2010 contract sales architects and engineers data manual
Quick Reference
Full Specs on pages 52 and 53
ALL UNITS REQUIRE POWER CONNECTION KIT
Power Connection Kit determines resistance heat output
7000 Btuh units are not offered with 4.7 KW resistance heater
4100 Series Cooling with Electric Heat
MODEL
NUMBER
AZ41E07DA*7300/710012.8/12.8
AZ 41E09 DA*9450/925012.3/12.3
AZ41E12DA*11800/1160011.8/11.8
AZ41E15DA*1470 0/1450 010.6/10.6
AZ41E07EA*730012.8
AZ 41E09 EA*945012.3
AZ41E12EA*1180011.8
AZ41E15EA*1470 010.6
COOLING
(Btuh)
EER
Dry Air 25
4100 Series Cooling with Electric Heat
6100 Series Heat Pump with Backup Electric Heat
MODEL
NUMBER
AZ61H07DA*7200/700013.2/13.26400/62004.0/4.0
AZ 61H09 DA*9400/920012.7/12.78300/81003.8/3.8
AZ 61H12DA*11800/1160012.1/12.11060 0/104003.7/3.7
AZ 61H15DA*14800/14 60011.2/11.214000/139003.3/3.3
AZ61H07EA*720013.264004.0
AZ 61H09 EA*940012.783003.8
AZ 61H12E A*118 0012.1106003.7
AZ 61H15E A*14 80011.2140003.3
COOLING
(Btuh)
EER
REVERSE CYCLE
BTUH
MODEL
NUMBER
AZ41E07DAP6800/660012.2/12.2
AZ 41E09 DAP9000/880011.8/11.8
AZ41E12DAP11200/1100011.3/11.3
AZ41E07EAP680012.2
AZ 41E09 EAP900011.8
AZ41E12EAP1120011.3
COP
COOLING
(Btuh)
EER
4100 and 6100 Series Control Panel
*Dual-rated 230/208-volt units are shown with ratings separated by “/”.
Units with single rating are 265-volt units.
2
Power Connection Kits
geappliances.com
230/208-Volt Line Cord Connection Units
Line Cord
Kit
RA K3153A8150/7900240 0/232011.0/11.615
RAK 3203A11200/109003300/320015.1/16.020
RAK3303A16000/154504700/453021.2/22.430
Electric Heat Amps include electric heater and fan motor current draw.
Each Line Cord Kit has an integral Leakage Current Detection and Interruption (LCDI) or Arc Fa ult
Current Interr upter (AFCI) device as required by National Ele ctrical Code (NEC) and Underwriter s
Laboratories (UL) for units m anufactured after August 1, 2004.
Electric Heat Amps include electric heater and fan motor cu rrent draw.
Units connected through sub-base do not require an LCDI or AFCI device since they are not
considered to be line-cord connected. Each 230/208-volt sub-base kit consists of sub-base wit h
appropriate receptacle for minimum circuit amperage, chaseway to route power connector from
sub-base to chassis, wiring to connect sub-base to building wiring and a short line cord with 9-pin
connector to connect to chas sis and plug into receptacle in sub-base.
Short sub -base line cord may not be u sed without sub-base.
Junction box for 230/208-volt chassis must be purchased separate ly.
RAK4002A for 2900, 3900, 4100, and 6100 series units, RAK4002B for 5800 series units.
Electric Heat Amps include electric heater and fan motor current draw.
265-volt units are to be permanently connected in compliance with National Electrical Code and local codes and have a factory-installed junction box on the chassis.
Each 265-volt sub-base kit consists of sub-base with appropriate receptacle fo r minimum circuit amperage, chaseway to route power connector from sub-base to chassis
and wiring to connect sub-base to building wiring.
265-Volt Power Connection Kit must be ordered separately.
Power
Connection Kit
Direct
Connection Kit
Electric Heat
BTUH
Electric Heater
Watts
Electric Heat
Amps
Min. Circuit Protection
(Amps)
Important
(Amps)
Essential Elements Ordering Overview
230/208-volt line cord connected units — order line cord kit
230/208-volt sub-base connected units — order sub-base
265-volt units — order sub-base and power connection kit
®
Zoneline
Chassis Nomenclature
The Zoneline chassis is identified by a model number defining the type of unit, cooling capacity, electrical information and
optional features included on the unit. When specifying or ordering the Zoneline chassis, the use of this nomenclature will
assure receiving the correct unit.
condensate
removal (ICR)
system (heat
pump models
only) (not for
coastal areas)
P= Dry Air 25 (4100
Series only)
3
The Zoneline® 4100 and 6100 Series have incorporated changes suggested by customers, along with
enhancements by GE’s Technology Team and changes necessary to meet new UL and NEC requirements.
“L” shaped condenser coil.
Cross flow blower across the product line for quieter operation.
The “Partial Open Vent Air” feature was a specific request by a customer.
“Heat Sentinel” is an enhancement developed by GE’s Technology Team to help lodging professionals welcome their
guests with a moderate-temperature room and to help lower cooling costs.
Devices have been added on cord-connected units to protect against injury from unsafe power cords.
See the “Features and Benefits” section for in-depth explanation of these changes and the industry-leading features
of GE Zoneline retained from the previous series.
