TEST OPERATION USING REMOTE CONTROLLER
TEST RUN CONTROL2-3
................................................................................................TEST RUN METHOD
3. REFRIGERANT PIPE SYSTEM DIAGRAM
COOLING ONLY / HEAT PUMP TYPE3-1
3-2
4. FUNCTION OF PRINTED CIRCUIT BOARD
PCB LAYOUTS4-1
MICROPROCESSOR BLOCK DIAGRAM4-2
MICROPROCESSOR FUNCTION LIST4-3
FUNCTION AND SETTING OF EACH SWITCH4-4
INDOOR UNIT
OUTDOOR UNIT
REMOTE CONTROLLER
Above units are required during heat recovery operation.
HEADER
Cooling only
– 6 –
■
1-2 SYSTEM CONSTRUCTION CONDITIONS
1-2-1 REFRIGERANT PIPING
COOLING ONLY / HEAT PUMP MODEL
a+e 100m (actual pipe length)
Difference in height between outdoor unit and indoor units (H1) maximum 50m.
(For the outdoor unit stated below:maximum 40m)
Difference in height between adjacent indoor units (H2) maximum 15m.
e 40m (actual pipe length)
a 70m (actual pipe length)
a+b+c+d+e 200m (total pipe length)
Outdoor
unit
a
H1
H2
Indoor
unit
Indoor
unit
Indoor
unit
dcb
Indoor
unit
e
a+b+c+d+e+f 100m (actual pipe length)
Difference in height between outdoor unit and indoor units (H1) maximum 50m.
Difference in height between adjacent indoor units (H2) maximum 15m.
From outdoor unit to first separation tube a 70m (actual pipe length)
b+c+d+e+f 40m (actual pipe length)
a+b+c+d+e+f+g+h+i+j+k 200m (total pipe length)
Outdoor
unit
a
bcde
ghijk
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
H2
Indoor
unit
H1
f
a+g+i 100m a+b+f 100m (actual pipe length)
Difference in height between outdoor unit and indoor units (H1) maximum 50m.
Difference in height between adjacent indoor units (H2) maximum 15m.
a+e 100m (actual pipe length)
Difference in height between outdoor unit and indoor units (H1) maximum 50m.
(For the outdoor unit stated below : maximum 40m)
Difference in height between adjacent indoor units (H2) maximum 15m.
Difference in height between RB unit and RB unit (H3) 15m or less.
Difference in height between
RB unit and indoor unit (H4) 5m or less
e
40m (actual pipe length)
f
10m (actual pipe length)
a+b+c+d+e 200m (total pipe length)
.
Outdoor
unit
a
H1
a+b+c+d+e+f 100m (actual pipe length)
b
RB
unit
Indoor
unit
c
Indoor
RB
unit
unit
RB
unit
Indoor
unit
d
RB
unit
H2
Indoor
unit
Difference in height between outdoor unit and indoor units (H1) maximum 50m.
Difference in height between adjacent indoor units (H2) maximum 15m.
Difference in height between RB unit and indoor unit (H3) 5m or less.
From outdoor unit to first separation tube a 70m (actual pipe length)
b+c+d+e+f 40m (actual pipe length)
10m (actual pipe length)
a+b+c+d+e+f+g+h+i+j+k 200m (total pipe length)
Outdoor
unit
a
bcde
ghijk
RB
unit
Indoor
unit
RB
unit
Indoor
unit
RB
unit
Indoor
unit
RB
unit
Indoor
unit
RB
unit
Indoor
unit
H3
H2
Indoor
a+g+i 100m a+b+f 100m (actual pipe length)
Difference in height between outdoor unit and indoor units (H1) maximum 50m.
Difference in height between adjacent indoor units (H2) maximum 15m.
Difference in height between RB unit and RB unit (H3) 15m or less.
