GE AZ61H15DAD, AZ41E15DAC AZ61H15DAD Architect and Engineering Manual

LEADERS IN
EFFICIENCY
GE ZONELINE
ARCHITECTS AND ENGINEERS DATA MANUAL
GE Zoneline packaged terminal air conditioners
®
QUICK REFERENCE
Full Specs on pages 54 and 55
ALL UNITS REQUIRE POWER CONNECTION KIT
Power Connection Kit determines resistance heat output 7000 BTUH units are not offered with 4.7 KW resistance heater
4100 series cooling with electric heat
MODEL
NUMBER
AZ41E07DAB
AZ41E09DAB
AZ41E12DAB
AZ41E15DAB
AZ41E07EAB 265 7200 12.3 580 AZ41E09EAB 265 9700 12.0 805 AZ41E12EAB 265 11800 11.1 1025 AZ41E15EAB 265 14300 10.3 1385
VOLTAGE
208 6900 12.3 560 230 7200 12.3 580 208 9600 12.0 795 230 9700 12.0 805 208 11500 11.1 1035 230 11800 11.1 1060 208 14000 10.3 1350 230 14300 10.3 1370
COOLING
(BTUH)
EER WATTS
4100 series cooling with electric heat (corrosion treated models)
MODEL
NUMBER
AZ41E07DAC
AZ41E09DAC
AZ41E12DAC
AZ41E15DAC
AZ41E07EAC 265 7200 12.3 580 AZ41E09EAC 265 9700 12.0 805 AZ41E12EAC 265 11800 11.1 1025 AZ41E15EAC 265 14300 10.3 1385
VOLTAGE
208 6900 12.3 560 230 7200 12.3 580 208 9600 12.0 795 230 9700 12.0 805 208 11500 11.1 1035 230 11800 11.1 1060 208 14000 10.3 1350 230 14300 10.3 1370
COOLING
(BTUH)
EER WATTS
Dry Air 25 4100 series cooling with electric heat
MODEL
NUMBER
AZ41E07DAP
AZ41E09DAP
AZ41E12DAP
AZ41E07EAP 265 6500 11.7 555 AZ41E09EAP 265 9200 11.5 795 AZ41E12EAP 265 11200 10 .8 1020
Specifications subject to change.
2
VOLTAGE
208 6300 11.7 535 230 650 0 11.7 555 208 8800 11.5 765 230 9200 11.5 790 208 110 00 10.8 1015 230 11200 10.8 1035
COOLING
(BTUH)
EER WATTS
4100 and 6100 Series Control Panel
QUICK REFERENCE
Full Specs on pages 54 and 55
ALL UNITS REQUIRE POWER CONNECTION KIT
Power Connection Kit determines resistance heat output 7000 BTUH units are not offered with 4.7 KW resistance heater
6100 series heat pump with backup electric heat
MODEL
NUMBER
AZ61H07DAB
AZ61H09DAB
AZ61H12DAB
AZ61H15DAB
AZ61H07EAB 265 7000 12.8 545 6200 3.9 450 AZ61H09EAB 265 9400 12.2 765 8100 3.6 655 AZ61H12EAB 265 11700 11.6 1000 10700 3.6 870 AZ61H15EAB 265 14400 10.6 1355 13500 3.3 1165
VOLTAGE
208 6900 13.0 525 6100 3.9 445 230 7100 13.0 545 6200 3.9 465 208 9100 12.2 740 8100 3.7 635 230 9400 12.2 755 8300 3.7 650 208 11600 11.6 965 10400 3.6 835 230 11700 11.6 985 10600 3.6 855 208 14200 10.6 1335 13400 3.3 1120 230 14500 10.6 1360 13500 3.3 1165
COOLING
(BTUH)
EER WATTS
HEATING
(BTUH)
COP WATTS
6100 series heat pump with backup electric heat (corrosion treated models)
MODEL
NUMBER
AZ61H07DAC
AZ61H09DAC
AZ61H12DAC
AZ61H15DAC
AZ61H07EAC 265 7000 12.8 545 6200 3.9 450 AZ61H09EAC 265 9400 12.2 765 8100 3.6 655 AZ61H12EAC 265 11700 11.6 1000 10700 3.6 870 AZ61H15EAC 265 14400 10.6 1355 13500 3.3 1165
VOLTAGE
208 6900 13.0 525 6100 3.9 445 230 7100 13.0 545 6200 3.9 465 208 9100 12.2 740 8100 3.7 635 230 9400 12.2 755 8300 3.7 650 208 11600 11.6 965 10400 3.6 835 230 11700 11.6 985 10600 3.6 855 208 14200 10.6 1330 13400 3.3 1155 230 14500 10.6 1350 13500 3.3 1190
COOLING
(BTUH)
EER WATTS
HEATING
(BTUH)
COP WATTS
6100 series heat pump with backup electric heat (models featuring ICR - internal condensate removal)
MODEL
NUMBER
AZ61H07DAD
AZ61H09DAD
AZ61H12DAD
AZ61H15DAD
AZ61H07EAD 265 6900 12.7 540 6200 3.9 455 AZ61H09EAD 265 9200 11.9 760 8200 3.6 665 AZ61H12EAD 265 11700 11.4 1015 10900 3.6 880 AZ61H15EAD 265 14300 10.4 1355 13500 3.2 1210
VOLTAGE
208 6900 12.7 530 6100 3.9 440 230 7000 12.7 550 6200 3.9 465 208 9100 11.9 750 8000 3.6 640 230 9200 11.9 760 8100 3.6 655 208 11600 11.4 960 10400 3.6 835 230 11700 11.4 980 10600 3.6 855 208 14100 10.4 1330 13400 3.2 1200 230 14300 10.4 1345 13500 3.2 1200
COOLING
(BTUH)
EER WATTS
HEATING
(BTUH)
COP WATTS
POWER CONNECTION KITS
230/208-Volt Line-Cord Connection Units
Line Cord
Kit
RAK3153A 8150/7900 2450/2360 11.0/11.6 15 RAK3203A 11200/10900 3350/3230 15.1/16.0 20 RAK3303A 16000/15450 4750/4580 21.2/22.4 30
Elect ric Heat Amps include electric heater and fan motor cur rent draw. Each Line-Cord Kit has an integral Leakage Current Detec tion and Interruptio n (LCDI) or Arc Fault Current Interrupter (AFCI) device as required by National Electrical Code (NEC) and Underwriters Labora tories (UL) for units manufac tured after August 1, 20 04.
