Fujitsu ASYE14, ASYE07, AS*A07LACH series, AS*A09LACH series, AS*A14LACH series Installation Manual

...
VRF SYSTEM INDOOR UNIT Compact Wall Mounted Type Comfort Model (EEV external model)
INSTALLATION MANUAL
For authorized service personnel only.
English
1. SAFETY PRECAUTIONS .............................................2
2. ABOUT THE UNIT
2.1. Precautions for using the R410A refrigerant .......... 2
2.2. Special tool for R410A ............................................ 2
2.3. Accessories ............................................................ 2
3. INSTALLATION WORK
3.1. Selecting an installation location ............................ 3
3.2. Installation dimensions ........................................... 4
3.3. Installing the unit .................................................... 4
4.
PIPE INSTALLATION
4.1. Selecting the pipe material ..................................... 7
4.2. Pipe requirement .................................................... 7
4.3. Flare connection (pipe connection) ........................ 7
4.4. Installing heat insulation ......................................... 8
5. ELECTRICAL WIRING
5.1. Electrical requirement ............................................ 9
5.2. Wiring method ...................................................... 10
5.3. Unit wiring ............................................................ 10
6. FIELD SETTING
6.1. Setting the address .............................................. 11
6.2. Custom code setting ............................................ 13
6.3. Function setting .................................................... 13
6.4.
Connecting the wired remote controller
(If necessary) .......................................................... 14
6.5. Installing the control unit ...................................... 15
7. FINISHING .................................................................. 16
8. DECORATION PANEL INSTALLATION ...................... 16
9. TEST OPERATION
9.1.
Test operation using PCB (Outdoor unit) .................. 17
9.2. Test operation using Remote Controller ............... 17
10. CHECK LIST ............................................................... 17
11. ERROR CODES ......................................................... 17
PART NO. 9377773043-02
1. SAFETY PRECAUTIONS
• Be sure to read this Manual thoroughly before installation.
• The warnings and precautions indicated in this Manual contain important information pertaining to your safety. Be sure to observe them.
• Hand this Manual, together with the Operating Manual to the customer.
Request the customer to keep them on hand for future
use, such as for relocating or repairing the unit.
This mark indicates procedures which, if
WARNING!
• Request your dealer or a professional installer to install the unit in accordance with this Manual.
An improperly installed unit can cause serious accidents
such as water leakage, electric shock, or fi re.
If the unit is installed in disregard of the instructions in the
Installation Manual, it will void the manufacturer’s warranty.
• Do not turn ON the power until all work has been completed.
Turning ON the power before the work is completed can
cause serious accidents such as electric shock or fi re.
• If refrigerant leaks while work is being carried out, ventilate the area.
If the refrigerant comes in contact with a flame, it
produces a toxic gas.
• Installation work must be performed in accordance with national wiring standards by authorized personnel only.
CAUTION!
improperly performed, might lead to the death or serious injury of the user.
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property.
2. ABOUT THE UNIT
2.1. Precautions for using the R410A refrigerant
WARNING
• Do not introduce any substance other than the prescribed refrigerant into the refrigeration cycle.
If air enters the refrigeration cycle, the pressure in the
refrigeration cycle will become abnormally high and cause the piping to rupture.
• If there is a refrigerant leakage, make sure that it does not exceed the concentration limit.
If a refrigerant leakage exceeds the concentration limit, it can
lead to accidents such as oxygen starvation.
2.2. Special tool for R410A
WARNING
• To install a unit that uses the R410A refrigerant, use dedicated tools and piping materials that have been manufactured specifi cally for R410A use.
Because the pressure of the R410A refrigerant is
approximately 1.6 times higher than the R22, failure to use dedicated piping material or improper installation can cause rupture or injury.
Furthermore, it can cause serious accidents such as water
leakage, electric shock, or fi re.
Tool name
Gauge manifold
Charging hose
Vacuum pump
Gas leakage
detector
• Pressure is huge and cannot be measured with a conventional gauge. To prevent erroneous mixing of other refrigerants, the diameter of each port has been changed.
It is recommended to use a gauge
manifold with a high pressure display range –0.1 to 5.3 MPa and a low pressure display range –0.1 to 3.8 MPa.
• To increase pressure resistance, the hose material and base size were changed.
• A conventional vacuum pump can be used by installing a vacuum pump adapter.
• Special gas leakage detector for HFC refrigerant R410A.
Contents of change
2.3. Accessories
WARNING
• For installation purposes, be sure to use the parts supplied by the manufacturer or other prescribed parts.
The use of non-prescribed parts can cause serious
accidents such as the unit to fall, water leakage, electric shock, or fi re.
• The following installation parts are furnished. Use them as required.
• Keep the Installation Manual in a safe place and do not discard any other accessories until the installation work has been completed.
Do not discard any accessories needed for installation until the installation work has been completed.
• Do not touch refrigerant that has leaked from the refrigerant pipe connections or other area. Touching the refrigerant directly can cause frostbite.
• If a refrigerant leakage occurs during operation, immediately vacate the premises and thoroughly ventilate the area.
If the refrigerant comes in contact with a fl ame, it produces a
toxic gas.
En-2
Name and Shape Q’ty Application
Operating Manual
1
3. INSTALLATION WORK
Especially, the installation place is very important for the split type air conditioner because it is very diffi cult to move from place to place after the fi rst installation.
3.1. Selecting an installation location
Installation Manual
Wall hook bracket
Binder
Cloth tape
Tapping screw
×
25mm)
(M4
Wire assebly
Air cleaning filter
(This book)
1
For indoor unit installation
1
For remote control cable binding
1
For indoor unit installation
1
For wall hook bracket installation
8
For wired remote control installation
1
2
WARNING
• Select installation locations that can properly support the weight of the indoor. Install the units securely so that they do not topple or fall.
CAUTION
• Do not install the unit in the following areas:
• Area with high salt content, such as at the seaside. It will deteriorate metal parts, causing the parts to fall or
the unit to leak water.
• Area fi lled with mineral oil or containing a large amount
of splashed oil or steam, such as a kitchen.
It will deteriorate plastic parts, causing the parts to fall or
the unit to leak water.
• Area that generates substances that adversely affect the
equipment, such as sulfuric gas, chlorine gas, acid, or alkali.
It will cause the copper pipes and brazed joints to
corrode, which can cause refrigerant leakage.
• Area that can cause combustible gas to leak, contains
suspended carbon fi bers or fl ammable dust, or volatile infl ammables such as paint thinner or gasoline.
If gas leaks and settles around the unit, it can cause a
re.
• Area where animals may urinate on the unit or ammonia
may be generated.
• Do not use the unit for special purposes, such as storing food, raising animals, growing plants, or preserving precision devices or art objects.
It can degrade the quality of the preserved or stored
objects.
• Do not install where there is the danger of combustible gas leakage.
• Do not install the unit near a source of heat, steam, or ammable gas.
• Install the unit where drainage does not cause any trouble.
Air cleaning filter frame
2
Seal A
For indoor unit installation
1
• Install the indoor unit, outdoor unit, power supply cable, transmission cable, and remote control cable at least 1 m away from a television or radio receivers. The purpose of this is to prevent TV reception interference or radio noise.
(Even if they are installed more than 1 m apart, you could still
receive noise under some signal conditions.)
• If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
• Decide the mounting position with the customer as follows:
(1) Install the indoor unit on a place having a suffi cient strength
so that it withstands against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air
should be able to blow all over the room.
(3) Leave the space required to service the air conditioner.
(4) A place from where the air can be distributed evenly
throughout the room by the unit.
(5) Install the unit where connection to the outdoor unit is easy.
En-3
(6) Install the unit where the connection pipe can be easily
installed.
(7) Install the unit where the drain pipe can be easily installed.
(8) Install the unit where noise and vibrations are not amplifi ed.
(9) Take servicing, etc., into consideration and leave the spaces.
Also install the unit where the fi lter can be removed.
3.2. Installation dimensions
Provide a service space for inspection purposes. Do not place any wiring or illumination in the service space, as they will impede service.
60 mm or over
1,500 mm or over
1,800 mm or over
* Select the most appropriate airflow direction from 3 or
4 directions according to the shape of the room and the installation position.
* When changing the number of outlets, we recommend
using the optional AIR OUTLET SHUTTER PLATE KIT to close the outlet.
* For the specific closing pattern, please refer to the
attached AIR OUTLET SHUTTER PLATE KIT’S MANUAL. (Do so before installing the decorative panel as it will be installed on the body.)
* Be sure to make the function settings with the remote
control according to the number of airfl ow outlets and the installed ceiling height.
50 mm or over
Wall hook bracket
90 mm or over
(Wall cap)
Drain hose O.D 15.8 - 16.7 mm I.D 13.8 mm
3.3.1. Determining the piping direction
The piping can be connected in the fi ve directions indicated by 1, 2, 3, 4, and 5 in (Fig. A). When the piping is connected in direction 2 or 5, cut along the piping groove in the side of the front cover with a hacksaw. When connecting the piping in direction 3, cut a notch in the thin wall at the front bottom of the front cover.
Fig. A
(Rear)
Left outlet
5
Rear outlet
Right outlet
2
Bottom outlet
3
1
Left rear outlet
4
3.3.2. Installing the wall hook bracket
CAUTION
• Install the wall hook bracket horizontally and perpendicularly.
(1) Install the wall hook bracket so that it is correctly positioned
horizontally and vertically. If the wall hook bracket is tiled, water will drip to the fl oor.
(2) Install the wall hook bracket so that it is strong enough to
withstand the weight of an adult.
• Fasten the wall hook bracket to the wall with 6 or more screws through the holes near the outer edge of the bracket.
• Check that there is no rattle at the wall hook bracket.
Wall hook bracket
Tapping screw
Wall hook bracket
Center notch
Hook
String
3.3. Installing the unit
WARNING
• Install the air conditioner in a location which can withstand a load do at least fi ve times the weight of the main unit and which will not amplify sound or vibration. If the installation location is not strong enough, the indoor unit may fall and cause injuries.
• If the job is done with the panel frame only, there is a risk that the unit will come loose. Please take care.
En-4
3.3.3. Cutting the hole in the wall for the connecting piping
WARNING
• If the wall pipe is not used, the cable interconnecting the indoor and outdoor units may touch metal and cause electric leakage.
(1) Cut a 80 mm diameter hole in the wall at the position shown
in Fig.B.
