Digital Time Switch
QTY Hardware
3 M4 Anchors 1” Long
3 M4 Screws 1” Long
2 8 AWG Jumpers for 240V AC
2 10 AWG Jumpers for 120V AC
1 Wire Nut (For Ground Wires)
APPLICATION
This digital GE Time Switch (15132) is a universal, electromechanical time
switch which can be field configured for various power supply voltages.
The voltage options include 120VAC, 208/240VAC and 277VAC – all within
the same unit! Selection of the desired supply voltage is easily achieved
by positioning dipswitches on the printed circuit board assembly (consult
Dipswitches Configuration on back). The mechanism is mounted in a NEMA
indoor or outdoor enclosure and is intended for the control of lighting, heating,
air conditioning, pumps, motors, or general electrical circuits in residential,
commercial, industrial and agricultural facilities.
SPECIFICATIONS
Input Voltage: 120 VAC, 208/240 VAC, or 277 VAC in all units based
upon dipswitch configuration.
15087 NEMA 3R Indoor & Outdoor BM-A301US5-O2
15207 NEMA 1 Indoor BM-A301US5-I2
56922 NEMA 1 Indoor BM-A301US5-I2
15132 NEMA 3R Indoor & Outdoor EM-A301US9-O2
Switch Rating: DPDT Models
Normally Open Contacts
40A Resistive, 120-277Vac.
30A General Purpose, 120-277Vac.
20A Resistive, 30Vdc
1 HP, 120Vac ; 2HP, 240Vac ;
20A Ballast, 120-277Vac.
15A Tungsten, 120Vac
5.4A Tungsten, 208-277Vac.
800VA, Pilot Duty, 120Vac.
720VA, Pilot Duty, 240-277Vac.
TV-5, 120Vac
Normally Closed Contacts
30A Resistive, 120-277Vac
15A General Purpose, 120-277Vac
15A Resistive, 30Vdc
20A Ballast, 120-277Vac
1/4HP, 120Vac; 1/2HP, 208-240Vac.
290VA, Pilot, 120Vac.
360VA, Pilot, 208-240Vac.
NOTE: If loads are connected to both NC and NO contacts, both contacts are
decorated to 67% of the above values.
ENVIRONMENTAL RATINGS
Ambient Temperature: –40F to 130F
Humidity: 0-95% RH, Non-condensing
WIRING CONNECTIONS
Screw clamp terminals for up to 2 AWG #8 wires per position. For supply
connections, use 8AWG or larger wires suitable for at least 105° C. Use copper
conductors only.
Lights
Power LED (Orange) – Light illuminates when power is applied to
the timer
Status LED (Green) – Light illuminates when power is applied to load.
Included Hardware
INSTALLATION
CAUTION: Before wiring or servicing, power to this time switch and the
equipment it controls must be turned off. Turning off the time switch only
will not prevent a shock hazard. Replace cover plate within housing before
supplying power to time switch. If you are not comfortable installing this
device please contact a licensed electrician. Before installing this product read
all instructions carefully.
Removing Knockout
1. Select knockouts to be used. Remove the inner 1/2” knockout by inserting
a flathead screwdriver on the inner most ring and carefully punching the
knockout loose. Remove slug. If the 3/4” knockout is required, remove the
outer ring with pliers after removing the 1/2” knockout. Smooth edges with
a knife if necessary.
Please refer to Quick Start Guide for Examples and More Details.
Mounting of the Time Switch Box
NOTE - Before mounting be sure to remove knockouts for the wires, (see Quick
Start Guide)
1. In order to mount the box you will need the 3 supplied anchors and 3
supplied screws from the hardware list above. (Anchors included are
designed for mounting on sheetrock.)
2. Using the box as a template, mark with a pencil where the three pilot holes
will be drilled.
3. Using the appropriate drill bit size, drill the pilot holes (Note that if drilling
into wood or metal a specialized drill bit may be needed.)
See Drill Diagram.
Drill Diagram
Material Drill Bit Size
Soft Wood 5/64”
Hard Wood 3/32”
Metal 5/64”
Sheetrock 3/16”
4. For sheetrock; use a hammer to gently tap the anchors into the pilot holes.
5. Place the box up to the pilot holes or anchors and insert the screws
accordingly.
Anchors Needed?
No
No
No
Yes
Wiring the Device to the Timer
NOTE - For outdoor installation use rain tight or wet location conduit hubs that
comply with requirements of UL 514B (standard for fittings for conduit and
outlet boxes).
1. Remove 2 screws retaining the interior cover panel and remove the panel.
2. Refer to Figure 1 and wiring diagrams to determine appropriate placement
of wires. It is the responsibility of the installer to ensure that all applicable
National and Local code requirements are met. If you are unsure of these
requirements, contact a licensed electrician immediately.