Electric
Heat
BTUH
Electric
Heater
Watts
Electric
Heat
Amps
Min. Circuit
Protection
(Amps)
230/208-Volt Sub-Base and Direct-Connected Units
Sub-Base
Connection
Kit
RAK204D15P RAK4157 8150/7900 2450/2360 11.0/11.6 15 RAK204D20P RAK4207 11200/10900 3350/3230 15.1/16.0 20 RAK204D30P RAK4307 16000/15450 4750/4580 21.2/22.4 30
Elect ric Heat Amps include electric heater and fan motor cur rent draw. Units connec ted through sub-base do not require an LCDI or AFCI device since they are not considered to be line-cord connected. Each 230/208-volt sub-base kit consists of sub-base with appropriate receptacle for min imum circuit amp erage, chaseway to route p ower connector from sub-base to chassis, wiring to connect sub-base to building wiring and a short line cord with 9-pin connector to connect to chassis and plug into receptacle in sub-base. Short sub-b ase line cord may not be used without sub-base. Junction box for 230/208-volt cha ssis mu st be purchased separa tely. RAK4002A for 2900, 3900, 4100, and 6100 series units, RAK4002B for 5800 series units.
Direct
Electric
Heat
BTUH
Electric
Heater
Watts
Electric
Heat
Amps
Min. Circuit
Protection
265-Volt Sub-Base and Direct-Connected Units
Sub-Base
RAK204E15 RAK5172 RAK5157 8150 2460 9.6 15 RAK204E20 RAK5202 RAK5207 11550 3460 13.3 20 RAK204E30 RAK5302 RAK5307 16350 4860 18.6 30
Elect ric Heat Amps include electric heater and fan motor cur rent draw. 265-volt units are to be per manently connected i n compliance with National Ele ctrical Code and local codes a nd have a factor y-installed junction box on the chassis. Each 265-volt sub-base kit consi sts of sub-ba se with a ppropriate re ceptacle for minimum circuit amperage, chaseway to route power connector from sub-base to chassis and wiring to connect su b-base to building wiring.
265-Volt Power Connection Kit mu st be orde red separately.
Power
Connection Kit
Direct
Connection Kit
Electric Heat
BTUH
Electric Heater
Watts
Electric Heat
Amps
Min. Circuit Protection
(Amps)
Important
(Amps)
Essential Elements Ordering Overview
230/208-volt line-cord connected units — order line cord kit 230/208-volt sub-base connected units — order sub-base 265-volt units — order sub-base and power connection kit
®
ZONELINE
CHASSIS NOMENCLATURE
The Zoneline chassis is identified by a model number defining the type of unit, cooling capacity, electrical information and optional features included on the unit. When specifying or ordering the Zoneline chassis, the use of this nomenclature will assure receiving the correct unit.
EXAMPLE
AZ61H12DAD
Zoneline
packaged terminal chassis
Chassis series
41= deluxe line cool/
electric heat
61=deluxe line heat pump
Unit type
E= cooling with electric
resistance heat
H= heat pump with electric
resistance heat
Nominal cooling capacity
07=7,000 BTUH cooling 09=9,000 BTUH cooling 12=12,000 BTUH cooling 15=15,000 BTUH cooling
Voltage/Phase/ Frequency
D= 230/208-Volt,
single-phase, 60 Hz
E= 265-Volt, single-phase,
60 Hz
Universal power connection
Special Features
B=base unit C=corrosion treated D= internal
condensate removal (ICR) system (heat pump models only) (not for coastal areas)
P= Dry Air 25 (4100
Series only)
Specifications subject to change.
4
The Zoneline 4100 and 6100 Series have incorporated changes suggested by customers, along with enhancements by GE’s Technology Team and changes necessary to meet new UL and NEC requirements.
“L” shaped condenser coil.
Cross-flow blower across the product line for quieter operation.
The “Partial Open Vent Air” feature was a specific request by a customer.
“Heat Sentinel” is an enhancement developed by GE’s Technology Team to help lodging professionals welcome their guests with a moderate-temperature room and to help lower cooling costs.
Devices have been added on cord-connected units to protect against injury from unsafe power cords.
See the “Features and Benefits” section for in-depth explanation of these changes and the industry-leading features of GE Zoneline retained from the previous series.
The Deluxe 4100 Series Zoneline models include The “Dry Air 25” models, which remove 25% more moisture than other Zoneline models.
As warm, humid air is pulled through the pre-cool (front) section of the heat pipe, the heat removed from the air is absorbed by the refrigerant, causing the refrigerant to change to a gas and flow to the re-heat (rear) section of the heat pipe. The air leaving the pre-cool section of the heat pipe is cooler and at a higher relative humidity level than the room air. The pre-cooled air is further cooled as it passes through the evaporator, consequently allowing the evaporator coil to remove more moisture.
When the cold air from the evaporator comes in contact with the re-heat section of the heat pipe, the heat that was removed by the pre-cool section is added back to the air
Deluxe Dry Air 25 Models
Cooling With Resistance Heat
• Removes 25% more moisture than standard Zoneline models
• Cools and dries air in less time than standard Zoneline models
• Dry Air is a separate sealed refrigerant system — No mechanical parts — No special maintenance required
• Helps maintain lower relative humidity in rooms
• Maintains comfort at slightly higher room temperatures — Reduces operating costs — Provides comfort without
overcooling
• Corrosion treatment is standard
• Excellent choice for humid climates
• Available in 7,000, 9,000 and 12,000 BTU sizes The Dry Air 25 system, a heat pipe, is a hermetically sealed
heat transfer surface installed in a “saddlebag” configuration around the indoor (evaporator) coil of the Zoneline unit. This coil arrangement will transfer heat from the front coil of the saddlebag to the rear coil without power consumption. This assembly uses R-410A as the refrigerant and is not connected to the regular Zoneline refrigerant circuit.
and the refrigerant in the heat pipe condenses and flows back to the pre-cool (front) section. The air discharged into the room by this process is much drier, creating a more comfortable room condition.
