Galaxy Aqua 9000 XP Installation Instructions Manual

Page 1
IMPORTANT!
This Step-by-Step guide should be given to the customer
after installation and demonstration.
SERVICE POLICY
In the event of you needing to contact the Galaxy Customer Service Department, the following procedure should be followed:-
1
If a service call is booked, you or a representative must be present during the Engineers visit.
Before telephoning the Galaxy Customer Service Department you should ensure that you have the model number, power rating, serial number and date of purchase.
The Galaxy Customer Service Department will be able to inform you whether the fault can be rectified by the provision of a replacement part or an on site visit by a Qualified Service Engineer.
If the product is no longer covered by the Guarantee, a charge will be made for the site visit and for any parts supplied.
A charge will be made where a call under the terms of the guarantee has been booked and a failure was not product related, or an engineer arrives and is not able to gain access.
2
3
4
5
Pumped Instantaneous
Electric Shower
Installation Instructions
XP
Customer Service Department
Telephone: 0845 600 5111 Fax: 01489 773053
9.00 am - 5.00 pm Monday to Friday
Technical Hotline
Telephone: 0844 372 7766 Fax: 0844 372 7767
Email: technical-services@applied-energy.com
9.00 am - 5.00 pm Monday to Friday
SERVICE POLICY
In the event of you needing to contact the Galaxy Technical Hotline, the following procedure should be followed:-
1
If a service call is booked, you or a representative must be present during the Engineers visit.
Before telephoning the Galaxy Technical Hotline you should ensure that you have the model number, power rating, serial number and date of purchase.
The Galaxy Technical Hotline will be able to inform you whether the fault can be rectified by the provision of a replacement part or an on site visit by a Qualified Service Engineer.
If the product is no longer covered by the Guarantee, a charge will be made for the site visit and for any parts supplied.
A charge will be made where a call under the terms of the guarantee has been booked and a failure was not product related, or an engineer arrives and is not able to gain access.
2
3
4
5
7300059 (B)
Technical Hotline
Telephone: 0844 372 7766 Fax: 0844 372 7767
Email: technical.services@redringxpelair.com
8.00 am - 5.30 pm Monday to Friday
SERVICE POLICY
In the unlikely event of a product breakdown during the guarantee period you should contact our Service and Repair Helpline who will be able to assist with the repair and advise of the best course of action to be taken. Please DO NOT remove the product prior to making this call as this may invalidate your guarantee. Service Tel: 0844 372 7766 or email technical.services@redringxpelair.com
1
If a service call is booked, you or a representative must be present during the Engineers visit.
Before telephoning the Galaxy Technical Hotline you should ensure that you have the model number, power rating, serial number and date of purchase.
The Galaxy Technical Hotline will be able to inform you whether the fault can be rectified by the provision of a replacement part or an on site visit by a Qualified Service Engineer.
If the product is no longer covered by the Guarantee, a charge will be made for the site visit and for any parts supplied.
A charge will be made where a call under the terms of the guarantee has been booked and a failure was not product related, or an engineer arrives and is not able to gain access.
2
3
4
5
Page 2
690 mm
365 mm
252 mm
GUARANTEE
Redring Xpelair Group Ltd guarantee this Galaxy product for a period of two years, from date of purchase, against mechanical and electrical defects arising from faulty materials or from poor workmanship, providing the product has been installed by a competent person in accordance with the fitting instructions.
undertake to repair or replace, at their discretion, without charge, provided the product has been properly maintained and operated in accordance with the operating instructions. Any component found to be defective during this period, as the result of misuse or damage, or the effects of scaling, will not be covered by this guarantee (with the exception of ‘si’ (‘Scalemaster’) models which are guaranteed against the effects of scaling).
This product must not be modified, repaired or taken apart except by a person authorised by Redring Xpelair
.
This Guarantee is only valid within the United Kingdom and does not cover product used commercially.
This Guarantee does not affect your statutory rights.
Redring Xpelair Group Ltd
Group Ltd
Redring Xpelair Group Ltd.,
Newcombe Way, Peterborough,
Cambridgeshire PE2 6SE
Telephone: 01733 456789 -
Fax: 01733 310606 -
Website: www.galaxy-showers.com
2
11
Page 3
Products manufactured by Galaxy are safe and without risk provided they are installed, used and maintained in good working order in accordance with our instructions and recommendations.