(2) When cutting the wall hole at the inside of the wall hook
bracket, cut the hole within the range of the left and right center marks 40 mm below the wall hook bracket.
When cutting the wall hole at the outside of the wall hook
bracket, cut the hole at least 10 mm below over.
(3) Cut the hole so that the outside end is lower (5 to 10 mm)
than the inside end.
(4) Always align the center of the wall hole. If misaligned, water
leakage will occur.
(5) Cut the wall pipe to match the wall thickness, stick it into the
wall cap, fasten the cap with vinyl tape, and stick the pipe through the hole. (The connection pipe is supplied in the installation set.) (Fig. B)
(6) For left piping and right piping, cut the hole a little lower so
that drain water will fl ow freely. (Fig. B)
Fig. B
Wall hook bracket
Center mark
[Rear piping, Right piping, Bottom piping]
(1) Install the indoor unit piping in the direction of the wall hole
and bind the drain hose and pipe together with vinyl tape.
Right piping
Bottom piping
Bind with vinyl tape
Pipe (top) Rear piping
Indoor unit drain hose (bottom)
(2) Install the piping so that the drain hose is at the bottom.
(3) Wrap the pipes of the indoor unit that are visible from the
outside with decorative tape.
[For Left rear piping, Left piping]
(1) Interchange the drain cap, insulation and the drain hose.
For left outlet piping, cut off the piping outlet cutting groove with a hacksaw.
Remove the drain cap by pulling
Insulation
Indoor unit drain hose
Drain cap
at the projection at the end of the cap with pliers, etc. And remove the insulation.
(2) Align the marks on the wall hook bracket and shape the
connection pipe.
Lower
80 mm dia. hole
Fasten with vinyl tape
(Wall cap)
5 to 10 mm low
80 mm dia. hole
(Wall pipe)
(Inside) Wall
Lower
10 mm or over
(Outside)
3.3.4. Forming the drain hose and pipe
CAUTION
• In order to align the drain hose and drain cap, be sure to insert securely and vertically. Incline insertion will cause water leakage.
• When inserting, be sure not to attach any material besides water. If any other material is attached, it will cause deterioration and water leakage.
Connection pipe (Liquid pipe)
Bend (R70) with a pipe bender
Connection pipe (Gas pipe)
Align the marks.
(3) Bend the connection piping at the bend radius of 70 mm or
more and install no more than 35 mm from the wall.
Installation method of Drain cap
Please put the heat insulation inside all along.
Use a hexagonal wrench (4mm at opposite side) to insert
the drain cap, till the drain cap contacts the tip of drain cock.
No gap
Hexagonal wrench
No gap
Drain Cock
Insulation
Drain cap
• After removing drain hose, be sure not to forget mounting drain cap.
• Be sure to fix the drain hose with tape to the bottom of piping.
En-5
[Removal method of drain hose]
Remove the screw at the left of drain hose and pull out drain hose.
Screw
Drain fi xture (blue)
Drain hose
[Installation method of drain hose]
Vertically insert the drain hose toward the inside, so that the drain fi xture (blue) can accurately align with the screw hole around the drain cock.
After inserting and before replacing, please reinstall and fi x the removed screws.
Drain fi xture(blue)
Screw hole
Drain cock
Screw
Drain hose
• Be sure to install around the drain hose connector.
• As the screw is inside, be sure to use screwdriver treated with magnet.
(3) Remove the front panel.
The thumb is hung on the lower part as shown in the
1
gure, and it pulls to the front, pushing [–] mark, and bottom hooks (two position) is removed from wall hook bracket.
The front panel bottom is pulled to the front, and bottom
2
hooks is removed indoor unit.
Screws (4 position)
Push
The front panel is pulled to the front, raising the upper
3
[–] mark
Push
Wall hook bracket
Front panel
surface, and a front panel is removed.
Front panel
(4) Insert the spacer, etc. between the indoor unit and the wall
hook bracket and separate the bottom of the indoor unit from the wall.
Indoor unit
3.3.5. Installing the indoor unit
(1) After passing the indoor piping and drain hose through the
wall hole, hang the indoor unit on the hooks at the top and bottom of the wall hook bracket.
Connection pipe (2 mm dia.)
Indoor unit
(Fitting)
(2) Remove the intake grille.
Open the intake grille.
1
Pull down the knob.
2
Intake grille
2
1
Top hooks
Wall hook bracket
Bottom hooks
2
1
Intake grille
Knob
Spacer
Wall hook bracket
Lift the intake grille upward, until the axle at the top of the
3
intake grille is removed.
En-6
4. PIPE INSTALLATION
CAUTION
• Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant R410A models. Also, when storing the piping, securely seal the openings by pinching, taping, etc.
• While welding the pipes, be sure to blow dry nitrogen gas through them.
4.1. Selecting the pipe material
CAUTION
• Do not use existing pipes.
• Use pipes that have clean external and internal sides without any contamination which may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.
• It is necessary to use seamless copper pipes.
Material : Phosphor deoxidized seamless copper pipes It is desirable that the amount of residual oil is less than
40 mg/10 m.
• Do not use copper pipes that have a collapsed, deformed, or discolored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
• Improper pipe selection will degrade performance. As an air conditioner using R410A incurs pressure higher than when using conventional refrigerant, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in the table.
Never use copper pipes thinner than those indicated in the table even if they are available on the market.
Thicknesses of Annealed Copper Pipes (R410A)
Pipe outside diameter [mm (in.)] Thickness [mm]
6.35 (1/4) 0.80
9.52 (3/8) 0.80
12.70 (1/2) 0.80
15.88 (5/8) 1.00
19.05 (3/4) 1.20
4.2. Pipe requirement
CAUTION
• Refer to the Installation Manual of the outdoor unit for description of the length of connecting pipe or for difference of its elevation.
• Use pipe with water-resistant heat insulation.
CAUTION
• Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 120 °C.
(Reverse cycle model only)
In addition, if the humidity level at the installation location
of the refrigerant piping is expected to exceed 70 %, install heat insulation around the refrigerant piping. If the expected humidity level is 70-80 %, use heat insulation that is 15 mm or thicker and if the expected humidity exceeds 80 %, use heat insulation that is 20 mm or thicker. If heat insulation is used that is not as thick as specifi ed, condensation may form on the surface of the insulation. In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 20 °C).
4.3. Flare connection (pipe connection)
WARNING
• Tighten the flare nuts with a torque wrench using the specifi ed tightening method. Otherwise, the fl are nuts could break after a prolonged period, causing refrigerant to leak and generate a hazardous gas if the refrigerant comes into contact with a fl ame.
4.3.1. Flaring
Use special pipe cutter and fl are tool exclusive for R410A.
(1)
Cut the connection pipe to the necessary length with a pipe cutter.
(2)
Hold the pipe downward so that cuttings will not enter the
pipe and remove any burrs.
(3)
Insert the fl are nut (always use the fl are nut attached to the indoor and outdoor units respectively) onto the pipe and perform the fl are processing with a fl are tool. Use the special R410A flare tool, or the conventional flare tool. Leakage of refrigerant may result if other fl are nuts are used.
(4)
Protect the pipes by pinching them or with tape to
prevent dust, dirt, or water from entering the pipes.
En-7
Pipe outside
diameter
[mm (in.)]
6.35 (1/4)
Dimension A [mm]
Flare tool for R410A,
clutch type
Dimension B
[mm]
9.1
-00.4
9.52 (3/8) 13.2
12.70 (1/2) 16.6
0 to 0.5
15.88 (5/8) 19.7
19.05 (3/4) 24.0
When using conventional fl are tools to fl are R410A pipes, the dimension A should be approximately 0.5 mm more than indicated in the table (for fl aring with R410A fl are tools) to achieve the specifi ed fl aring. Use a thickness gauge to measure the dimension A.
Pipe outside
diameter [mm (in.)]
Width across flats
of Flare nut [mm]
6.35 (1/4) 17
9.52 (3/8) 22
12.70 (1/2) 26
15.88 (5/8) 29
19.05 (3/4) 36
When the fl are nut is tightened properly by your hand, hold the body side coupling with a separate spanner, then tighten with a torque wrench.
Flare nut [mm (in.)] Tightening torque [N·m (kgf·cm)]
6.35 (1/4) dia. 16 to 18 (160 to 180)
9.52 (3/8) dia. 32 to 42 (320 to 420)
12.70 (1/2) dia. 49 to 61 (490 to 610)
15.88 (5/8) dia. 63 to 75 (630 to 750)
19.05 (3/4) dia. 90 to 110 (900 to 1,100)
Selecting the EV kit
MODEL APPLICABLE EV kit
AS
E07/09L UTR-EV09XB E12/14L UTR-EV14XB
AS
4.3.2. Bending pipes
If pipes are shaped by hand, be careful not to collapse them.
Do not bend the pipes in an angle more than 90°.
When pipes are repeatedly bend or stretched, the material will harden, making it diffi cult to bend or stretch them any more.
Do not bend or stretch the pipes more than three times.
CAUTION
• To prevent breaking of the pipe, avoid sharp bends.
• If the pipe is bent repeatedly at the same place, it will break.
4.3.3. Pipe connection
CAUTION
• Be sure to connect the EV kit (optional) that is suitable to the indoor unit.
For installation instructions, refer to the installation Manual of
the EV kit.
• Be sure to apply the pipe against the port on the indoor unit correctly. If the centering is improper, the fl are nut cannot be tighten smoothly. If the fl are nut is forced to turn, the threads will be damaged.
4.4. Installing heat insulation
CAUTION
• After checking for gas leaks (refer to the Installation Manual of the outdoor unit), perform this section.
• Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do so may cause water leaks.
After checking for gas leaks, insulate by wrapping insulation around the two parts (gas and liquid) of the indoor unit coupling, using the Coupler heat insulation. After installing the Coupler heat insulation, wrap both ends with vinyl tape so that there is no gap.
CAUTION
• Must fi t tightly against body without any gap.
• Do not remove the fl are nut from the indoor unit pipe until immediately before connecting the connection pipe.
• Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order to tighten the fl are nut correctly.
• Tighten the flare nuts with a torque wrench using the specifi ed tightening method. Otherwise, the fl are nuts could break after a prolonged period, causing refrigerant to leak and generate a hazardous gas if the refrigerant comes into contact with a fl ame.
En-8
5. ELECTRICAL WIRING
WARNING
• Electrical work must be performed in accordance with this Manual by a person certifi ed under the national or regional regulations. Be sure to use a dedicated circuit for the unit.