The Deluxe 4100 Series Zoneline models include The “Dry Air 25” models
which remove 25% more moisture than other Zoneline models.
As warm, humid air is pulled through the pre-cool (front)
section of the heat pipe, the heat removed from the air is
absorbed by the refrigerant, causing the refrigerant to change
to a gas and flow to the re-heat (rear) section of the heat
pipe. The air leaving the pre-cool section of the heat pipe is
cooler and at a higher relative humidity level than the room
air. The pre-cooled air is further cooled as it passes through
the evaporator; consequently allowing the evaporator coil to
remove more moisture.
When the cold air from the evaporator comes in contact
with the re-heat section of the heat pipe, the heat that was
removed by the pre-cool section is added back to the air
— Reduces operating costs — Provides comfort without
overcooling
• Corrosiontreatmentisstandard
• Excellentchoiceforhumidclimates
• Availablein7000,9000and12000BTUsizes
The Dry Air 25 system, a heat pipe, is a hermetically sealed
heat transfer surface installed in a “saddlebag” configuration
around the indoor (evaporator) coil of the Zoneline unit. This
coil arrangement will transfer heat from the front coil of the
saddlebag to the rear coil without power consumption.
This assembly uses R-410A as the refrigerant and is not
connected to the regular Zoneline refrigerant circuit.
and the refrigerant in the heat pipe condenses and flows
back to the pre-cool (front) section. The air discharged into
the room by this process is much drier, creating a more
comfortable room condition.
The Dry Air 25 models center around GE’s exclusive use of
the patented Dinh® Dehumidifier Heat Pipe from Heat Pipe
Technology, Inc. This innovative NASA spin-off technology
enables Dry Air 25 to remove 25% more moisture from the
air than other leading manufacturers’ packaged terminal air
conditioners. This helps maintain room comfort at a higher
room temperature, reducing operating costs.
The Dry Air 25 keeps a room cool and dry, and this is the
most important benefit when it comes to the occupant of
the room—hotel guests, apartment residents, students. In a
hot, humid climate, getting away from the humidity is just
as important as getting away from the heat, and the Dry Air
25 is the perfect solution. The dehumidification of the Dry
Air 25 has been verified by the same ARI test conditions that
standard units are rated under.
4
Table of Contents
Front Cover 1
Mini Specs 4100 and 6100 Series 2
Mini Specs Power Connection Kits and Nomenclature 3
Equipment used as a primary source for
heating or cooling is an integral part of
the building in which it is installed. Proper
application is essential for satisfactory
performance over a wide range of
operating conditions. It is strongly
recommended that a professional
engineer determine proper application.
If the unit is a replacement unit, its
specifications and performance
may differ from those of the unit it is
replacing. For that reason, we again
strongly recommend that a professional
engineer determine proper application.
5
Introduction
This manual is designed to provide product, performance
and application information to our customers and their
architects and engineers for use in selection and design
of a zonal comfort control system utilizing GE Zoneline®
Packaged Terminal Air Conditioners (PTAC) and Packaged
Terminal Heat Pumps (PTHP). GE Zoneline PTACs and PTHPs
are self-contained units designed for through-the-wall
installations in hotels, motels, apartments, hospitals,
nursing homes, add-on rooms and many other installations.
Zoneline units provide individual room or zone control in both
cooling and heating operation. There is a model for practically
every application, ranging in cooling capacity from 7,200 to
14,800 BTUH and heating capacity from 6,400 to 14,000 BTUH
in heat pump operation. See pages 42 and 54 for resistance
heaters available.
Zoneline offers a two-tier lineup: The Deluxe Line consists of
the 4100 Series with electric resistance heat, the 4100 Series
Dry Air 25 Models with enhanced dehumidification for hot
and humid climates and the 6100 Series heat pump. The
6100 Series heat pump features reverse cycle defrost and
simultaneous supplemental resistance heat, when needed,
to maintain room comfort. Both offer tactile touch controls
with digital display and optional corrosion protection.
Deluxe Line Standard Features:
• Two-fan-motorsystemwithIndoorCross-Flow
Blower for quieter operation
• DigitalControls
—LED Temperature Display
—Easy Temperature Selection
—Tactile Touch Pad
NOTE: Dry Air 25 models include all the standard features of the
4100 Series plus standard corrosion protection.
Advantages of the GE Zoneline System:
• FlexibleApplication
— May be installed from flush to finished floor to
3" from the ceiling
— 7,200 to 14,800 BTUH units in same physical size
— Deluxe 4100 and 6100 Series may be ducted to
condition more than one room
— Compatible with Class 2 remote thermostat control
— Compatible with 2-wire CDC or many Energy
Management Systems
• EconomicalInstallation
— No ductwork necessary
— No mechanical equipment rooms or pipes required
for heating/cooling units
— Replacement units fit existing 42"-wide by 16"-high
wall cases
• QuietOperation
— Indoor cross-flow blower
• Energy-SavingOperation
— Units in unoccupied areas may be turned off
— Designed for efficient cooling operation — EERs from
10.6 to 13.2
— Efficient heat pump units — COPs from 3.3 to 4.0
— Extended heat pump operation without sacrificing
room comfort
• EaseofMaintenance
— Permanently lubricated fan motors
— Upfront lift-out interchangeable filters
— Slide-out chassis for easy access for cleaning or if
service is required
• ReverseCycleHeatPumpOperation
The 6100 Series heat pumps utilize the unique GE PTAC
heat pump operation to ensure a comfortable room.