DO NOT connect this shower directly to the mains water supply. DO NOT operate shower if frozen, or suspected of being frozen. It must thaw out before using. DO NOT operate the unit if the spray­ head or spray hose becomes damaged. DO NOT restrict flow out of the shower by placing sprayhead in direct contact with your body. DO NOT operate the shower if water ceases to flow during use or if water has entered inside the unit because of an incorrectly fitted cover.
WARNING: If re-starting the shower immediately after stopping, be aware that a slug of hot water will be expelled for the first few seconds.
GENERAL
1. Isolate the electrical and water supplies before
removing the cover.
2. Read all of these instructions and retain them for later use.
3. DO NOT take risks with plumbing or electrical equipment.
4. Isolate electrical and water supplies BEFORE proceeding with the installation.
5. The unit must be mounted onto the finished wall surface (on top of the tiles). DO NOT tile up to unit after fixing to wall.
6. Contact Customer Service (see back page), if any of the following occur; a) If it is intended to operate the shower at pressures above the maximum or below the minimum stated.
b) If the unit shows a distinct change in performance. c) If the shower is frozen.
7. If it is intended to operate the shower in areas of
hard water (above 200 ppm temporary Hardness), a scale inhibitor may have to be fitted.
8. The sprayplate and cartridge must be cleaned
regularly with descalent to remove scale and debris, otherwise restrictions to the flow on the outlet of the unit will result in higher temperatures and could also cause the Pressure Relief Device in unit to operate.
9. This product is not suitable for mounting into steam rooms or steam cubicles.
PLUMBING
1. The plumbing installation must comply with Water
Regulations, Building Regulations or any particular regulations as specified by Local Water Company or Water Undertakers and should be in accordance with BS 6700.
2. The supply pipe must be flushed to clear debris before connecting to shower unit.
3. DO NOT solder pipes or fittings within 300mm of shower, as heat transfer can damage components.
4. DO NOT fit any form of outlet flow control as the outlet acts as a vent for the heater can.
5. DO NOT use excessive force when making connections to the flexible hose or sprayhead, finger tightness is sufficient.
6. Al plumbing connections MUST be completed BEFORE making the electrical connections.
ELECTRICAL
1. The installation must comply with BS 7671
Requirements for electrical installations’ (IEE wiring regulations) or any particular regulations as specified by the local Electrical Supply Company.
2. This appliance MUST be earthed.
3. In accordance with ‘The Plugs and Sockets etc.
(Safety) Regulations 1994’, this appliance is intended to be permanently connected to the fixed wiring of the electrical mains system.
4. Ensure all electrical connections are tight to prevent overheating.
5. Fuses do not give personal protection against electric shock.
PACK CONTENTS
1
SECTION
PACKING CONTENTS
PACK CONTENTS
2
SECTION
PLEASE READ THIS IMPORTANT SAFETY INFORMATION
Shower Unit Showerhead Showerhead Key Flexible Hose Slider Rail Tube Slider Rail Brackets Slider Rail Showerhead Holder Soap Dish Hose Retaining Ring Screw Pack
18
SECTION
FILTER MAINTENANCE
INSTRUCTIONS for INSTALLERS and SERVICE ENGINEERS
It is recommended that the filter is periodically cleaned in order to maintain the performance of the shower. It is
essential that this operation is carried out by a competent person.
SWITCH OFF THE ELECTRICITY SUPPLY. There is no need to turn off the mains water supply when cleaning the filter.
Remove the cover and disconnect the plug.Turn off the water supply to the unit by rotating the lever on top of the filter service shut off valve (Fig.21) anti­clockwise a quarter turn.
Filter Service
Shut-Off
Valve
Do not rely on the filter service shut off valve when carrying out repairs or service to other areas of the shower unit.
Unscrew the three screws in filter cover (Fig.22) remove cover.Take out filter and wash under running water. Ensure all debris etc. is removed.
Replace filter. Replace cover ensuring all three screws line up. Replace the three screws. DO NOT OVERTIGHTEN.
Fig.21
Turn unit water supply back on by rotating the lever on top of the filter service shut off valve clockwise a quarter turn.
Before replacing the cover, it is strongly advised to prime the unit by opening the bleed screw until water drains from it.
Close the bleed screw and connect the plug to the cover. Replace the cover and secure with the fixing screws.
Switch on the electric supply and start the shower on the COLD SETTING ONLY and with the temperature control rotated fully anti-clockwise.
When a smooth flow of water is obtained, the shower can then be used in the Normal manner.
Filter Cover
Screws
ATTENTION!
