Fujitsu ASYA12LCC, ASYB09LDC, ASYA09LCC, ASYA18LCC, ASYB12LDC Service Instruction

...
SPLIT TYPE ROOM AIR CONDITIONER
WALL MOUNTED
type
Models Indoor unit Outdoor unit
ASYA07LCC ASYA09LCC ASYA12LCC ASYA14LCC ASYA18LCC ASYB09LDC ASYB12LDC
AOYR07LCC AOYR09LCC AOYR12LCC AOYR14LCC AOYR18LCC AOYS09LDC AOYS12LDC
INVERTER
SERVICE
INSTRUCTION
R410A
CONTENTS
1. SPECIFICATION
ASYA07/09LCC, AOYR07/09LCC...................................................................................
2. DIMENSIONS
ASYA07/09LCC, AOYR07/09LCC...................................................................................
ASYA12LCC, AOYR12LCC.............................................................................................
3. REFRIGERANT SYSTEM DIAGRAM
ASYA07/09LCC, AOYR07/09LCC...................................................................................
ASYA12LCC, AOYR12LCC, ASYB09/12LDC, AOYS09/12LDC.....................................
4. CIRCUIT DIAGRAM
ASYA07/09LCC, AOYR07/09LCC...........................................................................................
ASYA12LCC, AOYR12LCC...............................................................................................
5. DESCRIPTION OF EACH CONTROL OPERATION
1. COOLING OPERATION..............................................................................................
3. DRY OPERATION......................................................................................................
2. HEATING OPERATION..............................................................................................
5. INDOOR FAN CONTROL...........................................................................................
4. AUTO CHANGEOVER OPERATION.........................................................................
7. LOUVER CONTROL...................................................................................................
6. OUTDOOR FAN CONTROL.......................................................................................
9. TIMER OPERATION CONTROL................................................................................
8. COMPRESSOR CONTROL........................................................................................
11. TEST OPERATION CONTROL..................................................................................
10. ELECTRONIC EXPANSION VALVE CONTROL........................................................
13. FOUR-WAY VALVE EXTENSION SELECT...............................................................
12. PREVENT TO RESTART FOR 3 MINUTES(3MINUTES ST )................................
15. MANUAL AUTO OPERATION ( Indoor unit body operation ).....................................
14. AUTO RESTART........................................................................................................
16. FORCED COOLING OPERATION............................................................................
18. COIL DRY OPEARTION CONTROL..........................................................................
17. COMPRESSOR PREHEATING..................................................................................
19. DEFROST OPERATION CONTROL..........................................................................
21. VARIOUS PROTECTIONS.........................................................................................
20. OFF DEFROST OPERATION CONTROL..................................................................
01-01
ASYA12/14/18LCC, AOYR12/14/18LCC......................................................................... 01-02
ASYB09/12LDC, AOYS09/12LDC................................................................................... 01-03
02-01
02-02
ASYB09/12LDC, AOYS09/12LDC................................................................................... 02-03
ASYA14/18LCC, AOYR14/18LCC................................................................................... 02-04
ASYB09/12LDC, AOYS09/12LDC................................................................................... 04-03
ASYA14/18LCC, AOYR14/18LCC................................................................................... 04-04
03-01
ASYA14/18LCC, AOYR14/18LCC
................................................................................... 03-03
03-02
04-01
04-02
05-01
05-02
05-03
05-04
05-05
05-07
05-08
05-09
05-10
05-12
05-12
05-12
05-12
05-13
05-13
05-13
05-13
05-14
05-16
05-17
05-12
6. REFRIGERANT CAUTION -R410A-
1. R410A TOOLS............................................................................................................
3. PRECAUTION FOR SERVICING...............................................................................
2. PRECAUTION FOR INSTALLATION.........................................................................
5. DEFFERENCE FROM CONVENTIONAL MODEL(R22) AND PRECAUTIONS........
4. NEW REFRIGERANT R410A.....................................................................................
7. TROUBLE SHOOTING
1. WHEN THE UNIT DOES NOT OPERATE AT ALL....................................................
3. TROUBLE SHOOTING METHOD
2. SELF DIAGNOSIS FUNCTION..................................................................................
1. EXPLODED VIEW......................................................................................................
2. INVERTER ASSEMBLY SPECIFICATION.................................................................
8. APPENDING DATA
1. JUMPER SETTING OF INDOOR UNIT AND OUTDOOR UNIT................................
3. THERMISTOR RESISTANCE VALUES.....................................................................
4. CAPACITY/INPUT DATA...........................................................................................
2. OUTDOOR UNIT PRESSURE VALUE AND TOTAL ELECTRIC
CURRENT CURVE...................................................................................................
9. REPLACEMENT PARTS
10. INSTALLATION MANUAL
4. SELF-DIAGNOSIS FUNCTION AND CHECKING POINTS.......................................
5. SERIAL SIGNAL DIAGNOSIS....................................................................................
6. IPM PROTECTION.....................................................................................................
7. TROUBLE SHOOTING OF REFRIGERANT CYCLE.................................................
06-01 06-02 06-04 06-05 06-08
07-01 07-02
07-03 07-07
07-08
08-01
08-02 08-08 08-09
09-01 09-16
07-09
1 . SPECIFICATIONS
R410A
WALL MOUNTED type
INVERTER
SPECIFICATIONS
TYPE
(COOL&HEAT INVERTER) (COOL&HEAT INVERTER)
INDOOR UNIT
ASYA07LCC ASYA09LCC
OUTDOOR UNIT AOYR07LCC AOYR09LCC
COOLING CAPACITY( ) : Range
(kW) 2.1 (0.5~3.0) 2.6 (0.5~3.6)
HEATING CAPACITY( ) : Range (kW) 3.0 (0.5~4.6) 3.6 (0.5~5.3)
POWER SOURCE
(V) 230
FREQUENCY
(Hz)
50
RUNNING CURRENT (A)
COOLING 2.5
3.2 4.0
0.845 (0.25~1.96)0.845 (0.25~1.76)
3.2
HEATING
INPUT WATTS (kW)
COOLING 0.47 (0.25~1.08) 0.655 (0.25~1.18)
HEATING
EER (kW/kW)
COOLING 4.47 3.97
4.55 4.26
1.3
HEATING
MOISTURE REMOVAL 1.0
AIR CIRCULATION-Hi (m3/hr) C 595 H645 C 595 H645
ELECTRICAL DATA
COMPRESSOR
Note : Always use a vacuum pump to purge the air.
Refrigerant for purging the air is not charged in the outdoor unit at the factory.
DIMENSIONS
TYPE Hermetic type,4 pole, 3 phase , DC inverter motor, Rotary
DISCRIMINATION DA 89 X 1F-20F
REFRIGERANT R410A
(g)
(r.p.m.)
(r.p.m.)
900
900
POWER SOURCE (V) 230
HI-SPEED
MED-SPEED
INDOOR UNIT
LO-SPEED
QUIET
C 1,300 H 1,390
C 1,120 H 1,200
C 950 H 1,000
C 700 H 760
C 1,300 H 1,390
C 1,120 H 1,200
C 950 H 1,000
C 700 H 760
OUTDOOR UNIT 800
INDOOR UNIT H x W x D (mm)
HxWxD (mm)
275 x 790 x 215
OUTDOOR UNIT 540 x 660 x 290
FAN MOTOR
(dB)
(dB)
HI-SPEED
MED-SPEED
INDOOR UNIT
LO-SPEED
QUIET
C41 H41
OUTDOOR UNIT
NOISE LEVEL
20 m
15m chargeless, 20g/m (>15m)
WEIGHTS
INDOOR UNIT
OUTDOOR UNIT
DA 89 X 1F-20F
( /hr)
C41 H41
C36 H36 C36 H36
C30 H30 C30 H30
C21 H21 C21 H21
C47 H48
Note : Noise was measured in accordance with JIS standards, Japan.
GROSS / NET (kg)
GROSS / NET (kg)
12 / 9
35 / 34 35 / 34
MAX PIPE LENGTH
ADDITIONAL REFRIGERANT
THICKNESSES OF ANNEALED COPPER PIPES
Nominal diameter
1/4
3/8
Outer diameter (mm)
6.35
9.52
R410A
0.80
0.80
[ref,] R22
0.80
0.80
Thickness (mm)
01-01
SPECIFICATIONS
INDOOR UNIT
HxWxD (mm)
HxWxD (mm)
275x790x215
OUTDOOR UNIT
540 x 790 x 290 578 x 790 x 300
DIMENSIONS
INDOOR UNIT
GROSS / NET (kg)
GROSS / NET (kg)
12 / 9
OUTDOOR UNIT
44 / 4041 / 37
WEIGHT
TYPE
COOL & HEAT INVERTER
INDOOR UNIT
ASYA14LCC
OUTDOOR UNIT
AOYR14LCC
ASYA12LCC
AOYR12LCC
COOLING CAPACITY
(kW) 4.20(0.9~5.3)
HEATING CAPACITY
(kW)
5.60(0.9~8.4)
ASYA18LCC
AOYR18LCC
5.20(0.9~5.7)
6.25(0.9~9.1)
POWER SOURCE (V) 230
FREQUENCY (Hz) 50
RUNNING CURRENT
COOLING 5.0
(A)
HEATING
6.4
INPUT WATTS
(kW)
COOLING 1.11(0.09~1.75)
HEATING 1.45(0.09~2.48)
E.E.R. COOLING 3.78
COP HEATING 3.86
MOISTURE REMOVAL
2.1
AIR CIRCULATION-Hi (m /hr)
3
C 700 H 700
7.6
7.7
1.72(0.09~2.00)
1.73(0.09~2.66)
3.02
3.61
2.8
C 700 H 700C 635 H 670
3.50(0.9~4.3)
4.80(0.9~6.7)
4.3
5.6
0.92(0.25~1.61)
1.24(0.25~2.30)
3.80
3.87
1.8
FAN MOTOR
TYPE
Hermetic type, 4 pole, 3 phase, DC inverter motor, Rotary
DISCRIMINATION DA 89 X 1F - 20F
REFRIGERANT R410A (g) 1,150 1,1501,050
POWER SOURCE (V) 230
HI-SPEED (r.p.m.) C 1,370 H 1,440
INDOOR UNIT
MED-SPEED (r.p.m.) C 1,150 H 1,200
LO-SPEED (r.p.m.) C 950 H 1,000
QUIET (r.p.m.) C 700 H 760
C 1,480 H 1,480
C 1,260 H 1,300
C 1,040 H 1,110
C850H950
OUTDOOR UNIT (r.p.m.) C860H820
C 1,480 H 1,480
C 1,260 H 1,300
C 1,040 H 1,110
C850H950
C860H820C 830 H 830
ELECTRICAL DATA
COMPRESSOR
( /hr)
(kW/kW)
(kW/kW)
THICKNESSES OF ANNEALED COPPER PIPES
Nominal diameter
1/4
3/8
Outer diameter (mm)
6.35
9.52
R410A
0.80
0.80
[ref,] R22
0.80
0.80
5/8
12.7 0.80
0.80
Thickness (mm)
01-02
(dB)
(dB)
HI-SPEED
MED-SPEED
INDOOR UNIT
LO-SPEED
QUIET
C42 H42
OUTDOOR UNIT
NOISE LEVEL
20 m
15m chargeless, 20g/m (>15m)
C44 H42
C36 H35 C38 H37
C30 H29 C32 H32
C21 H21 C25 H27
C44 H44
C38 H37
C32 H32
C25 H27
C47 H49 C48 H49 C50 H50
Note : Noise was measured in accordance with JIS standards, Japan.
