Series Setup software are registered trademarks of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin. The content of this manual is for informational use only and is subject to
change without notice.
Part number: 1601-0651-A5 (July 2017)
Note
May contain components with FCC ID: XF6-RS9110N1122
and IC ID: 8407A-RS9110N1122.
Voltage Inputs.......................................................................................................................................... 2 - 22
Control Power........................................................................................................................................... 2 - 24
Working with Graphical Display Pages.......................................................................................... 3 - 3
Single Line Diagram.................................................................................................................................3 - 6
Rugged and Membrane Front Panel LEDs .................................................................................... 3 - 8
Home Screen Icons................................................................................................................................3 - 10
Out of Service............................................................................................................................................3 - 15
Connecting to the Relay......................................................................................................................3 - 23
Working with Setpoints & Setpoints Files ....................................................................................3 - 24
Engaging a Device..................................................................................................................................3 - 25
Using Setpoints Files..............................................................................................................................3 - 26
4.SETPOINTSSetpoints Main Menu ......................................................................................................................4 - 1
Protection and Trip Breaker Selection............................................................................................. 4 - 2
Common Setpoints................................................................................................................................... 4 - 7
USB ................................................................................................................................................................4 - 30
Home Screens..........................................................................................................................................4 - 67
System ................................................................................................................................................4 - 70
Current Sensing....................................................................................................................................... 4 - 71
Voltage Sensing ...................................................................................................................................... 4 - 71
Traditional VT............................................................................................................................................4 - 71
Power Sensing ......................................................................................................................................... 4 - 73
Power System .......................................................................................................................................... 4 - 73
Analog Inputs .........................................................................................................................................4 - 122
Analog Outputs..................................................................................................................................... 4 - 136
Current Elements .................................................................................................................................4 - 153
Inverse Time Overcurrent Curves.................................................................................................4 - 153
Percent of Load-To-Trip....................................................................................................................4 - 160
Phase Time Overcurrent Protection (51P).................................................................................4 - 161
Voltage Elements .................................................................................................................................4 - 198
Volts per Hertz (24) ..............................................................................................................................4 - 217
Power Elements....................................................................................................................................4 - 223
Directional Power (32)........................................................................................................................4 - 223
Frequency Elements...........................................................................................................................4 - 229
Breaker Health ......................................................................................................................................4 - 262
Power Factor (55).................................................................................................................................4 - 266
Digital Counters....................................................................................................................................4 - 284
Local Control Mode (breakers and switches) ..........................................................................4 - 301
Breaker Control .....................................................................................................................................4 - 310
Switch Control (9)..................................................................................................................................4 - 313
Test LEDs ..................................................................................................................................................4 - 358
Last Trip Data.....................................................................................................................................5 - 5
GOOSE Rx and Tx.......................................................................................................................................5 - 8
Information .......................................................................................................................................5 - 13
Main CPU.................................................................................................................................................... 5 - 13
Comms CPU .............................................................................................................................................. 5 - 13
Device Status ...................................................................................................................................5 - 15
Tap Changer................................................................................................................................................ 6 - 7
Data Logger.........................................................................................................................................7 - 2
Clear Records .....................................................................................................................................7 - 6
A.APPENDIX AWarranty.............................................................................................................................................. A - 1
Major Updates ............................................................................................................................................A - 2
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUALVII
Page 10
VIII845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 11
GE
Grid Solutions
845 Transformer Protection System
Chapter 1: Introduction
Introduction
The Multilin 845 relay is a microprocessor-based unit intended for the management and
primary protection of the medium to large size medium voltage (MV) and high voltage (HV)
power transformers. Both 2-winding and 3-winding transformers are supported. The 845
relay provides a number of primary and backup current and voltage based protection
functions. This system allows for control of the circuit breakers at each winding plus a
number of monitoring and control functions are also provided.
Overview
Each relay provides protection, control, and monitoring functions with both local and
remote human interfaces. They also display the present trip/alarm conditions, and most of
the more than 35 measured system parameters. Recording of past trip, alarm or control
events, maximum demand levels, and energy consumption is also performed.
These relays contain many innovative features. To meet diverse utility standards and
industry requirements, these features have the flexibility to be programmed to meet
specific user needs. This flexibility will naturally make a piece of equipment difficult to
learn. To aid new users in getting basic protection operating quickly, setpoints are set to
typical default values and advanced features are disabled. These settings can be
reprogrammed at any time.
Programming can be accomplished with the front panel keys and display. Due to the
numerous settings, this manual method can be somewhat laborious. To simplify
programming and provide a more intuitive interface, setpoints can be entered with a PC
running the EnerVista 8 Setup software provided with the relay. Even with minimal
computer knowledge, this menu-driven software provides easy access to all front panel
functions. Actual values and setpoints can be displayed, altered, stored, and printed. If
settings are stored in a setpoint file, they can be downloaded at any time to the front panel
program port of the relay via a computer cable connected to the USB port of any personal
computer.
A summary of the available functions and a single-line diagram of protection and control
features is shown below. For a complete understanding of each feature operation, refer to
Chapter 4:
feature and show all logic signals passed between individual features. Information related
to the selection of settings for each setpoint is also provided.
Setpoints. The logic diagrams include a reference to every setpoint related to a
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL1–1
Page 12
DESCRIPTION OF THE 845 TRANSFORMER PROTECTION RELAYCHAPTER 1: INTRODUCTION
Description of the 845 Transformer Protection Relay
CPU
Relay functions are controlled by two processors: a Freescale MPC5125 32-bit
microprocessor that measures all analog signals and digital inputs and controls all output
relays, and a Freescale MPC8358 32-bit microprocessor that controls all the advanced
Ethernet communication protocols.
Analog Input and Waveform Capture
Magnetic transformers are used to scale-down the incoming analog signals from the
source instrument transformers. The analog signals are then passed through a 11.5 kHz
low pass analog anti-aliasing filter. All signals are then simultaneously captured by sample
and hold buffers to ensure there are no phase shifts. The signals are converted to digital
values by a 16-bit A/D converter before finally being passed on to the CPU for analysis.
The 'raw' samples are scaled in software, then placed into the waveform capture buffer,
thus emulating a fault recorder. The waveforms can be retrieved from the relay via the
EnerVista 8 Series Setup
Frequency
Frequency measurement is accomplished by measuring the time between zero crossings
of the composite signal of three-phase bus voltages, line voltage or three-phase currents.
The signals are passed through a low pass filter to prevent false zero crossings. Frequency
tracking utilizes the measured frequency to set the sampling rate for current and voltage
which results in better accuracy for the Discrete Fourier Transform (DFT) algorithm for offnominal frequencies.
The main frequency tracking source uses three-phase bus voltages. The frequency
tracking is switched automatically by an algorithm to the alternative reference source, i.e.,
three-phase currents signal or line voltage for the configuration of tie-breaker, if the
frequency detected from the three-phase voltage inputs is declared invalid. The switching
will not be performed if the frequency from the alternative reference signal is detected
invalid. Upon detecting valid frequency on the main source, the tracking will be switched
back to the main source. If a stable frequency signal is not available from all sources, then
the tracking frequency defaults to the nominal system frequency.
Phasors, Transients, and Harmonics
All waveforms are processed eight times every cycle with a DC decaying removal filter and
a Discrete Fourier Transform (DFT). The resulting phasors have fault current transients and
all harmonics removed. This results in an overcurrent relay that is extremely secure and
reliable and one that will not overreach.
Processing of AC Current Inputs
The DC Decaying Removal Filter is a short window digital filter, which removes the DC
decaying component from the asymmetrical current present at the moment a fault
occurs. This is done for all current signals used for overcurrent protection; voltage signals
use the same DC Decaying Removal Filter. This filter ensures no overreach of the
overcurrent protection.
The Discrete Fourier Transform (DFT) uses exactly one cycle of samples to calculate a
phasor quantity which represents the signal at the fundamental frequency; all harmonic
components are removed. All subsequent calculations (e.g. power, etc.) are based upon the
current and voltage phasors, such that the resulting values have no harmonic
components. RMS (root mean square) values are calculated from one cycle of samples
prior to filtering.
Protection Elements
All voltage, current and frequency protection elements are processed eight times every
cycle to determine if a pickup has occurred or a timer has expired. The voltage and current
protection elements use RMS current/voltage, or the magnitude of the phasor.
software for display and diagnostics.
1–2845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 13
894014A3.CDR
Winding 3
Amps
Amps
50/87
87T
Block
3
3
Calculate
Restraint
Amps
Calculate
Operate
Amps
Metering
Transient Recorder
Event Recorder
Fault Report
Data Logger
Calculate
2nd and 5th
Harmonics
Harmonic
Restraint
59N24
Winding 1
Harmonics
AmpsAmps
51N-1
50N-1
51N-2
50N-2
Calculate
3I_0
Calculate
3I_0
Amps
50P-2
51P-2
50P-1
55
51P-1
50BF-1
50G-1
51G-1
87G-1
50G-2
51G-2
87G-2
81R81U81O
RTD input
67P
67N
3V_0
Amps
Harmonics
50BF-2
AFP
59P27P27X
845
Тransformer Protection System
67G-167G-2
59X
Winding 2
3
33
T.C.
Tap
Position
OLTC
Failure
3VTs
49
Harmonics
Amps
50P-3
51P-3
50BF-3
VTFF
32
59_225
51_2
50_2
LIGHT
CHAPTER 1: INTRODUCTIONDESCRIPTION OF THE 845 TRANSFORMER PROTECTION RELAY
Figure 1-1: Single Line Diagram
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL1–3
Page 14
DESCRIPTION OF THE 845 TRANSFORMER PROTECTION RELAYCHAPTER 1: INTRODUCTION
Table 1-1: ANSI Device Numbers and Functions
ANSI DeviceDescription
24Volts per Hertz
25Synchrocheck
27PPhase Undervoltage
27XAuxiliary Undervoltage
32Directional Power
49Hottest Spot Temperature
Aging Factor
Loss of Life
50/87Instantaneous Differential Overcurrent
50BFBreaker Failure
50GGround Instantaneous Overcurrent
50NNeutral Instantaneous Overcurrent
50PPhase Instantaneous Overcurrent
50_2Negative Sequence Instantaneous Overcurrent
51GGround Time Overcurrent
51NNeutral Time Overcurrent
51PPhase Time Overcurrent
51_2Negative Sequence Time Overcurrent
55Power Factor
59NNeutral Overvoltage
59PPhase Overvoltage
59XAuxiliary Overvoltage
59_2Negative Sequence Overvoltage
67GGround Directional Element
67NNeutral Directional Element
67PPhase Directional Element
81OOverfrequency
81UUnderfrequency
81RFrequency Rate of Change
87GRestricted Ground Fault (RGF)
87TTransformer Differential
AFPArc Flash Protection
VTFFVoltage Transformer Fuse Failure
Table 1-2: Other Device Functions
Description
Analog Input
Analog Output
Breaker Arcing Current (I2t)
Breaker Control
Breaker Health
Data Logger
Demand
Digital Counters
Event Recorder
Fault Report
1–4845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 15
CHAPTER 1: INTRODUCTIONDESCRIPTION OF THE 845 TRANSFORMER PROTECTION RELAY
Description
Flexelements
FlexLogic Equations
Flexstates
IEC 61850 Communications
Metering: current, voltage, power, PF, energy, frequency, harmonics, THD
Modbus User Map
Non-volatile Latches
OPC-UA Communications
Output Relays
Setpoint Groups (6)
Transformer Dissolved Gas Analysis
Transformer Energization Reports
Transformer Integrated Fault Report
Transformer Overload
Transformer Loss of Life
Trip Bus (6)
Transient Recorder (Oscillography)
Trip and Close Coil Monitoring
User-programmable LEDs
User-programmable Pushbuttons
Virtual Inputs (32)
Virtual Outputs (32)
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL1–5
Page 16
Setpoints
Device
System
Inputs
Outputs
Protection
Monitoring
Control
FlexLogic
S
tatus
Switches
Contact Inputs
Metering
Summary
Currents
Voltages
Frequency
Harmonics
Power
Energy
Current Demand
Records
Events
Fault Reports
Breakers
Remote Modbus Device
Targets
Directional Power
Data Logger
Volts per Hertz
Digital Counters
RTDs
RTD Maximums
FlexElements
Arc Flash
Syncrocheck
Testing
Output Relays
Virtual Inputs
Information
Device Status
Clock
Arc Flash
Virtual Outputs
Communications
PTP Status
Flex States
Last Trip Data
Breakers
Summary
Transformer
Harmonic Magnitude
Transients
Clear Records
Power Factor
Analog Inputs
DESCRIPTION OF THE 845 TRANSFORMER PROTECTION RELAYCHAPTER 1: INTRODUCTION
Figure 1-2: Main Menu Hierarchy
1–6845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 17
CHAPTER 1: INTRODUCTIONSECURITY OVERVIEW
Security Overview
The following security features are available:
BASIC SECURITY
The basic security feature is present in the default offering of the 845 relay. The
845 introduces the notion of roles for different levels of authority. Roles are used as login
names with associated passwords stored on the device. The following roles are available
at present: Administrator, Operator, Factory and Observer, with a fixed permission
structure for each one. Note that the Factory role is not available for users, but strictly
used in the manufacturing process.