An insuffi cient power supply circuit or improperly performed
electrical work can cause serious accidents such as electric shock or fi re.
• Before starting work, check that power is not being supplied to the indoor unit and outdoor unit.
• For wiring, use the prescribed type of wires, connect them securely, making sure that there are no external forces of the wires applied to the terminal connections.
Improperly connected or secured wires can cause serious
accidents such as overheating the terminals, electric shock, or fi re.
• Securely install the electrical box cover on the unit.
An improperly installed electrical box cover can cause
serious accidents such as electric shock or fire through exposure to dust or water.
• Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit could result.
• Use the included connection cables and power cables or ones specifi ed by the manufacturer. Improper connections, insuffi cient insulation, or exceeding the allowable current can cause electric shock or fi re.
• Do not modify the power cables, use extension cables, or use any branches in the wiring. Improper connections, insuffi cient insulation, or exceeding the allowable current can cause electric shock or fi re.
• Match the terminal block numbers and connection cable colors with those of the outdoor unit. Erroneous wiring may cause burning of the electric parts.
• Securely connect the connection cables to the terminal board. In addition, secure the cables with wiring holders. Improper connections, either in the wiring or at the ends of the wiring, can cause a malfunction, electric shock, or fi re.
• Always fasten the outside covering of the connection cable with the cable clamp. (If the insulator is chafed, electric leakage may occur.)
• Install a ground leakage breaker. In addition, install the ground leakage breaker so that the entire AC main power supply is cut off at the same time. Otherwise, electric shock or fi re could result.
CAUTION
• Ground the unit. Do not connect the ground cable to a gas pipe, water pipe,
lightning rod, or a telephone ground cable.
Improper grounding may cause electric shock.
• Do not connect power supply cables to the transmission or remote control terminals, as this will damage the product.
• Never bundle the power supply cable and transmission cable together. Bundling these cables together will cause miss operation.
• When handling PCB, static electricity charged in the body may cause malfunction of the PCB. Follow the cautions below:
• Establish a ground for the indoor and outdoor units and
peripheral devices.
• Cut power (breaker) off.
• Touch metal part of the indoor and outdoor units for more
than 10 seconds to discharge static electricity charged in the body.
• Do not touch terminals of parts and patterns implemented
on PCB.
5.1. Electrical requirement
Voltage rating
Operating range
Recommended
Power supply
cable
Transmission
cable
Remote
control
cable
*: Use shielded cable in accordance with local rules for remote
control cable.
230 V
198 - 264 V
cable size
2
(mm
)
2.5
0.33
0.33
Cable type Remark
Type245 IEC57 or equivalent
1ø 50 Hz 198–264 V 2 Cable + ground 22 AWG LEVEL
LONWORKS compatible cable
4 (NEMA) non-polar 2 core, twisted pair solid core diameter
0.65 mm Sheathed PVC cable*
Polar 3 core Twisted pair
• Install a ground leakage breaker. If a ground leakage breaker is not installed, it may cause
electric shock or fi re.
• Always connect the ground cable. Improper grounding work can cause electric shocks.
• Install the remote control cables so as not to be direct touched with your hand.
• Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively.
• Connect the connection cable fi rmly to the terminal board. Imperfect installation may cause a fi re.
En-9
5.2. Wiring method
(EXAMPLE)
POWER SUPPLY
OUTDOOR UNIT
TRANSMISSION
TRANSMISSION TRANSMISSION
POWER SUPPLY
BREAKER
POWER SUPPLY
BREAKER
POWER SUPPLY
WALL MOUNTED TYPE
REMOTE CONTROL
REMOTE
CONTROL UNIT
POWER SUPPLY
EV KIT
INDOOR UNIT
POWER SUPPLY POWER SUPPLY
BREAKER
INDOOR UNIT
TRANSMISSION
BREAKER
POWER SUPPLY
REMOTE CONTROL
REMOTE
CONTROL UNIT
5.3. Unit wiring
• Before attaching the cable to terminal block.
5.3.1. Power supply cable
200 mm
Earth cable
220 mm
Power supply cable
A. For solid core wiring
(1) To connect the electrical terminal, follow the below diagram
and connect after looping it around the end of the cable.
(2) Use the specifi ed cables, connect them securely, and fasten
them so that there is no stress placed on the terminals.
(3) Use an appropriate screwdriver to tighten the terminal
screws.
Do not use a screwdriver that is too small, otherwise, the
screw heads may be damaged and prevent the screws from being properly tightened.
(4) Do not tighten the terminal screws too much, otherwise, the
screws may break. (5) See the table for the terminal screw tightening torques. (6) Please do not fi x two power supply cables with one screw.
Strip 25 mm
Loop
Screw with
Cable
special washer
Cable end (Loop)
Terminal block
Cable
WARNING
Screw with special washer
Cable end (Loop)
• When using solid core cables, do not use the attached ring terminal. If you use the solid core cables with the ring terminal, the ring terminal's pressure bonding may malfunction and cause the cables to abnormally heat up.
B. For strand wiring
(1) Use ring terminals with insulating sleeves as shown in the
gure below to connect to the terminal block.
(2) Securely clamp the ring terminals to the cables using an
appropriate tool so that the cables do not come loose.
(3) Use the specifi ed cables, connect them securely, and fasten
them so that there is no stress placed on the terminals.
(4)
Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the
screw heads may be damaged and prevent the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the
screws may break. (6) See the table for the terminal screw tightening torques. (7) Please do not fi x two power supply cables with one screw.
Strip 10 mm
Screw with special washer
Ring terminal
Cable
Ring terminal
Cable
Sleeve
Screw with special washer
Ring terminal
En-10
Terminal block
WARNING
• Use ring terminals and tighten the terminal screws to the specifi ed torques, otherwise, abnormal overheating may be produced and possibly cause heavy damage inside the unit.
Tightening torque
M4 screw
(Power supply /L, N, GND)
1.2 to 1.8 N·m
(12 to 18 kgf·cm)
5.3.2. Transmission and Remote control cable
6.1. Setting the address
Manual address setting method
CAUTION
• When setting the DIP switch, use an insulated screw driver.
40 mm
Shielded cable (no fi lm)
75 mm
Transmission cable
• Connect remote control and transmission cables as shown in Fig. C.
Fig. C
Different diameter
OK NO GOOD NO GOOD
WARNING
• Tighten the terminal screws to the specified torques, otherwise, abnormal overheating may be produced and possibly cause heavy damage inside the unit.
Connect to one side
Tightening torque
M4 screw
(Transmission /X1, X2)
0.8 to 1.2 N·m
( 8 to 12 kgf·cm)
• When handling the PCB, static electricity charged in the body may cause malfunction of the PCB. Follow the cautions below:
• Touch metal part of the indoor and outdoor units for more
than 10 seconds to discharge static electricity charged in the body.
• Do not touch terminals of parts and patterns implemented
on the PCB.
(1) Remove the cable clamp.
Cord clamp
Screw
(2) Remove screws of the heat exchanger, and then remove
grounding wire. (3) Remove three thermistors. (4) Remove the connector.
CAUTION
• To peel the fi lm from the lead cable, use a dedicated tool that will not damage the conductor cable.
• When installing a screw on the terminal block, do not cut the cable by overtightening the screw. On the other hand, an undertightened screw can cause faulty contact, which will lead to a communication failure.
6. FIELD SETTING
• Refer to the following three items for setting the FIELD SETTING address. The respective settings are included below.
(1) IU AD, REF AD SW settings ............ This section
(2) Remote control settings ................... Refer to the wired or
wireless remote control manual for detailed setting information. (Set IU AD, REF AD SW to 0)
(3) Automatic address settings .............. Refer to the indoor unit
manual for detailed setting information. (Set IU AD, REF AD SW to 0)
Thermistor
Screw
Grounding wire
(5) Remove screw, then remove the control unit.
Screw
Screw
Connector
Control unit
En-11
(6) Set the switches on the PCB.
Indoor unit address
1
Rotary switch (IU AD × 1)...Factory setting “0” Rotary switch (IU AD × 10)...Factory setting “0” When connecting multiple indoor units to one refrigerant
system, set the address at IU AD SW as shown in the Table A.
Refrigerant circuit address
2
Rotary switch (REF AD × 1)...Factory setting “0” Rotary switch (REF AD × 10)...Factory setting “0” In the case of multiple refrigerant systems, set REF AD
SW as shown in the Table A for each refrigerant system.
Set to the same refrigerant circuit address as the outdoor
unit.
Rotary switch
Rotary switch Example: “10”
SW1 SW2 SW3 SW4
Dip switch “SET 3”
Example: “0”
Rotary switch Example: “0”
Table A
Setting
Setting
range
Type of switch
Address
Refrigerant
circuit
0
Rotary
Switch Setting Switch Setting
REF AD SW
× 10 × 1 × 10 × 1
Address
Indoor unit
00 0 00
Rotary
IU AD SW
101101 202202 303303 404404 505505 606606 707707 808808
909909 10 1 0 10 0 0 11 1 1 11 1 1 12 1 2 12 1 2
. . .
. . .
. . .
. . .
. . .
99 9 9 63 6 3
Do not set the indoor unit address (IU AD SW) at 64 to 99. It may result failure.
Remote controller address
3
Rotary switch (RC AD SW)...Factory setting “0” When connecting multiple indoor units to one standard
wired remote controller, set the address at (RC AD SW) in sequence from 0.
Setting
Setting
range
Type of switch
. . .
Indoor unit
address
0–63
Setting
example
2
IU AD × 10 IU AD × 1
Refrigerant
circuit
0–99
address
If working in an environment where the wireless
Setting
example
63
REF AD × 10
REF AD × 1
remote controller can be used, the addresses can also be set using the remote controller.
If setting the addresses using the wireless remote controller, set the indoor unit address and refrigerant circuit address to “00”.
Remote
controller
address
0–15
Setting
example
0
RC AD
Example
Indoor unit
RC AD SW RC AD SW RC AD SW RC AD SW
If 4 indoor units are connected.
Indoor unit Indoor unit Indoor unit
0 1 2 3
Remote controller
RC AD SW Address
RC AD SW Address
01234567 01234567
89ABCDEF 8 9 10 11 12 13 14 15
En-12
6.2. Custom code setting
Function details
Selecting the custom code prevents the indoor unit mix-up. (Up to 4 codes can be set.) Perform the setting for both the indoor unit and the remote controller.