The Dry Air 25 models center around GE’s exclusive use of the patented Dinh® Dehumidifier Heat Pipe from Heat Pipe Technology, Inc. This innovative NASA spin-off technology enables Dry Air 25 to remove 25% more moisture from the air than other leading manufacturers’ packaged terminal air conditioners. This helps maintain room comfort at a higher room temperature, reducing operating costs.
The Dry Air 25 keeps a room cool and dry, and this is the most important benefit when it comes to the occupant of the room—hotel guests, apartment residents, students. In a hot, humid climate, getting away from the humidity is just as important as getting away from the heat, and the Dry Air 25 is the perfect solution. The dehumidification of the Dry Air 25 has been verified by the same AHRI test conditions under which standard units are rated.
Specifications subject to change.
5
TABLE OF CONTENTS
Front Cover 1
Mini Specs 4100 and 6100 Series 2–3
Mini Specs Power Connection Kits and Nomenclature 4
The 4100/6100 and Dry Air 25 5
Tab le of Conte nts 6
Introduction 7
®
The Zoneline
Features and Benefits
Features Table 9
Features and Benefits 10–12
Auxiliary Control Settings 13–14
Central Desk Control 15
Remote Thermostat Control 16–18
Heat Pumps and Energy Savings 19–20
Installation and Dimensions
Application Comments 21
Case Dimensions 22
Wall Case/Sub-Base Installation 23–34
Condensate Disposal Systems 35–37
Ducted Installations 38–40
Exterior Grilles 41–42
System 8
Product Data
Electrical Connection 43
Essential Elements Ordering Overview 44
Maximum Connected Load 45
Latent System Capacity 45
Normal Yearly Operating Data 46
Schematics 47–50
Product Specifications
Suggested Bid Form Specifications 51–52
Zoneline Chassis Nomenclature/Receptacles/Sub-Bases 53
Preliminary Specifications 54–55
Complete Accessory List 56
General Installation Suggestions 57–58
Warranty 58
Alphabetical Index 59
Back Cover 60
Important Notice
Equipment used as a primary source for heating or cooling is an integral part of the building in which it is installed. Proper application is essential for satisfactory performance over a wide range of operating conditions. It is strongly recommended that a professional engineer determine proper application.
If the unit is a replacement unit, its specifications and performance may differ from those of the unit it is replacing. For that reason, we again strongly recommend that a professional engineer determine proper application.
6
INTRODUCTION
This manual is designed to provide product, performance and application information to our customers and their architects and engineers for use in selection and design of a zonal comfort control system utilizing GE Zoneline Packaged Terminal Air Conditioners (PTAC) and Packaged Terminal Heat Pumps (PTHP). GE Zoneline PTACs and PTHPs are self-contained units designed for through-the-wall installations in hotels, motels, apartments, hospitals, nursing homes, add-on rooms and many other installations.
Zoneline units provide individual room or zone control in both cooling and heating operation. There is a model for practically every application, ranging in cooling capacity from 7,200 to 14,500 BTUH and heating capacity from 6,200 to 13,500 BTUH in heat pump operation. See pages 42 and 52 for resistance heaters available.
The Deluxe Line consists of the 4100 Series with electric resistance heat, the 4100 Series Dry Air 25 Models with enhanced dehumidification for hot and humid climates and the 6100 Series heat pump. The 6100 Series heat pump features reverse-cycle defrost and simultaneous supplemental resistance heat, when needed, to maintain room comfort. Both offer tactile touch controls with digital display and optional corrosion protection.
Deluxe Line Standard Features:
• Two-fan-motor system with indoor cross-flow blower for quieter operation
• Digital Controls
—LED Temperature Display —Easy Temperature Selection —Tactile Touch Pad
• Universal Heaters
• Heat Sentinel
• “L” Coil Design Condenser
• 3-Position Vent Door
• Freeze Sentinel
• Indoor Coil Frost Control
• Central Desk Control Interface
• Remote Thermostat Control Interface
• Random Restart
• Electronic Temperature Limiting
• “Smart Fan” Fan Cycle/Continuous Control
• Transfer Fan Interface
• Reverse Cycle Defrost and Simultaneous Supplemental Resistance Heat on Heat Pumps
• Quick Heat Recovery
Deluxe Line Optional Features:
• Corrosion Protection
• Internal Condensate Removal (on 6100 Series Heat Pump without Corrosion Protection)
NOTE: Dry Air 25 models include all the standard features of the
4100 Series plus standard corrosion protection.
Advantages of the GE Zoneline System:
• Flexible Application
— May be installed from flush to finished floor,
to 3" from the ceiling — 7,200 to 14,500 BTUH units in same physical size — Deluxe 4100 and 6100 Series may be ducted to
condition more than one room — Compatible with Class 2 remote thermostat control — Compatible with 2-wire CDC or many Energy
Management Systems
• Economical Installation — No ductwork necessary — No mechanical equipment rooms or pipes required
for heating/cooling units — Replacement units fit existing 42"-wide by 16"-high
wall cases
• Quiet Operation — Indoor cross-flow blower
• Energy-Saving Operation — Units in unoccupied areas may be turned off — Designed for efficient cooling operation — EERs from
10.3 to 13.0 — Efficient heat pump units — COPs from 3.3 to 3.9 — Extended heat pump operation without sacrificing
room comfort
• Ease of Maintenance — Permanently lubricated fan motors — Upfront lift-out interchangeable filters — Slide-out chassis for easy access for cleaning or if
service is required
• Reverse Cycle Heat Pump Operation The 6100 Series heat pumps utilize the unique GE PTAC
heat pump operation to ensure a comfortable room. The logic used by the units is the same logic used by central system heat pumps to provide greater savings.
Specifications subject to change.
7
THE ZONELINE® SYSTEM
The typical Zoneline installation consists of the wall case (or sleeve), chassis, power cord and exterior grille. Some installations may use a sub-base for support of the unit or for ease of electrical connections. Each of the components should be the standard products offered by GE, or, in the case of the exterior grille, approved by GE Applications Engineering. Use of components not specifically designed or approved for use with the Zoneline unit can result in unsatisfactory operation and can be the cause of failure not covered by the warranty.