The logic used by the units is the same logic used by
central system heat pumps to provide greater savings.
6
geappliances.com
The Zoneline System
The typical Zoneline installation consists of the wall case (or sleeve), chassis, power cord and exterior grille. Some installations may
use a sub-base for support of the unit or for ease of electrical connections. Each of the components should be the standard
products offered by GE or, in the case of the exterior grille, approved by GE Applications Engineering. Use of components not
specifically designed or approved for use with the Zoneline unit can result in unsatisfactory operation
and can be the cause of failure not covered by the warranty.
Components of the Zoneline System
Typical Installation
Chassis
Room Cabinet
(Deluxe Series shown)
Wall Case
RAB71A (Steel-Insulated)
RAB77A4 (SMC — Molded)
Wall Case Options
(See page 22)
RAG67 (shown)
Grille Options
(See page 40)
Power Connection Kit (required on all units)
Line Cord Kit shown
See pages 42-43
Power Supply Cord
Optional Accessories of the Zoneline System
Chaseway
RAK204D20P Sub-Base (shown)
Power Supply Cord (included with 208V/230V
sub-bases)
See pages 22 and 32 for information on electrical sub-bases and chaseway.
See pages 37-39 for information on ducted installations.
RAK6052 Duct Adapter
RAK601/602
Duct Extension, Register and Trim Flange
7
Zoneline® Features
Resistance heatHeat pump
AZ
41 Series
Cooling EER Range (230 Volts/265 Volts)10.6 - 12.811.3 - 12.211.2 - 13.2
Heating COP Range (230 Volts/265 Volts)N/A N/A 3.3 - 4.0
Refrigerant type R- 410AR- 410AR- 410A
Cross-flow (tangential) blower StandardStandardStandard
Enhanced DehumidificationOptionalStandard—
Heat pump with resistance heat back-up ——Standard
Heat pump with supplemental resistance heat ——Standard
Staged Heating— — 3-Stage***
Universal heaters - UPC**StandardStandardStandard
Tactile touch pad controls with LED StandardStandardStandard
Touch control set-up features StandardStandardStandard
Highly featured microcomputer controls StandardStandardStandard
Electric resistance heat lock-out (above 46°F) ——Standard
Automatic emergency heat StandardStandardStandard
Heat pump defrost system——Reverse cycle
High-Temperature Operation Protection — — Standard
Quickheatrecovery——Standard
Temperature Boost — — Selectable
Separate Indoor & Outdoor
Motors — Permanently Lubricated
2-Speed Outdoor Fan Standard Standard Standard
Indoor fan speed settingsHi/LowHi/LowHi/Low
Fan Only setting—2-speed Hi/LowHi/LowHi/Low
Cool & heat only settings Hi/Low/AutoHi/Low/AutoHi/Low/Auto
“SmartFan” Fan Cycle Control StandardStandardStandard
Auto power recovery StandardStandardStandard
Automatic Compressor Restart Delay StandardStandardStandard
Freeze Sentinel
Heat Sentinel (85F)StandardStandardStandard
Automatic indoor frost control StandardStandardStandard
Temperature limiting Electronic 7-stepElectronic 7-stepElectronic 7-step
Solid-state thermostat StandardStandardStandard
Remote thermostat compatibility StandardStandardStandard
Central desk control compatibility StandardStandardStandard
2-position discharge grille 50º/40ºStandardStandardStandard
Upfront filter (interchangeable) StandardStandardStandard
3-position manual air vent control StandardStandardStandard
Sleep function StandardStandardStandard
Transfer Fan Connections StandardStandardStandard
Ducted Installation Capability OptionalOptionalOptional
Corrosion-treated chassis OptionalStandardOptional
Internal condensate removal (ICR)* ——Optional
*Not for use in corrosive environments
**UPC — Universal Power Cord Connection (see pages 42 and 54).
*** Two stage heating if using remote thermostat
265-volt units must be connected in a manner to meet National Electrical Code and all local codes.
™
( 41F)StandardStandardStandard
ACACDC
AZ
41 Dry Air 25
AZ
61 Series
8
Features and Benefits
geappliances.com
Standard Physical Dimensions
GE has maintained the same dimensions since 1961 —
42" wide x 16" high x 13-3/4" deep
Replacement of older units is made easy.
Weather-Protected Electrical Components
Vital electrical components are protected from the weather
by locating them on the indoor side of the weather barrier.
Weather-Resistant “Superseal”
Properly installed unit in undistorted case keeps air leakage
to a minimum.
7 CFM air infiltration with 25 MPH wind on ICR
units — even less on units without ICR.
Industry specification is 19 CFM of air infiltration.
Heater Sizes to Meet Room Requirements
All units are equipped with a universal heater —
the resistance heat output is determined by power
connection kit.
230/208-volt — Line-Cord Connected Units — 2.4/2.32 KW
with RAK3153A — 15-amp circuit; 3.3/3.20 KW with
RAK3203A — 20-amp circuit; 4.7/4.53 KW with RAK3303A —
30-amp circuit.
