General Electric Company Telephone +41 (0)91 / 850 51 51
CH – 6595 Riazzino (Locarno)Fax+41 (0)91 / 850 51 44
SwitzerlandWebsitewww.gedigitalenergy.com
NetPro 19" UPS
Technology for the Digital World.
ver 3.0 - GB
g
GE Digital Energy
GB
USER MANUAL
NetPro 19"
Uninterruptible Power Supply
Uninterruptible Power Supply
Uninterruptible Power SupplyUninterruptible Power Supply
600 - 1500 VA
600 - 1500 VA
600 - 1500 VA600 - 1500 VA
Please read these instructions carefully before installation and start-up of the
NetPro 19” UPS. Keep this manual in a safe place for future reference.
subject to change; no liability can be accepted for any error or omission.
OPM_NPE_19X_600_1K5_2GB_V0301GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
. All rights reserved; reproduction in whole or in parts without permission is prohibited. This manual may be
g
GE Digital Energy
1 - Introduction
1.1Introduction
General Electric (GE) Digital Energy NetPro 19” UPS
The
protects your equipment from all forms of power interference, including complete power failures.
1.2Safety Rules
, a truly on-line uninterruptible power supply,
x
CAUTION: RISK OF ELECTRICAL SHOCK
outlets may be electrically live, even when the UPS is disconnected from the mains.
x
The UPS contains potentially hazardous voltages. Do not open the UPS, there are no user
serviceable parts inside.
x
All maintenance and service work,
performed by qualified service personnel.
except for replacement of the batteries
. The UPS contains batteries. The appliance
, should be
1.3Transport / Storage
x
No liability can be accepted for any transport damage when the equipment is shipped in nonoriginal packaging.
x
During transport the battery drawer must either be removed or fixed with two screws at the rear
side of the UPS (A, fig. 1).
x
Store the UPS in a dry location with the batteries in a fully charged state. Storage temperature
must be within -20 +45 qC. If the unit is stored for a period exceeding 3 months, optimal battery
lifetime is obtained if the storage temperature does not exceed 25°C.
x
If the unit is stored for an extended period of time, the batteries must be recharged periodically.
Be sure that the battery drawer is connected to the UPS. Subsequently connect the unit to a wall
outlet and recharge the batteries for 24 hours:
-if the storage temperature is within -20 and +30°C: every 3 months,
-if the storage temperature is within -20 and +45°C: every month.
Please note that with completely discharged batteries the UPS will not start at all. External
charging or replacement of the batteries will be necessary.
2 - Installation
The shipping box contains a
ROM and this manual. Inspect the UPS for damage after unpacking. If any damage is present please
immediately notify the carrier and place of purchase.
NetPro 19”
UPS, two IEC male-female power cords, a data cable, a CD
IMPORTANT
x
x
:
Before making any connection and switching on the
conditions:
your mains supply is 220 - 240 Volts and 50 Hz (if the mains frequency is 60Hz, the output
frequency of the UPS can be changed, see section 3.4), and
the total power demand of the connected equipment does not exceed the rated output power of
NetPro 19”
the
UPS (indicated on the rating label).
WARNING
Connecting the UPS output to neutral or ground will result in a malfunctioning UPS.
2.1Installation Rules
x
The UPS is intended to be used in normal domestic and office situations.
x
Protect the UPS, according to the wiring rules, with a 16A D-type fuse.
x
The UPS must be powered from a single phase grounded wall outlet. Do not use extension
cords.
x
Avoid locations that are excessively humid, near water, near heat sources or in direct sunlight.
x
The ambient temperature should not exceed 40qC. Optimal battery lifetime is obtained if the
ambient temperature does not exceed 30qC.
x
It is important that ventilation air can move freely around and through the unit. Do not block the air
vents.
x
Do not plug appliances such as electric heaters, toasters and vacuum cleaners into the UPS.
x
Be careful when connecting laser printers: be sure that the demanded power does not exceed the
capacity of the UPS.
x
The sum of the leakage currents of the UPS and the connected loads should not exceed 3.5mA.
NetPro 19”
UPS, please check the following
OPM_NPE_19X_600_1K5_2GB_V0302GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
g
2.2Installation Procedure
4
GE Digital Energy
A
B
51
6
1.Remove the transport screws (A, fig. 1) and store them in the free holes (B, fig.1). Mount the
NetPro 19”
it by using the front brackets only. The front brackets allow mounting of handles (not included).