Indoor unit
Remote controller
Custom code setting for indoor unit
Confusion
Code change
A B C D
A B C D
Set the DIP SET 3 SW1, SW2 referring to the Table B.
SW1SW2SW3SW
ON
OFF
Dip switch
4
"SET 3"
Table B
Custom code
A (Factory setting) B C D
DIP SW
SET 3 SW1
DIP SW
SET 3 SW2
OFF ON OFF ON
OFF OFF ON ON
6.3. Function setting
• FUNCTION SETTING can be performed with the wired or wireless remote control.
(The remote control is optional equipment)
• Refer to the wired or wireless remote control manual for detailed setting information. (Set IU AD, REF AD SW to 0)
• Refer to “6.1. Setting the address” for indoor unit address and refrigerant circuit address settings.
• Turn the power of the indoor unit ON before starting the setting.
Function
Function
indicator
indicator
temperature
temperature
External
number
Filter
interval
Filter
action
Cool air
trigger
Hot air
trigger
Auto
restart
control
Error report target
11
13
30
31
40
46
47
Setting
number
00 Default
01 Longer
02 Shorter
00 Enable
01 Disable
Display only on
02
central remote control
00 Default
01 Adjust (1)
02 Adjust (2)
00 Default
01 Adjust (1)
02 Adjust (2)
03 Adjust (3)
00 Enable
01 Disable
00 Start/Stop
Emergency
01
stop
00 All
Display only on
01
central remote control
Default
6.3.1. Button name and function
Details
Adjust the fi lter cleaning interval notifi cation. If the notifi cation is too early, change to setting
01. If the notifi cation is too late, change to setting 02.
Enable or disable the fi lter indicator. Setting 02 is for use with a central remote control.
Adjust the cool air trigger temperature. To lower the trigger temperature, use setting 01. To raise the trigger temperature, use setting 02.
Adjust the hot air trigger temperature. To lower the trigger temperature by 6 degrees C, use setting 01. To lower the trigger temperature by 4 degrees C, use setting 02. To raise the trigger temperature, use setting 03.
Enable or disable automatic system restart after a power outage.
Allow an external controller to start or stop the system, or to perform an emergency shutdown. * If an emergency shutdown is
performed from an external controller, all refrigerant sys­tems will be disabled.
Change the target for reporting errors. Errors can either be reported in all locations, or only on the wired remote.
* Turning on the power indoor units initializes EEV, so
make sure the piping air tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were
made before turning on the power.
FILTER indicator lamp (Red)
TIMER indicator lamp (Orenge)
OPERATION indicator lamp (Green)
En-13
6.3.2. Checking the function settings
(2) Others
• Press and hold the “MANUAL AUTO” button on the indoor unit for 3 seconds to check the function settings. It is necessary to disconnect the power in order to return to normal operation mode.
(1) Indoor unit and refrigerant address indication
Indication pattern
Indicator name
Indoor unit address Refrigerant address
OPERATION indicator lamp
ON
(Green) TIMER
indicator lamp (Orange)
Address: tens place (0.5s ON/0.5s OFF)
FILTER indicator lamp
Address: ones place (0.5s ON/0.5s OFF)
(Red)
• Indoor unit address example
Indication pattern
Flash (1.0s ON/1.0s OFF)
(Example) ADDRESS : 24
1 cycle 12 sec
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
ON
OFF ON
OFF ON
OFF
0.5s
0.5s
0.5s 0.5s 0.5s
0.5s
0.5s 0.5s
0.5s
0.5s
0.5s 0.5s
ON
10 sec
8 sec
Indication pattern
Indicator Name Indication pattern
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
Function number; tens place (0.5s ON/0.5s OFF)
Function number; ones place (0.5s ON/0.5s OFF)
Setting number: (0 - 9) (0.5s ON/0.5s OFF)
(Example) Function : 31, Setting number : 2
1 cycle 12 sec
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
ON
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s 0.5s 0.5s
0.5s
0.5s
OFF
ON
0.5s OFF ON
0.5s
OFF
6.4.
Connecting the wired remote controller
9 sec
11 sec
10 sec
(If necessary)
In order to connect the wired/simple remote control to the external switch controller, the wire assembly (Accessories) which is attached to the indoor unit needs be connected to the end of remote control cable.
(1) Use a tool to cut off the terminal on the end of the remote
control
cable
end of the
, and then remove the insulation from the cut
cable
as shown below.
• Refrigerant address example
(Example) ADDRESS : 30
1 cycle 12 sec
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
ON
OFF ON
OFF ON
OFF
1.0s 1.0s 1.0s 1.0s
1.0s 1.0s 1.0s
0.5s
0.5s 0.5s 0.5s 0.5s
0.5s
OFF
9 sec
• Setting details
Function number Item Setting number
01 Indoor unit address 00~63
02 Refrigeration address 00~99
For use with a remote control, set all rotary switches to 0, and refer to “6.1. Setting the address” for details. All switches are set to 0 at the factory.
20 mm
Remote control cable
(2) Connect the remote controller cable and wire assembly as
shown below.
White
Red
Black
White
Red
Remote control cable
Insutated connection
Black
(3) Connect the cable of wired remote control unit to the PCB of
Control unit.
(4) Fasten the remote control cable to the EV kit cable with the
binder as shown below.
En-14
PCB
Connector
10 mm or less
To EV kit
Binder
6.5. Installing the control unit
Refer to 6.1 (1) ~ (5) to install the control unit, thermistor, and grounding wire.
(1) Connect the connection cable.
OK NO GOOD
EV kit cable
(2) Install the cable clamp.
Cable clamp
L, N: Power supply cable
X1, X2: Transmission cable
Connect
Cable
Screw hole
Do not route the cables over the screw hole.
EV kit cable
After connecting the EV kit cable, slide the tube (included with the EV kit) over the connector to protect it.
Connect Tube
Binder (Small)
Cable
Screw hole
Screw
En-15
7. FINISHING
After completing the refrigerant leak check (for details, refer to the Installation Manual of the outdoor unit), install the insulation.
(1) Insulate between pipes.
• For rear, right, and bottom piping, overlap the connection pipe heat insulation and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap.
• For left and left rear piping, butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them with and vinyl tape so that there is no gap.
Overlap the insulation
Connection pipe (Heat insulation)
Bind the pipes together so that there is no gap.
Vinyl tape
• For left and left rear piping, wrap the area which accommodates the rear piping housing section with cloth tape.
Pipe
Wrap with cloth tape
Drain hose
Cloth tape
• For left and left rear piping, bind the connection cable to the top of the pipe with vinyl tape.
• For left and left rear piping, bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fi t into the rear piping housing section.
(2) Temporarily fasten the connection cable along the
connection pipe with vinyl tape. (Wrap to about 1/3 the width of the tape from the bottom of the pipe so that water does not enter.)
Connection cable –
Wall pipe
Drain hose
Connection pipe
Indoor unit pipe (Heat insulation)
Power supply cable Transmission cable EV kit cable
(7) Install the front panel.
• Firstly, fi t the lower part of the front panel, and insert top and bottom hooks. (Three top sides, six bottom sides)
Bottom hooks (Six position)
Indoor unit
Bottom hole (Six position)
Top holes (Two sides)
Top hole (Center)
Indoor unit
Top hooks (Two sides)
Front panel
Top hook (Center)
Front panel
• Four screws is attached.
(8) Install the intake grille.
• The fi xing axle of the intake grille is installed on the Panel.
• Lay down the intake grille.
(9) Fasten the drain hose to the outside wall, etc.
Check the condition of the drain hose and make sure that it is routed correctly.
OK
No Good No Good
Drain hose
Saddle
Lifted up Wave
CAUTION
No Good
End in water
• Make sure the drain water is properly drained.
8. DECORATION PANEL INSTALLA­TION
(3) Securely fasten the EV kit cable to the indoor unit pipe. (4) Conceal the tube protecting the EV kit connector with the
product, etc., so that the customer cannot access it.
(5) Fasten the connection pipe to the outside wall with saddles,
etc.
(Saddle)
Wall
Pipe
(Outside wall cap)
(Outdoors)
(6) Fill the gap between the outside wall pipe hole and the pipe
with sealer so that rain water and wind cannot blow in.
En-16
• Operate according to the installation Manual DECORATION PANEL.
• Be sure to confi rm there is no gap between the panel and main unit after installing the DECORATION PANEL.
(Sealer putty)
9. TEST OPERATION
11. ERROR CODES
9.1.
Test operation using PCB (Outdoor unit)
• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to be used for the test operation.
9.2. Test operation using Remote Controller
• Refer to the Installation Manual for the remote control unit to perform the test operation using the wireless remote control unit.
• When the air conditioner is being test run, the OPERATION and TIMER indicator lamps fl ash slowly at the same time.
10. CHECK LIST
Pay special attention to the check items below when installing the indoor unit(s). After installation is complete, be sure to check the following check items again.
CHECK ITEMS
Has the indoor unit been installed correctly?
Has there been a check for gas leaks (refrigerant pipes)?
Has heat insulation work been completed?
Does water drain easily from the indoor units?
Is the voltage of the power source the same as that indicated on the label on the indoor unit?
Are the wires and pipes all connected completely?
Is the indoor unit grounded?
Is the connection cable the specified thickness?
Are the inlets and outlets free of any obstacles?
After installation is completed, has the proper operation and handling been explained to the user?
Is the EV kit connected? No cooling, No heating
If not performed
correctly
Vibration, noise, indoor unit may drop
No cooling, No heating
Water leakage
Water leakage
No operation, heat or burn damage
No operation, heat or burn damage
Short circuit
No operation, heat or burn damage
No cooling, No heating
CHECK
BOX
If you use a wired type remote control, error codes will appear on the remote control display. If you use a wireless remote control, the lamp on the photodetector unit will output error codes by way of blinking patterns. See the lamp blinking patterns and error codes in the table below.
