Fujitsu UTG-LCGVCB Installation Manual

Page 1
AIR CONDITIONER OPTIONAL PARTS
PART No. 9378730137
CASSETTE GRILLE
INSTALLATION MANUAL
For authorized service personnel only.
EnglishFrançaisEspañol
1. SAFETY PRECAUTIONS
Indicates a potentially or imminently
WARNING
Do not turn on the power until all installation work is complete. Never touch electrical components immediately after the power
supply has been turned off. Electric shock may occur. After turning off the power, always wait 5 minutes or more before touching electrical components.
CAUTION
The louver angle cannot be changed if the power is not on. (If moved by hand, it may be damaged.)
Please refer to the installation manual attached to the indoor unit during installation.
Hand this manual to the customer to keep for future use, such as for maintenance.
Do not suspend very heavy weights from the intake grille.
hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation that may result in minor or moderate injury or damage to property.
2. ACCESSORIES
• The following installation parts are furnished. Use them as required.
Name and shape Q’ty Application
Installation Manual
(This manual)
1
3. INSTALLATION PROCEDURE
3.1. Removing the Intake grille
(1) Push the intake grille push-buttons (2 places). (2) Open and remove the intake grille. (3) Remove the corner panel (4 places). (4) Insert the hexagon screw and attach the washer so that it does not fall.
Washer (Accessory)
Corner panel
Hexagon screw (Accessory)
3.2. Installing the panel to indoor unit
When installing the main indoor unit, refer to the instructions on the
installation manual of the indoor unit.
(1) Install the decoration panel to the indoor unit.
• Align the stamped marks on the decoration panel against the pipe and the drain of the indoor unit.
“PIPE”
Hexagon Screw
Washer
Tapping screw
Strap
For mounting decoration panel
4
For mounting decoration panel
4
For installing grille holding wire
2
For installing corner panel
4
“DRAIN”
“PIPING SIDE”
“DRAIN SIDE”
• Attach the decoration panel temporarily at 2 places with metal fi ttings.
En-1
Page 2
CAUTION
Use only the supplied screws to install the decoration panel.
Install so that there is no gap between the decoration panel and
the main indoor unit.
If there is a gap, an error will occur as shown in the diagram below.
Condensation
Air leakage
Dirty ceiling
Condensation, dew drops
• Tighten the 4 hexagon screws.
Ensure that there is no gap between the hook and the decoration panel (4 places)
No Gap
Hexagon
screws (Accessory)
When there is a gap between the ceiling and the decoration panel even when the screw is tightened, readjust the height of the main indoor unit.
As long as it does not affect the levelness of the main indoor unit and the drain piping, you may adjust the height of the main indoor unit from the hole at the corner of the decoration panel, with the decoration panel still attached to the main indoor unit.
• Tighten the screw until the seal material between the decoration panel and the main indoor unit is compressed to a thickness of 3/16 to 1/4 in (5 to 7 mm).
(3) Open the control box cover by loosening the screws.
Control Box
(4) Connect the cassette grille connector as shown in the following fi gure.
Type A
Type B
(5) Close the control box cover and retighten the screws.
Cassette grille connector (CN37)
Cassette grille connector (CN155)
Screws
3.3. Attaching the Intake grille
(1) Tighten the 2 grille holding wires.
Indoor unit
(5 to 7 mm)
Ceiling
Attach the corner panel fi rmly in 5 places.
Sealant
Decoration panel
(2) Install the corner panels.
• As shown in the following fi gure, be sure to install the strap to prevent the corner panel from falling down.
Hook
Strap (Accessory)
Hook
3/16 to 1/4 in
No gap between ceiling and decoration panel around entire periphery
Corner panel
CAUTION
Be careful so that no wires or straps are caught between the panels.
En-2
Tapping screws (Accessory)
Intake grille
(2) Close the intake grille.
CAUTION
Install the grill holding wire to the decoration panel. If it falls, it may cause injuries.
Loading...