE
DUCTED DETAILED SIDE VIEWS (AZ2500/2800/2900/3500/3800/3900/4100/6100 SERIES)
Line-Cord Installation
6-1/2"
RAK6052
ADAPTER
10" 7-3/32"
TRANSITION
2-29/32"
16-1/8"
ROOM
CABINET
CAULK*
RECEPTACLE
FLOOR
FINISHED
(BY OTHERS
ALT. LOCATIONS)
*Caulk around perimeter of wall case all four sides
where it joins the building - Interior and Exterior.
40
EXTERIOR GRILLES
Four styles of outdoor grilles are available for exterior treatments. The standard stamped aluminum grille (RAG60), the molded architectural louvered exterior grilles (RAG61-63) and the extruded aluminum architectural louvered grille (RAG67). All grilles include air deflectors (RAK40) and gaskets to prevent condenser air recirculation.
RAG67
RAG60 Outdoor Grille
RAG60 Outdoor Grille — The standard exterior grille is made of durable aluminum to protect chassis components and prevent air recirculation.
RAG61 Outdoor Grille
RAG61, 62, 63 Architectural Grille — One-piece optional molded grille and frame assembly provides improved appearance, protection and weatherability. Molded of durable polycarbonate, the surfaces of the grille have a colorfast, slightly textured finish which blends well with most types of wall surfaces. The grilles can be painted in the field to match the building for improved aesthetics.
Colors: RAG61 — Beige
RAG62 — Dark Maple RAG63 — Bittersweet Chocolate
RAG67 Extruded Aluminum Grille — The RAG67 is made from extruded anodized aluminum for use where an aluminum architectural grille is preferred. The RAG67 is available in a clear finish and may be special ordered from GE in other colors. Minimum order quantities may be required. Contact your GE salesperson for details.
All grilles are installed and secured to the wall case from the inside. Keyhole slots in the rear flange of the case allow the grille to be placed in position before securing it firmly to the wall case.
Replacement of existing units: If an existing grille is not replaced, capacity and efficiency will be reduced and the unit may fail to operate properly or fail prematurely. A deflector kit, RAK40, must be used with grilles that were not designed for current AZ Series GE Zoneline
®
units. The RAK40 contains air deflectors and gaskets that mount to the chassis to direct the hot exhaust air away from the air intake to allow the unit to function properly. All grilles used with GE Zoneline units must comply with requirements of Exterior Architectural Treatments and Special Outdoor Grilles (See page 42).
41
EXTERIOR ARCHITECTURAL TREATMENTS AND SPECIAL OUTDOOR GRILLES
The architectural design of a building may dictate the use of special or oversized louvers for aesthetic reasons. Louvers other than standard Zoneline® exterior grilles may be used on the Zoneline unit, however, these special louvers, or any special exterior architectural treatments of the building facade that may restrict the free circulation of condenser airflow, should be referred to GE Application Engineering for evaluation and approval. The following guidelines should be followed in selecting a louver:
1. The louver must have a minimum of 65% free area. ASHRAE defines "free area" as the minimum area of the opening in an air inlet or outlet through which air can pass. Percent (%) free area equals the X dimension divided by the Y dimension.
2. The louver should be attached to the wall case in a manner that will prevent recirculation of condenser discharge air into the air inlet. If the louver is not attached directly to the wall case, a field-supplied splitter or gasket is required between the chassis and the louver to prevent recirculation.
It is important that the above criteria be followed since a louver that is too restrictive or allows recirculation will reduce the unit’s capacity and efficiency, increase the electrical current draw, cause intermittent operation due to the compressor overload protector shutting the compressor off, and cause failure of the compressor overload protector and shorten compressor life. Using the unit with a grille that is too restrictive or allows recirculation may constitute improper installation and will void the unit's warranty.
A scale drawing of the louver section should be sent to GE Application Engineering. To assure the proper performance of the Zoneline unit and comply with Underwriters Laboratories requirements, it may be necessary to send a sample louver section (at least 16" x 42") to an independent lab to be tested with the Zoneline unit.
Sample Calculations
Free Area (%) =
F.A. % =
42
x
x 100 x = 1" y = 1.5"
y
1
x 100 = 66.7%
1.5
POWER CONNECTION FOR 4100 AND 6100 SERIES ZONELINE UNITS
All 4100 and 6100 Series Zoneline units are equipped with universal heaters allowing chassis installation flexibility. The Zoneline units are connected to the building power supply by a unique power connection kit. By utilizing a separate universal power connection (UPC) kit, each unit is capable of providing various outputs of electric resistance heat to more closely meet the heating requirements of the particular room, thereby increasing the installation flexibility of the particular chassis. This power connection kit is the only means of supplying power to the Zoneline chassis. The appropriate kit is determined by the voltage, the means of electrical connection, either line-cord connected or permanently connected, and the desired resistance heat output that may be supported by the branch circuit.
230/208-Volt Line-Cord Connected Units
Line Cord Kits consist of a self-aligning nine-pin molded
connector that plugs into a mating connector on the Zoneline chassis and insulated line cord with an electrical plug on the end. The configuration of the electrical plug conforms to National Electrical Code (NEC) standards for the circuit amperage, and the position of the wires in the nine-pin connector determines the heater wattage and current requirements when it is plugged into the Zoneline chassis.
The power connection kit is selected by the amperage of the circuit where it will be installed. Each line cord kit has an integral Leakage Current Detection and Interruption (LCDI) or Arc Fault Current Interrupter (AFCI) device as required by the NEC and Underwriters Laboratory (UL) for line-cord connected air conditioners manufactured on or after August 1, 2004. The line-cord power connection kits are shown in the table below.
230/208-Volt Line-Cord Connected Units
Line Cord
Kit
RAK3153A 8150/7900 2450/2360 11.0/11.6 15 RAK3203A 11200/10900 3350/3230 15.1/16.0 20 RAK3303A 16000/15450 4750/4580* 21.2/22.4 30
Elect ric Heat Amps include electric heater and fan motor cur rent draw. *Watt age not available with 7,000 BTU systems.
Electric
Heat
BTUH
Electric
Heater
Watts
Electric
Heat
Amps
Min. Circuit
Protection
(Amps)
230/208-Volt Permanently Connected Units
Permanently connected units do not require the LCDI or AFCI device. Permanent connection is usually made through the use of a sub-base. Each 230/208-volt sub-base consists of a sub-base with appropriate receptacle for minimum circuit amperage, a chaseway to route power connector from the sub-base to the chassis, wiring to connect the sub-base to building wiring and a short line cord with a self-aligning nine-pin connector to connect to chassis and plug into the receptacle in the sub-base. Permanent, or direct-wired, installation of a 230/208-volt unit requires a junction box kit, RAK4002A, which attaches to the chassis to form an enclosed junction box.
The short sub-base line cord may not be used without the sub-base.
Specifications subject to change.
For 4100 and 6100 Series 230/208-volt units where a permanent installation using flexible conduit is desired, the RAK4002A forms an enclosed junction box on the chassis. The RAK4002A has a 7/8"-diameter hole to allow conduit to be connected to the junction box. For direct connection, purchase and install the appropriate Universal Power Supply Kit (also referred to as the Direct Connection Kit below) that matches the ampacity of the building circuit connected to the unit. This nine-pin connector with three 7"-long conductor wires is used for direct connections to the building wiring inside a direct-connect junction box. These wires are then connected to the building wiring by field-supplied connectors.
230/208 Volt Sub-Base and Direct-Connected Units
Sub-Base
RAK204D15P RAK4157 8150/7900 2450/2360 11.0/11.6 15 RAK204D20P RAK4207 11200/10900 3350/3230 15.1/16.0 20 RAK204D30P RAK4307 16000/15450 4750/4580* 21.2/22.4 30
Elect ric Heat Amps include electric heater and fan motor cur rent draw. *Watt age not available with 7,000 BTU systems.
Direct
Connection
Kit
Electric
Heat
BTUH
Electric
Heater
Watts
Electric
Heat
Amps
Min. Circuit
Protection
(Amps)
265- or 277-Volt Unit Installation — Permanently Connected Units
NEC (Article 440.60) requires permanent connection for units connected to power sources over 250 volts; therefore these units must be permanently connected (direct-wired) with field-supplied connectors. Units connected using a sub-base meet the requirement for permanent connection since all wiring is internal wiring between the sub-base and the chassis.
Since 265-volt units may not be line-cord connected, an LCDI device is not required.
265 Volt Sub-Base and Direct-Connected Units
Sub-Base
RAK204E15 8150 2460 9.6 15 RAK204E20 11550 3460 13.3 20 RAK204E30 16350 4860* 18.6 30
Elect ric Heat Amps include electric heater and fan motor cur rent draw. Each 265-volt sub-base kit consists of a sub-base with appropriate receptacle for minimum circuit ampera ge, a chaseway to route the power connector from the sub-base to the chassis and wi ring to conne ct the sub-ba se to the buildin g wirin g. *Watt age not available with 7,000 BTU systems.
Electric Heat
BTUH
Electric Heater
Watts
Electric Heat
Amps
The 265-volt power connection kit must be ordered separately.
All wiring must conform to local electrical regulations and codes.
Min. Circuit
Protection
(Amps)
43
ESSENTIAL ELEMENTS ORDERING OVERVIEW
230/208-volt line-cord connected units — order line cord kit. 230/208-volt sub-base connected units — order sub-base
(includes power connection kit) and junction box for chassis (if hard wired).
265-volt units — order sub-base and power connection kit separately.
ELECTRICAL WIRING INFORMATION – 4100/6100 SERIES
All Zonelines are single-phase 60 hertz units. For all installations, the feeder, sub-feeder, branch circuit
and electrical protective devices and selection must conform to the National Electrical Code (NEC) and to local codes.
Maximum connected load in amperes, including demands for the electric heater and the fan motor, are shown on page 45. Branch circuit ampacity and electrical protective device sizing are shown on page 43 for 230/208-volt and for 265-volt units.
