Gaylord CG3-UV, C-6000-UV Service Manual

THE
GAYLORD VENTILATOR
EFFECTIVE DATE 10-2007
TECHNICAL MANUAL
FOR THE Ultima Vent
WATER-WASH VENTILATORS
MODEL C-6000-UV ESP COMMAND CENTER
TM
CG3-UV SPC SERIES
GAYLORD INDUSTRIES
10900 S.W. AVERY STREET • TUALATIN, OREGON 97062 U ..S.A.
1-800-547-9696 • 503-691-2010 • FAX: 503-692-6048 • email: info@gaylordusa.com
1
“Undisputed World Leader in
Engineered Systems for
Commercial Kitchens”
tm
GAYLORD INDUSTRIES
World Headquarters: 10900 S.W. Avery Street • Tualatin, Oregon 97062-1149 U.S.A.
To Our Customers. . .
Congratulations on your recent purchase of a Gaylord kitchen exhaust hood system. We are proud to be able to provide you with a quality product that incorporates the latest engineering concepts and is a result of over 50 years of experience in the foodservice kitchen exhaust industry.
If you have other Gaylord equipment such as a Gaylord Utility Distribution System, Quencher Fire Protection System, or Roof Top Air Handling Equipment, etc., please refer to the corresponding supplementary equipment manuals.
If you have further questions, please visit our web site at: www.gaylordusa.com, or call us toll-free at 1-800- 547-9696. We are more than happy to help.
Sincerely,
Gaylord Industries
PHONE: 503-691-2010 800-547-9696 FAX: 503-692-6048 • email: gaylord@gaylordusa.com • www.gaylordusa.com
COMMERCIAL KITCHEN EXHAUST SY STEMS • FIRE PROTE CTION • UTILITY DI STRIBUTION • ROOF TOP UNITS • POLLUTION CONTROL
STREET ADDRESS: 10900 S.W. Avery Street, Tualatin, Oregon 97062 U.S.A.
2
TABLE OF CONTENTS
"CG3-UV" VENTILATOR DESCRIPTIONS .............................................................................................. 4–-5
"CG3-UV" SERIES PRINCIPLE OF OPERATION ..................................................................................... 6–9
DAILY OPERATION .................................................................................................................................. 10
PREVENTIVE MAINTENANCE ............................................................................................................. 11-12
SAFETY CONCERNS WITH UVC ............................................................................................................. 13
DETERGENT PUMP OPERATION ............................................................................................................ 14
DETERGENT FOR THE WASH SYSTEM ................................................................................................. 15
MODEL C-6000 SERIES COMMAND CENTER - INSTRUCTIONS........................................................16–19
ENGINEERING DATA ...........................................................................................................................20-21
START-UP PROCEDURES ....................................................................................................................... 22
RP DEVICE–INITIAL START-UP ................................................................................................... 23
MEASURING INLET SLOT VELOCITY .....................................................................................24-26
OPTIONAL CONTINUOUS COLD WATER MIST ....................................................................................... 27
TROUBLESHOOTING:
SMOKE LOSS ............................................................................................................................. 28
GREASE EXTRACTION ............................................................................................................... 28
EXHAUST FAN.................................................................................................................. .. 29
WASH SYSTEM ..................................................................................................................... 2930
FIRE CYCLE ................................................................................................................................ 31
BACKFLOW PREVENTERS .................................................................................................... 31-32
VACUUM BREAKER ................................................................................................................... 31
RP DEVICE .................................................................................................................................. 32
DRAINS........................................................................................................................................ 32
MISCELLANEOUS ....................................................................................................................... 32
UV SYSTEM ............................................................................................................................33-34
PLC STATUS LIGHT CHART ....................................................................................................... 35
C-6000-UV TERMINAL VOLTAGES .............................................................................................. 36
UV STATUS LIGHTS .................................................................................................................... 37
PARTS LISTS:
MODEL GPC-6000-UV-VB SERIES CONTROL CABINET ............................................................ 38
MODEL GPC-6000-UV SERIES CONTROL CABINET .................................................................. 39
MODEL GPC-6000-UV-S SERIES CONTROL CABINET .............................................................. 40
OPTIONAL CONTINUOUS COLD WATER MIST .......................................................................... 41
MODEL C-6000-UV SERIES CONTROL ....................................................................................... 42
DAMPER CONTROL MOTOR AND CG3-UV-FDL WIRING ........................................................... 43
DETERGENT PUMP .................................................................................................................... 44
MISCELLANEOUS VENTILATOR PARTS .................................................................................... 45
UV MODULE ................................................................................................................................ 46
WIRING DIAGRAMS ............................................................................................................................47–51
STANDARD VENTILATOR MODELS ........................................................................................................ 52
METRIC CONVERSION CHART................................................................................................................ 53
START-UP INSPECTION REPORT ........................................................................................................... 54
LIMITED WARRANTY ........................................................................................................ Inside back cover
Patent Pending
© Copyright 2004, Gaylord Industries
ALL RIGHT RESERVED. NO PART OF THIS BOOK MAY BE REPRODUCED, STORED IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM BY AN ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING MEANS OR OTHERWISE WITHOUT THE WRITTEN PERMISSION OF GAYLORD INDUSTRIES COPYRIGHT 2004.
The manufacturer reserves the right to modify the materials and specifications resulting from a continuing program of product improvement or the availability of new materials.
Additional Copies $15.00
3
"CG3-UV" VENTILATOR DESCRIPTIONS
There are 4 different types of "CG3-UV SPC” Gaylord water-wash ventilators. The differences involve the type and location of fire damper, whether it has an ultraviolet radiation system, and whether the ventilator has a fire damper. The first part of the model number indicates the type of ventilator, see below:
Explanation of Prefixes:
CG3-UV Water-wash ventilator with three-position, ther-
mostatically activated (electric) damper at air inlet slot.[With Damper motor and 1 or
more Thermostat(s)]
CG3-UV-FDL Water-wash ventilator with three-position, ther-
mostatically activated (electric) damper at air inlet slot. A bracket (Fire Damper Lockout) has been added to prevent the damper from closing to the fire position.[With Damper motor and
1 or more Thermostat(s)]
CG3-UV-FDD Inlet damper is fixed, and there is a weighted
fuse link activated fire damper located at the duct collar. [No Damper motor, No
Thermostats]
CG3-UV-ND Inlet damper is fixed. No Fire Damper at duct
collar. A bracket (Fire Damper Lockout) has been added to show that the damper will not close to the fire position. [No Damper motor,
No Thermostats]
Summary of "CG3-UV" Ventilators:
The CG3-UV and CG3-UV-FDL are very similar. Both have a damper motor that closes the inlet damper during the wash mode and stays closed until the exhaust fan is started. Both have thermostats that can detect an “Internal Fire”. The main difference is the CG3-UV-FDL has a Fire Damper Lockout (FDL) bracket added that prevents the inlet damper from closing to the fire position, so it does NOT have a fire damper.