Difference in height between RB unit and indoor unit (H4) 5m or less.
g+i 40m b+f 40m (actual pipe length)
j 10m (actual pipe length)
a+b+c+d+e+f+g+h+i 200m (total pipe length)
Outdoor
unit
a
b
RB unit
4 brunch
RB
unit
unit
e
H3
H4, f
H1
f
H1
g
edc
RB
unit
Indoor
unit
H3
i
H2
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
– 9 –
h
RB
unit
Indoor
unit
H4
f
j
HEAT RECOVERY MODEL
Pipe size connected to outdoor unit.
(unit : mm)
ModelSuction Gas Pipe
Discharge Gas Pipe
Liquid Pipe
AO 90 28.58 19.05 12.7
Between two adjacent refrigerant branch kits.
Total model code ofSuctionDischarge
Liquid Pipe
Separation Kit
indoor unitGas PipeGas Pipe
Less than 30 15.88 12.7 9.53
Up to a pipe length of 7.5 m, charging with additional refrigerant is not necessary.
If the pipe length exceeds 7.5 m, charging with refrigerant is necessary.
Charge with additional refrigerant in the amounts shown in the table below.
It is necessary to add refrigerant to all connected Indoor unit.
Add refrigerant to the corresponding type as shown in the Table for every connected Indoor unit to the
refrigerant system.
Example : When AR30 x2 and AU18 x2 are connected to the refrigerant system.
" Additional charge of system type" is 1.0(kg)x2 +0.65(kg)x2=3.3(kg)
Model / Model code
AS
AU
AB
AR
0.65
0.4
79
0.65120.65
0.4
0.65
0.45
14
0.9
0.65
0.65
0.45
18
0.65
0.65
0.7
ADDITIONAL CHARGE = (1) + (2)
20
0.9
0.8
24/25
0.9
0.9
0.8
0.8
1.0
1.0
1.0
1.0
30
36
45
54
1.5
1.5
1.0
2.0
amount of refrigerant (kg)
1.0
2.0
1.5
1.0
60
2.0
– 11 –
1-2-2 SYSTEM WIRING
Use
Outdoor
2
unit
Indoor
Power supply
cable (mm )
unit
Transmission
cable (mm )
2
Wired remote control
cable (mm )
1,2
3
410m cable attached.
2
The grounding wire is not included in this cable.
Always ground the unit.
Do not bundle the transmission cable with other wires.
Transmission cable between each unit : 200m max
Each unit means indoor unit,outdoor unit,central remote controller,
and signal amplifier.
Total wiring length:maximum 2000m.
However,when wiring exceeds 500m in length,
a signal amplifier (option) is required.
Use the shielded wire specified and always ground(however,one side only).
If not,transmit-receive with a transmission line is not
only impossible normally,but malfunction may occur.
Use the shielded cable in accordance with standards
in the country.
Wiring length of a remote controller group shall be
within 500m.
Size
MaximumH07RN-F or
Minimumequivalent
MaximumH07RN-F or
Minimumequivalent
Maximum
8.0
6.0
2.5
1.5
1.25
Wire typeRemarks
Shield cord
(LONWORKS
Minimum
MaximumSheathed vinyl
Minimumcord cable
0.75
1.25
0.75
compatible part)
3 4 wire 50Hz
380-415V
1 2 wire 50Hz
220-240V
Non-polar
2-core
Polar 3-core
1
2
3
4
Fuse
capacity
per one outdoor unit
5
per one refrigerant system.
6
ModelField fuse
Outdoor
unit
Indoor
unit
40A
20A
5
6
– 12 –
Leakage breaker
40A 100mA 0.1sec or less
20A 40mA 0.1sec or less
1-3 ADDRESS SETTING
This system is needed to set the address for the indoor unit, outdoor
unit and remote controller and central remote controller.
1 The refrigerant system address of the indoor and outdoor units can be set to optional numbers
in the range of 0 and 99.