NOTE: IN NORMAL USE, IT IS IN ORDER TO LEAVE THE WATER SUPPLY PERMANENTLY ON TO THE SHOWER UNIT, BUT AS WITH MOST
ELECTRICAL APPLIANCES, THE
UNIT MUST BE SWITCHED OFF AT THE ISOLATING SWITCH WHEN NOT IN USE.
Fig.12Fig.22
Page 4
6. To enhance electrical safety a 30mA residual current device (RCD) should be installed in all UK electric and pumped shower circuits. This may be part of the consumer unit or a separate unit.
7. Switch off immediately at isolating switch if water ceases to flow during use.
8. Other electrical equipment i.e. extractor fans, pumps must not be connected to the circuits within the unit.
9. Switch off at isolating switch when not in use. This is a safety procedure recommended with all electrical appliances.
10. As with all electrical appliances it is recommended to have the shower and installation checked at least every two years by a competent electrician to ensure there is no deterioration due to age and usage.
This book contains all the necessary fitting and operating instructions for your Galaxy Aqua 9000 XP pumped electric shower. Take time to read this book thoroughly and familiarise yourself with all instructions before commencing installation. Please keep it for future reference. The shower installation must be carried out by a competent person and in the sequence of this instruction book. Do not attempt any electrical or plumbing work necessary to install this product unless you have good practical experience and adequate understanding of the IEE regulations and water regulations Care taken during the installation will ensure a long, trouble-free life from your shower.
SPECIFICATIONS
3
SECTION
INTRODUCTION
Water
Inlet connection – 15mm diameter. Outlet connection – 1/2” BSP male thread.
Entry Points
Water and cable– bottom, top or back.
Materials
Backplate, cover, controls, sprayhead – ABS. Sprayplate – Acetal. Elements – Minerally insulated corrosion Resistant metal sheathing.
Dimensions ‘XP’
Height 365 mm Width 252 mm Depth 107 mm
Standards and Approvals
Splashproof rating IPX4. Complies with the requirements of current British and European safety standards for household and similar electrical appliances. Complies with requirements of the British Electrotechnical Approvals Board (BEAB). Meets with Compliance with European
Electrical
Nominal power rating at 240V
8.5kW - (40A MCB rating)
9.5kW – (40A MCB rating) Nominal power rating at 230V
8.5kW - (40A MCB rating)
9.5kW – (40A MCB rating)
The following points will help you understand how the shower operates: A. The electric heating elements operate at a constant rate at your chosen power setting. It is the flow rate of the water Passing through the heater unit which determines the shower temperature at any given setting. (The slower the flow the hotter the water becomes, and the faster The flow the cooler the water). B. During the Winter the Cold water supply will be cooler than in the Summer months. therefore, the temperature of the water
4
SECTION
ADVICE TO USERS
16
SECTION
ADJUSTING THE SPRAYHEAD
17
SECTION
SHOWERHEAD CLEANING INSTRUCTIONS
The showerhead should be cleaned periodically to remove limescale or debris which will reduce the performance of the shower. The frequency of cleaning will vary according to local water quality. In hard water areas cleaning will be needed more often than in soft water
IN SHOWER MAINTENANCE
To break away scale deposits on a daily basis simply rub your thumb over the rubber nipples whilst the shower is running.
Six sprayhead patterns are available. Ajustment is by turning the bezel on the sprayhead in either direction until the dersired pattern is obtained.
Tranquil
Single outer spray
Fresh
Single Inner spray
Excite
Single Centre spray
Allure
Outer & Inner combined spray.
Sensual
Outer & Centre combined spray.
Ecstasy
Centre & Inner combined spray.
5. Throughly clean and rinse the inside of the showerhead.
6. Replace the two black ‘O’ rings on the rear of the spray cartridge. A light smear of petroleum jelly will ensure an easy location into the grooves.
7. Refit cartridge to the showerhead and tighten with the spray key.
1. Engage the key into the spray cartridge recesses and turn anti-clockwise to unscrew.
2. Remove the two small black ‘O’ rings from the rear of the spray cartridge, and rinse ‘O’ rings clean.
4. Ensure all traces of limescale and limescale remover are rinsed off.
3. If deposits are stubborn, immerse and soak the spray cartridge for several hours in a proprietary limescale remover. Then with a small stiff bristled brush scrub the spray cartridge.
areas. A liquid non-abrasive bathroom cleaner may be used on external surfaces of the handset.