Abnormal display
OPERATION
lamp
(green)
(1) (2)
(1) (4)
(1) (6)
(3) (1)
(3) (2)
(4) (1)
(4) (2)
(5) (1)
(5) (3)
(9) (15)
Display mode : 0.5s ON / 0.5s OFF : 0.1s ON / 0.1s OFF ( ) : Number of fl ashing
Wired Remote Controller Display
TIMER
lamp
(orange)
FILTER
lamp
(red)
Wired
Remote
Controller
Error CODE
Error code
Abnormal
contents
Remote control abnormal communication
Anomalous network communications
Abnormal parallel communication
Abnormal power frequency
Abnormal model information / abnormal EEPROM accession
Abnormal room temperature thermistor
Abnormal indoor heat exchanger temperature thermistor
Abnormal indoor fan motor
Abnormal drainage
Abnormal outdoor unit
En-17
VRF 系统 室内机 小型挂壁式 静音型
EEV 外部机型)
仅针对授权的专业维修人员。
目录
1. 安全注意事项 ................................................................. 2
2. 关于机组
2.1. 使用 R410A 制冷剂时的注意事项 ................................ 2
2.2. R410A 的专用工具 .........................................................2
2.3. 附件 .................................................................................2
3. 安装工作
3.1. 选择安装位置 .................................................................3
3.2. 安装尺寸 .........................................................................4
3.3. 安装机组 .........................................................................4
4.
管道安装
4.1. 选择管材 .........................................................................6
4.2. 管道要求 .........................................................................6
4.3. 扩口接头(管接头) .......................................................6
4.4. 安装绝热材料 .................................................................7
5. 电气接线
5.1. 电气要求 .........................................................................8
5.2. 接线方法 .........................................................................8
5.3. 机组接线 .........................................................................8
6. 现场设置
6.1. 设置地址 .........................................................................9
6.3. 功能设置 ......................................................................11
6.2. 用户代码设置 ...............................................................11
6.4. 连接有线遥控器 ( 根据需要 ) ...................................... 12
6.5. 安装控制单元 ...............................................................13
7. 完成 ............................................................................. 14
8. 安装装饰面板 ............................................................... 14
9. 试运转
9.1. 使用 PCB 进行试运转(室外机) ................................14
9.2. 使用遥控器进行试运转 ...............................................14
10. 检查项目表 .................................................................. 15
11. 故障代码 ...................................................................... 15
部件编号 9377773043-02
安全注意事项
1.
2.2. R410A
的专用工具
安装之前务必彻底阅读该说明书。
该说明书指出的警告和注意事项包含与您的安全密切相关的
重要信息。请务必遵循这些信息。
将该说明书与操作手册交给用户。
请用户将它们收藏好,以便日后使用,例如更换机组位置或
对机组进行修理。
警告!
请您的经销商或专业安装人员依照该说明书安装机组。 机组安装不适当可能造成严重的事故,例如漏水、电击或
火灾。
如果没有依照安装说明书中的说明来安装机组,则制造商
不会保用。
未完成所有工作之前请勿打开电源。 在工作完成之前打开电源可能造成严重的事故,例如电击
或火灾。
如果制冷剂在执行工作时泄露,请为该区域通风。 如果制冷剂与火焰接触,它会产生有毒气体。
务必由授权的维修人员按照国家接线标准执行安装工作。
注意!
该标志表示如果步骤执行失当,可能会导 致用户死亡或严重伤害。
该标志表示,如果步骤执行不当,可能会导 致用户人身伤害或财产损害。
警告
若安装使用 R410A 制冷剂的机组,请使用专门为 R410A 制造 的专用工具和管道材料。
因为 R410A 制冷剂的压力大约比 R22 1.6 倍,所以未能使
用专用管道材料或不适当的安装可能造成破裂或伤害。
而且,可能造成严重的事故,例如漏水、电击或火灾。
工具名称 变更内容
压力较高,不能使用传统的压力计测量。为 了避免与其它制冷剂错误混合,每个接口
压力表歧管
充注软管
真空泵
气体泄漏检测器
附件
2.3.
的直径均已更改。
建议使用具有高压力显示范围为-0.1
5.3 MPa以及低压力显示范围为-0.1
3.8 MPa的压力表歧管。
为了增加抗压能力,软管材料和尺寸已变
更。
可以通过安装真空泵适配器使用传统的真 空泵。
• HFC制冷剂R410A的专用气体泄漏检测 器。
关于机组
2.
1
2.1.
使用
R410A
制冷剂时的注意事项
警告
请勿让除规定的制冷剂之外的其他物质进入制冷循环。 如果空气进入制冷循环,则其中的压力将变得异常之高,并且
会造成管道破裂。
如果制冷剂泄漏,请确保它未超过浓度限制。 如果制冷剂泄漏超过了浓度限制,则可能造成缺氧等事故。
请不要触摸从制冷剂管接头等部位泄漏的制冷剂。直接触摸制
冷剂会导致冻伤。
如果运行过程中发生制冷剂泄漏,请立即离开建筑物,并对该 区域彻底通风。
如果制冷剂与火焰接触,它会产生有毒气体。
警告
安装时,请务必使用制造商供应的部件或其他规定部件。 使用非规定部件可能造成严重的事故,例如机组掉落、漏水、
电击或火灾。
本机配有以下安装部件。 请按照需要使用。
请妥善保管安装说明书,并且不要在安装工作完成前丢弃
任何其它附件。
在安装工作完成之前,请勿丢弃安装需要的任何附件。
名称及形状 数量 应用
使用说明书
1
安装说明书
壁挂支架
(本书)
1
用于安装室内机
Sc-2
绑扎件
1
用于绑扎遥控器线
1
名称及形状 数量 应用
布带
自攻螺钉
(M4 × 25mm)
用于安装室内机
1
用于安装壁挂支架
8
安装工作
3.
对于分体式空调,安装地点尤为重要,因为首次安装后,移 动位置非常困难。
选择安装位置
3.1.
警告
选择能有效支撑室内机重量的安装位置。将机组安装牢固,以 免倾倒或坠落。
线束
空气过滤网
空气过滤网框
密封垫A数量
用于安装有线遥控器
1
2
2
用于安装室内机
1
注意
请勿将机组安装在下列区域 :
盐含量高的区域,例如海边。 这会损坏金属部件,使部件掉落或使机组漏水。
充满矿物油或包含大量溅油或蒸气的区域,例如厨房。 这会损坏塑料部件,使部件掉落或使机组漏水。
会产生对设备有负面影响的物质(例如硫磺气体、氯气、酸
或碱)的区域。
这会腐蚀铜管和铜焊接合,从而造成制冷剂泄漏。
会造成可燃气体泄漏、包含悬浮碳化纤维或易燃灰尘或挥发
性可燃物(例如涂料稀释剂或汽油)的区域。
如果气体泄漏并留在机组周围,就可能造成火灾。
动物可能会在机组上排尿或者可能会产生氨的区域。
请勿将机组用于特殊用途,例如存放食物、饲养动物、栽培植
物或保存精密装置或艺术品。
这可能降低保存或存放对象的质量。
请勿安装在可能泄漏易燃性气体的地方。
请勿将机组安装在靠近热源、蒸汽或易燃气体的地方。
将机组安装在排水不会造成任何问题的地方。
请在距离电视机或收音机 1m 以外的地方进行室内机、室外机、
电源线、信号线和遥控器线的安装。 以防止电视接收干扰或 无线电噪声。
(即使在 1m 以外进行了安装,在某些信号条件下可能仍会
接收到噪声。)
10 岁以下的儿童有可能接触到,请采取适当的预防措施, 使他们无法接触机组。
请根据以下准则征询用户意见,决定安装位置 :
(1) 将室内机安装在具有足够强度的地方,以便能承受室内机的
重量。
(2) 不得阻挡进气口和出气口,空气能够流通到整个房间。
(3) 请保留可以维修空调的空间。
(4) 可以让机组排出的空气在整个房间内均匀分布的地方。
(5) 将机组安装在容易连接室内机的地方。
(6) 将机组安装在容易安装连接管的地方。
(7) 将机组安装在容易安装排水管的地方。
(8) 将机组安装在不会将噪音和振动放大的地方。
(9) 应考虑之后的维修等情况,并留出空间。将机组安装在可以
拆卸过滤网的地方。
1
Sc-3
安装尺寸
3.2.
提供用于检查的维修空间。 切勿在维修空间布置线路或照明设施,否则会妨碍维修。
壁挂支架
50 mm
60 mm 或以上
1,500 mm 或以上
1,800 mm 或以上
或以上
90 mm 或 以上
( 墙壁帽 )
排水软管
O.D 15.8 - 16.7 mm I.D 13.8 mm
* 根据房间形状和安装位置从三向或四向中选择最适合的送风
气流。
* 改变出气口数时,建议用选购的出气口百叶窗板组件关闭出
气口。
* 有关具体的关闭型式,请参见附带的出气口百叶窗板组件说
明书。(请在安装装饰面板之前关闭,因为要将其安装在窗 体上。)
* 必须按照送风气流的出气口数和所安装的天花板高度用遥控
器进行功能设置。
安装机组
3.3.
警告
空调安装的位置应能承受至少等于主机重量 5 倍的载荷,且不 会增大噪音或振动。如果安装位置不够坚固,室内机会坠落, 引起人身伤害。
如果仅用面板外框进行施工,会有机组变松的危险。请小心。
安装壁挂支架
3.3.2.
注意
安装壁挂支架应横平坚直。
(1) 安装壁挂支架时要保证其水平和垂直位置正确。如果壁挂支
架倾斜,水会滴到地上。
(2) 安装壁挂支架时要保证其足够坚固,能够承受一个成人的体
重。
将至少 6 个螺钉穿过托架外沿附近的孔中,固定壁挂支 架。
检查壁挂支架有无嘎吱声。
壁挂支架
自攻螺钉
中心缺口
挂钩
壁挂支架
3.3.3. 在连接管的墙壁上钻一个孔
警告
如果不使用穿墙管,连接室内机与室外机的导线可能会接 触金属,引起漏电。
(1) 在图 B 所示位置的墙壁上钻一个 80 mm 直径的孔。
(2) 在壁挂支架内侧钻墙壁孔时,要在壁挂支架以下 40 mm 的左
右中心标记范围内钻孔。
在壁挂支架外侧钻墙壁孔时,要在向下至少 10 mm 处钻孔。
(3) 钻孔时,外端要比内端低(5 10 mm
(4) 务必对准墙壁孔的中心。如果不对准,会发生漏水。
(5) 将穿墙管切至墙壁的厚度,将其插入墙壁帽中,用聚氯乙烯
绝缘带固定墙壁帽,使管路穿过孔。(安装组件中附带连接管。)
(图 B
(6) 对于左管和右管,钻孔位置要稍低一些,以便于顺利排水。
(图 B
B
壁挂支架
中心标记
确定管路方向
3.3.1.
