Fujitsu ASYG07LLCE, ASYG12LLCE, ASYG09LLCE, AOYG12LLCE, AOYG07LLCE Design & Technical Manual

...
Page 1
AIR CONDITIONER
Wall mounted type
DESIGN & TECHNICAL MANUAL
INDOOR
ASYG07LLCE ASYG09LLCE ASYG12LLCE
OUTDOOR
AOYG07LLCE AOYG09LLCE AOYG12LLCE
2016.04.06
Page 2
Notices:
• Product specifications and design are subject to change without notice for future improvement.
• For further details, please check with our authorized dealer.
Copyright © 2016, 2017 Fujitsu General Limited. All rights reserved.
Page 3
CONTENTS
Part 1. INDOOR UNIT....................................................................... 1
1. Specifications............................................................................................2
2. Dimensions................................................................................................4
2-1. Models:ASYG07LLCE, ASYG09LLCE, and ASYG12LLCE........................................ 4
3. Wiring diagrams ........................................................................................6
3-1. Models:ASYG07LLCE, ASYG09LLCE, and ASYG12LLCE........................................ 6
4. Capacity table............................................................................................7
4-1. Cooling capacity.......................................................................................................... 7
4-2. Heating capacity .........................................................................................................8
5. Fan performance .......................................................................................9
5-1. Air velocity distributions............................................................................................... 9
5-2. Airflow....................................................................................................................... 10
6. Operation noise (sound pressure)......................................................... 11
6-1. Noise level curve....................................................................................................... 11
6-2. Sound level check point............................................................................................ 12
7. Safety devices ......................................................................................... 13
8. Remote controller ...................................................................................14
8-1. Wireless remote controller ........................................................................................ 14
9. Function settings .................................................................................... 17
9-1. Function settings by using remote controller............................................................. 17
9-2. Custom code setting for wireless remote controller................................................... 21
10. Accessories.............................................................................................22
Page 4
Part 2. OUTDOOR UNIT................................................................. 23
1. Specifications..........................................................................................24
2. Dimensions..............................................................................................25
2-1. Models:AOYG07LLCE, AOYG09LLCE, and AOYG12LLCE..................................... 25
3. Installation space ....................................................................................26
3-1. Models:AOYG07LLCE, AOYG09LLCE, and AOYG12LLCE..................................... 26
4. Refrigerant circuit ................................................................................... 29
4-1. Models:AOYG07LLCE, AOYG09LLCE, and AOYG12LLCE..................................... 29
5. Wiring diagrams ......................................................................................30
5-1. Models:AOYG07LLCE, AOYG09LLCE, and AOYG12LLCE..................................... 30
6. Capacity compensation rate for pipe length and height difference....31
6-1. Models:AOYG07LLCE and AOYG09LLCE............................................................... 31
6-2. Model:AOYG12LLCE................................................................................................ 32
7. Additional charge calculation ................................................................ 33
7-1. Models:AOYG07LLCE and AOYG09LLCE............................................................... 33
7-2. Model:AOYG12LLCE................................................................................................ 33
8. Airflow......................................................................................................34
8-1. Models:AOYG07LLCE and AOYG09LLCE............................................................... 34
8-2. Model:AOYG12LLCE................................................................................................ 34
9. Operation noise (sound pressure)......................................................... 35
9-1. Noise level curve....................................................................................................... 35
9-2. Sound level check point............................................................................................ 37
10. Electrical characteristics........................................................................38
11. Safety devices ......................................................................................... 39
12. Accessories.............................................................................................40
CONTENTS (continued)
Page 5
Part 1. INDOOR UNIT
WALL MOUNTED TYPE:
ASYG07LLCE ASYG09LLCE ASYG12LLCE
Page 6
1. Specifications
Type
Wall mounted
Inverter heat pump
Model name ASYG07LLCE ASYG09LLCE ASYG12LLCE
Power supply 230 V ~ 50 Hz Available voltage range 198—264 V
Capacity
Cooling
Rated
kW 2.00 2.50 3.40
Btu/h 6,800 8,500 11,600
Min.—Max.
kW 0.9—2.8 0.9—3.0 0.9—3.8
Btu/h 3,100—9,500 3,100—10,200 3,100—13,000
Heating
Rated
kW 2.70 3.00 4.00
Btu/h 9,200 10,200 13,600
Min.—Max.
