GE 845 Instruction Manual

Page 1
GE
845

Transformer Protection System

Transformer Protection, Control and Management
Instruction manual
Product version: GEK-
GE publication code: 1601-0651-A5 (GEK-119651D)
*1601-0450-A5*
Page 2
© 2017 GE Multilin Incorporated. All rights reserved. GE Multilin 845 Transformer Protection System instruction manual for revision 2.0x. 845 Transformer Protection System, EnerVista, EnerVista Launchpad, and EnerVista 8
Series Setup software are registered trademarks of GE Multilin Inc. The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The content of this manual is for informational use only and is subject to change without notice.
Part number: 1601-0651-A5 (July 2017)
Note
May contain components with FCC ID: XF6-RS9110N1122 and IC ID: 8407A-RS9110N1122.
Page 3

Table of Contents

1.INTRODUCTION Overview .............................................................................................................................................. 1 - 1
Description of the 845 Transformer Protection Relay....................................................1 - 2
Security Overview............................................................................................................................ 1 - 7
845 Order Codes............................................................................................................................... 1 - 8
Specifications...................................................................................................................................1 - 10
Device .......................................................................................................................................................... 1 - 10
Protection................................................................................................................................................... 1 - 10
Control......................................................................................................................................................... 1 - 17
Monitoring.................................................................................................................................................. 1 - 18
Recording................................................................................................................................................... 1 - 19
User-Programmable Elements ........................................................................................................ 1 - 20
Metering...................................................................................................................................................... 1 - 21
Inputs ........................................................................................................................................................... 1 - 23
Outputs........................................................................................................................................................ 1 - 25
Power Supply ........................................................................................................................................... 1 - 26
Communications .................................................................................................................................... 1 - 27
Testing & Certification.......................................................................................................................... 1 - 28
Physical....................................................................................................................................................... 1 - 29
Environmental.......................................................................................................................................... 1 - 29
Cautions and Warnings ..............................................................................................................1 - 30
Safety words and definitions............................................................................................................ 1 - 30
General Cautions and Warnings..................................................................................................... 1 - 30
Must-read Information................................................................................................................1 - 33
Storage........................................................................................................................................................ 1 - 34
For Further Assistance.................................................................................................................1 - 34
Repairs......................................................................................................................................................... 1 - 34
2.INSTALLATION Mechanical Installation................................................................................................................. 2 - 1
Product Identification..............................................................................................................................2 - 1
Dimensions...................................................................................................................................................2 - 2
Mounting .......................................................................................................................................................2 - 3
Standard Panel Mount.............................................................................................................................2 - 4
Depth Reducing Collar.............................................................................................................................2 - 5
Draw-out Unit Withdrawal and Insertion ...................................................................................... 2 - 7
Removable Power Supply .....................................................................................................................2 - 8
Removable Magnetic Module .............................................................................................................. 2 - 9
Arc Flash Sensor ..................................................................................................................................... 2 - 10
Sensor Fiber Handling & Storage....................................................................................................2 - 10
Sensor Installation..................................................................................................................................2 - 10
Electrical Installation ....................................................................................................................2 - 11
Typical Wiring Diagrams .................................................................................................................... 2 - 11
Terminal Identification ......................................................................................................................... 2 - 16
Wire Size......................................................................................................................................................2 - 20
Phase Sequence and Transformer Polarity ............................................................................... 2 - 21
Ground CT Inputs.................................................................................................................................... 2 - 21
Voltage Inputs.......................................................................................................................................... 2 - 22
Restricted Earth Fault Inputs ............................................................................................................ 2 - 22
Zero-Sequence CT Installation ......................................................................................................... 2 - 23
Control Power........................................................................................................................................... 2 - 24
Contact Inputs ......................................................................................................................................... 2 - 24
Output Relays .......................................................................................................................................... 2 - 25
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL I
Page 4
Serial Communications ........................................................................................................................2 - 27
IRIG-B............................................................................................................................................................2 - 29
3.INTERFACES Front Control Panel Interface......................................................................................................3 - 2
845 Graphical Display Pages .............................................................................................................. 3 - 2
Working with Graphical Display Pages.......................................................................................... 3 - 3
Single Line Diagram.................................................................................................................................3 - 6
Rugged and Membrane Front Panel LEDs .................................................................................... 3 - 8
Home Screen Icons................................................................................................................................3 - 10
Relay Messages.......................................................................................................................................3 - 11
Target Messages.....................................................................................................................................3 - 11
Self-Test Errors.........................................................................................................................................3 - 12
Out of Service............................................................................................................................................3 - 15
Flash Messages........................................................................................................................................3 - 15
Label Removal..........................................................................................................................................3 - 15
Software Interface ........................................................................................................................3 - 17
EnerVista 8 Series Setup Software..................................................................................................3 - 17
Hardware & Software Requirements ............................................................................................3 - 17
Installing the EnerVista 8 Series Setup Software.....................................................................3 - 18
Upgrading the Software......................................................................................................................3 - 20
Connecting EnerVista 8 Series Setup software to the Relay..............................................3 - 21
Using the Quick Connect Feature...................................................................................................3 - 21
Configuring Ethernet Communications........................................................................................3 - 22
Connecting to the Relay......................................................................................................................3 - 23
Working with Setpoints & Setpoints Files ....................................................................................3 - 24
Engaging a Device..................................................................................................................................3 - 25
Entering Setpoints ..................................................................................................................................3 - 25
File Support................................................................................................................................................3 - 26
Using Setpoints Files..............................................................................................................................3 - 26
Downloading & Saving Setpoints Files..........................................................................................3 - 27
Adding Setpoints Files to the Environment.................................................................................3 - 27
Creating a New Setpoints File...........................................................................................................3 - 28
Upgrading Setpoints Files to a New Revision............................................................................3 - 29
Printing Setpoints....................................................................................................................................3 - 30
Printing Values from a Connected Device...................................................................................3 - 31
Loading Setpoints from a File ...........................................................................................................3 - 31
Uninstalling Files and Clearing Data..............................................................................................3 - 32
Quick Setup................................................................................................................................................3 - 32
Upgrading Relay Firmware ................................................................................................................3 - 34
Loading New Relay Firmware...........................................................................................................3 - 35
Advanced EnerVista 8 Series Setup Software Features .......................................................3 - 38
SLD Configurator.....................................................................................................................................3 - 38
FlexCurve Editor.......................................................................................................................................3 - 45
Transient Recorder (Waveform Capture).....................................................................................3 - 46
Protection Summary.............................................................................................................................3 - 50
Offline Settings File Conversion........................................................................................................3 - 51
Convert SR 745 Files..............................................................................................................................3 - 51
Conversion Summary Report............................................................................................................3 - 53
Results Window.......................................................................................................................................3 - 53
4.SETPOINTS Setpoints Main Menu ......................................................................................................................4 - 1
Protection and Trip Breaker Selection............................................................................................. 4 - 2
Setpoints Entry Methods ....................................................................................................................... 4 - 7
Common Setpoints................................................................................................................................... 4 - 7
Logic Diagrams.......................................................................................................................................... 4 - 9
Setpoints Text Abbreviations.............................................................................................................4 - 10
II 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 5
Device..................................................................................................................................................4 - 11
Custom Configuration.......................................................................................................................... 4 - 11
Real-time Clock ....................................................................................................................................... 4 - 13
Clock..............................................................................................................................................................4 - 14
PTP Configuration...................................................................................................................................4 - 15
SNTP Protocol...........................................................................................................................................4 - 16
Security ....................................................................................................................................................... 4 - 17
Basic Security...........................................................................................................................................4 - 18
CyberSentry ..............................................................................................................................................4 - 20
Communications .................................................................................................................................... 4 - 26
RS485............................................................................................................................................................4 - 26
WiFi................................................................................................................................................................4 - 27
USB ................................................................................................................................................................4 - 30
Ethernet Ports...........................................................................................................................................4 - 30
Modbus Protocol.....................................................................................................................................4 - 32
Routing.........................................................................................................................................................4 - 36
DNP Protocol.............................................................................................................................................4 - 38
DNP / IEC104 Point Lists ......................................................................................................................4 - 41
IEC 60870-5-104 .....................................................................................................................................4 - 43
IEC 60870-5-103 .....................................................................................................................................4 - 45
IEC 61850....................................................................................................................................................4 - 45
Remote Modbus Device.......................................................................................................................4 - 47
Transient Recorder ................................................................................................................................ 4 - 48
Data Logger .............................................................................................................................................. 4 - 50
Fault Reports ............................................................................................................................................ 4 - 53
Event Data ................................................................................................................................................. 4 - 54
Flex States.................................................................................................................................................. 4 - 54
Front Panel ................................................................................................................................................ 4 - 54
Programmable LEDs..............................................................................................................................4 - 55
Programmable Pushbuttons.............................................................................................................4 - 56
Tab Pushbuttons.....................................................................................................................................4 - 60
Annunciator...............................................................................................................................................4 - 63
Display Properties ..................................................................................................................................4 - 65
Default Screens........................................................................................................................................4 - 66
Home Screens..........................................................................................................................................4 - 67
Resetting..................................................................................................................................................... 4 - 68
Installation................................................................................................................................................. 4 - 68
System ................................................................................................................................................4 - 70
Current Sensing....................................................................................................................................... 4 - 71
Voltage Sensing ...................................................................................................................................... 4 - 71
Traditional VT............................................................................................................................................4 - 71
Power Sensing ......................................................................................................................................... 4 - 73
Power System .......................................................................................................................................... 4 - 73
Transformer .............................................................................................................................................. 4 - 74
Transformer Setup .................................................................................................................................4 - 75
Xfmer Status Detection..................................................................................................................... 4 - 100
Thermal Inputs...................................................................................................................................... 4 - 103
On-load Tap Changer .......................................................................................................................4 - 104
Breakers....................................................................................................................................................4 - 110
Switches....................................................................................................................................................4 - 112
FlexCurves ...............................................................................................................................................4 - 115
Inputs................................................................................................................................................4 - 117
Contact Inputs .......................................................................................................................................4 - 117
Virtual Inputs ..........................................................................................................................................4 - 120
Remote Inputs........................................................................................................................................4 - 122
Analog Inputs .........................................................................................................................................4 - 122
Outputs ............................................................................................................................................4 - 127
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL III
Page 6
Output Relays........................................................................................................................................4 - 127
Auxiliary Relay selected for breaker Trip..................................................................................4 - 130
Aux Relay selected for breaker Close.........................................................................................4 - 132
Auxiliary Output Relays ....................................................................................................................4 - 134
Critical Failure Relay #8....................................................................................................................4 - 135
Virtual Outputs ......................................................................................................................................4 - 136
Analog Outputs..................................................................................................................................... 4 - 136
Protection....................................................................................................................................... 4 - 138
Percent Differential ............................................................................................................................. 4 - 140
Transformer Overload ....................................................................................................................... 4 - 151
Current Elements .................................................................................................................................4 - 153
Inverse Time Overcurrent Curves.................................................................................................4 - 153
Percent of Load-To-Trip....................................................................................................................4 - 160
Phase Time Overcurrent Protection (51P).................................................................................4 - 161
Phase Instantaneous Overcurrent Protection (50P)............................................................4 - 164
Phase Directional Overcurrent Protection (67P)....................................................................4 - 166
Neutral Time Overcurrent Protection (51N).............................................................................4 - 169
Neutral Instantaneous Overcurrent Protection (50N).........................................................4 - 172
Neutral Directional Overcurrent Protection (67N)................................................................4 - 175
Ground Time Overcurrent Protection (51G).............................................................................4 - 180
Ground Instantaneous Overcurrent Protection (50G).........................................................4 - 182
Ground Directional Overcurrent Protection (67G) ................................................................4 - 184
Restricted Ground (Earth) Fault (87G).........................................................................................4 - 188
Negative Sequence Time Overcurrent Protection (51_2)..................................................4 - 193
Negative Sequence Instantaneous Overcurrent Protection (50_2)..............................4 - 195
Voltage Elements .................................................................................................................................4 - 198
Undervoltage Curves .........................................................................................................................4 - 199
Phase Undervoltage Protection (27P).........................................................................................4 - 200
Auxiliary Undervoltage (27X)..........................................................................................................4 - 203
Phase Overvoltage Protection (59P)............................................................................................4 - 206
Auxiliary Overvoltage Protection (59X)......................................................................................4 - 209
Neutral Overvoltage Protection (59N)........................................................................................4 - 212
Negative Sequence Overvoltage Protection (59_2).............................................................4 - 215
Volts per Hertz (24) ..............................................................................................................................4 - 217
Power Elements....................................................................................................................................4 - 223
Directional Power (32)........................................................................................................................4 - 223
Frequency Elements...........................................................................................................................4 - 229
Underfrequency (81U) .......................................................................................................................4 - 229
Overfrequency (81O) ..........................................................................................................................4 - 232
Frequency Rate of Change (81R)..................................................................................................4 - 235
Monitoring...................................................................................................................................... 4 - 239
Transformer............................................................................................................................................4 - 239
Harmonic Derating..............................................................................................................................4 - 239
Thermal Elements................................................................................................................................4 - 242
Tap Changer Failure...........................................................................................................................4 - 250
Trip and Close Circuit Monitoring .................................................................................................4 - 252
Breaker Arcing Current...................................................................................................................... 4 - 259
Breaker Health ......................................................................................................................................4 - 262
Functions ................................................................................................................................................. 4 - 266
Power Factor (55).................................................................................................................................4 - 266
Demand....................................................................................................................................................4 - 272
Pulsed Outputs......................................................................................................................................4 - 281
Digital Counters....................................................................................................................................4 - 284
Harmonic Detection ...........................................................................................................................4 - 287
RTD Temperature.................................................................................................................................4 - 290
RTD Trouble.............................................................................................................................................4 - 295
Loss of Communications.................................................................................................................. 4 - 296
IV 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 7
Control..............................................................................................................................................4 - 298
Setpoint Group.......................................................................................................................................4 - 298
Local Control Mode (breakers and switches) ..........................................................................4 - 301
Breaker Control .....................................................................................................................................4 - 310
Switch Control (9)..................................................................................................................................4 - 313
Virtual Input Control............................................................................................................................4 - 316
Trip Bus......................................................................................................................................................4 - 317
Breaker Failure (50BF) ........................................................................................................................4 - 319
Setup.......................................................................................................................................................... 4 - 320
Initiate .......................................................................................................................................................4 - 322
Arc Flash Protection ............................................................................................................................4 - 324
Synchrocheck (25)................................................................................................................................4 - 326
VT Fuse Failure (VTFF) .........................................................................................................................4 - 331
FlexLogic .........................................................................................................................................4 - 333
Timers ........................................................................................................................................................4 - 343
Non-volatile Latches...........................................................................................................................4 - 343
FlexLogic Equation...............................................................................................................................4 - 345
Viewing FlexLogic Graphics............................................................................................................4 - 347
FlexElements...........................................................................................................................................4 - 348
Testing..............................................................................................................................................4 - 354
Simulation................................................................................................................................................4 - 355
Setup.......................................................................................................................................................... 4 - 355
Pre-Fault...................................................................................................................................................4 - 356
Fault ...........................................................................................................................................................4 - 357
Post-Fault ................................................................................................................................................4 - 357
Test LEDs ..................................................................................................................................................4 - 358
Contact Inputs .......................................................................................................................................4 - 358
Output Relays ........................................................................................................................................4 - 358
Ethernet Loopback Test.....................................................................................................................4 - 359
5.STATUS Summary ............................................................................................................................................. 5 - 2
Configurable SLD.......................................................................................................................................5 - 2
Annunciator ................................................................................................................................................. 5 - 3
Tab Pushbuttons........................................................................................................................................5 - 3
Breakers ............................................................................................................................................... 5 - 4
Switches ............................................................................................................................................... 5 - 5
Last Trip Data.....................................................................................................................................5 - 5
Arc Flash............................................................................................................................................... 5 - 5
Contact Inputs................................................................................................................................... 5 - 6
Output Relays.................................................................................................................................... 5 - 6
Virtual Inputs......................................................................................................................................5 - 7
Virtual Outputs .................................................................................................................................. 5 - 8
Flex State ............................................................................................................................................. 5 - 8
Communications.............................................................................................................................. 5 - 8
GOOSE Rx and Tx.......................................................................................................................................5 - 8
Information .......................................................................................................................................5 - 13
Main CPU.................................................................................................................................................... 5 - 13
Comms CPU .............................................................................................................................................. 5 - 13
Hardware Versions................................................................................................................................ 5 - 14
Environment ............................................................................................................................................. 5 - 14
Device Status ...................................................................................................................................5 - 15
Clock.....................................................................................................................................................5 - 16
PTP Status..........................................................................................................................................5 - 16
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL V
Page 8
6.METERING Summary..............................................................................................................................................6 - 4
Transformer.........................................................................................................................................6 - 5
Percent Differential Current ................................................................................................................. 6 - 5
Windings ....................................................................................................................................................... 6 - 6
Thermal Elements..................................................................................................................................... 6 - 7
Tap Changer................................................................................................................................................ 6 - 7
Currents.................................................................................................................................................6 - 8
Voltages .............................................................................................................................................6 - 10
Frequency.........................................................................................................................................6 - 11
Volts Per Hertz.................................................................................................................................6 - 12
Harmonic Magnitude...................................................................................................................6 - 12
Harmonics 1(Harmonics 4)........................................................................................................6 - 13
Harmonic Detection.....................................................................................................................6 - 14
Synchrocheck..................................................................................................................................6 - 14
Power...................................................................................................................................................6 - 15
Energy.................................................................................................................................................6 - 16
Power Factor....................................................................................................................................6 - 17
Current Demand 1.........................................................................................................................6 - 17
Current Demand K1......................................................................................................................6 - 18
Current Demand K2......................................................................................................................6 - 18
Directional Power ..........................................................................................................................6 - 19
Arc Flash ............................................................................................................................................6 - 19
RTDs .....................................................................................................................................................6 - 20
RTD Maximums...............................................................................................................................6 - 20
Analog Inputs...................................................................................................................................6 - 20
FlexElements....................................................................................................................................6 - 21
7.RECORDS Events.....................................................................................................................................................7 - 1
Transient Records.............................................................................................................................7 - 1
Fault Reports.......................................................................................................................................7 - 2
Data Logger.........................................................................................................................................7 - 2
Breakers................................................................................................................................................7 - 3
Breaker Arcing Current........................................................................................................................... 7 - 3
Breaker Health ........................................................................................................................................... 7 - 3
Digital Counters.................................................................................................................................7 - 3
Remote Modbus Device.................................................................................................................7 - 4
Clear Records .....................................................................................................................................7 - 6
8.TRANSFORMER M&D
DGA Monitoring .................................................................................................................................8 - 2
Device Data.........................................................................................................................................8 - 3
Dissolved Gas Analysis ..................................................................................................................8 - 3
Learned Data Records....................................................................................................................8 - 4
Energization Records......................................................................................................................8 - 5
Digital Fault Records.......................................................................................................................8 - 6
Models....................................................................................................................................................8 - 6
Transformer Models................................................................................................................................. 8 - 6
DGA Models ................................................................................................................................................. 8 - 7
Historical Maximum Record ........................................................................................................8 - 8
Transformer Health Report..........................................................................................................8 - 8
DGA Historical Trend.......................................................................................................................8 - 9
VI 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 9
9.MAINTENANCE Environmental Health Report.....................................................................................................9 - 1
General Maintenance..................................................................................................................... 9 - 3
In-service Maintenance.......................................................................................................................... 9 - 3
Out-of-service Maintenance................................................................................................................ 9 - 3
Unscheduled Maintenance (System Interruption) .....................................................................9 - 3
A.APPENDIX A Warranty.............................................................................................................................................. A - 1
Revision history.................................................................................................................................A - 1
Major Updates ............................................................................................................................................A - 2
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL VII
Page 10
VIII 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 11
GE
Grid Solutions
845 Transformer Protection System
Chapter 1: Introduction

Introduction

The Multilin 845 relay is a microprocessor-based unit intended for the management and primary protection of the medium to large size medium voltage (MV) and high voltage (HV) power transformers. Both 2-winding and 3-winding transformers are supported. The 845 relay provides a number of primary and backup current and voltage based protection functions. This system allows for control of the circuit breakers at each winding plus a number of monitoring and control functions are also provided.