Components of the Zoneline System
Typical Installation
Chassis
Room Cabinet
(Deluxe Series shown)
Wall Case RAB71A (Steel-Insulated) RAB77A4 (SMC — Molded) Wall Case Options (See pages 22-23)
RAG67 (shown) Grille Options (See page 41)
Power Connection Kit (required on all units) Line Cord Kit shown See pages 43-44
Power Supply Cord
Optional Accessories of the Zoneline System
Chaseway
RAK204D20P Sub-Base (shown)
Power Supply Cord (included with certain 208V/230V sub-bases)
See pages 23 and 33 for information on electrical sub-bases and chaseway. See pages 38-40 for information on ducted installations.
8
RAK6052 Duct Adapter
RAK601/602 Duct Extension, Register and Trim Flange
ZONELINE FEATURES
Resistance heat Heat pump
AZ
41 Series
Cooling EER range (230 Volts/265 Volts) 10.6 - 12.8 11.3 - 12.2 10.8 - 13.2 Heating COP range (230 Volts/265 Volts) N/A N/A 3.3 - 4.0 Refrigerant type R-410A R-410A R-410A Cross-flow (tangential) blower Standard Standard Standard Enhanced dehumidification Optional Standard — Heat pump with resistance heat back-up Standard Heat pump with supplemental resistance heat Standard Staged heating 3-Stage*** Universal heaters - UPC** Standard Standard Standard Tactile touch-pad controls with LED Standard Standard Standard Touch control set-up features Standard Standard Standard Highly featured microcomputer controls Standard Standard Standard Electric resistance heat lock-out (above 46°F) Standard Automatic emergency heat Standard Standard Standard Heat pump defrost system Reverse cycle High-temperature operation protection Standard Quick heat recovery Standard Heat boost Selectable Separate indoor & outdoor
motors — permanently lubricated 2-speed outdoor fan Standard Standard Standard Indoor fan speed settings Hi/Low Hi/Low Hi/Low "Fan Only" setting—2-speed Hi/Low Hi/Low Hi/Low "Cool & Heat Only" settings Hi/Low/Auto Hi/Low/Auto Hi/Low/Auto “SmartFan” fan cycle control Standard Standard Standard Auto power recovery Standard Standard Standard Automatic compressor restart delay Standard Standard Standard Freeze Sentinel (41F) Standard Standard Standard Heat Sentinel (85F) Standard Standard Standard Automatic indoor frost control Standard Standard Standard Temperature limiting Electronic 7-step Electronic 7-step Electronic 7-step Solid-state thermostat Standard Standard Standard Remote thermostat compatibility Standard Standard Standard Central Desk Control compatibility Standard Standard Standard 2-position discharge grille 50º/40º Standard Standard Standard Upfront filter (interchangeable) Standard Standard Standard 3-position manual air vent control Standard Standard Standard Sleep function Standard Standard Standard Transfer fan connections Standard Standard Standard Ducted installation capability Optional Optional Optional Corrosion-treated chassis Optional Standard Optional Internal condensate removal (ICR)* Optional
*Not for use in corrosive environments **UPC — Universal Power Cord Connection (see pages 43 and 53). *** Two-stage heating if using remote thermostat 265-volt units must be connected in a manner to meet National Electrical Code and all local codes.
AC AC DC
AZ
41 Dry Air 25
AZ
61 Series
Specifications subject to change.
9
FEATURES AND BENEFITS
Standard Physical Dimensions
GE has maintained the same dimensions since 1961 — 42" wide x 16" high x 13-3/4" deep — making replacement of older units easy.
Weather-Protected Electrical Components
Vital electrical components are protected from the weather by locating them on the indoor side of the weather barrier.
Weather-Resistant “Superseal”
Properly installed unit in undistorted case keeps air leakage to a minimum.
7 CFM air infiltration with 25 MPH wind on ICR units — even less on units without ICR
Industry specification is 19 CFM of air infiltration
Heater Sizes to Meet Room Requirements
All units are equipped with a universal heater
the resistance heat output is determined by power connection kit.
230/208-volt — Line-Cord Connected Units
2.4/2.32 KW with RAK3153A — 15-amp circuit
3.3/3.20 KW with RAK3203A — 20-amp circuit
4.7/4.53 KW with RAK3303A — 30-amp circuit
230/208-volt - Sub-Base Connected Units
2.4/2.32 KW with RAK204D15P — 15-amp circuit
3.3/3.20 KW with RAK204D20P — 20-amp circuit
4.7/4.53 KW with RAK204D30P — 30-amp circuit
265-volt
2.4 KW with RAK5172 — 15-amp circuit
3.4 KW with RAK5202 — 20-amp circuit
4.8 KW with RAK5302 — 30-amp circuit
Automatic Emergency Heat
Automatically uses electric resistance heat if the heat pump output is not sufficient to maintain selected room temperature.
Reverse Cycle Heat Pump Defrost System
Standard on all Zoneline 6100 Series heat pumps
Enables heat pump to operate at lower temperatures when other systems switch to more expensive electric resistance heat.
See pages 18 and 19 for discussion of heat pump operation and defrost systems.
High-Temperature Heat Pump Operation Protection
Automatically protects the compressor if heat pump is operated with high outdoor temperatures.
Power to the outdoor fan is turned off if the indoor coil gets too hot during heat pump operation to prevent damage to the compressor.
Quick Heat Recovery – Heat Pump Units
When the unit operation is changed from STOP or COOL to HEAT, the electric resistance heaters are used to warm the room to the thermostat set point. This provides faster room temperature increase for greater guest comfort.
Fan Motors – Permanently Lubricated
All units have two fan motors for quiet operation and maximum operating efficiency.
Motors are permanently lubricated to reduce maintenance and totally enclosed to keep dirt and water out of the motor windings.
Unit Controls
4100 and 6100 Series — touch pad controls with digital
readout of temperature set point
Highly Featured Microprocessor Controls
Microprocessor controls are programmed to interface with the temperature sensors to maximize comfort conditions for the room occupant and provide outstanding features.