More than one unit per branch circuit is not recommended. When in doubt, consult the NEC. All wiring, including installation of receptacle, must conform to local electrical regulations and codes.
REPLACEMENT OF EXISTING CHASSIS
230/208-Volt and 265-Volt Units
There have been changes to NEC and improvements and modifications to the Zoneline® chassis and sub-bases since the unit was first introduced. Some of these changes require alterations to be made when replacing an older unit with a new chassis.
Permanently Connected Units With Sub-Base
If the existing unit is connected to a sub-base, the installation of the new unit may involve modifying the existing installation slightly. It is recommended these modifications be made by a qualified electrician.
If the existing sub-base is the full width of the wall case, RAK201 sub-base access plate may be ordered and used to replace the cover on the old sub-base. Field-supplied wiring, conduit and conduit connectors should be used to make a connection between the new chassis and the center knockout of the RAK201. The wiring connections should be made inside the sub-base and the RAK201 attached to the sub-base with the two screws provided.
If the existing sub-base is not the full width of the wall case, the electrician will have to modify the existing cover plate to allow field-supplied wiring, conduit and conduit connectors to be run from the permanent connection kit to the sub-base.
The wiring harness can be ordered separately as RAK4002CW.
Receptacle
Type Mfg Part No Configuration
15 AMP
Tan dem
NEMA6-15R
20 AMP
Perpendicular
NEMA6-20R
30 AMP
Large Tandem
NEMA6-30R
Hubbell
P&S
Hubbell
P&S
Hubbell
P&S
5661 5661
5461 5871
9330 5930
Line-Cord Connected Units
The plug configuration of new line-cord connected units complies with the current NEC standards. Older installations may have wall receptacles that conformed to NEC standards at the time the building was constructed and may not match the configuration of the plug on the new line cord. The recommended solution is to change the wall receptacle to conform to current standard plug configuration. See chart on this page for current receptacle configuration.
58"
21"
Typ ical Line-Cord Power Connection Kit RAK3203A shown
44
Inside
Maximum Cord Extension
MAXIMUM CONNECTED LOAD
The maximum connected load of a Zoneline unit occurs when the unit is in resistance heating operation. The maximum amperage shown in the tables below is the combined total of the resistance heater and the indoor fan motor.
230/208-Volt Line-Cord Connected Units
Power Connector Kit
RAK3153A
RAK4157
RAK204D15P
MODEL
NUMBER
AZ41E07DA* 11.0 11.6 15.1 16.0 N/A N/A AZ41E09DA* 11.0 11.6 15.1 16.0 21.2 22.4 AZ41E12DA* 11.0 11.6 15.1 16.0 21.2 22.4
AZ41E15DA* 11.0 11.6 15.1 16.0 21.2 22.4 AZ61H07DA* 11.0 11.6 15.1 16.0 N/A N/A AZ61H09DA* 11.0 11.6 15.1 16.0 21.2 22.4
AZ61H12DA* 11.0 11.6 15.1 16.0 21.2 22.4
AZ61H15DA* 11.0 11.6 15.1 16.0 21.2 22.4
*All version s
Elect ric Heat Amps incl ude elec tric heater and fan motor current draw.
230 V 208 V 230 V 208 V 230 V 208 V
265-Volt Units
Sub-Base/Power Connector Kit
RAK204E15
RAK5172 RAK5157
MODEL
NUMBER
AZ41E07EA 9.6 13.3 N/A AZ41E09EA* 9.6 13.3 18.6 AZ41E12EA* 9.6 13.3 18.6 AZ41E15EA* 9.6 13.3 18.6
AZ61H07EA* 9.6 13.3 N/A AZ61H09EA* 9.6 13.3 18.6 AZ61H12EA* 9.6 13.3 18.6 AZ61H15EA* 9.6 13.3 18.6
*All version s
Elect ric Heat Amps incl ude elec tric heater and fan motor current draw.
265 V 265 V 265 V
RAK204E20
RAK5202 RAK5207
RAK204E30
RAK5302 RAK5307
RAK3203A
RAK4207
RAK204D20P
RAK3303A
RAK4307
RAK204D30P
LATENT SYSTEM CAPACITY
The total capacity of an air conditioner is made up of the sensible capacity, the output of the unit used to remove heat from the air in the area being conditioned, and the latent capacity, the output of the unit used to dehumidify the air in the area being conditioned. For humid climates and applications, the sensible/latent capacity split of the unit should be considered. The sensible capacity listed in the specification charts on pages 54 and 55 is at a standard rating condition of 95°F dry bulb/75°F wet bulb outdoors; 80°F
Specifications subject to change.
dry bulb/67°F wet bulb indoors. The latent system capacity is
1.00 minus the sensible capacity. (If the sensible capacity is listed at .74 the latent capacity is .26. This means that 74% of the capacity of the unit is used to remove heat from the air and 26% is used to remove moisture from the air at standard test conditions.)
In some applications, information about the sensible/latent split, or ratio, at conditions other than the standard rating conditions is needed.
45
NORMAL YEARLY OPERATING DATA
(Cooling Hours based on 75°F indoor temperature with air conditioner sized to meet the design conditions.)
ASHRAE Heating Estimated Degree Cooling Location Days Hours
ALABAMA
Birmingham 2,551 1,390 Huntsville 3,070 1,340 Mobile 1,560 1,640 Montgomery 2,291 1,580 ARIZONA Flagstaff 7,152 310 Phoenix 1,765 2,280 Tucson 1,800 1,920 Yuma 974 2,520 ARKANSAS Fort Smith 3,292 1,410 Little Rock 3,219 1,330 CALIFORNIA Bakersfield 2,122 1,530 Fresno 2,611 1,210 Los Angeles 2,061 310 Sacramento 2,502 1,030 San Diego 1,458 390 San Francisco 3,015 110 COLORADO Colorado Springs 6,423 520 Denver 6,283 550 Grand Junction 5,641 910 CONNECTICUT Hartford 6,235 480 DISTRICT of COLUMBIA Washington 4,224 1,010 DELAWARE Wilmington 4,930 770 FLORIDA Jacksonville 1,239 1,690 Miami 214 2,850 Orlando 766 1,930 Tallahassee 1,485 1,500 Tampa 683 2,350 GEORGIA Atlanta 2,961 1,130 Augusta 2,397 1,400 Macon 2,136 1,440 Savannah 1,819 1,510 IDAHO Boise 5,809 670 Lewiston 5,542 600 Pocatello 7,033 570 ILLINOIS Chicago 6,155 780 Moline 6,408 760 Springfield 5,429 890 INDIANA Evansville 4,435 1,090 Fort Wayne 6,205 710 Indianapolis 5,699 820 South Bend 6,439 600 IOWA Burlington 6,114 730 Des Moines 6,588 710 Sioux City 6,951 770 KANSAS Dodge City 4,986 1,020 Goodland 6,141 800 Topeka 5,182 880 Wichita 4,620 1,070
ASHRAE Heating Estimated Degree Cooling Location Days Hours
KENTUCKY Lexington 4,683 830 Louisville 4,660 1,130 LOUISIANA Alexandria 1,921 1,670 Baton Rouge 1,560 1,860 New Orleans 1,385 1,790 Shreveport 2,184 1,470 MAINE Portland 7,511 290 MARYLAND Baltimore 4,654 850 MASSACHUSETTS Boston 5,634 500 MICHIGAN Detroit 6,293 590 Flint 7,377 440 Grand Rapids 6,894 530 MINNESOTA Duluth 10,000 200 Minneapolis 8,382 550 MISSISSIPPI Jackson 2,239 1,560 MISSOURI Columbia 5,046 960 Kansas City 4,711 1,210 Springfield 4,900 970 St . Louis 4,900 1,080 MONTANA Billings 7,049 520 Glasgow 8,996 410 Great Falls 7,750 420 Missoula 8,125 350 NEBRASKA Grand Island 6,530 770 Omaha 6,612 750 NEVADA Ely 7,733 500 Las Vegas 2,709 1,980 Reno 6,332 520 NEW JERSEY Newark 4,589 710 NEW MEXICO Albuquerque 4,348 1,040 Clayton 5,158 720 Silver City 3,705 1,260 NEW YORK Albany 6,875 480 Binghamton 7,286 310 Buffalo 7,062 450 New York 4,811 790 Rochester 6,748 470 Syracuse 6,756 500 NORTH CAROLINA Asheville 4,042 690 Charlotte 3,191 1,230 Raleigh 3,393 1,070 Winston-Salem 3,595 960 NORTH DAKOTA Bismarck 8,851 510 Fargo 9,226 490 Williston 9,243 580
ASHRAE Heating Estimated Degree Cooling Location Days Hours
OHIO Cincinnati 5,265 840 Cleveland 6,351 610 Columbus 5,660 810 Dayton 5,622 740 Toledo 6,494 590 OKLAHOMA Oklahoma City 3,725 1,200 Tulsa 3,860 1,410 OREGON Medford 5,008 620 Pendleton 5,127 590 Portland 4,635 270 PENNSYLVANIA Harrisburg 5,251 730 Philadelphia 5,144 810 Pittsburgh 5,987 590 Scranton 6,254 440 Williamsport 5,934 600 RHODE ISLAND Providence 5,954 470 SOUTH CAROLINA Charleston 2,033 1,390 Columbia 2,484 1,440 Greenville 2,980 1,120 SOUTH DAKOTA Rapid City 7,345 580 Sioux Falls 7,839 610 TENNESSEE Chattanooga 3,254 1,180 Knoxville 3,494 1,070 Memphis 3,232 1,320 Nashville 3,578 1,220 TEXAS Corpus Christi 914 2,380 Dallas 2,363 1,900 El Paso 2,700 1,580 Houston 1,396 1,850 Lubbock 3,578 1,310 San Antonio 1,546 1,920 UTAH Milford 6,497 910 Salt Lake City 6,052 830 VERMONT Burlington 8,269 130 VIRGINIA Norfolk 3,421 1,010 Richmond 3,865 1,020 Roanoke 4,150 870 WASHINGTON Seattle 5,145 180 Spokane 6,655 430 Yakima 5,941 530 WEST VIRGINIA Charleston 4,476 860 Huntington 4,446 820 WISCONSIN Madison 7,863 530 Milwaukee 7,635 450 WYOMING Casper 7,410 600 Cheyenne 7,381 420 Sheridan 7,680 530
Formula for Calculating Operating Costs Using Above Data:
Heating*
* The above formula is for electric resistance heating only. Power consumption using the Zoneline® heat pumps should be adjusted by Seasonal Performance Factor (SPF).