kW 0.9—3.6 0.9—3.8 0.9—5.0
Btu/h 3,100—12,200 3,100—13,000 3,100—17,000
Input power
Cooling
Rated
kW
0.470 0.730 1.080
Min.—Max. 0.25—1.29 0.25—1.29 0.25—1.40
Heating
Rated 0.620 0.740 1.130 Min.—Max. 0.25—1.63 0.25—1.63 0.25—1.98
Fan
HIGH
W
29 MED 19 LOW 8 QUIET 5
Current
Cooling
Rated A
2.6 3.5 5.2
Heating 3.0 3.5 5.4
EER Cooling
kW/kW
4.26 3.42 3.15 COP Heating 4.35 4.05 3.54 Sensible capacity Cooling kW 1.30 1.60 2.20
Power factor
Cooling
%
79 91 91
Heating 90 92 92
Moisture removal L/h (pints/h) 1.0 (1.8) 1.3 (2.3) 1.8 (3.2)
Maximum operating current *1
Cooling
A
6.0 6.0 6.5
Heating 7.5 7.5 9.0
Fan
Airflow rate
Cooling
HIGH
m3/h
720 MED 600 LOW 420 QUIET 325
Heating
HIGH 740 MED 600 LOW 450 QUIET 325
Type × Q'ty Cross flow fan × 1 Motor output W 30
Sound pressure level *2
Cooling
HIGH
dB (A)
43 MED 38 LOW 33 QUIET 22
Heating
HIGH 43 MED 38 LOW 33 QUIET 22
Heat exchanger type
Dimensions (H × W × D)
mm
256 × 630 × 20 Fin pitch 1.1 Rows × Stages 2 × 16 Pipe type Copper tube Fin type Aluminum
Enclosure
Material Polystyrene
Color
White + Pearl white (painted)
Approximate color of Munsell N 9.25/
Dimensions (H × W × D)
Net
mm
262 × 820 × 206
Gross 263 × 870 × 328
Weight
Net
kg
7.0
Gross 9.5
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas Ø 9.52 (Ø 3/8)
Method Flare
Drain hose
Material PP+LLDPE Size mm Ø 13.8 (I.D.), Ø 15.8 to Ø 16.7 (O.D.)
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Remote controller type Wireless
NOTES:
• Specifications are based on the following conditions: – Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB. – Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum current is maximum value when operated within the operation range.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 2 -
WALL MOUNTED
ASYG07-12LLCE
Page 7
Model name ASYG07LLCE ASYG09LLCE ASYG12LLCE
Energy efficiency class
Cooling
A
++
A
++
A
++
Heating (Average)
A
+
A
+
A
Pdesign
Cooling
kW
2.0 (35 °C) 2.5 (35 °C) 3.4 (35 °C)
Heating (Average) 2.2 (-10 °C) 2.3 (-10 °C) 3.2 (-10 °C)
SEER Cooling
kWh/kWh
6.70 6.90 6.60
SCOP Heating (Average) 4.00 4.00 3.80
Annual energy consumption
QCE
kWh/a
104 127 180
QHE (Average) 770 805 1,179
Sound power level
Cooling
HIGH dB (A)
59 59 59
Heating 60 60 60
- 3 -
WALL MOUNTED
ASYG07-12LLCE
Page 8
2. Dimensions
2-1. Models:ASYG07LLCE, ASYG09LLCE, and ASYG12LLCE
262
1210
49
65
65
49
44
(820)
355 345
91 312 321 96
7248
Outline of unit
Unit: mm
820
262
206
- 4 -
WALL MOUNTED
ASYG07-12LLCE
Page 9
¢
Installation space requirement
Provide sufficient installation space for product safety.
Unit: mm
63 or more
70 or more
Outline of unit
100 or more
1,500 or more
1,800 or more
- 5 -
WALL MOUNTED
ASYG07-12LLCE
Page 10
3. Wiring diagrams
3-1. Models:ASYG07LLCE, ASYG09LLCE, and ASYG12LLCE
- 6 -
WALL MOUNTED
ASYG07-12LLCE
Page 11
4. Capacity table
Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR):
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP)
4-1. Cooling capacity
¢
Model:ASYG07LLCE
AFR
m3/h
720
