Fujitsu UTP-VX60A, UTP-VX30A, UTP-VX90A, UTY-VDGX Installation Manual

PART NO. 9381279005
[Original instructions]
INSTALLATION MANUAL
DX-kit
For authorized service personnel only.
UTY-VDGX UTP-VX30A UTP-VX60A UTP-VX90A
En-1
1. SAFETY PRECAUTIONS
• Be sure to read this Manual thoroughly before installation.
• The warnings and precautions indicated in this Manual contain important information per­taining to your safety. Be sure to observe them.
• Hand this Manual, to the customer. Request the customer to keep them on hand for future use, such as for relocating or repairing the unit.
• For installation of the air handling unit (heat exchanger), refer to the installation manual for the air handling unit.
WARNING
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user.
Request your dealer or a professional installer to install the DX-kit in accordance with this Installation Manual. An improperly installed unit can cause serious accidents such as water leakage, electric shock, or fi re. If the DX-kit is installed in disregard of the instructions in the Installation Manual, it will void the manufacturer’s warranty.
Do not turn ON the power until all work has been completed. Turning ON the power before the work is completed can cause serious accidents such as electric shock or re.
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with a fl ame, it produces a toxic gas.
Installation work must be performed in accordance with national wiring standards by authorized personnel only.
Except for EMERGENCY, never turn off main as well as sub breaker of the DX-kits during operation. It will cause compressor failure as well as water leakage. First, stop the DX-kit by operating the control unit, converter or external input device and then cut the breaker. Make sure to operate through the control unit, converter or external input device. When the breaker is designed, locate it at a place where the users cannot start and stop in the daily work.
CAUTION
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property.
Read carefully all security information before use or install the DX-kit.
Do not attempt to install the DX-kit or a part of the DX-kit by yourself.
This unit must be installed by qualified personnel with a capacity certificate for handling refrigerant fluids. Refer to regulation and laws in use on installation place.
Th
e installation must be carried out in compliance with regulations in force
in the place
of installation and the installation instructions of the manufacturer.
This unit is part of a set constituting the DX-kit. It must not be installed alone or with non­authorized by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all wires with a distance between contact of 3mm for this unit.
The unit must be correctly earthed (grounded) and the supply line must be equipped with a differential breaker in order to protect the persons.
The units are not explosion proof and therefore should not be installed in explosive atmosphere.
Never touch electrical components immediately after the power supply has been turned off. Electric shock may occur. After turning off the power, always wait 5 minutes before touching electrical components.
This unit contains no user-serviceable parts. Always consult authorized service personnel to repairs.
When moving, consult authorized service personnel for disconnection and installation of the unit.
2. ABOUT THIS PRODUCT
2.1. Precautions for using R410A refrigerant
WARNING
Do not introduce any substance other than the prescribed refrigerant into the refrigeration cycle. If air enters the refrigeration cycle, the pressure in the refrigeration cycle will become abnormally high and cause the piping to rupture.
If there is a refrigerant leak, make sure that it does not exceed the concentration limit. If a refrigerant leak exceeds the concentration limit, it can lead to accidents such as oxygen starvation.
Do not touch refrigerant that has leaked from the refrigerant pipe connections or other area. Touching the refrigerant directly can cause frostbite.
If a refrigerant leak occurs during operation, immediately vacate the premises and thoroughly ventilate the area. If the refrigerant comes in contact with a flame, it produces a toxic gas.
2.2. Special tool for R410A
WARNING
To install a unit that uses R410A refrigerant, use dedicated tools and piping materials that have been manufactured specifically for R410A use. Because the pressure of R410A refrigerant is approximately 1.6 times higher than the R22, failure to use dedicated piping material or improper installation can cause rupture or injury. Furthermore, it can cause serious accidents such as water leakage, electric shock, or re.
Tool name Changes
Gauge manifold
The pressure in the refrigerant system is extremely high and cannot be measured with a conventional gauge. To prevent erroneous mixing of other refrigerants, the diameter of each port has been changed. It is recommended to use a gauge manifold with a high pressure display range of –0.1 to 5.3 MPa and a low pressure display range of –0.1 to 3.8 MPa.
Charging hose
To increase pressure resistance, the hose material and base size were changed. (The charging port thread diameter for R410A is 1/2 UNF 20 threads per inch.)