MAX PIPE LENGTH
ADDITIONAL REFRIGERANT
SPECIFICATIONS
TYPE
(COOL&HEAT INVERTER) (COOL&HEAT INVERTER)
INDOOR UNIT
ASYB09LDC ASYB12LDC
OUTDOOR UNIT AOYS09LDC AOYS12LDC
COOLING CAPACITY( ) : Range
(kW) 2.6 (0.5~3.7) 3.5 (0.9~4.3)
HEATING CAPACITY( ) : Range (kW) 3.6 (0.5~6.1) 4.8 (0.9~6.7)
POWER SOURCE
(V) 230
FREQUENCY
(Hz)
50
RUNNING CURRENT (A)
COOLING 2.9
3.9 5.5
1.22 (0.25~2.30)0.81 (0.25~1.96)
4.3
HEATING
INPUT WATTS (kW)
COOLING 0.61 (0.25~1.38) 0.91 (0.25~1.61)
HEATING
EER (kW/kW)
COOLING 4.26 3.85
4.44 3.93
1.8
HEATING
MOISTURE REMOVAL 1.3
AIR CIRCULATION-Hi (m3/hr) C 595 H645 C 595 H645
ELECTRICAL DATA
COMPRESSOR
Note : Always use a vacuum pump to purge the air.
Refrigerant for purging the air is not charged in the outdoor unit at the factory.
DIMENSIONS
TYPE Hermetic type,4 pole, 3 phase , DC inverter motor, Rotary
DISCRIMINATION DA 89 X 1F-20F
REFRIGERANT R410A
(g)
(r.p.m.)
(r.p.m.)
950
1,050
POWER SOURCE (V) 230
HI-SPEED
MED-SPEED
INDOOR UNIT
LO-SPEED
QUIET
C 1,300 H 1,390
C 1,120 H 1,200
C 950 H 1,000
C 700 H 760
C 1,370 H 1,440
C 1,150 H 1,200
C 950 H 1,000
C 700 H 760
OUTDOOR UNIT C800 H760
INDOOR UNIT H x W x D (mm)
HxWxD (mm)
283 x 790 x 230
OUTDOOR UNIT 540 x 790 x 290
FAN MOTOR
(dB)
(dB)
HI-SPEED
MED-SPEED
INDOOR UNIT
LO-SPEED
QUIET
C39 H40
OUTDOOR UNIT
NOISE LEVEL
20 m
15m chargeless, 20g/m (>15m)
WEIGHTS
INDOOR UNIT
OUTDOOR UNIT
DA 89 X 1F-20F
( /hr)
C41 H41
C34 H35 C35 H35
C29 H28 C29 H28
C20 H21 C20 H21
C47 H48 C47 H49
Note : Noise was measured in accordance with JIS standards, Japan.
GROSS / NET (kg)
GROSS / NET (kg)
12 / 9.5
38 / 34 40 / 36
MAX PIPE LENGTH
ADDITIONAL REFRIGERANT
THICKNESSES OF ANNEALED COPPER PIPES
Nominal diameter
1/4
3/8
Outer diameter (mm)
6.35
9.52
R410A
0.80
0.80
[ref,] R22
0.80
0.80
Thickness (mm)
01-03
2 . DIMENSIONS
R410A
WALL MOUNTED type
INVERTER
DIMENSIONS
Models : ASYA07LCC / AOYR07LCC
ASYA09LCC / AOYR09LCC
02-01
(unit : mm)
275
2,000
290
540
215790
660
INDOOR UNIT
OUTDOOR UNIT
DIMENSIONS
Models : ASYA12LCC / AOYR12LCC
02-02
(unit : mm)
275
540
2,000
215
790
790
56
290
353
17
DIMENSIONS
ASYB12LDC / AOYS12LDC
Models : ASYB09LDC / AOYS09LDC
02-03
(unit : mm)
540
790
56
290
353
17
790
230
283
DIMENSIONS
ASYA18LCC / AOYR18LCC
Models : ASYA14LCC / AOYR14LCC
02-04
(unit : mm)
347
578
48
10
320
508
540
20
300
125
60
790
275
2,000
215790
3 . REFRIGERANT SYSTEM DIAGRAM
R410A
WALL MOUNTED type
INVERTER
REFRIGERANT SYSTEM DIAGRAM
Models : ASYA07LCC / AOYR07LCC
ASYA09LCC / AOYR09LCC
03-01
2-Way
valve
Strainer
Strainer
3-Way
valve
Muffler
4-Way valve
Expansion valve
Heat exchanger
( INDOOR )
Heat exchanger
( OUTDOOR )
Compressor
Cooling Heating
Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 3/8" (9.52 mm)
REFRIGERANT SYSTEM DIAGRAM
2-Way
valve
Strainer
Strainer
3-Way
valve
Muffler
Muffler
4-Way valve
Expansion valve
Heat exchanger
( INDOOR )
Heat exchanger
( OUTDOOR )
AOYS09LDC
(2Pass)
AOYR12LCC AOYS12LDC
(4Pass)
Compressor
Cooling Heating
ASYB09LDC / AOYS09LDC ASYB12LDC / AOYS12LDC
Models : ASYA12LCC / AOYR12LCC
03-02
REFRIGERANT SYSTEM DIAGRAM
2-Way
valve
Strainer
Strainer
Sub-heat
exchanger
( INDOOR )
3-Way
valve
Muffler
4-Way valve
Expansion valve
Heat exchanger
( INDOOR )
Heat exchanger
( OUTDOOR )
Sub-accumulator
Compressor
Cooling Heating
ASYA18LCC / AOYR18LCC
Models : ASYA14LCC / AOYR14LCC
03-03
4 . CIRCUIT DIAGRAM
R410A
WALL MOUNTED type
INVERTER
CIRCUIT DIAGRAM
Models : ASYA07LCC / AOYR07LCC
ASYA09LCC / AOYR09LCC
04-01
INDOOR UNIT
OUTDOOR UNIT
Terminal
Fuse 250V20A
Reactor Reactor
Fan Motor
Expansion Valve
4-Way Valve Assy
PCB (MAIN)
Compressor
Thermistor (pipe)
Thermistor (Discharge Pipe)
Thermistor (outdoor temp.)
1 2 3 4 5 6
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
4 5
1 2 3 4 5
1 2 3 4
1 2 3 4
1 2 3 4
5
6
3LN
WHITE
OR
RED
WHITE RED
BLACK
BLACK
BLACK
BLACK BLACK
GREEN
BLACK
BLACK
BLACK
BLACK
BLACK
RED
RED
RED
BROWN BLUE ORANGE
ORANGE
YELLOW WHITE
WHITE
WHITE WHITE
RED
WHITE
BLACK BROWN BROWN
W10
W7 W8 W9
W11
W4
W2
W1
W3
CN71
CN70
CN40
CN10
CN30
FM
C(W)
CM
S(V)
R(U)
PMV
4WV
POWER RELAY
34
TM1
W3
TM2
CN2
CN4 CN5
CN7
CN6
CN3
CN201
TERMINAL
POWER SOURCE
FAN M OTO R
ROOM TEMPERATURE
THERMISTOR
PIPE TEMPERATURE
THERMISTOR
STEP MOTOR
1
10
11
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
1
2
1
2
ORANGE
YELLOW
PINK
BLUE
RED
BLACK
BLACK
GREEN
WHITE
BLUE
RED
BROWN
BLACK
GREEN / YELLOW
N
L
3
THERMAL
FUSE 102
WHITE
YELLOW
BLACK
RED
BLUE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
RED
BLACK or GRAY
BLACK or GRAY
F. M .
INDICATOR PCB
CONTROLLER PCB
TO OUTDOOR UNIT
TEST
M
L
N
CIRCUIT DIAGRAM
Models : ASYA12LCC / AOYR12LCC
04-02
INDOOR UNIT
OUTDOOR UNIT
Fan Motor
Stepping Motor
Thermistor (room temp.)
Terminal
Terminal
Fuse 250V20A
Reactor Reactor
Fan Motor
Expansion Valve
4-Way Valve Assy
PCB (MAIN)
Power Relay
Compressor
Thermistor (pipe temp.)
Test
M
Thermistor (pipe)
Thermistor (Discharge Pipe)
Thermistor (outdoor temp.)
Display Board
Controller PCB
Power
102 C
Thermal Fuse
1 2 3 4 5 6
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
4 5
1 2 3 4 5
1 2 3
1 2 3
1 2 3
4
1 2 3 4
1 2 3 4
5
6
1
2
3
4
5
1
2
3
4
5
1
2
1
2
1
2
3
4
5
1
2
3
4
5
6
7
1
2
3
4
5
6
1
2
3
4
5
6
1
2
2
1
2
1
3
4
5
6
7
8
9
10
11
1
2
3
4
5
6
7
8
9
10
11
CN1
CN2 CN3
CN201
CN6CN7CN5CN4
43
3L
L
N
3LN
N
BLACK
RED
WHITE
WHITE
OR
RED
WHITE RED
BLACK
BLACK
BLACK
BLACK BLACK
GREEN
BLACK
BLACK
BLACK
BLACK
BLACK
RED
RED
RED
BROWN BLUE ORANGE
ORANGE
YELLOW WHITE
WHITE
WHITE WHITE
RED
WHITE
BLACK BROWN BROWN
BLACK
RED
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
RED
WHITE
ORANGE
RED
PINK
YELLOW
BLUE
GRAY
GRAY
GRAY
GRAY
W2
W3
W10
W7 W8 W9
W11
W4
W2
W1
W3
CN71
CN70
CN40
CN10
CN30
W1
BLACK
GREEN
BLUE
GREEN / YELLOW
BLACK
YELLOW
BLUE
BROWN
FM
C(W)
CM
FM
S(V)
R(U)
PMV
4WV
CIRCUIT DIAGRAM
OUTDOOR UNIT
ASYB12LDC / AOYS12LDC
Models : ASYB09LDC / AOYS09LDC
04-03
INDOOR UNIT
OUTDOOR UNIT
FAN MOTOR
DISPLAY BOARD
AIR CLEAN UNIT
REACTOR
THERMISTOR (PIPE)
THERMISTOR (DISCHARGE PIPE)
THERMISTOR (OUTDOOR TEMP.)
COMPRESSOR
C(W)
S(V)
R(U)
FUSE 250V20A
4WV
PWV
FM
CM
TERMINAL
4-WAY VALVE
EXPANSION VALVE
PRINTED CIRCUIT
BOARD (MAIN)
FAN
MOTOR
REACTOR
STEPPING
MOTOR
CONTROL BOARD
ROWER RELAY
65432
1
65432
1
654
987
321
6
5
4
7
3
2
1
6
5
4
7
3
2
1
3
2
1
3
2
1
4
3
2
1
4
3
2
1
6
5
4
3
2
1
6
5
4
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
54321
54321
5
443321
2
1
2
1
54321
54321
2
1
54321
54321
321
654
987
321
987
121110
654
FM
M
TERMINAL
THERMAL FUSE
THERMISTOR
(PIPE TEMP.)
THERMISTOR
(ROOM TEMP.)