The local power supplier should be consulted for recommended value of “C.” This factor will vary between 17 and 24.
Cooling —
46
Heat Loss KW x Heating Degree Days x “C” x Cost Per KWH
Outdoor Design Temperature Difference
Calculated Heat Gain (BTUH) Installed unit capacity (BTUH) 1000 Watts/KW
Unit Cooling Watts
x =
x Cooling Hours x Cost per KWH = Operating Cost
= Operating Cost
TYPICAL 4100 SERIES, 230/208-VOLT
TEST
7.Moto
TEST TEMPERATURE IS 68degF.
6.HEATER RESISTANCE:
5.This diagram applied to AZ41E series.
10970
17930
29960
49330
51940
94900
7320
11950
19970
32860
34620
63260
I.D COIL
ROOM
90
70
50
32
30
10
degF
SENSOR RESISTANCE(ohm)
3.THERMISTOR SENSOR RESISTANCE:
OR:ORANGE
RE:RED
WH:WHITE YL:YELLOW
BK:BLACK BL:BLUE BR:BROWN
GR:GREEN GY:GRAY
2.COLOR:
*1:The lead wires are multicolured with black tube. *2:The jointwires are white except that the first one is red. *3:The 7k BTU models don't have this wire.
1.
NOTE:
4.TRANSFORMER WINDING RESISTANCE:
2.4kW
1.4kW
1.0kW
PIN NO.3-6 WH-BL
PIN NO.2-5 RD-YL
PIN NO.1-4 BK-BR
265V
208V/230V
HEATER RESISTANCE(ohm)
CHECK POINT
HEATER
CONNECTOR
HEATER
195±35%
200±35%
200±35%
205±35%
75±35%
85±35%
208/230V PA052JB
265V PA053JB
PRIMARY COIL RESISTANCE(ohm) BK-BK
SECONDARY COIL RESISTANCE(ohm)
WH-WH
100±10%
1.31±10%
127±10%
1.27±10%
MODEL NAME
8.FAULT If the wheth
If the pleas
CN1
TERMINAL
BOARD
*1
OPEATION BOARD UNIT
MAIN BOARD UNIT
BCN301.BCN302
BCN7.BCN9
I.D.C
OIL
ROOM
CN11
CN3.CN5.CN6
TRANSFORMER
OR
OR
YL
YL
4321
*2
*2
DRIVE BOARD UNIT
BCN107.BCN108.BCN109
BCN106
CN104
BK
BK
WH
WH
7
1 2
5
BROR
YL
(208/230V)
(265V)
*3
OR
BL
WH
GR
RD
GY
BR
BK
98456321
*3
WH
RD
BK
BR
GY
RD
GR
WH
BL
OR
1
2
345
6
7
9
C
BK
O.L.P
BK
CT101
T1
RY101
NR101
CN8
HEATER CONNECTOR
BL
YL
BR
PR
OTECTOR
FUSE
BK
BL
RD
BLWHYL
RD
BR
BK
HE
AT
ER(2.4kW)
HE
ATER(1.4kW
)
HEAT
ER(1.0kW
)
1
2
3
4
5
6
6
5
4
3
2
1
BL YL BR
CN110
4
1
1
2
3
3 2 1
COMP
.
BL
RUNNING CAPACITOR
WH
RD
S
R
TRIAC UNIT
BL
YL
BT2
BT1
BCN112
E
D
C
RY102
VARISTOR
RD
WH
BK
BL
GY
O.D FM
O.D FAN
CAPACITOR
CN101(WH)
5
3
1
RD
BK
I.D FM
OR
OR
I.D FAN
CAPACITOR
PROTECTOR
A
*2
CN112
1
3
CN105 CN102(YH)
MO
AZ4 AZ4 AZ4
AZ4 AZ4 AZ4 AZ AZ4 AZ AZ AZ A4
AZ AZ AZ AZ AZ AZ AZ AZ
AZ AZ
8
WIRING DIAGRAM
NOTE:
1. *1:The lead wires are multicolured with black tube.
*2:The jointwires are white except that the first one is red. *3:The 7k BTU models don't have this wire.
2.COLOR:
3.THERMISTOR SENSOR RESISTANCE:
SENSOR RESISTANCE(ohm)
degF
10 30
32
50 70 90
4.TRANSFORMER WINDING RESISTANCE:
MODEL NAME
208/230V PA052JB
265V PA053JB
5.This diagram applied to AZ41E series.
6.HEATER RESISTANCE:
TEST TEMPERATURE IS 68degF.
CHECK POINT
HEATER
CONNECTOR
1.0kW
1.4kW
2.4kW
BK:BLACK BL:BLUE BR:BROWN
ROOM
I.D COIL
63260
94900
34620
51940 49330
32860
29960
19970 11950
17930 10970
7320
PRIMARY COIL RESISTANCE(ohm) BK-BK
100±10%
127±10%
HEATER
PIN NO.1-4 BK-BR
PIN NO.2-5 RD-YL
PIN NO.3-6 WH-BL
GR:GREEN GY:GRAY OR:ORANGE
HEATER RESISTANCE(ohm)
208V/230V
195±35%
200±35%
47
SECONDARY COIL RESISTANCE(ohm)
WH-WH
1.31±10%
1.27±10%
75±35%
RE:RED WH:WHITE YL:YELLOW
265V
200±35%
205±35%
85±35%
7.Motor winding resistance TEST TEMPERATURE IS 68degF.
8.FAULT ANALYSIS OF INDOOR FAN MOTOR
If the motor winding resistance is out of spec,please check whether it's the motor's problem; If there is no voltage between pin1 and pin2 of CN102, please check whether it's the problem of PWB.
MODEL NAME
AZ41E07DAB AZ41E07DAC AZ41E07DAP AZ41E07EAB AZ41E07EAC AZ41E07EAP AZ41E09DAB AZ41E09DAC AZ41E09DAP AZ41E09EAB AZ41E09EAC A441E09EAP
AZ41E12DAB AZ41E12DAC AZ41E12DAP AZ41E12EAB AZ41E12EAC AZ41E12EAP AZ41E15DAB AZ41E15DAC
AZ41E15EAB AZ41E15EAC
WINDING RESISTANCE(ohm)
INDOOR
MOTOR
RD-BK
183±15% 183±15% 183±15% 265±15% 265±15% 265±15% 183±15% 183±15% 183±15% 265±15% 265±15% 265±15% 183±15% 183±15%
183±15% 265±15% 265±15% 265±15%
183±15%
183±15% 265±15%
265±15%
OUTDOOR MOTOR HIGH
SPEED
SPEED
RD-BK WH-BK
390±15%
284±15% 148±15%
399±15%
148±15%
399±15% 400±15%
234±15% 139±15%
400±15%
139±15%
400±15% 193±15%
204±15%
193±15%
204±15%
193±15%
204±15%
294±15%
125±15%
294±15%
125±15% 125±15%
294±15% 126±15%
146±15%
126±15%
146±15%
126±15%
146±15%
148±15%
124±15%
148±15%
124±15%
148±15%
124±15%
126±15%
146±15% 146±15%
126±15%
124±15%
148±15%
124±15%
148±15%
LOW
47
TYPICAL 4100 SERIES, 230/208-VOLT SCHEMATIC DIAGRAM
UNIVERSAL CONNECTOR
RUNNING
CAPACITOR
R
COMP MOTOR
P. L. O.
*1: C101 is used for 230V models and both C101A and C102 are used for 265V models.
*2: 4A 250V is used for 230V models;3.15A 500V is used for 265Vmodels. *3: 61H models have this leadwire except for 7000btu models.
DECODER
OPE OPE COOL FAN HEAT
MODE
HIGH
D
LOW AUTO
FAN SPEED
SLEEP
SLEEP
OPERATION BOAR
THERMO
UP
DOWN
REMOTE T'STAT
CDC
EXTERNAL FAN
ROOM
ID.COIL
S
C
TRANSFORMER
CN11
BCN7.BCN9
CN2
INTERFACE
CN1
CN110
CUIT
HEATER POWER
CHECK CIR
Varistor
CN104
BCN106
MAIN BOARD UNIT
FU105
FU104
FU106
FU101
*2
(NR101)
Capacitor
(C101, C101A, C102)
FU103
RY102
*1
*1
AC CLOCK
PROTECTOR
FUSE
RY101
DIP SW
(for setting)
HEATER
HEATER
T1
HEATER
CONTROL CIRCUIT
*3
TERMINAL
BOARD
CN8
SWITCHING
POWER SUPPLY
Fan Motor Capacitor
12V
CN5
CN3
CN6
Outdoor Fan Motor
CN101
BCN108
TRIAC CONTROL
BCN107
BCN109
RY101
RY102
CIRCUIT
RY105
RY104
RY105
SSR1
CT MONITOR CIRCUIT
A
RY104
Indoor Fan Motor
CN102
Fan Motor
Capacitor
HALL IC
CN105
SSR1
TRIAC
DRIVE
BOARD
UNIT
CT101
48
TYPICAL 6100 SERIES, 230/208-VOLT WIRING DIAGRAM
BK
1
WH
2
YL
3
BL
4
RD
5
4
BL
8
1 2 3
6
1
2
1
3
1
3
BCN112
BT1
CN102(WH)
CN103(BL)
CN112
BCN202
)
CN201(YL
)
VARISTOR
CN105(BK
RY102
D
C
TRIAC UNIT
BCN101.BCN108.BCN109
BCN106
WH
1
CN104
WH
2
BK
5
BK
7
BL
3
3
YL
2
2
BR
1
1
DRIVE BOARD UNIT
CN8
NR101
RY110
E
YL
BT2
RY101
T1
CT101
CN110
1
4
OR
BK WH
YL BL
RD
GR
*2
BR
YL
YL
RD
RD
O.D.FAN MOTOR
I.D.FAN MOTOR
*1
FM
FM
*4
*4
ICR
RV
*2
*2
TRANSFORMER
TERMINAL
BOARD
YL
OR BR
CN4.CN5.CN6
MAIN BOARD UNIT
CN11
(265V)
(208/230V)
BK
O.L.P
BK
C
COMP.