Thermistors are used to sense small changes in temperature to give excellent room control and allow the microprocessor to monitor and react to changing conditions.
Electric Resistance Heat Lock-Out
To maximize the savings of the heat pump operation, the Zoneline® heat pumps do not utilize the resistance heater when the outdoor temperature is above 46°F during normal operation. The resistance heat is used in the Quick Heat Recovery feature.
10
Outdoor Fan
The unit automatically selects the most efficient speed for the outdoor fan. The operating sound level is lower when the outdoor fan can operate in low speed, yet there are situations where it must operate in high speed. The unit changes the fan speed automatically.
Indoor Fan Speed Selections – HIGH/LOW
Unit may be operated in HIGH HEAT or LOW HEAT or HIGH COOL or LOW COOL.
FEATURES AND BENEFITS (cont)
Fan-Only Setting – HIGH/LOW
The unit provides the option of selecting either HIGH or LOW speed for Fan-Only operation.
Fan-Cycle Switch – “SmartFan”
Unique “SmartFan” allows unit to operate fan continuously in cooling operation and fan cycle in heating to provide better guest comfort. Eliminates complaint of cold-air draft during the heating season.
Eliminates the need for changing fan-cycle switch seasonally.
“SmartFan” settings are controlled via the auxiliary control setting push button.
Compressor Random Restart
In the event of a power failure, all compressors attempting to restart immediately when power is restored can result in a power surge that can cause another power interruption.
The microprocessors in the Zoneline units have a random restart logic system that prevents all units from starting at the same time.
Rotary Compressor
Provides smoother operation for quiet, dependable service. GE has used rotary compressors since 1961.
Compressor Restart Delay
Zoneline units are designed to provide a minimum of three minutes of compressor-off time to allow refrigerant pressures to equalize before restarting to prevent compressor damage.
Zoneline units are also designed to provide a minimum of three minutes of compressor-run time to prevent room occupant disturbance due to short-cycling of the air conditioner.
Freeze Sentinel
Detects low room temperature and turns on heater to help protect against damage caused by freezing room temperature.
Heater turns on at 41°F and warms indoor thermistor temperature to 46°F and shuts off.
Freeze Sentinel may be turned off by dip switch on auxiliary control.
Heat Sentinel
The property owner may choose to activate the Heat Sentinel feature on the Zoneline unit. If the Heat Sentinel is activated and room temperature reaches 85°F (even when the unit is in the “STOP” setting), the unit will automatically start in air conditioning operation and will shut off when the room temperature reaches 80°F. This will help dehumidify the air and lower high temperatures so the guest will not be entering an extremely hot room.
Indoor Coil Frost Control
Prevents indoor coil from freezing and causing complaints due to lack of cooling. Frost can form on the indoor coil when the unit is operated in cooling when outdoor temperatures are low. The unit automatically shuts the compressor off until the indoor coil temperature warms to the point where frosting will no longer occur.
Trans fer Fan Inter face
24 VAC terminals are provided to operate a relay to control a fan mounted in a wall to move conditioned air into another space. The electrical power for the operation of the transfer fan itself is not provided by the Zoneline unit. Transfer fans and their controlling relays are field supplied.
Electronic Temperature Limiting
Seven independent programmable heating temperature limits and seven independent programmable cooling temperature limits.
Heating Temperature Limits
65 70 72 74 76 78 80 85
Lowest
Cool
60 64 66 68 70 72 74 76
Limits are set via the auxiliary control setting push button.
Cooling Temperature Limits
Highest
Heat
Remote Control Capability with Wall-Mounted Thermostat
See pages 16–18.
Central Desk Control Capability
See page 15.
Energy Management System Interface with Load-Shedding Option
All units have a switch via the auxiliary control setting to allow the indoor fan to continue operating if the unit is connected to an energy management system that shuts off compressor or heater operation. By allowing the indoor fan to run when the heater or compressor is shut off by the energy management system, the guest is less likely to realize the operation of the unit has been altered. This helps reduce peak energy demand loads without disturbing the room occupant.
Reversible Indoor Air Louvers
Allows air to be directed into room at 40º or 50º angle to provide better air distribution.
Angle is changed by removing room front and screws holding louver in place, and rotating louver section.
11
FEATURES AND BENEFITS (cont)
Up-Front Air Filters
Two interchangeable up-front filters, easy to remove and reinstall, may be cleaned without opening or removing the room front.
Clean filters by brushing, vacuuming or back­flushing under faucet or shower head.
Concealed Manual Vent Control
Open ventilation doors on GE Zoneline® Packaged Ter minal Air Con ditione rs and Heat Pumps allow outside air to enter the room through a screen-covered opening in the weather barrier that separates the indoor and outdoor sections of the unit.
A concealed lever, located along the left side of the unit under the front cover, is used to open and close the vent door.
The 3-position manual vent door control may be closed, partially open or fully open. Positive vent door closure prevents accidental opening and unwanted air infiltration.
Vent CFM High Speed
Unit Full Open Partial Open
7000 50 40
9000 70 45
12000 75 45
15000 75 45
CFM ratings at 230 and 265 volts.
For each CFM of air to enter the room, an equal amount of air must be removed through exhaust fans in the bathroom or roof tops. Greater amounts of air will be introduced (from chart shown above) depending on the size of the exhaust fan.
Outside ambient air entering the room through this screened vent opening is not conditioned. This unconditioned air becomes mixed with the conditioned air that is circulated by the indoor fan. This air mixture generates an additional heat load/heat loss that causes the unit to run longer and may translate into higher operating costs.
Zoneline vent openings are not intended to be the source of make-up air for building ventilation systems due to the additional heating or cooling loads generated.
Corrosion Protection (Optional)
4100 and 6100 Series units may be ordered with special protection to better withstand damage from salt air and salt water in seacoast or other corrosive areas.
Corrosion protection is standard on the Dry Air 25 models.
Heat pump units with ICR are not available with corrosion protection and should not be installed in seacoast or other corrosive environments.
Units installed in corrosive areas should use the RAB77 wall sleeve and be examined/cleaned more frequently than normal installations.
Internal Condensate Removal (ICR)
See page 35 for a discussion of the Internal Condensate Removal system available on 6100 Series heat pumps.
