GE 60-960-95 User Manual

*(6HFXULW\
)
ZZZ*(6HFXULW\FRP
Part Number: 60-960-95
T e s t S y s te m W e e k ly
A
B
C
D
p r e s s b o t h
p r e s s b o t h
p r e s s b o t h
O f f
N o D e la y
F e a t u r e s
S t a tu s
*
466-2061 Rev C June 2004
S t a y
2
S i le n t
5
S y s t e m
8
L ig h ts
0 #
B y p a s s
A w a y
3
6
M e n u
9
S y s t e m i s O K
1
4
7
Q u ic k G u id e
D is a r m S y s t e m / C a n c e l A la r m
P r es s 1 + C O D E .
A r m t o S T A Y
1
C l o s e a ll p ro te c te d d o o r s a n d w i n d o w s .
2
P r es s 2 + C O D E .
3
P r es s 4 t o a r m d e la y d o o r s i n st a n t ly , if d e si r ed .
A r m t o A W A Y
1
C l o s e a ll p ro te c te d d o o r s a n d w i n d o w s .
2
P r es s 3 + C O D E .
3
E x i t p r em is e s t h r o u g h d el a y d oo r .
Z o n e / S e n s o r N u m b e r
0 1 0 2 0 3 0 4 0 5 0 6 0 7
Concord Ultra
Installation Instructions
B y p as s S e n so rs
1
A r m s ys t e m t o d e s ir e d le v e l.
2
P r es s B Y P A S S + C O D E + S en so r N o .
T u r n C H I M E O n / O ff
1
M ak e su r e sy s t em i s d i s a rm ed .
2
P r es s 7 + 1 t o tu r n C H IM E o n o r o f f.
P r o g r a m U se r S e t t in g s
1
M ak e su r e sy s t em i s d i s a rm ed .
2
P r es s A o r B t o s c r o ll t h r o u g h m e n u s . P r es s # t o s e le c t o p t i o n o r ac c e p t e n t r P r es s to d e se l e ct o p t io n o r c a n c e l e n t ry . P r es s 1 f o r O FF ; p r e s s 2 fo r O N ; p r es s 0 - 9 fo r o th er e n t r ie s .
0 8 0 9 1 0 1 1 1 2 1 3 1 4
A r m e d
R e a d y
S ta y
T e st S y s te m W e e k l y
y .
Q u ic k E x i t
O f f
A
p r e s s b o t h
N o D e la y
415
B
p r e s s b o t h
F e a tu r e s
C
7
p r e s s b o t h
S ta t u s
D
*
2
S il e n t
S y s te m
8
L ig h t s
0 #
B y p a s s
A w a y
3
6
M e n u
9
Notices
FCC Part 15 Information to the User
Changes or modifications not expressly approved by GE Security can void the user’s authority to operate the equipment.
FCC Part 15 Class B
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the affected equipment and the panel receiver to separate outlets, on different branch circuits.
Consult the dealer or an experienced radio/TV technician for help.
ACTA Part 68
This equipment complies with Part 68 of the FCC Rules. Located on this equipment is a label that contains, among other information, the FCC registration num­ber and the ringer equivalence number (REN) for this equipment. If requested, this information must be provided to the telephone company.
FCC Part 68 Registration No. B4ZUSA-25644-AL-E The REN is used to determine the maximum number of devices that may be connected to your telephone line. Excessive RENs on a telephone line may result in
devices not ringing in response to an incoming call. In most areas, the sum of all device RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to a line, as determined by the total RENs, contact the local telephone company. For products approved after July 23, 2001, the REN for this product is part of the product identifier that has the format US:AAAEQ##TXXXX. The digits represented by ## are the REN without a decimal point (e.g., 03 is a REN of 0.3). For earlier products, the REN is separately shown on the label.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part 68 rules and require­ments as adopted by ACTA. A compliant telephone cord and modular plug is provided with this product. It is designed to be connected to a compliant modular jack that is also compliant. See the Installation Instructions for details.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly installed RJ31X jack that is electrically in series and ahead of all other equipment attached to the same telephone line. Proper installation is depicted in the fol­lowing diagram. If you have any questions concerning these instructions, consult your local telephone company or a qualified installer about installing an RJ31X jack and alarm dialing equipment for you.
C u s t o m e r P r e m i s e s E q u i p m e n t a n d W i r i n g
N e t w o r k S e r v i c e P r o v i d e r ' s F a c i l i t i e s
R J 3 1 X
J a c k
R J - 1 1 J a c k
U n u s e d
A l a r m D i a l i n g E q u i p m e n t
C o m p u t e r
T e l e p h o n e L i n e
N e t w o r k D e m a r c a t i o n P o i n t
T e l e p h o n e
A n s w e r i n g S y s t e m
F a x M a c
h i n e
T e l e p h o n e
T e l e p h o n e
U n u s e d R J - 1 1 J a c k
If this equipment causes harm to the telephone network, the telephone company may temporarily disconnect your service. If possible, you will be notified in advance. When advance notice is not practical, you will be notified as soon as possible. You will also be advised of your right to file a complaint with the FCC.
The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the equipment. You will be given advance notice in order to maintain uninterrupted service.
If you experience trouble with this equipment, please contact the company that installed the equipment for service and/or repair information. The telephone com­pany may ask you to disconnect this equipment from the network until the problem has been corrected or you are sure that the equipment is not malfunctioning.
This equipment may not be used on coin service provided by the telephone company. Connection to party lines is subject to state tariffs.
Patent Information
This product and the use of this product may be covered by one or more of the following patents: 5,805,063, 5,872,512, 5,942,981, 5,686,896, 5,686,885, 4,855,713. Except expressly provided herein, the purchase of this product shall not constitute a license or otherwise provide a right to practice a method covered by any of the identified patents. GE Security hereby grants the purchaser of this product a limited, non-exclusive license to practice the methods patented in the identified patents solely with products manufactured, sold or licensed by GE Security. This license grant does not extend to the use of unlicensed, third party products with this product.
Contents
About This Manual 1
Special Installation Requirements .............................................................................................................. 1
Planning the Installation 3
Standard Panel ............................................................................................................................................ 4
SuperBus 2000 Touchpads.......................................................................................................................... 4
Supervised Wireless Siren .......................................................................................................................... 4
SnapCards................................................................................................................................................... 5
SuperBus 2000 8Z Input Module (HIM).................................................................................................... 5
SuperBus 2000 4-Relay Output Module (HOM)........................................................................................ 5
Interrogator 200 Audio Verification Module.............................................................................................. 5
SuperBus 2000 Cellular Backup Module ................................................................................................... 5
SuperBus 2000 Energy Saver Module (ESM)............................................................................................ 5
SuperBus 2000 Automation Module .......................................................................................................... 5
SuperBus 2000 Wireless Gateway Module ................................................................................................ 5
UL Listed Installations............................................................................................................................ 1
SIA System Requirements...................................................................................................................... 2
Central Station Reporting ....................................................................................................................... 3
UL Canada Listed Installations............................................................................................................... 3
California State Fire Marshall Listed Installations................................................................................. 3
Installing the System 5
Determine the Panel Location..................................................................................................................... 6
Total System Power and Wire Length Guidelines...................................................................................... 6
Mounting the Panel..................................................................................................................................... 8
Identify Panel Components 9
Installing Antennas..................................................................................................................................... 9
Connecting the Panel to Earth Ground ..................................................................................................... 10
Installing Optional SnapCards.................................................................................................................. 10
Connecting Detection Devices to Panel Zone Inputs ............................................................................... 11
Connecting Intrusion Detection Devices.............................................................................................. 11
Connecting 2-Wire Smoke Detectors ................................................................................................... 11
Connecting 4-Wire Smoke Detectors ................................................................................................... 12
Connecting Speakers................................................................................................................................. 12
15-Watt Speaker (13-060)..................................................................................................................... 12
Hardwire Interior Speaker (60-528) ..................................................................................................... 13
Connecting Piezo Sirens........................................................................................................................... 13
Exterior Sirens ...................................................................................................................................... 14
Interior Sirens ....................................................................................................................................... 14
Installing Supervised Wireless Sirens (60-736-95) .................................................................................. 14
Connecting an Interrogator 200 Audio Verification Module (60-677)..................................................... 15
Connecting Alphanumeric and Fixed Display Touchpads ....................................................................... 16
Installing SuperBus 2000 Modules........................................................................................................... 16
SuperBus 2000 Phone Interface/Voice Module .................................................................................... 16
SuperBus 2000 Energy Saver Module (60-620-01) ............................................................................. 17
i
SuperBus 2000 8Z Input Module (60-774)........................................................................................... 18
SuperBus 2000 4-Relay Output Module (60-770)................................................................................ 18
SuperBus 2000 Cellular Backup Module ................................................................................................. 18