TEST
POWER
WHITE
TM1
CN201
CN101
TM2
W3
CN1 CN2 CN3 CN7 CN11
CN9CN4
CN10
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
BLACK
RED
RED
BLUE
YELLOW
WHITE
WHITE
RED
RED
RED
BLUE
BLUE
BLACK or GRAY
BLACK or GRAY
BLACK
BLACK
GREEN
GREEN / YELLOW
BROWN
BLACK
RED
RED
OR
W10 W11
CN71
CN70
W4
W2
W1
W3
CN30
CN40
CN800
W7 W8 W9
WHITE
RED
WHITE
BLACK BLACK
BLACK
BLACK
RED
WHITE
GREEN
BLACK
BLACK
BLACK
RED
RED
RED
RED
BROWN BLUE
BLUE
ORANGE YELLOW
YELLOW
WHITE
WHITE
BLACK
BLACK
WHITE
WHITE
BLACK BLACK
BROWN BROWN
BLUE
PINK
YELLOW
YELLOW
ORANGE
WHITE
RED
BLUE
YELLOW
L
L3
3LN
N
N
SWITCH
102 C
CIRCUIT DIAGRAM
ASYA18LCC / AOYR18LCC
Models : ASYA14LCC / AOYR14LCC
04-04
INDOOR UNIT
OUTDOOR UNIT
POWER RELAY
34
TM1
W3
TM2
CN2
CN4 CN5
CN7
CN6
CN3
CN201
TERMINAL
POWER SOURCE
FAN M OTOR
ROOM TEMPERATURE THERMISTOR
PIPE TEMPERATURE THERMISTOR
STEP MOTOR
1
10 11
2 3 4 5 6 7 8 9
1 2 3 4 5 6 7
1 2 3 4 5 6 7
1 2 3 4 5 6
1 2 3 4 5 6
1 2
3 4 5
1 2 3 4 5
1 2
3 4 5
1 2
1 2
ORANGE
YELLOW
PINK
BLUE
RED
BLACK
BLACK
GREEN
WHITE
BLUE
RED
BROWN
BLACK
GREEN / YELLOW
NL3
THERMAL FUSE 102
WHITE
YELLOW
BLACK
RED
BLUE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
RED
BLACKorGRAY
BLACKorGRAY
F. M .
INDICATOR PCB
CONTROLLER PCB
TO OUTDOOR UNIT
TEST
M
L
N
RED
WHITE
BLACK
RED
BLACK WHITE YELLOW BLUE
RED
WHITE
BLACK
BLACK
BLACK
RED BROWN
BLUE ORANGE YELLOW
WHITE
BLACK
BLACK
WHITE
RED
BLACK
BLACK
BLACK BLACK
BROWN
BROWN
WHITE
YELLOW
RED
YELLOW
CN71
CN70
CN40
CN800
CN30
GREEN
W4
W2
W1
W3
W10 W11
W7
W8 W9
1 2 3 4 5 6 7
1
2
1 2 3 4 5 6 7
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4
1 2 3
4
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
2
1
TERMINAL
N
L3
FUSE 250V-20A
PIPE TEMP. THERMISTOR
DISCHARGE TEMP. THERMISTOR
OUTDOOR TEMP. THERMISTOR
REACTOR
COMPRESSOR
FAN MOTO R
EXPANSION VALVE
4-WAY VALVE
CM
FM
PMV
4WV
R(R)
S(S)
C(T)
CONTROLLER PCB ASSY
5 . DESCRIPTION OF EACH
CONTROL OPERATION
R410A
WALL MOUNTED type
INVERTER
(Fig.1:LimitofMaximum Frequency based on Outdoor Temperature )
1. COOLING OPERATION
1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor.
* If the room temperature is 2°C higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
minimum frequency
maximum frequency
maximum
frequency ASYA07LCC 18Hz 61Hz 80Hz ASYA09LCC 18Hz 61Hz 80Hz ASYA12LCC 18Hz 80Hz 96Hz
Outside air Outside air temperature temperature
36°C
Azone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
Hi Me Lo Quiet A zone 80Hz 61Hz 51Hz 33Hz B zone 80Hz 61Hz 51Hz 33Hz C zone 80Hz 61Hz 51Hz 33Hz
07LCC 09LCC
D zone 51Hz 42Hz 36Hz 21Hz E zone 51Hz 42Hz 36Hz 21Hz F zone 51Hz 42Hz 36Hz 21Hz A zone 96Hz 61Hz 51Hz 33Hz12LCC B zone 96Hz 61Hz 51Hz 33Hz C zone 96Hz 61Hz 51Hz 33Hz D zone 51Hz 42Hz 36Hz 22Hz E zone 51Hz 42Hz 36Hz 22Hz
09LDC
F zone 51Hz 42Hz 36Hz 22Hz Azone B zone C zone D zone Ezone F zone
( Table1:Compressor Frequency Range )
When the compressor operates for 30 minutes continuously at over the maximum frequency , the maximum frequency is changed from Maximum Frequency to Maximum Frequency . The room temperature is controlled 1°C lower than the setting temperature for 40 minutes after starting the operation. After 40 minutes, it is controlled based on the normal setting temperature.
05-01
E zone
F zone
10°C
0°C
12°C
2°C
80Hz 61Hz 51Hz 33Hz 80Hz 61Hz 51Hz 33Hz 80Hz 61Hz 51Hz 33Hz 51Hz 42Hz 36Hz 27Hz 51Hz 42Hz 36Hz 27Hz 51Hz 42Hz 36Hz 27Hz
ASYB09LDC 18Hz 61Hz 80Hz ASYB12LDC 18Hz 80Hz 96Hz ASYA14LCC 18Hz 70Hz 90Hz ASYA18LCC 18Hz 70Hz 90Hz
12LDC A zone
B zone C zone D zone Ezone F zone
96Hz 61Hz 51Hz 33Hz 96Hz 61Hz 51Hz 33Hz 96Hz 61Hz 51Hz 33Hz 57Hz 42Hz 36Hz 27Hz 57Hz 42Hz 36Hz 27Hz 57Hz 42Hz 36Hz 27Hz
14LCC 18LCC
Azone B zone C zone D zone Ezone F zone
90Hz 45Hz 42Hz 30Hz 90Hz 45Hz 42Hz 30Hz 90Hz 45Hz 42Hz 30Hz 58Hz 38Hz 34Hz 24Hz 58Hz 38Hz 34Hz 24Hz 58Hz 38Hz 34Hz 24Hz
* When the room temperature is between +2°C to -2.5°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table1. However, the maximum frequency is limited in the range shown in Figure 1 based on the fan speed mode and the outdoor temperature.
* If the room temperature is 2.5°C lower than a set temperature, the compressor will be
stopped.
2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor.
* If the room temperature is lower by 3°C than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is higher 2.5°C than a set temperatire, the compressor will be
stopped.
minimum frequency
maximum
frequency ASYA07LCC 18Hz 130Hz ASYA09LCC 18Hz
18Hz
130Hz 130Hz
ASYA12LCC
Outside air Outside air temperature temperature
19°C
C zone
17°C
14°C
B zone
12°C
A zone
Hi Me Lo Quiet A zone 130Hz 96Hz 80Hz 68Hz B zone 130Hz 96Hz 80Hz 54Hz
07/09/12LCC 09/12LDC
C zone 130Hz 96Hz 80Hz 45Hz
* When the room temperature is between +2°C to -3°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table2. However, the maximum frequency is limited in the range shown in Figure 2 based on the fan speed mode and the outdoor temperature.
( Table 2 : Compressor Frequency Range )
( Fig.2 : Limit of Maximum Frequency based on Outdoor Temperature )
* The room temperature is controlled 2°C higher than the setting temperature for 60 minutes
after starting the operation. After 60 minutes, it is controlled based on the normal setting temperature.
05-02
ASYB09LDC 18Hz 130Hz ASYB12LDC 18Hz
18Hz
130Hz 119Hz
ASYA14LCC ASYA18LCC 18Hz 119Hz
A zone 119Hz 90Hz 70Hz 58Hz B zone 119Hz 90Hz 70Hz 58Hz
14/18LCC
C zone 119Hz 90Hz 70Hz 58Hz
3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature, and room temperature variation which the room temperature sensor of the indoor unit body has detected as shown in the Table 3. However, after the compressor is driven, the indoor unit shall run at operation frequency of 58Hz, for a minute.
Operating
frequency ASYA07LCC 33Hz ASYA09LCC 33Hz ASYA12LCC 33Hz
room room temperature temperature
compressor ON
Ts+1.5°C
Ts+0.5°C
compressor OFF
Compressor
ON
OFF
Indoor fan
Dry air flow
S-Lo
OFF
( Table 3 : Compressor frequency )
( Fig.3 : Compressor Control based on Room Temperature )
( Fig.4 : Indoor Fan Control )
05-03
10 30 60 180 60 180 60 10 30
(SEC)
ASYB09LDC 33Hz ASYB12LDC 33Hz ASYA14LCC 24Hz ASYA18LCC 24Hz
4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the AUTO mode by remote cintrol, operation starts in the optimum mode from amoung the HEATING, COOLING, DRY and MONITORING modes. During operation, the optimum mode is automatically swiched in accordance with temperature changes. The temperature can be set between 18°C and 30°C in 1°C steps.
.When operation starts, only the indoor and outdoor fans are operated for 1 minute. After 1 minute,
the room temperature and outside air temperature are sensed and the operation mode is selected in accordance with the table below.
Czone
32°C
B zone
10°C
A zone
( Table.4 Operation mode selection table)
Outside air temperature (TO)
Room temperature(TB)
A zone B zone C zone
TB > TS+2°C
Monitoring
Cooling
(automatic dry)
Cooling
(automatic dry)
TS+2°C TB TS - 2°C
Monitoring Monitoring Monitoring
TB TS - 2°C Heating Heating Monitoring
.When COOING was selected at , the air conditioner operates as follow:
The same operation as COOLING OPERATION of item 1 above is performed.
When the room temperature has remained at (set tempareure-1°C) for 8 minutes, operation is
automatically switched to DRY and the same operation as DRY OPERATION of item 3 above is performed.
If the room temperature reaches (set temperature+2°C during DRY operation, operation returns to COOLING operation.
.When HEATING was selected at , the same operation as HEATING OPERATION of item 2 above is performed.
When the compressor was stopped for 6 consecutive minutes by the temperature control function after the COOLING or HEATING operation mode was selected at above, operation is switched to MONITORING and the operation mode is selected again.
1
<
1
2
3
1
4
1
( Fig.5 : Outside air temperature zone selection )
05-04
5. INDOOR FAN CONTROL
(1).Fan speed
( Table 5 : Indoor Fan Speed )
07/09LCC, 09LDC
Operat ion mode Air flow mode Speed (rpm)
Hi 1390
Me+ 1350
Me 1200
Lo 1000
Quiet 760
Cool air
prevention
760
Heating
S-Lo 480
Hi 1300
Me 1120
Lo 950
Cooling Fan
Quiet 700
Dry 700
(2).FAN OPERATION
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH, while the indoor fan only runs. When Fan mode is set at (Auto), it operates on (MED) Fan Speed.
12LCC, 12LDC
Operation mode Air flow mode Speed (rpm)
Hi 1 440
Me+ 1350
Me 1200
Lo 1000
Quiet 760
Cool air
prevention
760
Heating
S-Lo 480
Hi 1370
Me 1150
Lo 950
Cooling Fan
Quiet 700
Dry 700
05-05
14/18LCC
Operation mode Air flow mode Speed (rpm)
Hi 1480
Me+ 1420
Me 1300
Lo 1110
Quiet 950
Cool air
prevention
850
Heating
S-Lo 480
Hi 1480
Me 1260
Lo 1040
Cooling Fan
Quiet 850
Dry 850
(3).COOLING OPERATION
Switch the airflow [AUTO], and the (Fig.6) indoor fan motor will run according
airflow change - over ( Cooling:AUTO )
to a room temperature, as shown in When the room Figure 6. temperature rises On the other hand, if switched in [HIGH]
[QUIET], the indoor motor
+2.5°C
will run at a constant airflow of [COOL]
operation modes QUIET, LOW, MED, HIGH, as shown in Table 5.
+1.5°C
+1°C
LOW mode
When the room
temperature lowers
(Room temperature) D (Setting temperature)
(4).DRY OPERATION
(5).HEATING OPERATION
Switch the airflow [AUTO], and the (Fig.7) indoor fan motor will run according
airflow change - over ( Heating:AUTO)
to a room temperature, as shown in When the room Figure 7. temperature rises On the other hand, if switched
LOW mode
[HIGH]
[QUIET], the indoor motor -1°C
will run at a constant airflow of [HEAT]
-1.5°C
operation modes QUIET, LOW, MED, HIGH, as shown in Table 5.
-2°C
-2.5°C
MED + mode
When the room
temperature lowers
(Room temperature) D (Setting temperature)
(6).COOL AIR PREVENTION CONTROL (Heating mode)
Indoor heat exchanger Indoor heat exchanger temperature temperature
47°C
Hi
40°C
Me+
37°C
Lo
Cool air prevention
30°C
S-Lo
Refer to the table 4. Durring the dry mode operation, the fan speed setting can not be changed.