Page 5
will vary from season to season on any one setting of the temperature control, e.g. if you have chosen 'Medium' power for your preferred shower temperature in the Summer, you may have to increase that to 'Full' power during the Winter Months. C. If for any reason there is a sudden rise in water temperature, the Aqua 9000 XP has thermal cut-out devices built-in. D. Switch off immediately at the isolating switch if water ceases to flow. Contact Galaxy Customer Service for advice. If
ever the water becomes too hot and you cannot obtain cooler water, first check that the sprayplate in the sprayhead is not blocked.
DO NOT place items such as soap or Shampoo bottles on top of the unit. Liquid could seep through the joint between the cover and backplate, and possibly damage the sealing rubber.
Replacement parts can be ordered from Galaxy Customer Service..
Due to continuous improvement and Updating, specification may be altered Without prior notice.
5
SECTION
ELECTRICAL REQUIREMENTS
WARNING
THIS APPLIANCE MUST BE
EARTHED
The installation, supply cable and circuit protection must conform with IEE wiring regulations and be sufficient for the amperage required.
2. If you are installing a shower with a
kilowatt rating above 9kW, it is advisable to contact the local electricity supply company.
3. The electrical rating of the shower is shown on the rating label (Fig.1)
within the unit.
4. Before making any sort of electrical
connection within the installation, ensure that no terminal is live. If in any doubt, switch off the whole installation at the consumer unit.
5. The shower must be connected to its own independent electrical circuit. IT MUST NOT be connected to a ring main, spur, socket outlet, lighting circuit or cooker circuit.
6. The electrical supply must be adequate for the loading of the unit and existing circuits.
7. Check your consumer unit (main fuse box) has a main switch rating of 80A or above and that it has a spare fuse way which will take the fuse or mcb necessary for the shower.
8. If your consumer unit has a rating below 80A or if there is no spare fuse way, then the installation will not be straight forward and may require a New consumer unit serving the house or just the shower.
9. You will need to contact the local electricity company. They will check the circuit and carry out what is necessary. They will also check the main bonding.
10. The earth continuity conductor of the electrical installation must be effectively connected electrically to all exposed metal parts of other
MAX SUPPLY HEAD 10 METRES MIN SUPPLY HEAD 0.08 METRES RATING 20 MINS ON/60MINS OFF RATED PRESSURE 0.Pa THIS SHOWER UNIT WILL NOT EXCEED A FLOW RATE OF 20 LPM
GALAXY SHOWERS COVENTRY UK
REGISTERED DESIGN
Model: AQUA 9000XP
8.5KW 240V IPX4
SERIAL No: A9XP 70005
1 2 3 4 5 6 7 8 9 10 11 12
The following notes are for guidance only:
1. The shower must only be connected to a 230-240V ac supply.
Fig.1
‘High’ setting (Double Solid Red Symbol):
Is maximum power setting which Allows the highest flow achievable for your preferred temperature. Temperature adjustment at this setting is via the temperature control.
To adjust the shower temperature
The shower temperature is altered by increasing or decreasing the flow rate of the water through the shower via the temperature control (Fig.19b). After obtaining your preferred shower temperature, the number can be remembered as the normal setting and should only need to be altered to compensate for seasonal changes in ambient water temperatures.
NOTE: To decrease the shower
temperature.
Turn the temperature control anti­ clockwise towards the
To increase the shower temperature.
Turn the temperature control clockwise towards the higher numbers; this will decrease the water flow.
CAUTION: Be certain the showering temperature is satisfactory by testing with your hand before stepping under the sprayhead. There will always be a time delay of ten to fifteen seconds between selecting a flow rate and the water reaching the stable temperature for that flow rate.
It is recommended that persons who may have difficulty understanding or operating the shower controls should not be left unattended whilst showering. Special consideration should be given to young children and the less able bodied.
Power on indicator (Fig.20)
The Blue power neon will light when the start/stop button is pressed. This indicates that power is on to the pump and power Selector.
15
SECTION
OPERATING FUNCTIONS
Low water pressure cut-out
Should the water pressure fall below the minimum required to operate the shower, power will be switched off to the heating elements preventing any maintained temperature rises.
Overheat cut-out
During normal operation if an overheat temperature is sensed, power to the elements will be reduced. Water will continue to flow. When the temperature has cooled sufficiently, power to the elements will be automatically restored to the previous setting at the time of interruption.