The 845 can still use the Setpoint access switch feature, but enabling the feature can be
done only by an Administrator. Setpoint access is controlled by a keyed switch to offer
some minimal notion of security.
CYBERSENTRY
The CyberSentry Embedded Security feature is a software option that provides advanced
security services. When the software option is purchased, the Basic Security is
automatically disabled.
CyberSentry provides security through the following features:
•An Authentication, Authorization, Accounting (AAA) Remote Authentication Dial-In
User Service (RADIUS) client that is centrally managed, enables user attribution, and
uses secure standards based strong cryptography for authentication and credential
protection.
•A Role-Based Access Control (RBAC) system that provides a permission model that
device operations and configurations based on specific roles
devices using the Secure Shell (SSH) protocol, the
FASTPATH:
allows access to 845
and individual user accounts configured on the AAA server. At present the defined
roles are: Administrator, Operator and Observer.
•Strong encryption of all access and configuration network messages between the
EnerVista software and 845
Advanced Encryption Standard (AES), and 128-bit keys in Galois Counter Mode (GCM)
as specified in the U.S. National Security Agency Suite B extension for SSH and
approved by the National Institute of Standards and Technology (NIST) FIPS-140-2
standards for cryptographic systems.
•Security event reporting through the Syslog protocol for supporting Security
Information Event Management (SIEM) systems for centralized cyber security
monitoring.
There are two types of authentication supported by CyberSentry that can be used to
access the 845 device:
•Device Authentication – in which case the authentication is performed on the
device itself, using the predefined roles as users (No RADIUS involvement).
845
–845 authentication using local roles may be done either from the front panel or
through EnerVista.
•Server Authentication - in which case the authentication is done on a RADIUS server,
using individual user accounts defined on the server. When the user accounts are
created, they are assigned to one of the predefined roles recognized by the 845
–845 authentication using RADIUS server may be done only through EnerVista.
WiFi and USB do not currently support CyberSentry security. For this reason WiFi is
disabled by default if the CyberSentry option is purchased. The user can enable WiFi, but
be aware that doing so violates the security and compliance model that CyberSentry is
supposed to provide.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL1–7
Page 18
845 ORDER CODESCHAPTER 1: INTRODUCTION
NOTE
When both 845 device and server authentication are enabled, the 845 automatically
directs authentication requests to the 845
device or the respective RADIUS server, based
on user names. If the user ID credential does not match one of the device local accounts,
automatically forwards the request to a RADIUS server when one is provided. If a
the 845
RADIUS server is provided, but is unreachable over the network, server authentication
requests are denied. In this situation, use local 845
system.
845
device accounts to gain access to the
USER ROLES
User Access Levels are used to grant varying permissions to specific user roles. User roles
are used by both Basic Security and CyberSentry.
The following user roles are supported:
•Administrator: The Administrator role has complete read and write access to all
settings and commands. The role does not allow concurrent access. The Administrator
role also has an operand to indicate when it is logged on.
•Operator: The Operator role is present to facilitate operational actions that may be
programmed and assigned to buttons on the front panel. The Operator has read/write
access to all settings under the command menu/section. The Operator can view
settings from EnerVista or the front panel but does not have the ability to change any
settings. This role is not a concurrent role.
•Observer: The Observer role has read-only access to all 845 settings. This role allows
concurrent access. The Observer is the default role if no authentication has been done
to the device. This role can download settings files and records from the device.
•Factory: This is an internal non-user accessible role used for manufacturing
diagnostics. The ability to enable or disable this role is a security setting that the
Administrator controls.
GENERAL RULES FOR USER ROLES WITH CYBERSENTRY
1.The only concurrent role is Observer. If the user is logged in through serial, front panel,
or over the network, that counts as the role being logged in for concurrency reasons.
2.Both EnerVista and the front panel provide a one-step logoff. For the front panel, the
root menu has a logoff command. From EnerVista right-clicking on a device and
providing a logoff function from the context menu is sufficient.
3.The EnerVista Login Screen has “User Name:” and “Password:” fields for the default
remote (Radius) authentication, but when a “Local Authentication” checkbox is
selected the “User Name:” field changes to a drop down menu where the user can
select one of the predefined roles on the 845.
845 Order Codes
NOTE:
NOTE:
1–8845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Support of some of the features described in the "Setpoints" section are order code
dependent. Each 8 Series unit is ordered with a number of required and optional modules.
Each of these modules can be supplied in a number of configurations specified at the time
of ordering.
Refer to https://www.gegridsolutions.com/multilin/catalog/845.htm for available order
code combinations.
The information to specify an 845 relay is provided in the following Order Code figure:
Page 19
CHAPTER 1: INTRODUCTION845 ORDER CODES
845 E ** ** ** * * * A * * * * * * * * * * * * N
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL1–9
Page 20
SPECIFICATIONSCHAPTER 1: INTRODUCTION
892800C5.PDF
Advanced Communications ConnectorN | | |None
S | | |ST, Multi-mode 1310 nm
C | | |RJ45, Copper 10/100M
Wireless CommunicationN | |None
W| | WiFi 802.11
SecurityB |Basic
A |Advanced: CyberSentry Level 1
Future OptionNNot Available
FASTPATH:
FASTPATH:
Harsh Environment Coating is a standard feature on all 8 Series units.
Advanced security is only available with advanced communications (1E, 1P, 2A, 2E, 3A, 3E).
When the advanced communications option is selected, the Ethernet port on the main CPU
is disabled.
Accessories
•18J0-0030 8 Series Depth Reducing Collar - 1 3/8"
•18J0-0029 8 Series Depth Reducing Collar - 3"
Specifications
To obtain the total operating time, i.e. from the presence of a trip condition to initiation of a
trip, add 8
Device
ANNUNCIATOR PANEL
Number of Elements: ........................................ 1 (36 indicators)
Layout:..................................................................... Grid of 2x2 or 3x3
Data Storage:........................................................Non-volatile memory
ANSI Extremely/Very/Normally/Moderately Inverse;
Definite T ime, IEC A/B/C and Short Inverse;
IAC Extremely/Very/Inverse/Short Inverse;
FlexCurve A/B/C/D, I
2
t, I4t
Curve Multiplier:...................................................0.05 to 600.00 in steps of 0.01
ANSI Extremely/Very/Normally/Moderately Inverse
IEC Curve A/B/C and Short Inverse
IAC Extreme/Very/Inverse/Short Inverse
FlexCurve™ A, FlexCurve™ B, FlexCurve™ C, FlexCurve™ D
2
I
t, I4t, Definite Time
Curve Multiplier: ..................................................0.05 to 600.00 in steps of 0.01
Current (for Phase IOC only):......................... Phasor or RMS
Current (for Neutral/Ground IOC only):.....Fundamental Phasor Magnitude
Pickup Level: .........................................................0.050 to 30.000 x CT in steps of 0.001 x CT
Dropout Level:......................................................97 to 98% of Pickup
Level Accuracy: ...................................................For 0.1 to 2.0 x CT: ±0.5% of reading or ±0.4% of rated,
whichever is greater
For > 2.0 x CT: ±1.5% of reading
Operate Time: ......................................................<12 ms typical at 3 × Pickup at 60 Hz (Phase/Ground IOC)
<16 ms typical at 3 × Pickup at 60 Hz (Neutral IOC)
<15 ms typical at 3 × Pickup at 50 Hz (Phase/Ground IOC)
<20 ms typical at 3 × Pickup at 50 Hz (Neutral IOC)
NOTE:
Operating time specifications given above are applicable when RMS inputs are used.
Typical times are average operate times over multiple test cases.
Timer Accuracy:.................................................. ±3% of delay setting or ± ¼ cycle (whichever is greater) from
Breaking Capacity:.............................................For Form-C relays the following ratings are applied to meet
UL508 requirements: 1 second “ON”/10 seconds “OFF” per
output relay at maximum rating
FASTPATH:
For 2 IO_A module configuration the following ratings are applied to meet UL508
requirements: 1 second “on”/ 10 seconds “off” per output relay at max rating.
PULSED OUTPUTS
Mode:........................................................................ 3-phase positive and negative active energy measurement,
Principle: .................................................................Pulsed output is energized for one second and then de-
Power Supply
POWER SUPPLY
Nominal DC Voltage:.........................................125 to 250 V
Minimum DC Voltage:.......................................88 V
Maximum DC Voltage:...................................... 300 V
Nominal AC Voltage:..........................................100 to 240 V at 50/60 Hz
Minimum AC Voltage:........................................88 V at 50 to 60 Hz
Maximum AC Voltage:......................................265 V at 50 to 60 Hz
Voltage loss ride through:...............................20 ms duration
POWER SUPPLY (FOR “L” DC ONLY OPTION)
Nominal DC Voltage:.........................................24 V to 48 V
Minimum DC Voltage:.......................................20 V
Maximum DC Voltage:...................................... 60 V
POWER CONSUMPTION
Typical: ....................................................................20 W / 40 VA
Maximum: ..............................................................34 W / 70 VA
3-phase positive and negative reactive energy
measurements
energized for one second after the programed energy
increment.