Overview

Each relay provides protection, control, and monitoring functions with both local and remote human interfaces. They also display the present trip/alarm conditions, and most of the more than 35 measured system parameters. Recording of past trip, alarm or control events, maximum demand levels, and energy consumption is also performed.
These relays contain many innovative features. To meet diverse utility standards and industry requirements, these features have the flexibility to be programmed to meet specific user needs. This flexibility will naturally make a piece of equipment difficult to learn. To aid new users in getting basic protection operating quickly, setpoints are set to typical default values and advanced features are disabled. These settings can be reprogrammed at any time.
Programming can be accomplished with the front panel keys and display. Due to the numerous settings, this manual method can be somewhat laborious. To simplify programming and provide a more intuitive interface, setpoints can be entered with a PC running the EnerVista 8 Setup software provided with the relay. Even with minimal computer knowledge, this menu-driven software provides easy access to all front panel functions. Actual values and setpoints can be displayed, altered, stored, and printed. If settings are stored in a setpoint file, they can be downloaded at any time to the front panel program port of the relay via a computer cable connected to the USB port of any personal computer.
A summary of the available functions and a single-line diagram of protection and control features is shown below. For a complete understanding of each feature operation, refer to Chapter 4: feature and show all logic signals passed between individual features. Information related to the selection of settings for each setpoint is also provided.
Setpoints. The logic diagrams include a reference to every setpoint related to a
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–1
Page 12
DESCRIPTION OF THE 845 TRANSFORMER PROTECTION RELAY CHAPTER 1: INTRODUCTION

Description of the 845 Transformer Protection Relay

CPU
Relay functions are controlled by two processors: a Freescale MPC5125 32-bit microprocessor that measures all analog signals and digital inputs and controls all output relays, and a Freescale MPC8358 32-bit microprocessor that controls all the advanced Ethernet communication protocols.
Analog Input and Waveform Capture
Magnetic transformers are used to scale-down the incoming analog signals from the source instrument transformers. The analog signals are then passed through a 11.5 kHz low pass analog anti-aliasing filter. All signals are then simultaneously captured by sample and hold buffers to ensure there are no phase shifts. The signals are converted to digital values by a 16-bit A/D converter before finally being passed on to the CPU for analysis.
The 'raw' samples are scaled in software, then placed into the waveform capture buffer, thus emulating a fault recorder. The waveforms can be retrieved from the relay via the EnerVista 8 Series Setup
Frequency
Frequency measurement is accomplished by measuring the time between zero crossings of the composite signal of three-phase bus voltages, line voltage or three-phase currents. The signals are passed through a low pass filter to prevent false zero crossings. Frequency tracking utilizes the measured frequency to set the sampling rate for current and voltage which results in better accuracy for the Discrete Fourier Transform (DFT) algorithm for off­nominal frequencies.
The main frequency tracking source uses three-phase bus voltages. The frequency tracking is switched automatically by an algorithm to the alternative reference source, i.e., three-phase currents signal or line voltage for the configuration of tie-breaker, if the frequency detected from the three-phase voltage inputs is declared invalid. The switching will not be performed if the frequency from the alternative reference signal is detected invalid. Upon detecting valid frequency on the main source, the tracking will be switched back to the main source. If a stable frequency signal is not available from all sources, then the tracking frequency defaults to the nominal system frequency.
Phasors, Transients, and Harmonics
All waveforms are processed eight times every cycle with a DC decaying removal filter and a Discrete Fourier Transform (DFT). The resulting phasors have fault current transients and all harmonics removed. This results in an overcurrent relay that is extremely secure and reliable and one that will not overreach.
Processing of AC Current Inputs
The DC Decaying Removal Filter is a short window digital filter, which removes the DC decaying component from the asymmetrical current present at the moment a fault occurs. This is done for all current signals used for overcurrent protection; voltage signals use the same DC Decaying Removal Filter. This filter ensures no overreach of the overcurrent protection.
The Discrete Fourier Transform (DFT) uses exactly one cycle of samples to calculate a phasor quantity which represents the signal at the fundamental frequency; all harmonic components are removed. All subsequent calculations (e.g. power, etc.) are based upon the current and voltage phasors, such that the resulting values have no harmonic components. RMS (root mean square) values are calculated from one cycle of samples prior to filtering.
Protection Elements
All voltage, current and frequency protection elements are processed eight times every cycle to determine if a pickup has occurred or a timer has expired. The voltage and current protection elements use RMS current/voltage, or the magnitude of the phasor.
software for display and diagnostics.
1–2 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 13
894014A3.CDR
Winding 3
Amps
Amps
50/87
87T
Block
3
3
Calculate Restraint
Amps
Calculate
Operate
Amps
Metering
Transient Recorder
Event Recorder
Fault Report Data Logger
Calculate
2nd and 5th
Harmonics
Harmonic Restraint
59N 24
Winding 1
Harmonics
Amps Amps
51N-1
50N-1
51N-2
50N-2
Calculate
3I_0
Calculate
3I_0
Amps
50P-2
51P-2
50P-1
55
51P-1
50BF-1
50G-1
51G-1
87G-1
50G-2
51G-2
87G-2
81R81U 81O
RTD input
67P
67N
3V_0
Amps
Harmonics
50BF-2
AFP
59P 27P 27X
845
Тransformer Protection System
67G-1 67G-2
59X
Winding 2
3
33
T.C.
Tap
Position
OLTC
Failure
3VTs
49
Harmonics
Amps
50P-3
51P-3
50BF-3
VTFF
32
59_2 25
51_2
50_2
LIGHT
CHAPTER 1: INTRODUCTION DESCRIPTION OF THE 845 TRANSFORMER PROTECTION RELAY
Figure 1-1: Single Line Diagram
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–3
Page 14
DESCRIPTION OF THE 845 TRANSFORMER PROTECTION RELAY CHAPTER 1: INTRODUCTION
Table 1-1: ANSI Device Numbers and Functions
ANSI Device Description
24 Volts per Hertz 25 Synchrocheck 27P Phase Undervoltage 27X Auxiliary Undervoltage 32 Directional Power 49 Hottest Spot Temperature
Aging Factor
Loss of Life 50/87 Instantaneous Differential Overcurrent 50BF Breaker Failure 50G Ground Instantaneous Overcurrent 50N Neutral Instantaneous Overcurrent 50P Phase Instantaneous Overcurrent 50_2 Negative Sequence Instantaneous Overcurrent 51G Ground Time Overcurrent 51N Neutral Time Overcurrent 51P Phase Time Overcurrent 51_2 Negative Sequence Time Overcurrent 55 Power Factor 59N Neutral Overvoltage 59P Phase Overvoltage 59X Auxiliary Overvoltage 59_2 Negative Sequence Overvoltage 67G Ground Directional Element 67N Neutral Directional Element 67P Phase Directional Element 81O Overfrequency 81U Underfrequency 81R Frequency Rate of Change 87G Restricted Ground Fault (RGF) 87T Transformer Differential AFP Arc Flash Protection VTFF Voltage Transformer Fuse Failure
Table 1-2: Other Device Functions
Description
Analog Input Analog Output Breaker Arcing Current (I2t) Breaker Control Breaker Health Data Logger Demand Digital Counters Event Recorder Fault Report
1–4 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 15
CHAPTER 1: INTRODUCTION DESCRIPTION OF THE 845 TRANSFORMER PROTECTION RELAY
Description
Flexelements FlexLogic Equations Flexstates IEC 61850 Communications Metering: current, voltage, power, PF, energy, frequency, harmonics, THD Modbus User Map Non-volatile Latches OPC-UA Communications Output Relays Setpoint Groups (6) Transformer Dissolved Gas Analysis Transformer Energization Reports Transformer Integrated Fault Report Transformer Overload Transformer Loss of Life Trip Bus (6) Transient Recorder (Oscillography) Trip and Close Coil Monitoring User-programmable LEDs User-programmable Pushbuttons Virtual Inputs (32) Virtual Outputs (32)
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–5
Page 16
Setpoints
Device
System
Inputs
Outputs
Protection
Monitoring
Control
FlexLogic
S
tatus
Switches
Contact Inputs
Metering
Summary
Currents
Voltages
Frequency
Harmonics
Power
Energy
Current Demand
Records
Events
Fault Reports
Breakers
Remote Modbus Device
Targets
Directional Power
Data Logger
Volts per Hertz
Digital Counters
RTDs
RTD Maximums
FlexElements
Arc Flash
Syncrocheck
Testing
Output Relays
Virtual Inputs
Information
Device Status
Clock
Arc Flash
Virtual Outputs
Communications
PTP Status
Flex States
Last Trip Data
Breakers
Summary
Transformer
Harmonic Magnitude
Transients
Clear Records
Power Factor
Analog Inputs
DESCRIPTION OF THE 845 TRANSFORMER PROTECTION RELAY CHAPTER 1: INTRODUCTION
Figure 1-2: Main Menu Hierarchy
1–6 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 17
CHAPTER 1: INTRODUCTION SECURITY OVERVIEW

Security Overview

The following security features are available:
BASIC SECURITY
The basic security feature is present in the default offering of the 845 relay. The 845 introduces the notion of roles for different levels of authority. Roles are used as login names with associated passwords stored on the device. The following roles are available at present: Administrator, Operator, Factory and Observer, with a fixed permission structure for each one. Note that the Factory role is not available for users, but strictly used in the manufacturing process.
The 845 can still use the Setpoint access switch feature, but enabling the feature can be done only by an Administrator. Setpoint access is controlled by a keyed switch to offer some minimal notion of security.
CYBERSENTRY
The CyberSentry Embedded Security feature is a software option that provides advanced security services. When the software option is purchased, the Basic Security is automatically disabled.
CyberSentry provides security through the following features:
An Authentication, Authorization, Accounting (AAA) Remote Authentication Dial-In User Service (RADIUS) client that is centrally managed, enables user attribution, and uses secure standards based strong cryptography for authentication and credential protection.
A Role-Based Access Control (RBAC) system that provides a permission model that
device operations and configurations based on specific roles
devices using the Secure Shell (SSH) protocol, the
FASTPATH:
allows access to 845 and individual user accounts configured on the AAA server. At present the defined roles are: Administrator, Operator and Observer.
Strong encryption of all access and configuration network messages between the EnerVista software and 845 Advanced Encryption Standard (AES), and 128-bit keys in Galois Counter Mode (GCM) as specified in the U.S. National Security Agency Suite B extension for SSH and approved by the National Institute of Standards and Technology (NIST) FIPS-140-2 standards for cryptographic systems.
Security event reporting through the Syslog protocol for supporting Security Information Event Management (SIEM) systems for centralized cyber security monitoring.
There are two types of authentication supported by CyberSentry that can be used to access the 845 device:
Device Authentication – in which case the authentication is performed on the
device itself, using the predefined roles as users (No RADIUS involvement).
845 – 845 authentication using local roles may be done either from the front panel or
through EnerVista.
Server Authentication - in which case the authentication is done on a RADIUS server, using individual user accounts defined on the server. When the user accounts are created, they are assigned to one of the predefined roles recognized by the 845
845 authentication using RADIUS server may be done only through EnerVista.
WiFi and USB do not currently support CyberSentry security. For this reason WiFi is disabled by default if the CyberSentry option is purchased. The user can enable WiFi, but be aware that doing so violates the security and compliance model that CyberSentry is supposed to provide.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–7
Page 18
845 ORDER CODES CHAPTER 1: INTRODUCTION
NOTE
When both 845 device and server authentication are enabled, the 845 automatically directs authentication requests to the 845
device or the respective RADIUS server, based
on user names. If the user ID credential does not match one of the device local accounts,
automatically forwards the request to a RADIUS server when one is provided. If a
the 845 RADIUS server is provided, but is unreachable over the network, server authentication requests are denied. In this situation, use local 845
system.
845
device accounts to gain access to the
USER ROLES
User Access Levels are used to grant varying permissions to specific user roles. User roles are used by both Basic Security and CyberSentry.
The following user roles are supported:
Administrator: The Administrator role has complete read and write access to all settings and commands. The role does not allow concurrent access. The Administrator role also has an operand to indicate when it is logged on.
Operator: The Operator role is present to facilitate operational actions that may be programmed and assigned to buttons on the front panel. The Operator has read/write access to all settings under the command menu/section. The Operator can view settings from EnerVista or the front panel but does not have the ability to change any settings. This role is not a concurrent role.
Observer: The Observer role has read-only access to all 845 settings. This role allows concurrent access. The Observer is the default role if no authentication has been done to the device. This role can download settings files and records from the device.
Factory: This is an internal non-user accessible role used for manufacturing diagnostics. The ability to enable or disable this role is a security setting that the Administrator controls.
GENERAL RULES FOR USER ROLES WITH CYBERSENTRY
1. The only concurrent role is Observer. If the user is logged in through serial, front panel, or over the network, that counts as the role being logged in for concurrency reasons.
2. Both EnerVista and the front panel provide a one-step logoff. For the front panel, the root menu has a logoff command. From EnerVista right-clicking on a device and providing a logoff function from the context menu is sufficient.
3. The EnerVista Login Screen has “User Name:” and “Password:” fields for the default remote (Radius) authentication, but when a “Local Authentication” checkbox is selected the “User Name:” field changes to a drop down menu where the user can select one of the predefined roles on the 845.

845 Order Codes

NOTE:
NOTE:
1–8 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Support of some of the features described in the "Setpoints" section are order code dependent. Each 8 Series unit is ordered with a number of required and optional modules. Each of these modules can be supplied in a number of configurations specified at the time of ordering.
Refer to https://www.gegridsolutions.com/multilin/catalog/845.htm for available order code combinations.
The information to specify an 845 relay is provided in the following Order Code figure:
Page 19
CHAPTER 1: INTRODUCTION 845 ORDER CODES
845  E ** ** ** * * * A * * * * * * * * * * * * N
Interface 845 | | | | | |||||||||||||||| 845 Transformer Protection System Application E | | | | | | | | | | | | | | | | | | | | Standard
Phase Currents ³ Slot J Bank 1/2
NN||||||||||||||||||| Two windings, no voltage
P1||||||||||||||||||| 1A three-phase current inputs (J1) with voltage (J2) P5||||||||||||||||||| 5A three-phase current inputs (J1) with voltage (J2)
Phase Currents ³ Slot K Bank 1/2
M1 | | | | | | | | | | | | | | | | | | 1A three-phase inputs (K1), 1A three-phase inputs (K2) M5 | | | | | | | | | | | | | | | | | | 5A three-phase inputs (K1), 5A three-phase inputs (K2) MX | | | | | | | | | | | | | | | | | | 5A three-phase inputs (K1), 1A three-phase inputs (K2) H1 | | | | | | | | | | | | | | | | | | 1A three-phase inputs (K1) - two windings with voltage H5 | | | | | | | | | | | | | | | | | | 5A three-phase inputs (K1) - two windings with voltage
R1 | | | | | | | | | | | | | | | | | |
1A three-phase inputs (K1), 1A three-phase inputs (K2) - three windings with voltage
R5 | | | | | | | | | | | | | | | | | |
5A three-phase inputs (K1), 5A three-phase inputs (K2) - three windings with voltage
Ground Currents G1 | |||||||||||||||| 1A ground inputs
G5||||||||||||||||| 5A ground inputs Q1||||||||||||||||| 5A, 1A - (NN+MX) or (P5+H1) - In line with Phase Current Q2||||||||||||||||| 5A (J1) + 1A (K1) + 1A (K2) Q3||||||||||||||||| 1A (J1) + 5A (K1) + 5A (K2)
Power Supply L | | | | | | | | | | | | | | | | 24 to 48 V DC
H | | | | | | | | | | | | | | | | 110 to 250 V DC/110 to 230 V AC
Slot B - LV I/O
N||||||||||||||| None R||||||||||||||| 6 X RTDS (Pt100, Ni100, Ni120)
S||||||||||||||| 6 X RTDS (Pt100, Ni100, Ni120, Cu10)
Slot C- LV I/O
N | | | | | | | | | | | | | | None R | | | | | | | | | | | | | | 6 X RTDS (Pt100, Ni100, Ni120) S | | | | | | | | | | | | | | 6 X RTDS (Pt100, Ni100, Ni120, Cu10)
Slot F - HV I/O A |||||||||||||
2 Form A (Vmon), 3 Form C, 7 Digital Inputs (Low/High Voltage, Int/Ext Supply)
Slot G - HV I/O
N | | | | | | | | | | | | None
A
||||||||||||||||||||||||2 Form A (Vmon), 3 Form C, 7 Digital Inputs (Low/High Voltage, Int/Ext
Supply)
L | | | | | | | | | | | | 7 DcmA O/P + 4 DcmA I/P + 1 RTD
Slot H - HV I/O
N||||||||||| None (High Voltage I/O) F||||||||||| 10 Digital Inputs + 4 Arc Flash Inputs
A
||||||||||||||||||||||2 Form A (Vmon), 3 Form C, 7 Digital Inputs (Low/High voltage, Int/Ext
supply)
Faceplate M | | | | | | | | | | Basic = Membrane Keypad
G | | | | | | | | | | Standard = Rugged Keypad
Current Protection
S||||||||| Basic: 87T, 50/87, 50P, 50N, 50G, 51P, 51N, 51G, Transformer Overload
M||||||||| Standard: Basic + 50_2, 51_2, RGF
A||||||||| Advanced: Standard + 67P, 67G, 67N (requires voltage selection)
Voltage Monitoring and Protection N | | | | | | | | None
S | | | | | | | | Standard Protection: 27P, 27X, 59P, 59N, 59X, 81O/U P | | | | | | | | Advanced Protection: Standard Protection + 24, 25, 32, 55, 59_2, 81R
Control B ||||||| Basic: Setpoint Group Control, Virtual Inputs, Trip Bus, Breaker Control
F||||||| Standard: Basic + FlexLogic, 50BF, VTFF
T
||||||||||||||Advanced HMI = Standard + Tab PBs, Annunciator Panel, Configurable
SLDs with Bay Control
Monitoring B
||||||||||||Basic: Breakers Coil Monitoring, Breaker Arcing, Harmonics, THD,
Demand, Trip Counters, Harmonic Derating Factor
C
||||||||||||Standard: Basic + Breaker Health, Health Report, Thermal Elements,
Tap Changer, Learned Data, Energization and Historical Max Record
A | | | | | | Advanced = Standard + Harmonic Detection M | | | | | | M&D = Standard + Dissolved Gas Analysis, Integrated Fault Report
Communications S E
||||||||Standard: Front USB, 1 x Rear RS485: Modbus RTU, DNP3.0, IEC60870-
5-103 + 1 x Ethernet (Modbus TCP, DNP)
1E
||||||||Advanced: Front USB, 1 x Rear RS485 + 2 x Ethernet Fiber, MODBUS
RTU/TCP, DNP3.0, IEC 60870-5-103/104, 1588, SNTP, OPC UA
1P|||| Advanced + PRP 2A|||| Advanced + IEC 61850 2E|||| Advanced + PRP + IEC 61850 3A|||| Advanced + Extended IEC 61850 3E|||| Advanced + PRP + Extended IEC 61850
Figure 1-3: 845 Order Codes
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–9
Page 20
SPECIFICATIONS CHAPTER 1: INTRODUCTION
892800C5.PDF
Advanced Communications Connector N | | | None
S | | | ST, Multi-mode 1310 nm C | | | RJ45, Copper 10/100M
Wireless Communication N | | None
W| | WiFi 802.11
Security B | Basic
A | Advanced: CyberSentry Level 1
Future Option N Not Available
FASTPATH:
FASTPATH:
Harsh Environment Coating is a standard feature on all 8 Series units.
Advanced security is only available with advanced communications (1E, 1P, 2A, 2E, 3A, 3E). When the advanced communications option is selected, the Ethernet port on the main CPU is disabled.
Accessories
18J0-0030 8 Series Depth Reducing Collar - 1 3/8"
18J0-0029 8 Series Depth Reducing Collar - 3"

Specifications

To obtain the total operating time, i.e. from the presence of a trip condition to initiation of a trip, add 8

Device

ANNUNCIATOR PANEL
Number of Elements: ........................................ 1 (36 indicators)
Layout:..................................................................... Grid of 2x2 or 3x3
Data Storage:........................................................Non-volatile memory
Mode:........................................................................ Self-reset, latched, acknowledgeable
Display Text:.......................................................... 3 lines of 15 characters maximum
Visual Indication: ................................................Flashing: 2Hz @ 50% duty cycle
CUSTOM CONFIGURATIONS
Config Mode: ........................................................ Simplified, Regular
ms output relay time to the operate times listed below.