Safety cut-out
The unit is fitted with a non re-settable over-temperature safety device. In the event of abnormal operation which could cause unsafe temperatures within the unit, the device will disconnect the heating elements. It will require a visit from a qualified engineer to determine the nature of the fault and replace the safety
Fig.20
Blue Power
Neon
Page 6
Twin and Earth PVC Insulated Cable
CURRENT CARRYING CAPACITY
Installed in an
Insulated
Wall
In Conduit or
Trucking
Clipped
Direct or
Buried in a
non Insulated
Wall
6mm2 6mm2 6mm2 32A 38A 46A
10mm2 10mm2 10mm2 43A 52A 63A
16mm2 16mm2 16mm2 57A 69A 85A
Note: Cable selection is dependent on de-rating factors
CIRCUIT PROTECTION
Unit
Rating
MCB
Cartridge
Fuse
7.0kW 30/32A 30A
7.5kW 32A 35A
8.0kW 40A 35A
8.5kW 40A 45A
9.0kW 40A 45A
9.5kW 40/45A 45A
10.5kW 45A 45A
appliances and services in the room in which the shower is to be installed, to conform to current IEE regulations.
11. All exposed metallic parts in the bathroom must be bonded together using a cable of at least 4mm2 cross sectional area. These parts include metal baths, radiators, water pipes, taps and waste fittings.
12. For close circuit protection DO NOT use a rewireable fuse. Instead use a suitably rated miniature circuit breaker (MCB) or cartridge fuse (See table A).
13. In the interest of electrical safety a 30mA residual current device (RCD) should be installed in all UK electric and pumped shower circuits.This may be part of the consumer unit or a separate unit.
14. A 45 amp double pole isolating switch with a minimum contact gap of 3mm in both poles must be incorporated in the circuit.
15. It must have a mechanical indicator showing when the switch is in the OFF position, and the wiring must be connected to the switch without the use of a plug or socket outlet.
16. The switch must be accessible and clearly identifiable, but out of reach of a person using a fixed bath or shower, except for the cord of a cord operated switch, and should be placed so that it is not possible to touch the switch body while standing in a bath or
shower cubicle. It should be readily accessible to switch off after using the shower.
17. Where shower cubicles are located in any rooms other than bathrooms, all socket outlets in those rooms must be Protected by a 30mA RCD.
18. The current carrying capacity of the cable must be at least that of the shower circuit protection (See table
B).
.19. To obtain full advantage of the power
provided by the shower, use the shortest cable route possible from the consumer unit to the shower.
20. It is also necessary to satisfy the disconnection time and thermal constraints which mean that for any given combination of current demand, voltage drop and cable size, there is a maximum permissible circuit length.
21. The shower circuit should be separated from other circuits by at least twice the diameter of the cable or conduit.
22. The current rating will be reduced if the cabling is bunched with others, surrounded by thermal loft or wall insulation or placed in areas where the ambient temperature is above 30°C. Under these conditions, de-rating factors apply and it is necessary to
Tabel ‘A’
Tabel ‘B’
1. To start the shower
Pressing the start/stop button (Fig.19) switches on the pump allowing water to immediately flow through the unit.
2. To stop the shower
Press the start/stop button. This initiate the Phased (Safety) Shutdown feature. The Phased (Safety) Shutdown feature lasts for approx 8 seconds, during which, the indicator light will flash ON & OFF, the flow of water will be reduced and the power to the heating elements cut. This allows the unit to safely flush out any residual heat. After which the pump switches off and the water flow will cease .
WARNING: If re-starting immediately after stopping, be aware that a slug of HOT water will be expelled for the first few seconds.
3. To use the power selector
The power selector (Fig.19a) has four settings – Cold, Low, Medium and Full power.
‘Cold’ setting (Solid Blue Symbol): Is Cold water only. Adjustment at
the temperature control at this setting will only increase or decrease the force of the water from the sprayhead. It will not alter
The water temperature.
‘Low’ setting (Outline Red Symbol): Is the low setting for extra economy
during hot months. Temperature adjustment at this setting is via the temperature control.
‘Medium’ setting (Solid Red Symbol): Is the medium setting for economy
during warmer months and any temperature adjustment at this setting is via the temperature Control.:
Fig.19
Start/Stop Button
Power Selector
Temperature Control
Fig.19b
COOLER WARMER
COLD
HIGH
MEDIUM
Fig.19a
LOW
Page 7
The installation must be in accordance with Water Regulations / Byelaws.
WARNING: Under no circumstances must this Aqua 9000 XP pumped shower be connected directly to the mains water supply.