R
RD
RUNNING CAPACITOR
BK
FUSE
BL
RD
S
WH
BL
2
1
YL
YL
ROOM
1
BK
1
BK
TOR
PROTEC
HEATER(1.0kW)
CN1
345678
OR
OR
BL
BK
BK
IL CO
COIL I.D.
O.D.
2
365
GY
RD
BR
2
GY
RD
BR
RD
YL
BR
3
1
2
4
5
3
1
2
4
5
YL
WH
RD
BR
BK
TER(2.4kW)
TER(1.4kW)
HEA
HEA
BL
OUTDOOR
GR
543
WH
GR
BL
6
6
BL
BCN7.BCN9
4
8
WH
BL
6
7
BL
WH
HEATER CONNECTO R
*1
9
*3
OR
9
OR
*3
OPEA
TION BOARD UNIT
BCN301.BCN302
NOTE:
1. *1:The lead wires are multicolured with black tube. *2:The jointwires are white ex *3:The 7k BTU models don't have this wire. *4:AZ61H series don't have these wires,except for
AZ61H07DAD.AZ61H09DAD.AZ61H12DAD.AZ61H15DAD. AZ61H07EAD.AZ61H09EAD.AZ61H12EAD.AZ61H15EAD.
2. COLOR:
BK:BLACK BL:BLUE BR:BROWN
GR:GREEN GY:GRAY
OR:ORANGE RE:RED WH:WHITE YL:YELLOW
3. THERMISTOR SENSOR RESISTANCE:
SENSOR RESISTANCE(ohm)
94900
51940 49330 29960
17930 10970
O.D COIL &OUTDOOR
28030 15340 14570 8850
5300 3280
degF
30 32 50 70 90
10
ROOM I.D COIL
63260 34620 32860 19970 11950
7320
4. TRANSFORMER WINDING RESISTANCE:
MODEL NAME
208/230V PA052JB
265V PA053JB
PRIMARY COIL RESISTANCE(ohm) BK-BK
100 ` 10%
127 ` 10%
SECONDARY COIL RESISTANCE(ohm) WH-WH
1.31 ` 10%
1.27 ` 10%
5. This diagram applied to AZ61H series.
6. Heater resistance: TEST TEMPERATURE IS 68degF.
CHECK POINT
HEATER
HEATER CONNECTOR
PIN NO.1-4
1.0kW BK-BR
PIN NO.2-5
1.4kW RD-YL
PIN NO.3-6
2.4kW
WH-BL
TOR VOLTAGE: (1)CN103:PIN 1-2(BK-WH) DC15V; PIN1-6(BK-RD): The DC voltage is AC power supply voltage x 1.4 (2)CN102:PIN1-2(BK-WH) DC15V; PIN1-5(BK-RD): The DC voltage is AC power supply voltage x 1.4
NOTICE: Tu disconnecting motor connector (CN102.CN103). or motor damage may occur.
HEATER RESISTANCE(ohm)
208V/230V
195 ` 35%
200 ` 35%
75 ` 35%
wer supply for 2 minutes before
265V
200 ` 35%
205 ` 35%
85 ` 35%
49
TYPICAL 6100 SERIES, 230/208-VOLT SCHEMATIC DIAGRAM
UNIVERSAL CONNECTOR
CAPACITOR
RUNNING
R
COMP MOTOR
C
. .L.P
O
*1: C101 is used for 230V models and both C101A and C102 are used for 265V models *2:4A 250V is used for 230V models;3.15A 500V is used for 265Vmodels.
*3:61H models have this leadwire except for 7000btu models.
DECODER
OPE
OPE
COOL
FAN
HEAT
MODE
HIGH
LOW
AUTO
FAN SPEED
SLEEP
SLEEP
TRANSFORMER
OPERATION BOARD
THERMO
UP
DOWN
REMOTE T'STAT
CDC
EXTERNAL FAN
ROOM
ID.COIL
OD.COIL
Outdoor
BCN7.BCN9
CN2
CN1
S
CN110
TER POWER
CHECK CIRCUIT
HEA
Varistor
CN104
BCN106
CN11
INTERFACE
MAIN BOARD UNIT
FU104
(NR101)
FU103
FU106
FU105
RY110
FU101
*2
Capacitor
(C101, C101A,C102)
AC CLOCK
*1
RY102
PROTECTOR
FUSE
DIP SW
(for setting)
101 RY
HEATER
HEATER
HEATER
T1
TERMINAL
BOARD
CONTROL CIRCUIT
*3
Outdoor
Fan
Motor
CN102
CN8
SWITCHING POWER SUPPLY
12V
CN5
CN4
CN6
FU102
Indoor
CN103
BCN108
BCN101
BCN109
Fan
Motor
SWITCHING POWER SUPPLY
15V
ISOLATOR
RY101
RY102
RY110
RY201
RY108
Reverse
CN105
CT MONITOR CIRCUIT
Valve
7. DC MO
TRIAC
ICR
RY108
PUMP
CN201
TRIAC CONTROL
CIRCUIT
DRIVE BOARD UNIT
RY201
Sol.
CT101
50
SUGGESTED BID FORM SPECIFICATIONS
The following are suggested specifications for the Zoneline® 4100 Series Packaged Terminal Air Conditioner and the 6100 Series Packaged Terminal Heat Pump.
The contractor will furnish Packaged Terminal Air Conditioners of the sizes and capacities shown on the schedule and in the specifications. The units shall be located as shown on the drawings and each shall consist of a chassis, room cabinet, wall case, sub-base if specified, and outdoor grille.
Units shall be listed by UL, and AHRI and cUL certified as to capacity and efficiency and shall be GE Zoneline models or equal. Unit dimensions shall not exceed 42-1/8" wide and 16-1/4" high with room cabinet in place.
Units shall be designed to operate on (208) (230) (265) volts, 60 Hz, single-phase power.
Chassis. The air conditioner chassis shall be the standard product of the manufacturer and shall be shipped in protective cartons to prevent damage. Cartons shall be appropriately marked at the factory with wording sufficient to warn handlers against improper stacking, up-ending, rolling or dropping.
The chassis shall be the slide-in type, ready to operate after installation.
Each shall consist of the following sections and components:
• Each unit shall have a matching, easily removable, textured finish, wrap-around room cabinet molded of high­temperature styrene to resist corrosion and damage. The room cabinet shall have slide-out washable filters accessible without requiring removal of room cabinet from chassis;
• Hermetically sealed refrigerant system with external vibration isolated rotary-type compressor, condenser and evaporator coils and capillary refrigerant control. Airflow system consisting of one permanently lubricated two-speed fan motor for the outdoor fan and a separate permanently lubricated two-speed fan motor for the indoor fan. Outdoor fan shall be multi-blade axial-flow design made of non­corrosive material. Indoor fan shall be of a design to optimize airflow and operating sound. All motors on the exterior side of the weather barrier shall be of an enclosed design to reduce the effects of moisture and corrosion;
• Line-cord connected units shall require a line-cord power connection kit with integral Leakage Current Detection and Interruption device or Arc Fault Current Interrupter as required by National Electrical Code
®
(NEC) and Underwriters Laboratories. The unit shall have a universal resistance heater with output determined by connection to the power source with the appropriate power connection kit to provide specified heat output;
• A fan-cycle option to permit continuous fan operation or fan cycle operation, independently selectable for heating and cooling operation;
• Fan-only operation in either high or low fan speed selectable by room occupant;
• A positive cooling condensate disposal system which meets the test requirements of applicable AHRI Standard 310 (for Packaged Terminal Air Conditioners) and 380 (for Packaged Terminal Heat Pumps) (80°F dry bulb, 75°F wet bulb, 80% relative humidity);
• Condenser and evaporator coils to be constructed of copper tubing and aluminum plate fins designed to achieve EER and COP rating of the unit;
• Indoor and outdoor airflows that match the capacity of the coils for efficient heat transfer. Water blow-off shall not occur on the indoor coil;
• Adjustable indoor discharge air louvers that provide a 50° off vertical air pattern with an alternate position to provide a 40° off vertical air pattern;
• Easily accessible controls for selection of unit operation and thermostat setting. Controls shall be covered by a hinged door;
• Positive-closing, manually controlled, three-position fresh-air vent capable of providing selection of fully open, partially open or closed setting. Vent door is to be secured for shipping;
• Solid-state thermostat control to sense room temperature;
• Electronic temperature limiting with seven independent heating and cooling settings to limit maximum and minimum temperatures without restricting movement of thermostat control knob;
• Freeze Sentinel to automatically activate the electric resistance heater and fan motor to warm and circulate indoor air to help prevent damage due to freezing temperatures. Freeze Sentinel shall operate as long as unit is connected to powered electrical circuit and unit shall provide ability for owner to defeat the Freeze Sentinel operation;
• Heat Sentinel to automatically activate air conditioner operation when the unit is in the STOP setting when the room temperature warms to 85ºF and turns air conditioner operation off when the room temperature cools to 80°F, if selected by owner;
• Compatible with two-wire Central Desk Control systems;
• Remote Thermostat compatibility with Class 2 remote thermostat;
• Connections to interface with a transfer fan to move air into another room;
Unit shall have means of electrical connection listed by Underwriters Laboratories and compatible with the unit’s required voltage and ampacity in conformance with National Electrical Code
and local codes.