The maximum value of the indoor fan speed is set as shown in Figure 8, based on the detected temperature by the indoor heat exchanger sensor on heating mode.
(Fig.8 : Cool Air Prevention Control)
05-06
40°C
28°C
32°C
34°C
HIGH mode
MED mode
+2°C
MED mode
6. OUTDOOR FAN CONTROL
Cooling Dry Heating
ASYA14/18LCC 860/820/670/500
400/340/280
ASYB09/12LDC
280/250/230
( Table 8 : Outdoor fan speed )
*
The outdoor fan speed mentioned avobe depends on the compressor frequency. (When the compressor frequency increases, the outdoor fan speed also changes to the higher speed. When the compressor frequescy decreases, the outdoor fan speed also changes to the lower speed.)
*
It runs at 500(A-D ZONE)/200(E,F ZONE) rpm for 20 seconds after starting up the outdoor fan.
*
After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed as table 9 without relating to the compressor frequency.
05-07
A-D
E
F
A-D
E
F
ZONE
800/760/470
400/280
09LDC: 200 12LDC: 250/200
09LDC: 200 12LDC: 250/200
500
400/280
200
500
400/280
820/750/670/550/450
760/680/470
Refer to Fig1.
(rpm)
*
Outdoor temperature falls, and if it becomes E and F zone(
Refer to Fig1), rotations of fan speed
will fall.
( Table 9 : Outdoor fan speed after the defrost )
ASYB09LDC
ASYB12LDC
ASYA14/18LCC
Min
800rpm
900rpm
950rpm
(1). Outdoor Fan Motor
AC Motor DC Motor ASYA07/09/12LCC ASYB09/12LDC ASYA14/18LCC
(2). Fan Speed
Cooling Dry Heating
ASYA07/09LCC 830rpm 830rpm 830rpm ASYA12LCC 820rpm 820rpm 820rpm
Following table shows the type of the outdoor fan motor. The control method is different between AC motor and DC motor.
( Table 6 : Type of Motor )
( Table7:ACMotor )
In conjunction with the compressor ON/OFF, the fan speed operates at around the speed shown above.
*
7. LOUVER CONTROL
(1). VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follow:
Cooling / Dry mode Heating mode Fan mode
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode
Horizontal flow
Heating mode Downward flow
When the temperature of the air being blown out is low at the start of heating operation or during defrosting, the airflow direction temporarily becomes
to prevent cold air being blown onto the body.
During use of the Cooling and Dry modes, do not set the Air Flow Direction Louver in the Heating range (
) for long period of time, since water vapor many condense near the outlet louvers and drop of water may drip from the air conditioner. During the Cooling and Dry modes, if the Air Flow Direction Louvers are left in the hating range for more than 30minutes, they will automatically return to position
.
During Monitor operation in AUTO CHANGEOVER mode, the airflow direction automatically becomes
, and it cannot be adjusted.
Cooling mode / Dry mode / Fan mode(
)
Heating mode / Fan mode( )
(Function Range)
(Fig 9: Air Direction Range)
(Operation Range)
(2). SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Swinging Range)
When the indoor fan is either at S-lo or Stop mode, the swinging operation is interrrupted and the louver stops at the memorized position.
05-08
8. COMPRESSOR CONTROL
(1). OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as shown in the table 10.
Cooling Heating
Min Max Min Max
Dry
07/09LCC, 09LDC 18Hz 80Hz 18Hz 130Hz 3 3 H z 12LCC, 12LDC 18Hz 96Hz 18Hz 130Hz 33Hz 14LCC, 18LCC 18Hz 90Hz 18Hz 119Hz 24 H z
ASYA07/09LCC 56Hz 74Hz 87Hz 97Hz 108Hz 119Hz ASYA12LCC 56Hz 64Hz 74Hz 87Hz 108Hz 120Hz ASYB09/12LDC 56Hz 74Hz 87Hz 97Hz 108Hz 119Hz
ASYA07/09LCC 80sec 60sec 60sec 180sec 60sec 60sec ASYA12LCC 80sec 30sec 30sec 30sec 50sec 60sec ASYB09/12LDC 80sec 60sec 60sec 180sec 60sec 60sec
(Table 10 : Compressor Operation Frequency Range)
(2). OPEARTION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in the figure 10.
(Fig.10 : Compressor Control at Start-up)
Time
Time Time Time
Time
Time
(Frequency)
(Time)
Frequency
Frequency
Frequency Frequency
Frequency
Frequency
Time Time
Time Time Time Time
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
05-09
ASYA14/18LCC 40Hz 59Hz 72Hz 80Hz 101Hz 110Hz
ASYA14/18LCC 60sec 40sec 40sec 60sec 150sec 60sec
9. TIMER OPEARTION CONTROL
(1). OPEARTION FREQUENCY RANGE
The table 11 shows the available timer setting based on the product model.
ON TIMER / OFF TIMER PROGRAM TIMER SLEEP TIMER ASYA07/09/12/14/18LCC ASYB09/12LDC
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation mode
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest
to the clock's current timer setting. The order of operations is indicated by the arrow in the remote control unit's display. SLEEP timer operation cannot be combined with ON timer operation.
(Table 11 : Timer Setting)
(2). PROGRAM TIMER
Stop mode
Stop mode
Stop mode
Operation mode
Operation mode
Set time
Set time Set time Set time
05-10
(3). SLEEP TIMER
If the sleep is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON.
Set temperature rises
( Ts : Set temperature )
Stop of operation
Set temperature lowers
( Ts : Set temperature )
Ts
Stop of operation
In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 1°C. It increases the setting temperature another 1°C after 1 hour. After that, the setting temperature is not changed and the operation is stopped at the time of timer setting.
Ts
+1°C
+2°C
Set
60min
In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 1°C. It decreases the setting temperature another 1°C every 30 minutes. Upon lowering 4°C, the setting temperature is not changed and the operation stops at the time of timer setting.
-4°C
-3°C
-2°C
-1°C
Set
30min
30min
30min
05-11
10. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the following values. The compressor frequency, the temperatures detected by the discharge temperature sensor, the indoor heat exchanger sensor, the outdoor heat exchanger sensor, and the outdoor temperature sensor.
The pulse range of the electronic expansion valve control is between 60 to 480 pulses.
The expansion valve is set at 480 pulses after 110 seconds of stopping compressor.
At the time of supplying the power to the outdoor unit, the initialization of the electronic expansion valve is operated (528 pulses are input to the closing direction).
11. TEST OPERATION CONTROL
Under the condition where the air conditioner runs, press the test operation button of the remote control, and the test operation control mode will appear. During test running, the operation lamp and timer lamp of the air conditioner body twinkle simultaneously. Set the test operation mode, and the compressor will continue to run regardless of whether the room temperature sensor detects.
The compressor won't enter operation status for 2 minutes and 20 seconds after the compressor is stopped, even if any operation is given.
At the time when the air conditioner is switched from the cooling mode to heating mode, the compressor is stopped, and the four-way valve is switched in 2 minutes and 20 seconds later after the compressor stopped.
When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically started with the memorized operation contents. When the power is interrupted and recovered during timer operation, since the timer operation time is shifted by the time the power was interrupted, an alarm is given by blinking (7 sec ON/2 sec OFF) the indoor unit body timer lamp.
[Operation contents memorized when the power is interrupted]
Operation mode Set temperature Set air flow Timer mode and timer time Set air flow Direction Swing
The test operation mode is released if 60 minutes have passed after setting up the test operation.
12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
13. FOUR-WAY VALVE EXTENSION SELECT
14. AUTO RESTART
05-12
Air clean(Only 9/12LDC model)
15. MANUAL AUTO OPERATION (Indoor unit body operation)
If MANUAL AUTO Button is set, the operation is controlled as shown in Table 12. If the remote control is lost or battery power dissipated, this function will work without the remote control.
OPERATION MODE Auto changeover FAN CONT. MODE Auto TIMER MODE Continuous SETTING TEMP. 24°C SETTING LOUVER Standard SWING OFF
When the outdoor heat exchanger temperature is lower than temperature and the heating operation has been stopped for 30 minutes, power is applied to the compressor and the compressor is heated. (By heating the compressor, warm air is quickly discharged when operation is started.) When operation was started, and when the outdoor temperature rises to temperature or greater, preheating is ended.
ASYA07/09/12/14/18LCC ASYA09/12LDC
ASYA07/09/12LCC
900rpm 36Hz
ASYB09/12LDC
900rpm 36Hz
(Table 12)
(No timer setting available)
17. COMPRESSOR PREHEATING
(Table 13 : Preheating Operation / Release Temperature)
Temperature
Temperature
5°C 5°C
7°C 7°C
18. COIL DRY OR AIR CLEAN OPERATION CONTROL
The coil-dry operation functions by pressing COIL DRY button on the remote controller. The coil-dry operation is consisted of 3 cycles of [Fan operation 3 minutes / Heating operation 2 minutes], and Fan operates for 3 minutes at last before ending the air conditioner operation. (It takes 18 minutes to complete the coil-dry operation.)
(Table 14 : COIL-DRY or AIR-CLEAN Operating Functions)
Indoor Fan Speed
Compressor Frequency
Louver Position
Main Unit Indication
COIL-DRY or AIR-CLEAN indication : ON Other indication : OFF
05-13
Forced cooling operation
Cooling
16. FORCED COOLING OPERATION
Forced cooling operation is started when pressing MANUAL AUTO button for 10 seconds or more. During the forced cooling operation, it operates regardless of room temperature sensor. Operation LED and timer LED blink during the forced cooling operation. They blink for 1 second ON and 1 second OFF on both operation LED and timer LED (same as test operation). Forced cooling operation is released after 60 minutes of starting operation. The FORCED COOLING OPERATION will start as shown in Table11.
-
-
480rpm
ASYA14/18LCC
900rpm 24Hz
(1). COIL DRY OPERATION CONTROL
(2). AIR CLEAN OPERATION CONTROL (ASYB09/12LDC model only)
The coil-dry operation functions by pressing AIR CLEAN button on the remote controller. It continues from COIL DRY operation, it turns on electricity to AIR CLEAN UNIT, sterilization is performed for 15 minutes. Indoor unit fan motor operation under AIR CLEAN operation : The cycle of 480rpm Fixation 5 sec ON /1 min OFF is repeated. (It takes 33 minutes to complete the AIR CLEANING operation.)
Hi
Horizontal OFF
Room Temp is not controlled
Manual auto operation
-
19. DEFROST OPERATION CONTROL
(1). CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor detects the temperature lower than the values shown in Table 15.
(Table 15 : Condition of starting Defrost Operation)
ASYA07/09LCC ASYA12LCC ASYB09/12LDC ASYA14/18LCC
ASYA07/09/12LCC
ASYB09/12LDC
ASYA14/18LCC
1 time defrosting
after starting
operation
ST
Compressor operating time
Less than 20 minutes 20 to 60 minutes
60 minutes to 4 hours
After 4 hours
Does not operate
-9°C
-9°C
-9°C
-9°C
-5°C
-5°C
-5°C
-5°C
-3°C
-3°C
-3°C
-3°C
ASYA07/09LCC ASYA12LCC ASYB09/12LDC ASYA14/18LCC
Defrosting after 2
time upon starting
operation
ST
Less than 35 minutes
35 minutes to
4 hours
Does not operate
Compressor operating time
After 4 hours
-3°C
-3°C
-3°C
-3°C
-6°C
-6°C
-6°C
-6°C
(2). CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table 16.
(Table 16 : Defrost Release Condition)
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 16°C or Compressor operation time has passed 15 minutes.
Outdoor heat exchanger temperature sensor value is higher than 16°C or Compressor operation time has passed 15 minutes.
Outdoor heat exchanger temperature sensor value is higher than 10°C or Compressor operation time has passed 15 minutes.
05-14
Defrost Flow Chart
The defrosting shall proceed by the integrating operation time and outdoor heat exchanger temperature as follows.