1–26845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
IP Address:..............................................................0.0.0.0 – standard Ethernet address
Slave Address: ......................................................254 (1 to 254)
Modbus Port:.........................................................502 (0 to 10000, default 502)
Poll Rate: .................................................................3 minute (OFF, 3 to 120 minutes), the continuous mode poll
interval is defined as the poll rate interval
Trigger:.....................................................................Off (any FlexLogic Operand), the trigger mode is based on
the FlexLogic operand designed to trigger the poll
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL1–27
Page 38
SPECIFICATIONSCHAPTER 1: INTRODUCTION
Testing & Certification
APPROVALS
Applicable Council DirectiveAccording to
CE complianceLow voltage directiveEN60255-27
EMC DirectiveEN60255-26
R&TTE DirectiveETSI EN300 328 ETSI EN301 489-1 ETSI
North AmericacULusUL508, e57838 NKCR, NRGU
ISOManufactured under a registered
TESTING AND CERTIFICATION
TestReference StandardTest Level
Dielectric voltage withstandEN60255-5/IEC60255-272.3 kV
Impulse voltage withstandEN60255-5/IEC60255-275 kV
Insulation resistanceIEC60255-27500 VDC
Damped OscillatoryIEC61000-4-182.5 kV CM, 1 kV DM, 1 MHz
Electrostatic DischargeEN61000-4-2Level 4
RF immunityEN61000-4-3Level 3
Fast Transient DisturbanceEN61000-4-4Class A and B
Surge ImmunityEN61000-4-5Level 3
Conducted RF ImmunityEN61000-4-6Level 3
Power Frequency ImmunityIEC60255-26Class A & B
Voltage variation, interruption and
Ripple DC
Radiated & Conducted Emissions CISPR11 /CISPR22Class A
Sinusoidal VibrationIEC60255-21-1Class 1
Shock & BumpIEC60255-21-2Class 1
SeismicIEC60255-21-3Class 2
Power magnetic ImmunityIEC61000-4-8Level 5
Pulse Magnetic ImmunityIEC61000-4-9Level 4
Damped Magnetic ImmunityIEC61000-4-10Level 4
Voltage Dip & interruptionIEC61000-4-110, 40, 70, 80% dips,
1–28845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 39
CHAPTER 1: INTRODUCTIONSPECIFICATIONS
Make and CarryIEEE C37.9030A /200 ops
Electrostatic Discharge (ESD)IEEE/ANSI C37.90.38kV CD/ 15 kV AD
Product SafetyIEC60255-27As per Normative sections
Rated Burden,IEC60255-1 Sec 6.10
Contact PerformanceIEC60255-1Sec 6.11
Physical
DIMENSIONS
Size: ...........................................................................Refer to Chapter 2
Weight:..................................................................... 9 kg [20.0 lbs]
Environmental
Ambient temperatures:
Storage/Shipping: -40°C to 85°C
Operating: -40°C to 60°C
Humidity:Operating up to 95% (non condensing) @ 55°C (As per
Altitude: 2000m (standard base reference evaluated altitude)
Pollution Degree: II
Overvoltage Category:II
Ingress Protection: IP54 Front
Insulation Class:1
Noise:0 dB
IEC60068-2-30 Variant 2, 6 days)
5000m (maximum achievable altitude)
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL1–29
Page 40
CAUTIONS AND WARNINGSCHAPTER 1: INTRODUCTION
Cautions and Warnings
Before attempting to install or use the device, review all safety indicators in this document
to help prevent injury, equipment damage, or downtime.
Safety words and definitions
The following symbols used in this document indicate the following conditions
DANGER:
Indicates a hazardous situation which, if not avoided, will result in death or serious
injury.
IMPORTANT:
CAUTION:
FASTPATH:
CAUTION:
CAUTION:
CAUTION:
Indicates a hazardous situation which, if not avoided, could result in death or serious
injury.
Indicates a hazardous situation which, if not avoided, could result in minor or
moderate injury.
Indicates practices not related to personal injury.
General Cautions and Warnings
The following general safety precautions and warnings apply.
Before attempting to use the equipment, it is important that all danger and caution
indicators are reviewed.
If the equipment is used in a manner not specified by the manufacturer or functions
abnormally, proceed with caution. Otherwise, the protection provided by the
equipment may be impaired and can result in impaired operation and injury.
Hazardous voltages can cause shock, burns or death.
Installation/service personnel must be familiar with general device test practices,
electrical awareness and safety precautions must be followed.
Before performing visual inspections, tests, or periodic maintenance on this device or
associated circuits, isolate or disconnect all hazardous live circuits and sources of
electric power.
Failure to shut equipment off prior to removing the power connections could expose
you to dangerous voltages causing injury or death.
Ensure that all connections to the product are correct so as to avoid accidental risk of
shock and/or fire, for example from high voltage connected to low voltage terminals.
Follow the requirements of this manual, including adequate wiring size and type,
terminal torque settings, voltage, current magnitudes applied, and adequate isolation/
clearance in external wiring from high to low voltage circuits.
Use the device only for its intended purpose and application.
1–30845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 41
CHAPTER 1: INTRODUCTIONCAUTIONS AND WARNINGS
Ensure that all ground paths are un-compromised for safety purposes during device
operation and service.
All recommended equipment that should be grounded and must have a reliable and
un-compromised grounding path for safety purposes, protection against
electromagnetic interference and proper device operation.
Equipment grounds should be bonded together and connected to the facility’s main
ground system for primary power.
Keep all ground leads as short as possible.
In addition to the safety precautions mentioned all electrical connections made must
respect the applicable local jurisdiction electrical code.
It is recommended that a field external switch, circuit breaker be connected near the
equipment as a means of power disconnect. The external switch or circuit breaker is
selected in accordance with the power rating.
This product itself is not Personal Protective Equipment (PPE). However, it can be used
in the computation of site specific Arc Flash analysis when the arc flash option is
ordered. If a new appropriate Hazard Reduction Category code for the installation is
determined, user should follow the cautions mentioned in the arc flash installation
section.
follow the cautions mentioned in the arc flash installation section.If a new appropriate Har
The critical fail relay must be connected to annunciate the status of the device when
the Arc Flash option is ordered.
Ensure that the control power applied to the device, the AC current, and voltage input
match the ratings specified on the relay nameplate. Do not apply current or voltage in
excess of the specified limits.
Only qualified personnel are to operate the device. Such personnel must be thoroughly
familiar with all safety cautions and warnings in this manual and with applicable
country, regional, utility, and plant safety regulations.
Hazardous voltages can exist in the power supply and at the device connection to
current transformers, voltage transformers, control, and test circuit terminals. Make
sure all sources of such voltages are isolated prior to attempting work on the device.
Hazardous voltages can exist when opening the secondary circuits of live current
transformers. Make sure that current transformer secondary circuits are shorted out
before making or removing any connection to the current transformer (CT) input
terminals of the device.
For tests with secondary test equipment, ensure that no other sources of voltages or
currents are connected to such equipment and that trip and close commands to the
circuit breakers or other switching apparatus are isolated, unless this is required by
the test procedure and is specified by appropriate utility/plant procedure.
When the device is used to control primary equipment, such as circuit breakers,
isolators, and other switching apparatus, all control circuits from the device to the
primary equipment must be isolated while personnel are working on or around this
primary equipment to prevent any inadvertent command from this device.
Use an external disconnect to isolate the mains voltage supply.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL1–31
Page 42
CAUTIONS AND WARNINGSCHAPTER 1: INTRODUCTION
CAUTION:
FASTPATH:
FASTPATH:
LED transmitters are classified as IEC 60825-1 Accessible Emission Limit (AEL) Class
1M. Class 1M devices are considered safe to the unaided eye. Do not view directly with
optical instruments.
To ensure the settings file inside the relay is updated, wait 30 seconds after a setpoint
change before cycling power.
This product is rated to Class A emissions levels and is to be used in Utility, Substation
Industrial environments. Not to be used near electronic devices rated for Class B levels.
1–32845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 43
CHAPTER 1: INTRODUCTIONMUST-READ INFORMATION
Must-read Information
The following general statements apply and are repeated in the relevant sections of the
manual.
FASTPATH:
•WiFi and USB do not currently support CyberSentry security. For this reason WiFi is
disabled by default if the CyberSentry option is purchased. The user can enable WiFi,
but be aware that doing so violates the security and compliance model that
CyberSentry is supposed to provide.
•Before upgrading firmware, it is very important to save the current 845 settings to a
file on your PC. After the firmware has been upgraded, it is necessary to load this file
back into the 845.
•The SNTP, IRIG-B and PTP settings take effect after rebooting the relay.
•Commands may be issued freely through other protocols than Modbus (i.e., DNP, IEC
104, and, IEC 61850) without user authentication or encryption of data taking place,
even if the relay has the advanced security feature enabled.
•Note that the factory role password may not be changed.
•In 845 both DNP and IEC104 protocol can work at the same time, but the user has to
consider that there is only one point map. So, both protocols use the same configured
points.
•The 52b contact is closed when the breaker is open and open when the breaker is
closed.
•The Phase Directional element responds to the forward load current. In the case of a
following reverse fault, the element needs some time – in the order of 8 ms – to
change the directional signal. Some protection elements such as Instantaneous
Overcurrent may respond to reverse faults before the directional signal has changed.
A coordination time of at least 10 ms must therefore be added to all the instantaneous
protection elements under the supervision of the Phase Directional element. If current
reversal is a concern, a longer delay – in the order of 20 ms – is needed.
•The same curves used for the time overcurrent elements are used for Neutral
Displacement. When using the curve to determine the operating time of the Neutral
Displacement element, substitute the ratio of neutral voltage to Pickup level for the
current ratio shown on the horizontal axis of the curve plot.
•If the 3-phase VT uses a delta connection and FREQUENCY INPUT is set to J2-3VT, the
positive sequence voltage is used as the supervision voltage. In such condition, the
true supervision level is internally changed to 1/sqrt(3) of the user setting since the
base of VT here is the phase-phase voltage.
•To monitor the trip coil circuit integrity, use the relay terminals “FA_1 NO” and “FA_1
COM” to connect the Trip coil, and provide a jumper between terminals “FA_1 COM”
and “FA_1 OPT/V” voltage monitor).
•In Power factor monitoring, SWITCH-IN and SWITCH-OUT are mutually exclusive
settings.
•The relay is not approved as, or intended to be, a revenue metering instrument. If used
in a peak load control system, the user must consider the accuracy rating and
method of measurement employed, and the source VTs and CTs, in comparison with
the electrical utility revenue metering system.
•In bulk oil circuit breakers, the interrupting time for currents is less than 25% of the
interrupting rating and can be significantly longer than the normal interrupting time.
•For future reference, the user is advised to take a printout of the conversion report
immediately after the conversion. All conversion reports are removed and become
inaccessible if the user closes or re-launches the 8 Series Setup software.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL1–33
Page 44
FOR FURTHER ASSISTANCECHAPTER 1: INTRODUCTION
Storage
Store the unit indoors in a cool, dry place. If possible, store in the original packaging. Follow
the storage temperature range outlined in the Specifications.
Use the factory-provided dust caps on all Arc Flash sensor fiber and connectors when not
in use, to avoid dust contamination in the transceiver and sensor plugs.
For Further Assistance
For product support, contact the information and call center as follows:
The firmware and software can be upgraded without return of the device to the factory.
For issues not solved by troubleshooting, the process to return the device to the factory for
repair is as follows:
•Contact a GE Grid Solutions Technical Support Center. Contact information is found in
the first chapter.
•Obtain a Return Materials Authorization (RMA) number from the Technical Support
Center.
•Verify that the RMA and Commercial Invoice received have the correct information.
•Tightly pack the unit in a box with bubble wrap, foam material, or styrofoam inserts or
packaging peanuts to cushion the item(s). You may also use double boxing whereby
you place the box in a larger box that contains at least 5 cm of cushioning material.
•Ship the unit by courier or freight forwarder, along with the Commercial Invoice and
RMA, to the factory.
•Customers are responsible for shipping costs to the factory, regardless of whether the
unit is under warranty.
•Fax a copy of the shipping information to the GE Grid Solutions service department .
1–34845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 45
GE
LISTED
C
US
L
U
E57838
IND. CONT. EQ.
2D58
R
MADE IN
CANADA
7UDQVIRUPer Protection System
Model: 85-EP5NNG5HNNANNGSSBSNNNB
Serial Number: MJAXXXXXXX
POWER SUPPLY RATINGS:
Nominal: 100 to 240V 125 to 250V
Range: 88 to 265V (50/60Hz) 88 to 300V
Power Consumption: 20W Typ, 34W/70VA Max
Input /Output Ratings: Refer to Manual
Instruction Manual: GEK-11951
Pollution Degree 2 / Degré de pollution 2
Technical Support:
Worldwide: +1 905 927 7070
North America: 1 800 547 8629
www.gegridsolutions.com/multilin/
650 Markland Street, Markham
ON, Canada L6C 0M1
MFG. Date: Mar. 11, 2016
g
~
~
Multilin 85
g
!&%%+
!&%%
Grid Solutions
845 Transformer Protection System
Chapter 2: Installation
Mechanical Installation
Installation
This section describes the mechanical installation of the system, including dimensions for
mounting and information on module withdrawal and insertion.