Additional specifications for GE Zoneline 6100 Series Packaged Terminal Heat Pumps
Heat pump units shall provide operation that will either: A) automatically phase in electric resistance heat, if outdoor temperature is below 46°F, if heat pump alone is unable to maintain room temperature; or B) use partial electric resistance heat simultaneous with heat pump operation any time the outdoor temperature is below 46;°F. Selection of A or B operation is made by means of a selector concealed from room occupant. In either A or B operation, the unit will switch to full resistance heat if room temperature continues to decline or the outdoor temperature falls below 25°F. If the outdoor temperature is above 46°F, unit will lock out electric resistance heat and operate on heat pump only.
51
SUGGESTED BID FORM SPECIFICATIONS (cont)
Heat pump unit shall include Reverse Cycle Defrost that automatically begins a defrost cycle when microprocessor determines criteria for defrosting has been met. Defrosting shall be accomplished by systematically ceasing heat pump operation, pausing to allow internal refrigerant pressures to equalize, then operating the compressor with the flow of refrigerant reversed to allow the hot gas to flow through the outdoor coil, melting the accumulated frost. The unit shall automatically resume heat pump operation, after pausing to allow refrigerant pressures to equalize, at conclusion of defrost cycle.
The unit shall be equipped with a temperature-activated drain valve to allow water generated in heat pump operation and defrost cycles to drain into the wall case.
The unit shall have a switch concealed from room occupant to allow heat pump operation to be overridden and heat provided by electric resistance heat regardless of outdoor temperature.
In the event of compressor failure during heat pump operation, unit shall automatically switch to electric resistance heat to maintain selected room temperature regardless of outdoor temperatures.
Specifications for optional Internal Condensate Removal (ICR) system for 6100 Series heat pump units.
The unit shall have a factory-installed Internal Condensate Removal (ICR) system to permit unit to automatically dispose of heat-pump-generated condensate water with no overflow to outdoors during heating under outdoor ambient of 55°F dry bulb, 90% relative humidity; indoor ambient 70°F dry bulb, 52% relative humidity, for four hours of continuous run time.
Wall Cases and Grilles (needed for new installations.) (Alternate specification for steel wall case)
Wall Case. The wall case shall be constructed of heavy-gauge, insulated, zinc-coated phosphated steel with a protective baked-on enamel finish. Bottom critical points of the steel wall case shall be coated with petroleum microcrystalline wax for added corrosion protection and shall meet ASTM B-117, 1800-hour hot air aerated salt spray test.
(Alternate specification for molded wall case)
Wall Case. The wall case shall be constructed of a non-corroding fiberglass-reinforced polyester compound.
Cases shall be installed through exterior walls where shown on the plans and shall be installed per manufacturer’s installation instructions. In no instance shall fasteners be used through the bottom in order to retain the water integrity of the bottom of the wall case.
Outside weather panels shipped with the cases shall remain in place until the outdoor air louvers and chassis are installed, at which time they are to be removed and discarded by the installer.
Outside Grille. Each unit shall be equipped with a standard exterior grille that has been designed to allow unit operation in high ambient conditions. Grilles shall be of material and design specified.
Special grilles or customer louver sections to be supplied by others will conform to a minimum of 65% free area (as calculated by ASHRAE) to allow for proper unit operation and shall be submitted to the PTAC/PTHP manufacturer, if requested, for feasibility and airflow characteristics.
Specifications for Sub-Base (if required)
Sub-Base. Each unit shall have a field-installed UL-listed electrical sub-base. The sub-base shall be attached to the lower inside flange of the wall case prior to installation in the exterior wall. It shall include adjustable screws at the bottom corners to permit exact leveling of the wall case. The sub-base shall have a factory-installed receptacle to allow unit line cord to plug into mating receptacle and shall have a chaseway to contain and conceal the line cord. The sub-base shall have side panels adjustable from a minimum of 2-3/8" to a maximum of 13-3/4" to enclose the area under the wall case.
Weather Resistance. Complete unit including outside louver shall be submitted to an independent agency for weather­resistance tests.
Air-infiltration test to be conducted in accordance with ASTM E283-91. With static air pressure differential of
1.57 lb./ft.
2
(.3" H2O) equivalent to 25 mph wind, allowable
air infiltration shall not exceed 7 ft.3/min. Water-infiltration test to be conducted in accordance
with ASTM E331-86 with static air pressure differential of 10.0 lb./ft2 (1.93" H20) equivalent to 63 mph wind,
5.0 gal./ft2 (8" rain/ft2/hr.) for 15 minutes and there shall be no leakage into the room.
Approvals. Units shall be certified under the AHRI and cUL certification program and listed by UL.
Service. Submit complete information with bid covering service availability to whom service on units will be assigned, along with complete address and phone number, including phone number of emergency service personnel.
Start-Up, Adjust, Demonstrate. Contractor shall be responsible for the initial starting of units, adjustments thereto, etc., to place the units in required operating condition. Contractor shall demonstrate to the owner or his representative the operation of units for both summer and winter functions.
Warranty. The warranty shall be a full one-year parts and labor on the entire unit, plus an additional full four years parts and labor for the sealed refrigerating system, including service call for diagnosis and transportation to and from service shop (if necessary) at no charge to the customer. The warranty shall also include a limited second-through­fifth-year parts-only warranty for fan motors, switches, thermostat, heater, heater protectors, compressor overload, solenoids, circuit boards, auxiliary controls, thermistors, frost controls, ICR pump, capacitors, varistors and indoor blower bearing.
Installation Responsibility. Units shall be installed according to the manufacturer’s recommendations and the manufacturer shall not be responsible for unit failure as a result of improper installation, or unit performance when installed with accessories not approved by the manufacturer.
52
ZONELINE® CHASSIS NOMENCLATURE
The Zoneline chassis is identified by a model number defining
EXAMPLE
the type of unit, cooling capacity, electrical information and optional features included on the unit. When specifying or ordering the Zoneline chassis, use of this nomenclature will assure receiving the correct unit.
AZ61H12DAD
Zoneline
packaged terminal chassis
Chassis series
41= deluxe line cool/
electric heat
61= deluxe line
heat pump
Unit type
E= cooling with electric
resistance heat
H= heat pump with electric
resistance heat
Nominal cooling capacity
07=7,000 BTUH cooling 09=9,000 BTUH cooling 12=12,000 BTUH cooling 15=15,000 BTUH cooling
Voltage/Phase/ Frequency
D= 230/208 Volt, single
phase, 60 Hz
E= 265 Volt, single phase,
60 Hz
Universal power connection
Special Features
B=base unit C=corrosion treated D= internal
condensate removal (ICR) system (heat pump models only) (not for coastal areas)
P=Dry Air 25
RECEPTACLES/SUB-BASES
Tan dem
230/208V 15 Amp NEMA6-15R
Sub-bases
RAK204U RAK204D15P RAK204D20P RAK204D30P RAK204E15 RAK204E20 RAK204E30
Voltage N/A 230/208 230/208 230/208 265 265 265
Amps N/A 15 20 30 15 20 30
Receptacle N/A NEMA6-20R NEMA6-20R NEMA6-30R NEMA7-15R NEMA7-20R NEMA7-30R
230/208 Volt sub-bases include appropriate power cord kit. 265 Volt units are to be direct connected. Cordset through enclosed chaseway into interior sub-base receptacle meets the NEC requirements.
Perpendicular
230/208V 20 Amp NEMA6-20R
Large tandem
230/208V 30 Amp NEMA6-30R
265V 15 Amp
NEMA7-15R
265V 20 Amp
NEMA7-20R;
265V 30 Amp
NEMA7-30R;
Power connection kits are required on all Zoneline® chassis (see chart below).
The correct kit for the installation is determined by the voltage and amperage of the electrical circuit and the means of connecting the unit to the building wiring. If the unit is to be plugged into a receptacle, a line-cord kit would be used; if the unit is to be permanently connected, a permanent­connection kit would be used. 265 volt cord set units must be installed in compliance with National Electrical Code
Power connection kits
Required on all models. See specification sheet for heater KW and branch circuit ampacity.
RAK3153A/3203A/3303A 230/208 volt line-cord connection kit
230/208 volt Line-cord connected units
LCDI Power Connection Kit RAK3153A RAK3203A RAK3303A
Heater KW 2.4/2.32 3.3/3.2 4.7/4.53
Watts 2,450/2,360 3,350/3,230 4,750/4,580*
BTUH 8,150/7,900 11,200/10,900 16,000/15,450
Amps 11.0/11.6 15.1/16.0 21.2/22.4
Min. circuit amps 15 20 30
Recommended
protective
device
230/208 volt Direct-connection kit
Heater KW 2.4/2.32 3.3/3.2 4.7/4.53
Watts 2,450/2,360 3,350/3,230 4,750/4,580*
BTUH 8,150/7,900 11,200/10,900 16,000/15,450
Amps 11.0/11.6 15.1/16.0 21.2/22.4
Min. circuit amps 15 20 30
Recommended
protective
device
*Wattage not available with 7,000 BTU systems. **To be used with sub-base †To be used with sub-base or connection to building wiring Specifications subject to change.
15 amp
time-delay
fuse or breaker
RAK4157 RAK4207 RAK4307
15 amp
time-delay
fuse or breaker
20 amp
time-delay
fuse or breaker
20 amp
time-delay
fuse or breaker
RAK4157/4207/4307 230/208 volt universal power supply kit
30 amp
time-delay
fuse or breaker
30 amp
time-delay
fuse or breaker
RAK5157/5207/5307 265 volt universal power supply kit
265 volt Permanent-connected units** (Cord set)
RAK5172 RAK5202 RAK5302
2.4 3.4 4.8
2,460 3,460 4,860*
8,150 11,550 16,350
9.6 13.3 18.6
15 20 30
15 amp
time-delay fuse
265 volt Direct-connection kit†
RAK5157 RAK5207 RAK5307
2.4 3.4 4.8
2,460 3,460 4,860*
8,150 11,550 16,350
9.6 13.3 18.6
15 20 30
15 amp
time-delay fuse
20 amp
time-delay fuse
20 amp
time-delay fuse
®
.