Enhanced Dehumidification
Moisture removal is an important function of an air conditioner. People are more comfortable at higher temperatures when the humidity level is relatively low. Air conditioners operate with less energy consumption when the room temperatures are set higher.
The GE Zoneline 4100 Series with the Dry Air 25 heat pipe application removes 25% more moisture than the base 4100 Series unit .
The GE Zoneline Dry Air 25 chassis is the only PTAC available with the application of the patented Dinh® Dehumidifier Heat Pipe under license from Heat Pipe Technology, Inc.
Customers who are using the Dry Air 25 report a fresher­smelling room as a result of the lower humidity levels, as well as lower operating costs.
Locking Door Kit
RAK8023 — A door with a lock that replaces the standard
control cover door to prevent unauthorized changing of control settings is offered as an accessory.
12
AUXILIARY CONTROL—AUX SET BUTTON
Press “AUX SET”
First Digit
Second Digit
Press “Mode”
Press
/
Smart Fan
HEAT COOL
Load Shedding
Sentinel
HEAT COOL
Constant Fan
Temperature
Limit
HEAT COOL
Class 2 Mode
Duct Mode
All I2R Mode
Boost Heat
0: 60F-85F 1: 64F-85F 2: 66F-85F 3: 68F-85F 4: 70F-85F 5: 72F-85F 6: 74F-85F 7: 76F-85F
0: 60F-65F 1: 60F-70F 2: 60F-72F 3: 60F-74F 4: 60F-76F 5: 60F-78F 6: 60F-80F 7: 60F-85F
HEAT
COOL
– Off
–On
– Off
–On
– Cycle
– Continue
(AZ61 Only)
(AZ61 Only)
The auxiliary control push button is located behind the room cabinet, below the control panel. The auxiliary controls come preset to the modes most desired by customers. However, the owner is responsible for ensuring the auxiliary controls are set to the desired function. There are 9 different modes that can be set using the auxiliary set button.
To change modes:
• Press the STOP button.
• Press AUX SET (“AU” appears on the display).
• Press the MODE button on the control pad until the first digit in the display shows the number corresponding to the mode you are choosing and the correct HEAT/COOL LED is lit.
• Press the UP or DOWN arrow to change the mode setting selection (second digit in the display).
• Press the MODE button to move to the next feature or the AUX SET button to exit the set up process.
Auxiliary Set Button
Access Cover
Press “AUX SET”
First Digit
Press “Mode”
Smart Fan
Load Shedding
Sentinel
Constant Fan
Temperature
Limit
Class 2 Mode
Duct Mode
All I2R Mode
(AZ61 Only)
Boost Heat
(AZ61 Only)
HEAT COOL
HEAT COOL
HEAT COOL
Press /
Second Digit
– Cycle
– Off
COOL
0: 60F-85F 1: 64F-85F 2: 66F-85F 3: 68F-85F 4: 70F-85F 5: 72F-85F 6: 74F-85F 7: 76F-85F
– Off
HEAT
0: 60F-65F 1: 60F-70F 2: 60F-72F 3: 60F-74F 4: 60F-76F 5: 60F-78F 6: 60F-80F 7: 60F-85F
– Continue
–On
–On
AUXILIARY CONTROL SETTINGS
Mode 1—Smart Fan—Cooling/Heating
The default setting for Mode 1 is as follows: Cooling: Continuous (ON) Heating: Cycle (OFF)
* Note: In cyclic Cooling Mode, the indoor fan will activate occasionally
to verify air temperature in the room. In cyclic Heating Mode, the fan will continue to operate for 90 seconds after the heating function has stopped in order to increase unit efficiency.
Mode 2—Load Shedding (Central Desk Control) The default setting for Mode 2 is OFF. This feature is active only if the unit is connected to a CDC and the CDC has control. When this mode is on, only the indoor fan can be turned ON or OFF with the unit controls. When this mode is off, all operation is disabled except Heat/Freeze Sentinel (Mode 3).
Press “SET”
First Digit
Press “Mode”
HEAT COOL
Press “Mode”
HEAT COOL
Press “Mode”
Second Digit
Press
Press
Press
/
Smart Fan Cool – Cycle*
Smart Fan Cool – Continue
/
Smart Fan Heat – Cycle*
Smart Fan Heat – Continue
/
Load Shedding – Off
Load Shedding – On
13
AUXILIARY CONTROL SETTINGS (cont)
Mode 3—Freeze Sentinel/Heat Sentinel
The default settings for Mode 3 are: Heat Sentinel is off Freeze Sentinel is on. When Freeze Sentinel is activated, it automatically provides heat without user interface. This helps to prevent plumbing damage by turning the heater and indoor fan ON at 41ºF and OFF at 46ºF. When Heat Sentinel is activated, it automatically provides cooling without user interface. This helps to prevent an excessively hot room by turning the air conditioner ON at 85ºF and OFF at 80ºF.
NOTE: These functions are active whenever the unit is plugged in, even if the unit is in the STOP position.
Mode 4—Constant ON Fan The default setting for Mode 4 is OFF.
Mode 5—Temperature Limiting The default setting for Mode 5 is as follows: Cool: 2 (66ºF to 85ºF) Heat: 5 (60ºF to 78ºF)
Temperature limits—Cool Temperature limits—Heat
0 = 60°F to 85°F 0 = 60°F to 65°F 1 = 64°F to 85°F 1 = 60°F to 70°F 2 = 66°F to 85°F 2 = 60°F to 72°F 3 = 68°F to 85°F 3 = 60°F to 74°F 4 = 70°F to 85°F 4 = 60°F to 76°F 5 = 72°F to 85°F 5 = 60°F to 78°F 6 = 74°F to 85°F 6 = 60°F to 80°F 7 = 76°F to 85°F 7 = 60°F to 85°F
Mode 6—Remote Thermostat – Class 2 The default setting for Mode 6 is OFF. Setting this mode to ON will allow the unit to operate with a Class 2 Remote Control Wall Thermostat.
Mode 7—Duct Mode The default setting for Mode 7 is OFF. This setting is used when the unit is installed using a duct adapter kit. If the unit is ducted, the Duct Mode needs to be set to ON. This increases the fan speed to ensure proper circulation.