Indoor temperature °CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW 20 1.87 1.32 0.33 2.09 1.33 0.34 2.16 1.45 0.34 2.30 1.45 0.34 2.37 1.57 0.34 2.51 1.56 0.35 2.65 1.66 0.35 25 1.78 1.26 0.37 1.98 1.26 0.38 2.05 1.37 0.38 2.18 1.38 0.38 2.25 1.49 0.38 2.39 1.48 0.39 2.52 1.58 0.39 30 1.68 1.19 0.41 1.87 1.19 0.42 1.94 1.30 0.42 2.06 1.30 0.42 2.13 1.41 0.43 2.25 1.40 0.43 2.38 1.49 0.44 35 1.58 1.12 0.45 1.76 1.12 0.46 1.82 1.22 0.46 1.94 1.23 0.47 2.00 1.32 0.47 2.12 1.32 0.47 2.24 1.40 0.48 40 1.41 1.00 0.45 1.57 1.00 0.46 1.62 1.09 0.46 1.73 1.09 0.47 1.78 1.18 0.47 1.89 1.17 0.47 2.00 1.25 0.48 43 1.31 0.92 0.45 1.45 0.93 0.46 1.50 1.01 0.46 1.60 1.01 0.47 1.65 1.09 0.47 1.75 1.09 0.47 1.85 1.16 0.48
¢
Model:ASYG09LLCE
AFR
m3/h
720
Indoor temperature °CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW 20 2.34 1.62 0.51 2.61 1.63 0.52 2.70 1.77 0.52 2.87 1.78 0.53 2.96 1.92 0.53 3.14 1.91 0.54 3.32 2.04 0.54 25 2.22 1.54 0.58 2.48 1.55 0.58 2.56 1.68 0.59 2.73 1.69 0.59 2.81 1.82 0.60 2.98 1.82 0.60 3.15 1.93 0.61 30 2.10 1.45 0.64 2.34 1.46 0.65 2.42 1.59 0.65 2.58 1.60 0.66 2.66 1.72 0.66 2.82 1.72 0.67 2.98 1.83 0.68 35 1.98 1.37 0.70 2.20 1.38 0.72 2.28 1.50 0.72 2.43 1.50 0.73 2.50 1.62 0.73 2.65 1.61 0.74 2.80 1.72 0.74 40 1.76 1.22 0.70 1.96 1.23 0.71 2.03 1.33 0.72 2.16 1.34 0.73 2.23 1.44 0.73 2.36 1.44 0.74 2.50 1.53 0.74 43 1.63 1.13 0.70 1.82 1.14 0.71 1.88 1.24 0.72 2.00 1.24 0.72 2.07 1.34 0.73 2.19 1.33 0.73 2.31 1.42 0.74
¢
Model:ASYG12LLCE
AFR
m3/h
720
Indoor temperature °CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW 20 3.18 2.18 0.76 3.55 2.19 0.77 3.67 2.39 0.77 3.91 2.39 0.78 4.03 2.59 0.79 4.27 2.57 0.79 4.51 2.74 0.80 25 3.02 2.07 0.85 3.37 2.08 0.87 3.48 2.27 0.87 3.71 2.27 0.88 3.83 2.45 0.88 4.06 2.44 0.89 4.28 2.60 0.90 30 2.86 1.96 0.95 3.18 1.97 0.96 3.29 2.14 0.97 3.51 2.15 0.98 3.62 2.32 0.98 3.83 2.31 0.99 4.05 2.46 1.00 35 2.69 1.84 1.04 2.99 1.85 1.06 3.09 2.01 1.06 3.30 2.02 1.07 3.40 2.18 1.08 3.60 2.17 1.09 3.81 2.31 1.10 40 2.39 1.64 1.04 2.67 1.65 1.06 2.76 1.79 1.06 2.94 1.80 1.07 3.03 1.94 1.08 3.21 1.94 1.09 3.39 2.06 1.10 43 2.22 1.52 1.04 2.47 1.53 1.05 2.56 1.66 1.06 2.73 1.67 1.07 2.81 1.80 1.08 2.98 1.80 1.09 3.15 1.91 1.10
- 7 -
WALL MOUNTED
ASYG07-12LLCE
Page 12
4-2. Heating capacity
¢
Model:ASYG07LLCE
AFR
m3/h
740
Indoor temperature
16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 2.42 1.22 2.36 1.24 2.30 1.27 2.24 1.30 2.19 1.32
-10 -11 2.51 1.17 2.45 1.20 2.39 1.22 2.33 1.24 2.27 1.27
-5 -7 2.75 1.15 2.68 1.18 2.61 1.20 2.55 1.23 2.48 1.25 0 -2 3.18 1.18 3.10 1.21 3.03 1.23 2.95 1.26 2.87 1.28 5 3 3.61 1.21 3.52 1.23 3.44 1.26 3.35 1.28 3.26 1.31 7 6 3.78 1.22 3.69 1.25 3.60 1.27 3.51 1.30 3.42 1.32
10 8 3.80 1.18 3.71 1.21 3.62 1.23 3.53 1.26 3.44 1.28 15 10 3.98 1.19 3.89 1.22 3.79 1.24 3.70 1.27 3.60 1.29
¢
Model:ASYG09LLCE
AFR
m3/h
740
Indoor temperature
16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 2.63 1.23 2.56 1.25 2.50 1.28 2.44 1.31 2.38 1.33
-10 -11 2.72 1.18 2.66 1.21 2.59 1.23 2.53 1.25 2.46 1.28
-5 -7 2.96 1.16 2.88 1.19 2.81 1.21 2.74 1.24 2.67 1.26 0 -2 3.39 1.20 3.31 1.22 3.23 1.25 3.14 1.27 3.06 1.30 5 3 3.82 1.23 3.73 1.25 3.64 1.28 3.54 1.30 3.45 1.33 7 6 3.99 1.24 3.90 1.27 3.80 1.29 3.71 1.32 3.61 1.34
10 8 3.94 1.18 3.84 1.21 3.75 1.23 3.66 1.26 3.56 1.28 15 10 4.11 1.19 4.01 1.22 3.91 1.24 3.81 1.27 3.71 1.29