30 amp
time-delay fuse
30 amp
time-delay fuse
53
PRELIMINARY SPECIFICATIONS
230/208V Models AZ41E07DAB AZ41E09DAB AZ41E12DAB AZ41E15DAB
4100 series cooling with electric heat
Capacity
Cooling BTUH 7,200/6,900 9,700/9,600 11,800/11,500 14,300/14,000 EER (BTU/Watt) 12.3/12.3 12.0/12.0 11.1/11.1 10.3/10.3 Dehumidification Pts/Hr 1.7 2.7 3.5 4.6
Features
Refrigerant type R-410A R-410A R-410A R-410A CFM, indoor fan high 290 340 420 409 CFM, indoor fan low 219 229 323 324 Vent CFM (full open/partial open) 50/40 70/45 75/45 75/45
Power/Ratings
Power factor 89% 93% 93% 90%/92% Sensible heat ratio @ 230 volts 80% 75% 70% 70% Watts 580/560 805/795 1,060/1,035 1,370/1,350 Cooling Amperes, F.L. 2.8/3.0 3.6/3.9 4.7/5.1 6.7/7.2 Amperes, L.R. 19.0 21.0 29.5 31.0
Weight (Net/Ship) 89.2/102.5 100.0/113.0 99.4/112.4 100.3/113.3
4100 series cooling with electric heat (corrosion treated models)
230/208V Models AZ41E07DAC AZ41E09DAC AZ41E12DAC AZ41E15DAC
Capacity
Cooling BTUH 7,200/6,900 9,700/9,600 11,800/11,500 14,300/14,000 EER (BTU/Watt) 12.3/12.3 12.0/12.0 11.1/11.1 10.3/10.3 Dehumidification Pts/Hr 1.7 2.7 3.5 4.6
Features
Refrigerant type R-410A R-410A R-410A R-410A CFM, indoor fan high 290 340 420 409 CFM, indoor fan low 218 229 323 324 Vent CFM (full open/partial open) 50/40 70/45 75/45 75/45
Power/Ratings
Power factor 89% 93% 93% 90%/92% Sensible heat ratio @ 230 volts 80% 75% 70% 70% Watts 580/560 805/795 1,060/1,035 1,370/1,350 Cooling Amperes, F.L. 2.8/3.0 3.6/3.9 4.7/5.1 6.7/7.2 Amperes, L.R. 19.0 21.0 29.5 31.0
Weight (Net/Ship) 91.3/104.3 100.3/113.3 99.4/112.4 100.3/113.3
265V Models AZ41E07EAB AZ41E09EAB AZ41E12EAB AZ41E15EAB
Capacity
Cooling BTUH 7,200 9,700 11,800 14,300 EER (BTU/Watt) 12.3 12.0 11.1 10.3 Dehumidification Pts/Hr 1.7 2.7 3.5 4.6
Features
Refrigerant type CFM, indoor fan high 290 340 420 406 CFM, indoor fan low 215 229 323 324 Vent CFM (full open/partial open) 50/40 70/45 75/45 75/45
Power/Ratings
Power factor 90% 91% 92% 92% Sensible heat ratio @ 265 volts 80% 75% 70% 70% Watts 580 805 1,025 1,385 Cooling Amperes, F.L. 2.4 3.2 4.1 5.7 Amperes, L.R. 12.0 16.5 23.5 26.0
Weight (Net/Ship) 91.3/104.3 101.2/114.2 99.9/112.9 101.0/114.0
265V Models AZ41E07EAC AZ41E09EAC AZ41E12EAC AZ41E15EAC
Capacity
Cooling BTUH 7,200 9,700 11,800 14,300 EER (BTU/Watt) 12.3 12.0 11.1 10.3 Dehumidification Pts/Hr 1.7 2.7 3.5 4.6
Features
Refrigerant type CFM, indoor fan high 290 340 420 406 CFM, indoor fan low 215 229 323 324 Vent CFM (full open/partial open) 50/40 70/45 75/45 75/45
Power/Ratings
Power factor 90% 91% 92% 92% Sensible heat ratio @ 265 volts 80% 75% 70% 70% Watts 580 805 1,025 1,385 Cooling Amperes, F.L. 2.4 3.2 4.1 5.7 Amperes, L.R. 12.0 16.5 23.5 26.0
Weight (Net/Ship) 91.7/104.7 101.4/114.4 100.3/113.3 101.0/114.0
230/208V Models AZ41E07DAP AZ41E09DAP AZ41E12DAP
Dry Air 25
Capacity
Cooling BTUH 6,500/6,300 9,200/8,800 11,200/11,000 EER (BTU/Watt) 11.7/11.7 11.5/11.5 10.8/10.8 Dehumidification Pts/Hr 2.3 3.4 4.4
Features
Refrigerant type R-410A R-410A R-410A CFM, indoor fan high 220 280 330 CFM, indoor fan low 190 208 270 Vent CFM (full open/partial open) 50/40 70/45 75/45
Power/Ratings
Power factor 86%/87% 92% 92% Sensible heat ratio @ 230 volts 60% 60% 60% Watts 555/535 790/765 1,035/1,015 Cooling Amperes, F.L. 2.8/3.0 3.6/3.9 4.7/5.1 Amperes, L.R. 19.0 21.0 29.5
Weight (Net/Ship) 97.0/110.0 105.2/118.2 105.4/118.4
265V Models AZ41E07EAP AZ41E09EAP AZ41E12EAP
Capacity
Cooling BTUH 6,500 9,200 11,200 EER (BTU/Watt) 11.7 11.5 10.8 Dehumidification Pts/Hr 2.3 3.4 4.4
Features
Refrigerant type CFM, indoor fan high 220 280 330 CFM, indoor fan low 190 208 270 Vent CFM (full open/partial open) 50/40 70/45 75/45
Power/Ratings
Power factor 87% 91% 92% Sensible heat ratio @ 265 volts 60% 75% 60% Watts 555 795 1,020 Cooling Amperes, F.L. 2.4 3.2 4.1 Amperes, L.R. 12.0 16.5 23.5
Weight (Net/Ship) 97.4/110.5 104.9/117.9 108.0/121.0
Specifications subject to change.
54
230/208V Models AZ61H07DAB A Z61H09DAB AZ61H12DAB AZ61H15DAB
Capacity
Cooling BTUH 7,100/6,900 9,400/9,100 11,700/11,600 14,500/14,200 EER (BTU/Watt) 13.0/13.0 12.2/12.2 11.6/11.6 10.6/10.6 Dehumidification Pts/Hr 1.7 2.7 3.5 4.5
Features
Refrigerant type R-410A R-410A R-410A R-410A CFM, indoor fan high 340 360 370 370 CFM, indoor fan low 194 212 284 290 Vent CFM (full open/partial open) 50/40 70/45 75/45 75/45
Power/Ratings
Power factor 91% 92% 92% 91%/92% Sensible heat ratio @ 230 volts 85% 75% 70% 65% Cooling Watts 545/525 755/740 985/965 1,360/1,335 Cooling Amperes, F.L. 2.6/2.8 3.5/3.8 4.6/5.0 6.3/6.8 Amperes, L.R. 19.0 21.0 29.5 31.0 Reverse cycle heat BTUH 6,200/6,100 8,300/8,100 10,600/10,400 13,500/13,400 COP 3.9/3.9 3.7/3.7 3.6/3.6 3.3/3.3 Heating Watts 465/445 650/635 855/835 1,165/1,120 Heating Amperes 2.2/2.4 3.1/3.3 4.1/4.5 5.8/6.3
Weight (Net/Ship) 94.1/107.1 101.4/114.4 102.1/115.1 100.8/113.8
6100 series heat pump with backup electric heat
265V Models AZ61H07EAB AZ61H09EAB AZ61H12EAB AZ61H15EAB
Capacity
Cooling BTUH 7,000 9,400 11,700 14,400 EER (BTU/Watt) 12.8 12.2 11.6 10.6 Dehumidification Pts/Hr 1.7 2.7 3.5 4.5
Features
Refrigerant type R-410A R-410A R-410A R-410A CFM, indoor fan high 340 360 370 370 CFM, indoor fan low 194 211 284 290 Vent CFM (full open/partial open) 50/40 70/45 75/45 75/45
Power/Ratings
Power factor 94% 90% 92% 93% Sensible heat ratio @ 265 volts 85% 75% 70% 65% Cooling Watts 545 765 1,000 1,355 Cooling Amperes, F.L. 2.2 3.1 4.0 5.4 Amperes, L.R. 12.0 16.5 23.5 26.0 Reverse cycle heat BTUH 6,200 8,100 10,700 13,500 COP 3.9 3.6 3.6 3.3 Heating Watts 450 655 870 1,165 Heating Amperes 2.0 2.7 3.6 5.0
Weight (Net/Ship) 94.6/107.6 103.6/116.6 103.6/116.6 104.3/117.3
230/208V Models AZ61H07DAC AZ61H09DAC AZ61H12DAC AZ61H15DAC
Capacity
Cooling BTUH 7,100/6,900 9,400/9,100 11,700/11,600 14,500/14,200 EER (BTU/Watt) 13.0/13.0 12.2/12.2 11.6/11.6 10.6/10.6 Dehumidification Pts/Hr 1.7 2.7 3.5 4.5
Features
Refrigerant type R-410A R-410A R-410A R-410A CFM, indoor fan high 340 360 370 370 CFM, indoor fan low 194 212 284 290 Vent CFM (full open/partial open) 50/40 70/45 75/45 75/45
Power/Ratings
Power factor 91% 92% 92% 91%/92% Sensible heat ratio @ 230 volts 85% 75% 70% 65% Cooling Watts 545/525 755/740 985/965 1,350/1,330 Cooling Amperes, F.L. 2.6/2.8 3.5/3.8 4.6/5.0 6.3/6.8 Amperes, L.R. 19.0 21.0 29.5 31.0 Reverse cycle heat BTUH 6,200/6,100 8,300/8,100 10,600/10,400 13,500/13,400 COP 3.9/3.9 3.7/3.7 3.6/3.6 3.3/3.3 Heating Watts 465/445 650/635 855/835 1,190/1,155 Heating Amperes 2.2/2.4 3.1/3.3 4.1/4.5 5.8/6.3
Weight (Net/Ship) 94.1/107.1 102.3/115.3 105.4/118.4 104.5/117.5
230/208V Models A Z61H07DAD AZ61H09DAD AZ61H12DAD AZ61H15DAD
Capacity
Cooling BTUH 7,000/6,900 9,200/9,100 11,700/11,600 14,300/14,100 EER (BTU/Watt) 12.7/12.7 11.9/11.9 11.4/11.4 10.4/10.4 Dehumidification Pts/Hr 1.7 2.7 3.5 4.5
Features
Refrigerant type R-410A R-410A R-410A R-410A CFM, indoor fan high 340 360 370 370 CFM, indoor fan low 194 212 284 290 Vent CFM (full open/partial open) 50/40 70/45 75/45 75/45