SuperBus 2000 Automation Module (60-783-02).................................................................................... 18
SuperBus 2000 Wireless Gateway Module (60-861) ............................................................................... 19
Setting Device Address on SuperBus 2000 Devices................................................................................ 19
Installing an RJ-31X Phone Jack (13-081)............................................................................................... 19
Connecting the AC Power Transformer ................................................................................................... 20
Powering Up the Panel ............................................................................................................................. 21
Programming the Panel 21
Entering Program Mode............................................................................................................................ 21
Touchpad Button Programming Functions............................................................................................... 22
Moving Through Program Mode Tiers and Menus.................................................................................. 22
Programming Tier 1 Menu Items.............................................................................................................. 23
Programming Tier 2 Menu Items.............................................................................................................. 24
Using Shortcut Numbers....................................................................................................................... 24
Security Menu....................................................................................................................................... 24
Phones Menu......................................................................................................................................... 27
Phone Options Menu ............................................................................................................................ 32
Timers Menu......................................................................................................................................... 36
Light Control Menu.............................................................................................................................. 38
Touchpad Options Menu....................................................................................................................... 39
Reporting Menu.................................................................................................................................... 40
Siren Options Menu.............................................................................................................................. 45
Sensors Menu........................................................................................................................................ 46
Audio Verification Menu ...................................................................................................................... 49
Accessory Modules Menu .................................................................................................................... 50
Onboard Options Menu ........................................................................................................................ 53
Exiting Programming Mode ..................................................................................................................... 55
Entering User Programming Mode........................................................................................................... 55
Time and Date Menu ............................................................................................................................ 55
User Codes Menu.................................................................................................................................. 56
Options Menu ....................................................................................................................................... 58
Set Up Schedules Menu........................................................................................................................ 59
Attach Schedules to Events Menu........................................................................................................ 60
Attach Lights to Sensors Menu............................................................................................................. 62
System Version Menu........................................................................................................................... 63
Downloader Programming........................................................................................................................ 63
ToolBox Downloader Programming..................................................................................................... 63
Testing the System 63
Basic System Commands.......................................................................................................................... 63
Testing Zones/Sensors.............................................................................................................................. 64
If a Wireless Sensor Does Not Test ...................................................................................................... 64
Testing Phone Communication................................................................................................................. 65
Testing Central Station/Pager Communication......................................................................................... 65
Testing Outputs and Sirens ....................................................................................................................... 66
Testing Light Control................................................................................................................................ 66
Testing the Energy Saver Module (ESM)................................................................................................. 66
ii
Changing Fixed Display LCD Touchpad Chime and Trouble Beep Tones ............................................. 67
)
Adjusting Touchpad Display Contrast ..................................................................................................... 67
Testing Audio Verification Module (AVM) Communication .................................................................. 67
Testing Cellular Backup Communication................................................................................................ 68
Troubleshooting 70
Appendix A: System Planning Worksheets 76
Appendix B: Reference Tables 83
Cross-Zoning............................................................................................................................................ 84
Appendix C: Settings 92
Specifications 97
System Wiring Notes 98
*(6HFXULW\
*(6HFXULW\6XSHU%XVDQG7RROER[DUHUHJLVWHUHGWUDGHPDUNVRI*(6HFXULW\ &RQFRUGLVDWUDGHPDUNRI*(6HFXULW\$OORWKHUWUDGHPDUNVDUHSURSHUWLHVRIWKHLU RZQHUV
$OOULJKWVUHVHUYHG
5HG)R[5RDG $UGHQ+LOOV01 7HFKQLFDO6XSSRUW
iii
About This Manual
This manual provides information for planning, installing, programming, and testing this security system. When necessary, this manual refers you to other documentation included with compati­ble peripherals.
Planning sheets are included for you to record hardware layout and software programming set­tings.
About the User’s Guide
The User’s Guide (466-2060) contains user worksheets that should be filled out during the instal- lation and programming of the system. With two partition systems, a User’s Manual for each par- tition is suggested.
Special Installation Requirements
This security system can be used as a fire warning system, an intrusion alarm system, an emer­gency notification system, or any combination of the three.
Some installations may require configurations dictated by city/state codes, insurance, or Under­writer’s Laboratories (UL). This section describes the various component and configuration list­ings.
UL Listed Installations
This section describes the requirements for UL Listed installations.
Basic System
Control Panel (60-960-95)
Backup Battery 12V 7 AH (60-680)
•SuperBus
LCD Touchpad (60-803-04), or 2x20 VFD Touchpad (60-804-04)
Class II 24 VAC, 50 VA Line Carrier Power Transformer (60-779)
Interior Speaker Siren (60-252), Exterior Speaker Siren (13-060), Slim Line Hardwire Inte-
rior Siren (60-483-01) or Hardwire Exterior Siren (13-046) per partition
®
2000 Fixed Display Touchpad (60-820), 2x16 LCD Touchpad (60-746-01), 2x20
Household Burglary Alarm System Unit (UL 1023)
Basic system, plus:
Hardwire Magnetic Contact (1035-N or 1075-N) or Wireless Learn Mode Door/Window
Sensor (60-362)
Immediate Beeps set to on
UL 98 Options set to on
Receiver Failure set to on (if wireless devices are used)
Siren Verify set to on
Exit Delay set to 60 seconds
Quick Exit set to off
Siren Timeout set to 4 minutes or more
Entry Delay set to 45 seconds or less
RF TX Timeout set to 24 hours (if system includes a built in or SuperBus 2000 RF Receiver
and wireless smoke sensors)
Extended Delay set to off
Sleep Time set to off
Two Trip Error set to off
Alarm Verify set to off
Disable Trouble Beeps set to off
Household Fire Warning System (UL 985)
Basic system, plus:
Hardwire Smoke Detector: System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400,
or 2400TH learned into sensor group 26 or Sentrol (ESL) models 429AT, 521B or 521BXT learned into sensor group 26
Wireless Smoke Sensor 60-506-319.5, 60-848-02-95 or 60-848-02-95 learned into sensor
group 26
1
Concord Ultra
Note
UL requirements take prior­ity over SIA requirements.
Immediate Beeps set to on
UL 98 Options set to on
Receiver Failure set to on (if wireless devices are used)
Siren Verify set to on
RF TX Timeout set to 4 hours (if system includes a built in or SuperBus 2000 RF Receiver and wireless smoke sensors)
Sleep Time set to off
Siren Timeout set to 4 minutes or more
Two Trip Error set to off
Disable Trouble Beeps set to off
UL 1023 & 985 24-Hour Backup
For 24-hour backup, the total current draw for all connected devices is limited to 190 mA (during normal standby conditions) using a 7.0 AH battery.
SIA System Requirements
SIA system requirements are the same as those described for a UL Listed Basic System on page 1, plus:
If multiple annunciation is required, use Hardwire Siren part no.13-046.
SIA Setting Requirements
The following table describes programming requirements to meet ANSI-SIA CP-01.
Shortcut # Function Programming
Page
Reference
0004 SIA False Alarm
partition 1: 0013 partition 2: 0023
partition 1: 0014 partition 2: 0024
partition 1: 0017 partition 2: 0027
02005 Dialer Abort 33 63 On On
02006 Dialer Abort Delay 33 63 30 Sec. 15-45 sec.
02007 Cancel Message 33 63 On On
02009 Call Wait Cancel 34 63 Disabled On if reporting to central station and
partition 1: 0310 partition 2: 0320
partition 1: 0311 partition 2: 0321
06014 Swinger Limit 43 63 1 1
1100 Smoke Verify 54 63 Off On if smoke alarms are
N/A Cross Zoning 83 63 Disabled Enabled for zones with a high
Reduction
Exit Extension 26 63 On On
Auto Stay Arming 26 63 On On
Duress Code 27 63 Disabled Disabled
Entry Delay 37 63 30 sec. 30-240 sec.
Exit Delay 37 63 60 sec. 45-184 sec.
25 63 On On
Testing
Page
Reference
Default Setting
Required Setting
customer has call waiting service
programmed into system
probability of false alarms
The following table describes non-programmable (hard coded) system operation as required to meet ANSI-SIA CP-01 and is provided only for your reference.
Function Operation
Disarm During Entry Delay Enter Code Only (or 1 + CODE)
Concord Ultra 2
Note
For UL 1635 installations, Entry Delay plus Dialer Abort Delay must not exceed 60 seconds.