Vacuum pump
A conventional vacuum pump can be used by installing a vacuum pump adapter. Be sure that the pump oil does not backflow into the system. Use one capable for vacuum suction of –100.7 kPa (5 Torr, –755 mmHg).
Gas leakage detector
Special gas leakage detector for R410A refrigerant.
INSTALLATION MANUAL
PART NO. 9381279005
VRF system DX-kit
Contents
1. SAFETY PRECAUTIONS .........................................................................................1
2. ABOUT THIS PRODUCT .......................................................................................... 1
2.1. Precautions for using R410A refrigerant ............................................................1
2.2. Special tool for R410A ........................................................................................ 1
2.3. Accessories ........................................................................................................2
2.4. Optional parts .....................................................................................................3
3. PRODUCT SELECTION ...........................................................................................3
3.1. Product Lineup ...................................................................................................3
3.2. System Design ...................................................................................................3
4. INSTALLATION WORK ............................................................................................4
4.1. Selecting an installation location ........................................................................4
4.2. Installation dimensions .......................................................................................4
4.3. Installing the unit .................................................................................................4
5. PIPE INSTALLATION ............................................................................................... 6
5.1. Selecting the pipe material .................................................................................6
5.2. Pipe requirement ................................................................................................6
5.3. Bending pipes ..................................................................................................... 6
5.4. Pipe connection ..................................................................................................6
5.5. Installing heat insulation .....................................................................................7
6. MOUNTING THERMISTORS ....................................................................................7
7. ELECTRICAL WIRING..............................................................................................7
7.1. Electrical requirement ......................................................................................... 8
7.2. Wiring method ....................................................................................................8
7.3. Unit wiring ........................................................................................................... 8
7.4. Connection of wiring .........................................................................................10
7.5. External input and external output (Optional parts) ..........................................12
8. FIELD SETTING ......................................................................................................15
8.1. Setting the address ...........................................................................................15
8.2. Dip switch setting .............................................................................................. 16
8.3. Function setting ................................................................................................16
9. TEST RUN ...............................................................................................................17
9.1. Test run using Outdoor unit (PCB) ...................................................................17
9.2. Test run using remote controller ....................................................................... 17
10. CHECK LIST (Example) ......................................................................................... 17
11. ERROR CODES ...................................................................................................... 17
12. OPERATIONS .........................................................................................................18
12.1. Analog external inputs ....................................................................................18
En-2
2.3. Accessories
WARNING
For installation purposes, be sure to use the parts supplied by the manufacturer or other prescribed parts. The use of non-prescribed parts can cause serious accidents such as the unit falling, water leakage, electric shock, or fi re.
The following installation parts are furnished. Use them as required.
Keep the Installation Manual in a safe place and do not discard any other accessories until the installation work has been completed.
(1) Control unit Accessories
Name and Shape Q’ty Application
Installation Manual
1
(This book)
Key
2
For the door of control unit
Sealing washer
3
For mounting the control unit to the wall Waterproof specifications
Nuts (M8)
3
For mounting the control unit to the wall
Cable ties (with stopper)
19
For securing the cables
Cable gland (M10)
4
For cable holes
Cable gland (M16)
5
For cable holes
Cable gland (M20)
1
For cable holes
Blind bar
5
For mounting when not passing the cable through the cable gland
Cable tie
3
For securing the optional remote controller cable
Screw (M4×L6 mm)
3
For mounting the optional remote controller
Cable tie mount
2
For securing the optional remote controller cable
Thermistor (Inlet air and Outlet air)
2
For measuring the room temperature
Thermistor (Label: GAS)
1
For measuring the gas pipe temperature (For gas pipes)
Thermistor (Label: LIQ)
1
For measuring the liquid pipe temperature (For liquid pipes)
Thermistor holder pipe (Small)
1
For mounting the thermistor
Thermistor holder pipe (Large)
1
For mounting the thermistor
Name and Shape Q’ty Application
Thermistor spring (For small thermistor holder pipe)
1
For mounting the thermistor
Thermistor spring (For large thermistor holder pipe)
1
For mounting the thermistor
Template
1
For installing the control unit
Connection cable 1 [Label : 32,33,35,37,39,41]
1
For external output
Connection cable 2
[Label : 32,34]
1
For external output
Connection cable 3
[Label : 34,36]
1
For external output
Connection cable 4
[Label : 36,38]
1
For external output
Connection cable 5
[Label : 38,40]
1
For external output
(2) EEV unit Accessories
Name and Shape Q’ty Application
Installation Manual
1
Secure fitting
4
For mounting the EEV unit to the wall, or stacking multiple EEV units
Tapping Screw L (M4×L16)
8
For mounting the EEV unit to the wall
Tapping Screw S (M4×L10)
8
For stacking multiple EEV unit
Rubber sheet
2
For mounting pipe joints
Pipe heat insulations
2
For mounting pipe joints
cable tie (Large)
4
For securing heat insulations
cable tie (Medium)
1
For securing cables
Seal
2
For pasting unused piping holes
En-3
2.4. Optional parts
The following options are available. When installing, refer to the installation manual of each optional part.