The CG3-UV-FDD and CG3-UV-FDT are similar to each other. Both have fixed inlet dampers and do not have damper motors. They both have fuse link activated fire dampers in the duct collar that will close when the temperature reaches 280°F. The CG3-UV-FDT has an added thermostat that will detect an “Internal Fire” and activate the “Internal Fire Mode”. The CG3­UV-FDD does NOT have any thermostats.
The CG3-UV-ND has a fixed inlet damper and does NOT have a fire damper.
4
"CG3-UV" SERIES VENTILATOR DESCRIPTIONS
CG3-UV SPC SERIES
ELECTRIC INTERNAL DAMPER
[W/DAMPER MOTOR &
THERMOSTAT(S)]
CG3-UV-SPC-FDD SERIES
FUSE LINK DUCT COLLAR DAMPER
[NO DAMPER MOTOR, NO
THERMOSTAT(S)]
CG3-UV-SPC-FDL SERIES
FIRE DAMPER LOCKOUT
[W/DAMPER MOTOR &
THERMOSTAT(S)]
CG3-UV-SPC-ND SERIES
NO DAMPERS
[NO DAMPER MOTOR, NO
THERMOSTAT(S)]
5
"CG3-UV" SERIES VENTILATOR PRINCIPLE OF OPERATION
GREASE EXTRACTION
The Gaylord “CG3-UV” SPC Series Ventilator extracts up to 99% of the grease, dust and lint particles from the airstream passing through it, when operated and maintained in accor­dance with design specifications.
The hot, contaminant-laden air rising from the cooking surface merges with the higher velocity air that wipes the front of the cooking equipment and extends, like an air blanket, from the front edge of the cooking equipment to the air inlet of the ventilator. As the air moves through the ventilator at a high speed, it is forced to make a series of turns around three baffles. As the high velocity air turns around each baffle, the heavier-than-air particles of grease, dust and lint are thrown out of the airstream by centrifugal force. The extracted grease, dust and lint are collected in the interior of the ventilator, remaining out of the airstream until removed daily by the wash cycle.
Baffle #1
This baffle, located at the air entrance of the ventilator, is a three position damper. Position 1 is the exhaust on mode as shown in Figure 1 below, position 2 is the wash mode, and position 3 is the fire mode. When the "Start Fan" button is pushed on the control cabinet, the damper opens to the exhaust mode (position 1) to become the preliminary grease extraction baffle. There is a small sloped grease collecting gutter on the back side of the damper which drains off liquefied grease, preventing it from re-entraining into the airstream.
Baffle #2
This baffle is located on the interior back wall of the ventilator and is a stainless steel pipe, equipped with brass spray nozzles on 8" to 10" centers. (Refer to Figure 1) During the wash cycle, hot detergent water is released through the nozzles. If the ventilator’s automatic fire control system is activated, fire smothering water spray is also released through the spray nozzles.
DUCT TAKE-OFF COLLAR
TRANSITION AREA
UV LAMPS
PARTICULATE SEPARATOR
BAFFLE #3
BAFFLE #2
OPTIONAL "CUSTOM AIR" BAFFLES
MAIN GUTTER
DRAIN LINE
FAIL-SAFE ELECTRIC DAMPER CONTROL
FAIL-SAFE THERMOSTAT
N/A ON FDD AND ND MODELS
SPC CELL
BAFFLE #1 ( 3 POS I­TION DAMPER IN THE EXHAUST POSITION)
INLET SLOT
Baffle #3
This baffle is located on the back of the inspection doors. This baffle is also a grease collecting gutter, collecting grease, dust and lint extracted by the ventilator - preventing the contaminants from dropping back into the high velocity airstream.
Particulate Separator
Once the largest particles of grease have been captured through inertial impaction by the baffles. The smaller particles of grease will be arrested in the particulate separator using the principles of diffusion and inertial impaction. These collected particles wil be washed away each day by the automatic wash.
UV Lamps
Once the baffles and particualte separator have collected the grease particles larger than 1 micron. The UV lights will be able to break down the remaining grease by direct exposure to 254nm light and by the Ozone, Hydroxyl Radicals and Anionic oxygen created by the 187nm UV light. This will carry down the ductwork and continue to break down the grease, particulate and odor molecules keeping the ductwork much cleaner. The byproducts of this process are CO from the grease and particulate matter coming off of the
, H20 and the base minerals
2
cooking surface. There will be a light gray dust that collects on the lamps which will be washed away each day during the wash. The ductwork will need to be inspected per NFPA-96 schedules but, will need much less frequent cleaning.
SPC Principles of Operation
The SPC Cell removes smoke particles by electrostatic pre­cipitation. The principle of operationof electrostatic precipita­tion is actually quite basic. The electrostatic cell is made up of a series of aluminum plates spaced approximately 1/4” (6.35 mm) apart and the number of cells used is determined by the air volume and the type of cooking equipment involved. Every other plate is energized with 5000 volts of D.C. power and the alternating plates are grounded. At the entry point of the cell is a series of thin wires spaced at approximately 4” (101.60mm) apart. These wires, referred to as ionizing wires, are energized with 10,000 volts D.C. and as the smoke par­ticles enter the cell and pass over the wires they receive a positive charge. As the charged particles continue through the cell, the positive plate repels them and the negative or ground­ed plate attracts them. Thus, the smoke particles are col­lected on the negative plates. The action isefficient, safe and simple.
NOTE: Some ventilators may be equipped with optional Custom Air” baffles (shown dotted) which reduces the exhaust volume where the baffle occurs.
NOTE: Some ventilators may be equipped with optional continuous cold water mist. Refer to Page 27 for details.
FIG. 1
GREASE EXTRACTION
6
"CG3-UV" SERIES VENTILATOR PRINCIPLE OF OPERATION
WASH CYCLE
The wash cycle is activated each time the exhaust fan is shut off by pushing the “Start Wash” button on the Command Center or as programmed on the clock. When activated the UV lamps shut off, the exhaust and supply fans shut off, the damper control is energized and the damper begins closing forward to the wash position, and once closed the hot water wash sprays come on.
This hot detergent water washes the day’s grease, dust and lint accumulation from the interior of the ventilator flushing it down to the main gutter which slopes to a pre-flushed drain which leads to the building drain system. Spray nozzles are located on 8" to 10" centers on the wash manifold mounted on the interior back wall of the ventilator. At the end of the wash cycle, the water automatically shuts off, and the interior of the ventilator is clean - ready for the next day’s operations. The damper remains in the wash position until the exhaust fan is restarted. This is to prevent conditioned air from going up the exhaust system during off hours.
The length of the wash cycle may be set between 3 minutes and 9 minutes. The length of time is dependent upon the type of cooking equipment being used. Typical settings are 3 minutes for light-duty equipment, 5 minutes for medium-duty equipment, and 9 minutes for heavy-duty equipment. However, adequate cleaning is dependent upon water pressure, water temperature, daily grease accumulation, the length of the wash cycle, frequency of wash cycle and the type of detergent being used. It may be necessary to increase the wash time to achieve proper cleaning. Refer to page 17 for details on setting the wash time.