(Not defrosted for 10 minutes)
(In case of 1st defrost) (In case of 2nd and later defrost)
Compressor OFF Outdoor fan motor OFF 30 sec later four - way valve OFF 36 sec later compressor ON
Heating operation start : Compressor ON
Compressor integrating operation: Over 20 minutes to below 60 minutes
Compressor integrating operation: Over 60 minutes to below 240 minutes
Compressor integrating operation: Over 240 minutes
Compressor integrating operation: Over 35 minutes to below 240 minutes
Compressor integrating operation: Over 240 minutes
Outdoor heat exchanger temperature: Below
-9°C
Outdoor heat exchanger temperature:
Outdoor heat exchanger temperature:
Outdoor heat exchanger temperature:
Outdoor heat exchanger temperature:
Defrost start
Defrost Indicator: [Operation lamp]
7 sec ON / 2 sec OFF
Outdoor heat exchanger temperature: Over 10°C / 16°C
or Compressor ON time: Over 15 minutes
Defrost end
Below -5°C
Below -3°C
Below -6°C
Below -3°C
05-15
20. OFF DEFROST OPEARTION CONTROL
(1). OFF DEFROST OPERATION CONDITION
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost, and then stop.
In heating operation, the outdoor heat exchanger temperature is less than -4°C, and compressor operation integrating time lasts for more than 30 minutes.
ASYA07/09/12LCC
ASYB09/12LDC
ASYA14/18LCC
OFF Defrost Flow Chart
Heating operation stop
Outdoor heat exchanger temperature: Below -4°C
and Compressor integrating operation: Over 30 minutes
Defrost start
Defrost Indicater: [Operation lamp]
Outdoor heat exchanger temperature: Over 10°C / 16°C
or Compressor ON time: Over 15 minutes
Defrost end
(2). OFF DEFROST END CONDITION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 16°C or Compressor operation time has passed 15 minutes.
Outdoor heat exchanger temperature sensor value is higher than 16°C or Compressor operation time has passed 15 minutes.
Outdoor heat exchanger temperature sensor value is higher than 10°C or Compressor operation time has passed 15 minutes.
7 sec ON / 2 sec OFF
05-16
21. VARIOUS PROTECTIONS
(1). DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature.
ASYA07/09/12/14/18LCC 104°C 101°C 110°C ASYB09/12LDC 104°C 101°C 110°C
07/09LCC, 09LDC 12LCC, 12LDC 14/18LCC
07/09LCC, 09LDC 12LCC, 12LDC 14/18LCC
OT (Control / Release)
17°C
12°C
46°C
40°C
3.5A / 3.0A
4.0A / 3.5A
5.5A / 5.0A
4.0A / 3.5A
5.0A / 4.5A
6.5A / 6.0A
4.5A / 4.0A
6.0A / 5.5A
8.5A / 8.0A
6.5A / 6.0A
8.0A / 7.5A
8.0A / 7.5A
8.0A / 7.5A
6.5A / 6.0A
8.0A / 7.5A
8.5A / 8.0A
9.5A / 9.0A
When the discharge temperature becomes higher than Temperature ,the compressor frequency is decreased 20 Hz, and it continues to decrease the frequency for 20 Hz every 120 seconds until the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature ,the control of the control of the compressor frequency is released.
When the discharge temperature becomes higher than Temperature ,the compressor is stopped and the indoor unit LED starts blinking.
(Table 17 : Discharge Temperature Over Rise Prevension Control / Release Temperature)
Temperature
Temperature
Temperature
(2). CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds the current limit velue that was set up with the outdoor temperature. The compressor frequency returns to the designated frequency of the indoor unit at the time when the frequency becomes lower than the release value.
(Table 18 : Current Release Operation Value / Release Value)
[ Heating ]
[ Cooling / Dry ]
OT : Outdoor Temperature
OT : Outdoor Temperature
OT (Control / Release)
5°C
05-17
7.0A / 6.5A
9.0A / 8.5A
10.5A / 10.0A
13.0A / 12.5A
OT (Control / Release)
17°C
12°C
5°C
OT (Control / Release)
17°C
12°C
5°C
46°C
40°C
OT (Control / Release)
46°C
40°C
OT (Control / Release)
(3). ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger temperature sensor detects the temperature lower than Temperature . Then, the anti-freezing control is released when it becomes higher than Temperature .
A-D E,F
(Table 19 : Anti-freezing Protection Operation / Release Temperature)
TemperatureTemperature
4°C 4°C
7°C 13°C
(4). COOLING PRESSURE OVERRISE PROTECTION
(Table 20 : Cooling Pressure Over Rise Protection Function Temperature)
When the outdoor unit heat exchange sensor temperature rises to temperature or greater, the compressor is stopped and trouble display is performed.
ASYA07/09/12/14/18LCC 67°C ASYB09/12LDC 67°C
Temperature
(5). HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the detection value of the indoor heat exchanger temperature sensor.
05-18
[ ASYA07/12LCC, ASYB09/12LDC ]
[ ASYA14/18LCC ]
46Hz or greater
45Hz
39Hz or greater
38Hz
39
45Hz
38Hz
26 38Hz 25Hz
19
29Hz 18Hz
18
25Hz OFF
OFF
Indoor heat exchange temperature
[ Control System ]
Temperature
Temperature
Refer to below
Temperature
Temperature
The compressor frequency is precisely controlled so that it does not exceeds Temperature .
It returns to the normal operation
Compressor Operation
18Hz
30
Frequency down every 120 sec
Frequency down every 120 sec
ASYA07/09/12/14/18LCC 55°C ASYB09/12LDC 55°C
Temp
Temp Temp Temp
53°C 53°C
52°C 52°C
50°C 50°C
6 . REFRIGERANT CAUTION -R410A-
R410A
WALL MOUNTED type
INVERTER
1. R410A TOOLS
Gauge manifold . . . ..................(Fig.4-1)
Since the normal pressure is high, the connection pipe size is also different.
Charge hose . . .....................(Fig.4-2)
Refrigerant cylinder .................(Fig.4-3)
Confirm the refrigerant type before charging. Always charge liquid-phase refrigerant.
Electronic balance for refrigerant
charging ...........................
(Fig.4-4)
Electronic balance is recommended as in the case of R410A.
Vacuum pump with adapter to prevent
reverse flow . . . . . . . . . ...............
(Fig.4-5)
Conventional pump can be used.
Vacuum holder . . . ..................(Fig.4-6)
Conventional pump can be used if adapter for preventing vacuum pump oil from flowing back is used.
Gas leakage tester . . . ...............(Fig.4-7)
Exclusive for HFC
Refrigerant cleaner . . . . . . ............(Fig.4-8)
Brown paint as designated by the ARI, USA
Flare tool . . . . . .....................(Fig.4-9)
Torque wrench . . . . ................(Fig.4-10)
Refrigerant recovering
equipment (Collector) . .............
(Fig.4-11)
The type which can be used for any refrigerant is available
Nitrogen cylinder . . . . . . .............(Fig.4-12)
This prevents an oxide film from forming in the pipe silver­alloy brazing work by turning the air out of the pipe and preventing the inside combustion.
Safety charger . . . . . ................(Fig.4-13)
It is always compulsory to change the liquid, because R410A is a mixed refrigerant and there is some fear that a mixing ratio changes. In order to avoid the refrigerant from returning to the compressor in a liquid state, the refrigerant can be charged instead of giving a load to the compressor with a safety charger.
Control valve . . . . . . ................(Fig.4-14)
The control valve prevents the refrigerant from spouting when it is removed, as the charging hose side and the ser­vice port side are possible to open and close at the same time.
Thermistor vacuum gauge . ..........(Fig.4-15)
To remove moisture from the refrigerating cycle complete­ly, it is necessary to perform appropriate vacuum drying. For that reason, vacuum conditions can be confirmed cer­tainly.
Vacuum valve . . . . . . . . . . . ..........(Fig.4-16)
This valve builts in a check valve, and it is easily possible to vacuum a refrigerating cycle or check for degree of vac­uum with it.
TOOLS AND EQUIPMENT (R410A)
Gauge Manifold
R410A
R22, R407C
High pressure
gauge
Compond gauge
Port size
-0.1 5.3 Mpa
-0.1 3.8 Mpa
1/2UNF 5/16"
-0.1 3.5 Mpa
-0.1 1.7 Mpa
7/16UNF 1/4"
*
1
Charge hose
R410A
R22, R407C
Normal pressure
Port size
5.1 Mpa
27.4 Mpa
1/2UNF
3.4 Mpa
17.2 Mpa
7/16UNF
*
2
Breaking pressure
This air conditioner used R410A. For installation and servicing, it is necessary to prepare the tools and machines that are different from the previous refrigerant.
Mark shows the exclusive use for R410A.
The specification of the gauge is different due to higher pressure. The size of connection pipe is also different to prevent mis-use.
The shape of flare is different for high pressure condition.
06-01
Gas charging
Vacuum
i
n
g
Piping work
Pressure control and Circuit switching
Charge hose
Fig.4-2
Outdoor unit
Electronic charging scale Fig.4-4
Vacuum pump Fig.4-5
Thermistor vacuum ga
g
e
F
ig.41
5
V
acu
u
m
Val
veF
ig.41
6
S
a
fety charger Fig.4-13
Control Valve
Fig.4-14
V
acu
u
m
hol
d
e
rFig.
4
6
Leakage tester Fig.4-7
Cleaner Fig.4-8
Collector Fig.4-11
Nitrogen Cylinder
Fig.4-12
Torque wrench
Fig.4-10
Flare tool
Fig.4-9
Gauge manifold
Fig.4-1
Fig.4-3
Refri
gerantcy
l
i
nder
Vacuum control
Low pressure
High pressure
side
side
2. PRECAUTION FOR INSTALLATION
06-02
Precaution for installation
The pipe must be properly pressure rated for R410A The pipe must be an air-conditioning refrigerant pipe.
Flare and flare nuts
Diameter 1/4(6.35mm) 3/8(9.52mm) 1/2 (12.7mm)
Refrigerant
R410A
R22 /R407C
R410A R410A
A 9.1 9.0 13.2 13.0 16.6
16.2
B 13 12 20 15 13 20
C 12 11 16 12.5 19 16
Nut width 17 22 26 24
Always use the flare nut that is packed with the product.
Do not use existing (for R22) pipes
Be sure to use new pipes when replacing conventional (R22) model with HFC (R407C, R410A) model.
If you use existing pipes, it may cause resolution of compressor oil by remaining mineral oil.
3/8(15.88mm)
R410A
22
29
19.7
25
R22 /R407C
R22 /R407C
R22 /R407C
19.4
23
20
27
3/4(19.05mm)
R410A
24
36
24
29
R22 /R407C
23.7
29
24
Material
Nominal diameter
(in)
1/4" 3/8" 1/2" 5/8" 3/4" 7/8" 1 1/8" 1 1/4" 1 1/2"1 3/8"1"
6.35 9.52 12.70 15.88 19.05 22.22 28.58 31.75 38.1034.9225.40
Outside diameter
(mm)
Wall thickness
(mm)
0.8 0.8 0.8 1.0 1.2 1.0 1.0 1.1 1.31.21.0
1) Allowable tensile stress 33 (N/mm );
> =
2
2) Allowable tensile stress 61 (N/mm ); 3) Design pressure 4.2MPa.
>
=
2
JIS H3300-C1220T-H or equivalent
2)
COPPER
JIS H3300-C1220T-O or equivalent
1)
COPPER
3)
Pipe diameter, recommended material and wall thickness
A
C
B
Be careful not to mix moisture and
contamination into the pipe
Moisture and contamination
in the pipe is a cause of trouble.
Air purge
Always use a
vacuum pump
to purge air.
Refrigerant charge
Do it always from the liquid phase side.
Don't charge from the gas phase side.
Compressor oil is changed
Be careful to handle synthetic oil, since it
resolves easily by moisture and
contamination.
Don't mix new synthetic oil and mineral oil.