Function Operation
Cancel Alarm Enter Code Only (or 1 + CODE)
Abort Annunciation Enabled
Cancel Report Annunciation Enabled
UL 1635 Digital Alarm Communicator System
Same as UL 1023 & 985 plus:
AC Failure set to on
Comm Failure set to on
RF Tx Timeout set to 4 hours
Low CPU Battery set to on
Phone Number must be programmed
Next Phone Test set to 1
Phone Test Freq. set to 1
High Level Rpts set to on
Low Level Rpts set to on
Central Station Reporting
The panel has been tested with the following central station receivers using SIA and Contact ID reporting formats:
CS-5000 Central Station Receiver
Sur-Gard Central Station Receiver with models SG-DRL2A and SG-CPM2
UL Canada Listed Installations
This section describes the requirements for CUL (UL Canada) Listed installations.
Note
For 24-hour backup, exter­nal power drain is limited to 90 mA (during normal standby condition) using a
4.0 AH battery, or 190 mA continuous using a 7.0 AH battery.
Planning the Installation
Canadian Standards CSA Certified Accessories
Residential Burglary Alarm System Unit (ULC-S309)
Basic system as described for “UL 1023 Listed Installations” plus:
Hardwire Magnetic Contact (1035-N or 1075-N) or Wireless Learn Mode Door/Window Sensor (60-362)
Siren Timeout set to 5 minutes or more
Residential Fire Warning System Control Unit (ULC-S545-M89)
Basic system as described for “UL 985 Listed Installations” plus:
Hardwire Smoke Detector: System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400, 2400TH learned into Sensor Group 26, or Sentrol (ESL) models 429AT, 521B, or 521BXT learned into sensor group 26
Wireless Smoke Sensor 60-506-319.5 or 60-848-02-95 learned into sensor group 26
Immediate Beeps set to on
•RF TX Timeout set to 4 hours (if system includes wireless smoke sensors)
California State Fire Marshall Listed Installations
Same as Household Fire Warning System (UL 985), plus:
SMOKE VERIFY must be set to off
This section describes system capabilities to help you get familiar with the system. “Appendix A” provides planning sheets with tables that let you record the hardware and programming con­figuration of the system. Fill in all necessary information ahead of time to help prepare for sys­tem installation.
When planning the installation, keep in mind that the panel has the following capabilities (depen­dent upon devices used):
Up to 16 SuperBus 2000 Devices (maximum of 4 RF receivers)
3
Concord Ultra
Up to 96 wireless or hardwired zones
Standard Panel
The following describe the basic panel (out-of-box) hardware capabilities.
Power: Input for an AC step-down, plug-in style transformer.
Auxiliary Power Output: Output that supplies 8.5 to 13.5 VDC with up 1.35 amps (with panel powered by 50 VA transformer) for bus devices and hardwired detectors, such as smoke and motion detectors.
Bus A and B: Input and output that provides communication between bus devices and the panel.
Siren Driver: Output that can drive an 8-ohm load and provides intrusion and fire alarm sounds for partition 1.
2 Onboard Outputs: Open-collector outputs that can be set up to activate other signalling devices, based on system events.
Microphone Input: Input used for 2-way audio when used in conjunction with the Interro­gator 200 Audio Verification Module.
8 Supervised Hardwire Zones: Inputs for various hardwired detectors. Zone 8 can be set up in programming to accept 2-wire smoke detectors.
Built-In SuperBus 2000 Transceiver allows use of up to 96 319.5 MHz. crystal Learn Mode wireless sensors and touchpads. Also allows supervision of supervised wireless sirens.
Built-In Phone Supervision Card allows the panel to check for the correct phone line volt­age (partition 1 only), upon dialing the central station/pager number. The panel can also be programmed to check the phone line voltage automatically.
Built-In SuperBus 2000 Phone/Interface Voice Module allows system access and control using touch-tone telephones, on- or off-site. The module includes an output for a speaker that sounds system status and alarm voice messages.
Built-In Power Line Carrier Card allows the system to use supervised wireless sirens and
Phone Line Connection: Allows panel to communicate with central monitoring station and/
X10
Powerhouse Lamp Modules for light control and light activation during alarms.
or pagers.
SuperBus 2000 Touchpads
The following describes the different touchpads that can be used for system programming and operation.
SuperBus 2000 Fixed Display Touchpad: Provides operation control and user-program- ming access (not installer/dealer programming). Displays system messages and indicates system status.
SuperBus 2000 2x16 LCD Touchpad: Provides complete system programming and opera- tion control. Displays system messages that prompt users for information when needed and indicates system status.
SuperBus 2000 2x20 LCD Touchpad: Provides complete system programming and opera- tion control. Large display shows system messages that prompt users for information when needed and indicates system status.
SuperBus 2000 2x20 VFD Touchpad: Provides complete system programming and opera- tion control. Large fluorescent display shows system messages that prompt users for infor­mation when needed and indicates system status.
Supervised Wireless Siren
Supervised Wireless Sirens plug into any standard electrical outlet and produce status and alarm sounds. The panel sends signals to the siren through the Power Line Carrier Card and Line Car­rier Power Transformer, through the AC electrical wiring.
The siren has a built-in transmitter that is used for supervising with the panel. With the siren transmitter learned into panel memory (panels with receivers), the siren can notify the panel if it is unplugged, stops receiving panel signals, or has a low backup battery.
SnapCards
The following SnapCards expand the system as described:
8Z Input SnapCard: Provides eight additional hardwire zone inputs, of which two are ded- icated for using two wire smoke detectors.
Concord Ultra 4
4 Output SnapCard: Provides four form C relay outputs that can be set up to activate other signalling devices, based on system events, schedules, or direct control.
4Z Input/2 Output Combo SnapCard: Provides three hardwire zone inputs, one two wire smoke detector loop, and two outputs that can be set up to activate other signalling devices, based on system events, schedules, or direct control.
SuperBus 2000 8Z Input Module (HIM)
Provides eight additional hardwire zone inputs.
SuperBus 2000 4-Relay Output Module (HOM)
Provides four form C relay outputs that can be set up to activate other signalling devices, based on system events.
Interrogator 200 Audio Verification Module
Adding this module allows central station operators to listen-in and talk to occupants on the pre­mises to verify the emergency when an alarm report is received.
SuperBus 2000 Cellular Backup Module
Provides central station communication (cellular transmission) a backup to regular phone line(s).
SuperBus 2000 Energy Saver Module (ESM)
Provides a money-saving and convenient way to monitor and control temperatures. The ESM uses low- and high-temperature limits to save energy by overriding the existing HVAC thermo­stat. When the ESM is on, temperature limits determine when the heat or air-conditioning turns on. When the ESM is off, the HVAC thermostat controls heat and air-conditioning.
Installing the System
SuperBus 2000 Automation Module
Provides a connection to a compatible home automation device.
SuperBus 2000 Wireless Gateway Module
Allows users to control and monitor the status of their system from the alarm.com internet web­site. A wireless data transceiver on the module provides the link to a wireless 2-way paging net­work for website access.
This section describes how to install the system control panel. Before starting the installation, plan your system layout and programming using the worksheets provided in Appendix A.
Installing the system consists of the following:
Determining the Panel Location
Determining Total System Power and Wire Length Guidelines
Mounting the Panel
Identifying Panel Main Components
Installing the Optional Power Line Carrier Card
Installing Optional SnapCards
Connecting Detection Devices to Panel Zone Inputs
Connecting Speakers
Connecting Piezo Sirens
Connecting an Interrogator 200 Audio Verification Module
Connecting Alphanumeric and Fixed Display Touchpads
Installing SuperBus 2000 Modules
Installing an RJ-31X Phone Jack
Connecting the Phone Line to the Panel with a DB-8 Cord
Connecting the AC Power Transformer
Powering Up the Panel
5
Concord Ultra
Note
(A) Class 2, Class 3, and power-limited fire alarm cir­cuits must be installed using FPL, FPLR, FPLP, or substi­tute cable permitted by the National Electrical Code ANSI/NFPA 70. Wire that extends beyond the cable jacket must be separated from all other conductors by a minimum of 1/4-inch or by a nonconductive barrier.
OR
(B) Class 2, Class 3, and power-limited fire alarm cir­cuit conductors must be installed as Class 1 or higher circuits.
Determine the Panel Location
Before permanently mounting the panel, determine panel location using the following guidelines:
Centrally locate the panel with relation to detection devices whenever possible, to help reduce wire run lengths and labor.
Locate the panel where the temperature will not exceed 120°F (49°C) or fall below 32°F (0°C).
Avoid running wires parallel with electrical wiring or fixtures such as fluorescent lighting, to prevent wire runs from picking up electrical noise.
Mount the panel at a comfortable working height (about 45 to 55 inches from the floor to the bottom of the panel, as shown in Figure 1).
A N T E N N A
A R E A
1 9 . 2 5 "
1 2 "
P A N E L
N O T E A L L O W A T L E A S T 2 4 " I N F R
4 5 - 5 5 "
O N T O F P A N E L T O A L L O W F O R O P E N I N G C A B I N E T D O O R A N D A C C E S S T O P A N E L C O M P O N E N T S .