Product Identification
The product identification label is located on the side panel of the 845. This label indicates
the product model, serial number, and date of manufacture.
Figure 2-1: Product Label
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL2–1
Page 46
MECHANICAL INSTALLATIONCHAPTER 2: INSTALLATION
>@
>@
>@
>@
>@
>@
Dimensions
The dimensions (in inches [millimeters]) of the 845 are shown below. Additional dimensions
for mounting, and panel cutouts, are shown in the following sections.
Figure 2-2: 845 Dimensions
2–2845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 47
CHAPTER 2: INSTALLATIONMECHANICAL INSTALLATION
Needle nose pliers
Mounting
The unit can be mounted two ways: standard panel mount or optional tab mounting, if
required.
•Standard panel mounting:
From the front of the panel, slide the empty case into the cutout. From the rear of the
panel, screw the case into the panel at the 8 screw positions (see figures in Standard
panel mount section).
•Optional tab mounting:
The “V” tabs are located on the sides of the case and appear as shown in the following
figure. Use needle nose pliers to bend the retaining "V" tabs outward to about 90°. Use
caution and do not bend and distort the wall of the enclosure adjacent to the tabs. The
relay can now be inserted and can be panel wired.
Figure 2-3: “V” Tabs Located on Case Side
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL2–3
Page 48
MECHANICAL INSTALLATIONCHAPTER 2: INSTALLATION
Standard Panel MountThe standard panel mount and cutout dimensions are illustrated below.
CAUTION:
To avoid the potential for personal injury due to f ire hazards, ensure the unit is
mounted in a safe location and/or within an appropriate enclosure.
Figure 2-4: Standard panel mount
Figure 2-5: Panel cutout dimensions
2–4845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 49
CHAPTER 2: INSTALLATIONMECHANICAL INSTALLATION
10.40
A
9.00
7.25
GE PN'A' DEPTH
1009-0310 1 3/8"
1009-0311 3"
Dimensions in inches
8.73
892703A1.dwg
7.25
9.00
3.863.86
3.85
3.85
4.74
4.74
8X
.220
Dimensions in inches
892703A1.dwg
Depth Reducing CollarTwo different sizes of optional depth reducing collar are available for mounting relays in
narrow-depth service panels, or wherever space is an issue.
NOTE:
The drill hole locations are different when a depth reducing collar is used. See Figure 2-
7:Depth reducing collar panel cutout.
•18J0-0030 8 Series Depth Reducing Collar - 1 3/8"
•18J0-0029 8 Series Depth Reducing Collar - 3"
Figure 2-6: Depth reducing collar dimensions
Figure 2-7: Depth reducing collar panel cutout
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL2–5
Page 50
MECHANICAL INSTALLATIONCHAPTER 2: INSTALLATION
DEPTH REDUCING COLLAR
GE PART# 1009-0311 3IN (76.2MM) DEPTH
GE PART# 1009-0310 1.375IN (34.9MM) DEPTH
8 SERIES UNIT
8-32x3/8IN P/HD PHIL BLK
GE PART# 1408-0306 (qty:16)
Tightening Torque: 15 in lb (1.7 Nm)
892703A1.dwg
Figure 2-8: Depth reducing collar installation
To mount an 8 Series relay with a depth reducing collar, follow these steps:
1. Drill mounting holes as shown on the panel cutout drawing (Figure 2-7:Depth
2. Mount the required collar (depth 1.375" or 3") on the captive unit using eight screws as
3. Mount the combined unit and collar on the panel using eight screws as shown.
reducing collar panel cutout).
shown.
2–6845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Unit withdrawal and insertion may only be performed when control power has been
removed from the unit .
FASTPATH:
Turn off control power before drawing out or re-inserting the relay to prevent maloperation.
Follow the steps outlined in the diagrams below to insert and withdraw the Draw-out unit.
Figure 2-9: Unit withdrawal and insertion diagram
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL2–7
Page 52
MECHANICAL INSTALLATIONCHAPTER 2: INSTALLATION
Removable Power Supply
Follow the steps outlined in the Insert or Remove Power Supply diagram to insert (#1) or
remove (#2) the power supply from the unit.
Figure 2-10: Insert or Remove the Power Supply
Figure 2-11: Unlatch Module (location is marked by arrow)
2–8845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 53
CHAPTER 2: INSTALLATIONMECHANICAL INSTALLATION
Removable Magnetic Module
Follow the steps outlined in the diagram below to insert or remove the magnetic module
from the unit.
Figure 2-12: Insert or Remove the Magnetic Module
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL2–9
Page 54
MECHANICAL INSTALLATIONCHAPTER 2: INSTALLATION
Arc Flash Sensor
The Arc Flash sensor houses the fiber optics and membrane that are used to detect the arc
flash. Two mounting screw holes are provided to affix the sensors to the panel.
CAUTION:
Sensor Fiber Handling
& Storage
CAUTION:
If the 8 Series is used in the computation for reducing the Hazard Reduction Category
code, operands for sensor failures must be assigned to an auxiliary output relay which
must be connected into the control logic of the breaker equipment to ensure safe
operations when the output relay is asserted. In the event of this assertion, the Hazard
Reduction Category code cannot be maintained unless backup protection is continuing
to maintain it.
Arc Flash sensor fiber is pressure sensitive and must be handled carefully to avoid
damage. Read the following guidelines fully before proceeding.
Care must be taken when handling the Arc Flash sensor fiber, which can be damaged if
twisted, bent, or clamped tightly during installation.
•Do not bend sensor fiber sharply, or with a radius of less than 25 mm (1 inch). Sharp
bends can damage the fiber. Do not pull or tug loops of sensor fiber, as sharp bends
may result.
•Do not clamp sensor fiber tightly during installation. Sensor fiber should be held in
place loosely for the best long-term performance. Avoid over-tightening ties which
may deform or break the sensor fiber.
•Do not pull or tug sensor fiber with force, as this may cause internal damage or
separate the fiber from the cable connector.
•Do not twist the sensor fiber, as twisting can damage the fiber resulting in
substandard performance.
•Do not attach sensor fiber directly to the bus.
•Avoid surface temperatures above 70 °C or 158 °F to prolong the life of the fiber.
•Secure all sensor fibers (loosely but securely) away from any moving parts.
•Use the factory-provided dust caps on all Arc Flash sensor fiber and connectors when
not in use, to avoid dust contamination in the transceiver and sensor plugs.
Sensor InstallationFigure 2-13: AF Sensor - front, side and top view
FASTPATH:
2–10845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Review the sensor fiber handling guidelines above.
Page 55
CHAPTER 2: INSTALLATIONELECTRICAL INSTALLATION
Sensor fiber should be held in place loosely for the best long-term performance. Avoid
over-tightening ties which may deform or break the sensor fiber.
Before installing the AF sensor unit, ensure that all other drilling and installation is
complete to minimize possible damage to the sensitive unit .
To install the AF sensor and route the sensor fiber, follow these steps:
1.Choose a location for the sensor clear of any obstructions that could shield the sensor
from arc flash light.
2.Mount the sensor securely, using the mounting screw holes.
3.Once the sensor is securely mounted, carefully route the sensor fiber from the AFS
sensor to the base unit, minimizing loops and curves for the strongest possible signal.
4.Secure all sensor fibers (loosely but securely) away from any moving parts.
FASTPATH:
Both the AF sensor connections (CH 1 through CH 4) and the sensor cables are shipped
with dust caps in place to avoid dust contamination. The small rubber dust caps must
be removed before operation.
Electrical Installation
Typical Wiring Diagrams
The following illustrates the electrical wiring of the Draw-out unit.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL2–11
* SLOT H I/O_A IS AVAILABLE WHEN SLOT G IS WITH I/O_L
ANY MEASURED OR
METERED ANALOG PARAMETER
INPUTS
SLOT A
TRIP W1 BKR
TRIP
COIL
52b
52a
+
-
-
+
CIRCUIT
CLOSE W1 BKR
CIRCUIT
COIL
52b
52a
52b
52a
W1 BREAKER
W2 BREAKER
BCD DECODER
TRIP W2 BKR
TRIP
COIL
52a
52a
+
-
-
+
CIRCUIT
TRIP W3 BKR
CIRCUIT
TRIP
COIL
OHMS
INPUT
CABLE SHIELD TO BE GROUNDED
AT PLC/COMPUTER END ONLY
A
C
B
LTC TAP
POSITION
IF OHMS
INPUT
SHIELD
PHASE CTs
PHASE CTs
52b
52a
W3 BREAKER
SLOT D
SLOT E
Figure 2-17: Typical Wiring Diagram for a 3-Winding Transformer
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL2–15
892789A2
Page 60
ELECTRICAL INSTALLATIONCHAPTER 2: INSTALLATION
NOTE
SCREW
WASHER
LOWER
TERMINAL
DIVIDER
TERMINAL
BLOCK
1
2
3
Terminal Identif ication
All the terminal strips are labeled with a slot letter to identify the module slot position and
numbers to identify the terminals within the module.
CAUTION:
NOTE:
Make sure that the first letter on the terminal strip corresponds to the slot location
identified on the chassis silkscreen.
Terminal Connections
When installing two lugs on one terminal, both lugs must be “right side up” as shown in the
picture below. This is to ensure the adjacent lower terminal block does not interfere with
the lug body.
Figure 2-18: Orient the Lugs Correctly
Figure 2-19: Correct Installation Method
2–16845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
A broad range of applications are available for the 845 relays. As such, it is not possible to
present typical connections for all possible schemes. The information in this section covers
the important aspects of interconnections, in the general areas of instrument transformer
inputs, other inputs, outputs, communications and grounding. The figure below shows the
rear terminal layout of the 845
Platform.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL2–17
Page 62
ELECTRICAL INSTALLATIONCHAPTER 2: INSTALLATION
AB
C
D
K
J
PORT 1
F
G
H
1
2
345
6
7
8910
2
3
1
2
345
6
7
8910
11
12131415161718
12
345
6
7
89101112131415161718192021222324
123456789101112131415161718192021222324
123456789101112131415161718192021222324
1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
345
6
7
8910
11
12131415161718
Tx4
Rx4
Tx5
Rx5
PORT 5
PORT 4
E
BASIC
COMMS
I/OPSU
ADV
COMMS
AC ANALOG INPUTS
BANK - J2
BANK - K2
BANK - K1
BANK - J1
I/O
Figure 2-21: Rear Terminal Layout of the 8 Series Platform
Table 2-1: Power Supply
H - HV Power Supply
TerminalDescription
1Line
2Neutral
3Ground
2–18845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Wire SizeUse the following guideline when selecting wires or lugs to connect to terminal strips A, B,
C, D, E, F, G, H, and terminal blocks J, K. Note that the first two bullets are applicable to
terminal blocks J and K only:
•12 AWG to 22 AWG (3.3 mm2 to 0.3 mm2): Single wire termination with/without 9.53
mm (0.375”) maximum diameter ring terminals.
•14 AWG to 22 AWG (2.1 mm2 to 0.3 mm2): Multiple wire termination with 9.53 mm
(0.375”) maximum diameter ring terminals. Two ring terminals maximum per circuit.
•Suggested wiring screw tightening torques are: terminal strips A-H tighten to 4.5 in-lbs
(0.5 N-m) and terminal blocks J, K to 15 in-lb (1.7 N-m).