It may cause trouble.
We developed new synthetic oil, since HFC refrigerant doesn't dissolve in mineral (for R22)oil.
06-03
3. PRECAUTION FOR SERVICING
Feature 1 Refrigerant oil is different from before.
Refrigerant oil for
New Refrigerant
Synthetic oil
Ether
Esther
Different point from
previous one
Previously it was mineral oil.
Absorbent character is high.
Contamination occurs when mixed withe other kind of oil.
Use the gauge manifold and charge hose for New Refrigerant(HFC), which shall be segregated from those of R22.
Attach the stop valve on the vacuum pump and avoid the oil from reverse frow.
It is necessary to use the vacuum pump which can obtain the high vacuum condition.
Precaution on Tools
Feature 2 New Refrigerant has Approx 1.6 times higher pressure than previous refrigerant.
R410A
High Pressure
Different point from
previous one
Diameter of Service port has been changed from 1/4 Flare to 5/16 Flare.
It requires the gauge manifold and charge hose exclusively for R410A.
It requires the flare tool and torque wrench that satisfies New JIS standard.
Precaution on Tools
R410A R22
1.6 times of R22.
JIS standard of flare
process It became lager
To keep thethickness of copper tube. (1/4,3/3=more than 0.8mm)
Previous flare tool + flare adapter can be used as well.
06-04
4. NEW REFRIGERANT R410A
What is HFC ?
Phase-out schedule of HCFC
according to Montreal protocol
1996 20102000 2004 2015 2020 2030
60
40
20
100
(Year)
(%)
80
(HCFC consumption of 1989) +
(CFC consumption of 1989) x 2.8%
65%
35%
10%
0.5%
started control
only service use
total abolition
100% =
0
*
06-05
Ozone Layer depleting mechanism
CFC
CFCl
2
Cl Ozone
(O
3
)
O
2
ClO
Cl
sunbeam
What is CFC and HCFC?
CFC : Chloro-Fluoro-Carbon
High ODP( ozone depletion potential ) chemical compound, including chlorine. (ODP:0.6-1.0) For example : R12 (for refrigerator and car air-conditioner)
Low ODP chemical compound, including chlorine and hydrogen. (ODP:0.02-01)
HCFC : Hydro-Chloro-Fluoro-Carbon
For example : R22 (for air-conditioner)
R134a (for Car air conditioner)
HFC
3 : Hydro-Fluoro-Carbon
R407C (for air conditioner)
Refrigerant characteristics
R22
Composition
(wt%)
R22
(100)
Boiling Point
- 40.8
Behavior ---
Pressure at 54.5
C
(kPa)
2,151
Temperature Glide
(deg)
0
ODP 0.055
R407C
R32/R125/R134a
(23/25/52)
- 43.6
zeotrope
2,262
5.4
0
R410A
R32/R125
(50/50)
- 51.4
near azeotrope
3,406
0.11
0
06-06
Summary of R407C and R410A characteristics
Pressure(Mpa)Temp(C
)
2.20 37.9
2.25 38.7
2.30 39.6
2.35 40.5
2.40 41.3
2.45 42.1
2.55 43.8
2.60 44.6
2.65 45.3
2.70 46.1
2.75 46.8
2.80 47.6
2.85 48.3
2.90 49.0
2.95 49.8
3.00 50.5
3.05 51.2
3.10 51.9
3.15 52.6
3.20 53.2
3.25 53.9
3.30 54.6
3.35 55.3
3.40 55.9
3.45 56.5
3.50 57.1
2.55 57.8
3.60 58.4
3.65 59.0
3.70 59.6
3.75 60.2
3.80 60.8
3.85 61.4
3.90 52.0
3.95 62.5
4.00 63.1
4.05 63.6
4.10 64.2
4.15 64.8
Temp ( C) Pressure (Mpa)
39 2.27 40 2.32 41 2.38 42 2.44 44 2.57 45 2.63 46 2.69 47 2.76 48 2.83 49 2.90 51 3.04 52 3.11 53 3.18 54 3.26 56 3.41 57 3.49 58 3.57 59 3.65 61 3.82 62 3.90 63 3.99 64 4.08
Desighed pressure of R410A refrigerant
< Pressure Temp >
Relation between R410A condensing temperature and saturated pressure.
< Temp Pressure >
Advantage
Disadvantage
Suitable for
R410A
higher system
performance
Near-Azeotropic
refrigerant
1.6 times higher
(difficult to design against
pressure resistance)
Small Air-Conditioners
pressure than R22
R407C
similar pressure as R22
(possible to design
large equipment)
Zeotropic refrigerant
(handle with care)
Large Air-Conditioners
*
05-07
OIL
• Use new synthetic oils such as ester because HFC series refrigerant has less solubility with mineral oils conventionally used for R22.
• As these new synthetic oils are easily influenced by moisture and dusts, they must be treated more care-
fully than the conventional lubricating oils.
CAUTION
For installation/servicing, take more precautions than the case of conventional refrigerants to avoid moisture and dusts entering the refrigerant circuit. Also, for storing parts, more precautions must be taken.
2, 3-WAY VALVE
• Review material O-ring, valve core seal for securing suitability with oil.
CAUTION
Check if the valve is suitable for the refrigerant (model) when replacing.
CAUTION
Check if the compressor is suitable for the refrigerant (model) when replacing. Complete welding within 15 minutes after opening the cap when replacing.
COMPRESSOR
• Use better grade of material for sliding parts for securing good lubrication of sliding part as HFC
refrigerant does not contain chloride.
• Review insulating materials
• Increase pressure resistance strength
CAUTION
During storage, due care must be taken so that foreign matters such as dust and water do not enter.
HEAT EXCHANGER
• Review the water,contaminants controlling level
• Use thinner tube to increase pressure Increase capacity for resistance strength (only outdoor unit) improving performance
CAUTION
Check if the valve is suitable for the refrigerant (model) when replacing.
4-WAY VALVE
• Review materials
5. DEFFERENCE FROM CONVENTIONAL MODEL (R22) AND PRECAUTIONS
06-08
7 . TROUBLE SHOOTING
R410A
WALL MOUNTED type
INVERTER
1. When the unit does not operate at all (Operation lamp and Timer lamp do not light up)
2. Self Diagnosis Function (Either Operation lamp or Timer lamp is blinking) * How to operate the self-diagnosis function * Self- diagnosis table and Check points
3. Trouble shooting method * Serial signal check * IPM protection check * Refrigeration cycle diagnosis
Does not operate at all (Operation Lamp and Timer Lamp do not light up)
[Check Point]
(1) Is the input power voltage from the exclusive circuit AC outlet normal? (2) Is the AC plug inserted to the AC outlet securely and not loose?
(4) Check if each connector is inserted securely.
[Checking Flow Chart]
YES (AC220/230V)
YES (AC220/230V)
YES (AC260~400V)
YES (DC5V)
(IC5, T1 or IC8,11 defective)
YES (DC15V)
YES (DC5Vp-p, Pulse wave of 60Hz)
Controller PCB defective
NO
NO
NO
NO
NO
NO
NO
LCC:(F2, D1, T2 defective) LDC:(F2, D1, L2 defective)
LCC:(IC2, T1, IC3 defective) LDC:(IC5, T1, IC15 defective)
(F1, VA1 defective)
07-01
Does not connected cable do wrong wiring?(3)
LDC (C9:DC20, C10:DC13.5V 1V)
YES LCC (C7:DC20, C12:DC13.5V 1V)
Is AC input voltage from AC outlet normal ?
Fault of an input power supply.
Is AC voltage between VA 1 normal?
Switching power circuit
LCC: Is DC voltage between terminal of C4 normal? LDC: Is DC voltage between terminal of C5 normal?
Switching power circuit
Switching power circuit
LCC: Is DC voltage between terminals of C7 & C12 normal? LDC: Is DC voltage between terminals of C9 & C10 normal?
LCC: Is DC voltage between terminals 3 & 4 of IC7 normal? LDC: Is DC voltage between terminals 3 & 4 of IC8 normal?
Is DC voltage between terminals of C17 normal?
LCC: IC6 defective LDC: IC7 defective
LCC: IC4 defective LDC: IC13 defective
LCC: IC7 defective LDC: IC8 defective
LCC: Is DC voltage between terminals of C9 normal? LDC: Is DC voltage between terminals of C24 normal?
YES (AC220/230V)
NO
Is AC voltage between 4pin of W1 and K1 normal?
Temp fuse defective
SELF-DIAGNOSIS FUNCTION
This function memorizes the self-diagnosis function (lamp display) in the in door control P.C.Board when trouble occurs. (The memory contents are not destroyed even when the power cord is unplugged from the AC outlet.)
The self-diagnosis function (lamp display) can also be switched between major classification display
and minor classification display and precise diagnosis can be made.
Self-diagnosis function [lamp display] (memory reading)
(1) When error occurs, it is indicated by blinking [Operation lamp (Red)] and [Timer lamp (Green)]. (2) Upon pulling out and inserting the AC plug, the starts to operates from remote control.
(At this state, a normal operation indication is performed.)
(3) By pressing [TEST] button of remote control, [Error Indication] is indicated only
during
[3 minutes ST].
(3 minutes ST : 2 minutes 20 seconds from the timing AC plug is ON)
[Lamp display]
3 minutes delay
Turn off Operating
Error Indication Normal indication after
3min.ST
Indication
AC Plug ON Start operation Input TEST signal
How to erase Memory
(1)
(Indoor unit buzzer beeps 3 seconds.)
07-02
While [Error indication] is ON by the self-diagnosis function, the memorized contents can be erased by pressing [Forced Auto Button] on the main unit.
Self - diagnosis function and Checking points
Error Indication
Operation
(RED)
Timer
(GREEN)
Error
(Protection)
Diagnosis Method
0.5 sec 2 times
When the indoor unit does not receive the signal for 10 consecutive seconds during the operation >Permanent stop after 30 seconds.
The outdoor unit does not receive the signal for 10 consecutive seconds from the time when the power relay was ON. >Outdoor unit stops.
OFF
07-03
Serial forward transfer error during the operation
Serial forward transfer error at starting up operation
Serial reverse transfer error during the operation
Serial reverse transfer error at starting up operation
At the start up, the indoor unit does not receive the signal for 10 consecutive seconds from the time when the power relay was ON. >Permanent stop after 30 seconds.
[Diagnosis Point]
Check the indoor /outdoor cable connection (in order). If the cable wiring is not abnormal, measure the voltage of the outdoor unit terminals and diagnose the defective location. (Refer to the after mentioned [Serial Signal Diagnosis] for the voltage measuring method and diagnosis method.)
[Diagnosis Point]
Check the indoor /outdoor cable connection (in order). If the cable wiring is not abnormal, measure the voltage of the outdoor unit terminals and diagnose the defective location. (Refer to the after mentioned [Serial Signal Diagnosis] for the voltage measuring method and diagnosis method.)
[Diagnosis Point]
Check the indoor /outdoor cable connection (in order). If the cable wiring is not abnormal, measure the voltage of the outdoor unit terminals and diagnose the defective location. (Refer to the after mentioned [Serial Signal Diagnosis] for the voltage measuring method and diagnosis method.)
When the outdoor unit does not receive the signal for 10 consecutive seconds during the operation > Outdoor unit stops.
[Diagnosis Point]
Check the indoor /outdoor cable connection (in order). If the cable wiring is not abnormal, measure the voltage of the outdoor unit terminals and diagnose the defective location. (Refer to the after mentioned [Serial Signal Diagnosis] for the voltage measuring method and diagnosis method.)
The room temperature thermistor detective a abnormai temperature when the power was turned on. > Remote control does not operate.
[Diagnosis Point]
Check thermistor resistance value (Refer to "Themistor characteristics table"). Controller PCB defective.
The detection value of the indoor heat exchanger thermistor is either open or shoted when the power is ON. > Remote control dose not operate.
[Diagnosis Point]
Check thermistor resistance value (Refer to "Themistor characteristics table"). Controller PCB defective.