2 Address of the indoor unit can be set to optional numbers in the range of 0 to 15.
3 Set address of the remote controller in the order of 0,1,2,...15.(Blank is impossible)
4 Address of the central remote controller can be set to optional numbers in the range of 0 to 15.
ONDIP SW1-1
Number of the unit
in the group
Refrigeration
circuit address
Rotary-sw8,7
DIP SW1-1 Remote controller address1
DIP SW1-2 Number of indoor unit connection
DIP SW1-4 Remote controller address2
Indoor unit PCB (Address setting No.0
Setting by rotary SW7,8
Indoor unit address
0
00 0 01 1 02 2 13 0 14 1 15 003
0 0 0 0 0 0 0
Indoor unit PCB (Address setting No. 0
15)
Setting by rotary SW5
Remote controller address
(Indoor unit)
0
00 001 102 2 0 03 3 0 04 0 0 05 0
0
Indoor unit PCB (Address setting No.0
0 0
15)
Setting by rotary SW9
– 16 –
Remote controller switch 1
[Master] [Slave]
OFF
ON
Remote controller unit PCB
Setting by DIP SW 1-1
No. indoor unit connection
ONOFF
ON
Remote controller PCB
124
Setting by DIP SW 1-2
– 17 –
Remote controller switch 2
(Remote controller)
[Master] [Slave]
Remote controller unit PCB
Setting by DIP SW 1-4
Central remote controller address
[Master] [Slave]
00
01
02
03
Central remote controller (Max.16)
Set central remote controller address first,to conduct the initial setting of it.
– 18 –
Outdoor
unit
3 4W 50Hz 380 - 415V
1 50Hz
220 - 240V
Transmission line
Indoor
unit
1
13
7 8
4
7
8
1
9
14 15 16
10 11
12
2
3 5 6
13
14
Central
remote controller
Wired
remote controller
RB unit
Before test running, check the following items.
Note: RB unit ( ) is for the heat recovery type.
Is the selection of the outdoor unit and the indoor unit correct?
(Maximum operating indoor unit, total capacity of the indoor unit)
Is the piping length correct?
(Ex. Maximum piping length : 100m)
Is the separate selected correct?
Doesn't gas leak?
Is the refrigerant flow correct?
Are the power supplies connected?
1
2
(Power supply for the indoor unit and outdoor unit is separated.)
Is the spec. for the power supply cable correct?
Is the RB unit cable connected?
Is the length of the transmission line under the limit?
Is the spec. for the transmission cable correct?
(non-polar 2-core, 0.75-1.25mm )
Is the transmission cable connected to all units?
2
Are the addresses set? (Ex. Refrigerant circuit address, indoor unit address, remote controller address, etc.)
Have the all settings done on the PCB?
Is the refrigerant valve opened?
Is the power supplied to crank case heater for 12 hours before winter operation?
3
4
5
6
7
8
9
10
Is the diameter of the pipe selected correct?
11
12
13
14
15
2-1 CHECK ITEMS BEFORE TEST RUNNING
9
2. TEST RUN
1 50Hz 220 - 240V
16
– 19 –
2-2 TEST RUNNING METHOD
Supply power to the crankcase heater for 12 hours prior to the start of operation in the winter.
The following is the procedure for the test operation.
2-2-1 OUTDOOR PC BOARD
If the test operation is to be done for cooling operation, set DIP switch (SW-1-1) to on. If the test operation is to be done for heating,
set DIP switch (SW1-2) to on.
2-2-2 TEST OPERATION USING REMOTE CONTROLLER
(1) Standard wired remote controller
For test running, when the remote controller FAN CONTROL
button and MASTER CONTROL button are pressed simulta-
neously for more than three seconds when the air conditioner is
not running, the air conditioner starts and TEST is displayed on
the remote controller display.
However, the SET TEMP./DAY setting button does not function,
but all other buttons, displays, and protection functions operate.
CLOCK
NON STOP
SET TIME
TIMER
MODE
CLOCK ADJUST
TEST
TEMP./DAY
C
CONTROL
FAN
COOL
MASTER
CONTROL
When EE : EE blinks at the current time display, there
DAY button ( ) are pressed
simultaneously for more than three seconds, the self
be displayed at the current time display. In addition,
lights, press the START/STOP button and after
CLOCK
NON STOP
SET TIME
TIMER
MODE
CLOCK ADJUST
TEMP./DAY
C
CONTROL
FAN
COOL
MASTER
CONTROL
operation lamp goes off, perform the same operation.