9 "
P H O N E J A C K A N D
O P T I O N A L M O D U L E
M O U N T I N G A R E A
2 7 "
1 8 "
F L O O R
Figure 1. Determining Panel Location
Leave space to the left and right of the panel for wiring, phone jack, and mounting optional modules.
Allow at least 9 inches above the panel cabinet for antennas.
Allow at least 24 inches in front of the panel to open the panel door.
Total System Power and Wire Length Guidelines
Power
The panel can supply up to 1.35 amps (1,350 mA) when powered by the 24 VAC, 50 VA trans­former for system devices.
Wire Length
The total system wire length allowed can vary depending on devices powered by the panel, the wire length between devices and the panel, and the combined wire length of all devices.
Table 1 describes the maximum wire length allowed between compatible devices and the panel, including the maximum current draw of each device.
Table 1: Maximum Device Wire Length and Current Draw
Device
SuperBus 2000 2x16 LCD Alphanumeric Touchpad
SuperBus 2000 2x20 LCD Alphanumeric Touchpad
SuperBus 2000 2x20 VFD Alphanumeric Touchpad
SuperBus 2000 Fixed Display Touchpad
Max. Wire Length
to Panel
22 ga.—300 ft. 18 ga.—750 ft.
22 ga.—250 ft. 18 ga.—600 ft.
22 ga.—250 ft. 18 ga.—600 ft.
22 ga.—300 ft. 18 ga.—700 ft.
4 Input/2 Output SnapCard N/A 185 mA*
Max. mA
Draw
90 mA
120 mA
120 mA
65 mA
Concord Ultra 6
Table 1: Maximum Device Wire Length and Current Draw (Continued)
Device
8Z Hardwire Zone Expander SnapCard N/A 230 mA*
4 Output SnapCard N/A 130 mA*
SuperBus 2000 8Z Input Module
SuperBus 2000 4-Relay Output Module
SuperBus 2000 Energy Saver Module
SuperBus 2000 Cellular Backup Module
SuperBus 2000 Automation Module
SuperBus 2000 Wireless Gateway Module
Interrogator 200
Interrogator AVM
*Maximum current draw for the SnapCards does not include the load which may be applied to their auxiliary DC supply.
Max. Wire Length
to Panel
22 ga.—1,800 ft. 18 ga.—4,000 ft.
22 ga.—350 ft. 18 ga.—900 ft.
22 ga.—1,600 ft. 18 ga.—4,000 ft.
Standard Power: 22 ga.—15 ft. 18 ga.—40 ft.
High Power 22 ga.—10 ft. 18 ga.—30 ft.
22 ga.—1,500 ft. 18 ga.—4,000 ft.
22 ga.—40 ft. 18 ga.—90 ft.
22 ga.—3,200 ft. 18 ga.—4,500 ft.
22 ga.—110 ft. 18 ga.—260 ft.
Max. mA
Draw
35 mA
180 mA
20 mA
1600 mA
1900 mA
35 mA
1600 mA
10 mA
300 mA
Table 2 describes the total system wire lengths allowed when installing systems using unshielded or shielded cable.
Table 2: Total System Wire Length Allowed
Wi re Typ e To tal Sys tem W ire
18-gauge, unshielded 18-gauge, shielded
22-gauge, unshielded 22-gauge, shielded
4,500 ft. 3,000 ft.
3,500 ft. 2,200 ft.
Table 3 describes the minimum current draw of each device when the panel is operating only from the backup battery. For 24-hour backup, the total current draw of all SnapCards connected to the panel and devices connected to +12V BUS (panel terminal 4) is limited to 190 mA (during normal standby condition) using a 7.0 AH battery.
Table 3: Minimum Device Current Draw
Device Min. mA Draw
SuperBus 2000 2x16 LCD Alphanumeric Touchpad 15 mA
SuperBus 2000 2x20 LCD Alphanumeric Touchpad 15 mA
SuperBus 2000 2x20 VFD Alphanumeric Touchpad 15 mA
SuperBus 2000 Fixed Display Touchpad 11 mA
4 Input/2 Output SnapCard 20 mA
8Z Hardwire Zone Expander SnapCard 38 mA
4 Output SnapCard 1 mA
SuperBus 2000 8Z Input Module 18 mA
SuperBus 2000 4-Relay Output Module 12 mA
SuperBus 2000 Energy Saver Module 20 mA
SuperBus 2000 Cellular Backup Module 90 mA
7
Concord Ultra
Table 3: Minimum Device Current Draw
Device Min. mA Draw
SuperBus 2000 Automation Module 30 mA
SuperBus 2000 Transceiver Module 50 mA
SuperBus 2000 Wireless Gateway Module 55 mA
Interrogator 200 10 mA
Interrogator AVM 45 mA
After determining panel location, run all necessary wires to that location using the guidelines in Table 4.
Table 4: Wire Requirements
Device Wire Requirements
AC Power Transformer 2-conductor, 18-gauge, 25 feet max
Earth Ground Single conductor, 16-gauge solid, 25 feet max
Telephone (RJ-31X) 4-conductor
Detection Devices
Speakers
SuperBus 2000 Devices 4-conductor, 22- or 18-gauge
Interrogator 200 AVM Power and Microphone 4-conductor, 22-gauge, shielded
2-Wire Smoke Detectors
2- or 4-conductor, 18- to 22-gauge, 300-ohms max loop resistance including device
2-conductor, 22-gauge, 175 feet max 2-conductor, 18-gauge, 440 feet max
2-conductor, 22-gauge, 330 feet max 2-conductor, 18-gauge, 830 feet max (based on 10-ohms max loop resistance plus a 2k-ohm, end-of-line resistor)
Note
Insert the top left screw as far as possible into the wall, leaving enough room to hang the panel on it. After
the panel is hung, you will be unable to tighten this screw.
Mounting the Panel
Use the following procedure to mount the panel to the wall or wall studs.
Make sure you are free of static electricity whenever you work on the panel with the cover open. To discharge any static, first touch the metal panel chassis, then stay in contact with the chassis when touching the circuit board. Using an approved grounding strap is recom-
!
Caution
¾To mount the panel:
1. Open the panel door and remove the necessary wiring knockouts (see Figure 2). Be careful
2. Feed all wires through wiring knockouts and place the panel in position against the wall.
3. Level the panel and mark the top right and bottom mounting holes (see Figure 2). You will
4. Make a level mark 10 inches to the left of the top right mounting mark. This will be the posi-
5. Install anchors where studs are not present.
6. Partially insert screws into the two top mounting hole locations, then hang the panel on the
7. Recheck for level, insert the two lower screws, and tighten the top right and lower mounting
mended.
not to damage the circuit board.
be unable to mark the top left mounting hole.
tion of the top left mounting screw.
two screws.
screws.
Concord Ultra 8
ID : X X XX X XX X
SuperBus 2000
Transceiver
Mounting
Hole
Panel Circuit Board
(under Transceiver)
Identify Panel Components
Knockout
Phone Interface/
Voice Module
Knockout
Mounting
Holes
Figure 2. Mounting the Panel
Before installing devices and making wiring connections, familiarize yourself with the main panel components. Figure 3 shows the three main panel components: the circuit board, trans­ceiver and phone interface/voice module.
Panel Circuit Board
Backup Battery Leads
Power Line Carrier Card
Programming Touchpad
Header
Snapcard
Header
Phone
Supervision
Card
Power LED
Transceiver
I D : X X X X X X X X
Antenna Terminal
Status LED
Blocks
Terminal Strip
Terminal Strip
Phone Interface/Voice Module
Terminal Strip
Status LED
DIP Switches
Figure 3. Panel Components
Installing Antennas
Install the antennas (included with panel) through the holes in the panel cabinet and into the inside terminal of each antenna terminal block on the SuperBus 2000 Transceiver (see Figure 4).
9
Concord Ultra
Transceiver
Connect
To I nside
Terminals
ID : X X X X X XX X
Figure 4. Installing the Antennas
Note
For best results, it is recom­mended that you crimp a spade lug on the wire end at the panel and secure the lug under the circuit board screw as shown in Figure 5.
Note
Figure 6 shows the control panel without the transceiver and its mounting brackets.
Connecting the Panel to Earth Ground
For maximum protection from lightning strikes and transients, connect the lower-left circuit board screw to earth ground as shown in Figure 5. Use 16-gauge, solid copper wire from an earth grounded cold water pipe clamp to the panel.
ID : X XX X XX XX
Transceiver
To Wa te r P ipe
Pipe
Ground Clamp
Figure 5. Connecting the Panel to Earth Ground
Panel Circuit Board
Installing Optional SnapCards
The SnapCard Header on the right side of the panel allows for the installation of one SnapCard. Install the desired SnapCard onto the panel SnapCard Header and secure it in place with two screws, included with the card (see Figure 6).