Room temperature therm­istor defective
Indoor heat exchanger thermistor error
0.5 sec 3 times
0.5 sec 4 times
0.5 sec 5 times
0.5 sec 2 times
0.5 sec 3 times
0.5 sec 2 times
Self - diagnosis function and Checking points
Error Indication
Operation
(RED)
Timer
(GREEN)
Error
(Protection)
Diagnosis Method
0.5 sec 2 times
The detection value of the outdoor heat exchanger thermistor is either open or shorted. > Compressor, outdoor fan : OFF (It automatically releases when the normal value is detected.)
The detection value of the outdoor temperature thermistor is either open or shorted. > Compressor, outdoor fan : OFF (It automatically releases when the normal value is detected.)
0.5 sec 3 times
07-04
Forced auto switch error
Outdoor temperature ther­mistor error
Outdoor heat exchanger thermistor error
Discharge thermistor error
The detection value of the discharge thermistor is either open or shorted. > Compressor, outdoor fan : OFF (It automatically releases when the normal value is detected.)
[Diagnosis Point]
Check thermistor resistance value (Refer to "Themistor characteristics table"). Controller PCB defective.
[Diagnosis Point]
Check thermistor resistance value (Refer to "Themistor characteristics table"). Controller PCB defective.
[Diagnosis Point]
Check thermistor resistance value (Refer to "Themistor characteristics table"). Controller PCB defective.
Forced auto switch becomes ON for 30 consecutive seconds. > It indicates the error but the operation continues.
[Diagnosis Point]
Check if forced auto switch is kept pressed. Forced auto switch defective. Controller PCB defective.
After 2 minutes 20 seconds of stopping operation, the signal from outdoor unit is received even though the main relay is OFF. > Main relay OFF continues (outdoor unit OFF command)
[Diagnosis Point]
Main relay defective Controller PCB defective.
The power supply frequency can not be recognized after 4 seconds of power ON. > Permanent stop.
[Diagnosis Point]
Controller PCB defective.
Main relay error
Power supply fequency detection error
0.5 sec 3 times
0.5 sec 4 times
0.5 sec 2 times
0.5 sec 3 times
0.5 sec 4 times
0.5 sec 4 times
Self - diagnosis function and Checking points
Error Indication
Operation
(RED)
Timer
(GREEN)
Error
(Protection)
Diagnosis Method
0.5 sec 7 times
The air clean operation signal was detected for 1 minute at the time of air clean mode OFF. > All stop. Not operate remote controller.
Abnormal current value of IPM is detected. > Permanent stop.
0.5 sec 4 times
07-05
CT error
IPM protection
Reverde-VDD permanence stop protection (Electric air clean power supply circuit abnormal)
VDD permanence stop protection (Electric air clean)
When the air cleanness monitor trial protection operates 4 times. > Only clean air permanent stop.
[Diagnosis Point]
The front panel is closed. The foreign body such as dust doesn't adhere.
[Diagnosis Point]
Electric air clean defective. Controller PCB defective.
[Diagnosis Point]
Heat radiation is blocked (inlet/outlet). Check if outdoor fan is defetcive (does not rotate). Controller PCB defective (Refer to after mentioned "IPM diagnosis"). Refrigeration cycle defective (Refer to after mentioned "refrigeration cycle diagnosis").
The current value during the operation after 1 minute from starting up the compressor is 0A. > permanent stop.
[Diagnosis Point]
Controller PCB defective.
The compressor speed does not synchronze with the control signal. (Including start up failure of the compressor). > permanent stop.
[Diagnosis Point]
Check if 2-way valve or 3-way valve is left open. Check the compressor (Winding resistance value, loose lead wire). Refrigeration cycle defective (Refer to after mentioned "refrigerant cycle diagnosis")
Either the outdoor fan motor abnormal current or location error was detected. > Permanent stop.
[Diagnosis Point]
Fan motor connector loose/ defective contact. Fan motor defective. Controller PCB defective.
Compressor location error
Outdoor fan error (DC motor)
0.5 sec 8 times
0.5 sec 2 times
0.5 sec 3 times
0.5 sec 5 times
0.5 sec 6 times
0.5 sec 5 times
Self - diagnosis function and Checking points
Error Indication
Operation
(RED)
Timer
(GREEN)
Error
(Protection)
Diagnosis Method
0.5 sec 2 times
The indoor fan speed is 1/3 of the target frequency after 56 seconds from starting operation or from the time the fan mode was changed. > Operation stop. (It releases by sending the operation stop signal from the remote controller).
The discharge temperature error is activated. > Permanent stop.
0.5 sec 6 times
07-06
Excessive high pressure protection on cooling
Discharge temperature error
Indoor fan speed error
Indoor fan lock error
The indoor fan speed is 0 rpm after 56 seconds from starting operation or from the time the fan mode was changed. > Operation stop. (It releases by sending the operation stop signal from the remote controller).
[Diagnosis Point]
Fan motor connector loose /defective contact. Fan motor defective Controller PCB defective.
[Diagnosis Point]
Fan motor connector loose /defective contact. Fan motor defective Controller PCB defective.
[Diagnosis Point]
Check if 2-way valve or 3-way valve is left open. Heat radiation is blocked (Inlet /outlet). Check if outdoor fan is defective (does not rotate). Refrigeration cycle defective (Refer to after mentioned "refrigerant cycle disagnosis").
Excessive high pressure protection on cooling mode has been activated. > Compressor, outdoor fan : Off (It releases after 3 minute ST).
[Diagnosis Point]
Heat radiation is blocked (Inlet /outlet). Check if outdoor fan is defective (does not rotate). Refrigeration cycle defective (Refer to after mentioned "refrigerant cycle disagnosis").
Excessive voltage of DC voltage on PFC circuit in inverter PCB is detected, or the excessive current in the circuit is detected. > Permanent stop.
[Diagnosis Point]
Controller PCB defective (Refer to after mentioned "PFC circuit diagnosis")
PFC circuit error
0.5 sec 3 times
0.5 sec 2 times
0.5 sec 3 times
0.5 sec 4 times
0.5 sec 7 times
0.5 sec 8 times
Serial Signal Receiving Error
[Check Point] Check which has a cause of error, either Indoor unit or Outdoor unit.
* Remove indoor unit front panel and cable xlampers and keep the terminal block clear so that it can be
measured with a meter.
* Remove AC power and reset the power, and press Test Operation switch on remote control.
[Check Procedure]
[Indoor Unit Check]
CAUTION: Keep out hands from terminal base and electrical components. Voltage is
applied on them and you may get electric shock.
NO
YES
07-07
[Outdoor Unit Check]
Indoor unit control unit is normal.
Check outdoor unit control unit.
Check cable wiring of terminal base of indoor and outdoor unit correctly connected as numbered.
Does voltage AC220 to 230V appear between NO terminal L and N of indoor unit terminal base?
Check cable wiring of terminal base.
Does indoor unit start to operate? Conduct the inspection on "no operation at all".
Outdoor unit controller PCB board failure.
Measure voltage between terminal N and 3 of indoor unit terminal base. Is it normal?
Indoor unit controller PCB IC7 failure.
Does voltage AC350 to 415V appear at NO DC voltage terminal?
Check broken fuse, wiring connection.
Does voltage AC220 to 230V appear between terminai N and L of outdoor unit terminal base?
Check power supply connection.
NO
NO
NO
NO
YES
YES
YES
YES
YES
IPM Protection
[Checking Points]
Check the following points and locate the cause in the outdoor unit.
[Cause]
(1) Compressor failure(2) Refrigeration cycle failure(3) PC Board defective(4) IPM defective(5) Incorrect wiring
[First step]
Measure the DC voltage at terminals (between Electrolytic Capacitor and discharge resistance) in the Inverter Controller Assy, and make sure it is lower than DC5V.
Check point (1)
Check point (2)
Open the Inverter Controller Assy
Yes(Normal)
Go to Check point (2)
and check if there is abnormal points.
No(Abnormal)
Incorrect wiring > Correct and recheck Parts touched > Correct and recheck
Parts broken > Change the broken part
Check point (3)
Turn on the power and press TEST button
Yes(Rotating)
Go to Check point (3)
on Remote Control.
No(Not rotating)
PCB or Compressor defective
Is the outdoor fan rotating?
Check point (4)
Operate the unit for certain time and
Yes(Operating)
The unit is normal.
check if the compressor is operating.
No(Not operating)
IPM or PCB defective > Replace PCB
If it is higher than 5V, wait until the discharging is over.
Yes(Normal)
No(Abnormal)
IPM defective
Check point (4)
Recheck, is compressor normal?
Yes(Operating)
No(Not operating)
Please redo from the start. (Refrigerant cycle has the possibility of abnormalities.)
07-08
1, Remove the lead of compressor. 2, Connect the P to minus and measure the U, V and W.
4, Connect the N to plus and measure the U, V and W.
3, Check the balance of resistance. (+/- 10%)
5, Check the balance of resistance. (+/- 10%) *0is failure even when resistance is the same
(The above resistance value is a typical value. There is some distribution. A
Trouble Shooting of Refrigerant Cycle
[Diagnosis Table for Defective Component]
: Item of most possible cause
IPM Protection
Compressor
Location error
Discharge
Temperature Error
Cooling High
Pressure
Protection
Refrigerant leak
Compressor failure(*)
EEV failure (*)
Thermistor failure (*)
(*) Trouble Shooting Method
(1) Checking method of the compressor failure
Insert the AC plug and start up the cooling operation. Input Test operation signal and check if the compressor operates. If it does not operate, measure the resistance value of compressor windings between U-V, V-W, W-U. If any of the resistance v alue between U-V, V-W, W-U is not same as others, the compressor is defective.
Compressor Failure
NORMAL
ASYA07/09/12 LCC Compressor Case Temperature at 20°C: 0.710 ohm
ASYB09/12LDC Compressor Case Temperature at 20°C: 0.710 ohm
ASYA14/18LCC Compressor Case Temperature at 20°C: 0.730 ohm
s it also changes by the compressor temperature, the measured value may be much different from the above table when measured right after stopping operation.)
(2) Checking method of EEV failure
- Insert the AC plug and start up the operation. Check if the EEV operates just before compressor is turned on. (Touch EEV by hand and check it.) If it does not operate, check if the coil or connector of EEV is removed or loose. If it operates, check the discharge thermistor / outdoor heat exchanger thermistor / indoor heat exchanger thermistor. (Refer to (3) for checking method.)
(3) Checking method of Thermistor
- Check each thermistor if it is removed or the connector is loose. If there is no problem, remove the connector of the thermistor from the PCB and che ck the resistance value (refer to the thermitor characteristics table).
07-09
8 . APPENDING DATA
R410A
WALL MOUNTED type
INVERTER
1. Jumper setting of Indoor unit and Outdoor unit
2. Outdoor unit Pressure Value and Total Electric Current Curve
3. Thermistor Resistance Values
4. Capacity/Input Data
JP (Jumper) Setting
[Indoor Unit]
ASYA07/09/12LCC ASYB09/12LDC ASYA14/18LCC
- Remote control custom code When multiple number of indoor units are installed in the same room, erroneous receipt of the signal can be avoided by setting up the remote control custom code separately. To set up the remote control custom code, always set up the same code on both indoor unit PCB and remote control PCB. (When the indoor unit PCB is changed to Code B, it can not receive the signal unless remote control PCB is also changed to Code B.)
Indoor Unit Remote Control
JM1(JP)
J4 (JP)
Code A (Default) Code B
- Auto Restart
It is possible to disengage Auto Restart function if it is not needed.
Indoor Unit
JM2 (JP)
With Auto Restart function (Default) Without Auto Restart function
[Outdoor Unit]
AOYR07/09/12LCC
JP
JM500 JM103 JM102 JM101
Normal Preheat
07/09LCC
Higher Preheat
Normal Preheat
12LCC
Higher Preheat
AOYS09/12LDC
AOYR14/18LCC
- it is possible to select the higher or standard level of preheating function.