Power/Ratings
Power factor 91% 92% 92% 91%/92% Sensible heat ratio @ 230 volts 85% 75% 70% 65% Cooling Watts 550/530 760/750 980/960 1,345/1,330 Cooling Amperes, F.L. 2.6/2.8 3.5/3.8 4.6/5.0 6.3/6.8 Amperes, L.R. 19.0 21.0 29.5 31.0 Reverse cycle heat BTUH 6,200/6,100 8,100/8,000 10,600/10,400 13,500/13,400 COP 3.9/3.9 3.6/3.6 3.6/3.6 3.2/3.2 Heating Watts 465/440 655/640 855/835 1,200/1,200 Heating Amperes 2.2/2.4 3.1/3.3 4.1/4.5 5.8/6.3
Weight (Net/Ship) 96.8/109.8 104.1/117.1 105.8/118.8 106.0/119.0
6100 series heat pump with backup electric heat (corrosion treated models)
6100 series heat pump with backup electric heat
265V Models AZ61H07EAC AZ61H09EAC AZ61H12EAC AZ61H15EAC
Capacity
Cooling BTUH 7,000 9,400 11,700 14,400 EER (BTU/Watt) 12.8 12.2 11.6 10.6 Dehumidification Pts/Hr 1.7 2.7 3.5 4.5
Features
Refrigerant type R-410A R-410A R-410A R-410A CFM, indoor fan high 340 360 370 370 CFM, indoor fan low 194 211 284 290 Vent CFM (full open/partial open) 50/40 70/45 75/45 75/45
Power/Ratings
Power factor 94% 90% 92% 93% Sensible heat ratio @ 265 volts 85% 75% 70% 65% Cooling Watts 545 765 1,000 1,355 Cooling Amperes, F.L. 2.2 3.1 4.0 5.4 Amperes, L.R. 12.0 16.5 23.5 26.0 Reverse cycle heat BTUH 6,200 8,100 10,700 13,500 COP 3.9 3.6 3.6 3.3 Heating Watts 450 655 870 1,165 Heating Amperes 2.0 2.7 3.6 5.0
Weight (Net/Ship) 94.6/107.6 104.1/117.1 103.6/116.6 104.7/117.7
265V Models AZ61H07EAD AZ61H09EAD AZ61H12EAD AZ61H15EAD
Capacity
Cooling BTUH 6,900 9,200 11,700 14,300 EER (BTU/Watt) 12.7 11.9 11.4 10.4 Dehumidification Pts/Hr 1.7 2.7 3.5 4.5
Features
Refrigerant type R-410A R-410A R-410A R-410A CFM, indoor fan high 340 360 370 370 CFM, indoor fan low 194 211 284 290 Vent CFM (full open/partial open) 50/40 70/45 75/45 75/45
Power/Ratings
Power factor 92% 90% 92% 93% Sensible heat ratio @ 265 volts 85% 75% 70% 65% Cooling Watts 540 760 1,015 1,355 Cooling Amperes, F.L. 2.2 3.1 4.0 5.4 Amperes, L.R. 12.0 16.5 23.5 26.0 Reverse cycle heat BTUH 6,200 8,200 10,900 13,500 COP 3.9 3.6 3.6 3.2 Heating Watts 455 665 880 1,210 Heating Amperes 2.0 2.7 3.6 5.0 Weight (Net/Ship) 97.0/110.0 106.3/119.3 106.5/119.5 106.3/119.3
Specifications subject to change.
55
COMPLETE ACCESSORY LIST
Kit Number Description For Additional Information Refer to Page
RAA63 Spare Filters for AZ2900, AZ3900, AZ4100, AZ5800 and AZ6100 Series units 12 RAB71A Steel Wall Case – 13-3/4" deep 23 RAB7116 Steel Wall Case – 16" deep 23 RAB7124 Steel Wall Case – 24" deep 23 RAB7128 Steel Wall Case – 28" deep 23 RAB7131 Steel Wall Case – 31" deep 23 RAB77A4 Molded Wall Case 23 RAD10 Interior/Exterior Drain kit 36 RAF453A Room Front for A228, 29, 38, 39, 58, 41 & 61 series (included with chassis) 12 RAG60 Stamped Aluminum Exterior Grille 41 RAG61 Architectural Exterior Grille, Beige Molded High-Impact Plastic 41 RAG62 Architectural Exterior Grille, Maple Molded High-Impact Plastic 41 RAG63 Architectural Exterior Grille, Bittersweet Chocolate Molded High-Impact Plastic 41 RAG67 Aluminum Architectural Grille (Custom Colors Available by Special Order) 41 RAK40 Condenser Air Deflector Kit 41 RAK148D2 Wall Thermostat For Heat Pump Models - Electronic Digital 17 RAK148P2 Wall Thermostat For Heat Pump Models – Electronic Digital Programmable 17 RAK164D2 Wall Thermostat For Resistance Heat Models – Electronic Digital 16 RAK164P2 Wall Thermostat For Resistance Heat Models – Electronic Digital Programmable 16 RAK201 Sub-Base Cover Plate with Knockouts 44 RAK204D15P Sub-Base - 208/230-Volt with NEMA 6-20R 15/20 Amp Receptacle – Power Cord and Chaseway included 23 RAK204D20P Sub-Base - 208/230-Volt with NEMA 6-20R 15/20 Amp Receptacle – Power Cord and Chaseway included 23 RAK204D30P Sub-Base - 208/230-Volt with NEMA 6-30R 30 Amp Receptacle –Power Cord and Chaseway included 24 RAK204E15 Sub-Base – 265-Volt with NEMA 7-15R 15 Amp Receptacle – Chaseway included 24 RAK204E20 Sub-Base – 265-Volt with NEMA 7-20R 20 Amp Receptacle – Chaseway included 24 RAK204E30 Sub-Base – 265-Volt with NEMA 7-30R 30 Amp Receptacle – Chaseway included 24 RAK204U Sub-Base – non-electrical Chaseway not included 23 RAK205CW Chaseway for Sub-Base 23 RAK3153A Universal Power Cord – 4100/6100 series – 15-Amp 230/208 V – 2.40/2.32 kW heat 43 RAK3203A Universal Power Cord – 4100/6100 – 20-Amp 230/208 V – 3.3/3.2 kW heat 43 RAK3303A Universal Power Cord – 4100/6100 – 30-Amp 230/208 V – 4.7/4.53 kW heat 43 RAK4002A Direct-Connect Junction Box – 230/208-volt units 4100/6100 Series 43 RAK4002B Direct-Connect Junction Box – 230/208-volt units 5800 Series 43 RAK4002CW Wiring Harness w/Inline Connector - Adapt Line Cord to Direct Connection 44 RAK4157 208/230V Universal Power Supply, 15 Amp for 2800, 2900, 3800, 3900, 4100, 5500, 5800, 6100, 7500 and 8500 only 43 RAK4207 208/230V Universal Power Supply, 20 Amp for 2800, 2900, 3800, 3900, 4100, 5500, 5800, 6100, 7500 and 8500 only 43 RAK4307 208/230V Universal Power Supply, 30 Amp for 2800, 2900, 3800, 3900, 4100, 5500, 5800, 6100, 7500 and 8500 only 43 RAK5157 265V Universal Power Supply, 15 Amp for 2800, 2900, 3800, 3900, 4100, 5500, 5800, 6100, 7500 and 8500 only 53 RAK5207 265V Universal Power Supply, 20 Amp for 2800, 2900, 3800, 3900, 4100, 5500, 5800, 6100, 7500 and 8500 only 53 RAK5307 265V Universal Power Supply, 30 Amp for 2800, 2900, 3800, 3900, 4100, 5500, 5800, 6100, 7500 and 8500 only 53 RAK5172 Universal Connection Kit – 265V – 15 Amp – Use w/RAK204E15 Sub-Base – 2.40 kW heat 53 RAK5202 Universal Connection Kit – 265V – 20 Amp – Use w/RAK204E20 Sub-Base – 3.40 kW heat 53 RAK5302 Universal Connection Kit – 265V – 30 Amp – Use w/RAK204E30 Sub-Base – 4.80 kW heat 53 RAK601 Duct Extension – Insulated – 44" long – includes Register and Trim Flange 38 RAK602 Register and Trim Flange (Included with RAK601) 38 RAK6052 Duct Adapter for New Installation (or older non-GE duct adapter installation) 38
RAK7012
RAK7022
RAK8023 Locking Door Kit 12 RAK806 Control Panel Cover (for use with remote thermostat) 16 RAK901L Wall Case Insulation Kit 23
Duct Adapter for replacement of A-B with rounded-front AZ chassis for 2200, 3200, 2500, 3500, 2800, 2900, 3800, 3900, 4100 and 6100 only
Duct Transition for replacement of AZC with rounded-front AZ chassis for 2200, 3200, 2500, 3500, 2800, 2900, 3800, 3900, 4100 and 6100 only
38
38
56
GENERAL INSTALLATION SUGGESTIONS
Many times poor or non-existent caulking around the exterior of the wall case results in air infiltration, causing the unit to run excessively. One way to check for air infiltration is to look under and around the unit to the outdoors. If you can see light, there is air infiltration. The first floor of a building is where this problem most frequently occurs since caulking the bottom of the wall case may require lying outside in the dirt while working. This has been the cause of many complaints about the “short cycling” of the unit.