Connect all necessary input/output wiring using the Installation Instructions included with the SnapCard.
Connector
SnapCard
SnapCard
Header
Screw Locations
Figure 6. Installing a SnapCard
Concord Ultra 10
Note
The panel comes with fac­tory programmed onboard hardwire zones. Install 2k-ohm, end of line (EOL) resistors on all unused fac­tory programmed onboard hardwire zones. If you don’t want to install EOL resistors, delete any unused zones from memory. See Table 8 for onboard hardwire zone factory programming.
Connecting Detection Devices to Panel Zone Inputs
Zone inputs 1 through 8 are supervised using included 2k-ohm, end-of-line resistors at the last device on each circuit. All eight zones accept either normally open (N/O) or normally closed (N/ C) detection devices.
Connecting Intrusion Detection Devices
The graphics in Figure 7 show the typical wiring for N/C and N/O door/window intrusion detec­tion and for a Detection Systems model DS922 (part no. 13-082) motion detector. The minimum available panel voltage for hardwired PIR motion detectors is 8.5 VDC (9.5 VDC for UL listed installations).
Note
When using 2-wire smoke detectors on zone 8, the Two-Wire Smoke setting (in program mode) must be turned on before entering the “Programming the Panel” for complete details.
Panel Terminals
Zone 2
GND
LEARN SENSORS menu. See ONBOARD OPTIONSINPUTS in the section
Zone 3
+12
BUS
4
Panel
Ter mi nal s
GND
Zone
2 0 2 1
7
Normally
Closed
(N/C) Contacts In Series
2k Ohm EOL Resistor 49-454
Normally Open
(N/O) Contacts in
Parallel
2k Ohm EOL Resistor 49-454
2k Ohm EOL Resistor 49-454
Figure 7. Wiring Intrusion Detection
Motion
Detector
L P
L N
+
-
(Locate at Sensor)
Connecting 2-Wire Smoke Detectors
Zone input 8 can be set up (in program mode) to accept the following 12 VDC, 2-wire smoke detectors:
System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400, 2400TH
ESL models 429AT, 521B, 521BXT—(models 521B and 521BXT require the following dip switch settings: 1-on, 2-off)
Use only the 2-wire smoke detector models described above. Alarm signals from other
!
Caution
When set up for 2-wire smoke detectors, zone 8 can handle up to 10 smoke detectors with 120 uA maximum idle current per detector. Maximum total loop current allowed in an alarm con­dition is 100 mA. Connect one or more, 2-wire smoke detectors to the panel as shown in Figure 8.
detectors may not be processed correctly if the panel has lost AC power and is operat­ing only from the backup battery.
11
Concord Ultra
Note
2 2
2 3
Z O N E8+ 1 2 V
2 W S M K
+
-
+
-
The Two-Wire Smoke set­ting (in program mode) must be off when using 4-wire smoke detectors. See
ONBOARD OPTIONSINPUTS
in the section “Programming the Panel” for complete details.
Note
Zone 8 must be learned into sensor group 26 (fire) for connected smoke detectors to reset after canceling a fire alarm.
2-Wire
Zone
Panel
Ter mi nal s
8
22
2k Ohm EOL
Resistor 49-454
(Locate at Last Detector)
+12V
2W SMK
23
Panel
Terminals
4-Wire
(Locate at Last Detector)
Model 449AT
2k Ohm EOL
Resistor 49-454
Model 449AT
Figure 8. Wiring Smoke Detectors
Connecting 4-Wire Smoke Detectors
Zone input 8 can be used with 4-wire smoke detectors that latch and remain in the alarm state until power is removed, then restored to the detector. The panel provides this power interruption from terminal 23 (2-wire smoke power +), provided that zone 8 is learned into sensor group 26 (fire).
Table 5 describes the minimum available panel power. Use only 4-wire smoke detectors that operate at these power limits. Connect up to five Sentrol (ESL) model 449AT (part no. 13-360) smoke detectors to panel power and zone 8 input as shown in Figure 8.
Table 5: Panel Minimum Available Power
Min. Voltage/Max. Current Available
8.3 VDC, up to 30 mA total (combined alarm) current
8.1 VDC, up to 40 mA total (combined alarm) current
7.7 VDC, up to 60 mA total (combined alarm) current
7.4 VDC, up to 80 mA total (combined alarm) current
Connecting Speakers
Note
Install all sirens/speakers indoors, in a concealed loca­tion.
Concord Ultra 12
The panel provides one siren driver output for intrusion (steady), fire (temporal 3), and auxiliary (on-off-on-off) alarm sounds. This output trips only for partition 1 alarms.
The output can drive a single 8-ohm speaker or multiple speaker circuit of 8-ohms or higher (as shown in the following speaker wiring diagrams). Compatible speakers are described under “Connecting Piezo Sirens”.
To avoid disabling the panel speaker output, do not make speaker connections with the
!
Caution
panel powered up.
15-Watt Speaker (13-060)
For exterior siren applications. Connect the speaker to the panel as shown in Figure 9.
Hardwire Interior Speaker (60-528)
For interior siren applications. Connect the speaker to the panel as shown in Figure 9.
Connect only the large speaker to the panel terminals 7 and 8 as shown. The smaller
!
Caution
Connect two units to the panel terminals with speakers in series (16-ohms), as shown in Figure 10.
speaker cannot handle to output of terminals 7 and 8. To avoid damaging the speaker, the smaller speaker should not be connected to terminals 7 and 8.
Exterior
Speaker
8
7
2 8-Ohm Speakers in Series (16 Ohms)
Splice
Speaker
7
8
Figure 9. Wiring Speakers
Interior
Panel
Ter minals
Not Used
Speaker
Not Used
87
13
Panel
Ter mi nal s
Figure 10. Wiring Two Hardwire Interior Speakers w/Dual Speaker Units to Panel Terminals
Speaker
Not Used
Connecting Piezo Sirens
Output 1
Onboard output 1 (OUT 1—terminal 9) is an open-collector (switched path-to-ground), program­mable output that can handle a maximum of 200 mA current sink. The default setting (01614) activates the output 15 seconds after a police or fire alarm condition occurs. This allows you to connect a piezo siren without changing the output configuration number in programming. This output is typically used for exterior siren application.
Output 2
Onboard output 2 (OUT 2—terminal 10) is an open-collector (switched path-to-ground), pro­grammable output that can handle a maximum of 200 mA current sink. The default setting
Concord Ultra
Note
Piezo siren connections to terminal 10 require a 2k resistor that can be located at the panel, since it does not supervise the circuit. If using an external power supply instead of panel ter­minal 4, the supply voltage must be limited to 9.5 VDC maximum and the negative side of the power supply must be connected to panel ground (terminal 3).
(01710) activates the output for status and alarm tones, allowing for a piezo siren connection without changing the output configuration number. It is typically used for interior siren applica­tion.
For more information on output configuration numbers, see “Onboard Options Menu”.
Exterior Sirens
Hardwire Exterior Siren (13-046)
Note
This siren is not UL approved for use as an outdoor sounding device.
Connect the siren to panel as shown in Figure 11.
Interior Sirens
Interior Piezo Siren (60-278)
Connect the piezo siren to the panel terminals with a 2k-ohm resistor, as shown in Figure 11.
Note
The volume switch settings inside the siren do not affect the siren output.
Exterior
Panel
Ter mi na ls
+12V Out 1
49
Red
Black
Figure 11. Wiring Sirens
Slim Line Hardwire Interior Siren (60-483-01)
Connect the siren to the panel as shown in Figure 12.
Not
Used
Panel
Ter mi na ls
+12V
4
Interior
+12V Out 2
10
Panel Terminals
4
2k Ohm
Resistor
49-454
Red
OUT2
10
Black
Figure 12. Wiring the Slim Line Hardwire Interior Siren
Installing Supervised Wireless Sirens (60-736-95)
Note
Power Line Carrier Card must be installed for Super­vised Wireless Sirens to work.
Concord Ultra 14
Supervised Wireless Sirens (SWS) plug directly into electrical outlets and are not wired to the panel. The panel (when powered by a line carrier power transformer) sends alarm and status mes­sages to the siren, along the building AC wiring.
For supervised operation, the siren has a built-in transmitter that, when learned into panel mem­ory, transmits to the panel receiver if the siren has a low battery or other trouble condition.
Before plugging in Supervised Wireless Sirens, the panel must be powered up and partition House Codes and the SWS Supervision Code set (in program mode) to the desired settings.
The following procedures describe the basic steps for installing Supervised Wireless Sirens. For complete installation details, refer to the Supervised Wireless Siren Installation Instructions, included with each siren.
Note
Regardless of supervised or unsupervised siren installa­tion, you must follow the order of installation as described to avoid learning the wrong (or undesired) House Code and SWS Supervision Code into siren memory.
