GE ARITECH FP1500 Series, ARITECH DI1552, ARITECH DP1551, ARITECH 1500 Series, ARITECH DP1551T Installation And Maintenance Manual

...
Series 1500 Analogue Addressable Detectors
X
Y
Z
[
\
© 2003 GE Interlogix B.V.. All rights reserved. Version 1.0 / July 2003 1044999
Installation and Maintenance Guide
DESCRIPTION
For general guidelines on system planning, design, installation, commissioning, use and maintenance, refer to the EN54-14 (2001) standard and local regulations.
DI1552 Analogue addressable ionisation smoke detector
DP1551 Analogue addressable optical smoke detector
DT1553 Analogue addressable rate of rise heat detector
DB304 Detector mounting base
S700 Mounting supplement
The S1500 series detectors are designed specifically for use with the ARITECH FP1500 series of analogue addressable fire detection control panels. On these systems the control panel communicates with the individual detectors using a unique data transmission protocol. The detectors continuously monitor the environment where they are installed and report any changes in smoke or heat concentration to the control panel. In turn, the control panel generates the alarm condition if applicable.
The detectors have indicators that flash in a “pre-alarm” condition and light continuously in a ”full” alarm condition. The system is reset at the control panel.
An optional remote indicator (part no. AI300) may be connected from the mounting base connections and will mimic the detector indicator.
The DP1551 and DI1552 comply with EN54-7 (2000).
I
NSTALLATION
The detectors must not be exposed to dusty or dirty environments. During building works or repairs, the detectors must be removed.
Smoke detectors should not be installed in environments where condensation may be present.
The surface of the detector must not be painted.
Positioning
Smoke and temperature detectors are designed to be positioned on the ceiling and should be well away from ventilation inlets and air extractors. Once the location is decided, the detector base should be fitted first either to the pre-wired mounting box or direct to the ceiling through the S700 mounting supplement.
Connections
The detectors must be connected as shown in figure X. The cable from the last detector on the loop should return to the control panel to close the loop.
The positive line cable (+) must be connected to terminal 1, and the negative line (-) to terminal 3. If a remote indicator is used, its positive line cable (+) must be connected to terminal 2 in the mounting base and the negative to terminal 3.
To connect the cables in the mounting base, remove a piece of insulation (about 1 cm in length), pass the cables through the hole and connect each cable in its proper location. To lock each cable, unscrew each mounting base connection. Slide the un-insulated tip of the cable under the metal piece and screw down (figure Y).
Check cable continuity before connecting.
Addressing
Each detector requires a numeric address between 1 and 125 for identification purposes. The address may be set using the PG700 portable address programmer or the fire system control panel. Consult the handset or fire panel manual for more full instructions.
Connecting the detector to the mounting base
Once the mounting base is in position, the detector is connected by inserting it and turning. To remove the detector, turn it in the opposite direction (figure [).
Locking catch
All of the detector heads have a locking catch to prevent unauthorised removal.
To enable locking, the locking catch must be broken (figure Z). After connecting the detector, it will be locked in place.
To remove a locked detector, press through the hole (figure \) using a screwdriver or similar, and turn.
Testing
Check that all detectors are properly assembled in their mounting bases.
Activate the control panel and check for correct operation.
Check that all of the installed detectors are recognised by the
control panel. If any detector is not recognised, check that no duplicate addresses have been assigned, check the correct assembly of the detector and its connection.
To test smoke detectors, apply smoke or approved aerosol and verify alarm condition.
To test heat detectors apply temperature using for example a hair dryer and verify that the detector goes into alarm.
Consult the fire panel manual for further test procedures.
M
AINTEN ANCE
In normal environments cleaning should be done at least every three or four years. It is recommended that random functional tests be carried out every six months.
DP1551, DI1552
1. Remove the detector form the mounting base
2. Remove the detector cover by pressing the catch with a screwdriver and turning (see figure 6)
3. Use a vacuum cleaner or clean compressed air to remove the dust from the chamber.
4. Re-install the detector cover
5. Assemble again the detector in its mounting base and test it.
DT1553
These detectors do not require special maintenance or cleaning.
Only authorised personnel must carry out adjustments.
S
ECURITY CERTIFICATE (DI1552)
KILSEN S.A. radioactive facilities....................................IR-B/197/97
The DI1552 has been approved by Spanish Industry and Energy Ministry, as EXEMPT from authorisation as radioactive installation.
Approval code .................................................................. NHM-D161
The detector corresponds exactly with approved sample.
Quality system........................................................ ISO9001 certified
Source manufacturer............................. Amersham International plc.
NRPB and CIEMAT laboratories measures done, (following European Nuclear Energy Agency):
Radioactive source..................................................... Americium 241
Average activity............................... 0.33 ± 0.04 µCi (12.1 ± 1.5 kBq)
Radiation level at 0.1m......................................................0.01 µSv/h
Contamination .................................................................<0.1 Bq/cm
Valid use period is for 10 years. It is forbidden to tamper with the workings of the unit or to remove any labels or signs. If radioactive source is suspected of being faulty, please contact KILSEN S.A. This certificate covers all devices with referred approval code.
2
Loading...
+ 1 hidden pages