¢
Model:ASYG12LLCE
AFR
m3/h
740
Indoor temperature
16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 3.17 1.39 3.10 1.42 3.02 1.45 2.94 1.48 2.87 1.51
-10 -11 3.35 1.44 3.27 1.47 3.20 1.50 3.12 1.53 3.04 1.56
-5 -7 3.72 1.48 3.63 1.51 3.54 1.54 3.45 1.57 3.37 1.60 0 -2 4.36 1.51 4.25 1.54 4.15 1.57 4.05 1.60 3.94 1.63 5 3 5.00 1.53 4.88 1.57 4.76 1.60 4.64 1.63 4.52 1.66 7 6 5.25 1.55 5.13 1.58 5.00 1.61 4.88 1.64 4.75 1.67
10 8 4.90 1.38 4.78 1.41 4.66 1.44 4.55 1.47 4.43 1.50 15 10 5.15 1.39 5.02 1.42 4.90 1.45 4.78 1.48 4.66 1.51
- 8 -
WALL MOUNTED
ASYG07-12LLCE
Page 13
5. Fan performance
5-1. Air velocity distributions
¢
Models:ASYG07LLCE, ASYG09LLCE, and ASYG12LLCE
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
2.0
1.0
0.5
2
1
0
1
2
Unit: m/s(m)
(m)
012345678
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
2.0
1.0
1.0
0.5
0.5
3
2
1
0
1
2
3
Unit: m/s(m)
(m)
012345678
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
2.0
1.0
0.5
3
2
1
0
Unit: m/s(m)
(m)
012345678
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
2.0
1.0
0.5
3
2
1
0
Unit: m/s(m)
(m)
012345678
- 9 -
WALL MOUNTED
ASYG07-12LLCE
Page 14
5-2. Airflow
¢
Models:ASYG07LLCE, ASYG09LLCE, and ASYG12LLCE
Cooling
Fan speed Airflow
HIGH
m3/h
720
l/s 200
CFM 424
MED
m3/h
600
l/s 167
CFM 353
LOW
m3/h
420
l/s 117
CFM 247
QUIET
m3/h
325
l/s 90
CFM 191
Heating
Fan speed Airflow
HIGH
m3/h
740
l/s 206
CFM 436
MED
m3/h
600
l/s 167
CFM 353
LOW
m3/h
450
l/s 125
CFM 265
QUIET
m3/h
325
l/s 90
CFM 191
- 10 -
WALL MOUNTED
ASYG07-12LLCE
Page 15
6. Operation noise (sound pressure)
6-1. Noise level curve
¢
Models:ASYG07LLCE and ASYG09LLCE
Cooling
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,00 0 2,000 4,000 8,00 0
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HIGH
QUIET
Heating
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 50 0 1,000 2,0 00 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HIGH
QUIET
¢
Model:ASYG12LLCE
Cooling
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 50 0 1,000 2,0 00 4,000 8,000
HIGH
QUIET
Heating
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,00 0 2,000 4,00 0 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HIGH
QUIET
- 11 -
WALL MOUNTED
ASYG07-12LLCE
Page 16
6-2. Sound level check point
0.8 m
1 m
Microphone Microphone
- 12 -
WALL MOUNTED
ASYG07-12LLCE
Page 17
7. Safety devices
Type of
protection
Protection form
Model
ASYG07LLCE ASYG09LLCE ASYG12LLCE
Circuit protection Current fuse (PCB*) 250 V, 3.15 A
Fan motor protection
Thermistor protection program
Activate
93±5 °C
Fan motor speed down
Reset
93±5 °C
Fan motor speed recover
*PCB: Printed Circuit Board
- 13 -
WALL MOUNTED
ASYG07-12LLCE
Page 18
8. Remote controller
8-1. Wireless remote controller
¢
Overview
o
b
d
e
f
a
c
g
i
j
k
l
n m
h
Display panel
u
rs
ptq
a FAN button b SET button c SWING button d START/STOP button e RESET button f TIMER CANCEL button g ON TIMER button h OFF TIMER button i SLEEP TIMER button j TEST RUN button
• Used only when installing the air conditioner, and should not be used under normal conditions, as it will cause the indoor unit’s thermostat malfunction.