Mode 8—All-Electric Heat (AZ6100 only) The default setting for Mode 8 is OFF. This electric heat option functions only on the 6100 model. When this option is ON, heat pump operation is locked out, causing the unit to provide only electric resistance heat.
Mode 9—Heat Boost (AZ6100 only) The default setting for Mode 9 is OFF. When Heat Boost is ON and outer temperatures are between 25ºF and 46ºF, heat pump-only operation is locked out. This setting is used to provide supplementary heat to the heat pump operation by electric resistance heat in conditions where the heat pump-only operation is not sufficient to maintain a consistent, comfortable room temperature.
NOTE: Heat Boost option should NOT be used with remote thermostat operation. This will cause the unit to switch to resistance heat when the outdoor temperature is 46ºF.
14
Press “Mode”
HEAT
COOL
Press “Mode”
HEAT COOL
Press “Mode”
Press “Mode”
HEAT COOL
Press “Mode”
HEAT COOL
Press “Mode”
Press “Mode”
Press “Mode”
Press “Mode”
Press
Press
Press
Press
Press
Press
Press
Press
Press
/
Freeze Sentinel – Off
Freeze Sentinel – On
/
Heat Sentinel – Off
Heat Sentinel – On
/
Constant Fan – Off
Constant Fan – On
/
Temperature Limit Cool
0: 60F-85F 1: 64F-85F 2: 66F-85F 3: 68F-85F 4: 70F-85F 5: 72F-85F 6: 74F-85F 7: 76F-85F
/
Temperature Limit Heat
0: 60F-65F 1: 60F-70F 2: 60F-72F 3: 60F-74F 4: 60F-76F 5: 60F-78F 6: 60F-80F 7: 60F-85F
/
Class 2 Mode – Off
Class 2 Mode – On
/
Duct Mode – Off
Duct Mode – On
/
ALL 12R Mode – Off
ALL 12R Mode – On
/
Boost Heat – Off
Boost Heat – On
CENTRAL DESK CONTROL
Unit #2
Unit #1
Unit #3
CDC Terminals
on Zoneline unit
Some installations may want to govern the ability of the unit to operate from a control device remote to the unit or even remote to the room in which the unit is located. The general term given to systems such as this is Central Desk Control (CDC). The most common installation of this type of system is a switch mounted at the registration desk and, upon guest check-in, a button is pushed or a switch is moved to allow the air conditioner to operate. Likewise, when the guest checks out, the device is put into the “OFF” position so the unit will not operate while the room is vacant.
It is not necessary that the controlling device be located at a central desk to employ a device that will control the unit operation. For instance, in some resort areas, devices are connected to sliding glass doors and opening the door causes a contact to close, turning the air conditioner off. This prevents energy being wasted by operating the air conditioner when warm, humid air is entering the room. Some systems operate by motion sensors or heat-sensing detectors mounted in the room. These types of systems determine occupant presence in the room and allow the unit to operate; if no one is in the room the device signals the air conditioner to turn off.
®
Zoneline
models offer load-shedding capabilities on units connected to Central Desk Control systems. For more information on the models’ load-shedding feature, see page 11.
There is a wide variety of devices available, each with its own benefits and constraints. While GE does not offer components that are external to the unit for a Central Desk Control system, GE Zoneline units are compatible with most CDC and energy management systems. Zoneline units
provide a 24 VAC circuit that powers the Central Desk Control system and no external power is needed.
All Zoneline 4100 and 6100 Series units are compatible with simple on/off 2-wire Central Desk Control systems. Consult with the provider of the energy management system to be sure it is compatible with GE Zoneline units. Zoneline units have standard connectors factory-installed to provide a CDC interface that permits the unit to be connected to most of the energy management systems. The devices connected to the Zoneline units require no power supply or transformers external to the unit.
Important CDC Comments (all series applicable)
4. Recommended wire size must be followed as a minimum requirement.
Wire Size #AWG Maximum Allowable Length
#22 600 Ft. #20 900 Ft. #18 1500 Ft. #16 2000 Ft.
Freeze Sentinel and Heat Sentinel remain operational when the unit is connected to a CDC system. Even if the unit is turned “OFF” at the central location, if the sensor at the unit detects the low or high limit temperature, the unit will automatically turn on until it reaches the preset shutdown temperature (46°F heating, 80°F cooling).
Connecting the Zoneline unit to a CDC system does not eliminate the ability to connect the unit to a remote thermostat. Once the circuit is “opened,” and control of the unit removed from the CDC system, the selected controls—either the unit­mounted control or the remote thermostat—govern the operation of the unit.
Please see page 57 for installation recommendations for the Central Desk Control wiring.
CDC Terminal Location and Typical Wiring
See page 16 for location of CDC terminals on unit.
Example of Common Busing
NOT PERMITTED
INCORRECT Common Busing
Normally Open
Switch -
Unit Operational
1. When the switching device closes the circuit of the CDC conductors, the unit operation stops.
2. Do not use a common bus (at the unit or at the switch panel) in the wiring. Both wires comprising the circuit must connect to the unit connectors and to the controlling switch. Running one wire from one unit to another unit is common busing and may damage internal components or cause erratic operation of the system.
3. A 24-volt transformer is contained within the Zoneline unit. No external voltage may be applied to the unit through the CDC terminals. (Voltage on the CDC conductors is 24 volt s AC.)
Typical Wiring
(All Wiring Shown Is Field Supplied)
15
REMOTE THERMOSTAT CONTROL
R
GL
GH
B
Y
W
C
Common White — Heater Yellow — Compressor Black — Not Used On 4100 Green — High-Speed Fan Green — Low-Speed Fan Red — 24V AC CDC Terminal
CDC
In some installations, control of the operation of the unit at a location remote from the unit itself may be desired. A unit mounted high in the wall or over a door, for instance, where the unit-mounted controls are inaccessible, can be connected to a wall-mounted thermostat. Other installations may use remote thermostat control for design or performance enhancement. The unit is connected to the thermostat by low-voltage wiring which permits the operation of the unit to be selected and the temperature sensed at the thermostat.