Note
When installing Supervised Wireless Sirens for super­vised operation, be sure to program sensor text that clearly identifies each siren. For example, HALLWAY SIREN or BASEMENT SIREN. This can help both you and your customer locate a specific siren if a problem occurs.
¾For unsupervised wireless siren installations:
1. Power up the panel (see “Powering Up the Panel”).
2. Enter program mode and set the partition House Code to the desired setting (see the
CONTROL
menu in the section “Programming the Panel”).
LIGHT
3. Exit program mode.
4. Install the siren backup battery.
5. Plug the siren into an electrical outlet.
6. Press the STATUS button on any working touchpad. The siren should beep once and the siren LED should flash 5 times, indicating it has learned the partition House Code.
7. If the siren doesn’t beep or the LED doesn’t flash, reset the house code on the siren by press­ing and holding its button for 20 seconds. The siren will beep three times when the memory has been cleared. Repeat step 6.
¾
For supervised wireless siren installations:
1. Power up the panel (see “Powering Up the Panel”).
2. Install the siren backup battery.
3. Clear the siren memory by pressing and holding the siren button for 20 seconds. The siren will beep three times when the memory has been cleared.
4. Enter program mode and set the partition House Code to the desired setting (see the
CONTROL
menu in the section “Programming the Panel”).
LIGHT
5. Proceed to the SIREN OPTIONS menu and set the SWS Supervision Code to the desired set­ting.
6. Proceed to the
LEARN SENSORS menu and select the desired partition, sensor group 33, and
the desired sensor number.
7. When the touchpad display shows TRIP SENSOR nn, plug the siren into an electrical outlet. The siren should beep once and the siren LED should flash 10 times, indicating the panel learned the siren transmitter ID and that the siren learned both the partition House Code and SWS Supervision Code.
8. Exit program mode.
Connecting an Interrogator 200 Audio Verification Module (60-677)
Connect the Interrogator 200 Audio Verification Module (AVM) to the panel terminals as shown in Figure 13. Partition 1 use only.
!
Caution
If a speaker is already connected to panel terminals 7 and 8, the Interrogator 200 speaker must be hooked up in series with that speaker to provide a 16-ohm load. Hook­ing up speakers in parallel to panel terminals 7 and 8 creates a 4-ohm load that can cause permanent damage to the panel.
Black
Yellow
Run Separate Wire Cabl es As Shown
Panel Terminals
Speaker
Figure 13. Connecting an Interrogator 200 AVM to the Panel
87
4
+ 1 2 V3G N D
Splice
Cable Shield
1 1
M I C
15
Concord Ultra
Connecting Alphanumeric and Fixed Display Touchpads
Alphanumeric and Fixed Display touchpads use the same color-coded wire scheme. Connect the touchpads to the panel power output and bus terminals as shown in Figure 14.
SuperBus 2000
Fixed Display
Touchpad or
LCD Alphanumeric
Touchpads
GND +12V
3
4
ABUSB
5
+12V/Red
Bus B/White
Bus A/Green
GND/Black
6
Figure 14. Wiring Touchpads
Installing SuperBus 2000 Modules
SuperBus 2000 modules can be installed inside the panel cabinet or away from the panel. Use the following guidelines when installing modules inside the panel cabinet:
Up to 16 bus modules can be connected to the panel. (The transceiver and Phone Interface/ Voice Module each count as one module, leaving 14 available.)
Up to 2 of the SuperBus 2000 modules listed in Table 1 can be mounted inside the cabinet.
SuperBus 2000 modules can be mounted inside the cabinet either to the right of the Trans­ceiver on the mounting brackets or to the right of the Phone Interface/Voice Module (see Figure 15).
Note
In UL Listed installations, the Phone Interface/Voice Mod­ule is for supplementary use only.
Note
For RJ-31X connections, see “Installing an RJ-31X Phone Jack (13-081).
ID : X X X X X XX X
Locations for mounting SuperBus Modules
Figure 15. Mounting SuperBus 2000 Modules Inside the Cabinet
SuperBus 2000 Phone Interface/Voice Module
The module requires panel power and bus connections (already wired), phone line connection through panel terminals and DB-8 cord (from an RJ-31X jack), and speaker connection through panel terminals.
Wiring—Phone Line
For partition 1, connect the phone line to the module through the panel terminals using the DB-8 cord (from an RJ-31X jack) as shown in Figure 16. Much of the connection between the Panel Circuit Board and the Phone Interface/Voice Module is pre-wired. For partition 2 phone connec­tion, see the SuperBus 2000 Phone Interface/Voice Module Installation Instructions.
Concord Ultra 16
Phone Interface/Voice Module Terminal Strip
2A3B4
1
+ 1 2 V
G N D5G N D6S P K 17S P K 28A U D 19A U D 2
Panel Terminals
Grn
2 4
Green
Brn
2 5 2 6 2 7
1 0
1 1
1 2
1 4
T I P 1
Red
1 3
T I P 2
R I N G
DB-8 Cord
R I N G
2
1
G N D
Red
Gry
Gray
Brown
Plug
Brn Gry
Grn
6 0 7 3 4 1 0 9 d . d s f
Red
RJ-31X Jack
Figure 16. Connecting a Phone Line
Wiring—Speaker
To connect a speaker to the panel, wire the speaker to the Phone Interface/Voice Module termi­nals 6 and 7, as shown in Figure 17.
Phone Interface/Voice Module Terminal Strip
1 3
1 4
R I N G
1 1
1 2
R I N G
T I P 1
T I P 2
1
2
8
1 0
G N D
7
A U D 19A U D 2
S P K 2
4
2
6
G N D5G N D
S P K 1
1
3
A
+ 1 2 V
B
17
Not Used
Figure 17. Wiring a Speaker
SuperBus 2000 Energy Saver Module (60-620-01)
Connect the Energy Saver Module to the panel and premises thermostat as shown in Figure 18.
HEAT
OFF
50 60 70 80 90
TO HVAC
A/C
Figure 18. Connecting the Energy Saver Module
PANEL TERMINAL
1
23456
GND
3 4 5
S
+12V
BUS
B
A
6
Concord Ultra
SuperBus 2000 8Z Input Module (60-774)
Connect the SuperBus 2000 8Z Input Module to the panel as shown in Figure 19. Connect all necessary input wiring using the Installation Instructions included with module.
SuperBus 2000 4-Relay Output Module (60-770)
Connect the SuperBus 2000 4-Relay Output Module to the panel as shown in Figure 19. Connect all necessary output wiring using the Installation Instructions included with the module.
Input
ID : X X X X X X X X
1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6
Z O N E 1
Z O N E C O M M O N
Z O N E 2
Z O N E 3
Z O N E 4
Z O N E 5
Z O N E C O M M O N
Z O N E C O M M O N
Z O N E 6
Z O N E 7
Z O N E C O M M O N
Z O N E 8
G N D
+ 1 2 V
3 4 5
B U S
B
A
6
Output
I D : X X X X X X X X
1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7
C O M 4
C O M 3
N O 4
N C 4
C O M 2
N O 3
N C 3
N O 2
N C 2
N O 1
N C 1
C O M 1
G N D
+ 1 2 V
3 4 5 6
1 8
Z O N E C O M
Z O N E 1
B U S
A
Figure 19. Wiring Input and Output Modules
SuperBus 2000 Cellular Backup Module
Connect the SuperBus 2000 Cellular Backup Module to the panel as shown in Figure 20.
B
1 2 3 4 5 6
Z O N E 1
Z C O M
B U S
BG N D
+ 1 2 V
6 0 7 3 4 g 3 0 6 d . d s f
Panel Ter minals
A
3 4 5 6
Figure 20. Connecting the Cellular Backup Module to the Panel
SuperBus 2000 Automation Module (60-783-02)
Connect the SuperBus 2000 Automation Module to the panel as shown in Figure 21.
Concord Ultra 18
Automation Module Circuit Board
1 2 3 4 5 6
Z O N E 1
Z C O M
B U S
G N D
+ 1 2 V
3 4 5
B
A
Panel
6
Terminals
DB-9 Serial Cable
Automation Device
Figure 21. Connecting the SuperBus to the Panel
SuperBus 2000 Wireless Gateway Module (60-861)
Connect the SuperBus 2000 Wireless Gateway Module to the panel as shown in Figure 22.
Note
The panel cannot be used on a digital or PBX phone line. These systems are designed for digital type devices only, operating any­where from 5 volts DC and up. The panel uses an ana­log modem and does not have a digital converter, adapter, or interface to oper­ate through such systems.