• If this button is pressed during normal operation, the in­door unit will switch to test operation mode, and the oper­ation indicator lamp and the timer indicator lamp on the indoor unit will begin to flash simultaneously.
• To stop the test operation mode, press the START/STOP button. Then, the air conditioner stops the operation.
k ECONOMY button l POWERFUL button
m
SET TEMP. (temperature) (
/ ) button
• Sets desired temperature.
• Sets remote controller custom code.
n MODE button
• Switches operation mode (AUTO, COOL, DRY, FAN, and HEAT).
• Starts/ends the remote controller custom code (max. 4 types) change.
o Signal transmitter p Operating mode indicator q Signal transmit indicator r Temperature and time indicator
• Displays set temperature.
• In timer setting, it displays the timer time. After finishing the timer setting, set temperature will reappear.
s Swing indicator t Fan speed indicator u Timer mode indicator
Sleep timer
OFF timer
OFF-ON timer
ON-OFF timer
ON timer
- 14 -
WALL MOUNTED
ASYG07-12LLCE
Page 19
NOTE: Functions may differ by type of the indoor unit. For details, refer to the operation
manual.
- 15 -
WALL MOUNTED
ASYG07-12LLCE
Page 20
¢
Specifications
Controller
Unit: mm
Front view Side view Rear view
139
18
56
Top view
Size (H × W × D) mm 139 × 56 × 18 Weight g 70 (without batteries)
Holder
Unit: mm
Front view Side view Bottom view
60.4
30.2
Ø 3.5
3.5 x 6.5
(hole)
(hole)
13.592
26.2
140
Size (H × W × D) mm 140 × 60.4 × 26.2 Weight g 25
- 16 -
WALL MOUNTED
ASYG07-12LLCE
Page 21
9. Function settings
To adjust the functions of this product according to the installation environment, various types of function settings are available.
NOTE:
Incorrect settings can cause a product malfunction.
9-1. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting pro­cedure and the content of each function setting, select appropriate functions for your installation environment.
NOTE: Incorrect settings can cause a product malfunction.
¢
Setting procedure by using wireless remote controller
The function number and the associated setting value are displayed on the LCD of the remote controller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
Before connecting the power supply of the indoor unit, reconfirm following items:
• Piping air tight test and vacuuming have been performed firmly.
• There is no wiring mistake.
Then, connect the power supply of indoor unit.
Entering function setting mode:
While pressing the FAN button and SET TEMP. ( ) button simultaneously, press the RESET button to enter the function setting mode.
STEP 1: Setting the remote controller custom code
Use the following steps to select the custom code of the remote controller. (Note that the air con­ditioner cannot receive a custom code if the air conditioner has not been set for the custom code.)
The custom codes that are set through this process are applicable only to the signal in the func­tion setting.
For details on how to set the custom codes through the normal process, refer to "Custom code
setting for wireless remote controller" on page 21.
1. Press the SET TEMP. (
) ( ) buttons to change the custom code between → → → . Match the code on the display to the air conditioner custom code. (Initially set to
.) If the custom code does not need to be selected, press the MODE button, and proceed to STEP 2.
2. Press the MODE button to accept the custom code, and proceed to STEP 2.
*1: Small is displayed on the right of the custom code during the function setting.
*1
- 17 -
WALL MOUNTED
ASYG07-12LLCE
Page 22
NOTES:
• The air conditioner custom code is set to
prior to shipment. To change the custom code,
contact your retailer.
• The remote controller resets to custom code
when the batteries on the remote controller are
replaced. If you use a custom code other than code , reset the custom code after replacing the batteries.
• If you do not know the air conditioner custom code setting, try each of the custom codes ( → → → ) until you find the code that operates the air conditioner.
STEP 2: Selecting the function number and setting value
1. Press the SET TEMP. (
) ( ) buttons to select the function number. To switch between the left and right digits, press the MODE button.
2. Press the FAN button to proceed the setting value. To return the function number selection, press the FAN button again.
3. Press the SET TEMP. ( ) ( ) buttons to select the setting value. To switch between the left and right digits, press the MODE but­ton.
4. Press the SLEEP button, then after you hear the beep emitted from the indoor unit, the START/STOP button in the order to con­firm the settings.
5. Press the RESET button to cancel the function setting mode.
6. After completing the function setting, be sure to disconnect the power supply and then reconnect it.
*1: Small
is displayed on the right of the custom code during the
function setting.
*1
*1
Function number
Setting value
CAUTION
After disconnect the power supply, wait 30 seconds or more before reconnecting it. The function setting will not become active unless the power supply is disconnected and then reconnected.
- 18 -
WALL MOUNTED
ASYG07-12LLCE
Page 23
¢
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ­ment.