COMMAND CENTER MODEL C-6000-UV-ESP SERIES
FIG. 2
VENTILATOR CONTROL CABINET
MODEL GPC-6000-UV SERIES
WATER SUPPLY FROM CONTROL CABINET
SPRAY NOZZLES
HOT DETERGENT WATER SPRAY
PRE-FLUSH LINE
MAIN GUTTER
DRAIN LINE
HINGED UV ACCESS DOORS
FULL-LENGTH HINGED INSPECTION DOORS
DAMPER CLOSED FORWARD TO THE WASH POSITION (N/A ON FDD AND ND MODEL CG3-UV SPC)
FIG. 3
WASH CYCLE
7
"CG3-UV" SERIES VENTILATOR PRINCIPLE OF OPERATION
INTERNAL FIRE MODE—For CG3-UV SPC
Automatic internal fire protection is accomplished by the action of the thermostat(s), which are located at the point where the ductwork joins the ventilator. When the temperature of the conveying airstream, which must pass over the thermo­stats, reaches 250°F, the system is activated, and the following occurs:
1. The damper begins closing back to the fire position, position 3 as shown in Fig.4—stopping the combustion­supporting, natural draft through the ventilator and creating a fire barrier to contain the fire in the kitchen.
2. The UV lamps are shut off.
3. The exhaust fan serving the ventilator is shut off. The supply fan is also shut off.
4. Fire-smothering water spray is released into the interior of the ventilator through the spray nozzles.
5. The digital display reads "Fire In Hood, Fan Off, Wash On" for approximately 5 seconds.
6. Then the digital display reads "Fire In Hood, Damper Closing" for approximately 5 seconds.
CAUTION:
In case of severe fire the thermostats located in the plenum will activate. As a precautionary measure, it is recommended that the thermostats be replaced.
7. Then the digital display reads "Fire In Hood, Notify Fire Department". This display stays on until the thermostat cools down below 250°F.
7. A red light on the Command Center illuminates.
8. On the C-6000control: dry contacts A1 & A2 will CLOSE and dry contact Q1 & Q2 will OPEN.
9. Upon cooling of the thermostat below 250
o
F, the Cool Down Cycle starts. The water continues to spray during the Cool Down Cycle (2 minutes). The damper moves to the exhaust position.
10.While in the cool down cycle the digital display reads "Cool Down Cycle, xxx sec. to end". xxx is the countdown in seconds until the wash turns off. The damper moves to the exhaust position.
11.At the end of the cool down cycle the wash turns off and the digital display reads "Fan Off 12:00 (actual time), Start Fan>F1". The damper closes to the wash position.
NOTE: The water may be shut off prior to the end of the 2 minute
cool down cycle by pushing the Exit button on the C-6000 Command Center. After the water has shut off, the damper remains in the wash position until the Start Fan button is pushed.
Starting the Exhaust Fan
WATER SUPPLY FROM CONTROL CABINET
FIRE QUENCHING WATER SPRAY
WATER BARRIER
DRAIN LINE
DAMPER CLOSED BACK TO THE FIRE POSITION
SURFACE FIRE PROTECTION NOZZLE (OPTIONAL)
FIG. 4
FIRE CYCLE
8
"CG3-UV" SERIES VENTILATOR PRINCIPLE OF OPERATION
EXTERNAL FIRE MODE
An External Fire Mode is activated by the Ventilator’s Surface Fire Protection (Duct, Plenum, Surface/Appliance) system’s microswitch or contacts and/or an optional break glass fire switch (see Figure 5).
Note: The Surface Fire Protection system must be UL listed for such application and is separate from the ventilator’s water-wash system. Terminals 4 & FS are used for the External Fire Mode, refer to the wiring diagram for details. The break glass fire switch, if used, would normally be located at the exit of the kitchen. When the External Fire Mode is activated the following occurs:
1. The Exhaust Fan comes on immediately if it was off to help
remove smoke, heat, etc.
2. The Supply Fan shuts off immediately.
3. The digital display reads “Ext.FireActive” and alternates
between “Reset FireSwitch” and “Fan On, Wash On”.
4. A red light on the Command Center flashes.
5. After a 60-second delay, a water spray is released into the
interior of the ventilator through the spray nozzles. The 60- second delay allows the ventilator’s fire suppression sys- tem time to put out the fire, before starting the water spray.
If the fire intensifies and the thermostat reaches 250°F, the fire damper would then close and the exhaust fan would shut off. See Internal Fire Mode.
To resume normal operations, open the fire switch and flip the toggle switch to the position marked “normal”. Replace the glass rod and close the cover. Push either the “Start Fan” or
“Start Wash button.
TESTING INTERNAL FIRE MODE
To test the Internal Fire Mode, a fire detected by the ventilator’s thermostat(s), push and hold the “Fire Test Switch” button for 20 seconds. It is located inside the electrical compartment of the control cabinet. Pushing this switch duplicates thermo­static action.
CAUTION: Before any Fire Tests are performed, check with the building superintendent to see if the Gaylord control cabinet or Surface Fire Protection system is wired to the building alarm, monitoring system, and/or the fire department
TO RESUME NORMAL OPERATION
1. To discontinue the 2 minute cool down cycle at any point
during the cycle, push the “Exit” F5 button on the C-6000 Command Center.
2. Push the “Start Fan” F1 button on the Command Center.
SURFACE FIRE PROTECTION
The National Fire Protection Association, NFPA-96 document requires fire extinguishing equipment over all grease producing cooking equipment such as griddles, ranges, fryers, broilers, and woks. In addition, the system must protect the interior of the ventilator and the exhaust duct.
The most common fire system is the wet chemical type. In the event of a fire, this system would normally be activated and discharged prior to the ventilator’s water spray being act­ivated. If the fire is unusually severe or the surface fire prot­ection system malfunctions, the thermostat(s) in the ventilator would activate the ventilator’s water spray. Surface fire pro­tection systems may be wired to the ventilator control cabinet to activate the External Fire Mode.
.
FIG. 5
BREAK GLASS FIRE SWITCH
C-1357A SERIES
INTERNAL & EXTERNAL FIRE MODES AT THE SAME TIME
It is possible that both the Internal and External Fire modes can be activated at the same time. If this occurs the Internal Fire Mode will override the External Fire mode until the thermostat(s) cool below 250°F. At this point the Cool Down Cycle will start counting down for 2 minutes. After the Cool Down Cycle, the External Fire mode will start.
Special Note: If the control is in the Cool Down Cycle when the External Fire mode is activated, the Cool Down Cycle will finish counting down for 2 minutes, before switching to the External Fire Mode.
Summary of Both Fire Modes at the Same Time
1. Internal Fire Mode (until thermostat temperature drops
below 250°F)
Cool Down Cycle (for 2 minutes)
2.
3.
External Fire Mode (until the External Fire Switch is reset)
FIRE MODE SUMMARY:
Note: The Damper Posi­tion does not apply to CG3-U V-FDL SP C CG3-U V-
FDD SPC
or CG3-UV-ND SPC
Exhaust Fan Supply Fan Damper Position Water Spray UV Lamps
INTERNAL
FIRE
OFF OFF ON OFF OFF OFF
FIRE EXHAUST EXHAUST
ON ON ON
OFF OFF ON
COOL DOWN
CYCLE (for Internal
Fire Mode only!)