230/208-volt - Sub-Base Connected Units — 2.4/2.32 KW
with RAK204D15P — 15-amp circuit; 3.3/3.20 KW with
RAK204D20P — 20-amp circuit; 4.7/4.53 KW with RAK204D30P
— 30-amp circuit.
265-volt — 2.4 KW with RAK5172 — 15-amp circuit; 3.4 KW
with RAK5202 — 20-amp circuit; 4.8 KW with RAK5302 —
30-amp circuit.
Unit Controls
4100 and 6100 Series — touch pad controls with digital
readout of temperature set point.
Highly Featured Microprocessor Controls
Microprocessor controls are programmed to interface with
the temperature sensors to maximize comfort conditions
for the room occupant and provide outstanding features.
Thermistors are used to sense small changes in temperature
to give excellent room control and allow the microprocessor
to monitor and react to changing conditions.
Automatic Emergency Heat
Automatically uses electric resistance heat if the heat
pump output is not sufficient to maintain selected
room temperature.
Reverse Cycle Heat Pump Defrost System
Standard on all Zoneline 6100 Series heat pumps.
Enables heat pump to operate at lower temperatures
when other systems switch to more expensive electric
resistance heat.
See pages 18 and 19 for discussion of heat pump operation
and defrost systems.
High-Temperature Heat Pump Operation Protection
Automatically protects the compressor if heat pump is
operated with high outdoor temperatures.
Power to the outdoor fan is turned off if the indoor coil
gets too hot during heat pump operation to prevent
damage to the compressor.
Quick Heat Recovery – Heat Pump Units
When the unit operation is changed from STOP or COOL to
HEAT, the electric resistance heaters are used to warm the
room to the thermostat set point. This provides faster room
temperature increase for greater guest comfort.
Fan Motors – Permanently Lubricated
All units have two fan motors for quiet operation and
maximum operating efficiency.
Motors are permanently lubricated to reduce maintenance
and totally enclosed to keep dirt and water out of the
motor windings.
Outdoor Fan
The unit automatically selects the most efficient speed
for the outdoor fan. The operating sound level is lower
when the outdoor fan can operate in low speed yet
there are situations where it must operate in high
speed. The unit changes the fan speed automatically.
Indoor Fan Speed Selections – HIGH/LOW
Unit may be operated in HIGH HEAT or LOW HEAT or
HIGH COOL or LOW COOL.
Electric Resistance Heat Lock-Out
To maximize the savings of the heat pump operation, the
Zoneline heat pumps do not utilize the resistance heater
when the outdoor temperature is above 46°F during normal
The unit provides the option of selecting either HIGH or LOW
speed for Fan-Only operation.
Fan-Cycle Switch – “SmartFan”
Unique “SmartFan” allows unit to operate fan continuously
in cooling operation and fan cycle in heating to provide better
guest comfort. Eliminates complaint of cold air draft during
heating operation.
Eliminates need of changing fan-cycle switch seasonally.
“SmartFan” settings are controlled via the auxiliary control
setting push button.
Compressor Random Restart
In the event of a power failure, all compressors attempting
to restart immediately when power is restored can result
in a power surge that can cause another power interruption.
The microprocessors in the Zoneline® units have a random
restart logic system that prevents all units from starting at
the same time.
Rotary Compressor
Smoother operation for quiet, dependable service. GE has
used rotary compressors since 1961.
Compressor Restart Delay
Zoneline units are designed to provide a minimum of three
minutes of compressor off time to allow refrigerant pressures
to equalize before restarting to prevent compressor damage.
Zoneline units are also designed to provide a minimum
of three minutes of compressor run time to prevent room
occupant disturbance due to short-cycling of the air
conditioner.
Freeze Sentinel
Detects low room temperature and turns on heater to
help protect against damage caused by freezing room
temperature.
Heater turns on at 41°F and warms indoor thermistor
temperature to 46°F and shuts off.
Freeze Sentinel may be turned off by dip switch on
auxiliary control.
™
Heat Sentinel
The property owner may choose to activate the Heat Sentinel
feature on the Zoneline unit. If the Heat Sentinel is activated
and room temperature reaches 85°F while the
unit is in the “STOP” setting, the unit will automatically start
in air conditioning operation and will shut off when the room
temperature reaches 80°F. This will help dehumidify the air
and lower high temperatures so the guest will not be entering
an extremely hot room.
Indoor Coil Frost Control
Prevents indoor coil from freezing
and causing complaints due to lack
of cooling. Frost can form on the
indoor coil when the unit is operated
in cooling when outdoor temperatures
are low. The unit automatically shuts
the compressor off until the indoor coil
temperature warms to the point where
frosting will no longer occur.
Transfer Fan Interface
24 VAC terminals are provided to operate a relay to control
a fan mounted in a wall to move conditioned air into another
space. The electrical power for the operation of the transfer
fan itself is not provided by the Zoneline unit. Transfer fans
and their controlling relays are field supplied.
Electronic Temperature Limiting
Seven independent programmable heating temperature
limits and seven independent programmable cooling
temperature limits.