NOTE:
Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no. Functions
1) 11 Filter sign
2) 30 Room temperature sensor control for cooling
3) 31 Room temperature sensor control for heating
4) 40 Auto restart
5) 44 Remote controller custom code
6) 49 Indoor unit fan control for energy saving for cooling
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the esti­mated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number Setting value Setting description Factory setting
11
00 Standard (400 hours) 01 Long interval (1,000 hours) 02 Short interval (200 hours) 03 No indication
2) Room temperature sensor control for cooling
Depending on the installed environment, correction of the room temperature sensor may be re­quired. Select the appropriate control setting according to the installed environment.
Function number Setting value Setting description Factory setting
30
00 Standard ♦ 01 Slightly lower control 02 Lower control 03 Higher control
3) Room temperature sensor control for heating
Depending on the installed environment, correction of the room temperature sensor may be re­quired. Select the appropriate control setting according to the installed environment.
Function number Setting value Setting description Factory setting
00 Standard ♦ 01 Lower control
31 02 Slightly higher control
03 Higher control
- 19 -
WALL MOUNTED
ASYG07-12LLCE
Page 24
4) Auto restart
Enables or disables automatic restart after a power interruption.
Function number Setting value Setting description Factory setting
40
00 Enable ♦ 01 Disable
NOTE: Auto restart is an emergency function such as for power outage etc. Do not attempt to
use this function in normal operation. Be sure to operate the unit by remote controller or external device.
5) Remote controller custom code
(Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code.
Function number Setting value Setting description Factory setting
44
00 A ♦ 01 B 02 C 03 D
6) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation.
Function number Setting value Setting description Factory setting
49
00 Disable 01 Enable
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the set-
ting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low
speed.
- 20 -
WALL MOUNTED
ASYG07-12LLCE
Page 25
9-2. Custom code setting for wireless remote controller
To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required.
NOTE:
Air conditioner cannot receive a custom code if the air conditioner has not been set for the custom code.
1. Press the MODE button for at least 5 seconds to display the current custom code. (Initially set to
.)
2. Press the SET TEMP. ( or ) button to change the custom code between → → → . Match the code on the display to the air conditioner custom code.
3. Press the MODE button again. The custom code will be changed.
NOTES:
• If no button is pressed within 30 seconds after the custom code is displayed, the system re­turns to the original clock indicator. In this case, start again from step 1.
• The air conditioner custom code is set to prior to shipment. To change the custom code, contact your retailer.
• The remote controller resets to custom code when the batteries in the remote controller are replaced. If you use a custom code other than code , reset the appropriate custom code af-
ter replacing the batteries. If you do not know the assigned code for the air conditioner, try each of the custom code ( → → → ) until you find the code which operates the air condi-
tioner.
- 21 -
WALL MOUNTED
ASYG07-12LLCE
Page 26
10. Accessories
Part name Exterior Q’ty Part name Exterior Q’ty
Operating manual 1 Battery 2
Installation manual 1 Cloth tape 1
Wall hook bracket 1
Tapping screw (large), M4 × 25 mm
5
Remote controller 1
- 22 -
WALL MOUNTED
ASYG07-12LLCE
Page 27
Part 2. OUTDOOR UNIT
SINGLE TYPE:
AOYG07LLCE AOYG09LLCE AOYG12LLCE
Page 28
1. Specifications
Type Inverter heat pump
Model name AOYG07LLCE AOYG09LLCE AOYG12LLCE
Power supply 230 V ~ 50 Hz Available voltage range 198—264 V Starting current A 3.0 3.5 5.4
Fan
Airflow rate
Cooling
m3/h
1,670 1,830
Heating 1,470 1,600 Type × Q'ty Propeller fan × 1 Motor output W 23
Sound pressure level *1
Cooling
dB (A)
47 50
Heating 48 51
Sound power level
Cooling
dB (A)
61 65
Heating 61 65
Heat exchanger type
Dimensions
(H × W × D)
mm
650 × 504 × 18.2
642 × 504 × 18.2
612 × 504 × 18.2 Fin pitch 1.30 1.40 Rows × Stages 1 × 24 2 × 24 Pipe type Copper
Fin type
Type (Material) Corrugate (Aluminum) Surface treatment Corrosion resistance (Blue fin)
Compressor
Type × Q'ty Rotary × 1 Motor output W 610 670
Refrigerant
Type (Global warming potential) R410A (1975) Charge g 650 850
Refrigerant oil
Type POE (VG74) Amount
cm
3
370
Enclosure
Material Steel sheet
Color
Beige
Approximate color of MUNSELL 10YR7.5/1.0 Dimensions (H × W × D)
Net
mm
535 × 663 × 293
Gross 595 × 790 × 395
Weight
Net
kg
24 26
Gross 27 29
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas Ø 9.52 (Ø 3/8) Method Flare Pre-charge length
m
15 Max. length 20 Max. height difference 15
Operation range
Cooling
°C
-10 to 43
Heating -15 to 24
Drain hose
Material LDPE Size mm Ø 13.0 (I. D.), Ø 16.0 to Ø 16.7 (O. D.)