EXTERNAL
FIRE
9
DAILY OPERATION
DAILY OPERATION
All functions of the ventilator, such as starting the exhaust fan, starting the wash cycle, etc., are controlled by the Command Center located on the control cabinet. Refer to Pages 16 through 19 for detailed instructions on the operation of the Command Center.
ESP CELL STATUS LIGHTS
COMMAND CENTER MODEL C-6000-UV SPC SERIES
VENTILATOR CONTROL
MODEL GPC-6000-UV-ESP
FIG. 6
CABINET
SERIES
To start the exhaust fan push the “Start Fan” button on the Command Center. If the Command Center is programmed to start the fan automatically, then the start button does not need to be pushed. It is important to start the exhaust fan before turning on the cooking equipment.
When the exhaust fan is activated the following occurs:
1. The damper begins opening on to the exhaust position. (N/A on CG3-UV-SPC-FDD and CG3-UV-SPC-ND)
2. Green status lights on the Command Center illuminate.
3. The supply fan comes on.
4. The digital display reads “Starting Fan & Damper Opening” for approximately 5 seconds. Then the digital display reads “Starting Fan, xx Seconds to Fan On”. xx is the countdown in seconds until the exhaust fan comes on.
5. After the damper fully opens (elapsed time approximately 45 seconds), the exhaust fan comes on.
6. The red UV Saftey Interlock Activated and the UV Audible Alarm Cancel Button” lights will illuminate until the exhaust fans reaches operating speed.
7. Once the exhaust fan reaches operating speed, the UV lamps in the ventilator and the green UV System On light on the ventilator and the GPC-6000-UV ESP cabinet will turn on, along with the cell status lights.
8. The digital display then reads “Fan On 12:00” (current time) and “Start Wash> F2”.
Stopping the Exhaust Fan and Starting the Wash Cycle
CAUTION: The cooking equipment must be shut off prior to
shutting off the exhaust fan. Failure to do this will cause excessive heat buildup and could cause the surface fire protection system to discharge.
To start the wash cycle push the Start Washbutton on the Command Center. If the Command Center is programmed to start the wash automatically, then the start button does not need to be pushed. When the wash cycle is activated the following occurs:
1. The UV lamps and electrostatic cells shut off.
2. The exhaust and supply fans shut off.
3. The damper begins closing forward to the wash position.
(See Figure 3, page 7). This action takes approximately 45 seconds. (N/A on FDD and ND models)
4. The digital display reads "Starting Wash, Damper Closing"
for approximately 5 seconds, then the digital display reads
"Starting Wash, Wash On in xx seconds". xx is the countdown in seconds to until the wash starts.
After the damper in the ventilator closes to the wash pos-
5. ition, the hot detergent injected water sprays come on to wash away the grease and smoke collected during the day’s operation. The wash cycle stays on for the length of time pro­grammed in the Command Center. The length of the wash cycle may be set between 3 and 9 minutes. Typical settings for the CG3 Ventilator are 3 minutes for light-duty equip­ment, 5 minutes for medium-duty equipment and 9 min­utes for heavy-duty equipment. The typical setting for the SPC wash is 5 minutes. Refer to page 20 for details on setting the length of the wash.
6. During the wash cycle, the digital display reads "Wash On, Wash #1 xxx seconds". xxx is the coundown in seconds until the wash system shuts off.
7. During an SPC wash, the digital display reads:
“ESP Wash 1, Wash #2 xxx seconds” “Hot Water Heating, Wash #2 xxx seconds” “ESP Wash 2, Wash #2 xxx seconds” “Hot Water Heating, Wash #2 xxx seconds” “ESP Rinse, Wash #2 xxx seconds” xxx is the countdown in seconds until this portion of the wash is completed.
8. Upon completion of the wash cycle, the damper stays in the closed wash position until the exhaust fan is re-started. This is to prevent conditioned air from going up the exhaust stack during off hours.(N/A on FDD and ND models)
9. The digital display now reads "Fan Off 12:00" (current time) and Start Fan>F1.
After the wash cycle is completed, wipe the exposed front surface of the damper at the air inlet slot, as well as other exposed exterior surfaces. (Refer to Figure 7, Page 11).
In very heavy cooking operations it may be necessary to wash the ventilator(s) more than once a day. This can be done manually by pushing the “Start Wash” button.
NOTE: For proper operation of the wash system there must be adequate water pressure and temperature. There is a pressure/temperature gauge inside the control cabinet.
Water Pressure 40 psi min. - 80 psi max.
Water temperature 140°F min. - 180°F max. NOTE: Some control cabinets are equipped with a low detergent switch. If so equipped, the green light will flash if the detergent tank is empty or if the detergent pump is malfunc­tioning and detergent is not pumping. The digital display reads "Low Detergent" and the text alternates from "Fill Tank" and "Check Pump". If the detergent tank is filled with water the detergent switch will activate as if there is no detergent.
NOTE: The ventilator wash system is designed to remove daily accumulations of grease within the extraction chamber. If the ventilator is not washed a minimum of once during a cooking day, a grease buildup could accumulate which the wash system cannot remove. If this occurs, it is recommended that the ventilator be put through several wash cycles by pushing the “Start Wash” button on the Command Center. If this does not remove the grease, it will be necessary to remove the grease manually by using a scraping tool, such as a putty knife, or retain the services of a commercial hood cleaning service to steam clean or pressure wash the system.
WARNING: Some commercial hood cleaning services blow a fire retardant chemical into hood and duct systems. Fire retardant chemicals should never be applied to any portion of The Gaylord Ventilator. If retardant is applied to the ventilator, it must be removed.
10
PREVENTIVE MAINTENANCE
PREVENTIVE MAINTENANCE
Some of the required maintenance can be performed by the operator. However, direct exposure to UV light is hazardous to your Skin and Eyes and contact with live electrical compo­nents poses a significant risk up to and including death. Therefore, a trained, qualified and certified technician must perform most of the maintenance.
The following should be checked periodically in order to keep the Gaylord Ventilator and UV System operating at design efficiency:
Daily
1. Make sure the green "UV System On" and “Cell Satus” lamps on the hood and control cabinet are on when the fan is on. If not, follow the UV SPC Troubleshooting proc- edures on pages 33-34.
Weekly
1. The detergent tank should be checked at least weekly and kept full with a recommended detergent. (Refer to Page 15)
Monthly
1. The detergent system fittings should be checked at least monthly. This is an airtight system and fittings should be tight. (For complete details refer to the Detergent Pump section on Page 14.)
2. At least monthly, at the conclusion of a wash cycle, open the inspection doors of the ventilator and check to ensure that the interior has been cleaned of grease, dust, and lint. (Refer to Figure 7) If overall cleaning appears to be inadequate, refer to “Troubleshooting of the Wash Sys- tem”, Page 29.
3. The main grease gutter of the ventilator should be checked at least monthly to remove any foreign material such as paper towels, order chits, etc.