Heating Temperature Limits
6570727476788085
Lowest
Cool
6064666870727476
Limits are set via the auxiliary control setting push button.
Cooling Temperature Limits
Highest
Heat
Remote Control Capability with Wall-Mounted
Thermostat
See pages 15–17.
Central Desk Control Capability
See page 14.
Energy Management System Interface with
Load-Shedding Option
All units have a switch via the auxiliary control setting to
allow the indoor fan to continue operating if the unit is
connected to an energy management system that shuts off
compressor or heater operation. By allowing the indoor fan to
run when the heater or compressor is shut off by the energy
management system, the guest is less likely to realize the
operation of the unit has been altered. This helps reduce peak
energy demand loads without disturbing the room occupant.
Reversible Indoor Air Louvers
Allows air to be directed into room at 40º or 50º angle to
provide better air distribution.
Angle is changed by removing room front and screws
holding louver in place, and rotating louver section.
10
Features and Benefits
geappliances.com
Up-Front Air Filters
Two interchangeable
up-front filters, easy
to remove and reinstall,
may be cleaned without
opening or removing
the room front.
Clean filters by brushing,
vacuuming or backflushing under faucet
or shower head.
Concealed Manual
Vent Control
Open ventilation doors on
GE Zoneline® Packaged
Terminal Air Conditioners
and Heat Pumps allow
outside air to enter the room through a screen-covered
opening in the weather barrier that separates the indoor
and outdoor sections of the unit.
A concealed lever is located along the left side of the unit
under the front cover is used to open and close the vent door.
The 3-position manual vent door control may be closed,
partially open or fully open. Positive vent door closure
prevents accidental opening and unwanted air infiltration.
Vent CFM High Speed
U n i t F u l l O p e n P a r t i a l O p e n
7000 50 40
9000 70 45
12000 75 45
15000 75 45
CFM ratings at 230 and 265 volts.
For each CFM of air to enter the room, an equal amount of
air must be removed through exhaust fans in the bathroom
or roof tops. Greater amounts of air will be introduced (from
chart shown above) depending on the size of the exhaust fan.
Outside ambient air entering the room through this screened
vent opening is not conditioned. This unconditioned air
becomes mixed with the conditioned air that is circulated by
the indoor fan. This air mixture generates an additional heat
load/heat loss that causes the unit to run longer and may
translate into higher operating costs.
Zoneline vent openings are not intended to be the source
of make-up air for building ventilation systems due to the
additional heating or cooling loads generated.
Corrosion Protection (Optional)
4100 and 6100 Series units may be ordered with special
protection to better withstand damage from salt air and
salt water in seacoast areas.
Corrosion protection is standard on the Dry Air 25 models.
Heat pump units with ICR are not available with corrosion
protection and should not be installed in seacoast or
corrosive environments.
Units installed in corrosive areas should use the RAB77 wall
sleeve and be examined/cleaned more frequently than
normal installations.
Internal Condensate Removal (ICR)
See page 34 for a discussion of the Internal Condensate
Removal system available on 6100 Series heat pumps.
Enhanced Dehumidification
Moisture removal is an important function of an air
conditioner. People are more comfortable at higher
temperatures when the humidity level is relatively low.
Air conditioners operate with less energy consumption
when the room temperatures are set higher.
The GE Zoneline 4100 Series with the Dry Air 25 heat pipe
application removes 25% more moisture than the base
4100 Series unit.
The GE Zoneline Dry Air 25 chassis is the only PTAC available
with the application of the patented Dinh® Dehumidifier
Heat Pipe under license from Heat Pipe Technology, Inc.
Customers who are using the Dry Air 25 report a freshersmelling room as a result of the lower humidity levels, as
well as lower operating costs.
Locking Door Kit
RAK8023 — A door with a lock that replaces the standard
control cover door to prevent unauthorized changing of
control setting is offered as an accessory.
11
Auxiliary Control—Aux Set Button
The auxiliary control push button is located behind the room
cabinet, below the control panel. The auxiliary controls come
preset to the modes most desired by customers. However,
the owner is responsible for ensuring the auxiliary controls
are set to the desired function. There are 9 different modes
that can be set using the auxiliary set button.
the first digit in the display shows the number
corresponding to the mode you are choosing
and the correct HEAT/COOL LED is lit.
•Presstheupordownarrowtochangethemode
setting selection (second digit in the display).
•PresstheMODEbuttontomovetothenextfeature
or the AUX SET button to exit the set up process.
Auxiliary Set Button
Access
Cover
Auxiliary Control Settings
Mode 1—Smart Fan—Cooling/Heating
The default setting for Mode 1 is as follows:
Cooling: Continuous (ON)
Heating: Cycle (OFF)
Mode 2—Load Shedding (Central Desk Control)
The default setting for Mode 2 is OFF.
This feature is active only if the unit is connected to a
CDC and the CDC has control. When this mode is on,
only the indoor fan can be turned ON or OFF with the
unit controls. When this mode is off, all operation is
disabled except Heat/Freeze Sentinel (Mode 3).
12
Auxiliary Control Settings (cont)
Mode 3—Freeze Sentinel/Heat Sentinel
The default settings for Mode 3 are:
Heat Sentinel is off
Freeze Sentinel is on.