Protection

ARC FLASH HS PHASE/GROUND INSTANTANEOUS OVERCURRENT HS 50P/50G
Current:.................................................................... Phasor Magnitude (special high speed algorithm)
Pickup Level: .........................................................0.050 to 30.000 x CT in steps of 0.001 x CT
Dropout Level:......................................................97 to 98% of Pickup
Level Accuracy: ...................................................For 0.1 to 0.2 x CT: ± 0.2% of reading or 1.5% of rated,
whichever is greater For > 0.2 x CT: ± 1.5% of reading
Operate Time: ......................................................4 ms at >6 x Pickup at 60 Hz
5 ms at >6 x Pickup at 50 Hz 4-8 ms at > (3-6) x Pickup at 60 Hz 4-10 ms at > (3-6) x Pickup at 50 Hz
1–10 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 21
CHAPTER 1: INTRODUCTION SPECIFICATIONS
TRANSFOMER PERCENT DIFFERENTIAL PROTECTION
Differential/Restraint Characteristic:.........Dual Slope, Dual Breakpoint
Minimum Pickup level:......................................0.05 to 1.00 x CT in steps of 0.01
Slope 1 range:.......................................................1 to 100% in steps of 1%
Slope 2 range:.......................................................1 to 100% in steps of 1%
Breakpoint 1:.........................................................0.50 to 2.00 x CT in steps of 0.01
Breakpoint 2:.........................................................2.00 to 30.00 x CT in steps of 0.01
nd
2
harmonic inhibit level: ..............................0.1 to 40.0% in steps of 0.1%
nd
2
harmonic inhibit mode:............................Per-phase, Average, 2-out-of-3, 1-out-of-3
th
5
harmonic inhibit level:...............................1.0 to 40.0% in steps of 0.1%
Dropout level:........................................................97 to 98% of Pickup
Operate time:........................................................< 16/22 ms at >3 x Pickup @60Hz (harmonic inhibits
disabled/enabled) < 18/26 ms at >3 x Pickup @50Hz (harmonic inhibits disabled/enabled)
Level accuracy:....................................................± 0.5% of reading current, or ±1% of rated
TRANSFORMER OVERLOAD
Operating Parameter:.......................................Winding 1, 2, 3 loads
Pickup level:...........................................................50 to 300% in steps of 1%
Dropout level:........................................................97 to 98% of Pickup
Level Accuracy:....................................................Per current input
Operate time:........................................................<25 ms at >3 x Pickup at 60 Hz,
<30 ms at >3 x Pickup at 50 Hz
Timer Accuracy: ..................................................±3% of delay setting or ± ¼ cycle (whichever is greater) from
pickup to operate
INSTANTANEOUS PHASE DIFFERENTIAL FUNCTION
Pickup level:...........................................................3.00 to 30.00 per unit in steps 0.01
Dropout level:........................................................97 to 98% of Pickup
Operate time:........................................................<12 ms at >3 x Pickup@60Hz
<15 ms at >3 x Pickup@50Hz
PHASE/NEUTRAL/GROUND TIME OVERCURRENT (51P/N/G)
Current:....................................................................Phasor or RMS
Pickup Level:..........................................................0.050 to 30.000 x CT in steps of 0.001 x CT
Dropout Level: ......................................................97 to 98% of Pickup
Level Accuracy:....................................................For 0.1 to 2.0 x CT: ±0.5% of reading or ±0.4% of rated,
whichever is greater; For > 2.0 x CT: ±1.5% of reading
Curve Shape:.........................................................IEEE Extremely/Very/Moderately Inverse;
ANSI Extremely/Very/Normally/Moderately Inverse; Definite T ime, IEC A/B/C and Short Inverse; IAC Extremely/Very/Inverse/Short Inverse; FlexCurve A/B/C/D, I
2
t, I4t
Curve Multiplier:...................................................0.05 to 600.00 in steps of 0.01
Reset Time: ............................................................Instantaneous, Timed
Curve Timing Accuracy: ..................................Currents > 1.03 to 20 x pickup: ± 3% of operate time or ± ½
cycle (whichever is greater) from pickup to operate
Voltage Restrained Function (51V):.............Modif ies Pickup from 0.1 < V < 0.9 VT Nominal in a fixed
linear relationship
FASTPATH:
Add 1.5 cycles to the curve time to obtain the TOC operating time, i.e., from fault inception until operation.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–11
Page 22
SPECIFICATIONS CHAPTER 1: INTRODUCTION
NOTE
NOTE
NEGATIVE SEQUENCE TIME OVERCURRENT (51_2)
Operating Parameter: ......................................I_2 (Fundamental Phasor Magnitude)
Pickup Level: .........................................................0.050 to 30.000 x CT in steps of 0.001 x CT
Dropout Level:......................................................97 to 98% of Pickup
Level Accuracy: ...................................................For 0.1 to 2.0 x CT:± 0.5% of reading or ±0.4% of rated,
whichever is greater For > 2.0 x CT: ± 1.5% of reading
Curve Shape:......................................................... IEEE Extremely/Very/Moderately Inverse
ANSI Extremely/Very/Normally/Moderately Inverse IEC Curve A/B/C and Short Inverse IAC Extreme/Very/Inverse/Short Inverse FlexCurve A, FlexCurve B, FlexCurve C, FlexCurve™ D
2
I
t, I4t, Definite Time
Curve Multiplier: ..................................................0.05 to 600.00 in steps of 0.01
Reset Time: ............................................................Instantaneous, Timed
Curve Timing Accuracy:.................................. Currents > 1.1 x pickup: ± 3% of curve delay or ± ½ cycle
(whichever is greater) from pickup to operate
NOTE:
Add 1.5 cycles to the curve time to obtain the TOC operating time, i.e., from fault inception until operation.
PHASE/NEUTRAL/GROUND INSTANTANEOUS OVERCURRENT (50P/N/G)
Current (for Phase IOC only):......................... Phasor or RMS
Current (for Neutral/Ground IOC only):.....Fundamental Phasor Magnitude
Pickup Level: .........................................................0.050 to 30.000 x CT in steps of 0.001 x CT
Dropout Level:......................................................97 to 98% of Pickup
Level Accuracy: ...................................................For 0.1 to 2.0 x CT: ±0.5% of reading or ±0.4% of rated,
whichever is greater For > 2.0 x CT: ±1.5% of reading
Operate Time: ......................................................<12 ms typical at 3 × Pickup at 60 Hz (Phase/Ground IOC)
<16 ms typical at 3 × Pickup at 60 Hz (Neutral IOC) <15 ms typical at 3 × Pickup at 50 Hz (Phase/Ground IOC) <20 ms typical at 3 × Pickup at 50 Hz (Neutral IOC)
NOTE:
Operating time specifications given above are applicable when RMS inputs are used. Typical times are average operate times over multiple test cases.
Timer Accuracy:.................................................. ±3% of delay setting or ± ¼ cycle (whichever is greater) from
pickup to operate
NEGATIVE SEQUENCE INSTANTANEOUS OVERCURRENT (50_2)
Current:.................................................................... I_2 Fundamental Phasor Magnitude
Pickup Level: .........................................................0.050 to 30.000 x CT in steps of 0.001 x CT
Dropout Level:......................................................97 to 98% of Pickup
Level Accuracy: ...................................................For 0.1 to 2.0 x CT: ±0.5% of reading or ± 0.4% of rated,
whichever is greater
For > 2.0 x CT: ± 1.5% of reading
Pickup Time Delay: ............................................0.000 to 6000.000 s in steps of 0.001 s
Dropout Time Delay:......................................... 0.000 to 6000.000 s in steps of 0.001 s
Overreach: .............................................................< 2%
Operate Time: ......................................................< 12 ms typical at 3 x Pickup at 60 Hz
< 15 ms typical at 3 x Pickup at 50 Hz
Timer Accuracy:.................................................. ±3% of delay setting or ± ¼ cycle (whichever is greater) from
pickup to operate
1–12 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 23
CHAPTER 1: INTRODUCTION SPECIFICATIONS
PHASE DIRECTIONAL OVERCURRENT (67P)
Relay Connection: ..............................................90º(Quadrature)
Quadrature Voltage:..........................................ABC phase seq.: phase A (Vbc), phase B (Vca), phase C (Vab);
ACB phase seq.: phase A (Vcb), phase B (Vac), phase C (Vba)
Polarizing Voltage Threshold:........................0.050 to 3.000 x VT in steps of 0.001 x VT
Current Sensitivity Threshold:.......................0.05 x CT
Characteristic Angle:.........................................0º to 359º in steps of 1°
Angle Accuracy: ..................................................± 2º
Operation Time (FlexLogic™ operands): ..Reverse to Forward transition: < 12 ms, typically;
Forward to Reverse transition: <8 ms, typically
NEUTRAL DIRECTIONAL OVERCURRENT (67N)
Directionality: .......................................................Co-existing forward and reverse
Polarizing: ...............................................................Voltage, Current, Dual
Polarizing Voltage:..............................................V_0 or VX
Polarizing Current:..............................................Ig
Operating Current: .............................................I_0
Level Sensing:.......................................................3 x (|I_0| – K x |I_1|), Ig
Restraint, K: ...........................................................0.000 to 0.500 in steps of 0.001
Characteristic Angle:.........................................-90º to 90º in steps of 1°
Limit Angle: ............................................................40º to 90º in steps of 1°, independent for forward and
reverse
Angle Accuracy: ..................................................±2º
Pickup Level:..........................................................0.050 to 30.000 x CT in steps of 0.001 x CT
Dropout Level: ......................................................97 to 98% of Pickup
Operate Time (no direction transition):.....< 16 ms at 3 x Pickup at 60 Hz
< 20 ms at 3 x Pickup at 50 Hz
GROUND DIRECTIONAL OVERCURRENT (67G)
Directionality: .......................................................Co-existing forward and reverse
Polarizing: ...............................................................Voltage
Polarizing Voltage:..............................................V_0 or VX
Polarizing Current:..............................................Isg
Operating Current: .............................................Ig
Level Sensing:.......................................................Ig, Isg
Characteristic Angle:.........................................-90º to 90º in steps of 1°
Limit Angle: ............................................................40º to 90º in steps of 1°, independent for forward and
reverse
Angle Accuracy: ..................................................±2º
Pickup Level:..........................................................0.050 to 30.000 x CT in steps of 0.001
Dropout Level: ......................................................97 to 98%
Operate Time (no direction transition):.....< 12 ms typical at 3 x Pickup at 60 Hz
< 15 ms typical at 3 x Pickup at 50 Hz
RESTRICTED GROUND (EARTH) FAULT (87G)
Operating Parameter:.......................................Ia, Ib, Ic and Ig (Fundamental Phasor Magnitude)
Pickup Level:..........................................................0.050 to 30.000 x CT in steps of 0.001 x CT (phase CT)
Ground Supervision Level:..............................0.050 to 30.000 x CT in steps of 0.001 x CT (ground CT)
Dropout Level: ......................................................97 to 98% of Pickup
Slope Range: .........................................................0 to 100% in steps of 1%
Pickup Delay: ........................................................0.000 to 6000.000 s in steps of 0.001 s
Level Accuracy:....................................................For 0.1 to 2.0 x CT: ±0.5% of reading or ±0.4% of rated,
whichever is greater
For > 2.0 x CT: ± 1.5% of reading
Operate Time:.......................................................<25 ms at 1.1 x slope x Imax at 60 Hz, typically
<30 ms at 1.1 x slope x Imax at 50 Hz, typically
Timing Accuracy:................................................±3% of delay setting or ± ¼ cycle (whichever is greater) from
pickup to operate
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–13
Page 24
SPECIFICATIONS CHAPTER 1: INTRODUCTION
PHASE UNDERVOLTAGE (27P)
Voltage:....................................................................Fundamental Phasor Magnitude
Minimum Voltage: .............................................. 0.00 to 1.50 x VT in steps of 0.01 x VT
Pickup Level: .........................................................0.00 to 1.50 x VT in steps of 0.01 x VT
Dropout Level:......................................................102 to 103% of Pickup
Level Accuracy: ...................................................±0.5% of reading from 10 to 208 V
Phases Required for Operation:................... Any one, Any two, All three
Undervoltage Curves:.......................................Definite Time, GE IAV Inverse Time or FlexCurves A/B/C/D
Pickup Time Delay: ............................................0.000 to 6000.000 s in steps of 0.001s
Operate Time: ......................................................< 20 ms at 0.90 x pickup at 60 Hz
< 25 ms at 0.90 x pickup at 50 Hz
Curve Timing Accuracy:.................................. at < 0.90 x pickup: ± 3.5% of curve delay or ± ½ cycle
(whichever is greater) from pickup to operate
AUXILIARY UNDERVOLTAGE (27X)
Operating Parameter: ......................................Vx (Phasor)
Minimum Voltage: .............................................. 0.00 to 1.50 x VT in steps of 0.01 x VT
Pickup Level: .........................................................0.00 to 1.50 x VT in steps of 0.01 x VT
Dropout Level:......................................................102 to 103% of Pickup
Level Accuracy: ...................................................± 0.5% of reading from 10 to 208 V
Undervoltage Curves:.......................................Definite Time, GE IAV Inverse Time or FlexCurves A/B/C/D
Pickup Time Delay: ............................................0.000 to 6000.000 s in steps of 0.001 s
Operate Time: ......................................................< 20 ms at 0.90 x pickup at 60 Hz
< 25 ms at 0.90 x pickup at 50 Hz
Curve Timing Accuracy:.................................. at < 0.90 x pickup: ± 3.5% of curve delay or ± ½ cycle
(whichever is greater) from pickup to operate
PHASE OVERVOLTAGE (59P)
Voltage:....................................................................Fundamental Phasor Magnitude
Pickup Level: .........................................................0.02 to 3.00 x VT in steps of 0.01 x VT
Dropout Level:......................................................97 to 98% of Pickup
Level Accuracy: ...................................................±0.5% of reading from 10 to 208 V
Phases Required for Operation:................... Any one, Any two, All three
Pickup Time Delay: ............................................0.000 to 6000.000 s in steps of 0.001s (Definite Time)
Dropout Time Delay:......................................... 0.000 to 6000.000 s in steps of 0.001s (Definite T ime)
Pickup Accuracy: ................................................Per phase voltage input channel error
Operate Time: ......................................................< 25 ms at 1.1 x pickup at 60Hz
< 30 ms at 1.1 x pickup at 50Hz
Timer Accuracy:..................................................± 3% of delay setting or ± ¼ cycle (whichever is greater)
from pickup to operate
AUXILIARY OVERVOLTAGE (59X)
Operating Parameter: ......................................Vx (Phasor)
Pickup Level: .........................................................0.00 to 3.00 x VT in steps of 0.01 x VT
Dropout Level:......................................................97 to 98% of Pickup
Level Accuracy: ...................................................±0.5% of reading from 10 to 240 V
Overvoltage Curves:.......................................... Definite Time, Inverse Time, FlexCurves A/B/C/D
Pickup Time Delay: ............................................0.000 to 6000.000 s in steps of 0.001s
Dropout Time Delay:......................................... 0.000 to 6000.000 s in steps of 0.001s
Pickup Accuracy: ................................................‘Auxiliary voltage input channel error
Operate Time: ......................................................< 30 ms at 1.1 x pickup at 60Hz
Curve Timing Accuracy:.................................. at >1.1 x PKP: 3.5% of operate time ± ½ cycle (whichever is
greater) from pickup to operate
Timer Accuracy:..................................................± 3% of operate time or ± ½ cycle (whichever is greater)
1–14 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 25
CHAPTER 1: INTRODUCTION SPECIFICATIONS
NEUTRAL OVERVOLTAGE (59N)
Operating Parameter:.......................................3V_0 calculated from phase to ground voltages
Pickup Level:..........................................................0.02 to 3.00 x VT in steps of 0.01 x VT
Dropout Level: ......................................................97 to 98% of Pickup
Level Accuracy:....................................................±0.5% of reading from 10 to 208 V
Neutral Overvoltage Curves: .........................Definite time, FlexCurve A,B,C,D
Pickup Time Delay:.............................................0.000 to 6000.000 s in steps of 0.001 s (Definite Time)
Dropout Time Delay: .........................................0.000 to 6000.000 s in steps of 0.001 s (Def inite T ime)
Operate Time:.......................................................< 25 ms at 1.1 x pickup at 60Hz
< 30 ms at 1.1 x pickup at 50Hz
Curve Timing Accuracy: ..................................at > 1.1 x Pickup: ± 3% of curve delay or ± 1 cycle (whichever
is greater) from pickup to operate
NEGATIVE SEQUENCE OVERVOLTAGE (59_2)
Operating Parameter:.......................................V_2
Pickup Level:..........................................................0.00 to 3.00 x VT in steps of 0.01 x VT
Dropout Level: ......................................................97 to 98% of Pickup
Level Accuracy:....................................................± 0.5% of reading from 10 to 208 V
Pickup Time Delay:.............................................0.000 to 6000.000 s in steps of 0.001 s
Dropout Time Delay: .........................................0.000 to 6000.000 s in steps of 0.001 s
Operate Time:.......................................................< 25 ms at 1.1 x pickup at 60 Hz
< 30 ms at 1.1 x pickup at 50 Hz
Timer Accuracy: .................................................. ± 3% of delay setting or ± ¼ cycle (whichever is greater)
from pickup to operate
VOLTS PER HERTZ (24)
Voltages:..................................................................Phasor only
Pickup Level:..........................................................0.80 to 4.00 in steps of 0.01 pu
Dropout Level: ......................................................97 to 98% of pickup
Level Accuracy:....................................................±0.02 pu
Timing Curves: .....................................................Definite Time; IEC Inverse A/B/C; FlexCurves A, B, C, and D
TD Multiplier: .........................................................0.05 to 600.00 s in steps of 0.01
Reset Delay:...........................................................0.00 to 6000.000 s in steps of 0.01
Timer Accuracy: ..................................................±3% of operate time or ±15 cycles (whichever is greater) for
values greater than 1.1 x pickup
Number of Elements: ........................................2
Number of Elements: ........................................1
DIRECTIONAL POWER (32)
Measured Power: ................................................3-phase
Number of Stages:..............................................2
Characteristic Angle:.........................................0º to 359º in steps of 1°
Calibration Angle: ...............................................0.00º to 0.95º in steps of 0.05°
Power Pickup Range:.........................................–1.200 to 1.200 x Rated Power in steps of 0.001
Pickup Level Accuracy: ....................................± 1% or ± 0.001 x Rated Power, whichever is greater
Hysteresis:..............................................................2% or 0.001 x Rated Power, whichever is greater
Pickup Time Delay:.............................................0.000 to 6000.000 s in steps of 0.001 s
Operate Time:.......................................................< 55 ms at 1.1 x pickup at 60 Hz
< 65 ms at 1.1 x pickup at 50 Hz
Timer Accuracy: ..................................................± 3% of delay setting or ± ¼ cycle (whichever is greater)
from pickup to operate
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–15
Page 26
SPECIFICATIONS CHAPTER 1: INTRODUCTION
UNDERFREQUENCY (81U)
Pickup Level: .........................................................20.00 to 65.00 Hz in steps of 0.01
Dropout Level:......................................................Pickup + 0.03 Hz
Pickup Time Delay: ............................................0.000 to 6000.000 s in steps of 0.001s
Dropout Time Delay:......................................... 0.000 to 6000.000 s in steps of 0.001s
Minimum Operating Voltage:........................ 0.000 to 1.250 x VT in steps of 0.001 x VT
Minimum Operating Current:........................0.000 to 30.000 x CT in steps of 0.001 x CT
Level Accuracy: ...................................................± 0.001 Hz
Timer Accuracy:..................................................± 3% of delay setting or ± ¼ cycle (whichever is greater)
from pickup to operate
Operate Time: ......................................................typically 7.5 cycles at 0.1 Hz/s change
typically 7 cycles at 0.3 Hz/s change typically 6.5 cycles at 0.5 Hz/s change
FASTPATH:
Typical times are average Operate Times including variables such as frequency change instance, test method, etc., and may vary by ± 0.5 cycles.
OVERFREQUENCY (81O)
Pickup Level: .........................................................20.00 to 65.00 Hz in steps of 0.01
Dropout Level:......................................................Pickup - 0.03 Hz
Pickup Time Delay: ............................................0.000 to 6000.000 s in steps of 0.001 s
Dropout Time Delay:......................................... 0.000 to 6000.000 s in steps of 0.001 s
Minimum Operating Voltage:........................ 0.000 to 1.250 x VT in steps of 0.001 x VT
Level Accuracy: ...................................................± 0.001 Hz
Timer Accuracy:..................................................± 3% of delay setting or ± ¼ cycle (whichever is greater)
from pickup to operate
Operate Time: ......................................................typically 7.5 cycles at 0.1 Hz/s change
typically 7 cycles at 0.3 Hz/s change typically 6.5 cycles at 0.5 Hz/s change
FASTPATH:
Typical times are average Operate Times including variables such as frequency change instance, test method, etc., and may vary by ± 0.5 cycles.
FREQUENCY RATE OF CHANGE (81R)
df/dt Trend:............................................................Increasing, Decreasing, Bi-directional
df/dt Pickup Level:..............................................0.10 to 15.00 Hz/s in steps of 0.01 Hz/s
df/dt Dropout Level: ..........................................96% of Pickup Level
df/dt Level Accuracy:........................................ 80 mHz/s or 3.5%, whichever is greater
Minimum Frequency:........................................ 20.00 to 80.00 Hz in steps of 0.01 Hz
Maximum Frequency: ......................................20.00 to 80.00 Hz in steps of 0.01 Hz
Minimum Voltage Threshold:........................ 0.000 to 1.250 x VT in steps of 0.001 x VT
Minimum Current Threshold: ........................0.000 to 30.000 x CT in steps of 0.001 x CT
Pickup Time Delay: ............................................0.000 to 6000.000 s in steps of 0.001 s
Timer Accuracy:..................................................± 3% of delay setting or ± ¼ cycle (whichever is greater)
from pickup to operate
95% Settling Time for df/dt: ..........................< 24 cycles
Operate Time: ......................................................typically 10 cycles at 2 × Pickup
RTD PROTECTION
Pickup:...................................................................... 1°C to 250°C in steps of 1°C
Hysteresis: .............................................................2°C
Timer Accuracy:..................................................<2 s
Elements:................................................................ Trip and Alarm
1–16 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 27
CHAPTER 1: INTRODUCTION SPECIFICATIONS
FLEXELEMENTS
Number of elements: ........................................8
Operating signal:.................................................Any analog actual value, or two values in a differential mode
Operating signal mode: ...................................Signed, or Absolute value
Operating mode:.................................................Level, Delta
Comparison direction: ......................................Over, Under
Pickup Level:..........................................................-30.000 to 30.000 pu in steps of 0.001 pu
Hysteresis:..............................................................0.1 to 50.0% in steps of 0.1%
Delta dt:...................................................................40 msec to 45 days
Pickup and dropout delays:...........................0.000 to 6000.000 s in steps of 0.001 s

Control

ARC FLASH SENSOR/FIBER
Number of Point Sensors: ...............................4
Detection Radius:................................................180 degree
Maximum Fiber Length (Point Sensor): .....18 ft
Fiber Size:................................................................1000 um
Mode:........................................................................Multi-mode
Connector:..............................................................Small Media Interface (SMI)
Fiber Type:..............................................................Plastic Optical Fiber
Bend Radius: .........................................................>25 mm
BREAKER CONTROL
Operation:...............................................................Asserted FlexLogic Operands
Function: .................................................................Opens/closes, blocks, bypasses blocks to the feeder breaker
BREAKER FAILURE
Mode:........................................................................3-pole
Current Supervision:..........................................phase and neutral current (fundamental phasor magnitude)
Current Supervision Pickup:...........................0.050 to 30.000 x CT in steps of 0.001 x CT
Current Supervision Dropout: .......................97 to 98% of pickup
Current Supervision Accuracy:.....................For 0.1 to 2.0 x CT: ± 0.5% of reading or ± 0.4% of rated
(whichever is greater),
For > 2.0 x CT: ± 1.5% of reading
Time Delay:............................................................0.000 to 6000.000 s in steps of 0.001 s
Timer Accuracy: ..................................................± 3% of delay setting or ± ¼ cycle (whichever is greater)
from pickup to operate
Reset Time: ............................................................< 10 ms typical at 2 x Pickup at 60 Hz
< 12 ms typical at 2 x Pickup at 50 Hz
LOCAL CONTROL MODE
Number of Elements: ........................................1
Select Before Operate Mode: ........................Disabled, Enabled
Mode:........................................................................Local Mode ON, Local Mode OFF
Display Status:......................................................LM (local mode) displayed in banner
Tagging:...................................................................Disabled, Enabled
SWITCH CONTROL
Operation:...............................................................Local (PB control and SLD) and Remote (asserted FlexLogic
operands)
Function: .................................................................Opens/Closes the disconnect switch
Timers: .....................................................................0.000 to 6000.000 s in steps of 0.001 s
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–17
Page 28
SPECIFICATIONS CHAPTER 1: INTRODUCTION
SYNCHROCHECK (25)
Maximum Frequency Difference: ...............0.01 to 5.00 Hz in steps of 0.01 Hz for frequency window of
f
± 5 Hz
Maximum Angle Difference:.......................... 1° to 100° in steps of 1°
Maximum Voltage Difference:...................... 10 to 600000 V in steps of 1 V
Hysteresis for Maximum Frequency
Difference: ........................................................0.01 to 0.10 Hz in steps of 0.01 Hz
Breaker Closing Time:.......................................0.000 to 6000.000 s in steps of 0.001 s
Dead Source Function:..................................... None, LB & DL, DB & LL, DB & DL, DB OR DL, DB XOR DL
Dead/Live Levels for Bus and Line: ............0.00 to 1.50 x VT in steps of 0.01 x VT
nom
TRIP BUS
Number of Elements: ........................................ 6
Number of Inputs: ..............................................16
Pickup Time Delay: ............................................0.000 to 6000.000 s in steps of 0.001 s
Dropout Time Delay:......................................... 0.000 to 6000.000 s in steps of 0.001 s
Operate Time: ......................................................< 2 ms at 60 Hz
Timer Accuracy:..................................................± 3% of delay time or ± ¼ cycle (whichever is greater) from
pickup to operate

Monitoring

HARMONIC DERATING
Timer Accuracy:..................................................±3% of delay setting or ±3 cycle (whichever is greater) from
pickup to operate
TRIP CIRCUIT MONITOR (TCM)
Applicable Voltage:............................................ 20 to 250 VDC
Trickle Current:..................................................... 1 to 2.5 mA
Timing Accuracy:................................................ ± 3 % or ± 4 ms, whichever is greater
CLOSE CIRCUIT MONITOR (CCM)
Applicable Voltage:............................................ 20 to 250 VDC
Trickle Current:..................................................... 1 to 2.5 mA
Timing Accuracy:................................................ ± 3 % or ± 4 ms, whichever is greater
BREAKER ARCING CURRENT
Mode:........................................................................ 3-pole
Principle: .................................................................accumulates breaker duty (I
Initiation:................................................................. any operand
Alarm Threshold:.................................................0 to 50000 kA2-cycle in steps of 1 kA2-cycle
Timer Accuracy:..................................................± 3% of delay setting or ± ¼ cycle (whichever is greater)
from pickup to operate
BREAKER HEALTH
Timer Accuracy:.................................................. ± 3% of delay setting or ± 1 cycle (whichever is greater) from
pickup to operate
POWER FACTOR (55)
Switch-In Level:.................................................... 0.01 Lead to 1 to 0.01 Lag in steps of 0.01
Dropout Level:......................................................0.01 Lead to 1 to 0.01 Lag in steps of 0.01
Delay: ....................................................................... 0.000 to 6000.000 s in steps of 0.001 s
Minimum Operating Voltage:........................ 0.00 to 1.25 x VT in steps of 0.01 x VT
Level Accuracy: ...................................................± 0.02
Timer Accuracy:..................................................± 3% of delay setting or ± 1¼ cycle (whichever is greater)
from pickup to operate
FAULT REPORTS
Number of Reports: ...........................................15
Captured Data: ....................................................Pre-fault and fault phasors for all CT and VT banks, pre-fault
and fault trigger operands, user-programmable analog channels 1 to 32
2
t) during fault
1–18 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 29
CHAPTER 1: INTRODUCTION SPECIFICATIONS
DEMAND
Measured Values:................................................Phase A/B/C present and maximum current
Measurement Type:...........................................Thermal Exponential, 90% response time (programmed): 5,
10, 15, 20, 30 minutes Block Interval / Rolling Demand, time interval (programmed):
5, 10, 15, 20, 30 minutes
Current Pickup Level:.........................................10 to 10000 in steps of 1 A
Dropout Level: ......................................................96-98% of Pickup level
Level Accuracy:....................................................± 2%
WINDING HOTTEST-SPOT
Operating Quantity:...........................................Computed temperature in ºC
Pickup Level:..........................................................50 to 300ºC in steps of ºC (122ºF to 572ºF in steps of 1ºF)
Dropout Level: ......................................................1ºC below pickup
Pickup Delay: ........................................................0 to 60000 minutes in steps of 1 min
AGING ACCELERATION FACTOR
Operating Quantity:...........................................Computed Aging Acceleration Factor, per-unit
Pickup Level:..........................................................1 pu to 10 pu in steps of 0.1 pu
Pickup Delay: ........................................................0 to 60000 minutes in step of 1 min
XFMR LOSS OF LIFE
Operating Quantity:...........................................Computed Accumulated Transformer Loss of Life, hours
Pickup Level:..........................................................0 to 300000 hours in steps of 1 hour
TAP C H A N G ER FAILURE
Operating Parameter:.......................................Tap Changer Position
Time Delay:............................................................0.00 to 600.00 s
Timer Accuracy: ..................................................±3% of delay setting or ±2 cycles (whichever is greater) from
pickup to operate
HARMONIC DETECTION
Operating Parameter:.......................................Current 2nd, 3rd, 4th, 5th harmonic or THD per phase
Timer Accuracy: ..................................................Harmonics: ±3% of delay setting or ±1/4 cycle (whichever is
greater) from pickup to operate
THD: ±3% of delay setting or ±3 cycles (whichever is greater)
from pickup to operate