4. Check the Particulate Separators, UV Lamps, and SPC
Cells to ensure they are being cleaned of grease, lint and dust. If the cleaning is inadequate:
1. Remove the particulate separators, and/or SPC cell, through the inspection (wash access) doors and run them through a dishwasher or soak tank and replace.
2. The wash system needs adjustment. Refer to "Trouble
shooting the Wash System", page 29.
Every Six Months
1. Exhaust fan(s) should be checked every six months for belt tightness, belt alignment, and lubrication of necessary moving parts.
NOTE: A blue lithium based grease is best suited for high heat and speed bearing lubrication.
2. Check for proper velocity at air inlet slot. Refer to Pages 24 through 26 for method of checking velocity.
3. Test the "Internal Fire Mode" to check for proper damper closure. Refer to Page 9 for instructions.
4. Detergent tank and foot valve should be cleaned every six months.
Every Six Months (SPC)
Every 6 months remove and inspect the SPC cells and check the following:
1. Check all the spray nozzles to ensure that they are spray­ ing properly.
2. Examine the SPC Cells for the following:
a.Check for any missing or loose ionizer wires. Replace wires as necessary. (Refer to Ionizing Wire Replacement illustration).
b.Check for any physical damage to the collector plates. Plates can become bent at their corners and must be straightened to maintain proper plate spacing.
c.Check for any grease film build-up on the high-voltage insulators (white porcelain material.) Clean the insul tors to avoid possible high-voltage tracking to the ground.
d.Check for any material which has lodged or built up between adjacent plates.
INSPECTION AND CLEANING REQUIREMENTS
NFPA-96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations) require that hoods, ducts and exhaust fans be inspected by a properly trained, qualified and certified company or person(s) in accordance with the following table.
Upon inspection, if found to be contaminated with deposits from grease-laden vapors, the entire exhaust system shall be cleaned by a properly trained, qualified, and certified company or person(s) acceptable to the authority having jurisdiction in accordance.
When a vent cleaning service is used, a certificate showing date of inspection or cleaning shall be maintained on the premises. After cleaning is completed, the vent cleaning contractor shall place or display within the kitchen area a label indicating the date cleaned and the name of the servicing company. It shall also indicate areas not cleaned.
ELUDEHCSNOITCEPSNIMETSYSTSUAHXE
snoitarepognikoocemulov-hgihgnivressmetsyS
gnikooc
kowrogniliorbrahc,gnikoocruoh-42sahcus
gnikoocemulov-etaredomgnivressmetsyS
snoitarepo
,snoitarepognikoocemulov-wolgnivressmetsyS
lanosaes,spmacyad,sehcruhcsahcus
sretnecroinesro,sessenisub
ylretrauQ
yllaunna-imeS
yllaunnA
Factory trained service agencies are certified by Gaylord Industries, Inc. to perform these inspections. For the name and phone number of your nearest agent visit our web site at www.gaylordusa.com, email at info@gaylordusa.com, or call 1-800-547-9696.
11
ESP SECTION - PREVENTIVE MAINTENANCE
MOUNTING
BRACKET
IONIZING
WIRE
INSERT HOOK OF ONE SPRING INTO HOLE
A
PULL SECOND SPRING UNTIL HOOK CAN BE SECURED IN MOUNTING BRACKET HOLE
B
SMOKE POLLUTION CONTROL CELL
AIRFLOW
HighVoltage - Be sure power is off and high voltage circuit is grounded before
touching the wire terminals. Refer to the GaylordClearAireTechnical Manual for complete operation & maintenance instructions.
Cell Removal - This cell weighs more than 52lbs. Handle with care when removing for cleaning and servicing.When handling cell, hold framework only. Do not touch the plates as they could be damaged.
Cleaning Cell -The smoke pollution control cells in this system are made of aluminum. Use of a deter- gent harmful to aluminum will void the warranty and may cause permanent damage.
WARNING: CELL AND UNIT AIRFLOW DIRECTION MUST MATCH
AIRFLOW
INNER CELL
MODELNO.: C-24-I
CAUTION
INNER CELL
MODELNO.: C-24-I
SMOKE POLLUTION CONTROL CELL
HighVoltage - Be sure power is off and high voltage circuit is grounded before
touching the wire terminals. Refer to the Gaylord“ClearAire”Technical Manual
for complete operation & maintenance instructions.
Cell Removal - This cell weighs more than 52lbs. Handle with care when removing for cleaning and
servicing.When handling cell, hold framework only. Do not touch the plates as they could be damaged.
Cleaning Cell - The smoke pollution control cells in this system are made of aluminum. Use of a deter-
gent harmful to aluminum will void the warranty and may cause permanent damage.
WARNING: CELL AND UNIT AIRFLOW DIRECTION MUST MATCH
CAUTION
b. Check for any physical damage to the collector plates.
Plates can become bent at their corners and must be straightened to maintain proper plate spacing.
c.Check for any grease film build-up on the high voltage
insulators (white porcelain material.) Clean the insula­tors to avoid possible high voltage “tracking” to the ground.
d.Check for any material which has lodged or built up
between adjacent plates.
Replacing the Ionizing Wire
1.Remove all of the broken wire from the cell mounting brackets.
2.Install the new wire:
A. Insert hook of one spring into hole.
B. Use long-nose pliers and carefully pull second spring until hook can be secured in mounting bracket hole.
CAUTION: The electrostatic cells are made of aluminum. DO NOT use any type of detergent that may attack aluminum or anodizing. It is highly recommended that Formula G-510 Colloid Cleaner be used in the wash system. Refer to Page 27 for details.
OUTER CELL
Note: See page 63 for part numbers
SPC CELL
UV LAMPS
PARTICULATE SEPARATOR
MAIN GREASE GUTTER
DURING CLEAN-UP PROCEDURES AT THE END OF THE COOKING PERIOD SPECIAL ATTENTION SHOULD BE GIVEN TO WIPING CLEAN THE DAMPER AT THE AIR INLET OF THE VENTILATOR
IONIZING WIRE REPLACEMENT
SPC ACCESS DOOR(S)
INSPECTION (WASH ACCESS DOO RS)
DURING CLEAN-UP PROCEDURES AT THE END OF THE COOKING PERIOD THESE AREAS SHOULD BE WIPED DOWN.
FIG. 7
PLUNGER SAFETY SWITCH
"DAMPER ACTUATOR ACCESS” PANEL
DAMPER ACTUATOR LOCATED BEHIND THIS PANEL
12
UV PREVENTIVE MAINTENANCE
CERTIFIED SERVICE AGENT MAINTENACE WARNING!
Warning: Do NOT defeat the purpose of the interlocks during cleaning and maintenance!
These items will need to be performed by a trained and quali­fied Certified Service Agency (CSA) on the same schedule as the exhaust system inspection schedule described in NFPA­96 and on the previous page in this tech manual. These tasks involve potential exposure to high doses of UV light and live electrical components. There is risk of injury to skin and eyes and in the case of electrical shock, injury or death! For a list of CSAs go to www.gaylordusa.com and go to "Service Agen­cies" for a list of companies nearest you.