When Freeze Sentinel is activated, it automatically provides
heat without user interface. This helps to prevent plumbing
damage by turning the heater and indoor fan ON at 41ºF and
OFF at 46ºF.
When Heat Sentinel is activated, it automatically provides
cooling without user interface. This helps to prevent an
excessively hot room by turning the air conditioner ON at 85ºF
and OFF at 80ºF.
NOTE: These functions are active whenever the unit is plugged
in, even if the unit is in the STOP position.
Mode 4—Constant ON Fan
The default setting for Mode 4 is OFF.
Mode 5—Temperature Limiting
The default setting for Mode 5 is as follows:
Cool: 0 (60ºF to 85ºF)
Heat: 7 (60ºF to 85ºF)
geappliances.com
Temperature limits—Cool Temperature limits—Heat
0 = 60°F to 85°F 0 = 60°F to 65°F
1 = 64°F to 85°F 1 = 60°F to 70°F
2 = 66°F to 85°F 2 = 60°F to 72°F
3 = 68°F to 85°F 3 = 60°F to 74°F
4 = 70°F to 85°F 4 = 60°F to 76°F
5 = 72°F to 85°F 5 = 60°F to 78°F
6 = 74°F to 85°F 6 = 60°F to 80°F
7 = 76°F to 85°F 7 = 60°F to 85°F
Mode 6—Remote Thermostat – Class 2
The default setting for Mode 6 is OFF.
Setting this mode to ON will allow the unit to operate
with a Class 2 Remote Control Wall Thermostat.
Mode 7—Duct Mode
The default setting for Mode 7 is OFF.
This setting is used when the unit is installed using a duct
adapter kit. If the unit is ducted, the Duct Mode needs to
be set to ON. This increases the fan speed to ensure proper
circulation.
Mode 8—All-Electric Heat (AZ6100 only)
The default setting for Mode 8 is OFF.
This electric heat option functions only on the 6100 model.
When this option is ON, heat pump operation is locked out,
causing the unit to provide only electric resistance heat.
Mode 9—Heat Boost (AZ6100 only)
The default setting for Mode 9 is OFF.
When Heat Boost is ON and outer temperatures are between
25ºF and 46ºF, heat pump only operation is locked out. This
setting is used to provide supplementary heat to the heat
pump operation by electric resistance heat in conditions
where the heat pump-only operation is not sufficient to
maintain a consistent, comfortable room temperature. NOTE:
Temperature Boost option should NOT be used with remote
thermostat operation. This will cause the unit to switch to
resistance heat when the outdoor temperature is 46ºF.
13
Central Desk Control
Unit #2
Unit #1
Unit #3
CDC Terminals
on Zoneline unit
Some installations may want to govern the ability of the unit
to operate from a control device remote to the unit or even
remote to the room in which the unit is located. The general
term given to systems such as this is Central Desk Control.
The most common installation of this type of system is a
switch mounted at the registration desk and, upon guest
check-in, a button is pushed or a switch is moved to allow
the air conditioner to operate. Likewise, when the guest
checks out the device is put into the “OFF” position so the
unit will not operate while the room is vacant.
It is not necessary that the controlling device be located
at a central desk to employ a device that will control the
unit operation. For instance, in some resort areas devices
are connected to sliding glass doors and opening the door
causes a contact to close, turning the air conditioner off.
This prevents energy being wasted by operating the air
conditioner when warm, humid air is entering the room.
Some systems operate by motion sensors or heat-sensing
detectors mounted in the room. These types of systems
determine occupant presence in the room and allow the
unit to operate; if no one is in the room the device signals
the air conditioner to turn off.
Zoneline® models offer load-shedding capabilities on
units connected to Central Desk Control systems. For
more information on the models’ load-shedding feature,
see page 10.
There is a wide variety of devices available, each with
its own benefits and constraints. While GE does not offer
components that are external to the unit for a Central Desk
Control (CDC) system, GE Zoneline units are compatible with
most CDC and energy management systems. Zoneline units
provide a 24 VAC circuit that powers the Central Desk
Control system and no external power is needed.
All Zoneline 4100 and 6100 Series units are compatible with
simple on/off 2-wire Central Desk Control systems. Consult
with the provider of the energy management system to be
sure it is compatible with GE Zoneline units. Zoneline units
have standard connectors factory-installed to provide a
CDC interface that permits the unit to be connected to most
of the energy management systems. The devices connected
to the Zoneline units require no power supply or transformers
external to the unit.
Important CDC Comments (all series applicable)
4. Recommended wire size must be followed as a minimum
requirement.
Wire Size #AWG Maximum Allowable Length
#22 600 Ft.
#20 900 Ft.
#18 1500 Ft.
#16 2000 Ft.
Freeze Sentinel™ and Heat Sentinel remains operational when
the unit is connected to a CDC system. Even if the unit is
turned “OFF” at the central location, if the sensor at the unit
detects the low or high limit temperature, the unit will
automatically turn on until it reaches the preset shutdown
temperature (46°F heating, 80°F cooling).
Connecting the Zoneline unit to a CDC system does not
eliminate the ability to connect the unit to a remote thermostat.
Once the circuit is “opened,” and control of the unit removed
from the CDC system, the selected controls—either the unit—
mounted control or the remote thermostat—govern the
operation of the unit.