Curtains, furniture or other obstructions interfering with the discharge air circulation will make the unit cycle/turn off too soon since the cooled (or heated) discharge air is pulled back into the unit. This results in a room that is not adequately heated or cooled.
Blocking the discharge air on the unit during the heating operation can result in the air getting hot enough to distort the plastic room front. If you have a property where this may occur we recommend a “tent card” advising room occupants not to put anything on the unit.
Electrical Wiring Installation
Do not allow the installer to drill a hole in the wall case to run the electrical wiring. If this is done, the wiring will have to be run between the chassis and the edge of the wall case so it can be connected to the unit wiring on the room side of the wall case. When the chassis is removed for servicing or cleaning, the insulation on the wires can be cut and can create a safety hazard.
If the electrical connection on a 230-volt or 208-volt installation is to be made by the line cord plugged into a wall-mounted receptacle, the receptacle should be located in the wall under the case or close to the side of the wall case. This installation makes a much neater appearance than a line cord running a foot or more across the floor. The electrician may want to place the receptacle as far from the unit as possible to save a few feet of wiring without considering how the installation may appear.
Central Desk Control and Remote Thermostat Wiring
Do not allow the installer to drill a hole in the wall case to run Central Desk Control wiring or remote thermostat wiring to the unit terminals. CDC and remote thermostat wiring is classified as low-voltage wiring and does not have to be run in conduit unless required by local code. CDC and remote thermostat wiring should be run in the walls and exit the wall under the wall case about 2" from the right-hand side. The base pan is designed with a clearance for the line cord and the low-voltage wiring can also be run to the chassis in this area. Wire molding can be used to hold the wiring close to the bottom of the wall case. If a sub-base is used, the wiring can be run through the sub-base, entering the rear and exiting through one of the front panels. When the room cabinet is in place the CDC or remote thermostat wiring is usually not
visible to someone standing or sitting in the room. Do not run the low-voltage wiring in conduits with line-voltage wiring or near uninsulated line-voltage wiring since induced current can interrupt the low-voltage controls.
Consult the electrical inspector early in the project, especially if the power to the air conditioner is to be 265 volts, to understand what is required to comply with local electrical codes.
Wall Case/Exterior Grille
When making an installation where the exterior grille is flush with the exterior wall, or part of a custom window/louver section, make sure the installer caulks the wall case to the exterior wall, especially the bottom of the case. Many times the air conditioners are run during construction and the building is not closed. This can result in excessive humidity from the warm humid air entering the building, or from the “drying out” of the building materials. Many problems have been caused by condensate water or rainwater running back into the building where proper caulking has not been done.
Capacity Considerations
A unit that has a greater cooling capacity than required will cool the room quickly but will usually not run long enough under normal operation to adequately dehumidify the room. Most musty odors in rooms are due to excess humidity. Using a smaller-capacity unit or using Dry Air 25 units will provide better dehumidification. The largest factor in causing mold and mildew in the room is excess moisture. A smaller unit running longer or a Dry Air 25 model can remove more moisture. Mold behind wall coverings that do not allow water vapor to pass through—vinyl wallpaper or oil-base paints, for example—is not a problem of excessive moisture in the room, but rather is caused by moisture trapped in the walls.
Using a resistance heater larger than required—using a
4.7 kW heater when a 3.3 kW heater would suffice for
example—may not cost any more in electrical consumption since the larger heater will operate for less time. The “Demand Charge” portion of the utility bill—which is based on the highest electrical load for a period of time—may be a significant portion of the utility bill. Some customers have reported the demand charge actually being more than the usage charge. In a 100-room property it would be possible for the demand of the 4.7 kW heater versus a 3.3 kW heater to be 140 kW more than the demand charge if the lower wattage heaters were used. Working with the utility companies to understand their method of billing and taking advantage of any rebates they may offer can reduce the utility bill.
Exterior Grilles
When replacing an older unit, the existing outdoor grille may need to be changed or modified. Outdoor airflow patterns have changed and this may dictate the need for outdoor grille replacement or modification.
57
GENERAL INSTALLATION SUGGESTIONS (cont)
Ducted Installation Comments
New Installations
®
The GE Zoneline
4100 and 6100 Series are approved for ducted installation using the GE Duct Adapter model RAK6052 and the GE Duct Extension RAK601. A field-fabricated duct extension with the same interior measurements as the RAK601 may be used with the RAK6052 duct adapter. GE does not allow ducting in more than one direction.
The use of a duct adapter other than the RAK6052 is not approved by GE and may cause problems such as inadequate airflow to the secondary room or the unit shutting off on one of the overload devices.
Failure to allow for adequate air return from the secondary room is often the cause of less than satisfactory performance of a ducted installation.
Replacement Installations
GE offers duct adapters to allow for easy replacements of previous-design chassis in ducted installations where a GE duct adapter was used in the original installation. A duct adapter is available that will align with the duct extension when GE-built components were used in the original installation.
The duct adaptor/extension used from the early 1960s until late 1987 was 8-3/8" high by 6-1/2" wide. If the chassis to be replaced is the flat-top discharge (design until late 1987) the duct adapter model RAK7012 will align with the existing duct extension. This means the duct extension will not have to be changed. However, to keep the cost of the replacement to a minimum there are components that will need to be taken off the existing installation and used on the RAK7012 duct adapter. The wall case mounting brackets, screws, discharge grille, damper and end cap will need to be retained.
If the chassis is a slope-front discharge and the duct dimensions are 8-3/8" high by 6-1/2" wide, then the chassis has already been replaced and the purchase of a new duct adapter is not required. The only piece that needs to be replaced in this installation is the transition piece, model RAK7022, which fits between the chassis and the duct adapter.
If the chassis being replaced has a model number that begins with AZ22, AZ25, AZ28, AZ29, AZ32, AZ35, AZ38 or AZ39, the new 4100 or 6100 Series unit can be installed using the same duct components.
If the existing chassis is a slope-front discharge and the duct dimensions are 7-3/32" high by 6-1/2" wide, only the RAK7022 transition piece is required to install a 4100 or 6100 Series unit in the ducted installation.
There were a number of Zoneline units installed in ducted installations that did not use a GE duct adapter. The easiest way to determine if the existing duct adapter is a GE duct adapter is to compare the duct adapter dimensions to the dimensions above. If the dimensions are different from the dimensions above or if the duct adapter is not made of sheet metal, it is not a GE duct adapter. In such installations, GE recommends the removal of the old duct adapter and duct extension and the installation of a RAK6052 duct adapter and a RAK601 duct extension. Zoneline units installed in installations not using GE duct adapters and an extension with the same cross-section dimensions as the duct adapter may not be covered by the warranty.
ZONELINE WARRANTY*
What is covered
Limited one-year warranty
For one year from the date of the original purchase, GE will repair or replace any part of the air conditioner which fails due to a defect in materials or workmanship. During this limited one-year warranty, GE will provide, free of charge, all labor and related service costs to repair or replace the defective part.
Limited five-year warranty
For five years from the date of the original purchase, GE will repair or replace the Sealed Refrigerating System if any part of the Sealed Refrigerating System (the compressor, condenser, evaporator, and
58
all connecting tubing) should fail due to a defect in materials or workmanship. During this limited five-year warranty, GE will provide, free of charge, all labor and related service costs to repair or replace the defective part.
Limited second-through-fifth-year parts warranty
From the second through the fifth year from the date of the original purchase, GE will replace the Fan Motors, Switches, Thermostat, Heater, Heater Protectors, Compressor Overload, Solenoids, Circuit Boards, Auxiliary Controls, Thermistors, Freeze Sentinel, Frost Controls, ICR Pump, Capacitors, Varistors and Indoor Blower Bearing, if any of these parts should fail due to a defect in materials or workmanship. During this additional four-year limited warranty, you will be responsible for any labor and related service costs.
*See written warranty for details
ALPHABETICAL INDEX
Category Page No.
Accessory List 56
Application Comments 21
Auxiliary Control Settings 13–14
Case Dimensions 22
Central Desk Control 15
Condensate Disposal Systems 35–37
Ducted Installations 38–40
Dry Air 25 5
Electrical Connection 43
Essential Elements Ordering Overview 44
Exterior Grilles 41–42
Features and Benefits 10–12
Features Table 9
General Installation Suggestions 57–58
Heat Pumps and Energy Savings 19–20
Introduction to Zoneline
Latent System Capacity 45
Maximum Connected Load 45
Mini Specs 4100 2
Mini Specs 6100 3
Mini Specs Power Connection Kits and Nomenclature 4
Normal Yearly Operating Data 46
Remote Thermostat Control 16–18
Schematics 47–50
Suggested Bid Form Specifications 51–52
Tab le of Conte nts 6
Wall Case/Sub-Base Installation 23–34
Warranty 58
Zoneline System 8
Units 7
EXTERIOR GRILLE COLOR SAMPLES
Beige
Maple
Bittersweet
Colors may vary slightly due to printing process.
59
GE
s
k
geapp
m
GE APPLIANCES
At GE, we’re reimagining home to introduce a new world of innovation in appliances. Today, we’re even more in sync with the consumer. Listening. Anticipating. Engineering ingenious ways to simplify life with more industry-fi rst exclusives. We’re redefi ning style and functional design across all our products. Expanding our U.S. workforce and transforming manufacturing. Improving quality and effi ciency. Helping our partners spread the word of GE solutions—from the sales fl oor to the national stage—and igniting sales. GE Appliances. We’re not just imagining. We’re doing.
Appliance Appliance Par Louisville, KY 40225
liances.co
© 2014 General Electric Company Pub. No. 20-S114 PC80306 rev 12/2014
Loading...