Connectable Peripheral Devices
Model Name Notes
Wired Remote Controller UTY-RNKY *1, *2
Wired Remote Controller UTY-RNRY *1, *2
Wireless Remote Controller (IR receiver unit)
UTY-LNHY (UTB-YWC)
*2
Group Remote Controller (via network converter)
UTY-CGGY (UTY-VGGXZ1)
*2
Touch Panel Controller UTY-DTGY *2
Central Remote Controller UTY-DCGY *2
Network Convertor for LONWORKS® UTY-VLGX *2
BACnet® Gateway UTY-ABGX *2
System Controller UTY-APGX *2
System Controller Lite UTY-ALGX *2
Service Tool UTY-ASGX *2
Web Monitoring Tool UTY-AMGX *2
Separation Tube (For EEV unit 2 connections) UTP-LX180A
*1 Remote controller groups cannot be connected using DX-kits or other indoor units. *2 If controlling using “external input and output” analog inputs from an external controller
(DDC), operations from the controllers described above are disabled.
3. PRODUCT SELECTION
• Failure to observe the selection conditions described below will affect the outdoor unit service life and operational reliability.
• When selecting air handling unit, it must be designed for R410A refrigeration.
3.1. Product Lineup
(1) Product Lineup
Unit Name Model Name Environment specifi cations
Control unit UTY-VDGX
• Temperature:
-20 to 46 °C
• Humidity: 10 to 90% RH (No condensation)
EEV unit
UTP-VX30A
UTP-VX60A
UTP-VX90A
(2) EEV unit Selection
• The EEV unit is selected according to the capacity class conditions.
• If the capacity class is 40 kW or 50 kW, 2 EEV units are connected (in parallel).
Capacity Class (kW) 5.0 6.3 8.0 10.0 12.5 EEV unit model No.
30 30 30 60 60
Cooling capacity (kW)
5.6
6.3 8 10 12.5
Heating capacity (kW)
6.3
7.1 9 11.2 14
Heat exchanger capacity
Refer to the Design &Technical manual.
Airfl ow rate (Reference) (m3/h)
1,060
1,200 1,520 1,600 2,000
Capacity range Cool (kW) 5.1~5.9 6.0~7.1 7.2~9.0 9.1~11.1
11.2~13.2
Heat (kW) 5.7~6.7 6.8~8.0 8.1~10.0
10.1~12.4 12.5~15.0 Evaporation temperature Refer to the Design &Technical manual. Condensation temperature Refer to the Design &Technical manual.
Capacity Class (kW) 14.0 20.0 25.0 40.0 50.0 EEV unit model No.
60 90 90 90+90 90+90
Cooling capacity (kW)
14
22.4 25 40 50.4
Heating capacity (kW)
16
25 28 45 56.5
Heat exchanger capacity
Refer to the Design &Technical manual.
Airfl ow rate (Reference) (m
3
/h)
2,240
3,560 4,000 6,400 8,000
Capacity range Cool (kW)
13.3~18.0 18.1~23.7 23.8~28.0 28.1~44.7 44.8~50.4
Heat (kW)
15.1~20.0 20.1~26.5 26.6~31.5 31.6~49.9 50.0~56.5 Evaporation temperature Refer to the Design &Technical manual. Condensation temperature Refer to the Design &Technical manual.