Please see page 55 for installation recommendations
for the Central Desk Control wiring.
CDC Terminal Location and Typical Wiring
See page 15 for location of CDC terminals on unit.
Example of Common Busing
NOT PERMITTED
INCORRECT Common Busing
Normally Open
Switch -
Unit Operational
1. When the switching device closes the circuit of the CDC
conductors, the unit operation stops.
2. Do not use a common bus (at the unit or at the switch
panel) in the wiring. Both wires comprising the circuit
must connect to the unit connectors and to the controlling
switch. Running one wire from one unit to another unit is
common busing and may damage internal components
or cause erratic operation of the system.
3. A 24-volt transformer is contained within the Zoneline unit.
No external voltage may be applied to the unit through
the CDC terminals. (Voltage on the CDC conductors is
24 volts AC.)
14
Typical Wiring
(All Wiring Shown Is Field Supplied)
Remote Thermostat Control
R
GL
GH
B
Y
W
C
Common
White — Heater
Yellow — Compressor
Black — Not Used On 4100
Green — High-Speed Fan
Green — Low-Speed Fan
Red — 24V AC
CDC Terminal
CDC
geappliances.com
In some installations, control of the operation of the unit at
a location remote from the unit itself may be desired. A unit
mounted high in the wall or over a door, for instance, where
the unit-mounted controls are inaccessible, can be connected
to a wall-mounted thermostat. Other installations may use
remote thermostat control for design or performance
enhancement. The unit is connected to the thermostat by
low-voltage wiring which permits the operation of the unit to
be selected and the temperature sensed at the thermostat.
Important Notes: Remote thermostat wiring should NOT be
run through wall case. Thermostat wiring should exit the
wall below the unit and enter the unit between room cabinet
and chassis. Wire molding may be used to hide thermostat
wiring. If a sub-base is used, the thermostat wiring may be
concealed by the sub-base. Thermostat wiring should NOT be
run parallel to line voltage wires since induced current may
cause erratic operation.
All Zoneline 4100 and 6100 Series units are adaptable to Class
2 remote low-voltage thermostat. The only additional fieldsupplied components are the remote thermostat and wiring
necessary to connect it.
The controls on the unit are not functional when the remote
control function is used.
Resistance Heat Models
The Zoneline 4100 resistance heat units may be connected
to a single-stage thermostat designed for use with cooling
with electric heat systems. GE offers two thermostats
compatible with the 4100 Series unit.
The fan speed for the 4100 Series in remote thermostat
operation is selected by the connection of the fan wire from
the thermostat to either the HIGH or LOW terminal on the unit.
See the sketch of the unit terminals below for the location of
the HIGH and LOW fan-speed terminals. Operating the unit in
low fan speed reduces the operating sound level of the unit.
Freeze Sentinel™ and Heat Sentinal remain operational if the
unit is connected to a remote thermostat. The unit may be
connected to a Central Desk Control (CDC) system and
controlled with a remote thermostat when the CDC system has
the unit in operation. See page 14 for additional information on
the CDC system.
Unit temperature limiting settings are not functional when unit
is connected to a remote thermostat.
Field Wiring Terminal
R — 24V AC
GL — Low-Speed Fan
GH — High-Speed Fan
B — Not Used on 4100
Y — Compressor
W — Heater
C — Common
RAK806 Universal Control Cover Label
RAK164D1 —
a solid-state
digital thermostat
requiring five
connection wires.
RAK164P1 —
a solid-state digital
programmable
thermostat
requiring five
connection wires.
The remote thermostat-Class 2 option (Mode 6 in the auxiliary
control setting) must be turned ON to enable remote
thermostat control. Refer to installation instructions packaged
with the chassis.
Please see page 55 for installation recommendations for
the remote thermostat wiring.
Compatibility of other thermostats considered for use with
GE Zoneline units is the responsibility of the customer. The
control voltage on the remote control conductors is 24 volts
AC. The AC voltage may not be compatible with some
solid-state thermostats.
When a Zoneline unit is using a remote thermostat control,
the RAK806 Universal
Control Cover Label is
recommended. The
RAK806 is only
available in a
package of 10 labels.
The label is placed
over the control panel
to direct the user to
the wall thermostat
for operation of the
Zoneline unit.
15
Remote Thermostat Control
R
GL
GH
B
Y
W
C
Common
White — Heater
Yellow — Compressor
Black — Reversing Valve
Green — High-Speed Fan
Green — Low-Speed Fan
Red — 24V AC
CDC Terminal
CDC
Heat Pump Models
The Zoneline® 6100 Series heat pump units may be
connected to a single-stage cooling/two-stage heating
thermostat designed for use with heat pump systems.
GE offers two thermostats compatible with the
6100 series units:
RAK148D1 —
solid-state digital
thermostat
requiring six
connection wires.
Please see page 55 for installation recommendations
for the remote thermostat wiring. Compatibility of other
thermostats considered for use with the GE Zoneline
unit is the responsibility of the customer.
The control voltage on the remote control conductors is 24 VAC.
The remote thermostat-Class 2 option (Mode 6 in the
auxiliary control setting) must be turned ON to enable remote
thermostat control. Refer to installation instructions packaged
with the chassis.