2.Make sure that the air vents in the side panels of the module are not blocked by the mounting
rails or the side panels of the 19” rack.
7a
UPS in the 19” rack. The module must be supported by mounting rails, do not mount
1000VA model only:
3.
2
7
fig. 2
Battery extension module(s) can be installed to
increase the battery runtime. Connect the DC
connector of the battery module (7, fig. 2) to the DC
socket of the UPS (2, fig. 1/2). You will hear a click
when the cable is properly installed. Block the DC
connector: install the small locking plate (7a, fig. 2)
that came with the battery module, and fasten it with
the screw provided. Using the DC connector of the
battery module (not shown) you can install a second,
third, etc. module. See also section 5.1.
4.Switch off your computer, and unplug it from the
socket-outlet.
5.Disconnect the power cord from the computer
(rating 250Vac/10A) and connect this cord to the
mains input socket (5, fig. 1) of the UPS. See fig. 4.
2
3
fig. 1
6.Using the output cord(s) provided, connect the
computer(s) to the appliance outlet(s) (1, fig. 1) of
fig. 3
fig. 4
8.For best results, allow the UPS to recharge the batteries during a period of approx. 2 hours. It is
acceptable to use the UPS without first charging the battery, but the runtime may be reduced.
9.For advanced communication possibilities, the RS232 interface port (6, fig. 1) can be connected
to a computer system and/or optional interface cards (3, fig. 1) can be added. See chapter 4.
the UPS. Spread the loads over the appliance
outlets as equally as possible. If you use a
distribution box to connect more than one appliance
per outlet, please note that the maximum AC-current
rating of each appliance outlet is 10Amps. See fig. 3.
7.Connect the mains cord of the UPS to a working,
grounded AC wall socket outlet. See fig. 4. The
green LED 'on' (8, fig. 6) will blink now: mains power
is available and the batteries are charging. If the
LED does not blink but illuminates continuously
instead, press ‘0’ for one second.
OPM_NPE_19X_600_1K5_2GB_V0303GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
g
GE Digital Energy
3 - Operation
Please refer to figure 6.
3.1Start-up
3.1.1Start-up, mains available
1Press keypad 'I' (14, fig. 6) briefly; LED ‘on’ (already blinking) will illuminate continuously now.
2The equipment connected to the UPS can now be switched on.
3.1.2Start-up, mains not available
If the mains input is absent (power cord not connected, or mains failure):
1Press keypad 'I' until the buzzer sounds.
The LEDs 'on' and 'on battery' (13, fig. 6) will illuminate. The UPS operates on battery: it
discharges the batteries.
3.2Use: Normal Operation
3.2.1Normal operation conditions:
x
the mains supply is present,
x
the UPS is on,
x
the load does not exceed the capacity of the UPS and
x
the operating temperature is below alarm level
3.2.2Load indication (fig. 5)
1During normal operation, press keypad 'I' briefly.
2Yellow LEDs will blink during 3 seconds, the number is load
dependent (in case of overload LED 'alarm' (9, fig. 6) blinks as well).
3.2.3Auto-off (no-load shutdown)
If this function is activated, the UPS will switch off during a mains failure when the load is less
than 5% of the maximum load. In this way unnecessary discharging of the batteries is avoided.
The unit will automatically turn on again when mains power is restored. The default setting of the
no-load shutdown function is: activated. Changing of the setting is described in 3.4.
3.2.4Automatic bypass switch
The UPS is equipped with an automatic bypass switch. This switch automatically transfers the
load to the mains if the UPS is unable to deliver the demanded output power due to overload or
overtemperature. The UPS will switch back to normal operation when the overload has been
removed or the temperature has dropped below alarm level.
If a power failure occurs during bypass operation, the UPS will switch to battery operation and
eventually, when the batteries are depleted, output power is lost. If the UPS functions under
overload or overtemperature conditions it may not be able to protect the load.
See also 3.3.6 and 3.4.
3.2.5Switching off
1Press keypad ‘0’ (15, fig. 6) for 1 second. If the UPS is switched off the output will always be
absent for a few seconds to ensure that the connected equipment is able to reboot.
2If electric isolation is required, unplug the power cord from the wall outlet.
fig. 5
OPM_NPE_19X_600_1K5_2GB_V0304GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
Loading...
+ 9 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.