1. Inspection of the Lamps and Ballasts
a. Check the lamps for proper operation
1. Turn on the fan and look for the green "UV System On" light on each hood section a. If it is not on refer to "UV Troubleshooting",
pages 34-35.
2. Open the UV Access door with the key
3. Turn on fan
4. Close inspection (wash access) doors
5. Depress the UV Access door safety switch
6. Check all indicator LEDs, 6 green and 3 red, to ensure that they are all on. If they are not all on go to "UV Troubleshooting", pages 34-35.
2. Inspect the Upper Wash chamber (around the UV lamps)
a. Disconnect the UV module power cord b. Remove the nuts holding the UV module to the ventila-
tor with a nut driver c. Remove the UV module from the ventilator d. Check for build-up of deposits of grease, dust and/or lint. e. Clean as necessary with a mild dteregent, water and a rag f. If the area is not clean refer to "Troubleshooting the Wash System", on page 29. g. Reinstall the UV module.
3. Test the Safety Interlock switches
a. Open the inspection (wash access) door with the fan on
The UV lamps should shut off
An audible alarm on the C-6000 should come on
The Red “UV Safety Interlock Activated” light on the ventilator and C-6000 control should come on
b. Open the UV Access door with the fan on
The UV lamps should shut off
An audible alarm on the C-6000 should come on
The Red “UV Safety Interlock Activated” light on the ventilator and C-6000 control should come on
c. Turn off the breaker to the Exhaust Fan. Press the
“Start Fanbutton on the C-6000 control
The UV lamps should shut off (stay off)
An audible alarm on the C-6000 should come on
The Red “UV Safety Interlock Activated” light on the ventilator and C-6000 control should come on
4. Check all gaskets for damage
a. Replace any gaskets that are worn or damaged
5. Check the Hour Meter
a. Record the hours. b. Determine the approximate hours between inspection
intervals.
c. Determine when the 8000-hour life of the lamps will
occur and inform the operator of the approximate date when the lamps will need to be replaced
Replacing UV Lamps
Danger!
These items will need to be performed by a trained and qualified Certified Service Agency (CSA). These tasks involve potential exposure to high doses of UV light and live electrical compo­nents. There is a risk of serious injury to skin and eyes from UV light. There is risk of shock, injury, and/or death from electrical. For a list of CSA’s go to www.gaylordusa.com and go to the “Service Agencies” for a list of certified companies nearest you.
1. Secure all power to the C-6000 control
2. Secure all circuits that provide power to the UV lamps
3. Open the UV Access door with the key
4. Disconnect the UV module power cord
5. Remove the nuts holding the UV module to the ventilator with a nut driver
6. Remove the UV module from the ventilator
7. Remove the bolts on each end of the UV module (2 on each end) that hold the end caps on
8. Disconnect the lamp connector(s) on the UV lamp(s) to be replaced
Each lamp connector should be labeled from 1 to 6 on
both ends
Lamp #1 is at the Front of the ventilator when the UV
module is installed
Lamp #6 is at the Back of the ventilator when the UV
module is installed
Be sure to re-label the lamp connectors if necessary
9. Lubricate the lamps around the grommets on each end of the UV lamp with a small amount of G-510 or similar detergent
10.Slide the UV lamp out one end, CAREFULLY!
11.Inspect the grommets around the lamps
Replace any grommets that show cracks, checking, or
any other damage
12.Check all wires for damage
Replace any wires showing damage
13.Lubricate each of the new UV lamp(s) before installing with a small amount of G-510 or similar detergent
14.Re-connect the lamp connectors on both ends of the UV lamps
Each lamp connector should be labeled from 1 to 6) on
both ends
Lamp #1 is at the Front of the ventilator when the UV
module is installed
Lamp #6 is at the Back of the ventilator when the UV
module is installed
15.Re-install the UV module end caps and torque the bolts to 7-10 in-lbs.
16.Re-install the UV module in the ventilator
17.Tighten all nuts holding the UV module to the ventilator
18.Re-connect the UV module power cord
19.Check for proper operation of UV lamps
13
SAFETY CONCERNS WITH UVC
As with many types of technology if it is not used properly and/ or proper precautions are not taken there is the potential for injury or harm. This is especially true with UVC light due to the fact that it does not physically hurt at the time of exposure. While UVC is very effective at breaking down grease mol­ecules, direct exposure to large amounts is harmful to skin and eyes. The amount of UVC generated in these hoods is greater than that what results from direct exposure to the sun. Under no circumstances is it acceptable to view the lighted lamps without proper eye protection or expose bare skin directly to the light. All interlocks and safety precautions called for in this manual must be followed to avoid the potential for harm to service personnel and/or operators. In addition, only trained and authorized personnel may perform some maintenance See previous page for details.
Personal Protective Equipment
1. Eye protection that prevents 100% of UVC being transmit- ted through the lens must be worn at all times when performing service work on any Ultima Vent that is ener- gized and/or has the potential to be energized and expose personnel to UVC light.
2. Whenever service work is performed it is recommended that long sleeve pants and shirts be worn to minimize the potential for inadvertent exposure of the skin to UVC.
Safety Interlocks
This product comes equipped with the following sensors to verify that all access doors are in place and that the exhaust fan is running:
1. Mechanical door switch on the UV Access door to ensure that the door is closed
2. Proximity Switch on the Inspection (wash access door) to ensure that the door is closed.
3. Air Pressure switch to verify air flow and exhaust fan operation
All of these devices must be working and/or adjusted properly in order for the system to operate properly.
14
DETERGENT PUMP OPERATION
The Gaylord Ventilator detergent pump is an integral part of the wash-down system of The Gaylord Ventilator. The pump is located within the control cabinet unless otherwise specified. (Refer to schematics on Pages 38 through 40.)
OPERATION
The detergent pump is started when the wash cycle begins. The pump draws detergent up from the detergent tank, pushing it through the copper tubing and into the hot water line serving the ventilator.
NOTE: Some control cabinets are equipped with a low detergent switch. If so equipped, the green light will flash if the detergent tank is empty or if the detergent pump is malfunc­tioning and detergent is not pumping. The digital display reads "Low Detergent" and the text alternates from "Fill Tank" and "Check Pump". If the detergent tank is filled with water the detergent switch will activate as if there is no detergent.
Initial Operation
To prime and operate the pump for the first time, it is recom- mended that water be used instead of detergent to prevent detergent from spilling in case of leaks at the systems fittings.
Priming The Pump
The detergent pump is self-priming. Push the pump test switch, located on the junction box of the motor, and hold down until liquid climbs up the vinyl tubing and fills the pump head. The pump will be operating properly when both upper and lower poppet checks can be seen moving up and down slightly. If the pump does not self-prime, an air lock may have developed within the pump head and the following action should be taken:
1. Hold down pump test switch and loosen top cap slightly to allow air to be pushed out. Repeat as necessary until liquid climbs up tube and fills pump head.
Note: Do not overly tighten cap or damage to the pump head will occur.