Recording

TRANSIENT RECORDER
Default AC Channels:......................................... currents + 4 voltages
Configurable Channels: ...................................16 analog and 64 digital channels
Sampling Rate:.....................................................128/c, 64/c, 32/c, 16/c, 8/c
Trigger Source:.....................................................Any element pickup, dropout or operate, digital input or
output change of state, FlexLogic operand
Trigger Position:...................................................0 to 100%
Storage Capability: ............................................Non-volatile memory
EVENT DATA
Number of Records:...........................................1024 (matches the existing Event Recorder)
Data Storage:........................................................Non-volatile memory
Time-tag Accuracy: ...........................................One microsecond
Settings:...................................................................64 Configurable FlexAnalog parameters,
Event Selector
Actuals:....................................................................Selected Event Number,
Timestamp of Selected Event ,
Cause of Selected Event,
64 Configurable FlexAnalog values
Commands: ...........................................................None (using existing Clear Event Recorder)
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–19
Page 30
SPECIFICATIONS CHAPTER 1: INTRODUCTION
DATA LOGGER
Data Logger channels:..................................... 16
Data Logger Rate: ..............................................1 cycle, 1 sec., 30 sec., 1 min., 15 min., 30 min., 1 hour
Inputs: ......................................................................Any analog parameter from the list of available analog
parameters
Data Collection Mode:...................................... Continuous, Triggered
Trigger Source:..................................................... Any digital flag from the list of digital flags
Trigger Position:................................................... 0 to 50% in steps of 1%
Channel 1(16) Mode:.......................................... Sample, Min, Max, Mean
EVENT RECORDER
Number of events:.............................................. 1024
Header:....................................................................relay name, order code, firmware revision
Content:................................................................... any element pickup, any element operate, digital input
change of state, digital output change of state, self-test
events
Data Storage:........................................................non-volatile memory
Time-tag Accuracy:........................................... to one microsecond
LAST TRIP DATA
Number of Records: ..........................................1
Data Storage:........................................................Non-volatile memory
Time-tag Accuracy:........................................... One microsecond
Actuals:....................................................................Event Number of Last Trip,
Timestamp of Last Trip,
Cause of Last Trip,
64 Configurable FlexAnalog values
Commands:........................................................... Clear Last Trip Data

User-Programmable Elements

FLEXLOGIC
Lines of code:........................................................ 1024
Supported operations: .....................................NOT, XOR, OR (2 to 16 inputs), AND (2 to 16 inputs), NOR (2 to
Inputs: ......................................................................any logical variable, contact, or virtual input
Number of timers: .............................................. 32
Pickup delay: ........................................................0 to 60000 (ms, sec., min.) in steps of 1
Dropout delay:..................................................... 0 to 60000 (ms, sec., min.) in steps of 1
Timer accuracy: .................................................. ±3% of delay setting or ±¼ cycle (whichever is greater) from
FLEXELEMENTS
Number of elements:........................................ 8
Operating signal: ................................................Any analog actual value, or two values in a differential mode
Operating signal mode:................................... Signed, or Absolute value
Operating mode:.................................................Level, Delta
Comparison direction:......................................Over, Under
Pickup Level: .........................................................-30.000 to 30.000 pu in steps of 0.001 pu
Hysteresis: .............................................................0.1 to 50.0% in steps of 0.1%
Delta dt:...................................................................40 msec to 45 days
Pickup and dropout delays:........................... 0.000 to 6000.000 s in steps of 0.001 s
FLEXSTATES
Number of States: ..............................................256 logical variables grouped under 16 Modbus addresses
Programmability:................................................ Any FlexLogic operand, any digital input, any virtual input,
16 inputs), NAND (2 to 16 inputs), latch (reset-dominant),
edge detectors, timers
pickup to operate
any remote input
1–20 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 31
CHAPTER 1: INTRODUCTION SPECIFICATIONS
NON-VOLATILE LATCHES
Type: .........................................................................Set-dominant or Reset-dominant
Range: ......................................................................16 individually programmed
Output:.....................................................................Stored in non-volatile memory
Execution sequence: .........................................As input prior to protection, control and FlexLogic
FLEXCURVES
Number: ..................................................................4 (A through D)
Reset points:..........................................................40 (0.00 to 0.98 x pickup)
Operate points: ....................................................80 (1.03 to 20.0 x pickup)
Time delay: ............................................................0 to 200,000,000 ms in steps of 1 ms
Saturation level:...................................................20 times the pickup level
TAB PUSHBUTTONS
Number of elements: ........................................1 (20 Tab Pushbuttons)
Data Storage:........................................................Non-volatile memory
Mode:........................................................................Self-reset, latched
Display Message:................................................2 lines; 15 characters per line
Dropout Timer: .....................................................0.000 to 60.000 s in steps of 0.005
Auto-reset Timer: ................................................0.2 to 600.0 s in steps of 0.1
Hold Timer: ............................................................0.1 to 10.0 s in steps of 0.1
Timer Accuracy: ..................................................±3% of delay setting or ±¼ cycle (whichever is greater) from
pickup to operate
USER-PROGRAMMABLE LEDS
Number: ..................................................................17 (14 + 3 PB LEDS) for Membrane and Rugged Front Panels
Programmability:................................................any logic variable, contact, or virtual input
Reset mode:........................................................... self-reset or latched
USER-PROGRAMMABLE PUSHBUTTONS
Number of pushbuttons:.................................3 (Membrane and Rugged Front Panels)
Mode:........................................................................Self-reset, latched
Display message:................................................2 lines of 13 characters on each line
Dropout timer:......................................................0.000 to 60.000 s in steps of 0.005
Auto-reset timer:.................................................0.2 to 600.0 s in steps of 0.1
Hold timer:..............................................................0.0 to 10.0 s in steps of 0.1

Metering

RMS PARAMETERS Currents
Parameters: ...........................................................Phase A, B, C, Neutral, Ground
Accuracy:................................................................± 0.25% of reading or ± 0.2% of rated (whichever is greater)
from 0.1 to 2.0 x CT ± 1% of reading > 2.0 x CT
Voltages
Parameters: ...........................................................Wye VTs: A-n, B-n, C-n, A-B, B-C, C-A, Average Phase, Neutral
and Residual Delta VTs: A-B, B-C, C-A, Neutral and Residual
Accuracy:................................................................± 0.5% of reading from 15 to 208 V
± 1% for open Delta connections
Real Power (Watts)
Range: ......................................................................-214748364.8 kW to 214748364.7 kW
Parameters: ...........................................................3-phase; per phase if VT is Wye
Accuracy:................................................................± 1.0% of reading or 0.2 kW (whichever is greater) at -0.8 <
PF -1.0 and 0.8 < PF < 1.0
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–21
Page 32
SPECIFICATIONS CHAPTER 1: INTRODUCTION
Reactive Power (Vars)
Range:......................................................................-214748364.8 kvar to 214748364.7 kvar
Parameters:...........................................................3-phase; per phase if VT is Wye
Accuracy: ...............................................................± 1.0% of reading or 0.2 kvar (whichever is greater) at -0.2 <
PF 0.2
Apparent Power (VA)
Range:......................................................................0 kVA to 214748364.7 kVA
Parameters:...........................................................3-phase; per phase if VT is Wye
Accuracy: ...............................................................± 1.0% of reading or 0.2 kVA (whichever is greater)
Power Factor
Parameters:...........................................................3-phase; per phase if VT is Wye
Range:......................................................................0.01 Lag to 1.00 to 0.01 Lead
Accuracy: ...............................................................± 0.02 for 50 Hz and 60 Hz; ± 0.05 for 25 Hz
Watt-hours (positive and negative)
Range:......................................................................- 2147483.648 MWh to 2147483.647 MWh
Parameters:...........................................................3-phase only
Update Rate:......................................................... 50 ms
Accuracy: ...............................................................± 2.0% of reading
Var-hours (positive and negative)
Range:......................................................................- 2147483.648 Mvarh to 2147483.647 Mvarh
Parameters:...........................................................3-phase only
Update Rate:......................................................... 50 ms
Accuracy: ...............................................................± 2.0% of reading
PHASORS Current
Parameters:...........................................................Phase A, B, C, Neutral and Ground
Magnitude Accuracy: .......................................± 0.5% of reading or ± 0.2% of rated (whichever is greater)
from 0.1 to 2.0 x CT
± 1.0% of reading > 2.0 x CT
Angle Accuracy: ..................................................2° (3° for 25 Hz)
Voltages
Parameters:...........................................................Wye VTs: A-n, B-n, C-n, A-B, B-C, C-A, Average Phase, Neutral
and Residual;
Delta VTs: A-B, B-C, C-A, Neutral and Residual
Magnitude Accuracy: .......................................± 0.5% of reading from 15 to 208 V;
± 1% for open Delta connections;
± 10% for 25 Hz with 150 V <V < 208V
Angle Accuracy: .................................................. 0.5° (15 V <V < 208 V)
FREQUENCY
Range:......................................................................2.000 to 90.000 Hz
Accuracy at:..........................................................V = 15 to 208 V: ± 0.01 Hz (input frequency 15 to 70 Hz);
I = 0.1 to 0.4 x CT: ± 0.020 Hz (input frequency 15 to 70 Hz);
I > 0.4 x CT: ± 0.01 Hz (input frequency 15 to 70 Hz)
CURRENT AND VOLTAGE HARMONICS
Parameters:...........................................................Magnitude of each harmonic and THD
Range:......................................................................2
nd
to 25th harmonic: per-phase displayed as % of f1 fundamental frequency THD: per-phase displayed as % of f
1
1–22 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 33
CHAPTER 1: INTRODUCTION SPECIFICATIONS
NOTE
DEMAND
Measured Values:................................................Phase A/B/C present and maximum current
Measurement Type:...........................................Thermal Exponential, 90% response time (programmed): 5,
10, 15, 20, 30 minutes Block Interval / Rolling Demand, time interval (programmed):
5, 10, 15, 20, 30 minutes
Current Pickup Level:.........................................10 to 10000 in steps of 1 A
Dropout Level: ......................................................96-98% of Pickup level
Level Accuracy:....................................................± 2%
NOTE:
Factory tested at 25°C

Inputs

AC CURRENTS
CT Rated Primary:...............................................1 to 12000 A
CT Rated Secondary:.........................................1 A or 5 A based on relay ordering
Burden: ....................................................................< 0.2 VA at rated secondary
Short Term CT Withstand:...............................1 second at 100 x rated current
2 seconds at 40 x rated current
continuous at 3 x rated current
AC VOLTAGE
VT Range:................................................................10 to 260 V
Nominal Frequency:..........................................20 to 65 Hz
Burden: ....................................................................<0.25 VA at 120 V
Conversion Range: .............................................1 to 275 V
Voltage Withstand:.............................................continuous at 260 V to neutral
1 min/hr at 420 V to neutral
ANALOG INPUTS
Current Input (mA DC):......................................0 to 1mA, 0 to 5mA, 0 to 10mA, 0 to 20mA, 4 to 20mA
(configurable)
Input Impedance:................................................375 ± 10%
Conversion range: ..............................................0 to +21 mA DC
Accuracy:................................................................± 1% of full scale,
Type: .........................................................................Passive
Analog Input Supply:.........................................+24 V DC at 100 mA max.
Sampling Interval: ..............................................Typically 500 ms
FREQUENCY
Nominal frequency setting: ...........................50 Hz, 60 Hz
Sampling frequency:.........................................64 samples per power cycle
128 samples per power cycle (available for transient
recorder
Tracking frequency range:.............................3 to 72 Hz
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–23
Page 34
SPECIFICATIONS CHAPTER 1: INTRODUCTION
ARC FLASH SENSOR/FIBER
Number of Point Sensors:...............................4
Detection Radius: ...............................................180 degree
Maximum Fiber Length (Point Sensor):..... 18 ft
Fiber Size: ...............................................................1000 um
Mode:........................................................................ Multi-mode
Connector: .............................................................Small Media Interface (SMI)
Fiber Type: .............................................................Plastic Optical Fiber
Bend Radius:......................................................... >25 mm
CONTACT INPUTS
Number of Inputs: ..............................................Based on relay ordering
Type:......................................................................... Wet or Dry
Wet Contacts:....................................................... 300 V DC maximum
Selectable thresholds:...................................... 17, 33, 84, 166 VDC
Tolerance:............................................................... ±20%
Recognition time:................................................ 1 ms (typical)
Debounce time: ................................................... 0.0 to 16.0 ms in steps of 0.5 ms
Continuous current draw (burden):............2 mA
CLOCK
Setup: .......................................................................Date and T ime, Daylight Saving Time, UTC (Coordinated
Universal Time)
Backup Retention: .............................................. 1 hour
IRIG-B INPUT
Auto-detect: ..........................................................DC and AM
Amplitude Modulation:..................................... 1 V to 10 V pk-to-pk
DC Shift:................................................................... TTL
Input Impedance: ...............................................40 k
Isolation: .................................................................2 kV
RTD INPUTS
Types (3-wire):...................................................... 100 Platinum, 120 Nickel, 100 Nickel, 10 Copper
Sensing current: .................................................. 5 mA
Range:......................................................................–40 to +250°C (-40 to +482°F)
Accuracy: ...............................................................±2°C (±4°F)
Isolation: .................................................................36 V pk-pk (a group of RTDs to ground)
Lead Resistance:................................................. 25 Ohms max. per lead for platinum or nickel and 3 Ohms
max. per lead for copper RTDs
OHMS INPUT
Type:......................................................................... Resistance (ohms)
Range:......................................................................0 to 500 or 0.5 to 5.1 k
Bias current:.......................................................... 1.9 mA through the full range
Accuracy: ...............................................................± 1% (of full scale based on input range)
TAP C H A N G ER
Operating Parameter: ......................................BCD, ohms In 1, Analog Ip 1
Tap Changer Range:..........................................-19 to +39
Accuracy: ...............................................................Per Input accuracy
1–24 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 35
CHAPTER 1: INTRODUCTION SPECIFICATIONS

Outputs

ANALOG OUTPUTS
Range (configurable):........................................0 to 1mA, 0 to 5mA, 0 to 10mA, 0 to 20mA, 4 to 20mA
Max. load resistance:.........................................10 k @ 1 mA,
600 @ 20 mA
Accuracy:................................................................± 1% of full scale
Isolation:.................................................................. 500V DC for one minute (functional isolation between analog
inputs and output group; and each group of chassis)
Driving Signal:.......................................................any Analog quantity
Sampling Interval: ..............................................Typically 500 ms
Upper and lower limit
(for the driving signal):................................-90 to 90 pu in steps of 0.001
TRIP/CLOSE OUTPUT RELAYS
(Relays #1 and #2 from Slot F, Relays #9 and #10 from Slot G)
Type: .........................................................................FORM-A
Configuration:.......................................................2 (two) electromechanical
Contact material: ................................................silver-alloy
Operate time:........................................................<8 ms
Continuous current:...........................................10 A
Make and carry for 0.2s:..................................30 A per ANSI C37.90
Break (DC inductive, L/R=40 ms):.................24 V / 1 A
48 V / 0.5 A
125 V / 0.3 A
250 V / 0.2 A
Break (DC resistive):............................................24 V / 10 A
48 V / 6 A
125 V / 0.5 A
250 V / 0.3 A
Break (AC inductive):..........................................720 VA @ 250 VAC Pilot duty A300
Break (AC resistive):............................................277 VAC / 10 A
Operation Mode:..................................................Self-Reset , Latched, Pulsed, Non-Failsafe, Failsafe
FORM-A VOLTAGE MONITOR
Applicable voltage:.............................................20 to 250 VDC
Trickle current:......................................................1 to 2.5 mA
Timer acurracy:...................................................± 3% of operate time or ± 1/4 cycle (whichever is greater)
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–25
Page 36
SPECIFICATIONS CHAPTER 1: INTRODUCTION
AUXILIARY OUTPUT RELAYS
(Relays #3, #4 and the Critical Failure Relay from Slot F, and Relays #11, #12 and #16 from Slot G)
Type:......................................................................... FORM-C
Configuration: ......................................................electromechanical
Contact material:................................................silver-alloy
Operate time:........................................................ <8 ms
Continuous current:........................................... 10 A
Make and carry for 0.2s: .................................30 A per ANSI C37.90
Break (DC inductive, L/R=40 ms):.................24 V / 1 A
48 V / 0.5 A 125 V / 0.3 A 250 V / 0.2 A
Break (DC resistive): ........................................... 24 V / 10 A
48 V / 6 A 125 V / 0.5 A
250 V / 0.3 A
Break (AC inductive):.......................................... 720 VA @ 250 VAC Pilot duty A300
Break (AC resistive):............................................ 277 VAC / 10 A
Operation Mode: ................................................. Self-Reset, Latched, Pulsed, Non-Failsafe, Failsafe
Breaking Capacity:.............................................For Form-C relays the following ratings are applied to meet
UL508 requirements: 1 second “ON”/10 seconds “OFF” per
output relay at maximum rating
FASTPATH:
For 2 IO_A module configuration the following ratings are applied to meet UL508 requirements: 1 second “on”/ 10 seconds “off” per output relay at max rating.
PULSED OUTPUTS
Mode:........................................................................ 3-phase positive and negative active energy measurement,
Principle: .................................................................Pulsed output is energized for one second and then de-

Power Supply

POWER SUPPLY
Nominal DC Voltage:.........................................125 to 250 V
Minimum DC Voltage:.......................................88 V
Maximum DC Voltage:...................................... 300 V
Nominal AC Voltage:..........................................100 to 240 V at 50/60 Hz
Minimum AC Voltage:........................................88 V at 50 to 60 Hz
Maximum AC Voltage:......................................265 V at 50 to 60 Hz
Voltage loss ride through:...............................20 ms duration
POWER SUPPLY (FOR “L” DC ONLY OPTION)
Nominal DC Voltage:.........................................24 V to 48 V
Minimum DC Voltage:.......................................20 V
Maximum DC Voltage:...................................... 60 V
POWER CONSUMPTION
Typical: ....................................................................20 W / 40 VA
Maximum: ..............................................................34 W / 70 VA
3-phase positive and negative reactive energy
measurements
energized for one second after the programed energy
increment.
1–26 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 37
CHAPTER 1: INTRODUCTION SPECIFICATIONS

Communications

ETHERNET – BASE OFFERING
Modes:......................................................................10/100 Mbps
One Port: .................................................................RJ45
Protocol: ..................................................................Modbus TCP
ETHERNET – CARD OPTION “C” - 2X COPPER (RJ45) PORTS
Modes:......................................................................10/100 MB
Two Ports:...............................................................RJ45 (with this option both enabled ports are on the
communications card; the Ethernet port located on the base CPU is disabled)
Protocols:................................................................Modbus TCP, DNP3.0, IEC60870-5-104, IEC 61850, IEC 61850
GOOSE, IEEE 1588, SNTP, IEC 62439-3 clause 4 (PRP)
ETHERNET – CARD OPTION “S” - 2X ST FIBER PORTS
Modes:......................................................................100 MB
Two Ports:...............................................................ST (with this option both enabled ports are on the
communications card; the Ethernet port located on the base CPU is disabled)
Protocols:................................................................Modbus TCP, DNP3.0, IEC60870-5-104, IEC 61850, IEC 61850
GOOSE, IEEE 1588, SNTP, IEC 62439-3 clause 4 (PRP)
Wavelength: ..........................................................1310nm
Typical link distance:.........................................4 km
USB
Standard specification: ....................................Compliant with USB 2.0
Protocols:................................................................Modbus TCP, TFTP
SERIAL
RS485 port: ............................................................Isolated
Baud rates:.............................................................Supports 9600, 19200, 38400, 57600, and 115200 kbps
Response time:.....................................................10 ms typical
Parity: .......................................................................None, Odd, Even
Protocol: ..................................................................Modbus RTU, DNP 3.0, IEC 60870-5-103
Maximum distance: ...........................................1200 m (4000 feet)
Isolation:..................................................................2 kV
WIFI
Standard specification: ....................................IEEE802.11bgn
Range: ......................................................................30 ft (direct line of sight)
REMOTE MODBUS DEVICE PROFILE
Device Name:........................................................BSG3 (13 alphanumeric characters maximum)
IP Address:..............................................................0.0.0.0 – standard Ethernet address
Slave Address: ......................................................254 (1 to 254)
Modbus Port:.........................................................502 (0 to 10000, default 502)
Poll Rate: .................................................................3 minute (OFF, 3 to 120 minutes), the continuous mode poll
interval is defined as the poll rate interval
Trigger:.....................................................................Off (any FlexLogic Operand), the trigger mode is based on
the FlexLogic operand designed to trigger the poll
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–27
Page 38
SPECIFICATIONS CHAPTER 1: INTRODUCTION

Testing & Certification

APPROVALS
Applicable Council Directive According to
CE compliance Low voltage directive EN60255-27
EMC Directive EN60255-26 R&TTE Directive ETSI EN300 328 ETSI EN301 489-1 ETSI
North America cULus UL508, e57838 NKCR, NRGU
ISO Manufactured under a registered
TESTING AND CERTIFICATION
Test Reference Standard Test Level
Dielectric voltage withstand EN60255-5/IEC60255-27 2.3 kV Impulse voltage withstand EN60255-5/IEC60255-27 5 kV Insulation resistance IEC60255-27 500 VDC Damped Oscillatory IEC61000-4-18 2.5 kV CM, 1 kV DM, 1 MHz Electrostatic Discharge EN61000-4-2 Level 4 RF immunity EN61000-4-3 Level 3 Fast Transient Disturbance EN61000-4-4 Class A and B Surge Immunity EN61000-4-5 Level 3 Conducted RF Immunity EN61000-4-6 Level 3 Power Frequency Immunity IEC60255-26 Class A & B Voltage variation, interruption and
Ripple DC
Radiated & Conducted Emissions CISPR11 /CISPR22 Class A
Sinusoidal Vibration IEC60255-21-1 Class 1 Shock & Bump IEC60255-21-2 Class 1 Seismic IEC60255-21-3 Class 2 Power magnetic Immunity IEC61000-4-8 Level 5 Pulse Magnetic Immunity IEC61000-4-9 Level 4 Damped Magnetic Immunity IEC61000-4-10 Level 4 Voltage Dip & interruption IEC61000-4-11 0, 40, 70, 80% dips,
Harmonic Immunity IEC61000-4-13 Class 3 Conducted RF Immunity 0-150kHz IEC61000-4-16 Level 4 Ingress Protection IEC60529 IP54 front Environmental (Cold) IEC60068-2-1 -40C 16 hrs Environmental (Dry heat) IEC60068-2-2 85C 16hrs Relative Humidity Cyclic IEC60068-2-30 6 day humidity variant 2 EFT IEEE/ANSI C37.90.1 4kV, 5 kHz Damped Oscillatory IEEE/ANSI C37.90.1 2.5 kV, 1 MHz Dielectric Between contacts IEEE C37.90 1500Vrms
quality program
IEC60255-26 PQT levels based on
EN301-489-17
C22.2.No 14, e57838 NKCR7, NRGU7 ISO9001
IEC61000-4-29, IEC61000-4-11 and IEC61000-4-17
250/300 cycle interrupts
1–28 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 39
CHAPTER 1: INTRODUCTION SPECIFICATIONS
Make and Carry IEEE C37.90 30A /200 ops Electrostatic Discharge (ESD) IEEE/ANSI C37.90.3 8kV CD/ 15 kV AD Product Safety IEC60255-27 As per Normative sections Rated Burden, IEC60255-1 Sec 6.10 Contact Performance IEC60255-1 Sec 6.11

Physical

DIMENSIONS
Size: ...........................................................................Refer to Chapter 2
Weight:..................................................................... 9 kg [20.0 lbs]

Environmental

Ambient temperatures: Storage/Shipping: -40°C to 85°C Operating: -40°C to 60°C Humidity: Operating up to 95% (non condensing) @ 55°C (As per
Altitude: 2000m (standard base reference evaluated altitude)
Pollution Degree: II Overvoltage Category: II Ingress Protection: IP54 Front Insulation Class: 1 Noise: 0 dB
IEC60068-2-30 Variant 2, 6 days)
5000m (maximum achievable altitude)
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–29
Page 40
CAUTIONS AND WARNINGS CHAPTER 1: INTRODUCTION

Cautions and Warnings

Before attempting to install or use the device, review all safety indicators in this document to help prevent injury, equipment damage, or downtime.