To ensure activation of the heating elements, the shower must be connected to a Cold water supply which is gravity fed from a static Cold water storage cistern with a minimum capacity of 114 litres (25 galls).
There must be a maximum head of water of 10 metres (33ft) and a minimum head of 8 cm (3") as measured between the Bottom of the cistern and the top of the shower unit. There must be no other Cold water draw offs between the cistern and the unit and the pipe must not supply water to any other tap or fitting at a lower level.
NOTE: The supply pipe from the cistern should be on the opposite side to the float operated valve to prevent air being drawn into the pipe when the cistern is filling.
If it is intended to operate the shower in hard water areas (above 200 ppm
select a larger cable size.
23. In the majority of installations, the cable will unavoidably be placed in one or more of the above conditions. This being so, it is strongly recommended to use a minimum of 10mm cabling throughout the shower installation.
24. In any event, it is essential that
Individual site conditions are assessed by a competent electrician in order to Determine
6
SECTION
WATER REQUIREMENTS
temporary hardness) a scale inhibitor should be fitted.
Fig.2 shows a typical system layout. Do not use jointing compounds on any pipe fittings for the installation.
WARNING: The shower must not be positioned where it will be subjected to freezing conditions.
FOR EASE OF SERVICING, THE UNIT MUST ALWAYS BE MOUNTED ON THE SURFACE OF TILED WALLS. NEVER TILE UP TO THE UNIT.
Refer to Fig.3 for correct siting of the shower. This product is splash-proof rated and is approved for use in shower cubicles and over baths. However, do not install the unit in a Position where the sprayhead will consistently direct water over it.
The shower unit MUST be positioned vertically.
7
SECTION
SITING OF THE SHOWER
Fig.2
CAUTION
Check there are no hidden cables or pipes before drilling holes for wall plugs. Exercise great care when using power tools near water. The use of a residual current device (RCD) is recommended.
4. The crimped end of the riser rail. NOTE If it is necessary to
shorten the rail, use a junior hacksaw to cut the excess material from the plain end of the rail.
1. Establish position for the riser rail, and mark the wall for the lower mounting bracket. Make allowances for the tallest person likely to use the shower regularly.
2. Use a No 10/5.5mm masonry drill to make a hole 35mm deep, and fit the wall plug. (NB some
wall constructions may require the use of alternative types of wall fixings). Screw the lower bracket
base to the wall.
3. Locate the crimped end of the riser rail (Figure 4) into the mounting bracket, then fit the upper bracket. Ensure the rail is vertical, then mark the wall for the fixing.
5. The three components that comprise the Handset Height Adjuster assembly are produced with alphabetical ‘A’s and ‘B’s moulded into the end section of each part. Simply just match the letter identification of each part with the central piece i.e. ‘A’ to ‘A’ and ‘B’ to ‘B’ for correct assembly.
6. With the showerhead height adjuster lever set a 3 o’clock and the showerhead holder in the upright position, slide the assembly onto the rail. Tighten to the rail by turning the lever.
14
SECTION
OPERATING THE SHOWER
8. Re-assemble the rail and
screw the upper mounting bracket in place.
7. To lock the Handset Height Adjuster at your chosen position on the rail. Turn the lever up right. This action is also used for holding the showerhead at the angle required.
Maintenance:
Clean regularly with a non-abrasive liquid bathroom cleaner.
9. Slide the end cap onto the mounting brackets.
10. Snap the soap dish onto the rail below the holder assembly.
11. Slide soap dish down the rail to required position.
12. Firmly attach flexible hose to the showerhead making sure sealing washer is in place.
NOTE the adjustable slider grips the conical end of the hose, not the handle of the showerhead.
IMPORTANT: Ensure the commissioning procedure has been carried out.
Page 8
operates, then water will eject from the bottom of the unit. Should this happen, turn off the electricity and water supplies to the shower at the isolating switch and stopvalve. Contact Customer Service for advice on replacing the PRD. The PRD is situated adjacent to the outlet pipe (Fig.4). To gain access to it, FIRST SWITCH OFF THE ELECTRICITY SUPPLY, remove the cover, then unscrew using suitable wrench or grips.
CAUTION: Do not attempt to replace the PRD unless competent to do so.
NOTE: Before replacing the cover, it is strongly advised to prime the unit (see ‘commissioning’).
Allow sufficient room between the ceiling and the shower to access the cover top screws.
8
SECTION
PRESSURE RELIEF SAFETY DEVICE
A pressure relief device (PRD) is designed into the shower unit which complies with European standards. The PRD provides a level of appliance protection should an excessive build up of pressure occur within the shower.