Module Wiring Terminals
Panel Terminals
G N D
6 0 8 6 1 G 0 3 A . D S F
+ 1 2 V
A B G N D
3 4 5
+ 1 2 V
A
B U S
UL-Listed
Closed (N/C)
Z 1
Z C O M
6
B
Normally
Contacts
in Series
OR
UL-Listed
Normally
Open (N/C)
Contacts
in Parallel
2.0K Ohm EOL Resistor 01-022 (Install at Last Contact)
Figure 22. Connecting the Wireless Gateway Module to the Panel
Setting Device Address on SuperBus 2000 Devices
When the panel is powered up it automatically assigns device addresses and unit numbers to SuperBus 2000 devices, enabling the panel and module to communicate.
Installing an RJ-31X Phone Jack (13-081)
Use the following guidelines when installing an RJ-31X phone jack for system control by phone and central station monitoring.
Locate the RJ-31X jack (CA-38A in Canada) no further than five feet from the panel.
The panel must be connected to a standard analog (loop-start) phone line, that provides 48 volts DC (on-hook or idle) which increases to 89 to 105 volts DC (ring voltage).
For full line seizure, install an RJ-31X phone jack on the premises phone line so the panel is ahead of all phones and other devices on the line. This allows the panel to take control of the phone line when an alarm occurs, even if the phone is in use or off-hook.
19
Concord Ultra
Note
Connecting the panel to an analog line off the phone switch places the panel ahead of the phone system, preventing panel access from phones on the pre­mises. However, the panel can still be accessed from off-site phones.
If an analog line is not available, contact a telecommunications specialist and request an ana­log line off the phone switch (PBX mainframe) or a 1FB (standard business line).
¾
To connect a phone line to the panel using an RJ-31X/CA-38A jack (see Figure 23):
1. Run a 4-conductor cable from the TELCO protector block to the jack location.
2. Connect one end of the cable to the jack (see B in Figure 34).
3. At the TELCO protector block, remove the premises phone lines from the block and splice them to the black and white (or yellow) wires of the 4-conductor cable (see C in Figure 34).
4. Connect the green and red wires from the 4-conductor cable to the TIP (+) and RING (-) posts on the block (see D in Figure 34).
5. Check the phones on the premises for dial tone and the ability to dial out and make phone calls. If phones do not work correctly, check all wiring and correct where necessary. Proceed to the “Troubleshooting” section of this manual if problems persist.
Gry
Brn
RJ-31X
Jack
B
Green
Red
Red
White
(or Yellow)
Grn
Black
TELCO
Protector Block
R I N G
T I P ( + )
D
Green
Black
C
Green
( - )
Red
White
Red
(or Yellow)
A
RJ-31X Phone Line Wire Run
Lines From Phones On Premises
Figure 23. Installing an RJ-31X Phone Jack
Connecting the AC Power Transformer
The panel must be powered with the Line Carrier Power Transformer that supplies 24 VAC, 50 VA (60-779). Connect the power transformer to the panel as shown in Figure 24.
Do not plug in the power transformer at this time. The panel must be powered up using
!
Caution
the sequence of steps described in the next section, “Powering Up the Panel.”
Panel Terminals
2 4 V A C
1
2
Black
Backup Battery Connections
Red
Black
6 0 7 3 4 g 1 0 4 d . d s f
Red
Battery
Figure 24. Connecting a Power Transformer and Backup Battery to the Panel
Concord Ultra 20
Powering Up the Panel
After connecting and wiring all devices to the panel, you are ready to apply AC and backup bat­tery power to the panel. The panel comes with the backup battery leads already connected to the lugs on the panel.
¾
To power up the panel:
1. Connect the red and black battery leads not already connected to the lugs on the panel to the battery terminals (see Figure 24).
2. Plug the transformer into an outlet that is not controlled by a switch. Alphanumeric touchpads display
date and time display.
************, then SCANNING BUS DEVICES, and finally a
Note
If alphanumeric touchpads don’t display anything, immediately unplug the transformer and disconnect the backup battery. Refer to the “Troubleshooting” sec­tion.
Programming the Panel
Note
If the system is powered up after the programming touchpad is connected or if a bus command scan is exe­cuted, the programming touchpad will be “learned” into the system and must later be manually deleted.
3. To permanently mount the transformer, unplug it and remove the existing screw securing the AC outlet cover.
Use extreme caution when securing the transformer to a metal outlet cover. You could
!
Warning
receive a serious shock if a metal outlet cover drops down onto the prongs of the plug while you are securing the transformer and cover to the outlet box.
4. Hold the outlet cover in place and plug the transformer into the lower receptacle.
5. Use the screw supplied with the transformer to secure the transformer to the outlet cover.
For on-site system programming, an alphanumeric touchpad is required.
Entering Program Mode
Entering program mode is done using an installer/dealer code (default = 4321). The system can be put into program mode only when the system is disarmed.
¾To enter program mode:
1. Make sure the system is disarmed in all partitions.
2. Press 8 + 4321 + 0 + 0. The display shows
To enter programming mode using a programming touchpad:
¾
1. Connect the wires from the Programming Touchpad Cable (60-791) to the power and bus wires on an alphanumeric touchpad, matching the wire colors on each.
2. Make sure the system is powered up and disarmed.
3. Connect the plug on the cable onto the panel programming touchpad header (see Figure 25).
4. Press 8 + 4321 + 0 + 2. The touchpad sounds one short beep. Press * and verify that the dis­play shows
SERVICE TOUCHPAD ACTIVE.
5. Press 8 + 4321 + 0 + 0 and the display shows
6. After programming is completed, simply disconnect the touchpad from the panel header.
SYSTEM PROGRAMMING.
SYSTEM PROGRAMMING.
21
S ta y
pr es s bo th
BA4
pr es s bo th
C
D
A w ay
O ff
1
S ile n t
N o D e la y
F ea t ur e s
S ys te m
7
pr es s bo th
S ta tu s
L ig ht s
*
2
5
8
0 #
3
P ag e r
6
M e nu
9
B yp a s s
Programming Touchpad Cable (60-791)
6 0 7 3 4 G 3 0 8 D . D S F
Te s t S ys te m W e ek ly
Figure 25. Connecting a Programming Touchpad
Concord Ultra
Touchpad Button Programming Functions
In program mode, touchpad buttons let you navigate to all installer programming menus for con­figuring the system. Table 6 describes the touchpad button functions in program mode.
Table 6: Touchpad Button Functions
Button Programming Function
# *
A & B
Selects menu item or data entry.
Deselects menu item or data entry (if pressed before #).
Scroll through available options at the current menu tier. Also scroll through sen­sor text options during sensor text programming.
C
D
0 thru 9
Enters pauses when programming phone numbers.
Deletes certain programmed settings.
Enter numeric values wherever needed.
1 & 2 Select off (1) or on (2) wherever needed.
1 thru 6
Press and hold to enter alphabetical characters A thru F for account numbers.
7 & 9 Press and hold to enter * (7) or # (9) for phone numbers.
Moving Through Program Mode Tiers and Menus
There are two basic tiers of programming menus. Tier 1 menus are accessible immediately after entering program mode (see Figure 26).
Tier 1 Menu
System
Programming
#
To Ti er 2
Menus
Menus
B
Demo Kit
Off/On
A
From Tier 2
*
B
A
Partition 1
Copy
B
Clear
Memory
A
B
Programming
Ready
A
Exit
B
Figure 26. Tier 1 Program Menus
Arrows pointing right represent pressing B to advance forward through the menus. Pressing A moves through the menus in reverse.
The arrow below the gramming menus. Only when
SYSTEM PROGRAMMING menu represents pressing # to advance to tier 2 pro-
SYSTEM PROGRAMMING is displayed can you advance to tier 2
menus (see Figure 27).
Tier 2
Menu
Security Phones
#
Touchpad
#
Accessory
Modules
#
Options
B
A
#
*
B
Reporting
A
#
*
B
Onboard
Options
A
#
*
B
Phone
Options
A
#
*
B
Siren
Options
A
#
*
B
To Security Menu From Security Menu
A
*
B
Timer s
A
#
*
B
Sensors
A
#
*
*
*
B
A
#
B
Verification
A
#
Light
Control
Audio
6 0 7 3 4 g 3 1 0 d . d s f
B
A
*
B
A
*
Figure 27. Tier 2 Program Menus
Concord Ultra 22
Again, arrows pointing right represent pressing B to advance forward through the menus. Press­ing A moves through the menus in reverse.
Arrows below each menu represent pressing # to advance to those settings that pertain to that menu. Only when a specific menu is displayed can you advance to those settings. For example, from the
SENSORS menu pressing # gives you access to learning sensors, programming sensor
text, deleting sensors, and viewing/editing sensor programming. Settings in tier 2 menus can also be accessed by entering shortcut numbers. See the section, “Programming Tier 2 Menu Items” for complete details.
Programming Tier 1 Menu Items
This section guides you through programming tier 1 menu items as they appear in sequence. The exact order you follow will depend on whether you’re installing a new system or changing pro­gramming in an existing system.