Figure 2-22: Fiber Connector Types (S - ST)
2–20845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 65
CHAPTER 2: INSTALLATIONELECTRICAL INSTALLATION
892773A2.cdr
8 Series
J1
J2
J3
J4
J5
J7J6J8J7 J8J8 J7
Phase Sequence and Transformer Polarity
For correct operation of the relay features, follow the instrument transformer polarities,
shown in the Typical Wiring Diagram above. Note the solid square markings that are
shown with all instrument transformer connections. When the connections adhere to the
drawing, the arrow shows the direction of power flow for positive watts and the positive
direction of vars. The phase sequence is user programmable for either ABC or ACB rotation.
The 845 relay has four (4) current inputs in each J slot and K slot. Three of them are used
for connecting to the phase CT phases A, B, and C. The fourth input is a ground input that
can be connected to either a ground CT placed on the neutral from a Wye connected
transformer winding, or to a “donut” type CT measuring the zero sequence current from a
grounded system. The relay CTs are placed in a packet mounted to the chassis of the
relay. There are no internal ground connections on the current inputs. Current
845
transformers with 1 to 12000 A primaries may be used.
CAUTION:
Verify that the relay’s nominal input current of 1 A or 5 A matches the secondary rating
of the connected CTs. Unmatched CTs may result in equipment damage or inadequate
protection.
CAUTION:
IMPORTANT: The phase and ground current inputs correctly measure up to 46 times the
current input’s nominal rating. Time overcurrent curves become horizontal lines for
currents above 20 × PKP.
Ground CT Inputs
Before making ground connections, be aware that the relay automatically calculates the
neutral (residual) current from the sum of the three phase current phasors. The following
figures show three possible ground connections using the ground current input (Terminals
J7 and J8).
The ground input (Terminals J7 and J8) is used in conjunction with a Zero Sequence CT as
source, or in the neutral of wye-connected source CTs. The ground current input can be
used to polarize the neutral. When using the residual connection, set the
GROUND
Figure 2-23: Ground Inputs
CT PRIMARY setpoint to a value equal to the PHASE CT PRIMARY setpoint.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL2–21
Page 66
ELECTRICAL INSTALLATIONCHAPTER 2: INSTALLATION
892776A3.CDR
TO BUS VTs
A
C
B
J15
AUX
J16
VV
12
2V1
V
AUX
J15 J16
Van
Vab
52
TO BUS VTs
A
C
B
J15
AUX
J16
VV
12
Vbn
52
TO BUS VTs
A
C
B
J15
AUX
J16
VV
12
Vcn
52
TO BUS VTs
A
C
B
52
2V1
V
AUX
J15 J16
Vbc
TO BUS VTs
A
C
B
52
2V1
V
AUX
J15 J16
Vca
TO BUS VTs
A
C
B
52
J1 J2 J3 J4 J5 J6 J7 J8
CURRENT INPUTS
PHASE A PHASE B PHASE C
GROUND
I
A
N
I
C
I
B
I
G
NN
N
FEEDER
TRANSFORMER
892775A1.cdr
Voltage Inputs
The 845 relays have four channels for AC voltage inputs, each with an isolating
transformer. Voltage transformers up to a maximum 5000:1 ratio may be used. The
nominal secondary voltage must be in the 10 to 240 V range. The Bus VT connections most
commonly used, wye and delta (or open delta), are shown in the typical wiring diagram.
The single Auxiliary voltage input is commonly used as the “line voltage”. The line VT input
channel, used for the synchrocheck feature, can be connected for phase-neutral voltages
, Vbn, or Vcn; or for phase-phase voltages Vab, Vbc, or Vca as shown.
V
an
Figure 2-24: Line VT Connections
CAUTION:
If Delta VTs are used for three-phase voltages, the zero sequence voltage (V0) and
neutral ground polarizing voltage (–V0) are zero. Also, with the Delta VT connection, the
phase-neutral voltage cannot be measured and is not displayed.
Restricted Earth Fault Inputs
Restricted Earth Fault protection is often applied to transformers having grounded Wye
windings to provide ground fault detection for faults near the transformer neutral. Each
current bank on the relay has 3 phase current inputs and one ground input. Any of the
available inputs on the relay current banks can be selected as a signal input for an RGF
element.
The phase and ground input CT connections to the relay are shown below:
Figure 2-25: Restricted Ground Fault Inputs
2–22845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 67
CHAPTER 2: INSTALLATIONELECTRICAL INSTALLATION
Ground connection to neutral
must be on the source side
UNSHIELDED CABLE
LOAD
ABCNG
Ground
outside CT
Source
LOAD
SHIELDED CABLE
996630A5
AB C
Source
To ground;
must be on
load side
Stress cone
shields
Zero-Sequence CT Installation
The figure below shows the various CT connections and the exact placement of a Zero
Sequence current CT, so that ground fault current can be detected. Twisted pair cabling on
the Zero Sequence CT is recommended.
Figure 2-26: Zero Sequence (Core Balance) CT Installation
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL2–23
Page 68
ELECTRICAL INSTALLATIONCHAPTER 2: INSTALLATION
Control Power
Control power is supplied to the relay such that it matches the relay’s installed power
supply range.
CAUTION:
CAUTION:
Control power supplied to the relay must match the installed power supply range. If the
applied voltage does not match, damage to the unit may occur. All grounds MUST be
connected for normal operation regardless of control power supply type.
For more details, please refer to the Power Supply subsection located in the Introduction
chapter.
The relay should be connected directly to the ground bus, using the shortest practical
path. A tinned copper, braided, shielding and bonding cable should be used. As a
minimum, 96 strands of number 34 AWG should be used. Belden catalog number 8660
is suitable.
Figure 2-27: Control Power Connection
FASTPATH:
Contact Inputs
Depending on the order code, the 845 relay has a different number of contact inputs which
can be used to operate a variety of logic functions for circuit switching device control,
external trips, blocking of protection elements, etc. The relay has ‘contact inputs’ and
‘virtual inputs’ that are combined in a form of programmable logic to facilitate the
implementation of various schemes.
The voltage threshold at which the contact inputs detect a closed contact input is
programmable as 17 V DC for 24 V sources, 33 V DC for 48 V sources, 84 V DC for 110 to
125 V sources, and 166 V DC for 250 V sources.
Wet or Dry input signal types can be connected to contact input terminals as shown in the
figure: Wet and Dry Contact Input Wiring Examples.
Dry inputs use an internal +24V that is supplied by the 845. The voltage threshold must be
set to 17V for the inputs to be recognized using the internal +24V.
The same type of input signal must be connected to all contact inputs on the same contact
input card.
2–24845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 69
CHAPTER 2: INSTALLATIONELECTRICAL INSTALLATION
INPUT
SIGNAL
SWITCH
(DRY)
INPUT
SIGNAL
SWITCH
(WET)
EXTERNAL
DC POWER
SUPPLY
Figure 2-28: Wet and Dry Contact Input Wiring Examples
Output Relays
The locations of the output relays have a fixed assignment for the platform called the
master identifier. I/O options that include inputs occupy the fixed assigned output
locations so in these cases the relay assignment maps to the master identifier.
The output relays for the 845 relay are fully programmable, and can be assigned in the
transformer breakers menu for breaker tripping or closing. The output relays assigned for
breaker closing, are automatically excluded from the menus for output selection for the
rest of the elements.
The critical failure output relay is reserved as Relay_8 and it is omitted and is not
programmable.
One two-wire RS485 port is provided. Up to thirty-two 8 Series IEDs can be daisy-chained
together on a communication channel without exceeding the driver capability. For larger
systems, additional serial channels must be added. Commercially available repeaters can
also be used to add more than 32 relays on a single channel. Suitable cable should have a
characteristic impedance of 120 ohms and total wire length should not exceed 1200
meters (4000 ft).
Voltage differences between remote ends of the communication link are not uncommon.
For this reason, surge protection devices are internally installed across all RS485
terminals.Internally, an isolated power supply with an opto-coupled data interface is used
to prevent noise coupling.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL2–27
Page 72
ELECTRICAL INSTALLATIONCHAPTER 2: INSTALLATION
SCADA, PLC, OR
PERSONAL COMPUTER
COM
ISOLATION
DATA
8-Series IED
SHIELD
892780A4.CDR
UP TO 32, 8-Series
OR OTHER IEDs,
MAXIMUM CABLE
LENGTH OF
1200 m (4000 ft.)
LAST
DEVICE
(*) TERMINATING IMPEDANCE AT EACH END
(typically 120 ohms and 1 nF)
TWISTED PAIR
Z (*)
T
RS485 +
RS485 -
COMMON
RS485 +
RS485 -
COMMON
IED
RS485 +
IED
RS485 -
COMMON
GROUND THE SHIELD AT THE
SCADA/PLC/COMPUTER ONLY
OR THE 8-Series ONLY
DATA
ISOLATION
D3
D4
D5
Z (*)
T
Figure 2-29: RS485 wiring diagram
CAUTION:
To ensure that all devices in a daisy-chain are at the same potential, it is imperative
that the common terminals of each RS485 port are tied together and grounded only
once, at the master or at the 845. Failure to do so may result in intermittent or failed
communications.
The source computer/PLC/SCADA system should have similar transient protection devices
installed, either internally or externally. Ground the shield at one point only, as shown in
the figure above, to avoid ground loops. Correct polarity is also essential. The 845
IEDs
must be wired with all the positive (+) terminals connected together and all the negative (–)
terminals connected together. Each relay must be daisy-chained to the next one. Avoid
star or stub connected configurations. The last device at each end of the daisy-chain
should be terminated with a 120 ohm ¼ watt resistor in series with a 1 nF capacitor across
the positive and negative terminals. Some systems allow the shield (drain wire) to be used
as a common wire and to connect directly to the COM terminal; others function correctly
only if the common wire is connected to the COM terminal, but insulated from the shield.
Observing these guidelines ensure a reliable communication system immune to system
transients.
2–28845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 73
CHAPTER 2: INSTALLATIONELECTRICAL INSTALLATION
GE MULTILIN
8-SERIES
IRIG-B(-)
RECEIVER
TO OTHER DEVICES
SHIELDED CABLE
GPS SATELLITE SYSTEM
GPS CONNECTION
OPTIONAL
IRIG-B(+)
D1
D2
+
–
892781A3.CDR
IRIG-B
TIME CODE
GENERATOR
(DC SHIFT OR
AMPLITUDE MODULATED
SIGNAL CAN BE USED)
IRIG-B
IRIG-B is a standard time code format that allows time stamping of events to be
synchronized among connected devices within 1 millisecond. The IRIG-B time code
formats are serial, width-modulated codes which can be either DC level shift or amplitude
modulated (AM) form. The type of form is auto-detected by the 845
equipment is available for generating the IRIG-B signal; this equipment may use a GPS
satellite system to obtain the time reference so that devices at different geographic
locations can also be synchronized.
Figure 2-30: IRIG-B connection
relay. Third party
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL2–29
Page 74
ELECTRICAL INSTALLATIONCHAPTER 2: INSTALLATION
2–30845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 75
GE
Grid Solutions
845 Transformer Protection System
Chapter 3: Interfaces
Interfaces
There are two methods of interfacing with the 845.
•Interfacing via the relay keypad and display.
•Interfacing via the EnerVista 8 Series Setup software.
This section provides an overview of the interfacing methods available with the 845 using
the relay control panel and EnerVista 8 Series Setup
interface parameters (for example, settings, actual values, etc.), refer to the individual
chapters.
FIRST ACCESSING THE RELAY
When first accessing the relay, log in as Administrator either through the front panel or
through EnerVista connected serially (so that no IP address is required). Use the default
password (the default password is “0”).