Safety words and definitions

The following symbols used in this document indicate the following conditions
DANGER:
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
IMPORTANT:
CAUTION:
FASTPATH:
CAUTION:
CAUTION:
CAUTION:
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Indicates practices not related to personal injury.

General Cautions and Warnings

The following general safety precautions and warnings apply.
Before attempting to use the equipment, it is important that all danger and caution indicators are reviewed.
If the equipment is used in a manner not specified by the manufacturer or functions abnormally, proceed with caution. Otherwise, the protection provided by the equipment may be impaired and can result in impaired operation and injury.
Hazardous voltages can cause shock, burns or death.
Installation/service personnel must be familiar with general device test practices, electrical awareness and safety precautions must be followed.
Before performing visual inspections, tests, or periodic maintenance on this device or associated circuits, isolate or disconnect all hazardous live circuits and sources of electric power.
Failure to shut equipment off prior to removing the power connections could expose you to dangerous voltages causing injury or death.
Ensure that all connections to the product are correct so as to avoid accidental risk of shock and/or fire, for example from high voltage connected to low voltage terminals.
Follow the requirements of this manual, including adequate wiring size and type, terminal torque settings, voltage, current magnitudes applied, and adequate isolation/ clearance in external wiring from high to low voltage circuits.
Use the device only for its intended purpose and application.
1–30 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 41
CHAPTER 1: INTRODUCTION CAUTIONS AND WARNINGS
Ensure that all ground paths are un-compromised for safety purposes during device operation and service.
All recommended equipment that should be grounded and must have a reliable and un-compromised grounding path for safety purposes, protection against electromagnetic interference and proper device operation.
Equipment grounds should be bonded together and connected to the facility’s main ground system for primary power.
Keep all ground leads as short as possible.
In addition to the safety precautions mentioned all electrical connections made must respect the applicable local jurisdiction electrical code.
It is recommended that a field external switch, circuit breaker be connected near the equipment as a means of power disconnect. The external switch or circuit breaker is selected in accordance with the power rating.
This product itself is not Personal Protective Equipment (PPE). However, it can be used in the computation of site specific Arc Flash analysis when the arc flash option is ordered. If a new appropriate Hazard Reduction Category code for the installation is determined, user should follow the cautions mentioned in the arc flash installation section.
follow the cautions mentioned in the arc flash installation section.If a new appropriate Har
The critical fail relay must be connected to annunciate the status of the device when the Arc Flash option is ordered.
Ensure that the control power applied to the device, the AC current, and voltage input match the ratings specified on the relay nameplate. Do not apply current or voltage in excess of the specified limits.
Only qualified personnel are to operate the device. Such personnel must be thoroughly familiar with all safety cautions and warnings in this manual and with applicable country, regional, utility, and plant safety regulations.
Hazardous voltages can exist in the power supply and at the device connection to current transformers, voltage transformers, control, and test circuit terminals. Make sure all sources of such voltages are isolated prior to attempting work on the device.
Hazardous voltages can exist when opening the secondary circuits of live current transformers. Make sure that current transformer secondary circuits are shorted out before making or removing any connection to the current transformer (CT) input terminals of the device.
For tests with secondary test equipment, ensure that no other sources of voltages or currents are connected to such equipment and that trip and close commands to the circuit breakers or other switching apparatus are isolated, unless this is required by the test procedure and is specified by appropriate utility/plant procedure.
When the device is used to control primary equipment, such as circuit breakers, isolators, and other switching apparatus, all control circuits from the device to the primary equipment must be isolated while personnel are working on or around this primary equipment to prevent any inadvertent command from this device.
Use an external disconnect to isolate the mains voltage supply.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–31
Page 42
CAUTIONS AND WARNINGS CHAPTER 1: INTRODUCTION
CAUTION:
FASTPATH:
FASTPATH:
LED transmitters are classified as IEC 60825-1 Accessible Emission Limit (AEL) Class 1M. Class 1M devices are considered safe to the unaided eye. Do not view directly with optical instruments.
To ensure the settings file inside the relay is updated, wait 30 seconds after a setpoint change before cycling power.
This product is rated to Class A emissions levels and is to be used in Utility, Substation Industrial environments. Not to be used near electronic devices rated for Class B levels.
1–32 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 43
CHAPTER 1: INTRODUCTION MUST-READ INFORMATION

Must-read Information

The following general statements apply and are repeated in the relevant sections of the manual.
FASTPATH:
WiFi and USB do not currently support CyberSentry security. For this reason WiFi is
disabled by default if the CyberSentry option is purchased. The user can enable WiFi, but be aware that doing so violates the security and compliance model that CyberSentry is supposed to provide.
Before upgrading firmware, it is very important to save the current 845 settings to a
file on your PC. After the firmware has been upgraded, it is necessary to load this file back into the 845.
The SNTP, IRIG-B and PTP settings take effect after rebooting the relay.
Commands may be issued freely through other protocols than Modbus (i.e., DNP, IEC
104, and, IEC 61850) without user authentication or encryption of data taking place, even if the relay has the advanced security feature enabled.
Note that the factory role password may not be changed.
In 845 both DNP and IEC104 protocol can work at the same time, but the user has to
consider that there is only one point map. So, both protocols use the same configured points.
The 52b contact is closed when the breaker is open and open when the breaker is
closed.
The Phase Directional element responds to the forward load current. In the case of a
following reverse fault, the element needs some time – in the order of 8 ms – to change the directional signal. Some protection elements such as Instantaneous Overcurrent may respond to reverse faults before the directional signal has changed. A coordination time of at least 10 ms must therefore be added to all the instantaneous protection elements under the supervision of the Phase Directional element. If current reversal is a concern, a longer delay – in the order of 20 ms – is needed.
The same curves used for the time overcurrent elements are used for Neutral
Displacement. When using the curve to determine the operating time of the Neutral Displacement element, substitute the ratio of neutral voltage to Pickup level for the current ratio shown on the horizontal axis of the curve plot.
If the 3-phase VT uses a delta connection and FREQUENCY INPUT is set to J2-3VT, the
positive sequence voltage is used as the supervision voltage. In such condition, the true supervision level is internally changed to 1/sqrt(3) of the user setting since the base of VT here is the phase-phase voltage.
To monitor the trip coil circuit integrity, use the relay terminals “FA_1 NO” and “FA_1
COM” to connect the Trip coil, and provide a jumper between terminals “FA_1 COM” and “FA_1 OPT/V” voltage monitor).
In Power factor monitoring, SWITCH-IN and SWITCH-OUT are mutually exclusive
settings.
The relay is not approved as, or intended to be, a revenue metering instrument. If used
in a peak load control system, the user must consider the accuracy rating and method of measurement employed, and the source VTs and CTs, in comparison with the electrical utility revenue metering system.
In bulk oil circuit breakers, the interrupting time for currents is less than 25% of the
interrupting rating and can be significantly longer than the normal interrupting time.
For future reference, the user is advised to take a printout of the conversion report
immediately after the conversion. All conversion reports are removed and become inaccessible if the user closes or re-launches the 8 Series Setup software.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–33
Page 44
FOR FURTHER ASSISTANCE CHAPTER 1: INTRODUCTION

Storage

Store the unit indoors in a cool, dry place. If possible, store in the original packaging. Follow the storage temperature range outlined in the Specifications.
Use the factory-provided dust caps on all Arc Flash sensor fiber and connectors when not in use, to avoid dust contamination in the transceiver and sensor plugs.

For Further Assistance

For product support, contact the information and call center as follows:
GE Grid Solutions
650 Markland Street Markham, Ontario Canada L6C 0M1 Worldwide telephone: +1 905 927 7070 Europe/Middle East/Africa telephone: +34 94 485 88 54 North America toll-free: 1 800 547 8629 Fax: +1 905 927 5098 Worldwide e-mail: multilin.tech@ge.com Europe e-mail: multilin.tech.euro@ge.com Website: http://www.gegridsolutions.com/multilin

Repairs

The firmware and software can be upgraded without return of the device to the factory. For issues not solved by troubleshooting, the process to return the device to the factory for
repair is as follows:
Contact a GE Grid Solutions Technical Support Center. Contact information is found in the first chapter.
Obtain a Return Materials Authorization (RMA) number from the Technical Support Center.
Verify that the RMA and Commercial Invoice received have the correct information.
Tightly pack the unit in a box with bubble wrap, foam material, or styrofoam inserts or packaging peanuts to cushion the item(s). You may also use double boxing whereby you place the box in a larger box that contains at least 5 cm of cushioning material.
Ship the unit by courier or freight forwarder, along with the Commercial Invoice and RMA, to the factory.
Customers are responsible for shipping costs to the factory, regardless of whether the unit is under warranty.
Fax a copy of the shipping information to the GE Grid Solutions service department .
Use the detailed return procedure outlined at
https://www.gegridsolutions.com/multilin/support/ret_proc.htm
The current warranty and return information are outlined at
https://www.gegridsolutions.com/multilin/warranty.htm
1–34 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 45
GE
LISTED
C
US
L
U
E57838
IND. CONT. EQ.
2D58
R
MADE IN CANADA
7UDQVIRUPer Protection System
Model: 85-EP5NNG5HNNANNGSSBSNNNB Serial Number: MJAXXXXXXX
POWER SUPPLY RATINGS: Nominal: 100 to 240V 125 to 250V Range: 88 to 265V (50/60Hz) 88 to 300V Power Consumption: 20W Typ, 34W/70VA Max Input /Output Ratings: Refer to Manual Instruction Manual: GEK-11951 Pollution Degree 2 / Degré de pollution 2
Technical Support: Worldwide: +1 905 927 7070 North America: 1 800 547 8629 www.gegridsolutions.com/multilin/ 650 Markland Street, Markham ON, Canada L6C 0M1 MFG. Date: Mar. 11, 2016
g
~
~
Multilin 85
g
!&%%+
!&%%
Grid Solutions
845 Transformer Protection System
Chapter 2: Installation

Mechanical Installation

Installation

This section describes the mechanical installation of the system, including dimensions for mounting and information on module withdrawal and insertion.

Product Identification

The product identification label is located on the side panel of the 845. This label indicates the product model, serial number, and date of manufacture.
Figure 2-1: Product Label
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2–1
Page 46
MECHANICAL INSTALLATION CHAPTER 2: INSTALLATION
 >@
 >@
 >@
 >@
 >@
 >@

Dimensions

The dimensions (in inches [millimeters]) of the 845 are shown below. Additional dimensions for mounting, and panel cutouts, are shown in the following sections.
Figure 2-2: 845 Dimensions
2–2 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 47
CHAPTER 2: INSTALLATION MECHANICAL INSTALLATION
Needle nose pliers

Mounting

The unit can be mounted two ways: standard panel mount or optional tab mounting, if required.
Standard panel mounting:
From the front of the panel, slide the empty case into the cutout. From the rear of the panel, screw the case into the panel at the 8 screw positions (see figures in Standard panel mount section).
Optional tab mounting:
The “V” tabs are located on the sides of the case and appear as shown in the following figure. Use needle nose pliers to bend the retaining "V" tabs outward to about 90°. Use caution and do not bend and distort the wall of the enclosure adjacent to the tabs. The relay can now be inserted and can be panel wired.
Figure 2-3: “V” Tabs Located on Case Side
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2–3
Page 48
MECHANICAL INSTALLATION CHAPTER 2: INSTALLATION
Standard Panel Mount The standard panel mount and cutout dimensions are illustrated below.
CAUTION:
To avoid the potential for personal injury due to f ire hazards, ensure the unit is mounted in a safe location and/or within an appropriate enclosure.
Figure 2-4: Standard panel mount
Figure 2-5: Panel cutout dimensions
2–4 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 49
CHAPTER 2: INSTALLATION MECHANICAL INSTALLATION
10.40
A
9.00
7.25
GE PN 'A' DEPTH
1009-0310 1 3/8"
1009-0311 3"
Dimensions in inches
8.73
892703A1.dwg
7.25
9.00
3.863.86
3.85
3.85
4.74
4.74
8X
.220
Dimensions in inches
892703A1.dwg
Depth Reducing Collar Two different sizes of optional depth reducing collar are available for mounting relays in
narrow-depth service panels, or wherever space is an issue.
NOTE:
The drill hole locations are different when a depth reducing collar is used. See Figure 2-
7:Depth reducing collar panel cutout.
18J0-0030 8 Series Depth Reducing Collar - 1 3/8"
18J0-0029 8 Series Depth Reducing Collar - 3"
Figure 2-6: Depth reducing collar dimensions
Figure 2-7: Depth reducing collar panel cutout
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2–5
Page 50
MECHANICAL INSTALLATION CHAPTER 2: INSTALLATION
DEPTH REDUCING COLLAR
GE PART# 1009-0311 3IN (76.2MM) DEPTH
GE PART# 1009-0310 1.375IN (34.9MM) DEPTH
8 SERIES UNIT
8-32x3/8IN P/HD PHIL BLK
GE PART# 1408-0306 (qty:16)
Tightening Torque: 15 in lb (1.7 Nm)
892703A1.dwg
Figure 2-8: Depth reducing collar installation
To mount an 8 Series relay with a depth reducing collar, follow these steps:
1. Drill mounting holes as shown on the panel cutout drawing (Figure 2-7:Depth
2. Mount the required collar (depth 1.375" or 3") on the captive unit using eight screws as
3. Mount the combined unit and collar on the panel using eight screws as shown.
reducing collar panel cutout).
shown.
2–6 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 51
CHAPTER 2: INSTALLATION MECHANICAL INSTALLATION
67(3
6&$/(
67(3
+$1'/(72%(/,)7('72 326,7,21:+,/(6/,',1* '5$:28781,7,172 &$37,9(81,7
67(3
0$,17$,1+$1'/(/,)7('326,7,21 817,/'5$:28781,7 ,6)8//<,16(57('
386++$1'/('2:1 $1'7,*+7(17+(6&5(: :,7+,1/%72548(
+$1'/(6+28/'%()/86+
:,7+)52173$1(/685)$&(

Draw-out Unit Withdrawal and Insertion

Unit withdrawal and insertion may only be performed when control power has been removed from the unit .
FASTPATH:
Turn off control power before drawing out or re-inserting the relay to prevent mal­operation.
Follow the steps outlined in the diagrams below to insert and withdraw the Draw-out unit.
Figure 2-9: Unit withdrawal and insertion diagram
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2–7
Page 52
MECHANICAL INSTALLATION CHAPTER 2: INSTALLATION

Removable Power Supply

Follow the steps outlined in the Insert or Remove Power Supply diagram to insert (#1) or remove (#2) the power supply from the unit.
Figure 2-10: Insert or Remove the Power Supply
Figure 2-11: Unlatch Module (location is marked by arrow)
2–8 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 53
CHAPTER 2: INSTALLATION MECHANICAL INSTALLATION

Removable Magnetic Module

Follow the steps outlined in the diagram below to insert or remove the magnetic module from the unit.
Figure 2-12: Insert or Remove the Magnetic Module
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2–9
Page 54
MECHANICAL INSTALLATION CHAPTER 2: INSTALLATION

Arc Flash Sensor

The Arc Flash sensor houses the fiber optics and membrane that are used to detect the arc flash. Two mounting screw holes are provided to affix the sensors to the panel.
CAUTION:
Sensor Fiber Handling
& Storage
CAUTION:
If the 8 Series is used in the computation for reducing the Hazard Reduction Category code, operands for sensor failures must be assigned to an auxiliary output relay which must be connected into the control logic of the breaker equipment to ensure safe operations when the output relay is asserted. In the event of this assertion, the Hazard Reduction Category code cannot be maintained unless backup protection is continuing to maintain it.
Arc Flash sensor fiber is pressure sensitive and must be handled carefully to avoid damage. Read the following guidelines fully before proceeding.
Care must be taken when handling the Arc Flash sensor fiber, which can be damaged if twisted, bent, or clamped tightly during installation.
Do not bend sensor fiber sharply, or with a radius of less than 25 mm (1 inch). Sharp bends can damage the fiber. Do not pull or tug loops of sensor fiber, as sharp bends may result.
Do not clamp sensor fiber tightly during installation. Sensor fiber should be held in place loosely for the best long-term performance. Avoid over-tightening ties which may deform or break the sensor fiber.
Do not pull or tug sensor fiber with force, as this may cause internal damage or separate the fiber from the cable connector.
Do not twist the sensor fiber, as twisting can damage the fiber resulting in substandard performance.
Do not attach sensor fiber directly to the bus.
Avoid surface temperatures above 70 °C or 158 °F to prolong the life of the fiber.
Secure all sensor fibers (loosely but securely) away from any moving parts.
Use the factory-provided dust caps on all Arc Flash sensor fiber and connectors when not in use, to avoid dust contamination in the transceiver and sensor plugs.
Sensor Installation Figure 2-13: AF Sensor - front, side and top view
FASTPATH:
2–10 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Review the sensor fiber handling guidelines above.
Page 55
CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATION
Sensor fiber should be held in place loosely for the best long-term performance. Avoid over-tightening ties which may deform or break the sensor fiber.
Before installing the AF sensor unit, ensure that all other drilling and installation is complete to minimize possible damage to the sensitive unit .
To install the AF sensor and route the sensor fiber, follow these steps:
1. Choose a location for the sensor clear of any obstructions that could shield the sensor
from arc flash light.
2. Mount the sensor securely, using the mounting screw holes.
3. Once the sensor is securely mounted, carefully route the sensor fiber from the AFS
sensor to the base unit, minimizing loops and curves for the strongest possible signal.
4. Secure all sensor fibers (loosely but securely) away from any moving parts.
FASTPATH:
Both the AF sensor connections (CH 1 through CH 4) and the sensor cables are shipped with dust caps in place to avoid dust contamination. The small rubber dust caps must be removed before operation.