The fan speed for the 6100 Series in remote thermostat
operation is selected by the connection of the fan wire from
the thermostat to either the HIGH or LOW terminal on the
unit. See the sketch of the unit terminals for the location of
the HIGH and LOW fan speed terminals. Operating the unit in
low fan speed reduces the operating sound level of the unit.
RAK148P1 —
solid-state digital
programmable
thermostat
requiring six
connection wires.
FeatureHeat PumpElectric Heat
Indoor Frost ControlYesYes
Freeze Sentinel
Heat SentinelYesYes
Auto Fan SpeedNoNo
Electronic
Temperature Limiting NoNo
Switch to Resistance
Heat Based on Indoor
Temperature
Switch to Resistance
Heat Based on
Outdoor Temperature YesN/A
Reverse Cycle Defrost YesN/A
Simultaneous
Resistance Heat
with Heat PumpNoN/A
Resistance Heat
LockoutYe sN/A
“Smart Fan”
Fan Cycle
Central Desk ControlYesYes
™
YesYes
Determined by
Remote ThermostatN /A
Fan ON/AUTO Set On
Remote Thermostat
Fan ON/AUTO Set On
Remote Thermostat
When connected to a remote thermostat, the indoor-airtemperature sensing is shifted from the unit to the remote
thermostat. For this reason, the units will operate slightly
differently when connected to a remote thermostat. The
above chart shows the unit operation when connected
to a remote thermostat.
Boost heat option should NOT be used with remote
thermostat operation since this will cause the unit to
switch to resistance heat when outdoor temperatures
are below 46ºF.
Field Wiring Terminal
R — 24V A C GL — Lo w- Sp ee d Fa n
GH — High-Speed Fan B — Reversing Valve
Y — Compressor W — Heater
C — Common
16
geappliances.com
Remote Thermostat Control Selection Chart For Zoneline Packaged Terminal Units
Thermostat wire size – up to 60 feet AWG20 – up to 66 feet AWG18
For remote thermostat operation follow the steps below:
1. Turn on the unit and ensure it is working properly
BEFORE proceeding.
2. Unplug the unit or disconnect power and remove
the room cover.
3. Connect the thermostat wiring per the appropriate
diagram/colors for your model.
4. Plug the unit back in or reconnect power.
5. Press the Aux Set button once. The letters AU will
appear in the display.
6. Press the mode button until the number “6” appears
in the left hand digit.
7. Press the up arrow once so the top half of the right
hand digit is lit.
8. Press the Aux Set button to exit the setup function.
9. Replace the room cover.
Cooling and Heating
Single-Stage Cooling –
2-Stage Heating
5
6
See pages 12 and 13 for full instructions on using the
Auxiliary Controls Feature.
17
Heat Pumps and Energy Savings
• GEZoneline® heat pumps are designed to provide
cost-efficient heat pump operation while monitoring
room conditions to maintain comfort.
The units employ a logic system monitoring both outdoor
and indoor temperatures to determine the heat source, thus
increasing energy savings by operating longer in the heat
pump mode.
Heat pumps save energy and cost less to operate than
units with electric resistance heaters as the only heat source.
Just as the EER of an air conditioner is an indication of the
efficiency of the unit, COP (Coefficient of Performance) is the
indication of the efficiency of the heat pump. This relative
efficiency of a heat pump compares the unit to electric
resistance heat. If a unit has a COP of 3.0, it means the
unit will produce three times as much heat at rating
conditions for the same electrical input wattage used
for electric resistance heat.
The compressor is used in heat pump operation just as
in air conditioning operation. In heat pump operation,
the hot refrigerant gas is directed to the indoor coil rather
than to the outdoor coil. Room air that circulates over the
indoor coil gains heat from the coil rather than losing heat
to the coil as during cooling operation.
As the outdoor temperature falls, the heat pump is able to
extract less heat from the outdoor air to raise the temperature
of the indoor air. For this reason, all packaged terminal heat
pumps also have electric resistance heaters as backup to heat
pump operation. At some point, the heat pump is unable to
provide sufficient heat to adequately warm the room. Many
Packaged Terminal Heat Pumps cease heat pump operation
and change to more expensive resistance heat at some
pre-determined outdoor temperature to compensate for
the inability of the heat pump to maintain room temperature.
This point, called the “switchover point,” is usually at an outdoor
temperature where savings from heat pump operation may
still be realized if the unit is designed to maintain room comfort
at the lower outdoor temperatures.
Balance Point
An important consideration in the selection of a heat pump
unit is the “balance point” of the installation. Virtually every
room is unique—with different insulation, different sizes
and types of windows, different types of construction,
different directional exposures. All these variables, as well
as geographical location, must be considered in order to
determine the balance point, the point at which the heat pump
is unable to produce enough heat to compensate for the heat
loss of the room or area being heated. For these reasons a
consulting engineer should be engaged to calculate the heat
loss and specify the heat pump unit required.
GE offers the 6100 series of Zoneline heat pump units—with
highly featured microprocessor controls—react to the
indoor temperature as well as the outdoor temperature in
determining the heat source to provide comfortable room
conditions and energy savings. This determination of the heat
source based on the indoor temperature helps provide a more
comfortable room.
18
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.