Basic Security
If the relay is in the commissioning phase and you want to bypass authentication, switch
the “Setpoint access” setting on or assign it to a contact input. Once the setting is on, you
have complete administrator access from the front panel. If a contact input is chosen, the
access is also conditional on the activation of the respective contact input.
For more information on setpoint access and other security features available with basic
security, refer to the Basic Security section in the Setpoints chapter.
CyberSentry
If logging in through EnerVista, choose Device authentication and login as Administrator.
Note: If the relay is in the commissioning phase and the user wants to bypass
authentication, the user may use the setpoint access feature to gain administrative access
to the front panel in the same way as with basic security (see the “Basic Security” section).
For more information on security features available with CyberSentry, refer to the
CyberSentry security section in the Setpoints chapter.
software. For additional details on
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL3–1
Page 76
FRONT CONTROL PANEL INTERFACECHAPTER 3: INTERFACES
ESCAPE
ENTERHELP
IN SERVICE
TRIP
ALARM
PICK UP
XFMR OVERLOAD
LOAD-LIMIT REDUCED
XFMR DE-ENERGIZED
CLOSE
RESET
OPENF1
W1 BKR OPEN
W2 BKR CLOSED
LOCAL MODE
DIFFERENTIAL BLOCKED
TARGETSSTATUSMETERING SETPOINTSRECORDS
Navigation
Pushbuttons
Menu tabs associated
with pushbuttons for
screens navigation
Pushbuttons for
setpoints, and Up/ Down
value selections
“HELP”:help with
setting selection
“ESCAPE”:return to
previous menu
“Home”:return to
default screen
“ENTER”: enter selected
setting
“RESET”: reset targets,LEDs,
output relays
LEDs #1and LED #4(non-
programmable)
LED#2,LED#3,
and LEDs 5 to 14
(programmable)
Function PBs with LEDs
(programmable)
USB port
Display
LED labels
TEST MODE
MESSAGE
W3 BKR CLOSED
Front Control Panel Interface
The relay provides an easy to use faceplate for menu navigation using 5 navigation
pushbuttons and a high quality graphical display. Conveniently located on the panel is a
group of 7 pushbuttons for Up/Down value selection, Enter, Home, Escape, Help, and Reset
functions. The faceplate also includes 3 programmable function pushbuttons with LEDs.
Fourteen other status LEDs are available, 12 of which are programmable.
Figure 3-1: Front Control Panel
Figure 3-2: 845 Front Control Panel)
3–2845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
The USB port is intended for connection to a portable computer.
845 Graphical Display Pages
The front panel liquid crystal display (LCD) allows visibility under varied lighting conditions.
When the keypad and display are not being used, system information is displayed after a
user-defined period of inactivity. Pressing the Menu key during the display of the default
message, returns the display to the last message shown before the default message
appeared. Any Trip, Alarm, or Pickup is displayed immediately, automatically overriding
the default message.
Page 77
Setpoints
Device
System
Inputs
Outputs
Protection
Monitoring
Control
FlexLogic
S
tatus
Switches
Contact Inputs
Metering
Summary
Currents
Voltages
Frequency
Harmonics
Power
Energy
Current Demand
Records
Events
Fault Reports
Breakers
Remote Modbus Device
Targets
Directional Power
Data Logger
Volts per Hertz
Digital Counters
RTDs
RTD Maximums
FlexElements
Arc Flash
Syncrocheck
Testing
Output Relays
Virtual Inputs
Information
Device Status
Clock
Arc Flash
Virtual Outputs
Communications
PTP Status
Flex States
Last Trip Data
Breakers
Summary
Transformer
Harmonic Magnitude
Transients
Clear Records
Power Factor
Analog Inputs
CHAPTER 3: INTERFACESFRONT CONTROL PANEL INTERFACE
Figure 3-3: 845 Display Page Hierarchy
Working with
Graphical Display
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL3–3
Pages
The display contains five main menu items labeled Targets, Status, Metering, Setpoints,
and Records located at the bottom of the screen. Choosing each main menu item displays
the corresponding sub-menu.
Page 78
FRONT CONTROL PANEL INTERFACECHAPTER 3: INTERFACES
TARGETSSTATUSMETERING
SETPOINTS
RECORDS
Figure 3-4: Typical paging operation from the Main Menu
3–4845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
There are two ways to navigate throughout the 845 menu: using the pushbuttons
corresponding to the soft tabs from the screen, or by selecting the item from the list of
items on the screen using the “Up” and “Down” pushbuttons to move the yellow
highlighted line, and pressing the pushbutton “Enter”.
Figure 3-5: Tab Pushbuttons
The tab pushbuttons are used to enter the menu corresponding to the label on the tabs. If
more than 5 tabs exist, the first and the last tab are labelled with arrows to allow you to
scroll to the other tabs.
Page 79
CHAPTER 3: INTERFACESFRONT CONTROL PANEL INTERFACE
<<NIOC 2NIOC 3
NIOC 4
>>
ENTER
Figure 3-6: Keypad Pushbuttons
Each Keypad pushbutton serves the following function:
The Home pushbutton is used to display the home screen, and all screens defined under
the Front Panel/Screens menu as default screens.
The Enter pushbutton has a dual function. It is used to display a sub-menu when an item is
highlighted. It is also used to save the desired value for any selected setpoint.
The Up, and Down pushbuttons are used to select/highlight an item from a menu, as well
as select a value from the list of values for a chosen item.
The Up, Down, Left, and Right pushbuttons on the membrane faceplate are used to move
the yellow highlight. These pushbuttons are also used on special screens to navigate to
multiple objects.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL3–5
Page 80
FRONT CONTROL PANEL INTERFACECHAPTER 3: INTERFACES
ESCAPE
RESET
The Escape pushbutton is used to display the previous menu. This pushbutton can also be
used to cancel a setpoint change.
The Reset pushbutton clears all latched LED indications, target messages, and latched
output relays, providing the conditions causing these events are not present.
To change (or view) an item on (or from) the 845 menus:
1.Use the pushbuttons that correspond to the tabs (Targets, Status, Metering, Setpoints,
Records) on the screen to select a menu.
2.Use the Up and Down pushbuttons to highlight an item.
3.Press Enter to view a list of values for the chosen item. (Some items are view-only.)
4.Use the Up and Down pushbuttons to highlight a value.
5.Press Enter to assign the highlighted value to the item.
Single Line DiagramBKR1 LED setting for Breaker symbol color configuration
In all 8 Series devices the Breaker symbol color is configurable as per the color scheme
setting in
Setpoints > Device > Front Panel > Display Properties > Color Scheme.
Single Line Diagram for 845 and Breaker/Transformer status color
The 845 has a single line diagram (SLD) that represents the power system. The single line
diagram provided is pre-configured to show:
•Breaker status
•AC input connection
•Rated Winding voltage
Accompanying the single line diagram are typical metered values associated with the
power system.
The single line diagram is configured as the default menu but this can be changed under
Setpoints > Device > Front Panel > Default Screen.
Figure 3-7: SLD and typical metered values screen
The breaker status icon changes state according to the breaker status input and the color
scheme setting (
Setpoints > Device > Front Panel > Display Properties > Color Scheme) to
show Breaker status.
The winding voltage setting for each breaker is displayed on the associated branch. The
winding configuration icon will display either a 2-winding or 3-winding transformer based
on the order code.
3–6845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 81
CHAPTER 3: INTERFACESFRONT CONTROL PANEL INTERFACE
SLD Breaker symbol Color Transformer Status
Color Scheme
Open Color
Close Color
Not
Configured
Unknown Disconnected De-Energized Energized
Not
Configured
Red (Open)
Red Green Orange
Green (Open)
Green Red Orange
The transformer status is indicated in the top right of the display.
The parameters displayed in the Front panel screen example are as follows for a 2Winding Transformer with VT:
ParameterInput for the value
W1 IaMetering\ CT Bank 1 -J1\ J1 Ia
W1 IbMetering\ CT Bank 1 -J1\ J1 Ib
W1 IcMetering\ CT Bank 1 -J1\ J1 Ic
W2 IaMetering\ CT Bank 2 -K1\ K1 Ia
W2 IbMetering\ CT Bank 2 -K1\ K1 Ib
W2 IcMetering\ CT Bank 2 -K1\ K1 Ic
P:Metering\ Power 1\ Pwr1 Real
Q:Metering\ Power 1\ Pwr1 Reactive
PFMetering\ Power 1\ Pwr1 PF
The parameters displayed in the Front panel screen example are as follows for a 2Winding Transformer without VT:
ParameterInput for the value
W1 IaMetering\ CT Bank 2 -K1\ K1 Ia
W1 IbMetering\ CT Bank 2 -K1\ K1 Ib
W1 IcMetering\ CT Bank 2 -K1\ K1 Ic
W2 IaMetering\ CT Bank 3 -K2\ K2 Ia
W2 IbMetering\ CT Bank 3 -K2\ K2 Ib
W2 IcMetering\ CT Bank 3 -K2\ K2 Ic
P:Metering\ Power 1\ Pwr1 Real
Q:Metering\ Power 1\ Pwr1 Reactive
PFMetering\ Power 1\ Pwr1 PF
The parameters displayed in the Front panel screen example are as follows for 3-Winding
Transformer:
ParameterInput for the value
W1 IaMetering\ CT Bank 1 -J1\ J1 Ia
W1 IbMetering\ CT Bank 1 -J1\ J1 Ib
W1 IcMetering\ CT Bank 1 -J1\ J1 Ic
W2 IaMetering\ CT Bank 2 -K1\ K1 Ia
W2 IbMetering\ CT Bank 2 -K1\ K1 Ib
W2 IcMetering\ CT Bank 2 -K1\ K1 Ic
W3 IaMetering\ CT Bank 3 -K2\ K2 Ia
W3 IbMetering\ CT Bank 3 -K2\ K2 Ib
W3 IcMetering\ CT Bank 3 -K2\ K2 Ic
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL3–7
Page 82
FRONT CONTROL PANEL INTERFACECHAPTER 3: INTERFACES
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
LED 9
LED 10
LED 11
LED 12
LED 13
LED 14
LED 15
LED 16LED 17
IN SERVICE
TRIP
ALARM
PICK UP
XFMR OVERLOAD
LOAD-LIMIT REDUCED
XFMR DE-ENERGIZED
W1 BKR OPEN
W2 BKR CLOSED
LOCAL MODE
DIFFERENTIAL BLOCKED
TEST MODE
MESSAGE
Rugged and Membrane Front Panel LEDs
Front panel LED details:
•Number of LEDs: 17
•Programmability: Any FlexLogic operand
•Reset mode: self-reset or latched
The 845 front panel provides two columns of 7 LED indicators each, and 3 LED pushbutton
indicators. The “IN-SERVICE” (LED 1) and the “PICKUP” (LED 4) indicators from the first LED
column are non-programmable LEDs. The bottom 3 LED indicators from the first column,
and the 7 LED indicators from the second LED column are fully programmable. The
indicators “TRIP” (LED 2), and “ALARM” (LED 3), are also programmable, and can be
triggered by either a selection of FlexLogic operand assigned in their own menu, or by the
operation of any protection, control or monitoring element with function selected as Trip,
Alarm, or Latched Alarm.
The RESET key is used to reset any latched LED indicator or Target Message once the
condition has been cleared (latched conditions can also be reset via the RESETTING menu).
Figure 3-8: LED numbering
Figure 3-9: LEDs for 845 relay protecting 2W Xfmr
3–8845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 83
IN SERVICE
TRIP
ALARM
PICK UP
XFMR OVERLOAD
LOAD-LIMIT REDUCED
XFMR DE-ENERGIZED
W1 BKR OPEN
W2 BKR CLOSED
LOCAL MODE
DIFFERENTIAL BLOCKED
TEST MODE
MESSAGE
W3 BKR CLOSED
CHAPTER 3: INTERFACESFRONT CONTROL PANEL INTERFACE
Figure 3-10: LEDs for 845 relay protecting 3W Xfmr
Some status indicators are common while some are feature specific which depend on the
availability in the order code. The common status indicators in the first column are
described below.