Electrical Installation

Typical Wiring Diagrams

The following illustrates the electrical wiring of the Draw-out unit.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2–11
Page 56
WYE VT
845 Transformer Protection System
PHASE CTs
W1 BREAKER
Phase C
Phase B
Phase A
TRANSFORMER
W2 BREAKER
SLOT J
Typical auxiliary
contacts connection
SLOT K
+24 V
F21
COMMON
DIGITAL INPUT 7
DIGITAL INPUT 6
DIGITAL INPUT 5
DIGITAL INPUT 4
DIGITAL INPUT 3
DIGITAL INPUT 2
DIGITAL INPUT 1
F20
F19
F18
F17
F16
F15
F14
F13
SLOT D
SLOT E
G1 G2 G3 G4 G5 G6 G7 G8 G9 G10 G11 G12 G13 G14 G15 G16 G17 G18 G19 G20 G21 G22 G23 G24
DCmA I/O
ANALOG OUTPUT
ANALOG INPUT
RTD
1
12
34567
11
2
34
SHIELD
SHIELD
SHIELD
RETURN
HOT
COMP
RESERVED
RESER
VED
RETURN
RETURN
AMBIENT
TEMPERATURE
H9
DIGITAL INPUT 7
DIGITAL INPUT 6
DIGITAL INPUT 5
DIGITAL INPUT 4
DIGITAL INPUT 3
DIGITAL INPUT 2
DIGITAL INPUT 1
H8
H7
H6
H5
H4
H3
H2
H1
+24 V
H12
COMMON
DIGITAL INPUT 10
H11
H10
DIGITAL INPUT 9
DIGITAL INPUT 8
SLOT G: I/O_L (OPTIONAL)
CH1
CH4
CH3
CH2
FIBER INPUT 1
FIBER INPUT 2
FIBER INPUT 3
FIBER INPUT 4
C9
C8
C7
C6
C5
C4
C3
C2
C1
C12
C11
C10
C15
C14
C13
C18
C17
C16
SHIELD
RETURN
COMP
HOT
COMP
HOT
RETURN
COMP
HOT
HOT
RESERVED
SHIELD
COMP
RETURN
COMP
HOT
COMP
HOT
RTD 7
RTD 7/8
RTD 8
RTD 9
RTD 10
RTD 11
RTD 12
RTD 9/10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B12
B11
B10
B15
B14
B13
B18
B17
B16
SHIELD
RETURN
COMP
HOT
COMP
HOT
RETURN
COMP
HOT
HOT
RESERVED
SHIELD
COMP
RETURN
COMP
HOT
COMP
HOT
RTD 1
RTD 1/2
RTD 2
RTD 3
RTD 4
RTD 5
RTD 6
RTD 3/4
RTD 5/6
SLOT B OR C: I/O_R OR I/O_S* (OPTIONAL)
* SUPPORTS 10 OHM COPPER RTD AS WELL
G/H2
G/H1
G/H24
G/H23
G/H22
G/H12
G/H11
G/H10
G/H9
G/H8
G/H7
G/H6
G/H5
G/H4
G/H3
+24 V
G/H21
COMMON
DIGITAL INPUT 7
DIGITAL INPUT 6
DIGITAL INPUT 5
DIGITAL INPUT 4
DIGITAL INPUT 3
DIGITAL INPUT 2
DIGITAL INPUT 1
G/H20
G/H19
G/H18
G/H17
G/H16
G/H15
G/H14
G/H13
SLOT G OR H: I/O_A* (OPTIONAL)
ANY MEASURED
OR METERED
ANALOG PARAMETER
OUTPUTS
* SLOT H I/O_A IS AVAILABLE WHEN SLOT G IS WITH I/O_L
ANY MEASURED OR
METERED ANALOG PARAMETER
INPUTS
SLOT A
TRIP W1 BKR
TRIP COIL
52a
52a
+
-
-
+
CIRCUIT
TRIP W2 BKR CIRCUIT
TRIP COIL
52b
52a
52b
52a
W1 BREAKER
W2 BREAKER
BCD DECODER
CLOSE W1 BKR
COIL
52b
52b
+
-
-
+
CIRCUIT
CLOSE W2 BKR CIRCUIT
COIL
OHMS INPUT
CABLE SHIELD TO BE GROUNDED
AT PLC/COMPUTER END ONLY
A
C
B
LTC TAP
POSITION
IF OHMS
INPUT
SHIELD
PHASE CTs
ELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION
Figure 2-14: Typical Wiring Diagram for a 2-Winding Transformer with VTs on HV Side
2–12 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
892841A2
Page 57
CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATION
WYE VT
845 Transformer Protection System
PHASE CTs
Phase C
Phase B
Phase A
TRANSFORMER
SLOT K
Typical auxiliary contacts connection
SLOT J
+24 V
F21
COMMON
DIGITAL INPUT 7
DIGITAL INPUT 6
DIGITAL INPUT 5
DIGITAL INPUT 4
DIGITAL INPUT 3
DIGITAL INPUT 2
DIGITAL INPUT 1
F20
F19
F18
F17
F16
F15
F14
F13
G1 G2 G3 G4 G5 G6 G7 G8 G9 G10 G11 G12 G13 G14 G15 G16 G17 G18 G19 G20 G21 G22 G23 G24
DCmA I/O
ANALOG OUTPUT
ANALOG INPUT
RTD
1
12
34567
11
2
34
SHIELD
SHIELD
SHIELD
RETURN
HOT
COMP
RESERVED
RESER
VED
RETURN
RETURN
AMBIENT
TEMPERATURE
H9
DIGITAL INPUT 7
DIGITAL INPUT 6
DIGITAL INPUT 5
DIGITAL INPUT 4
DIGITAL INPUT 3
DIGITAL INPUT 2
DIGITAL INPUT 1
H8
H7
H6
H5
H4
H3
H2
H1
+24 V
H12
COMMON
DIGITAL INPUT 10
H11
H10
DIGITAL INPUT 9
DIGITAL INPUT 8
SLOT G: I/O_L (OPTIONAL)
CH1
CH4
CH3
CH2
FIBER INPUT 1
FIBER INPUT 2
FIBER INPUT 3
FIBER INPUT 4
C9
C8
C7
C6
C5
C4
C3
C2
C1
C12
C11
C10
C15
C14
C13
C18
C17
C16
SHIELD
RETURN
COMP
HOT
COMP
HOT
RETURN
COMP
HOT
HOT
RESERVED
SHIELD
COMP
RETURN
COMP
HOT
COMP
HOT
RTD 7
RTD 7/8
RTD 8
RTD 9
RTD 10
RTD 11
RTD 12
RTD 9/10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B12
B11
B10
B15
B14
B13
B18
B17
B16
SHIELD
RETURN
COMP
HOT
COMP
HOT
RETURN
COMP
HOT
HOT
RESERVED
SHIELD
COMP
RETURN
COMP
HOT
COMP
HOT
RTD 1
RTD 1/2
RTD 2
RTD 3
RTD 4
RTD 5
RTD 6
RTD 3/4
RTD 5/6
SLOT B OR C: I/O_R OR I/O_S* (OPTIONAL)
* SUPPORTS 10 OHM COPPER RTD AS WELL
G/H2
G/H1
G/H24
G/H23
G/H22
G/H12
G/H11
G/H10
G/H9
G/H8
G/H7
G/H6
G/H5
G/H4
G/H3
+24 V
G/H21
COMMON
DIGITAL INPUT 7
DIGITAL INPUT 6
DIGITAL INPUT 5
DIGITAL INPUT 4
DIGITAL INPUT 3
DIGITAL INPUT 2
DIGITAL INPUT 1
G/H20
G/H19
G/H18
G/H17
G/H16
G/H15
G/H14
G/H13
SLOT G OR H: I/O_A* (OPTIONAL)
ANY MEASURED
OR METERED
ANALOG PARAMETER
OUTPUTS
* SLOT H I/O_A IS AVAILABLE WHEN SLOT G IS WITH I/O_L
ANY MEASURED OR
METERED ANALOG PARAMETER
INPUTS
SLOT A
TRIP W1 BKR
TRIP COIL
52a
52a
+
-
-
+
CIRCUIT
TRIP W2 BKR CIRCUIT
COIL
52b
52a
52b
52a
W1 BREAKER
W2 BREAKER
BCD DECODER
CLOSE W1 BKR
COIL
52b
52b
+
-
-
+
CIRCUIT
CLOSE W2 BKR CIRCUIT
COIL
OHMS INPUT
CABLE SHIELD TO BE GROUNDED
AT PLC/COMPUTER END ONLY
A
C
B
LTC TAP
POSITION
IF OHMS
INPUT
SHIELD
PHASE CTs
TRIP
SLOT D
SLOT E
Figure 2-15: Typical Wiring Diagram for a 2-Winding Transformer with VTs on LV Side
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2–13
892822A2
Page 58
ELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION
845 Transformer Protection System
PHASE CTs
Phase C
Phase B
Phase A
TRANSFORMER
Winding 2
W2 BREAKER
SLOT K
Typical auxiliary contacts connection
+24 V
F21
COMMON
DIGITAL INPUT 7
DIGITAL INPUT 6
DIGITAL INPUT 5
DIGITAL INPUT 4
DIGITAL INPUT 3
DIGITAL INPUT 2
DIGITAL INPUT 1
F20
F19
F18
F17
F16
F15
F14
F13
G1
G2 G3 G4 G5 G6 G7 G8 G9 G10 G11 G12 G13 G14 G15 G16 G17 G18 G19 G20 G21 G22 G23 G24
DCmA I/O
ANALOG OUTPUT
ANALOG INPUT
RTD
1
12
34567
11
2
34
SHIELD
SHIELD
SHIELD
RETURN
HOT
COMP
RESERVED
RESER
VED
RETURN
RETURN
AMBIENT
TEMPERATURE
H9
DIGITAL INPUT 7
DIGITAL INPUT 6
DIGITAL INPUT 5
DIGITAL INPUT 4
DIGITAL INPUT 3
DIGITAL INPUT 2
DIGITAL INPUT 1
H8
H7
H6
H5
H4
H3
H2
H1
+24 V
H12
COMMON
DIGITAL INPUT 10
H11
H10
DIGITAL INPUT 9
DIGITAL INPUT 8
SLOT G: I/O_L (OPTIONAL)
CH1
CH4
CH3
CH2
FIBER INPUT 1
FIBER INPUT 2
FIBER INPUT 3
FIBER INPUT 4
C9
C8
C7
C6
C5
C4
C3
C2
C1
C12
C11
C10
C15
C14
C13
C18
C17
C16
SHIELD
RETURN
COMP
HOT
COMP
HOT
RETURN
COMP
HOT
HOT
RESERVED
SHIELD
COMP
RETURN
COMP
HOT
COMP
HOT
RTD 7
RTD 7/8
RTD 8
RTD 9
RTD 10
RTD 11
RTD 12
RTD 9/10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B12
B11
B10
B15
B14
B13
B18
B17
B16
SHIELD
RETURN
COMP
HOT
COMP
HOT
RETURN
COMP
HOT
HOT
RESERVED
SHIELD
COMP
RETURN
COMP
HOT
COMP
HOT
RTD 1
RTD 1/2
RTD 2
RTD 3
RTD 4
RTD 5
RTD 6
RTD 3/4
RTD 5/6
SLOT B OR C: I/O_R OR I/O_S* (OPTIONAL)
* SUPPORTS 10 OHM COPPER RTD AS WELL
G/H2
G/H1
G/H24
G/H23
G/H22
G/H12
G/H11
G/H10
G/H9
G/H8
G/H7
G/H6
G/H5
G/H4
G/H3
+24 V
G/H21
COMMON
DIGITAL INPUT 7
DIGITAL INPUT 6
DIGITAL INPUT 5
DIGITAL INPUT 4
DIGITAL INPUT 3
DIGITAL INPUT 2
DIGITAL INPUT 1
G/H20
G/H19
G/H18
G/H17
G/H16
G/H15
G/H14
G/H13
SLOT G OR H: I/O_A* (OPTIONAL)
ANY MEASURED
OR METERED
ANALOG PARAMETER
OUTPUTS
* SLOT H I/O_A IS AVAILABLE WHEN SLOT G IS WITH I/O_L
ANY MEASURED OR
METERED ANALOG PARAMETER
INPUTS
SLOT A
TRIP W1 BKR
TRIP COIL
52a
52a
+
-
-
+
CIRCUIT
TRIP W2 BKR CIRCUIT
COIL
52b
52a
52b
52a
W1 BREAKER
W2 BREAKER
BCD DECODER
CLOSE W1 BKR
COIL
52b
52b
+
-
-
+
CIRCUIT
CLOSE W2 BKR CIRCUIT
COIL
OHMS INPUT
CABLE SHIELD TO BE GROUNDED
AT PLC/COMPUTER END ONLY
LTC TAP
POSITION
IF OHMS
INPUT
SHIELD
PHASE CTs
TRIP
SLOT D
SLOT E
Figure 2-16: Typical Wiring Diagram for a 2-Winding Transformer without VTs
2–14 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
892823A2
Page 59
CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATION
WYE VT
845 Transformer Protection System
PHASE CTs
Phase C
Phase B
Phase A
TRANSFORMER
SLOT J
Typical auxiliary contacts connection
SLOT K
+24 V
F21
COMMON
DIGITAL INPUT 7
DIGITAL INPUT 6
DIGITAL INPUT 5
DIGITAL INPUT 4
DIGITAL INPUT 3
DIGITAL INPUT 2
DIGITAL INPUT 1
F20
F19
F18
F17
F16
F15
F14
F13
G1
G2 G3 G4 G5 G6 G7 G8 G9 G10 G11 G12 G13 G14 G15 G16 G17 G18 G19 G20 G21 G22 G23 G24
DCmA I/O
ANALOG OUTPUT
ANALOG INPUT
RTD
1
12
34567
11
2
34
SHIELD
SHIELD
SHIELD
RETURN
HOT
COMP
RESERVED
RESER
VED
RETURN
RETURN
AMBIENT
TEMPERATURE
H9
DIGITAL INPUT 7
DIGITAL INPUT 6
DIGITAL INPUT 5
DIGITAL INPUT 4
DIGITAL INPUT 3
DIGITAL INPUT 2
DIGITAL INPUT 1
H8
H7
H6
H5
H4
H3
H2
H1
+24 V
H12
COMMON
DIGITAL INPUT 10
H11
H10
DIGITAL INPUT 9
DIGITAL INPUT 8
SLOT G: I/O_L (OPTIONAL)
CH1
CH4
CH3
CH2
FIBER INPUT 1
FIBER INPUT 2
FIBER INPUT 3
FIBER INPUT 4
C9
C8
C7
C6
C5
C4
C3
C2
C1
C12
C11
C10
C15
C14
C13
C18
C17
C16
SHIELD
RETURN
COMP
HOT
COMP
HOT
RETURN
COMP
HOT
HOT
RESERVED
SHIELD
COMP
RETURN
COMP
HOT
COMP
HOT
RTD 7
RTD 7/8
RTD 8
RTD 9
RTD 10
RTD 11
RTD 12
RTD 9/10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B12
B11
B10
B15
B14
B13
B18
B17
B16
SHIELD
RETURN
COMP
HOT
COMP
HOT
RETURN
COMP
HOT
HOT
RESERVED
SHIELD
COMP
RETURN
COMP
HOT
COMP
HOT
RTD 1
RTD 1/2
RTD 2
RTD 3
RTD 4
RTD 5
RTD 6
RTD 3/4
RTD 5/6
SLOT B OR C: I/O_R OR I/O_S* (OPTIONAL)
* SUPPORTS 10 OHM COPPER RTD AS WELL
G/H2
G/H1
G/H24
G/H23
G/H22
G/H12
G/H11
G/H10
G/H9
G/H8
G/H7
G/H6
G/H5
G/H4
G/H3
+24 V
G/H21
COMMON
DIGITAL INPUT 7
DIGITAL INPUT 6
DIGITAL INPUT 5
DIGITAL INPUT 4
DIGITAL INPUT 3
DIGITAL INPUT 2
DIGITAL INPUT 1
G/H20
G/H19
G/H18
G/H17
G/H16
G/H15
G/H14
G/H13
SLOT G OR H: I/O_A* (OPTIONAL)
ANY MEASURED
OR METERED
ANALOG PARAMETER
OUTPUTS
* SLOT H I/O_A IS AVAILABLE WHEN SLOT G IS WITH I/O_L
ANY MEASURED OR
METERED ANALOG PARAMETER
INPUTS
SLOT A
TRIP W1 BKR
TRIP COIL
52b
52a
+
-
-
+
CIRCUIT
CLOSE W1 BKR CIRCUIT
COIL
52b
52a
52b
52a
W1 BREAKER
W2 BREAKER
BCD DECODER
TRIP W2 BKR
TRIP COIL
52a
52a
+
-
-
+
CIRCUIT
TRIP W3 BKR CIRCUIT
TRIP COIL
OHMS INPUT
CABLE SHIELD TO BE GROUNDED
AT PLC/COMPUTER END ONLY
A
C
B
LTC TAP
POSITION
IF OHMS
INPUT
SHIELD
PHASE CTs
PHASE CTs
52b
52a
W3 BREAKER
SLOT D
SLOT E
Figure 2-17: Typical Wiring Diagram for a 3-Winding Transformer
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2–15
892789A2
Page 60
ELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION
NOTE
SCREW
WASHER
LOWER
TERMINAL
DIVIDER
TERMINAL
BLOCK
1
2
3

Terminal Identif ication

All the terminal strips are labeled with a slot letter to identify the module slot position and numbers to identify the terminals within the module.
CAUTION:
NOTE:
Make sure that the first letter on the terminal strip corresponds to the slot location identified on the chassis silkscreen.
Terminal Connections
When installing two lugs on one terminal, both lugs must be “right side up” as shown in the picture below. This is to ensure the adjacent lower terminal block does not interfere with the lug body.
Figure 2-18: Orient the Lugs Correctly
Figure 2-19: Correct Installation Method
2–16 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 61
CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATION
Figure 2-20: INCORRECT INSTALLATION METHOD (lower lug reversed)
A broad range of applications are available for the 845 relays. As such, it is not possible to present typical connections for all possible schemes. The information in this section covers the important aspects of interconnections, in the general areas of instrument transformer inputs, other inputs, outputs, communications and grounding. The figure below shows the rear terminal layout of the 845
Platform.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2–17
Page 62
ELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION
AB
C
D
K
J
PORT 1
F
G
H
1
2
345
6
7
8910
2 3
1
2
345
6
7
8910
11
12131415161718
12
345
6
7
89101112131415161718192021222324
123456789101112131415161718192021222324
123456789101112131415161718192021222324
1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
345
6
7
8910
11
12131415161718
Tx4
Rx4
Tx5
Rx5
PORT 5
PORT 4
E
BASIC
COMMS
I/OPSU
ADV
COMMS
AC ANALOG INPUTS
BANK - J2
BANK - K2
BANK - K1
BANK - J1
I/O
Figure 2-21: Rear Terminal Layout of the 8 Series Platform
Table 2-1: Power Supply
H - HV Power Supply
Terminal Description
1 Line 2 Neutral 3 Ground
2–18 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 63
CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATION
Table 2-2: Power Supply
L - LV Power Supply
Terminal Description (DC Voltage input polarity)
1 +ve (positive) 2 -ve (negative) 3 Ground
Table 2-3: Comms
SE - Comms - Basic Ethernet 1E/1P/2E/2A - Comms - Advanced Ethernet
Terminal Description Terminal Description
1 IRIG-B (+) 1 IRIG-B (+) 2 IRIG-B (-) 2 IRIG-B (-) 3 RS485_1 (+) 3 RS485_1 (+) 4 RS485_1 (-) 4 RS485_1 (-) 5 RS485_1 COM 5 RS485_1 COM 6 RESERVED 6 RESERVED 7 RESERVED 7 RESERVED 8 RESERVED 8 RESERVED 9 RESERVED 9 RESERVED 10 RESERVED 10 RESERVED RJ45 ETHERNET RJ45 NOT USED
Table 2-4: HV IO
A - HV I/O - 2 FA (Vmon), 3FC, 7 Contact Inputs
Terminal Description
1 FA_1 COM TRIP 2 FA_1 NO TRIP 3 FA_1 OPT/V TRIP 4 FA_2 COM CLOSE/AUX 5 FA_2 NO CLOSE/AUX 6 FA_2 OPT/V CLOSE/AUX 7 FC_1 NC AUX 8 FC_1 COM AUX 9 FC_1 NO AUX 10 FC_2 NC AUX 11 FC_2 COM AUX 12 FC_2 NO AUX 13 CONTACT IN_1 14 CONTACT IN_2 15 CONTACT IN_3 16 CONTACT IN_4 17 CONTACT IN_5 18 CONTACT IN_6 19 CONTACT IN_7 20 CONTACT IN COM 21 DC +24
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2–19
Page 64
ELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION
22 FC_3 NC Critical Fail Relay 23 FC_3 COM Critical Fail Relay 24 FC_3 NO Critical Fail Relay
Table 2-5: AC Analog
AC Inputs - 4 X 1/5A CT, 4 VT
Terminal Description
1 CT1_IN 2 CT1_RETURN 3 CT2_IN 4 CT2_RETURN 5 CT3_IN 6 CT3_RETURN 7 CT4_IN 8 CT4_RETURN 9 VT1_IN 10 VT1_RETURN 11 VT2_IN 12 VT2_RETURN 13 VT3_IN 14 VT3_RETURN 15 VT4_IN 16 VT4_RETURN
Wire Size Use the following guideline when selecting wires or lugs to connect to terminal strips A, B,
C, D, E, F, G, H, and terminal blocks J, K. Note that the first two bullets are applicable to terminal blocks J and K only:
12 AWG to 22 AWG (3.3 mm2 to 0.3 mm2): Single wire termination with/without 9.53 mm (0.375”) maximum diameter ring terminals.
14 AWG to 22 AWG (2.1 mm2 to 0.3 mm2): Multiple wire termination with 9.53 mm (0.375”) maximum diameter ring terminals. Two ring terminals maximum per circuit.
Suggested wiring screw tightening torques are: terminal strips A-H tighten to 4.5 in-lbs (0.5 N-m) and terminal blocks J, K to 15 in-lb (1.7 N-m).
Figure 2-22: Fiber Connector Types (S - ST)
2–20 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 65
CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATION
892773A2.cdr
8 Series
J1
J2
J3
J4
J5
J7J6J8J7 J8J8 J7

Phase Sequence and Transformer Polarity

For correct operation of the relay features, follow the instrument transformer polarities, shown in the Typical Wiring Diagram above. Note the solid square markings that are shown with all instrument transformer connections. When the connections adhere to the drawing, the arrow shows the direction of power flow for positive watts and the positive direction of vars. The phase sequence is user programmable for either ABC or ACB rotation.
The 845 relay has four (4) current inputs in each J slot and K slot. Three of them are used for connecting to the phase CT phases A, B, and C. The fourth input is a ground input that can be connected to either a ground CT placed on the neutral from a Wye connected transformer winding, or to a “donut” type CT measuring the zero sequence current from a grounded system. The relay CTs are placed in a packet mounted to the chassis of the
relay. There are no internal ground connections on the current inputs. Current
845 transformers with 1 to 12000 A primaries may be used.
CAUTION:
Verify that the relay’s nominal input current of 1 A or 5 A matches the secondary rating of the connected CTs. Unmatched CTs may result in equipment damage or inadequate protection.
CAUTION:
IMPORTANT: The phase and ground current inputs correctly measure up to 46 times the current input’s nominal rating. Time overcurrent curves become horizontal lines for currents above 20 × PKP.

Ground CT Inputs

Before making ground connections, be aware that the relay automatically calculates the neutral (residual) current from the sum of the three phase current phasors. The following figures show three possible ground connections using the ground current input (Terminals J7 and J8).
The ground input (Terminals J7 and J8) is used in conjunction with a Zero Sequence CT as source, or in the neutral of wye-connected source CTs. The ground current input can be used to polarize the neutral. When using the residual connection, set the
GROUND
Figure 2-23: Ground Inputs
CT PRIMARY setpoint to a value equal to the PHASE CT PRIMARY setpoint.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2–21
Page 66
ELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION
892776A3.CDR
TO BUS VTs
A
C
B
J15
AUX
J16
VV
1 2
2V1
V
AUX
J15 J16
Van
Vab
52
TO BUS VTs
A
C
B
J15
AUX
J16
VV
1 2
Vbn
52
TO BUS VTs
A
C
B
J15
AUX
J16
VV
1 2
Vcn
52
TO BUS VTs
A
C
B
52
2V1
V
AUX
J15 J16
Vbc
TO BUS VTs
A
C
B
52
2V1
V
AUX
J15 J16
Vca
TO BUS VTs
A
C
B
52
J1 J2 J3 J4 J5 J6 J7 J8
CURRENT INPUTS
PHASE A PHASE B PHASE C
GROUND
I
A
N
I
C
I
B
I
G
NN
N
FEEDER
TRANSFORMER
892775A1.cdr

Voltage Inputs

The 845 relays have four channels for AC voltage inputs, each with an isolating transformer. Voltage transformers up to a maximum 5000:1 ratio may be used. The nominal secondary voltage must be in the 10 to 240 V range. The Bus VT connections most commonly used, wye and delta (or open delta), are shown in the typical wiring diagram. The single Auxiliary voltage input is commonly used as the “line voltage”. The line VT input channel, used for the synchrocheck feature, can be connected for phase-neutral voltages
, Vbn, or Vcn; or for phase-phase voltages Vab, Vbc, or Vca as shown.
V
an
Figure 2-24: Line VT Connections
CAUTION:
If Delta VTs are used for three-phase voltages, the zero sequence voltage (V0) and neutral ground polarizing voltage (–V0) are zero. Also, with the Delta VT connection, the phase-neutral voltage cannot be measured and is not displayed.