NOTES:
• Specifications are based on the following conditions: – Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB. – Pipe length: 5 m, Height difference: 0 m.
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level – Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 24 -
OUTDOOR UNIT
AOYG07-12LLCE
Page 29
2. Dimensions
2-1. Models:AOYG07LLCE, AOYG09LLCE, and AOYG12LLCE
Top view
Unit: mm
Front view Side view
20 663 68 293
Drain hole 30
330
454
(Pitch of bolt)
103
535
15
48
352
330
- 25 -
OUTDOOR UNIT
AOYG07-12LLCE
Page 30
3. Installation space
3-1. Models:AOYG07LLCE, AOYG09LLCE, and AOYG12LLCE
¢
Space requirement
Provide sufficient installation space for product safety.
Single outdoor unit installation
When the upper space is open:
Unit: mm
When there are obstacles at the rear only. When there are obstacles at the rear and
sides.
100 or more
250 or more
100 or more
100 or more
When there are obstacles at the front only. When there are obstacles at the front and
rear.
600 or more
600 or more
100 or more
When there is an obstruction in the upper space:
Unit: mm
When there are obstacles at the rear and above.
When there are obstacles at the rear, sides, and above.
100 or more
Max. 200
600 or more
600 or more
100 or more
250 or more
100 or more
Max. 200
- 26 -
OUTDOOR UNIT
AOYG07-12LLCE
Page 31
Multiple outdoor unit installation
When the upper space is open:
Unit: mm
When there are obstacles at the rear only. When there are obstacles at the front only.
200
or more
1,000 or more
When there are obstacles at the front and rear.
200 or more
1,000 or more
When there is an obstruction in the upper space:
Unit: mm
When there are obstacles at the rear and above.
1,500 or more
200 or more
Max. 300
- 27 -
OUTDOOR UNIT
AOYG07-12LLCE
Page 32
Outdoor unit installation in multi-row
Unit: mm
Single parallel unit arrangement Multiple parallel unit arrangement
100 or more
200 or more
500 or more
1,000 or more
200 or more
400 or more
1,000 or more
2,000 or more
200 or more
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no obstacle.
• Height above the floor level should be 50 mm or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better opera­tion efficiency.
CAUTION
• Do not install the outdoor unit in two-stage where the drain water could freeze. Otherwise the drainage from the upper unit may form ice and cause a malfunction of the lower unit.
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in ex­tremely cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it might become difficult to get warm, and it is likely to cause product malfunction. Construct a canopy and a pedestal, or place the unit on a high stand that is locally installed.
- 28 -
OUTDOOR UNIT
AOYG07-12LLCE
Page 33
4. Refrigerant circuit
4-1. Models:AOYG07LLCE, AOYG09LLCE, and AOYG12LLCE
Heat exchanger
(INDOOR)
Th
D
Th
D
Th
P
Th
P
Th
R
Th
R
Th
HO
Th
HO
Th
O
Th
O
3-way
valve
Muffler
: Cooling : Heating
: Thermistor (Discharge temperature)
: Thermistor (Outdoor temperature)
: Thermistor (Heat exchanger out temperature)
: Thermistor (Room temperature)
: Thermistor (Pipe temperature)
Compressor
4-way valve
Strainer
Expansion valve
Strainer
2-way
valve
- 29 -
OUTDOOR UNIT
AOYG07-12LLCE
Page 34
5. Wiring diagrams
5-1. Models:AOYG07LLCE, AOYG09LLCE, and AOYG12LLCE
- 30 -
OUTDOOR UNIT
AOYG07-12LLCE
Page 35
6. Capacity compensation rate for pipe length and height difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH
6-1. Models:AOYG07LLCE and AOYG09LLCE
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 - - - 0.872 0.910 10 - - 0.961 0.886 0.925
7.5 - 0.979 0.965 0.890 0.929 5 0.992 0.983 0.969 0.893 0.933 0 1.000 0.991 0.976 0.901 0.940
Indoor unit is lower than
outdoor unit *2
-5 1.000 0.991 0.976 0.901 0.940
-7.5 - 0.991 0.976 0.901 0.940
-10 - - 0.976 0.901 0.940