Important Notes: Remote thermostat wiring should NOT be run through the wall case. Thermostat wiring should exit the wall below the unit and enter the unit between room cabinet and chassis. Wire molding may be used to hide thermostat wiring. If a sub-base is used, the thermostat wiring may be concealed by the sub-base. Thermostat wiring should NOT be run parallel to line voltage wires since induced current may cause erratic operation.
®
All Zoneline
4100 and 6100 Series units are adaptable to Class 2 remote low-voltage thermostats. The only additional field-supplied components are the remote thermostat and wiring necessary to connect it.
The controls on the unit are not functional when the remote control function is used.
RAK806 Universal Control Cover Label
When a Zoneline unit is using a remote thermostat control, the RAK806 Universal Control Cover Label is recommended. The RAK806 is only available in a package of 10 labels. The label is placed over the control panel to direct the user to the wall thermostat for operation of the Zoneline unit.
The remote thermostat-Class 2 option (Mode 6 in the auxiliary control setting) must be turned ON to enable remote thermostat control. Refer to installation instructions packaged with the chassis.
Please see page 57 for installation recommendations for the remote thermostat wiring. Compatibility of other thermostats considered for use with GE Zoneline units is the responsibility of the customer.
The control voltage on the remote control conductors is 24 volts AC. The AC voltage may not be compatible with some solid-state thermostats.
The fan speed for the 4100 Series in remote thermostat operation is selected by the connection of the fan wire from the thermostat to either the HIGH or LOW terminal on the unit. See the sketch of the unit terminals below for the location of the HIGH and LOW fan-speed terminals. Operating the unit in low fan speed reduces the operating sound level of the unit.
Freeze Sentinel and Heat Sentinel remain operational if the unit is connected to a remote thermostat. The unit may be connected to a Central Desk Control (CDC) system and controlled with a remote thermostat when the CDC system has the unit in operation. See page 15 for additional information on the CDC system.
Unit temperature-limiting settings are not functional when unit is connected to a remote thermostat.
Field Wiring Terminal
R — 24V AC GL — Low-Speed Fan GH — High-Speed Fan B — Not Used on 4100 Y — Compressor W — Heater C — Common
Resistance Heat Models
The Zoneline 4100 resistance heat units may be connected to a single-stage thermostat designed for use with cooling with electric heat systems. GE offers two thermostats compatible with the 4100 Series unit.
RAK164D2 — a solid-state digital thermostat requiring five connection wires.
16
RAK164P2 — a solid-state digital programmable thermostat requiring five connection wires.
REMOTE THERMOSTAT CONTROL (cont)
R
GL
GH
B
Y
W
C
Common White — Heater Yellow — Compressor Black — Reversing Valve Green — High-Speed Fan Green — Low-Speed Fan Red — 24V AC CDC Terminal
CDC
Heat Pump Models
The Zoneline 6100 Series heat pump units may be connected to a single-stage cooling/two-stage heating thermostat designed for use with heat pump systems. GE offers two thermostats compatible with the 6100 series units:
RAK148D2 — solid-state digital thermostat requiring six connection wires.
Please see page 57 for installation recommendations for the remote thermostat wiring. Compatibility of other thermostats considered for use with the GE Zoneline unit is the responsibility of the customer.
The control voltage on the remote control conductors is 24 VAC. The remote thermostat-Class 2 option (Mode 6 in the
auxiliary control setting) must be turned ON to enable remote thermostat control. Refer to installation instructions packaged with the chassis.
The fan speed for the 6100 Series in remote thermostat operation is selected by the connection of the fan wire from the thermostat to either the HIGH or LOW terminal on the unit. See the sketch of the unit terminals for the location of the HIGH and LOW fan speed terminals. Operating the unit in low fan speed reduces the operating sound level of the unit.
RAK148P2 — solid-state digital programmable thermostat requiring six connection wires.
Feature Heat Pump Electric Heat
Indoor frost control Yes Yes Freeze Sentinel Yes Yes Heat Sentinel Yes Yes Auto fan speed No No Electronic
temperature limiting No No Switch to resistance
heat based on indoor temperature
Switch to resistance heat based on outdoor temperature Yes N/A
Reverse cycle defrost Yes N/A Simultaneous
resistance heat with heat pump No N/A
Resistance heat lockout Yes N/A
“Smart Fan” fan cycle
Central Desk Control Yes Yes
Determined by remote thermostat N/A
Fan ON/AUTO set on remote thermostat
Fan ON/AUTO set on remote thermostat
When connected to a remote thermostat, indoor air­temperature sensing is shifted from the unit to the remote thermostat. For this reason, the units will operate slightly differently when connected to a remote thermostat. The above chart shows the unit operation when connected to a remote thermostat.
The Heat Boost option should NOT be used with remote thermostat operation since this will cause the unit to switch to resistance heat when outdoor temperatures are below 46ºF.
Field Wiring Terminal
R — 24V AC GL — Low-Speed Fan GH — High-Speed Fan B — Reversing Valve Y — Compressor W — Heater C — Common
17
REMOTE THERMOSTAT CONTROL (cont)
Remote Thermostat Control Selection Chart For Zoneline® Packaged Terminal Units
Zoneline Series Thermostat Model Type Function Low-Voltage Conductors
4100 RAK164D2 Di git al
RAK164P2 Digital Programmable 5
6100 RAK14 8D2 Dig ital
RAK148P2 Digital Programmable 6
Thermostat wire size – up to 60 feet AWG20 – up to 66 feet AWG18
For remote thermostat operation follow the steps below:
1. Turn on the unit and ensure it is working properly
BEFORE proceeding.
2. Unplug the unit or disconnect power and remove
the room cover.
3. Connect the thermostat wiring per the appropriate
diagram/colors for your model.
4. Plug the unit back in or reconnect power.
5. Press the AUX SET button once. The letters AU will
appear in the display.
6. Press the MODE button until the number “6” appears
in the left hand digit.
7. Press the UP arrow once so the top half of the right
hand digit is lit.
8. Press the AUX SET button to exit the setup function.
9. Replace the room cover.
Cooling and Heating
Single-Stage Cooling –
2-Stage Heating
5
6
See pages 13 and 14 for full instructions on using the Auxiliary Controls Feature.
18
Loading...
+ 42 hidden pages