Restricted Earth Fault Inputs

Restricted Earth Fault protection is often applied to transformers having grounded Wye windings to provide ground fault detection for faults near the transformer neutral. Each current bank on the relay has 3 phase current inputs and one ground input. Any of the available inputs on the relay current banks can be selected as a signal input for an RGF element.
The phase and ground input CT connections to the relay are shown below:
Figure 2-25: Restricted Ground Fault Inputs
2–22 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 67
CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATION
Ground connection to neutral must be on the source side
UNSHIELDED CABLE
LOAD
ABCN G
Ground outside CT
Source
LOAD
SHIELDED CABLE
996630A5
AB C
Source
To ground; must be on load side
Stress cone
shields

Zero-Sequence CT Installation

The figure below shows the various CT connections and the exact placement of a Zero Sequence current CT, so that ground fault current can be detected. Twisted pair cabling on the Zero Sequence CT is recommended.
Figure 2-26: Zero Sequence (Core Balance) CT Installation
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2–23
Page 68
ELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION

Control Power

Control power is supplied to the relay such that it matches the relay’s installed power supply range.
CAUTION:
CAUTION:
Control power supplied to the relay must match the installed power supply range. If the applied voltage does not match, damage to the unit may occur. All grounds MUST be connected for normal operation regardless of control power supply type.
For more details, please refer to the Power Supply subsection located in the Introduction chapter.
The relay should be connected directly to the ground bus, using the shortest practical path. A tinned copper, braided, shielding and bonding cable should be used. As a minimum, 96 strands of number 34 AWG should be used. Belden catalog number 8660 is suitable.
Figure 2-27: Control Power Connection
FASTPATH:

Contact Inputs

Depending on the order code, the 845 relay has a different number of contact inputs which can be used to operate a variety of logic functions for circuit switching device control, external trips, blocking of protection elements, etc. The relay has ‘contact inputs’ and ‘virtual inputs’ that are combined in a form of programmable logic to facilitate the implementation of various schemes.
The voltage threshold at which the contact inputs detect a closed contact input is programmable as 17 V DC for 24 V sources, 33 V DC for 48 V sources, 84 V DC for 110 to 125 V sources, and 166 V DC for 250 V sources.
Wet or Dry input signal types can be connected to contact input terminals as shown in the figure: Wet and Dry Contact Input Wiring Examples.
Dry inputs use an internal +24V that is supplied by the 845. The voltage threshold must be set to 17V for the inputs to be recognized using the internal +24V.
The same type of input signal must be connected to all contact inputs on the same contact input card.
2–24 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 69
CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATION
INPUT
SIGNAL
SWITCH
(DRY)
INPUT
SIGNAL
SWITCH
(WET)
EXTERNAL
DC POWER
SUPPLY
Figure 2-28: Wet and Dry Contact Input Wiring Examples

Output Relays

The locations of the output relays have a fixed assignment for the platform called the master identifier. I/O options that include inputs occupy the fixed assigned output locations so in these cases the relay assignment maps to the master identifier.
The output relays for the 845 relay are fully programmable, and can be assigned in the transformer breakers menu for breaker tripping or closing. The output relays assigned for breaker closing, are automatically excluded from the menus for output selection for the rest of the elements.
The critical failure output relay is reserved as Relay_8 and it is omitted and is not programmable.
Table 2-6: Slots F,G,H Terminal Master Identifier (left) and I/O options A,A,N (right)
Slots F,G,H Terminal Master Identifier Slots F,G,H with I/O options A,A,N
Terminal # SLOT F SLOT G SLOT H Terminal # SLOT F SLOT G
1 RELAY_1 RELAY_9 RELAY_17 1 RELAY_1 RELAY_9 2 RELAY_1 RELAY_9 RELAY_17 2 RELAY_1 RELAY_9 3 RELAY_1 RELAY_9 RELAY_17 3 RELAY_1 RELAY_9 4 RELAY_2 RELAY_10 RELAY_18 4 RELAY_2 RELAY_10 5 RELAY_2 RELAY_10 RELAY_18 5 RELAY_2 RELAY_10 6 RELAY_2 RELAY_10 RELAY_18 6 RELAY_2 RELAY_10 7 RELAY_3 RELAY_11 RELAY_19 7 RELAY_3 RELAY_11 8 RELAY_3 RELAY_11 RELAY_19 8 RELAY_3 RELAY_11
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2–25
Page 70
ELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION
Slots F,G,H Terminal Master Identifier Slots F,G,H with I/O options A,A,N
Terminal # SLOT F SLOT G SLOT H Terminal # SLOT F SLOT G
9 RELAY_3 RELAY_11 RELAY_19 9 RELAY_3 RELAY_11 10 RELAY_4 RELAY_12 REL AY_20 10 REL AY_4 RELAY_12 11 RELAY_4 RELAY_12 REL AY_20 11 REL AY_4 RELAY_12 12 RELAY_4 RELAY_12 REL AY_20 12 REL AY_4 RELAY_12 13 RELAY_5 RELAY_13 RELAY_21 13 Digital In_1 Digital In_8 14 RELAY_5 RELAY_13 RELAY_21 14 Digital In_2 Digital In_9 15 RELAY_5 RELAY_13 RELAY_21 15 Digital In_3 Digital In_10 16 RELAY_6 RELAY_14 RELAY_22 16 Digital In_4 Digital In_11 17 RELAY_6 RELAY_14 RELAY_22 17 Digital In_5 Digital In_12 18 RELAY_6 RELAY_14 RELAY_22 18 Digital In_6 Digital In_13 19 RELAY_7 RELAY_15 RELAY_23 19 Digital In_7 Digital In_14 20 RELAY_7 RELAY_15 RELAY_23 20 Common Common 21 RELAY_7 RELAY_15 RELAY_23 21 +24V +24V 22 RELAY_8 RELAY_16 REL AY_24 22 REL AY_8 RELAY_16 23 RELAY_8 RELAY_16 REL AY_24 23 REL AY_8 RELAY_16 24 RELAY_8 RELAY_16 REL AY_24 24 REL AY_8 RELAY_16
Table 2-7: Slots F,G,H with I/O options A,A,A (left) and I/O options A, L, A (right)
Slots F,G,H with I/O options A,A,A Slots F,G,H with I/O options A,L,A
Terminal # SLOT F SLOT G SLOT H Terminal # SLOT F SLOT G SLOT H
1 RELAY_1 RELAY_9 RELAY_17 1 RELAY_1 Analog Out_1 RELAY_9 2 RELAY_1 RELAY_9 RELAY_17 2 RELAY_1 Analog Out_2 RELAY_9 3 RELAY_1 RELAY_9 RELAY_17 3 RELAY_1 Analog Out_3 RELAY_9 4 RELAY_2 RELAY_10 RELAY_18 4 RELAY_2 Analog Out_4 RELAY_10 5 RELAY_2 RELAY_10 RELAY_18 5 RELAY_2 Analog Out_5 RELAY_10 6 RELAY_2 RELAY_10 RELAY_18 6 RELAY_2 Analog Out_6 RELAY_10 7 RELAY_3 RELAY_11 RELAY_19 7 RELAY_3 Analog Out_7 RELAY_11 8 RELAY_3 RELAY_11 RELAY_19 8 RELAY_3 Return RELAY_11 9 RELAY_3 RELAY_11 RELAY_19 9 RELAY_3 Shield RELAY_11 10 RELAY_4 RELAY_12 RELAY_20 10 RELAY_4 Analog In_1 RELAY_12 11 RELAY_4 RELAY_12 RELAY_20 11 RELAY_4 Analog In_2 RELAY_12 12 RELAY_4 RELAY_12 RELAY_20 12 RELAY_4 Analog In_3 RELAY_12 13 Digital In_1 Digital In_8 Digital In_15 13 Digital In_1 Analog In_4 Digital In_8 14 Digital In_2 Digital In_9 Digital In_16 14 Digital In_2 Return Digital In_9 15 Digital In_3 Digital In_10 Digital In_17 15 Digital In_3 Shield Digital In_10 16 Digital In_4 Digital In_11 Digital In_18 16 Digital In_4 Reserved Digital In_11 17 Digital In_5 Digital In_12 Digital In_19 17 Digital In_5 Reserved Digital In_12 18 Digital In_6 Digital In_13 Digital In_20 18 Digital In_6 Reserved Digital In_13 19 Digital In_7 Digital In_14 Digital In_21 19 Digital In_7 RTD_Hot Digital In_14 20 Common Common Common 20 Common RTD_Comp Common 21 +24V +24V +24V 21 +24V RTD_Return +24V 22 RELAY_8 RELAY_16 RELAY_24 22 RELAY_8 Shield RELAY_16 23 RELAY_8 RELAY_16 RELAY_24 23 RELAY_8 Reserved RELAY_16 24 RELAY_8 RELAY_16 RELAY_24 24 RELAY_8 Reserved RELAY_16
2–26 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 71
CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATION
Table 2-8: Slots F,G,H with I/O options A,A,F (left) and I/O options A, N, F (right)
Slots F,G,H with I/O options A,A,F Slots F,G,H with I/O options A,N,F
Terminal # SLOT F SLOT G SLOT H Terminal # SLOT F SLOT H
1 RELAY_1 RELAY_9 Digital In_15 1 RELAY_1 Digital In_8 2 RELAY_1 RELAY_9 Digital In_16 2 RELAY_1 Digital In_9 3 RELAY_1 RELAY_9 Digital In_17 3 RELAY_1 Digital In_10 4 RELAY_2 RELAY_10 Digital In_18 4 RELAY_2 Digital In_11 5 RELAY_2 RELAY_10 Digital In_19 5 RELAY_2 Digital In_12 6 RELAY_2 RELAY_10 Digital In_20 6 RELAY_2 Digital In_13 7 RELAY_3 RELAY_11 Digital In_21 7 RELAY_3 Digital In_14 8 RELAY_3 RELAY_11 Digital In_22 8 RELAY_3 Digital In_15 9 RELAY_3 RELAY_11 Digital In_23 9 RELAY_3 Digital In_16 10 RELAY_4 RELAY_12 Digital In_24 10 RELAY_4 Digital In_17 11 RELAY_4 RELAY_12 Common 11 RELAY_4 Common 12 RELAY_4 RELAY_12 +24V 12 RELAY_4 +24V 13 Digital In_1 Digital In_8 ARC 14 Digital In_2 Digital In_9 14 Digital In_2 15 Digital In_3 Digital In_10 15 Digital In_3 16 Digital In_4 Digital In_11 16 Digital In_4 17 Digital In_5 Digital In_12 17 Digital In_5 18 Digital In_6 Digital In_13 18 Digital In_6 19 Digital In_7 Digital In_14 19 Digital In_7 20 Common Common 20 Common 21 +24V +24V 21 +24V 22 RELAY_8 RELAY_16 22 RELAY_8 23 RELAY_8 RELAY_16 23 RELAY_8 24 RELAY_8 RELAY_16 24 RELAY_8
FLASHSensor 1Sensor 2Sensor 3Sensor 4
ARC FLASHSensor 1Sensor 2Sensor 3Sensor 4

Serial Communications

One two-wire RS485 port is provided. Up to thirty-two 8 Series IEDs can be daisy-chained together on a communication channel without exceeding the driver capability. For larger systems, additional serial channels must be added. Commercially available repeaters can also be used to add more than 32 relays on a single channel. Suitable cable should have a characteristic impedance of 120 ohms and total wire length should not exceed 1200 meters (4000 ft).
Voltage differences between remote ends of the communication link are not uncommon. For this reason, surge protection devices are internally installed across all RS485 terminals.Internally, an isolated power supply with an opto-coupled data interface is used to prevent noise coupling.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2–27
Page 72
ELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION
SCADA, PLC, OR PERSONAL COMPUTER
COM
ISOLATION
DATA
8-Series IED
SHIELD
892780A4.CDR
UP TO 32, 8-Series OR OTHER IEDs, MAXIMUM CABLE LENGTH OF 1200 m (4000 ft.)
LAST DEVICE
(*) TERMINATING IMPEDANCE AT EACH END (typically 120 ohms and 1 nF)
TWISTED PAIR
Z (*)
T
RS485 +
RS485 -
COMMON
RS485 +
RS485 -
COMMON
IED
RS485 +
IED
RS485 -
COMMON
GROUND THE SHIELD AT THE
SCADA/PLC/COMPUTER ONLY
OR THE 8-Series ONLY
DATA
ISOLATION
D3
D4
D5
Z (*)
T
Figure 2-29: RS485 wiring diagram
CAUTION:
To ensure that all devices in a daisy-chain are at the same potential, it is imperative that the common terminals of each RS485 port are tied together and grounded only once, at the master or at the 845. Failure to do so may result in intermittent or failed communications.
The source computer/PLC/SCADA system should have similar transient protection devices installed, either internally or externally. Ground the shield at one point only, as shown in the figure above, to avoid ground loops. Correct polarity is also essential. The 845
IEDs must be wired with all the positive (+) terminals connected together and all the negative (–) terminals connected together. Each relay must be daisy-chained to the next one. Avoid star or stub connected configurations. The last device at each end of the daisy-chain should be terminated with a 120 ohm ¼ watt resistor in series with a 1 nF capacitor across the positive and negative terminals. Some systems allow the shield (drain wire) to be used as a common wire and to connect directly to the COM terminal; others function correctly only if the common wire is connected to the COM terminal, but insulated from the shield. Observing these guidelines ensure a reliable communication system immune to system transients.
2–28 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 73
CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATION
GE MULTILIN
8-SERIES
IRIG-B(-)
RECEIVER
TO OTHER DEVICES
SHIELDED CABLE
GPS SATELLITE SYSTEM
GPS CONNECTION OPTIONAL
IRIG-B(+)
D1
D2
+
892781A3.CDR

IRIG-B

TIME CODE
GENERATOR
(DC SHIFT OR
AMPLITUDE MODULATED
SIGNAL CAN BE USED)
IRIG-B
IRIG-B is a standard time code format that allows time stamping of events to be synchronized among connected devices within 1 millisecond. The IRIG-B time code formats are serial, width-modulated codes which can be either DC level shift or amplitude modulated (AM) form. The type of form is auto-detected by the 845 equipment is available for generating the IRIG-B signal; this equipment may use a GPS satellite system to obtain the time reference so that devices at different geographic locations can also be synchronized.
Figure 2-30: IRIG-B connection
relay. Third party
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 2–29
Page 74
ELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION
2–30 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 75
GE
Grid Solutions
845 Transformer Protection System
Chapter 3: Interfaces

Interfaces

There are two methods of interfacing with the 845.
Interfacing via the relay keypad and display.
Interfacing via the EnerVista 8 Series Setup software. This section provides an overview of the interfacing methods available with the 845 using
the relay control panel and EnerVista 8 Series Setup interface parameters (for example, settings, actual values, etc.), refer to the individual chapters.
FIRST ACCESSING THE RELAY
When first accessing the relay, log in as Administrator either through the front panel or through EnerVista connected serially (so that no IP address is required). Use the default password (the default password is “0”).
Basic Security
If the relay is in the commissioning phase and you want to bypass authentication, switch the “Setpoint access” setting on or assign it to a contact input. Once the setting is on, you have complete administrator access from the front panel. If a contact input is chosen, the access is also conditional on the activation of the respective contact input.
For more information on setpoint access and other security features available with basic security, refer to the Basic Security section in the Setpoints chapter.
CyberSentry
If logging in through EnerVista, choose Device authentication and login as Administrator. Note: If the relay is in the commissioning phase and the user wants to bypass
authentication, the user may use the setpoint access feature to gain administrative access to the front panel in the same way as with basic security (see the “Basic Security” section).
For more information on security features available with CyberSentry, refer to the CyberSentry security section in the Setpoints chapter.
software. For additional details on
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3–1
Page 76
FRONT CONTROL PANEL INTERFACE CHAPTER 3: INTERFACES
ESCAPE
ENTER HELP
IN SERVICE
TRIP
ALARM
PICK UP
XFMR OVERLOAD
LOAD-LIMIT REDUCED
XFMR DE-ENERGIZED
CLOSE
RESET
OPEN F1
W1 BKR OPEN
W2 BKR CLOSED
LOCAL MODE
DIFFERENTIAL BLOCKED
TARGETS STATUS METERING SETPOINTS RECORDS
Navigation
Pushbuttons
Menu tabs associated
with pushbuttons for
screens navigation
Pushbuttons for
setpoints, and Up/ Down
value selections
“HELP”:help with
setting selection
“ESCAPE”:return to
previous menu
“Home”:return to
default screen
“ENTER”: enter selected
setting
“RESET”: reset targets,LEDs,
output relays
LEDs #1and LED #4(non-
programmable)
LED#2,LED#3,
and LEDs 5 to 14
(programmable)
Function PBs with LEDs
(programmable)
USB port
Display
LED labels
TEST MODE
MESSAGE
W3 BKR CLOSED

Front Control Panel Interface

The relay provides an easy to use faceplate for menu navigation using 5 navigation pushbuttons and a high quality graphical display. Conveniently located on the panel is a group of 7 pushbuttons for Up/Down value selection, Enter, Home, Escape, Help, and Reset functions. The faceplate also includes 3 programmable function pushbuttons with LEDs. Fourteen other status LEDs are available, 12 of which are programmable.
Figure 3-1: Front Control Panel
Figure 3-2: 845 Front Control Panel)
3–2 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
The USB port is intended for connection to a portable computer.

845 Graphical Display Pages

The front panel liquid crystal display (LCD) allows visibility under varied lighting conditions. When the keypad and display are not being used, system information is displayed after a user-defined period of inactivity. Pressing the Menu key during the display of the default message, returns the display to the last message shown before the default message appeared. Any Trip, Alarm, or Pickup is displayed immediately, automatically overriding the default message.
Page 77
Setpoints
Device
System
Inputs
Outputs
Protection
Monitoring
Control
FlexLogic
S
tatus
Switches
Contact Inputs
Metering
Summary
Currents
Voltages
Frequency
Harmonics
Power
Energy
Current Demand
Records
Events
Fault Reports
Breakers
Remote Modbus Device
Targets
Directional Power
Data Logger
Volts per Hertz
Digital Counters
RTDs
RTD Maximums
FlexElements
Arc Flash
Syncrocheck
Testing
Output Relays
Virtual Inputs
Information
Device Status
Clock
Arc Flash
Virtual Outputs
Communications
PTP Status
Flex States
Last Trip Data
Breakers
Summary
Transformer
Harmonic Magnitude
Transients
Clear Records
Power Factor
Analog Inputs
CHAPTER 3: INTERFACES FRONT CONTROL PANEL INTERFACE
Figure 3-3: 845 Display Page Hierarchy
Working with
Graphical Display
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3–3
Pages
The display contains five main menu items labeled Targets, Status, Metering, Setpoints, and Records located at the bottom of the screen. Choosing each main menu item displays the corresponding sub-menu.
Page 78
FRONT CONTROL PANEL INTERFACE CHAPTER 3: INTERFACES
TARGETS STATUS METERING
SETPOINTS
RECORDS
Figure 3-4: Typical paging operation from the Main Menu
3–4 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
There are two ways to navigate throughout the 845 menu: using the pushbuttons corresponding to the soft tabs from the screen, or by selecting the item from the list of items on the screen using the “Up” and “Down” pushbuttons to move the yellow highlighted line, and pressing the pushbutton “Enter”.
Figure 3-5: Tab Pushbuttons
The tab pushbuttons are used to enter the menu corresponding to the label on the tabs. If more than 5 tabs exist, the first and the last tab are labelled with arrows to allow you to scroll to the other tabs.
Page 79
CHAPTER 3: INTERFACES FRONT CONTROL PANEL INTERFACE
<< NIOC 2 NIOC 3
NIOC 4
>>
ENTER
Figure 3-6: Keypad Pushbuttons
Each Keypad pushbutton serves the following function:
The Home pushbutton is used to display the home screen, and all screens defined under the Front Panel/Screens menu as default screens.
The Enter pushbutton has a dual function. It is used to display a sub-menu when an item is highlighted. It is also used to save the desired value for any selected setpoint.
The Up, and Down pushbuttons are used to select/highlight an item from a menu, as well as select a value from the list of values for a chosen item.
The Up, Down, Left, and Right pushbuttons on the membrane faceplate are used to move the yellow highlight. These pushbuttons are also used on special screens to navigate to multiple objects.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3–5
Page 80
FRONT CONTROL PANEL INTERFACE CHAPTER 3: INTERFACES
ESCAPE
RESET
The Escape pushbutton is used to display the previous menu. This pushbutton can also be used to cancel a setpoint change.
The Reset pushbutton clears all latched LED indications, target messages, and latched output relays, providing the conditions causing these events are not present.
To change (or view) an item on (or from) the 845 menus:
1. Use the pushbuttons that correspond to the tabs (Targets, Status, Metering, Setpoints,
Records) on the screen to select a menu.
2. Use the Up and Down pushbuttons to highlight an item.
3. Press Enter to view a list of values for the chosen item. (Some items are view-only.)
4. Use the Up and Down pushbuttons to highlight a value.
5. Press Enter to assign the highlighted value to the item.
Single Line Diagram BKR1 LED setting for Breaker symbol color configuration
In all 8 Series devices the Breaker symbol color is configurable as per the color scheme setting in
Setpoints > Device > Front Panel > Display Properties > Color Scheme.
Single Line Diagram for 845 and Breaker/Transformer status color The 845 has a single line diagram (SLD) that represents the power system. The single line
diagram provided is pre-configured to show:
•Breaker status
AC input connection
Rated Winding voltage Accompanying the single line diagram are typical metered values associated with the
power system. The single line diagram is configured as the default menu but this can be changed under
Setpoints > Device > Front Panel > Default Screen.
Figure 3-7: SLD and typical metered values screen
The breaker status icon changes state according to the breaker status input and the color scheme setting (
Setpoints > Device > Front Panel > Display Properties > Color Scheme) to
show Breaker status. The winding voltage setting for each breaker is displayed on the associated branch. The
winding configuration icon will display either a 2-winding or 3-winding transformer based on the order code.
3–6 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 81
CHAPTER 3: INTERFACES FRONT CONTROL PANEL INTERFACE
SLD Breaker symbol Color Transformer Status
Color Scheme
Open Color
Close Color
Not
Configured
Unknown Disconnected De-Energized Energized
Not
Configured
Red (Open)
Red Green Orange
Green (Open)
Green Red Orange
The transformer status is indicated in the top right of the display.
The parameters displayed in the Front panel screen example are as follows for a 2­Winding Transformer with VT:
Parameter Input for the value
W1 Ia Metering\ CT Bank 1 -J1\ J1 Ia W1 Ib Metering\ CT Bank 1 -J1\ J1 Ib W1 Ic Metering\ CT Bank 1 -J1\ J1 Ic W2 Ia Metering\ CT Bank 2 -K1\ K1 Ia W2 Ib Metering\ CT Bank 2 -K1\ K1 Ib W2 Ic Metering\ CT Bank 2 -K1\ K1 Ic P: Metering\ Power 1\ Pwr1 Real Q: Metering\ Power 1\ Pwr1 Reactive PF Metering\ Power 1\ Pwr1 PF
The parameters displayed in the Front panel screen example are as follows for a 2­Winding Transformer without VT:
Parameter Input for the value
W1 Ia Metering\ CT Bank 2 -K1\ K1 Ia W1 Ib Metering\ CT Bank 2 -K1\ K1 Ib W1 Ic Metering\ CT Bank 2 -K1\ K1 Ic W2 Ia Metering\ CT Bank 3 -K2\ K2 Ia W2 Ib Metering\ CT Bank 3 -K2\ K2 Ib W2 Ic Metering\ CT Bank 3 -K2\ K2 Ic P: Metering\ Power 1\ Pwr1 Real
Q: Metering\ Power 1\ Pwr1 Reactive PF Metering\ Power 1\ Pwr1 PF
The parameters displayed in the Front panel screen example are as follows for 3-Winding Transformer:
Parameter Input for the value
W1 Ia Metering\ CT Bank 1 -J1\ J1 Ia W1 Ib Metering\ CT Bank 1 -J1\ J1 Ib W1 Ic Metering\ CT Bank 1 -J1\ J1 Ic W2 Ia Metering\ CT Bank 2 -K1\ K1 Ia W2 Ib Metering\ CT Bank 2 -K1\ K1 Ib W2 Ic Metering\ CT Bank 2 -K1\ K1 Ic W3 Ia Metering\ CT Bank 3 -K2\ K2 Ia W3 Ib Metering\ CT Bank 3 -K2\ K2 Ib W3 Ic Metering\ CT Bank 3 -K2\ K2 Ic
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3–7
Page 82
FRONT CONTROL PANEL INTERFACE CHAPTER 3: INTERFACES
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
LED 9
LED 10
LED 11
LED 12
LED 13
LED 14
LED 15
LED 16 LED 17
IN SERVICE
TRIP
ALARM
PICK UP
XFMR OVERLOAD
LOAD-LIMIT REDUCED
XFMR DE-ENERGIZED
W1 BKR OPEN
W2 BKR CLOSED
LOCAL MODE
DIFFERENTIAL BLOCKED
TEST MODE
MESSAGE