Pipe size
(b)
(a)
(c)
(c)
(b)
(b)
(c)
(a)
(c)
(b)
Heat
Exchanger
Heat
Exchanger
Gas pipe Gas pipe
Liquid pipe
Liquid pipe
EEV
unit
EEV
unit
Capacity Class (kW) 5.0 6.3 8.0 10.0 12.5 Pipe size Gas (a) (mm) 15.88 15.88 15.88 15.88 19.05
Liquid (b) (mm) 9.52 9.52 9.52 9.52 9.52 Liquid (c) (mm) ————
Capacity Class (kW) 14.0 20.0 25.0 40.0 50.0 Pipe size Gas (a) (mm) 19.05 22.2 22.2 28.58 28.58
Liquid (b) (mm) 9.52 12.7 12.7 12.7 15.88 Liquid (c) (mm) 12.7 12.7
Pipe length
(a)
(d)
(c)
(f)
(e)
(b)
Heat
Exchanger
Heat
Exchanger
Gas pipe Gas pipe
Liquid pipe
(a) 5 m (b) 2 m , (c) 2 m , (d) 2 m , (e) 2 m
(d) + (f) 5 m , (e) + (f) 5 m
Liquid pipe
EEV
unit
EEV
unit
3.2. System Design
3.2.1. Basic Refrigerating System Confi guration
Using the DX-kit enables indoor units manufactured by other than Fujitsu general to be used in the Fujitsu general refrigerant system.
DX-kit*
Outdoor unit
Indoor unit
Indoor unit Indoor unit
* DX-kit = Control unit + EEV unit
3.2.2. Basic DX-kit System Confi guration
(1) System Pattern 1
External controllers (DDC) not manufactured by Fujitsu general control the Fujitsu general outdoor units and indoor units (refrigerant cycle devices, etc.) not manufactured by Fujitsu general. With this system, control using a Fujitsu general VRF controller is not possible.
System Confi guration Diagram
Fujitsu general-approved devices
Outdoor unit
Indoor unit
Control unit
Liquid pipe
Gas pipe
Thermistor × 4
Wired remote controller
External controller not manufactured by Fujitsu general
Control line
Piping
Wiring
EEV unit
For control line details, see “External Input and External Output”.
En-4
If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
Take precautions to prevent the unit from falling.
(1) Install the DX-kit on a place having a suffi cient strength so that it withstands against
the weight of the DX-kit. (2) Leave the space required to service the DX-kit. (3) Install the unit where connection to the outdoor unit (or RB unit) is easy. (4) Install the unit where the connection pipe can be easily installed. (5) Install the unit where noise and vibrations are not amplifi ed. (6) Take servicing, etc., into consideration and leave the spaces. (7) Do not install the unit where it will be exposed to direct sunlight.
4.2. Installation dimensions
4.2.1. Control unit
400 120 134
306
3 × Ø10
(Unit: mm)
400
251
Weight of the Control unit (kg)
UTY-VDGX 10
4.2.2. EEV unit
EEV unit Dimensions
221
203
159
4 × Ø11
8 × Ø5
22 31
90
58
58(120)(127)
168
212.4(104)
29.2
182
14
22.2
(78)
231
A
B
36
(Unit: mm)
Connection pipe diameter (mm)
Model A B Weight of the EEV unit (kg)
UTP-VX30A 9.52 9.52 UTP-VX30A 2
UTP-VX60A 9.52 9.52 UTP-VX60A 2
UTP-VX90A 12.7 12.7 UTP-VX90A 2
4.3. Installing the unit
WARNING
Install the DX-kit in a location which can withstand a load of at least 5 times the weight of the main unit and which will not amplify sound or vibration. If the installation location is not strong enough, the DX-kit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that the unit will come loose. Please take care.
Carrying in and installation of the unit should be performed by a suffi cient number of people and with suffi cient equipment that is adequate for the weight of the unit. Performing such work by an insufficient number of people or with inadequate equipment could result in dropping of the unit or personal injury.
(2) Pattern 2
Fujitsu general remote controllers and control devices directly control Fujitsu general out­door units and indoor units (refrigerant cycle devices, etc.) not manufactured by Fujitsu general. A system confi guration example is shown below.