-15 - - - 0.901 0.940
HEATING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 - - - 0.832 0.822 10 - - 0.917 0.832 0.822
7.5 - 0.961 0.917 0.832 0.822 5 1.000 0.961 0.917 0.832 0.822 0 1.000 0.961 0.917 0.832 0.822
Indoor unit is lower than
outdoor unit *2
-5 0.995 0.956 0.912 0.828 0.818
-7.5 - 0.954 0.910 0.826 0.816
-10 - - 0.908 0.824 0.814
-15 - - - 0.815 0.805
- 31 -
OUTDOOR UNIT
AOYG07-12LLCE
Page 36
6-2. Model:AOYG12LLCE
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 - - - 0.858 0.868 10 - - 0.929 0.872 0.882
7.5 - 0.960 0.933 0.876 0.885 5 0.992 0.964 0.937 0.879 0.889 0 1.000 0.972 0.944 0.887 0.896
Indoor unit is lower than
outdoor unit *2
-5 1.000 0.972 0.944 0.887 0.896
-7.5 - 0.972 0.944 0.887 0.896
-10 - - 0.944 0.887 0.896
-15 - - - 0.887 0.896
HEATING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 - - - 0.896 0.879 10 - - 0.968 0.890 0.879
7.5 - 0.994 0.968 0.896 0.879 5 1.000 0.994 0.968 0.896 0.879 0 1.000 0.994 0.968 0.896 0.879
Indoor unit is lower than
outdoor unit *2
-5 0.995 0.989 0.963 0.891 0.875
-7.5 - 0.987 0.961 0.889 0.873
-10 - - 0.959 0.887 0.871
-15 - - - 0.878 0.862
- 32 -
OUTDOOR UNIT
AOYG07-12LLCE
Page 37
7. Additional charge calculation
7-1. Models:AOYG07LLCE and AOYG09LLCE
Refrigerant type R410A Refrigerant amount g 650
¢ Refrigerant charge
Total pipe length m 15 or less 20 (Max.)
20 g/m
Additional charge g 0 100
7-2. Model:AOYG12LLCE
Refrigerant type R410A Refrigerant amount g 850
¢ Refrigerant charge
Total pipe length m 15 or less 20 (Max.)
20 g/m
Additional charge g 0 100
- 33 -
OUTDOOR UNIT
AOYG07-12LLCE
Page 38
8. Airflow
8-1. Models:AOYG07LLCE and AOYG09LLCE
Cooling
m3/h
1,670
l/s 464
CFM 983
Heating
m3/h
1,470
l/s 408
CFM 865
8-2. Model:AOYG12LLCE
Cooling
m3/h
1,830
l/s 508
CFM 1,077
Heating
m3/h
1,600
l/s 444
CFM 942
- 34 -
OUTDOOR UNIT
AOYG07-12LLCE
Page 39
9. Operation noise (sound pressure)
9-1. Noise level curve
¢
Model:AOYG07LLCE
Cooling
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,00 0 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
¢
Model:AOYG09LLCE
Cooling
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,00 0 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
- 35 -
OUTDOOR UNIT
AOYG07-12LLCE
Page 40
¢
Model:AOYG12LLCE
Cooling
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,00 0 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
- 36 -
OUTDOOR UNIT
AOYG07-12LLCE
Page 41
9-2. Sound level check point
1 m
MicrophoneMicrophone
Rear
A
irflow
Rear view
Side view
NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrat-
ed above.
- 37 -
OUTDOOR UNIT
AOYG07-12LLCE
Page 42
10. Electrical characteristics
Model name AOYG07LLCE AOYG09LLCE AOYG12LLCE Power
supply
Voltage V 230 ~
Frequency Hz 50 Max operating current *1 A 7.5 7.5 9.0 Starting current A 3.0 3.5 5.4
Wiring spec. *2
Circuit breaker current A 15
Power cable
mm
2
1.5
Connection cable *3
mm
2
1.5
Limited wiring length m 21
*1: Maximum current is the total current of the indoor unit and the outdoor unit. *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
As the regulations of wire size and circuit breaker differ in each country or region, select appropri­ate devices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
- 38 -
OUTDOOR UNIT
AOYG07-12LLCE
Page 43
11. Safety devices
Type of
protection
Protection form
Model
AOYG07LLCE AOYG09LLCE AOYG12LLCE
Circuit protection Current fuse (Main PCB)
250 V, 25 A
250 V, 5 A
Fan motor protection
Terminal protection program
Activate
100±15 °C
Fan motor stop
Reset
95±10 °C
Fan motor restart
Compressor protection
Terminal protection program (Discharge temp.)
Activate
110 °C
Compressor stop
Reset
After 7 minutes
Compressor restart
- 39 -
OUTDOOR UNIT
AOYG07-12LLCE
Page 44
12. Accessories
Part name Exterior Q’ty Part name Exterior Q’ty
Drain pipe 1
- 40 -