可以按 ( 图 A) 中1,2,3,4,5指示的五个方向连接管路。 以方向2或5连接管路时,用钢锯沿著前盖一侧的管槽切割。 以方向3连接管路时,在前盖前面底部的薄壁上切一个缺口。
A
( 后侧 )
后侧出口
右侧出口
2
底部出口
3
1
左后侧出口
4
Sc-4
左侧出口
5
80 mm 直径的孔
用聚氯乙烯 绝缘带固定
( 墙壁帽 )
5
10 mm
( 穿墙管 )
( 内侧 ) 墙壁
10 mm 或 以上
80 mm 直径的孔
( 外侧 )
安装排水软管和管路
3.3.4.
注意
为了对准排水软管和排水帽,必须牢靠地垂直插入。插入倾 斜会引起漏水。
插入时,不得沾有除水以外的其它材料。如果沾有其它材料, 会引起变质和漏水。
[ 排水软管的拆卸方法 ]
拆下排水软管左侧的螺钉,拉出排水软管。
螺钉
排水软管
拆下排水软管后,切勿忘记安装排水帽。
必须用胶带将排水软管固定在管路底部。
[ 后管、右管、底部管 ]
(1) 按照墙壁孔的方向安装室内机管路,用聚氯乙烯绝缘带将排
水软管和管路固定在一起。
右管
底部管
用聚氯乙烯绝缘带固定
管路(顶部)后管
室内机排水软管(底部)
(2) 安装管路时,要使排水软管位于底部。
(3) 用彩色胶带缠绕可以从外面看到的室内机管路。
[ 左后管、左管 ]
(1) 交换排水帽,绝热材料和排水软管。
安装左侧出口管时,用钢 锯切下管路出口切割槽。
用钳子等工具夹住排水帽 端的突出部位向外拉,拆
绝热材料
室内机排 水软管
排水帽
下排水帽。 然后拆下绝热材料。
(2) 对准壁挂支架上的标记,将连接管弯曲成形。
排水定位器(蓝色)
[ 排水软管、的安装方法 ]
垂直向内侧插入排水软管,使排水定位器(蓝色)与排水阀周围 的螺钉孔精确对准。 请在插入后和更换前将拆下的螺钉重新装好固定。
排水定位器(蓝色)
螺钉孔
排水阀
螺钉
排水软管
必须安装在排水软管的管接头上。
因为螺钉在内侧,所以必须使用经磁化处理的螺丝刀。
3.3.5. 安装室内机
(1) 使室内管路和排水软管穿过墙壁孔后,将室内机悬吊在位于
壁挂支架顶部和底部的挂钩上。
连接管
2 mm 直径)
室内机
(配件)
(2) 拆下回风格栅。
打开回风格栅。
1
回风格栅
顶部挂钩
壁挂支架
底部挂钩
用弯管机弯曲(R70
连接管(气体管)
对准标记。
(3) 以至少 70 mm 的弯曲半径弯曲连接管,安装时距离墙壁不超
35 mm
排水盖的安装方法
请将绝热材料一直放到里面。
用六角扳手(对侧为 4mm)插入排水盖,直到排水盖接触
到排水旋塞的顶部。
无缝隙
六角扳手
无缝隙
排水旋塞
绝热材料
排水盖
连接管(液体管)
2
1
拉下旋钮。
2
回风格栅
旋钮
向上抬起回风格栅,直到回风格栅顶部的轴被拆下。
3
2
1
(3) 拆下前面板。
将拇指勾在图中所示的底部,向前拉,按 [-] 标记,将底部
1
挂钩(两处)从壁挂支架上拆下。
向前拉前面板的底部,将底部挂钩从室内机上拆下。
2
按下
[-]
标记
按下
螺钉(4 处)
前面板
壁挂支架
Sc-5
向前拉前面板,抬起上面,将前面板拆下。
3
(4) 将垫片等插入室内机与壁挂支架之间,将室内机的底部与墙
壁隔开。
室内机
壁挂支架
管道安装
4.
要小心注意的是,杂质(油、水等)不会像制冷剂 R410A 型 号那样进入管道。另外,存放管道时,通过夹住、捆绑等牢 固密封管口。
焊接管道时,务必向里面冲入干燥的氮气。
选择管材
4.1.
注意
前面板
垫片
使用带防水绝热材料的管道。
注意
请在气体和液体管道周围安装绝热材料。否则可能会导致漏 水。
请使用抗热能力超过 120℃的绝热材料。(仅限逆循环型) 此外,如果安装制冷剂管道的地方的湿度可能会超过 70%
请在制冷剂管道周围安装绝热材料。如果预计的湿度为 70-80%,请使用 15 mm 或更厚的绝热材料 ;如果预计的湿度 超过 80%,请使用 20 m m 或更厚的绝热材料。如果使用的绝 热材料未达到指定的厚度,可能会在材料表面形成冷凝。
此外,请使用热传导率为 0.045 W/m•K)或以下(20° C 时)
的绝热材料。
扩口接头(管接头)
4.3.
警告
请用扭矩扳手按照指定的方法紧固扩口螺母。如果扩口螺母拧 得太紧,长时间后扩口螺母会破裂而导致冷媒泄漏,如果接触 明火,会产生有毒气体。
4.3.1. 扩口
请使用专用的切管机和 R410A 专用的扩口工具。 (1) 使用切管机将连接管截成所需的长度。
(2) 向下握住水管以避免切屑进入管道并去除毛刺。 (3) 将扩口螺母(必须使用分别连接到室内机和室外机的扩口螺
母)插入管道,并使用扩口工具执行扩口工序。请使用专用 的 R410A 扩口工具或传统的扩口工具。如果使用其它扩口螺 母,会导致制冷剂泄漏。
(4) 请夹住或用胶带保护管道,防止灰尘、污物或水进入管道。
注意
不要使用原有的管道。
使用的管道应内外表面清洁,不含在使用过程中可能引起故
障的污染物,例如硫、氧化物、灰尘、切屑、油或水。
必须使用无缝铜管。 材料 :经过磷脱氧处理的无缝铜管。 残油量最好小于 40 mg/10 m
使用的铜管不能带有压扁、变形或变色的部分(尤其是在内
部表面)。否则,膨胀阀或毛细管可能会被污染物堵塞。
管道选择不当会降低性能。由于使用 R410A 的空调会比使用 传统的制冷剂时承受更高的压力,因此需要选择适当的材料。
使用 R410A 的铜管厚度如表所示。
绝对不要使用厚度不足于表中所示的铜管,即使市场上有售。
退火铜管的厚度(R410A
管外径 [mm (in.)] 厚度 [mm]
6.35 (1/4) 0.80
9.52 (3/8) 0.80
12.70 (1/2) 0.80
15.88 (5/8) 1.00
19.05 (3/4) 1.20
管道要求
4.2.
注意
• 有关连接管道长度或不同标高的规格,请参见室外机的安装
说明书。
管道外径
[mm (in.)]
6.35 (1/4)
尺寸 A [mm]
的扩口工具,
R410A
离合式
尺寸
[mm]
9.1
B
-00.4
9.52 (3/8) 13.2
12.70 (1/2) 16.6
0 0.5
15.88 (5/8) 19.7
19.05 (3/4) 24.0
当使用传统的扩口工具对 R410A 管道进行扩口时,尺寸 A 应 比表中(针对使用 R410A 扩口工具进行扩口)所指的多大约
0.5 mm 以获得指定的扩口。使用厚度测量仪测量尺寸 A
管道外径
[mm (in.)]
扩口螺母的扳手开口
宽度 [mm]
6.35 (1/4) 17
9.52 (3/8) 22
12.70 (1/2) 26
15.88 (5/8) 29
19.05 (3/4) 36
Sc-6
4.3.2. 弯管加工
如果用手使管道成形,注意请勿将它们压扁。
弯曲管道时角度不应超过 90°。
如果反复弯曲或拉伸管道,材料将变硬,以至很难再次弯曲或
拉伸。
弯曲或拉伸管道的次数不应超过三次。
注意
为了防止管道破裂,应避免过度的弯曲。
检查是否漏气后,用接管绝热材料在室内机接管的两个部分
(供气和供液)缠绕绝热材料进行绝热。
安装接管绝热材料后,用聚氯乙烯绝缘带缠绕两端使其不留 缝隙。
如果管道在同一位置反复弯曲,它会破裂。
4.3.3. 管道连接
注意
连接的 EV 组件(选购)必须适用于室内机。
有关安装说明,请参见 EV 组件的安装说明书。
必须使管路正确对准室内机的端口。如果定心不正确,扩口
螺母将无法顺利拧紧。如果强制拧紧扩口螺母,会损坏螺纹。
只有在对连接管道进行连接之前才能从室内机管道上拆除扩 口螺母。
握住扭矩扳手的手柄,使其与管道成 90 度,以便正确地拧紧 扩口螺母。
按照指定的拧紧方法,用扭矩扳手拧紧扩口螺母。否则长时 间以后,扩口螺母会破裂,导致制冷剂泄漏,如果制冷剂与 火焰接触,还会产生有害气体。
当用手将扩口螺母适当地拧紧时,请用单独的扳手将机身侧 的接管扳住,然后用扭矩扳手拧紧。
注意
必须紧密贴在主机上不留缝隙。
电气接线
5.
警告
必须由持有证书的人员在国家或地方条例的规定下依照该说明 书执行电气工作。务必对机组使用专用电路。
电源不足的电路或错误执行的电气工作可能造成严重的事故,
例如电击或火灾。
开始工作前,检查室内机和室外机是否没有通电。
对于接线,请使用规定的电线类型,牢固地连接电线,确保电
线上没有外力施加到终端连接上。
错误连接或固定的电线可能造成严重的事故,例如终端过热、
电击或火灾。
将电气盒盖牢固地安装在机组上。
不适当安装的电气盒盖可能由于接触灰尘或水而造成严重的事
故,例如电击或火灾。
请使用壁孔用管。如果不使用,有时会引起漏电等。
连接源线,请使用附属品及指定元件。否则可能会因接触不良、
绝缘不良、超过额定电流而导致触电、火灾。
扩口螺母 [mm (in.)] 拧紧扭矩 [N·m (kgf·cm)]
6.35 (1/4) dia. 16 18 (160 180)
9.52 (3/8) dia. 32 42 (320 420)
12.70 (1/2) dia. 49 61 (490 610)
15.88 (5/8) dia. 63 75 (630 750)
19.05 (3/4) dia. 90 110 (900 1,100)
选择 EV 组件
机型 适用的EV组件
E07/09L UTR-EV09XB
AS AS
E12/14L UTR-EV14XB
安装绝热材料
4.4.