DO NOT operate the shower with a damaged or kinked shower hose, or a blocked sprayhead which can cause the PRD to operate.
When commissioning, the sprayhead must be removed from the flexible hose. Failure to follow this procedure may also result in causing the PRD to operate. Ensure the shower is positioned over a bath or shower tray because if the PRD
PRD
9
SECTION
FITTING THE SHOWER TO THE WALL
NOTE: The control knobs are an integral part of the cover – do not attempt to remove them.
IMPORTANT: The unit must be mounted on a flat surface which covers the full width and length of the backplate. It is important that the wall surface is flat otherwise difficulty may be encountered when fitting the cover and subsequent operation of the unit may be impaired.
Fig.3
Fig.4
‘COLD' position and the temperature control is at ‘TEMPERATURE’.
Replace the cover squarely to the backplate and guide into position so that the controls locate correctly into the spindles while at the same time, ensuring wires are not trapped. Should any difficulty arise, re-check the points above
Secure the cover in position with the four retaining screws. DO NOT
OVERTIGHTEN..
Fig.12Fig.18
Fig.17
Fig.16
Switch on the mains electric supply to the shower at the isolating switch.
Press the ‘START/STOP’ button (Fig.17). The power indicator will light and the pump starts to operate.
It will take approximately thirty seconds for a smooth flow of water to be obtained whilst air and any debris is being dispersed from the shower. When a smooth flow of water is obtained, rotate the temperature control from ‘1’ to ‘10’ several times (Fig.18) to release any trapped air within the unit.
Once flushing out has been completed, stop the water flow by pressing the ‘start/stop’ button.
Because the shower is fitted with Phased (Safety) Shutdown, the indicator light will begin flash and water flow will be reduced for approx 8 seconds before the shower switches off. During this Phased (Safety) Shutdown, power to the heating elements is cut. This allows the unit to safely disipate any residual heat.
Commissioning is complete. Once the riser rail is fitted, the shower is ready for
13
SECTION
RISER RAIL & SOAP DISH FITTING INSTRUCTIONS
TIPS
A piece of insulating or masking tape applied to the wall before marking out the fixing holes will help stop the drill from wandering, particularly on tiled surfaces. When working near a basin or bath, insert the plug in the waste fitting so that small parts cannot be lost. Take care not to drop accessories or tools into basin or bath.
Page 9
Unscrew the two top and bottom retaining screws (Fig.5) and lift the cover from the backplate. NOTE: Deviations from the designated entry points will invalidate product approvals.
required for the Cold water pipe, then a aperture will need to be cut out of the cover (Fig.7) and the inlet elbow rotated to face downward.
If entry is required from the back, rotate the inlet elbow upwards and fit elbow to connect to the pipe (Fig.8). Ensure the hole in which the pipe enters through the wall is filled in completely in order to
Fig.5
Fig.6
If a top entry is required for the water pipe, remove the blanking plug in the backplate (Fig.6) and ensure the inlet elbow so that It points upward. If a bottom entry is
Fig.7
Bottom Entry
Aperture
‘Cut-Out’
W ALL
87 mm
28.5 mm
19 mm
Fig.8
prevent any possible ingress of water into the cavity area. After choosing the site for the shower, use the supplied template and mark the three fixing holes (Fig.9). Drill and plug to suit the fixing screws supplied.
(The wallplugs provided are suitable for most brick walls – use an appropriate masonry drill, but if the wall is plasterboard or a soft building block, you must use special wallplugs and an appropriate drill obtainable from most hardware stores).
Fig.15
Spindle in
COLD
position
Flat
Fig.12Fig.14
Element(s) to burn out and invalidate the guarantee.
The first operation of the shower is intended to flush out any remaining unit debris, and to ensure the heater unit contains water before the elements are switched on.
This operation must be carried out with the flexible hose (supplied) screwed to the outlet but without the sprayhead attached. Ensure the outlet of the flexible hose is directed to waste and ensure the end of the hose is below the shower unit.
To ensure the temperature control is correctly positioned on the stabilising valve, temporarily place the cover in position so that the splines engage then rotate the temperature control knob fully Anti-clockwise.
Remove the cover and position the temperature control so that it points towards ‘TEMPERATURE’ (Fig.13). Position the power selector to the 'COLD' position (Fig.12).
Ensure power selector is in Cold position (Fig.14) before continuing.