•IN SERVICE
–Green color = Relay powered up, passed self-test has been programmed, and
ready to serve. This LED indicates that control power is applied, all monitored
inputs, outputs, and internal systems are OK, and that the device has been
programmed.
–Red color = Relay failed self test, has not been programmed, or out of service
•TRIP
This LED indicates that the element selected to produce a trip has operated. This
indicator always latches; as such, a Reset command must be initiated to allow the
latch to be reset.
•ALARM
This LED indicates that the FlexLogic™ operand serving as an Alarm switch has
operated. Latching of the indicator depends on the selected protection function. A
Reset command must be initiated to allow the latch to be reset.
•PICKUP
This LED indicates that at least one element is picked up. This indicator is never
latched.
•TEST MODE
This LED indicates that the relay has been set into Test Mode.
•MESSAGE
This LED indicates the presence of Target Messages detected by the relay.
•LOCAL MODE
This LED indicates that the relay is operating in local mode.
Breaker status indication is based on the breaker’s 52a and 52b contacts. With both
contacts wired to the relay and configured, closed breaker status is determined by closed
52a contact and opened 52b contact. Vice-versa the open breaker status is determined by
opened 52a contact and closed 52b contact. If both 52a and 52b contacts are open, due to
a breaker being racked out from the switchgear, both the Breaker Open and Breaker
Closed LED Indicators will be off.
The Event Cause indicators in the first column are described as follows:
Events Cause LEDs are turned ON or OFF by protection elements that have their respective
target settings selected as either “Self-Reset” or “Latched”. If a protection element target
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL3–9
setting is “Self-Reset”, then the corresponding Event Cause LEDs remain ON as long as the
operate operand associated with the element remains asserted. If a protection element
Page 84
FRONT CONTROL PANEL INTERFACECHAPTER 3: INTERFACES
target setting is “Latched”, then the corresponding Event Cause LEDs turn ON when the
operate operand associated with the element is asserted and will remain ON until the
RESET button on the front panel is pressed after the operand is reset.
Default labels are shipped in the package of every 845, together with custom templates. A
custom LED template is available for editing and printing, refer to publication GET-20035
http://www.gegridsolutions.com/multilin. The default labels can be replaced by user-
from
printed labels. User customization of LED operation is of maximum benefit in installations
where languages other than English are used to communicate with operators.
FASTPATH:
For LED and Pushbutton programming details, please refer to Front Panel.
Home Screen Icons
The next figure shows the icons available on the front screen. For descriptions of these
screen icons see the following tables.
Figure 3-11: Home Screen Icons
Table 3-1: Security Icon
Security StateSecurity Icon Color
User not logged inIcon is green and locked
User logged inIcon is red and unlocked
NOTE:
The security icon only represents the security access level through the front panel.
Table 3-2: Setpoint Group Icon
Description
Identifies the active setpoint group
Table 3-3: Wifi Icon
Wifi StateWifi Icon Color
DisabledIcon is grey and crossed by a red line
DisconnectedGrey
Connecting Orange
ConnectedGreen
3–10845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 85
CHAPTER 3: INTERFACESFRONT CONTROL PANEL INTERFACE
NOTE
Table 3-4: Active Target Icon
Description
When the target auto navigation setting is disabled, the message LED and the Active Target icon are
the only indication of active target messages.
Table 3-5: Breaker Health Icon
Description
The Breaker Health icon is blue when the setting for the breaker health function is not disabled.
When the setting is disabled the icon is grey.
Table 3-6: Settings Save Icon
Description
Indicates that a setting is being saved on the relay (i.e., when changing one of relay settings).
Icon is ON (relay is saving to flash memory)
Icon is OFF (relay is not saving to flash memory)
NOTE:
Do not remove power from the relay whenever the Settings Save icon is ON. When power
is removed the data being saved can also be lost.
Table 3-7: Local Mode Icon
Description
Indicates that Local Mode is active. During Local Mode, the control for the breakers and disconnect
switches can be performed only by the relay front panel.
Relay Messages
Target MessagesTarget Messages are displayed in order of their activation, whereas in cases of
simultaneous activation, they are displayed in the order outlined below (from highest to
lowest priority):
1.Targets generated by pressing programmable pushbutton
2.Targets generated by Contact inputs
3.Targets generated by Protection, Control and Monitoring elements
4.Targets generated by communications.
In cases where the Pickup and Operate flags from an element are detected at the same
time, the Pickup flag is not displayed. The Operate flag is displayed instead.
LED #6, from the first column of LEDs, is factory configured to be triggered by the
FlexLogic operand ANY TARGET, to indicate the presence of at least one target message.
This LED is labeled as “MESSAGE”. The LED can be programmed to any other FlexLogic
operand by choice.
MESSAGE TIMEOUT:
The timeout applies to each screen that is different than the default screen to which the
user navigates. Examples include viewing, metering, or navigating to a screen with setting,
etc. If no further navigation is performed, no pushbutton is touched, and/or no target is
initiated for the time specified in the message timeout setpoint, the display goes back to
the default screen (the metering summary screen).
The target message interrupts the message timeout. It overrides it. The message timeout
starts timing after each target message, and if no more activity is recorded for the
specified time, the display goes back to the default screen.
Pressing a programmable pushbutton activates a new screen with a Target Message
corresponding to the programmed PB action. The PB Target Message is displayed for 10
seconds then defaults to the screen that was displayed before pressing the pushbutton.
The PB Target Message is recorded in the list with other generated Target Messages.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL3–11
Page 86
FRONT CONTROL PANEL INTERFACECHAPTER 3: INTERFACES
NOTE
Target Messages can be cleared either by pressing the PB corresponding to the tab
“CLEAR”, or by initiating a RESET command. The “CLEAR” command clears only the Target
Messages, while initiating a RESET clears not only the Target Messages, but also any
latched LEDs and output relays.
Self-Test ErrorsThe relay performs self-diagnostics at initialization (after power up), and continuously as a
background task to ensure that the hardware and software are functioning correctly.
There are two types of self-test warnings indicating either a minor or major problem. Minor
errors indicate a problem with the relay that does not compromise protection and control
functionality of the relay. Major errors indicate a problem with the relay which takes it out
of service.
CAUTION:
NOTE:
Self-Test Warnings may indicate a serious problem with the relay hardware!
Upon detection of a minor problem, the relay does the following:
•Displays a detailed description of the error on the relay display as a target message
•Records the minor self-test error in the Event Recorder
•Flashes the “ALARM” LED
Upon detection of a major problem, the relay does the following:
•De-energizes critical failure relay
•De-energizes all output relays
•Blocks protection and control elements
•Turns the "IN SERVICE" LED to red
•Flashes the "ALARM" LED
•Displays “Major Self-test error” with the error code as a target message
•Records the major self-test failure in the Event Recorder
The Critical Failure Relay (Output Relay 8) is energized when the relay is in-service, and no
major error is present
Under both conditions, the targets cannot be cleared if the error is still active.
Figure 3-12: Minor Errors
3–12845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 87
CHAPTER 3: INTERFACESFRONT CONTROL PANEL INTERFACE
Figure 3-13: Major Errors
Table 3-8: Minor Self-test Errors
Self-test Error
Message
1
Order Code ErrorHardware doesn’t
CPU S/N InvalidCPU card doesn’t have
Slot“$” IO S/N
2
Invalid
Comms S/N Invalid Comms card doesn’t
CPanel S/N Invalid Control Panel doesn’t
PSU S/N InvalidPower Supply Unit
RTC Error The CPU cannot read
Product Serial
Invalid
Comm Alert #1Communication error
Comm Alert #2Every 1 second
Comm Alert #3Every 1 second
FLASH ErrorThe permanent storage
SPI ErrorCommunication error
Invalid MAC
Address
Calibration ErrorUnit has default
Description of Problem How Often the Test is
Performed
Every 1 secondIf alert doesn’t self-reset then
match order code
Every 1 second
valid data to match the
order code.
IO ca rd lo cated in slot $
Every 1 second
doesn’t have valid data
to match the order
code.
Every 1 second
have valid data to
match the order code.
Every 1 second
have valid data to
match the order code.
Every 1 second
doesn’t have valid data
to match the order
code.
Every 1 second
the time from the real
time clock
The product serial
Every 1 second
number doesn’t match
the product type
Every 1 second
between CPU and
Comms board
Every 1 second
memory has been
corrupted
Every 1 second
between CPU and LEDs,
Keypad or peripheral
memory devices
MAC address is not in
Every 1 second
the product range
Boot-up and Every 1
calibration values
second
What to do
contact factory. Otherwise
monitor re-occurrences as
errors are detected and selfreset
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL3–13
Page 88
FRONT CONTROL PANEL INTERFACECHAPTER 3: INTERFACES
Self-test Error
Message
1
WiFi Default
Settings
Link Error Primary 3Port 1 or Port 4
Description of Problem How Often the Test is
Performed
SSID and Passphrase is
Every 1 secondSet SSID and Passphrase
the factory default
Every 1 secondEnsure Ethernet cable is
(depending on order
code) is not connected
Link Error
Port 5 is not connected Every 1 secondEnsure Ethernet cable is
Secondary
Traffic Error
Primary
Abnormally high
amount of Broadcast
Every 1 secondContact site IT department to
and Uni-cast traffic on
port 1 or port 4
Traffic Error
Secondary
Abnormally high
amount of Broadcast
Every 1 secondContact site IT department to
and Uni-cast traffic on
port 5
Ambient
Temperature >80C
The ambient
temperature
Every 1 secondInspect mounting enclosure
surrounding the
product has exceeded
80C
Event Rate HighAbnormally high
Every 1 secondEnsure settings are not set
amounts of events have
been generated so the
relay has stopped
logging to prevent
further issues
IRIG-B FailureA bad IRIG-B input
Every 1 secondEnsure IRIG-B cable is
signal has been
detected
Version Mismatch CPU and Comms do not
have the same revision
Boot-up and Every 1
second
on firmware
SelfTestFWUpdate The updating of the
Every 1 secondRe-try uploading firmware. If
firmware failed
Remote CAN IO
Mismatch
The value of the cards
in the slots detected by
the Remote IO does not
Every 1 second. A
failure is declared after
60 consecutive failures
match the value
validated by the user
configuration
1. – Failure is logged after the detection of 5 consecutive failures
2. $ – is the slot ID (i.e., F, G, H etc.)
What to do
connected, check cable
functionality (i.e. physical
damage or perform
continuity test), and ensure
master or peer device is
functioning. If none of these
apply, contact the factory.
connected, check cable
functionality (i.e. physical
damage or perform
continuity test), and ensure
master or peer device is
functioning. If none of these
apply, contact the factory.
check network for
malfunctioning devices
check network for
malfunctioning devices
for unexpected heat sources
(i.e loose primary cables) and
remove accordingly
close to nominal ratings.
Ensure FlexLogic equations
do not have impractical
timing for status events
connected, check cable
functionality (i.e. physical
damage or perform
continuity test), ensure IRIGB receiver is functioning, and
check input signal level (it
may be less than
specification). If none of
these apply, contact the
factory.
Ensure that both the CPU
and Comms FW was
uploaded during the upgrade
process
the upload doesn’t work a
second time contact factory
Fix the remote CANBUS IO
mismatch.