注意
检查是否漏气(请参见室外机的安装说明书)后,请按照本 章节的说明进行操作。
请在大管道(气体)和小管道(液体)周围安装绝热材料。 否则可能会导致漏水。
请勿加工电源线、使用延长线、分歧配线。否则可能会因接触 不良、绝缘不良、超过额定电流而导致触电、火灾。
将接线盒号码与室外机上的连接线颜色相匹配。错误的接线可 能会导致电气部件烧毁。
请将端子盘上的连接电缆安装牢靠。或是使用“配线压头”加 以固定。对连接电缆进行中段连接、或插入固定不牢靠,可能 会导致故障、触电、火灾等。
必须用线夹固定连接线的绝缘层。 (如果绝缘层未被夹住,可 能会发生漏电。)
请安装漏电开关。若要安装时,请将交流总电源全部同时切断。 如果不安装漏电开关,可能会导致触电及火灾。
安装漏地断路器。
如果没有安装漏地断路器,则可能造成电击或火灾。
必须连接地线。
不当的接地工作可能会导致触电。
安装遥控器导线时,要确保不会用手直接触摸到。
按照标准进行接线工作,以便空调器可以安全无故障地运行。
将连接电缆牢固地连接在接线板上。不正确的安装可能会导致
火灾。
Sc-7
注意
将机组接地。 请勿将地线连接到气体管、水管、避雷针或电话地线。 不适当的接地可能造成电击。
请勿将电源线连接到信号线或遥控器接线端,因为这会损坏该
产品。
机组接线
5.3.
将电线连接到接线板之前。
5.3.1. 电源线
绝不要将电源线和信号线束在一起。将这些线束在一起会导致 错误运行。
操作 PCB 时,机身上的静电可能造成控制 PCB 发生故障。请 遵循下列注意事项 :
对室内和室外机组以及外围设备使用接地线。
切断电源(断路器)。
请触摸室内和室外机组金属部分 10 秒以上,以释放机身静
电。
请勿触碰接线 PCB 上的部件端子和布线模式。
电气要求
5.1.
198 - 264 V
2
(mm
)
230 V
245 IEC57或相
当品
电线类型 备注
1ø 50 Hz 198-264 V 2 电线 + 地线
额定电压 操作范围
电缆尺寸推荐值
电源线 2.5
22 AWG LEVEL
信号线 0.33
LONWORKS
兼容线
4 NEMA 非极 性双芯双绞实芯 线,直径0.65 mm
遥控器线 0.33
聚氯乙烯外皮 电缆*
极性3芯 双绞线
*: 根据当地规则,对遥控器使用屏蔽电缆。
接线方法
5.2.
(示例)
电源
室外机
信号线
断路器
EV 组件
电源
200 mm
地线
220 mm
电源线
对于实心接线
A.
(1)
要连接电气端子,请在将电线的端部结环后按照下图进行连接。
(2) 将指定的电线牢固地连接,并将其固定,使端子上没有压力。
(3) 使用适合的螺丝刀拧紧端子螺钉。
请勿使用过小的螺丝刀,否则可能会损坏螺钉头并造成螺钉
无法正确紧固。
(4) 请勿将端子螺钉拧得过紧,否则螺钉可能会破裂。
(5) 请参见表中的端子螺钉拧紧扭矩。
(6) 请不要用一颗螺丝固定两根电源线。
25 mm
剥去
线圈
带特殊垫片的
电线
螺钉
电线端部
(环)
电线
接线盒
带特殊垫片的 螺钉
电线端部
(环)
挂壁式
信号线 信号线 信号线
电源
遥控
电源
遥控器 遥控器
电源 电源
室内机 室内机
断路器 断路器断路器
电源 电源
Sc-8
遥控
警告
使用实心线时,请勿使用附带的环形端子。如果将实心线用于 环形端子,环形端子的气压粘结可能会出现故障并导致电线异 常发热。
对于绞合线
B.
(1) 使用下图中所示的带有绝缘套管的环形端子连接接线盒。
(2) 使用适合的工具将环形端子牢固地夹紧到电线,这样电线就
不会松散。
(3) 将指定的电线牢固地连接,并将其固定,使端子上没有压力。
(4) 使用适合的螺丝刀拧紧端子螺钉。
请勿使用过小的螺丝刀,否则可能会损坏螺钉头并造成螺钉
无法正确紧固。
(5) 请勿将端子螺钉拧得过紧,否则螺钉可能会破裂。
(6) 请参见表中的端子螺钉拧紧扭矩。
(7) 请不要用一颗螺丝固定两根电源线。
剥去 10 mm
环形端子
套管
如图 C 所示连接遥控和传输电缆。
C
直径不同 连接到同
正确 不正确 不正确
警告
将端子螺钉拧紧到指定的扭矩,否则可能会发生异常过热并可 能导致机组内部的严重损坏。
一端
拧紧扭矩
M4 螺钉
(信号线 /X1, X2
0.8 1.2 N·m
(8 12 kgf·cm)
带特殊垫片的 螺钉
环形端子
电线
接线盒
使用环形端子并将端子螺钉拧紧到指定的扭矩,否则可能会发 生异常过热并可能导致机组内部的严重损坏。
警告
电线
带特殊垫片的 螺钉
环形 端子
拧紧扭矩
M4 螺钉
(电源线 /L, N, GND
1.2 1.8 N·m
(12 18 kgf·cm)
5.3.2. 信号线和遥控器线
40 mm
屏蔽电线
(无绝缘层)
75 mm
注意
要剥去引线上的绝缘层,请使用不会损坏导线的专用工具。
在接线盒上安装螺钉时,请勿过度拧紧螺钉而折断电线。同时,
过度拧紧的螺钉可能造成错误接触,从而导致通信故障。
6. 现场设置
要设置现场设置地址,请参考下列 3 个项目。 以下包括了相 应的设置。
(1) IU AD, REF AD SW 设置 ........ 本部分内容
(2) 遥控器设置 ............................... 有关详细的设置信息,请参考有
线或无线遥控器的说明书。(将
IU AD, REF AD SW 设为 0)
(3) 自动地址设置 ........................... 有关详细的设置信息,请参考室
内机的说明书。 (将 IU AD, REF AD SW 设为 0
6.1. 设置地址
手动地址设置方法
注意
设置 DIP 开关时,请使用绝缘的螺丝刀。
操作 PCB 时,人体所带静电会引起 PCB 故障。请遵守以下注
意事项 :
触摸室内机和室外机的金属件 10 秒以上,以放掉人体所带 的静电。
切勿触摸 PCB 上的零件端子和所形成的电路。
信号线
Sc-9
(1) 拆下线夹。
旋转开关 示例 :“0
旋转开关 示例 :“0
线夹
螺钉
(2) 拆下热交换器的螺钉,然后拆下地线。
(3) 拆下 3 个热敏电阻。
(4) 拆下插头。
热敏电阻
螺钉
地线
(5) 拆下螺钉,然后拆下控制单元。
插头
控制单元
SW1 SW2 SW3 SW4
Dip 开关
SET 3
旋转开关 示例 :“0
A
设置
室内机地址 0–63
设置 范围
开关类型
设置示例
2
IU AD×10 IU AD×1
制冷剂回路
地址
如果工作环境允许使用无线遥控器, 也可以用遥控
0–99
设置示例
63
REF AD×10
REF AD×1
器设置地址。
如果用无线遥控器设置地址, 应将室内机地址和制 冷剂回路地址设为 「00」。
螺钉
螺钉
(6) 设置 PCB 上的开关。
室内机地址
1
旋转开关 (IU AD×1)...... 出厂设置“0
旋转开关 (IU AD×10)...... 出厂设置“0
将多台室内机连接到一个制冷剂系统时,请参见表 A IU
AD SW 处的地址。
制冷剂回路地址
2
旋转开关 (REF AD×1)...... 出厂设置“0
旋转开关 (REF AD×10)...... 出厂设置“0
在有多个制冷剂系统的情况下,请按表 A 所示为每个制冷
剂系统设置 REF AD SW
设置为与室外机相同的制冷剂回路地址。
地址
制冷剂
回路
0
旋转开关
设置 设置
REF AD SW
×10 ×1 ×10 ×1
地址
室内机
00 0 00
旋转开关
IU AD SW
101101 202202 303303 404404 505505 606606 707707 808808
909909 10 1 0 10 0 0 11 1 1 11 1 1 12 1 2 12 1 2
. . .
. . .
. . .
. . .
. . .
99 9 9 63 6 3
请勿在6499之间设定室内机地址(IU AD SW)。 否则可能会导致故障。
. . .
Sc-10
遥控器地址
3
旋转开关 (RC AD SW) ...... 出厂设定为“0
将多台室内机连接到一个标准有线遥控器时,请从 0 开始
顺次设置 RC AD SW 处的地址。
设置
设置 范围
开关类型
B
DIP SW
SET 3 SW1
DIP SW
SET 3 SW1
用户代码
A(出厂设置) BCD
关(OFF)开ON)关(OFF)开(ON
关(OFF)关OFF)开(ON)开(ON
遥控器地址 0–15
设置示例
0
RC AD
示例
如果安装了 4 台室内机。
室内机 室内机 室内机 室内机
RC AD SW RC AD SW RC AD SW RC AD SW
0 1 2 3
遥控器
RC AD SW
地址
RC AD SW
地址
6.2.