Rugged and Membrane Front Panel LEDs

Front panel LED details:
Number of LEDs: 17
Programmability: Any FlexLogic operand
Reset mode: self-reset or latched The 845 front panel provides two columns of 7 LED indicators each, and 3 LED pushbutton
indicators. The “IN-SERVICE” (LED 1) and the “PICKUP” (LED 4) indicators from the first LED column are non-programmable LEDs. The bottom 3 LED indicators from the first column, and the 7 LED indicators from the second LED column are fully programmable. The indicators “TRIP” (LED 2), and “ALARM” (LED 3), are also programmable, and can be triggered by either a selection of FlexLogic operand assigned in their own menu, or by the operation of any protection, control or monitoring element with function selected as Trip, Alarm, or Latched Alarm.
The RESET key is used to reset any latched LED indicator or Target Message once the condition has been cleared (latched conditions can also be reset via the RESETTING menu).
Figure 3-8: LED numbering
Figure 3-9: LEDs for 845 relay protecting 2W Xfmr
3–8 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 83
IN SERVICE
TRIP
ALARM
PICK UP
XFMR OVERLOAD
LOAD-LIMIT REDUCED
XFMR DE-ENERGIZED
W1 BKR OPEN
W2 BKR CLOSED
LOCAL MODE
DIFFERENTIAL BLOCKED
TEST MODE
MESSAGE
W3 BKR CLOSED
CHAPTER 3: INTERFACES FRONT CONTROL PANEL INTERFACE
Figure 3-10: LEDs for 845 relay protecting 3W Xfmr
Some status indicators are common while some are feature specific which depend on the availability in the order code. The common status indicators in the first column are described below.
IN SERVICE Green color = Relay powered up, passed self-test has been programmed, and
ready to serve. This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are OK, and that the device has been programmed.
Red color = Relay failed self test, has not been programmed, or out of service
TRIP This LED indicates that the element selected to produce a trip has operated. This
indicator always latches; as such, a Reset command must be initiated to allow the latch to be reset.
ALARM This LED indicates that the FlexLogic™ operand serving as an Alarm switch has
operated. Latching of the indicator depends on the selected protection function. A Reset command must be initiated to allow the latch to be reset.
PICKUP This LED indicates that at least one element is picked up. This indicator is never
latched.
TEST MODE This LED indicates that the relay has been set into Test Mode.
MESSAGE This LED indicates the presence of Target Messages detected by the relay.
LOCAL MODE This LED indicates that the relay is operating in local mode.
Breaker status indication is based on the breaker’s 52a and 52b contacts. With both contacts wired to the relay and configured, closed breaker status is determined by closed 52a contact and opened 52b contact. Vice-versa the open breaker status is determined by opened 52a contact and closed 52b contact. If both 52a and 52b contacts are open, due to a breaker being racked out from the switchgear, both the Breaker Open and Breaker Closed LED Indicators will be off.
The Event Cause indicators in the first column are described as follows: Events Cause LEDs are turned ON or OFF by protection elements that have their respective
target settings selected as either “Self-Reset” or “Latched”. If a protection element target
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3–9
setting is “Self-Reset”, then the corresponding Event Cause LEDs remain ON as long as the operate operand associated with the element remains asserted. If a protection element
Page 84
FRONT CONTROL PANEL INTERFACE CHAPTER 3: INTERFACES
target setting is “Latched”, then the corresponding Event Cause LEDs turn ON when the operate operand associated with the element is asserted and will remain ON until the RESET button on the front panel is pressed after the operand is reset.
Default labels are shipped in the package of every 845, together with custom templates. A custom LED template is available for editing and printing, refer to publication GET-20035
http://www.gegridsolutions.com/multilin. The default labels can be replaced by user-
from printed labels. User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators.
FASTPATH:
For LED and Pushbutton programming details, please refer to Front Panel.

Home Screen Icons

The next figure shows the icons available on the front screen. For descriptions of these screen icons see the following tables.
Figure 3-11: Home Screen Icons
Table 3-1: Security Icon
Security State Security Icon Color
User not logged in Icon is green and locked User logged in Icon is red and unlocked
NOTE:
The security icon only represents the security access level through the front panel.
Table 3-2: Setpoint Group Icon
Description
Identifies the active setpoint group
Table 3-3: Wifi Icon
Wifi State Wifi Icon Color
Disabled Icon is grey and crossed by a red line Disconnected Grey Connecting Orange Connected Green
3–10 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 85
CHAPTER 3: INTERFACES FRONT CONTROL PANEL INTERFACE
NOTE
Table 3-4: Active Target Icon
Description
When the target auto navigation setting is disabled, the message LED and the Active Target icon are the only indication of active target messages.
Table 3-5: Breaker Health Icon
Description
The Breaker Health icon is blue when the setting for the breaker health function is not disabled. When the setting is disabled the icon is grey.
Table 3-6: Settings Save Icon
Description
Indicates that a setting is being saved on the relay (i.e., when changing one of relay settings). Icon is ON (relay is saving to flash memory) Icon is OFF (relay is not saving to flash memory)
NOTE:
Do not remove power from the relay whenever the Settings Save icon is ON. When power is removed the data being saved can also be lost.
Table 3-7: Local Mode Icon
Description
Indicates that Local Mode is active. During Local Mode, the control for the breakers and disconnect switches can be performed only by the relay front panel.

Relay Messages

Target Messages Target Messages are displayed in order of their activation, whereas in cases of
simultaneous activation, they are displayed in the order outlined below (from highest to lowest priority):
1. Targets generated by pressing programmable pushbutton
2. Targets generated by Contact inputs
3. Targets generated by Protection, Control and Monitoring elements
4. Targets generated by communications.
In cases where the Pickup and Operate flags from an element are detected at the same time, the Pickup flag is not displayed. The Operate flag is displayed instead.
LED #6, from the first column of LEDs, is factory configured to be triggered by the FlexLogic operand ANY TARGET, to indicate the presence of at least one target message. This LED is labeled as “MESSAGE”. The LED can be programmed to any other FlexLogic operand by choice.
MESSAGE TIMEOUT: The timeout applies to each screen that is different than the default screen to which the
user navigates. Examples include viewing, metering, or navigating to a screen with setting, etc. If no further navigation is performed, no pushbutton is touched, and/or no target is initiated for the time specified in the message timeout setpoint, the display goes back to the default screen (the metering summary screen).
The target message interrupts the message timeout. It overrides it. The message timeout starts timing after each target message, and if no more activity is recorded for the specified time, the display goes back to the default screen.
Pressing a programmable pushbutton activates a new screen with a Target Message corresponding to the programmed PB action. The PB Target Message is displayed for 10 seconds then defaults to the screen that was displayed before pressing the pushbutton. The PB Target Message is recorded in the list with other generated Target Messages.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3–11
Page 86
FRONT CONTROL PANEL INTERFACE CHAPTER 3: INTERFACES
NOTE
Target Messages can be cleared either by pressing the PB corresponding to the tab “CLEAR”, or by initiating a RESET command. The “CLEAR” command clears only the Target Messages, while initiating a RESET clears not only the Target Messages, but also any latched LEDs and output relays.
Self-Test Errors The relay performs self-diagnostics at initialization (after power up), and continuously as a
background task to ensure that the hardware and software are functioning correctly. There are two types of self-test warnings indicating either a minor or major problem. Minor errors indicate a problem with the relay that does not compromise protection and control functionality of the relay. Major errors indicate a problem with the relay which takes it out of service.
CAUTION:
NOTE:
Self-Test Warnings may indicate a serious problem with the relay hardware!
Upon detection of a minor problem, the relay does the following:
Displays a detailed description of the error on the relay display as a target message
Records the minor self-test error in the Event Recorder
•Flashes theALARM LED
Upon detection of a major problem, the relay does the following:
De-energizes critical failure relay
De-energizes all output relays
Blocks protection and control elements
Turns the "IN SERVICE" LED to red
Flashes the "ALARM" LED
Displays “Major Self-test error” with the error code as a target message
Records the major self-test failure in the Event Recorder
The Critical Failure Relay (Output Relay 8) is energized when the relay is in-service, and no major error is present
Under both conditions, the targets cannot be cleared if the error is still active.
Figure 3-12: Minor Errors
3–12 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 87
CHAPTER 3: INTERFACES FRONT CONTROL PANEL INTERFACE
Figure 3-13: Major Errors
Table 3-8: Minor Self-test Errors
Self-test Error Message
1
Order Code Error Hardware doesn’t
CPU S/N Invalid CPU card doesn’t have
Slot“$” IO S/N
2
Invalid
Comms S/N Invalid Comms card doesn’t
CPanel S/N Invalid Control Panel doesn’t
PSU S/N Invalid Power Supply Unit
RTC Error The CPU cannot read
Product Serial Invalid
Comm Alert #1 Communication error Comm Alert #2 Every 1 second Comm Alert #3 Every 1 second FLASH Error The permanent storage
SPI Error Communication error
Invalid MAC Address
Calibration Error Unit has default
Description of Problem How Often the Test is
Performed
Every 1 second If alert doesn’t self-reset then
match order code
Every 1 second valid data to match the order code.
IO ca rd lo cated in slot $
Every 1 second doesn’t have valid data to match the order code.
Every 1 second have valid data to match the order code.
Every 1 second have valid data to match the order code.
Every 1 second doesn’t have valid data to match the order code.
Every 1 second the time from the real time clock
The product serial
Every 1 second number doesn’t match the product type
Every 1 second between CPU and Comms board
Every 1 second memory has been corrupted
Every 1 second between CPU and LEDs, Keypad or peripheral memory devices
MAC address is not in
Every 1 second the product range
Boot-up and Every 1 calibration values
second
What to do
contact factory. Otherwise monitor re-occurrences as errors are detected and self­reset
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3–13
Page 88
FRONT CONTROL PANEL INTERFACE CHAPTER 3: INTERFACES
Self-test Error Message
1
WiFi Default Settings
Link Error Primary 3Port 1 or Port 4
Description of Problem How Often the Test is
Performed
SSID and Passphrase is
Every 1 second Set SSID and Passphrase
the factory default
Every 1 second Ensure Ethernet cable is (depending on order code) is not connected
Link Error
Port 5 is not connected Every 1 second Ensure Ethernet cable is
Secondary
Traffic Error Primary
Abnormally high amount of Broadcast
Every 1 second Contact site IT department to
and Uni-cast traffic on port 1 or port 4
Traffic Error Secondary
Abnormally high amount of Broadcast
Every 1 second Contact site IT department to
and Uni-cast traffic on port 5
Ambient Temperature >80C
The ambient temperature
Every 1 second Inspect mounting enclosure
surrounding the product has exceeded 80C
Event Rate High Abnormally high
Every 1 second Ensure settings are not set amounts of events have been generated so the relay has stopped logging to prevent further issues
IRIG-B Failure A bad IRIG-B input
Every 1 second Ensure IRIG-B cable is signal has been detected
Version Mismatch CPU and Comms do not
have the same revision
Boot-up and Every 1
second on firmware
SelfTestFWUpdate The updating of the
Every 1 second Re-try uploading firmware. If firmware failed
Remote CAN IO Mismatch
The value of the cards in the slots detected by the Remote IO does not
Every 1 second. A
failure is declared after
60 consecutive failures match the value validated by the user configuration
1. – Failure is logged after the detection of 5 consecutive failures
2. $ – is the slot ID (i.e., F, G, H etc.)
What to do
connected, check cable functionality (i.e. physical damage or perform continuity test), and ensure master or peer device is functioning. If none of these apply, contact the factory.
connected, check cable functionality (i.e. physical damage or perform continuity test), and ensure master or peer device is functioning. If none of these apply, contact the factory.
check network for malfunctioning devices
check network for malfunctioning devices
for unexpected heat sources (i.e loose primary cables) and remove accordingly
close to nominal ratings. Ensure FlexLogic equations do not have impractical timing for status events
connected, check cable functionality (i.e. physical damage or perform continuity test), ensure IRIG­B receiver is functioning, and check input signal level (it may be less than specification). If none of these apply, contact the factory.
Ensure that both the CPU and Comms FW was uploaded during the upgrade process
the upload doesn’t work a second time contact factory
Fix the remote CANBUS IO mismatch.
3–14 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 89
CHAPTER 3: INTERFACES FRONT CONTROL PANEL INTERFACE
NOTE
3.To disable Link Error Primary target when not in-use with SE order code, change IP address to 127.0.0.1
Table 3-9: Major Self-test Errors
Self-test Error Message
Relay Not Ready
Major Self-Test (error code)
NOTE:
When a total loss of power is present, the Critical Failure Relay (Output Relay 8) is de-
Latched Target Message
No PRODUCT SETUP
Yes Unit hardware fa ilure
Description of Problem
INSTALLATION setting indicates relay is not in a programmed state.
detected
How Often the Test is Performed
On power up and whenever the PRODUCT SETUP INSTALLATION setting is altered.
Every 1 second Contact the factory and
What to do
Program all required settings and then set the PRODUCT SETUP INSTALLATION setting to “Ready”.
supply the failure code as noted on the display.
energized.
Out of Service When the relay is shipped from the factory, the DEVICE IN SERVICE is set to “Not Ready”.
The IN SERVICE LED will be orange and the critical fail relay will be de-energized but this will not be classified as a major self-test. An out of service event will be generated in the event recorder.
Flash Messages Flash messages are warning, error, or general information messages displayed in response
to pressing certain keys. The factory default flash message time is 2 seconds.

Label Removal

The following procedure describes how to use the label removal tool.
1. Bend the tabs of the tool upwards as shown in the image.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3–15
Page 90
FRONT CONTROL PANEL INTERFACE CHAPTER 3: INTERFACES
2. Slide the label removal tool under the LED label as shown in the next image. Make sure the bent tabs are pointing away from the relay. Move the tool inside until the tabs enter the pocket.
3. Remove the tool with the LED label.
The following describes how to remove the user-programmable pushbutton label from the
front panel.
845
1. Slide the label tool under the user-programmable pushbutton label as shown in the next image. Make sure the bent tab is pointing away from the relay.
2. Remove the tool and user-programmable pushbutton label as shown in image.
3–16 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 91
CHAPTER 3: INTERFACES SOFTWARE INTERFACE

Software Interface

EnerVista 8 Series Setup Software

Although settings can be entered manually using the control panel keys, a PC can be used to download setpoints through the communications port. The EnerVista 8 Series
software is available from GE Multilin to make this as convenient as possible. With
Setup EnerVista 8 Series Setup software running, it is possible to:
Program and modify settings
Load and save setting files to and from a disk
Read actual values
Monitor status
Read pre-trip data and event records
Get help on any topic
Upgrade the 845 firmware The EnerVista 8 Series Setup software allows immediate access to all 845 features with
easy to use pull down menus in the familiar Windows environment. This section provides the necessary information to install EnerVista 8 Series Setup firmware, and write and edit setting files.
The EnerVista 8 Series Setup software can run without a 845 connected to the computer. In this case, settings may be saved to a file for future use. If a 845 communications are enabled, the 845 addition, measured values, status and trip messages can be displayed with the actual value screens.
can be programmed from the setting screens. In
software, upgrade the relay
is connected to a PC and
Hardware & Software
Requirements
The following requirements must be met for the software.
Dual-core processor
Microsoft Windows™ 7 or 8.1; 32-bit or 64-bit is installed and running properly.
At least 1 GB of free hard disk space is available.
At least 2 GB of RAM is installed.
1280 x 800 display screen The software can be installed from either the GE EnerVista CD or the GE Multilin website at
http://www.gegridsolutions.com/.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3–17
Page 92
SOFTWARE INTERFACE CHAPTER 3: INTERFACES
Installing the
EnerVista 8 Series
Setup Software
After ensuring the minimum requirements indicated earlier, use the following procedure to install the EnerVista 8 Series Setup software from the enclosed GE EnerVista CD.
1. Insert the GE EnerVista CD into your CD-ROM drive.
2. Click the Install Now button and follow the installation instructions to install the no­charge EnerVista software on the local PC.
3. When installation is complete, start the EnerVista Launchpad application.
4. Click the IED Setup section of the LaunchPad toolbar.
5. In the EnerVista Launchpad window, click the Add Product button and select the 845 Protection System as shown below. Select the Web option to ensure the most recent software release, or select CD if you do not have a web connection, then click the Add Now button to list software items for the 845.
6. EnerVista Launchpad obtains the latest installation software from the Web or CD and automatically starts the installation process. A status window with a progress bar is shown during the downloading process.
3–18 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 93
CHAPTER 3: INTERFACES SOFTWARE INTERFACE
7. Select the complete path, including the new directory name, where the EnerVista 8
Series Setup software is being installed.
8. Click on Next to begin the installation. The files are installed in the directory indicated,
the USB driver is loaded into the computer, and the installation program automatically creates icons and adds the EnerVista 8 Series Setup software to the Windows start menu.
9. The 845 device is added to the list of installed IEDs in the EnerVista Launchpad
window, as shown below.
If you are going to communicate from your computer to the 845 Relay using the USB port:
10. Plug the USB cable into the USB port on the 845 Relay then into the USB port on your
computer.
11. Launch EnerVista 8 Series Setup software from LaunchPad.
12. In EnerVista > Device Setup:
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3–19
Page 94
SOFTWARE INTERFACE CHAPTER 3: INTERFACES
Upgrading the
Software
13. Select USB as the Interface type.
14. Select the Read Order Code button.
The latest EnerVista software and firmware can be downloaded from:
https://www.gegridsolutions.com/
After upgrading, check the version number under Help > About. If the new version does not display, try uninstalling the software and reinstalling the new versions.
3–20 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 95
CHAPTER 3: INTERFACES SOFTWARE INTERFACE

Connecting EnerVista 8 Series Setup software to the Relay

Using the Quick
Connect Feature
The Quick Connect button can be used to establish a fast connection through the front panel USB port of a relay, or through the Ethernet port. The following window appears when the QuickConnect button is pressed:
As indicated by the window, the "Quick Connect" feature can quickly connect the software to a front port if the USB is selected in the interface drop-down list. Select “USB” and press the Connect button. Ethernet or WiFi can also be used as the interface for Quick Connect as shown next.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3–21
Page 96
SOFTWARE INTERFACE CHAPTER 3: INTERFACES
When connected, a new Site called “Quick Connect” appears in the Site List window.
The Site Device has now been configured via the Quick Connect feature for either USB or Ethernet communications. Proceed to Connecting to the Relay next, to begin communications.
Configuring Ethernet
Communications
FASTPATH:
Before starting, verify that the Ethernet cable is properly connected to the RJ-45 Ethernet port.
845 supports a maximum of 3 TCP/IP sessions.
1. Install and start the latest version of the EnerVista 8 Series Setup software (available from the GE EnerVista CD or Website). See the previous section for the installation procedure.
2. Click on the Device Setup button to open the Device Setup window and click the Add Site button to define a new site.
3. Enter the desired site name in the "Site Name" field. If desired, a short description of the site can also be entered. In this example, we will use “Substation 1” as the site name.
4. The new site appears in the upper-left list.
5. Click the Add Device button to define the new device.
6. Enter the desired name in the "Device Name" field, and a description (optional).
3–22 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Page 97
CHAPTER 3: INTERFACES SOFTWARE INTERFACE
7. Select “Ethernet” from the Interface drop-down list. This displays a number of
interface parameters that must be entered for proper Ethernet functionality.
Connecting to the
Relay
8. Enter the IP address, slave address, and Modbus port values assigned to the 845 relay
(from the Setpoints > Device > Communications menu).
9. Click the Read Order Code button to connect to the 845 and upload the order code. If
a communications error occurs, ensure that the Ethernet communication values correspond to the relay setting values.
10. Click OK when the relay order code has been received. The new device will be added
to the Site List window (or Online window) located in the top left corner of the main EnerVista 8 Series Setup software window.
The 845 Site Device has now been configured for Ethernet communications. Proceed to the following section to begin communications.
Now that the communications parameters have been properly configured, the user can easily communicate with the relay.
1. Expand the Site list by double clicking on the site name or clicking on the «+» box to
list the available devices for the given site.
2. Desired device trees can be expanded by clicking the «+» box. The following list of
headers is shown for each device: Device Definition
Status Metering Quick Setup Setpoints Records Maintenance.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3–23
Page 98
SOFTWARE INTERFACE CHAPTER 3: INTERFACES
3. Expand the Setpoints > Device > Front Panel list item and double click on Display Properties or Default Screens to open the settings window as shown:
4. The settings window opens with a corresponding status indicator on the lower left of the window.
5. If the status indicator is red, verify that the serial, USB, or Ethernet cable is properly connected to the relay, and that the relay has been properly configured for communications (steps described earlier).
The settings can now be edited, printed, or changed. Other setpoint and command windows can be displayed and edited in a similar manner. "Actual Values" windows are also available for display. These windows can be arranged, and resized, if desired.

Working with Setpoints & Setpoints Files

FASTPATH:
3–24 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
When a settings file is being uploaded to a device, the DEVICE IN SERVICE state (Setpoints > Device > Installation) switches to "Not Ready" for the duration of the upload. This ensures that all new settings are applied before the device is operational. Settings file upload operations include both 1) Enervista 8 Series Setup software menu option "Write Settings File to Device" and 2) saving Logic Designer changes online.
Individual setting changes from the device front panel or Enervista 8 Series Setup software Online Window do not change the DEVICE IN SERVICE state.
Page 99
CHAPTER 3: INTERFACES SOFTWARE INTERFACE
Engaging a Device The software may be used in on-line mode (relay connected) to directly communicate with
a relay. Communicating relays are organized and grouped by communication interfaces and into sites. Sites may contain any number of relays selected from the product series.
Entering Setpoints The System Setup page is used as an example to illustrate entering setpoints. In this
example, we are changing the voltage sensing setpoints.
1. Establish communications with the relay.
2. Select the Setpoint > System > Voltage Sensing menu item.
3. Select the Aux. VT Secondary setpoint by clicking anywhere in the parameter box. This
displays three arrows: two to increment/decrement the value and another to launch the numerical keypad.
4. Clicking the arrow at the end of the box displays a numerical keypad interface that
allows the user to enter a value within the setpoint range displayed near the top of the keypad: Click = to exit from the keypad and keep the new value. Click on X to exit from the keypad and retain the old value.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 3–25
Page 100
SOFTWARE INTERFACE CHAPTER 3: INTERFACES
5. For setpoints requiring non-numerical pre-set values (e.g. Phase VT Connection below), clicking anywhere within the setpoint value box displays a drop-down selection menu arrow. Select the desired value from this list.
6. In the Setpoints > System Setup > Voltage Sensing dialog box, click on Save to save the values into the 845. Click YES to accept any changes and exit the window. Click Restore to retain previous values. Click Default to restore Default values.
7. For setpoints requiring an alphanumeric text string (e.g. "relay name"), the value may be entered directly within the setpoint value box.
File Support Opening any file automatically launches the application or provides focus to the already
opened application. New files are automatically added to the tree.
Using Setpoints Files The software interface supports three ways of handling changes to relay settings:
In off-line mode (relay disconnected) to create or edit relay settings files for later download to communicating relays.
Directly modifying relay settings while connected to a communicating relay, then saving the settings when complete.
Creating/editing settings files while connected to a communicating relay, then saving them to the relay when complete.
Settings files are organized on the basis of file names assigned by the user. A settings file contains data pertaining to the following types of relay settings:
Device Definition
•Relay Setup
•System Setup
•Protection
Control
Inputs/Outputs
Monitoring
•FlexLogic
•Quick setup
Protection summary
IEC 61850 configurator
Modbus user map
Factory default values are supplied and can be restored after any changes.
3–26 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Loading...