ZONE
ENERG
SET
D
is an error inside the air conditioner. If the SET TIME
diagnosis check will start and the error
the remote controller address will be displayed below.
TIMER
MODE
CLOCK ADJUST
SET TIME
TEMP./DAY
FAN
CONTROL
MASTER
CONTROL
OP
SET
button ( ) and SET TEMP.
contents will
When the oper
ation
lamp
Stop operation
ZONE
SET
START/STOP
ENERGY SAVE
DAY OFF
– 20 –
ZONE
SET
SET
START/STOP
ENERGY SAVE
DAY OFF
Error Code
Error contents
Error Code
Error contents
No error
Model information abnormal
Power supply frequency abnormal
EEPROM access error
EEPROM elimination error
Room temperature thermistor error
Indoor unit heat exchange thermistor
(middle) error
Indoor unit heat exchange thermistor
(inlet) error
Indoor unit heat exchange
(exit) error
thermistor
To stop test running, press the START/STOP button.
For the operation method, refer to the operating manual and perform operation check.
Check that there are no abnormal sounds or vibration sounds during test running.
(2) Standard wireless remote controller
Press the remote control unit test run button while the air condi tioner is running.
Blower temperature thermistor error
Drain abnormal
Room temperature abnormal
Indoor unit fan error
Communication error
Node setting error
Parallel communication error
Outdoor unit error
Remote control unit
At the end of test running, press the remote control unit start-
stop button.
Operation can be checked by lighting and flashing of the display
section OPERATION and TIMER lamps.
Perform judgment in accordance with the following.
Test running
When the air conditioner is run by pressing the remote control
unit test run button, the OPERATION and TIMER lamps flash
slowly at the same time.
START
STOP
A B C D
START/STOP button
TEST RUN button
– 21 –
– 22 –
1) When the test run signal is transmitted from the standard wired remote controller, the wireless remote controller
and the central remote controller.
(1) In the test running status, operated in accordance with the setting of each switch besides the room temperature
switch. The room temperature adjustment does not funtion, and then the electric expansion valve is controlled
with maximum flow.
(2) De-frosting and de-icing prevention has priority over item(1).
(3) After 60 minutes passes, the test run stops.
2) When the test run signal is transmitted from the outdoor unit.
(1) Whether state of the indoor unit operates or stops, test run will be made in accordance with the operation
mode of the indoor unit , which belongs to the same refrigerant system.
Ceiling height setting.
Changeover the fan speed of the indoor fan phase control according to ceiling height (cassette type).
Details of rotation is according to DIP SW3 setting.
CEILING HEIGHT SETTING 1,2
StandardHigh ceiling 1Low ceiling
SW1-1
SW1-2
(2)
NOTCH
Ceiling height
Room temp correct coefficient of heating.
2
Decide room temp correct coefficient value of heating.
ROOM TEMP. CORRECT COEFFICIENT OF HEATING
SW1-3
OFF
ONOFF- 2 deg
(3)
(4)
(5)
(6)
OFF
OFFOFF
HIGH(1)
MED
LOWLOW
S-LOWS-LOWS-LOWS-LOW
2.5 3.0m
SW1-4
OFF
ON
3.0 3.5m
Coefficient value
High ceiling 2
ON
HIGHHIGH
MEDMED
+ 2 deg
0 degOFF
OFF
ONON
LOW
more than
3.5m
ON
HIGH
MEDLOW
less than
2.5m
+ 4 degONON
2. DIP SWITCH 2
Room temp. correct coefficient of cooling.
1
Decide room temp correct coefficient value of cooling.
ROOM TEMP CORRECT COEFFICIENT OF COOLING
SW2-1
OFF
ON+ 2 deg
2
Zone control switch.
Decide the indoor unit for zone control use and not for zone control.
ZONE CONTROL SWITCH
SW2-2
OFF
ON
Coefficient value
0 deg
Switch control
Validity
Invalidity
Ð 12Ð
– 30 –
Loading...
+ 169 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.