3. GROUNDING: This enclosure is of plastic construction and does not require
a ground connection. This enclosure does not provide grounding between
conduits. When using non-metallic conduit or cable, connect
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
14
12
10
8
15
20
30
40
60
60
60
105
MINIMUM COPPER
WIRE SIZE (AWG)
MAX. LOAD (AMP) MIN. INSULATION
TEMP(°C)
4
3
2
1
ON
ON
ON
ON
120VAC
4
3
2
1
OFF
OFF
OFF
OFF
277VAC (Default)
4
3
2
1
OFF
ON
ON
OFF
208~240VAC
the ground wires of all cables together with the provided
wire nut. When metallic conduit is used; as the grounding
connection, use grounding type bushing and a jumper wire
between each conduit.
Dipswitch Configuration
WARNING: Failure to properly configure the dipswitch will result
in damage to the unit and void any warranty! Before installing
and wiring the GE Time Switch, proper configuration must
be selected. Unit is shipped with DIP Switches set for 277VAC
Input Voltage. Also, do not check circuits by “sparking” wires to
terminals. Damage to timer may result.
4. Determine the input voltage which will be applied to the timer.
(120V AC, 208-240V AC, or 277V AC)
5. Set the DIP Switch according to the diagram below.
6. Reinstall interior cover panel. Opposite of step 1.
Figure 1
Typical Wiring Diagrams—SPDT
Timer and Load, Same Voltage
Wired as Single Throw
T
TO POWER SUPPLY
Timer and Load, Different Voltage
NCTIMERN OC OM
TO LOAD
Wired as Single Throw
T
Typical Wiring Diagrams—DPDT
120V Timer, 200/240/277V Load Double Break
Wired as Single Throw
T
TIMERN CN O
H
TO 120V LINE
N
120V Timer, 120V Load and 24V Load
T
COM
NC2
LOAD
Wired as Single Throw
NO2
COM2
TO 200/240/277V LINE
Operating Instructions
(Reset)
H-
(Hours Setting)
M-
(Minutes Setting)
Day
(Days Setting)
(Function Figures)
(Current Time Setting)
(9 Programs Setting)
(Manual ON/OFF Switched)
Basic Settings
Initial Set Up:
1. Push the “R” button before programming to clear out any settings. Once
the “R” button is pressed the screen will begin to flash. A paperclip may be
needed for this step.
(If the “R” button appears to stick down, use a paperclip to maneuver
it until it pops back up. The screen will flash if the button is popped up
successfully.)
2. Press the “Clock” button and the screen will stop flashing and be ready for
programming.
Setting the Current Time:
1. Press and Hold the “Clock” button during the entire setting.
2. Press the “H+” button to set the hours.
3. Press the “M+” button to set the minutes.
4. Press the “Day” button to set the day of the week.
5. Release the “Clock” button.
LCD
Clock
Timer
Override
TO POWER SUPPLY 1
Wired as Double Throw
H
TO 120V LINE
N
TIMERN CN OC OM
120V Two Speed Fan
T
TIMERN CN OCOM
Field Wiring
Timer Internab Wiring
TO POWER SUPPLY 2
LOAD
HIGH
LOW
COM
TIMERN CN O
H
TO 120V LINE
N
N
TO LOAD
H
200/240/277V Timer, 200/240/277V Load, Double Break
T
TIMERN CN O
L1
L2
COM
NC2
Wired as Single Throw
COM
NC2
NO2
NO2
COM2
TO 24V LINE
LOAD
COM2
LOAD
Programming ON/OFF Settings:
1. Press the “Timer” button once and the TIMER 1 ON - - : - - appears.
2. Press the “H+” and “M+” button to set the hours and minutes to the
desired time.
3. Press the “Day” button to select the day(s) the setting will be active. Refer
to the Multiple Weekday Group below to see the available settings.
4. Press the “Timer” button to store the setting and proceed to the next
setting TIMER 1 OFF - - : - -.
5. Repeat for all remaining setting options (9 Total ON/OFF settings). Once
completed press the “Clock” button to return to the main display.
Multiple Weekday Groups:
Apart from individual week days, pressing the “Day” button also selects
multiple day combinations such as:
‧ Monday thru Friday ‧ Tuesday & Thursday & Saturday
‧ Saturday & Sunday ‧ Monday thru Wednesday
‧ Monday thru Saturday ‧ Thursday thru Saturday
‧ Monday & Wednesday & Friday ‧ Monday thru Sunday
After setting a single day or a multi-day-combination the programmed timer
settings will be carried out on each of the week-days at the same time.