2. If the pump still does not work properly, check the following:
A. Foot valve should be clean and immersed in the liquid.
B. Check all fittings to ensure an airtight system.
C. Poppet checks within the foot valve, pump head and brass check valve should be clean and operating freely.
D. Detergent lines should be free and clear.
PREVENTIVE MAINTENANCE
As with any piece of fine equipment, a reasonable amount of care must be taken to keep it in good working order:
1. Caution should be taken not to spill detergent on the exterior of the pump.
2. A periodic check should be made of all fittings to guarantee their tightness.
NOTE: The detergent pump motor has sealed bearings and will not require lubrication.
DETERGENT CONSUMPTION CHART
Control
Cabinet
Pipe Size
1 1/4"
& 1 1/2"
Factory
Cam
Setting
1/2" #1 3.2 9.6 2.1 16.0 3.5 28.8 6.3 3/4" #2 5.1 15.3 3.3 25.5 5.6 45.9 10.0
1" #3 6.0 18.0 3.9 30.0 6.6 54.0 11.8
Min.
#4 6.3 18.9 4.1 31.5 6.9 56.7 12.4
Oz. Per
(Impe ria l)
3 Minutes
Oz.
Gal.
Per
Per
Day
Mo.
Wash Cycle Length
5 Minutes 9 Minutes
Oz.
Gal.
Per
Per
Day
Mo.
Oz. Per
Day
Gal.
Per Mo.
DETERGENT FLOW
Detergent flow is initially factory set according to the pipe size of the control cabinet (refer to chart). Generally, the factory setting will be sufficient to provide adequate cleaning of the ventilator. However, adequate cleaning is dependent upon a number of factors:
1. Temperature of hot water 4. Wash cycle time
2. Water pressure 5. Frequency of wash cycle
3. Daily grease accumulation 6. Type of detergent
Depending upon these factors, it may be necessary to adjust the detergent flow. Adjustment may be accomplished by changing the cam to a different size. To change the cam:
1. Loosen Allen set screw on brass cam.
2. Remove cam and replace with next size as required.
3. Cam #1 minimum setting. Cam #4 maximum setting.
NOTE: Cams are available from Gaylord Industries or your Gaylord Certified Service Agency.
FIG. 8
15
DETERGENT FOR THE WASH SYSTEM
FORMULA G-510 is the only cleaner recommended by Gay­lord Industries for use in the washdown system of The Gaylord Ventilator. FORMULA G-510 is a concentrated colloid cleaner specially formulated to remove the daily accumulation of grease inside The Gaylord Ventilator without damaging the rubber and synthetic parts of the detergent pumping system. FORMULA G-510 is biodegradable, safe for kitchen person­nel, and has a variety of uses.
DILUTION OF FORMULA G-510 FOR VENTILATOR CLEANING Normal Cleaning
For ventilators covering cooking equipment such as broilers, griddles, fryers, or any other heavy grease producing equip­ment, fill the detergent tank with full strength FORMULA G-510.
Light-Duty Cleaning
For ventilators covering light grease producing equipment such as ovens, kettles, steamers and ranges, fill the detergent tank with a mixture of one part FORMULA G-510 to one part water.
Cleaning the Ventilator Exterior
Mix one part FORMULA G-510 to twenty parts water in hand spray bottle. Spray on and wipe off. NOTE: Once a day, this same solution should be used to clean the front of the fire damper and main grease extracting baffle.
FOR OTHER CLEANING JOBS
The colloidal action of FORMULA G-510 makes it a cleaner especially well-suited for use in kitchens. The colloids break up dirt and grease into millions of tiny particles that constantly repel each other. These particles cannot recombine or rede- posit on a surface and are, therefore, easily washed away. FORMULA G-510 is biodegradable and contains no harsh chemicals, yet offers outstanding performance on the tough- est cleaning jobs.
Use a mixture of one part FORMULA G-510 to twenty parts water for:
VINYL/PLASTIC/WALLS...Removes dirt, grease, food de- posits and fingerprints. REFRIGERATORS...Removes dirt, spilled milk, blood, mildew and objectionable odors. RESTROOMS...Add a disinfectant to clean all fixtures, walls, floors, etc.
Use a mixture of one part FORMULA G-510 to five parts water for extremely heavy grease build-up, such as on the floor and on equipment around deep-fryers. Spray on and rinse or wipe off. For extremely soiled areas, gentle agitation, followed by a soaking period, will result in more thorough cleaning.
DON’T be afraid to experiment with FORMULA G-510 because it contains no phosphates, nitrates, enzymes, sulfates, sul­fonates or silicates.
LIMITED WARRANTY
G-510 CHEMICAL DIVISION warrants that FOR­MULA G-510 will not cause cleansing agent damage to the rubber and synthetic parts of the injection pump (“O” rings, diaphragms, washers, tubing, and other such parts) used with The Gaylord Ventilator, Heat Reclaim Unit, or Pollution Control Equipment. G-510 CHEMICAL DIVISION’S obligation under this war­ranty and any warranties implied by law shall be limited to repairing or replacing, at its option, any of said parts which G-510 CHEMICAL DIVISION'S examination shall disclose to its satisfaction to have been damaged by the use of FORMULA G-510 for the life of the detergent pumping system. This warranty shall not cover damages caused by any other deter­gent. The use of any other detergent shall void this warranty.
All repairs and replacement parts under this warranty shall be F.O.B. G-510 CHEMICAL DIVISION’S fac- tory. The owner shall pay the necessary freight and delivery charges; also removal and installation costs. Any federal, state or local taxes are also extra. Requests for repairs or replacement parts should be made to 20/10 Products Inc., PO Box 7609, Salem, OR 97303.
This is the sole warranty with respect to FORMULA G-
510. G-510 CHEMICAL DIVISION MAKES NO OTHER WARRANTY OF ANY KIND WHATSOEVER, EX­PRESSED OR IMPLIED, AND ALL IMPLIED WAR­RANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH EXCEED THE AFORESAID OBLIGATION ARE HEREBY DIS­CLAIMED AND EXCLUDED FROM THIS AGREE­MENT. G-510 CHEMICAL DIVISION SHALL NOT BE RESPONSIBLE FOR INCIDENTAL OR CONSE­QUENTIAL DAMAGES RESULTING FROM A BREACH OF THIS WARRANTY.
IMPORTANT
If a cleansing agent other than FORMULA G-510 is used with The Gaylord Ventilator injection pump, it is recommended that a warranty similar to the above be obtained from the manufac­turer of said product.
For name and address of the nearest FORMULA G-510 distributor contact:
20/10 Products Inc. P.O. Box 7609 Salem, OR 97303 Phone: 800-286-2010 FAX: 503-363-4296 E-Mail: twentyten@juno.com
16
MODEL C-6000 SERIES COMMAND CENTER - INSTRUCTIONS
General Description:
The C-6000 Command Center is designed to start and stop the exhaust fan and wash up to 5 groups of ventilators in sequence with a delay period between each group. A sequence wash may be necessary if the building’s hot water system is not capable of supplying the required volume of water at one given time.
The exhaust fan and wash sequence may be started Manu- ally by pushing the “Start Fan” or “Start Wash” buttons, or may be programmed for Automatic operation.