01234567 01234567
8 9ABCDE F 8 9 10 11 12 13 14 15
用户代码设置
选择用户代码可以防止室内机信号混同。 ( 可以设置多达 4 个代码。) 为室内机和遥控器执行该设置。
室内机
混同
遥控器
代码变化
A B C D
A B C D
室内、机的自定义代码设置
参考表 B 设置 DIP SW SET 3 SW1, SW2
SW1SW
ON
SW
SW
2
4
3
6.3. 功能设置
可以使用有线或无线遥控器执行功能设置。 (遥控器为选购设备)
有关详细的设置信息,请参考有线或无线遥控器的说明书。 (将 IU AD, REF AD SW 设为 0
有关室内机地址和制冷剂回路地址设置,请参考“6.1 设置
地址”。
开始设置之前,请打开室内机的电源。
* 打开电源时,室内机初始化 EEV,所以请确保在打开电源
之前已执行了管道气密性测试和抽真空作业。
* 打开电源前,请再次检查以确保没有接线错误。
功能说明
功能
过滤网指 示器间隔
过滤网指 示器操作
冷空气温
度触发
热空气温
度触发
自动重新
启动
外部 控制
故障报告
对象
功能 号码
设置号码
00 默认设置 调节过滤网清洁间隔通知。如 01 较长
11
02 较短
00 启用 01 禁用
13
30
31
40
46
47
仅在中央
02
遥控器上
显示
00 默认设置 01 调节(1) 02 调节(2) 00 默认设置 调节热空气触发温度。要降低 01 调节(1) 02 调节(2)
03 调节(3)
00 启用 01 禁用 00 启动/停止 允许外部控制器启动或停止
01 紧急停止
00 所有
仅在中央
01
遥控器上
显示
默认 设置
果通知时间过早,更改为设置 01。如果通知时间过迟,更改 为设置02
启用或禁用过滤网指示器。设 置02适用于中央遥控器。
调节冷空气触发温度。要降低 触发温度,使用设置01。要提 高触发温度,使用设置02
触发温度6摄氏度,使用设置 01。要降低触发温度4摄氏度, 使用设置02。要提高触发温 度,使用设置03
电源中断后,启用或禁用自动 系统重新启动。
系统,或者执行紧急关机。 * 如果从外部控制器执行紧急
关机,将禁用所有制冷剂系 统。执行紧急关机后,系统 将自动恢复并返回其原始 状态。
更改报告故障的对象。可以在 所有位置报告故障,也可以只 在有线遥控器上报告故障。
说明
OFF
Dip 开关
"SET 3"
Sc-11
6.3.1. 按钮名称和功能
定时器(TIME)指示灯(橙色)
运行(OPERATION)指示灯(绿色)
过滤网(FILTER)指示灯(红色)
(2) 其它
指示方式
指示器名称 指示方式
运转(OPERATION) 指示灯(绿色)
定时器(TIMER) 指示灯(橙色)
过滤网(FILTER) 指示灯(红色)
(示例)功能 :31,设置号码 :2
运转
OPERATION)
指示灯(绿色) 定时器
TIMER
指示灯(橙色) 过滤网
FILTER
指示
点亮
0.5 秒 熄灭 点亮
0.5 秒 熄灭 点亮
0.5 秒 熄灭
(红色)
连接有线遥控器 ( 根据需要 )
6.4.
功能号码 ;10 处
0.5 秒开/ 0.5 秒关)
功能号码 ;1 处
0.5 秒开/ 0.5 秒关)
设置号码 :(0-9
0.5 秒开/ 0.5 秒关)
0.5
0.5
0.5 0.5 0.5
0.5
0.5
0.5
0.5
12 1 个循环
9
11
10
6.3.2. 检查功能设置
按住室内机上的“手动 自动(MANUAL AUTO)”按钮 3 秒 钟以检查功能设置。要返回到正常运转模式,需要切断电源。
(1) 室内机和制冷剂地址指示
指示方式
指示器名称
运转(OPERATION) 指示灯(绿色)
定时器(TIMER) 指示灯(橙色)
过滤网(FILTER) 指示灯(红色)
室内机地址示例
(示例)地址 :24
运转
OPERATION)
指示灯(绿色) 定时器
TIMER
指示灯(橙色) 过滤网
FILTER
指示
(红色)
点亮
熄灭 点亮
熄灭 点亮
熄灭
制冷剂地址示例
(示例)地址 :30
运转
OPERATION)
指示灯(绿色) 定时器
TIMER
指示灯(橙色) 过滤网
FILTER
指示
(红色)
点亮
熄灭 点亮
熄灭 点亮
熄灭
室内机地址 制冷剂地址
点亮
地址 :10 处(0.5 秒开/ 0.5 秒关)
地址 :1 处(0.5 秒开/ 0.5 秒关)
0.5
0.5 0.5
0.5
0.5
0.5 0.5 0.5
0.5
1.0 1.0 1.0 1.0
1.0 1.0 1.0
0.5
0.5 0.5 0.5 0.5
0.5
指示方式
闪烁
1.0 秒开/ 1.0 秒关)
12 1 个循环
点亮
10
0.5
0.5 0.5
12 1 个循环
9
熄灭
8
为了将有线遥控器 / 简易遥控器连接到外部开关控制器,需要将
固定在室内机上的线束(标准部件)连接到遥控器线的一端。
(1) 用工具切下遥控器线一端的端头,然后按下图所示剥下导线
切割端的绝缘皮。
20 mm
遥控器线
(2) 按下图所示连接遥控器线与线束。
白色
红色
黑色
白色
红色
绝缘连接
遥控器线
黑色
(3) 将有线遥控单元的导线连接到控制单元的 PCB (4) 按下图所示用绑扎件将遥控器线固定到 EV 组件线上。
PCB
设置详情
功能号码 项目 设置号码
01 室内机地址 00~63
02 制冷剂地址 00~99
用于遥控器时,将所有的旋转开关设为 0,有关详细信息,请参 考“6.1. 设置地址”。 出厂时,所有开关都被设为 0
Sc-12
插头
EV 组件
绑扎件
6.5. 安装控制单元
要安装控制单元、热敏电阻和地线,请参见图 6.11)至(5)。
(1) 连接连接电缆。
正确 不正确
EV 组件线
(2) 安装线夹。
L, N: 电源线
X1, X2: 信号线
连接
导线
切勿使导线穿过螺钉孔。
EV 组件线
连接 EV 组件线后,将管子(包含 EV 组件)推 过插头对其进行保护。
连接 管子
螺钉孔
绑扎件(小)
导线
螺钉孔
线夹
螺钉
Sc-13
7. 完成
完成制冷剂泄漏检查后 (有关详细信息, 请参见室 外机的安装说明页), 安装绝热材料。
(1) 在管路之间安装绝热材料。
对于后管、右管和底部管,将连接管的绝热材料和室内机
管路的绝热材料搭接在一起,用聚氯乙烯绝缘带固定,使 其没有缝隙。
对于左管和左后管,将接连接管的绝热材料和室内机管路 的绝热材料对接在一起,用聚氯乙烯绝缘带固定,使其没 有缝隙。
连接管
(绝热材料)
将管路固定在一起, 使其没有缝隙。
对于左管和左后管,用布带缠绕包含后管壳部分的区域。
搭接绝热材料
室内机管路(绝热材料)
聚氯乙烯绝缘带
顶部挂钩(两侧)
顶部孔(中心)
室内机
固定 4 个螺钉。
(8) 安装回风格栅。
将回风格栅的固定轴安装在面板上。
放下回风格栅。
(9) 将排水软管固定到外墙壁等处。
检查排水软管的情况,确保其方向正确。
正确
排水 软管
鞍形架
不正确 不正确
顶部孔(两侧)
顶部挂钩(中心)
前面板
不正确
管路
用布带缠绕
排水软管
对于左管和左后管,用聚氯乙烯绝缘带将连接线固定在管 路的顶部。
对于左管和左后管,用布带缠绕管路和排水软管插入后管 壳部分的区域,将它们固定在一起。
(2) 用聚氯乙烯绝缘带沿连接管暂时固定连接线。(缠到距离管路
底部大约 1/3 绝缘带宽度之处,使水不会进入。)
穿墙管
排水软管
(3) EV 组件线牢靠地固定在室内机管路上。
(4) 用产品等将 EV 组件插头的保护管隐蔽起来,使用户接触不到。
(5) 用鞍形架等将连接管固定到外壁上。
(鞍形架)
管路
(6) 用密封胶填塞外穿墙管孔与管路之间的缝隙,使雨水和风不
能吹入。
(7) 安装前面板。
先安装前面板的下部,插入顶部和底部挂钩。(3 个顶边,
6 个底边)
布带
连接线—
墙壁
(外墙壁帽)
(室外)
电源线 信号线 EV 组件线
连接管
(密封腻子)
底部挂钩(6 处)
提起 波纹
请确保排水操作正常。
安装装饰面板
8.
注意
端部没入水中
请按照装饰面板的安装说明书操作。
安装装饰面板之后,必须确认面板与主机之间没有缝隙。
试运转
9.
9.1.
使用
进行试运转(室外机)
PCB
如果使用室外机的 PCB 来进行试运转,请参考本安装说明 书了解室外机。
使用遥控器进行试运转
9.2.
要使用无线遥控器来进行试运转,请参考遥控器的安装说明 书。
对空调器进行试运转时,运转和定时器指示灯同时缓慢地闪 烁。
室内机
底部孔(6 处)
Sc-14
前面板
检查项目表
10.
安装室内机(组)时,请特别注意以下的检查项目。安装完成后, 请确保再次检查以下的检查项目。
检查项目 如果未正确执行 检查框
正确地安装了室内机了 吗?
已检查气体泄漏(制冷剂管 道)了吗?
已完成绝热工作了吗? 漏水 室内机组排水容易吗? 漏水 电源电压与室内机标签上
显示的相同吗? 电线和管道全都连接正确
吗? 室内机接地了吗? 短路 连接电缆具有规定的粗细
吗? 保持进口和出口无阻塞物
了吗? 安装完成后,向用户说明正
确的操作和处理了吗? 是否连接了EV组件? 无制冷,无制热
振动,噪音,室内机可能 掉落
无制冷,无制热
不运转,发热或烧坏
不运转,发热或烧坏
不运转,发热或烧坏
无制冷,无制热
有线遥控器显示
故障代码
故障代码
11.
如果您使用有线型遥控器,则故障代码将显示在遥控器的显示屏 上。如果您使用无线遥控器,机组上的指示灯将通过各种闪 烁的
组合输出故障代码。请参阅下表中的指示灯闪烁组合和故障
代码。
故障显示
运转
指示器
(绿色)
定时器 指示器
(橙色)
(1) (2) 遥控器通信故障
(1) (4) 网络通信故障
(1) (6) 并行通信故障
(3) (1) 电源频率异常
(3) (2)
(4) (1) 室温热敏电阻故障
(4) (2)
过滤网 指示器
(红色)
有线遥 控器故 障代码
故障内容
型号信息异常/ EEPROM存取故障
室内机热交换器热敏 电阻故障
(5) (1) 室内机风扇故障
(5) (3) 排水异常
(9) (15) 室外机故障
显示方法 : 0.5 秒开 / 0.5 秒关 : 0.1 秒开 / 0.1 秒关 ( ) : 闪烁次数
Sc-15
Loading...