Ensure the water supply is still turned on to the shower.
Open the bleed screw adjacent the rubber hose (Fig.15) by rotating anti-clockwise slowly until water flows from the drain pipe, this indicates that any trapped air is vented and that the pump unit is primed. The bleed valve must now be closed by rotating clockwise. DO NOT
OVERTIGTHEN.
Attach to the stop/start switch inside the cover is a power lead. The socket on the end of this lead must be connected to the plug that is situated near the top of the backplate unit (Fig.16). NOTE: The plug and socket can only fit one way.
Offer the cover to the backplate unit. Ensure the power selector is still at the
Bleed Screw
(’XP’ Model)
Fig.13
Fig.12
Page 10
Screw the two upper fixing screws into position leaving the base of the screw heads protruding 6mm (0.25in) out from the wall. Hook the backplate over the top screws and fit the lower fixing screw into position. DO NOT fully tighten the screws at this stage, as the fixing holes are elongated to allow for out of square adjustment after the plumbing connections have been completed.
10
SECTION
PLUMBING CONNECTIONS
PLUMBING TO PRECEDE WIRING
WARNING: The outlet of the shower acts as a vent and must not be connected to anything other than the hose and sprayhead supplied.
GALAXY ‘AQUA 9000 XP’
FIXING TEMPLATE
V E R TI C AL C
EN T
R E L
I
N E
HORIZONTAL CENTRE LINE
Fig.9
DO NOT use jointing compounds on
any pipe fittings for the installation. DO NOT use soldered fittings within the vicinity of the shower unit. NOTE: An additional gate valve or fullway lever valve must be fitted in the water supply to the shower as an independent means of isolating the water supply should maintenance or servicing be necessary.
IMPORTANT: The fitting on the inlet elbow is a push-in type. The pipework must be cut with a pipe cutter and all burrs and rough edges removed from the end of the tube. The fitting can be used with copper and plastic pipe. If using chrome plated copper pipe, remove the first 25mm of plating completely from the connecting surface. If it is not completely removed then the collet will not grip the pipe and under pressure the pipe may be forced out.
CONNECTION PROCEDURE: Turn off water supply either at the mains stopvalve or the isolating stopvalve to the cistern. Drain the cistern.
IMPORTANT: The pipework must be brought direct from the Cold water storage cistern with no other Cold water draw offs between the shower and the cistern.
IMPORTANT: Before completing the connection of the water supply to the inlet of the shower, flush out the pipework to remove all swarf and system debris. This can be achieved by connecting a hose to the pipework and turning on the water supply long enough to clear the debris to waste.
Fit the pipework to the inlet elbow. Ensure the elbow collet is fully engaged with the pipe. Although the pipework connection to the shower is via 15mm diameter pipework, on long runs use 22mm diameter piping as far as possible to avoid restricting the flow to the shower.
Ensure that the backplate of the unit is flat on the wall and positioned squarely. Tighten the fixing screws.
Turn on the water supply and check for leaks in the pipework connection to the shower. NOTE: At this stage no water can flow through the unit.
11
SECTION
ELECTRICAL CONNECTIONS
SWITCH OFF THE ELECTRICITY SUPPLY
The cable entry points are shown in
(Fig. 10).
The cable can be surface clipped, hidden Or via 20mm conduit. NOTE: Metal conduit entry can only be from rear.
Route the cable into the shower unit and connect to the terminal block (Fig. 11) As Follows:-
Earth cable to terminal marked ......
Neutral cable to terminal marked ...N
Live cable to terminal marked.........L
E
IMPORTANT: Fully tighten the terminal block screws and ensure that no cable insulation is trapped under the screws. Loose connections can result in cable Overheating..
Fig.11
NOTE: The supply cable earth conductor must be sleeved. The outer sheath of the supply cable must be stripped back to the minimum. The supply cable must be secured either by routing through conduit or in trunking or by embedding in the wall, in accordance with current IEE regulations.
The use of connections within the unit, or other points in the shower circuit, to supply power to other equipment i.e. extractor fans, pumps etc. will invalidate the guarantee.
DO NOT switch on the electricity supply until the cover has been fitted.
Fig.10
12
SECTION
COMMISSIONING
DO NOT switch on the electricity supply until the following procedure has been completed and the cover has been fitted. Failure to do so could Cause the pump to run dry and invalidate the guarantee.
Cold position must be selected on power selector (Fig.14) Before carrying out any of the steps below. Failure to
do so WILL cause the heating
Loading...