3. Programming the length of the wash cycles and delay periods between the wash and rinse cycles. The maximum
length of a wash cycle is 9 minutes. The maximum length of the delay period is 99 minutes.
4. Skipping a day so the exhaust fan and wash cycle do not operate for holidays or specific days within a 7-day week when the kitchen is not operating.
Programmed operations may include:
1. Starting the exhaust fan once within a 24-hour period.
2. Stopping the exhaust fan and starting the wash cycle sequence once within a 24-hour period
START WASH
SPANI SH
MEN U EXI T EN TER
ESPAN OL
START
FAN
Part # 1 9764
The C-6000 Command Center provides information and pro­gramming for various functions by accessing nine different menu catagories. An overview of the nine menu items are as follows:
1. Service - Di splay s Gaylo rd's web site add ress: gaylordusa.com
2. Detergent - Displays Toll-Free Number to order detergent: 800-286-2010
3. Wash Length - Sets length of each wash cycle from 3 to 9 minutes
4. Delay Time (for sequence wash units only) - Sets delay between washes from 1 minute to 99 minutes
5. Set Clock - Day, hour and minutes
6. AutoMode [M or A] - Sets the C-6000 to Manual or Automatic modes. In Automatic mode, the C-6000 will start the Fan and Wash at the preset times that were set using the Set Wash Times option.
A = Automatic / M = Manual
Also allows individual days (Mon, Tues., etc.) to be set ON or OFF when Automatic mode is selected.
7. Set Wash Times - Sets Start Times for Automatic start of Fan and wash when C-6000 is set to Automatic mode.
8. Wash Test - Runs through a complete Wash Cycle with decresed times
Damper Closing Time = 10 sec. Wash Times = 10 sec. Water Heating Time = 10 sec. Exits menu when finished.
9. Number of Washes - Preset at factory and protected with a password. Allows the number of washes to be changed from 1 to 5 (S1 to S5).
FIGURE 9
C-6000 COMMAND CENTER
Using the Menu:
To Enter the Menu, press the MENU button [F4].
To navigate the Menu:
• Press [F1] to go to the Next menu item
• Press [F2] to go to the Previous menu item
• Press [F5], the EXIT button to exit the Menu
• Press [F6], the ENTER button to select a Menu item
17
MODEL C-6000 SERIES COMMAND CENTER - INSTRUCTIONS
1. Service
• Press [F6] [ENTER] to display Gaylord’s web site address: gaylordusa.com
• Press [F5] [EXIT] to return to the menu
2. Detergent
• Press [F6] [ENTER] to display the Phone Number to order Detergent: 800-286-2010
• Press [F5] [EXIT] to return to the menu
3. Wash Length
• Press [F6] [ENTER] to display the Length of Wash #1
• Press [F3] to Increase the Wash Time up to 9 Minutes (Maximum)
• Press [F4] to Decrease the Wash Time down to 3 Minutes (Minimum)
• Press [F1] to adjust the Length of Wash #2 (if applicable)
• Press [F5] [EXIT] to return to the menu
• Note: Press [F1] to advance through all washes (ex.) “-S2” has 2 washes)
4. Delay Time
• Press [F6] [ENTER] to display the Delay Time between washes (Not used if there is only one wash)
• Press [F3] to Increase the Delay Time up to 99 Minutes (Maximum)
• Press [F4] to Decrease the Delay Time down to 1 Minute (Minimum)
• Press [F5] [EXIT] to return to the menu
5. Set Clock
• Press [F6] [ENTER] to display the current Day of the Week (1=Sunday)
• Press [F3] to change to the next Day of the Week (1=Sun, 2=Mon, 3=Tues, etc.), keep pressing [F3] to cycle around if necessary
• Press [F1] to go to the current Hour
• Press [F3] to increase the Hour, keep pressing [F3] to cycle around if necessary
Press [F1] to go to the current Minute
Press [F3] to increase the Minute, keep pressing [F3] to cycle around if necessary
Press [F5] [EXIT] to return to the menu
6. AutoMode [A or M]
Used to select [M]anual or [A]utomatic mode. If [A] is displayed, the C-6000 is set to operate in Automatic mode. If [M] is displayed, the C-6000 is set to operate in Manual mode.
Press [F6] [ENTER] to display the “Set Mode” screen
• Press [F6] [ENTER] again to toggle between [M]anual or [A]utomatic mode
Setting Which Days of the Week to Run:
• Press [F1] to select which days to run the C-6000 in Automatic mode
• “Sun ON” or “Sun OFF” will display
• Press [F3] to set a day to “ON”. Set a day to “ON” in order for the C-6000 to run on that day
• Press [F4] to set a day to “OFF”. Set a day to “OFF” in order for the C-6000 NOT to run on that day
• Press [F1] to cycle through each day of the week [Sun – Sat.]
• Press [F5] [EXIT] to return to the menu
7. Set WashTimes
• Only used when C-6000 is set to Automatic mode
• Press [F6] [ENTER] to display the Start time for the Fan on Sunday (Sun. Fan)
• Press [F3] to increase the Hour
• Press [F4] to increase the Minutes
• Press [F1] to go to the Start time for the Wash on Sunday (Sun.Wash)
• Set the time, using the same method described above
• Press [F1] to cycle through for each day of the week, for the Start Times for the Fan and Wash
Press [F5] [EXIT] to return to the menu
8. Wash Test
Press [F6] [ENTER] to run the C-6000 through a complete Wash cycle with decreased times
After the Wash Test is complete, the C-6000 will return to the Fan Off mode
9. Number of Washes
Pressing [F6] [ENTER] will prompt for a password It is not necessary to change this value. It is preset at the Factory.
TIME CLOCK OPERATION
AutoMode is used to have C-6000 start the exhaust/supply fans automatically, once per day. The AutoMode also stops the fans and starts the wash cycle, once per day.
To use the AutoMode:
1. Set Wash Length(s) (Menu item #3)
Set length of each wash cycle, from 3 minutes to 9 minutes
2. Set Delay Time between washes, if control has more than one wash solenoid (Menu item #4)
Set amount of time to wait between washes, from 1 minute to 99 minutes
3. Set Clock (Menu item #5)
Please note that the clock is a 24-hour clock. Example: 1:00 PM = 13:00
Set the current day of the week. Example: 1 = Sun. 2 = Mon. 3 = Tues, etc.
4. Turn AutoMode ON (Menu item #6)
Pressing (F6) Enter will toggle between [A]utomatic and [M]anual modes
After it is set to [A]utomatic mode, set which days of the week the Exhaust/Supply Fan will run - setting a day to "ON" means the Exhaust/Supply Fan will start on that day, and the Wash will run.
Example: Sun ON
Mon OFF Tues ON
5. Set Wash Times, set start times for Fans & Wash (Menu item #7).
Set the time for the Fans to Start for each day of the week.
Example: Sun. Fan 5:00
Mon.Fan 5:00
Set the time for the Wash to Start for each day of the week.
Example: Sun.Wash 22:00
Mon.Wash 22:00
18
Loading...
+ 41 hidden pages