3–14845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 89
CHAPTER 3: INTERFACESFRONT CONTROL PANEL INTERFACE
NOTE
3.To disable Link Error Primary target when not in-use with SE order code, change IP
address to 127.0.0.1
Table 3-9: Major Self-test Errors
Self-test Error
Message
Relay Not
Ready
Major Self-Test
(error code)
NOTE:
When a total loss of power is present, the Critical Failure Relay (Output Relay 8) is de-
Latched
Target
Message
NoPRODUCT SETUP
YesUnit hardware fa ilure
Description of
Problem
INSTALLATION
setting indicates
relay is not in a
programmed state.
detected
How Often the Test
is Performed
On power up and
whenever the
PRODUCT SETUP
INSTALLATION
setting is altered.
Every 1 secondContact the factory and
What to do
Program all required
settings and then set the
PRODUCT SETUP
INSTALLATION setting to
“Ready”.
supply the failure code as
noted on the display.
energized.
Out of ServiceWhen the relay is shipped from the factory, the DEVICE IN SERVICE is set to “Not Ready”.
The IN SERVICE LED will be orange and the critical fail relay will be de-energized but this will
not be classified as a major self-test. An out of service event will be generated in the event
recorder.
Flash MessagesFlash messages are warning, error, or general information messages displayed in response
to pressing certain keys. The factory default flash message time is 2 seconds.
Label Removal
The following procedure describes how to use the label removal tool.
1.Bend the tabs of the tool upwards as shown in the image.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL3–15
Page 90
FRONT CONTROL PANEL INTERFACECHAPTER 3: INTERFACES
2.Slide the label removal tool under the LED label as shown in the next image. Make sure
the bent tabs are pointing away from the relay. Move the tool inside until the tabs
enter the pocket.
3.Remove the tool with the LED label.
The following describes how to remove the user-programmable pushbutton label from the
front panel.
845
1.Slide the label tool under the user-programmable pushbutton label as shown in the
next image. Make sure the bent tab is pointing away from the relay.
2.Remove the tool and user-programmable pushbutton label as shown in image.
3–16845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 91
CHAPTER 3: INTERFACESSOFTWARE INTERFACE
Software Interface
EnerVista 8 Series Setup Software
Although settings can be entered manually using the control panel keys, a PC can be used
to download setpoints through the communications port. The EnerVista 8 Series
software is available from GE Multilin to make this as convenient as possible. With
Setup
EnerVista 8 Series Setup software running, it is possible to:
•Program and modify settings
•Load and save setting files to and from a disk
•Read actual values
•Monitor status
•Read pre-trip data and event records
•Get help on any topic
•Upgrade the 845 firmware
The EnerVista 8 Series Setup software allows immediate access to all 845 features with
easy to use pull down menus in the familiar Windows environment. This section provides
the necessary information to install EnerVista 8 Series Setup
firmware, and write and edit setting files.
The EnerVista 8 Series Setup software can run without a 845 connected to the computer. In
this case, settings may be saved to a file for future use. If a 845
communications are enabled, the 845
addition, measured values, status and trip messages can be displayed with the actual
value screens.
can be programmed from the setting screens. In
software, upgrade the relay
is connected to a PC and
Hardware & Software
Requirements
The following requirements must be met for the software.
•Dual-core processor
•Microsoft Windows™ 7 or 8.1; 32-bit or 64-bit is installed and running properly.
•At least 1 GB of free hard disk space is available.
•At least 2 GB of RAM is installed.
•1280 x 800 display screen
The software can be installed from either the GE EnerVista CD or the GE Multilin website at
http://www.gegridsolutions.com/.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL3–17
Page 92
SOFTWARE INTERFACECHAPTER 3: INTERFACES
Installing the
EnerVista 8 Series
Setup Software
After ensuring the minimum requirements indicated earlier, use the following procedure to
install the EnerVista 8 Series Setup software from the enclosed GE EnerVista CD.
1.Insert the GE EnerVista CD into your CD-ROM drive.
2.Click the Install Now button and follow the installation instructions to install the nocharge EnerVista software on the local PC.
3.When installation is complete, start the EnerVista Launchpad application.
4.Click the IED Setup section of the LaunchPad toolbar.
5.In the EnerVista Launchpad window, click the Add Product button and select the
845 Protection System as shown below. Select the Web option to ensure the most
recent software release, or select CD if you do not have a web connection, then click
the Add Now button to list software items for the 845.
6.EnerVista Launchpad obtains the latest installation software from the Web or CD and
automatically starts the installation process. A status window with a progress bar is
shown during the downloading process.
3–18845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 93
CHAPTER 3: INTERFACESSOFTWARE INTERFACE
7.Select the complete path, including the new directory name, where the EnerVista 8
Series Setup software is being installed.
8.Click on Next to begin the installation. The files are installed in the directory indicated,
the USB driver is loaded into the computer, and the installation program automatically
creates icons and adds the EnerVista 8 Series Setup software to the Windows start
menu.
9.The 845 device is added to the list of installed IEDs in the EnerVista Launchpad
window, as shown below.
If you are going to communicate from your computer to the 845 Relay using the USB
port:
10. Plug the USB cable into the USB port on the 845 Relay then into the USB port on your
computer.
11. Launch EnerVista 8 Series Setup software from LaunchPad.
12. In EnerVista > Device Setup:
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL3–19
Page 94
SOFTWARE INTERFACECHAPTER 3: INTERFACES
Upgrading the
Software
13. Select USB as the Interface type.
14. Select the Read Order Code button.
The latest EnerVista software and firmware can be downloaded from:
https://www.gegridsolutions.com/
After upgrading, check the version number under Help > About. If the new version does
not display, try uninstalling the software and reinstalling the new versions.
3–20845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 95
CHAPTER 3: INTERFACESSOFTWARE INTERFACE
Connecting EnerVista 8 Series Setup software to the Relay
Using the Quick
Connect Feature
The Quick Connect button can be used to establish a fast connection through the front
panel USB port of a relay, or through the Ethernet port. The following window appears
when the QuickConnect button is pressed:
As indicated by the window, the "Quick Connect" feature can quickly connect the software
to a front port if the USB is selected in the interface drop-down list. Select “USB” and press
the Connect button. Ethernet or WiFi can also be used as the interface for Quick Connect
as shown next.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL3–21
Page 96
SOFTWARE INTERFACECHAPTER 3: INTERFACES
When connected, a new Site called “Quick Connect” appears in the Site List window.
The Site Device has now been configured via the Quick Connect feature for either USB or
Ethernet communications. Proceed to Connecting to the Relay next, to begin
communications.
Configuring Ethernet
Communications
FASTPATH:
Before starting, verify that the Ethernet cable is properly connected to the RJ-45 Ethernet
port.
845 supports a maximum of 3 TCP/IP sessions.
1.Install and start the latest version of the EnerVista 8 Series Setup software (available
from the GE EnerVista CD or Website). See the previous section for the installation
procedure.
2.Click on the Device Setup button to open the Device Setup window and click the Add Site button to define a new site.
3.Enter the desired site name in the "Site Name" field. If desired, a short description of
the site can also be entered. In this example, we will use “Substation 1” as the site
name.
4.The new site appears in the upper-left list.
5.Click the Add Device button to define the new device.
6.Enter the desired name in the "Device Name" field, and a description (optional).
3–22845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 97
CHAPTER 3: INTERFACESSOFTWARE INTERFACE
7.Select “Ethernet” from the Interface drop-down list. This displays a number of
interface parameters that must be entered for proper Ethernet functionality.
Connecting to the
Relay
8.Enter the IP address, slave address, and Modbus port values assigned to the 845 relay
(from the Setpoints > Device > Communications menu).
9.Click the Read Order Code button to connect to the 845 and upload the order code. If
a communications error occurs, ensure that the Ethernet communication values
correspond to the relay setting values.
10. Click OK when the relay order code has been received. The new device will be added
to the Site List window (or Online window) located in the top left corner of the main
EnerVista 8 Series Setup software window.
The 845 Site Device has now been configured for Ethernet communications. Proceed to
the following section to begin communications.
Now that the communications parameters have been properly configured, the user can
easily communicate with the relay.
1.Expand the Site list by double clicking on the site name or clicking on the «+» box to
list the available devices for the given site.
2.Desired device trees can be expanded by clicking the «+» box. The following list of
headers is shown for each device:
Device Definition
Status
Metering
Quick Setup
Setpoints
Records
Maintenance.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL3–23
Page 98
SOFTWARE INTERFACECHAPTER 3: INTERFACES
3.Expand the Setpoints > Device > Front Panel list item and double click on Display Properties or Default Screens to open the settings window as shown:
4.The settings window opens with a corresponding status indicator on the lower left of
the window.
5.If the status indicator is red, verify that the serial, USB, or Ethernet cable is properly
connected to the relay, and that the relay has been properly configured for
communications (steps described earlier).
The settings can now be edited, printed, or changed. Other setpoint and command
windows can be displayed and edited in a similar manner. "Actual Values" windows are
also available for display. These windows can be arranged, and resized, if desired.
Working with Setpoints & Setpoints Files
FASTPATH:
3–24845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
When a settings file is being uploaded to a device, the DEVICE IN SERVICE state (Setpoints >
Device > Installation) switches to "Not Ready" for the duration of the upload. This ensures
that all new settings are applied before the device is operational. Settings file upload
operations include both 1) Enervista 8 Series Setup software menu option "Write Settings
File to Device" and 2) saving Logic Designer changes online.
Individual setting changes from the device front panel or Enervista 8 Series Setup software
Online Window do not change the DEVICE IN SERVICE state.
Page 99
CHAPTER 3: INTERFACESSOFTWARE INTERFACE
Engaging a DeviceThe software may be used in on-line mode (relay connected) to directly communicate with
a relay. Communicating relays are organized and grouped by communication interfaces
and into sites. Sites may contain any number of relays selected from the product series.
Entering SetpointsThe System Setup page is used as an example to illustrate entering setpoints. In this
example, we are changing the voltage sensing setpoints.
1.Establish communications with the relay.
2.Select the Setpoint > System > Voltage Sensing menu item.
3.Select the Aux. VT Secondary setpoint by clicking anywhere in the parameter box. This
displays three arrows: two to increment/decrement the value and another to launch
the numerical keypad.
4.Clicking the arrow at the end of the box displays a numerical keypad interface that
allows the user to enter a value within the setpoint range displayed near the top of the
keypad: Click = to exit from the keypad and keep the new value. Click on X to exit from
the keypad and retain the old value.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL3–25
Page 100
SOFTWARE INTERFACECHAPTER 3: INTERFACES
5.For setpoints requiring non-numerical pre-set values (e.g. Phase VT Connection
below), clicking anywhere within the setpoint value box displays a drop-down
selection menu arrow. Select the desired value from this list.
6.In the Setpoints > System Setup > Voltage Sensing dialog box, click on Save to save
the values into the 845. Click YES to accept any changes and exit the window. Click
Restore to retain previous values. Click Default to restore Default values.
7.For setpoints requiring an alphanumeric text string (e.g. "relay name"), the value may
be entered directly within the setpoint value box.
File SupportOpening any file automatically launches the application or provides focus to the already
opened application.
New files are automatically added to the tree.
Using Setpoints FilesThe software interface supports three ways of handling changes to relay settings:
•In off-line mode (relay disconnected) to create or edit relay settings files for later
download to communicating relays.
•Directly modifying relay settings while connected to a communicating relay, then
saving the settings when complete.
•Creating/editing settings files while connected to a communicating relay, then saving
them to the relay when complete.
Settings files are organized on the basis of file names assigned by the user. A settings file
contains data pertaining to the following types of relay settings:
•Device Definition
•Relay Setup
•System Setup
•Protection
•Control
•Inputs/Outputs
•Monitoring
•FlexLogic
•Quick setup
•Protection summary
•IEC 61850 configurator
•Modbus user map
Factory default values are supplied and can be restored after any changes.
3–26845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.