System Confi guration Diagram
Fujitsu general-approved devices
Outdoor unit
Indoor unit
Control unit
Liquid pipe
Gas pipe
Control line Thermistor × 4
Wired remote controller
Piping
Wiring
EEV unit
3.2.3. Pipe Conditions
EEV
unit
Heat
Exchanger
R
Straight pipe = 200 mm or more
Liquid pipe
Gas pipe
4. INSTALLATION WORK
Correct initial installation location is important because it is diffi cult to move unit after it is installed.
4.1. Selecting an installation location
Decide the mounting position together with the customer as follows.
WARNING
Select installation locations that can properly support the weight of the DX-kit. Install the units securely so that they do not topple or fall.
CAUTION
Do not install the DX-kit in the following areas:
• Area with high salt content, such as at the seaside. It will deteriorate metal parts, causing the parts to fail or the unit to leak water.
• Area fi lled with mineral oil or containing a large amount of splashed oil or steam, such as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.
• Area that generates substances that adversely affect the equipment, such as sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to corrode, which can cause refrigerant leakage.
• Area that can cause combustible gas to leak, contains suspended carbon fi bers or ammable dust, or volatile infl ammables such as paint thinner or gasoline. If gas leaks and settles around the unit, it can cause a fi re.
• Area where animals may urinate on the unit or ammonia may be generated.
Do not use the unit for special purposes, such as storing food, raising animals, growing plants, or preserving precision devices or art objects. It can degrade the quality of the preserved or stored objects.
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or fl ammable gas.
Install the DX-kit, power supply cable, transmission cable, and remote controller cable at least 1 m away from a television or radio receivers. The purpose of this is to prevent TV reception interference or radio noise. (Even if they are installed more than 1 m apart, you could still receive noise under some signal conditions.)
En-5
4.3.2.3. Mounting Secure Fittings (If Using 1 EEV unit)
(1) Use the 8 screws (accessories) to secure the secure fi ttings (accessories).
Secure fi tting (Accessories)
Screws M4×L10 (Accessories)
Tightening torque
M4 screw
0.8 to 2.8 Nm
(8 to 28 kgf·cm)
4.3.2.4. Mounting Secure Fittings (If Using 2 EEV units)
(1) If using 2 EEV units, stacking the 2 kits is recommended.
If stacking 2 EEV units, secure using the secure fi ttings (accessories) and screws
(accessories).
Secure fi tting (Accessories)
Screws M4×L10 (Accessories)
4.3.2.5. Installing EEV units
Mount the EEV unit to the wall. Select the securing method according to the installation environment.
Method 1: Use the 8 screws (accessories) to secure the unit. Method 2: Mount the 4 anchor bolts (fi eld supply) to the wall, and then secure the unit.
Screws M4×L16 (Accessories)
Method 1 Method 2
Nuts and washers (Field supply)
Installable EEV unit orientations
A
AA
A
B
BB
B
Orient the arrow upwards
Installable both indoors and outdoors
Installable indoors only
(Cannot be installed outdoors)
EEV unit inclination limits
±10° or less
±10° or less
4.3.1. Installing the Control unit
• If installing outdoors, make sure to orient A upwards.
• Using a template (accessory) is recommended when positioning the holes for mounting the control unit.
±5° or less
Inclination limits
Sealing washers (×3, Accessories)
M8 Nuts (×3, Accessories)
A
A
Contorl
unit
200 mm or more
Service
space
200 mm or more
Service
space
Rubber inside the washer is contacted tightly with the Control unit.
anchor
bolt
Rubber Steel
4.3.2. Installing the EEV unit
4.3.2.1. Changing Pipe Orientation
• EEV unit pipe orientation can be changed according to the installation conditions.
(1) Remove the 4 screws and remove the cover. (2) Cut the cable tie fi xing the cable. (3) Invert both the pipes and heat insulation. (4) Pass the cable tie (accessory) through the cable clamp, and fi rmly secure the cable,
and then cut any unnecessary part of cable tie.
(5) Use the 4 screws to mount the cover.
Cable Cable
Cable clamp
Cable tie
Cable tie (accessory)
(2)
(1), (5)
Cover
Heat insulation
(4)
(3)
4.3.2.2. Pasting Seals to the piping holes
Use the seals (accessories) to cover any unused piping holes.
Seal (Accessories)
Seal
(Accessories)
Loading...
+ 13 hidden pages