Demo Kit Mode (System Programming)
(Default = off) This setting determines whether the panel is used for a standard installation (off) or as a demo kit (on). When the Demo Kit option is on, only sensors learned into groups 01 and 03, duress code use, and phone test ( this feature and performing a memory clear changes the following settings:
Partition 1 Master Code = 1000
Partition 2 Master Code = 2000
User Code 00 = 1001 (partition 1 code—can also be used to jump to partition 2)
User Code 01 = 1002 (partition 1 code—can also be used to bypass sensors)
User Code 02 = 2001 (partition 2 code—can also be used for remote or off-site access)
User Code 03 = 2002 (partition 2 code—can also be used to perform system tests)
User Code 04 = 1122 (partition 1 code—can also be used to jump to partition 2, for remote or off-site access, and system tests)
User Code 05 = 1122 (partition 2 code—can also be used to jump to partition 1, for remote or off-site access, bypassing sensors, and system tests)
Partition 1 House Code = 255 (P)
Partition 2 House Code = 254 (O)
Zone 1 (hardwire input 1) = Group 10, Front Door
Zone 2 (hardwire input 2) = Group 13, Bedroom Window
Zone 3 (hardwire input 3) = Group 17, Living Room Motion Sensor
Zone 4 (hardwire input 4) = Group 1, Panic
Zone 5 (wireless, keychain touchpad, ID F00201) = Group 01, (no text)
Zone 6 (wireless, DWS, ID A00206) = Group 13, Kitchen Window
COMM FAILURE = off Demo Kit = on
AVM code = 1212
Entry Delay = 8 sec
Exit Delay = 8 sec
Extended Delay = 1 minute
Siren Timeout = 2 minutes
8 + System Master Code + 2) will be reported. Turning on
23
¾
To turn Demo Kit Mode off or on:
1. With the display showing DEMO KIT MODE OFF/ON (current setting), press 1 (off) or 2 (on), then press #.
2. The display flashes the entered setting, then stops after pressing # and displays
MODE OFF/ON
Partition 1 Copy (System Programming)
(new setting).
DEMO KIT
(Default = none) After programming all settings pertaining to partition 1, you can make an exact copy to use for partition 2. This helps reduce programming time when the system is set up for two partitions. If there are certain settings that are unique to partition 2, simply advance to the appropriate menu and make the necessary changes.
¾
To Copy Partition 1:
With the display showing PARTITION 1 COPY, press # + installer CODE + #. The display
flashes, then stops after pressing # and shows
DONE.
Concord Ultra
Note
Clearing the memory will erase onboard hardwire zone factory programming.
Clear Memory (System Programming)
Clearing memory deletes all existing programming information (except the Dealer Code).
¾To Clear Panel Memory:
1. With the system in program mode, press A or B until the display shows CLEAR MEMORY.
2. Press # and the display shows
3. Enter the 4-digit installer or dealer
ENTER CODE TO CLEAR MEMORY.
code (if programmed) + #. After about five seconds, the
system restarts and the panel scans the bus to learn all bus devices.
If the system doesn’t respond as described, repeat step 3.
Programming Tier 2 Menu Items
This section guides you through programming tier 2 menu items as they appear in sequence. Figure 27 shows the menus available on tier 2.
Each menu on tier 2 represents a group of settings related to the menu name. Some tier 2 menus break down into settings that affect the whole system (global) or a specific partition.
Using Shortcut Numbers
To go directly to a setting in tier 2, you can enter the shortcut number for that setting. Shortcut numbers in this manual appear in parenthesis ( ), next to the setting name. The menu appears to
the right. For example this heading shows the Downloader Code shortcut to be 0000.
Downloader Code (0000)
Shortcut numbers can be used from any setting location within tier 2.
¾
To advance to tier 2 program menus:
With the system in program mode and the display showing SYSTEM PROGRAMMING, press #
once. The display should show
SECURITY.
Security Menu
The SECURITY menu lets you choose whether security settings affect the whole system (global) or a specific partition.
¾
To access global or partition security menu items:
1. With the display showing SECURITY, press #. The display should show GLOBAL.
2. Press # again to advance to global settings, or press A or B to display # to advance to selected partition 1 or 2 settings.
The following describes how to program the security settings that appear under
Downloader Code (0000)
The 5-digit downloader code is used in conjunction with downloader pro­gramming. The down-loader operator must have the panel account number and downloader code in order to perform any programming.
Note
The Downloader Code cannot be deleted from panel memory. To change the Downloader Code to its default setting, enter 12345 in the procedure to the right. The Downloader Code will be reset to defaults during a Memory Clear only if the Dealer Code is not set OR if the Dealer Code is used to initiate the Memory Clear.
System Programming
PARTITION n, then press
GLOBAL.
Security-Global (Default = 12345)
¾ To program a Downloader Code:
1. With the display showing DOWNLOADER
CODE nnnnn (current code), enter the desired
5-digit code, + ƒ. The display flashes the entered code.
2. Press
ƒ and the display shows the new
code.
Installer Code (0001)
The 4-digit installer code is used for entering program mode and changing system settings. If a dealer code is programmed, only those settings not associated with phone numbers can be changed.
Note
The Installer Code cannot be deleted or cleared from panel memory. To change the Installer Code to its default setting, enter 4321.
¾ To program a Downloader Code:
¾To program an Installer Code:
1. With the display showing INSTALLER CODE nnnn (current code), enter the desired 4-digit code. The display flashes the entered code.
Security-Global (Default = 4321)
2. Press # and the display shows the new code.
Concord Ultra 24
Dealer Code (0002)
Security-Global (Default = none)
The 4-digit dealer code is used to prevent unauthorized persons from changing the programmed central station phone numbers. When this feature is enabled, central station phone numbers cannot be changed (unless you enter the program mode by using the dealer code). All other system settings are still acces­sible by entering the program mode with the installer code.
Note
The Dealer Code cannot be deleted by clearing panel memory.
¾To program a Dealer Code:
1. With the display showing DEALER CODE ****, enter the desired 4-digit code. The display flashes the entered code.
2. Press # and the display shows the new code.
¾
To delete a Dealer Code:
1. With the display showing DEALER CODE nnnn (current code), press D. The display shows DEALER CODE ****.
Access Code Lock (0003)
¾
This setting determines whether or not the panel will include Access Codes when sending user information to the automation module. When this option is on, it means the Access Codes are not sent.
To turn Access Code Lock off or on:
1. With the display showing ACCESS CODE LOCK
ON/OFF
flashes the entered setting.
2. Press # and the display shows the new setting.
SIA False Alarm Reduction (0004)
Controls the following settings that are required by the SIA False Alarm Reduction Standard:
Arming level changes made from wireless touchpads and keychain touchpads are sounded (beeps) on exterior siren output (on) OR are not sounded on exte­rior siren output (off).
Note
The siren output must be configured for “Exterior Siren” (016xx) and on the two onboard outputs and SnapCard outputs only, for the arming level beeps to be annunciated.
The Arming Always Silent feature is disabled for users if this setting is on OR can be controlled by users if the setting is off. Silent Arming on Demand is not affected.
Security-Global (Default = on)
, press 1 (off) or 2 (on). The display
Security-Global (Default = on)
¾
To turn SIA False Alarm Reduction off or on:
1. With the display showing SIA FALSE
ALARM (current setting), press 1
(off) or 2 (on). The display flashes the entered setting.
2. Press
ƒ and the display shows the
new setting.
The following sections describe the security settings that appear under PARTITION 1 and 2.
Account Number (partition 1: 0010, partition 2: 0020)
The account number is used as panel (or customer) identification for the central monitoring station. The panel sends the account number every time it reports to the central station. Account numbers must be 1 to 10 characters long.
Alpha characters A–F can be assigned to the account number by pressing and holding buttons 1–6 respectively, until the character appears.
Quick Arm (partition 1: 0011, partition 2: 0021)
Quick Arm allows system arming without using an access code. When Quick Arm is on, the system arming level can be increased from Level 1­OFF to LEVEL 2-STAY, from Level 1-OFF to LEVEL 3-AWAY, or from Level 2-STAY to LEVEL 3-AWAY, without entering an access code.
A valid access code is still required to decrease the arming level or disarm the system.
25
Security-Partition 1-2 (Default = 00000)
¾
To program an Account Number:
1. With the display showing ACCOUNT NUMBER
nnnnn
(current number), enter the desired
account number. The display flashes the entered number.
2. Press # and the display shows the new number.
Security-Partition 1-2 (Default = off)
¾
To turn Quick Arm off or on:
1. With the display showing QUICK ARM OFF/ON (current setting), press 1 (off) or 2 (on). The display flashes the entered setting.
2. Press # and the display shows the new setting.
Concord Ultra
Loading...
+ 74 hidden pages