- When it is set up at the higher level of preheat, the magnetic noise of the compressor becomes higher.
08-01
JP
JM500 JM103 JM102 JM101
Normal Preheat
09LDC
Higher Preheat
Normal Preheat
12LDC
Higher Preheat
JP
JM500 JM103 JM102 JM101
Normal Preheat
14LCC
Higher Preheat
Normal Preheat
18LCC
Higher Preheat
Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : ASYA07/09/12LCC
[Condition] Ambient
temperature
Indoor / Outdoor - Same temperature
Refrigerant
amount
Standard amount
Piping
length
7.5m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
condition
TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
Measuring
m
ethod
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Colling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
AS*9LSACW series ASYA12LCC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*9LSACW series ASYA12LCC
Measure the low pressure with the pressure meter at the service valve. Measure the outdoor
0.8
0.9
1
1.1
1.2
1.3
1.4
15 20 25 30 35
In/outdoor ambient temparature (degC)
Low-pressure of outdoor unit MPaG
RH 50% RH 60% RH 70%
2.00
2.20
2.40
2.60
2.80
15 20 25 30 35
In/outdoor ambient temparature (degC)
Outdoor total electric current A
RH 50% RH 60% RH 70%
unit overall current with the current clamp meter at Power Cable.
08-02
0.7
0.8
0.9
1
1.1
1.2
16 18 20 22 24 26 28 30 32
In/outdoor ambient temparature [degc]
Low-pressure of outdoor unit [MPa]
RH50% RH60% RH70%
3
3.5
4
4.5
16 18 20 22 24 26 28 30 32
In/outdoor ambient temparature [degc]
Outdoor total electric current [A]
RH50% RH60% RH70%
Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : ASYA07/09/12LCC
[Condition] Ambient
temperatur
e
Indoor 15 - 23degC, Outdoor 2 - 12degC
Refrigerant
amount
Standard amount
Piping 7.5m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
con
diti
on
TEST mode (Heating), Hi Fan, Lower direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AS*9LSACW series ASYA12LCC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*9LSACW series ASYA12LCC
outdoor unit overall current with the current clamp meter at Power Cable.
1.8
2
2.2
2.4
2.6
2.8
3
0 5 10 15
outdoor ambient temparature C
High-pressure of outdoor unit MPa
15 C
20 C(Indoor inlet tempe)
23 C
3.00
3.50
4.00
4.50
0 5 10 15
outdoor ambient temparature C
Outdoor total electric current A
15 C 20 C(Indoor inlet temp) 23 C
length
08-03
2
2.2
2.4
2.6
2.8
3
3.2
3.4
0246 8101214
Outdoor ambient temparature [degC]
High-pressure of outdoor unit
[MPa]
15degC 20degC
(Indoor ambient temp. )
23degC
4
4.5
5
5.5
6
6.5
7
02468101214
Outdoor ambient temparature [degC]
Outdoor total electric current [A]
15degC 20degC
(Indoor ambient temp. )
23degC
Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : ASYB09LDC, ASYB12LDC
[Condition] Ambient
t
emperatur
e
Indoor / Outdoor - Same temperature
Refrigerant
amount
Standard amount
Piping 7.5m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
con
diti
on
TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
Measuring
me
thod
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Colling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatic
a
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
ASYB09LDC ASYB12LDC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
ASYB09LDC ASYB12LDC
Measure the low pressure with the pressure meter at the service valve. Measure the outdoor unit overall current with the current clamp meter at Power Cable.
0.80
0.90
1.00
1.10
1.20
1.30
1.40
17.5 20 22.5 25 27.5 30 32.5
In/Outdoor ambient temperature C
Outdoor High Pressure (Mpa)
Relative Humidity 50% Relative Humidity 60% Relative Humidity 70%
2.00
2.10
2.20
2.30
2.40
2.50
2.60
2.70
17.5 20 22.5 25 27.5 30 32.5
In/Outdoor ambient temperature C
Outdoor Total Electric Current (A)
Relative Humidity 50%
Relative Humidity 60%
Relative Humidity 70%
0.7
0.75
0.8
0.85
0.9
0.95
1
1.05
1.1
1.15
1.2
17.5 20 22.5 25 27.5 30 32.5
In/Outdoor ambient temperature C
Outdoor High Pressure (MPa)
Relative Humidity 50%
Relative Humidity 60%
Relative Humidity 70%
3
3.2
3.4
3.6
3.8
4
4.2
17.5 20 22.5 25 27.5 30 32.5
In/Outdoor ambient temperature C
Outdoor Total Electric Current (A)
Relative Humidity 50%
Relative Humidity 60%
Relative Humidity 70%
length
08-04
Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : ASYB09LDC, ASYB12LDC
[Condition] Ambient
temperature
Indoor 15 - 23degC, Outdoor 2 - 12degC
Refrigerant
amount
Standard amount
Pi
ping
7.5m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
condition
TEST mode (Heating), Hi Fan, Lower direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automat
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
ASYB09LDC ASYB12LDC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
ASYB09LDC ASYB12LDC
Measure the high pressure with the pressure meter at the service valve. Measure the outdoor unit overall current with the current clamp meter at Power Cable.
2.10
2.20
2.30
2.40
2.50
2.60
2.70
2.80
2.90
02468101214
Outdoor ambient temperature C
Outdoor High Pressure (Mpa)
Indoor inlet temp 15 C
Indoor inlet temp 20 C
Indoor inlet temp 23 C
3.50
3.60
3.70
3.80
3.90
4.00
4.10
4.20
4.30
4.40
02468101214
Outdoor ambient temperature C
Outdoor Total Electric Current (A)
Indoor inlet temp 15 C
Indoor inlet temp 20 C
Indoor inlet temp 23 C
2.40
2.50
2.60
2.70
2.80
2.90
3.00
3.10
3.20
3.30
02468101214
Outdoor ambient temperature C
Outdoor High Pressure (Mpa)
Indoor inlet temp 15 C
Indoor inlet temp 20 C
Indoor inlet temp 23 C
5.00
5.20
5.40
5.60
5.80
6.00
6.20
6.40
02468101214
Outdoor ambient temperature C
Outdoor Total Electric Current (A)
Indoor inlet temp 15 C
Indoor inlet temp 20 C
Indoor inlet temp 23 C
length
08-05
Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : ASYA14LCC, ASYA18LCC
[Condition] Ambient
temperature
Indoor / Outdoor - Same temperature
Refrigerant
amount
Standard amount
Piping 7.5m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
condition
TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Colling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
ASYA14LCC ASYA18LCC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
ASYA14LCC ASYA18LCC
Measure the low pressure with the pressure meter at the service valve. Measure the outdoor unit overall current with the current clamp meter at Power Cable.
0.8
0.9
1
1.1
1.2
1.3
1.4
15 20 25 30 35
In/Outdoor ambient temperature C
Outdoor Low Pressure (Mpa)
Relative Humidity 50%
Relative Humidity 60%
Relative Humidity 70%
3
3.5
4
4.5
15 20 25 30 35
In/Outdoor ambient temperature C
Outdoor Total Electric Current (A)
Relative Humidity 50%
Relative Humidity 60%
Relative Humidity 70%
0.7
0.8
0.9
1
1.1
1.2
1.3
15 20 25 30 35
In/Outdoor ambient temperature C
Outdoor Low Pressure (Mpa)
Relative Humidity 50%
Relative Humidity 60%
Relative Humidity 70%
4
4.5
5
5.5
6
15 20 25 30 35
In/Outdoor ambient temperature C
Outdoor Total Electric Current (A)
Relative Humidity 50%
Relative Humidity 60%
Relative Humidity 70%
length
08-06
Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : ASYA14LCC, ASYA18LCC
[Condition] Ambient
temperature
Indoor 15 - 23degC, Outdoor 2 - 12degC
Refrigerant
amount
Standard amount
Piping 7.5m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
condition
TEST mode (Heating), Hi Fan, Lower direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
ASYA14LCC ASYA18LCC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
ASYA14LCC ASYA18LCC
Measure the high pressure with the pressure meter at the service valve. Measure the outdoor unit overall current with the current clamp meter at Power Cable.
6.5
7
7.5
8
8.5
9
051015
Outdoor ambient temperature [degC]
Outdoor Total Electric Current (A)
Indoor inlet temp :15 C Indoor inlet temp :20 C Indoor inlet temp :23 C
length
08-07
2.50
2.70
2.90
3.10
3.30
3.50
3.70
3.90
0 2 4 6 8 101214
Outdoor ambient temparature [degC]
High-pressure of outdoor unit [MPa]
Indoor inlet temp
15degC
Indoor inlet temp
20degC
Indoor inlet temp
23degC
6.00
6.20
6.40
6.60
6.80
7.00
7.20
7.40
7.60
7.80
8.00
02468101214
Outdoor ambient temparature [degC]
Outdoor total electric current [A]
Indoor inlet temp
15degC
Indoor inlet temp
20degC
Indoor inlet temp
23degC
3
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
4
02468101214
Outdoor ambient temparature [degC]
High-pressure of outdoor unit
[MPa]
15degC 20degC Indoor ambient temp. ) 23degC
0.00 33.62 1.15 0.00 176.03 1.10
5.00 25.93 1.39 5.00 134.23 1.36
10.00 20.18 1.66 10.00 103.34 1.63
15.00 15.84 1.94 15.00 80.28 1.92
20.00 12.54 2.22 20.00 62.91 2.21
25.00 10.00 2.50 25.00 49.70 2.51
30.00 8.04 2.77 30.00 39.57 2.79
35.00 6.51 3.03 35.00 31.74 3.06
40.00 5.30 3.27 40.00 25.64 3.30
45.00 4.35 3.48 45.00 20.85 3.53
50.00 3.59 3.68 50.00 17.06 3.73
55.00 2.98 3.85 55.00 14.10 3.90
60.00 2.47 4.00 60.00 11.64 4.55
65.00 2.09 4.14 65.00 9.69 4.19
70.00 1.76 4.25 70.00 8.12 4.30
75.00 1.49 4.35 75.00 6.83 4.40
80.00 1.27 4.44 80.00 5.78 4.48
85.00 1.09 4.51 85.00 4.91 4.55
90.00 0.93 4.57 90.00 4.19 4.61
95.00 0.81 4.63 95.00 3.59 4.66
100.00 0.70 4.67 100.00 3.09 4.71
0.00 175.70 0.18 -20.00 49.20 2.66 -20.00 115.24 1.25
5.00 134.93 0.24 -15.00 36.58 3.02 -15.00 84.21 1.56
10.00 104.59 0.30 -10.00 27.51 3.35 -10.00 62.28 1.90
15.00 81.79 0.31 -5.00 20.91 3.64 -5.00 46.58 2.26
20.00 64.50 0.38 0.00 16.05 3.89 0.00 35.21 2.61
25.00 51.27 0.47 5.00 12.44 4.09 5.00 26.88 2.94
30.00 41.07 0.70 10.00 9.73 4.26 10.00 20.72 3.25
35.00 33.13 0.84 15.00 7.67 4.40 15.00 16.12 3.52
40.00 26.91 0.99 20.00 6.10 4.51 20.00 12.64 3.76
45.00 22.01 1.16 25.00 4.89 4.60 25.00 10.00 3.97
50.00 18.10 1.34 30.00 3.95 4.67 30.00 7.97 4.14
55.00 14.98 1.54 35.00 3.21 4.73 35.00 6.40 4.28
60.00 12.47 1.74 40.00 2.62 4.78 40.00 5.18 4.41
65.00 10.44 1.95 45.00 2.16 4.81 45.00 4.21 4.51
70.00 8.78 2.16 50.00 1.79 4.85 50.00 3.45 4.59
75.00 7.42 2.36 55.00 1.49 4.87 55.00 2.85 4.65
80.00 6.31 2.57 60.00 1.25 4.89 60.00 2.36 4.71
85.00 5.38 2.76 65.00 1.05 4.91 65.00 1.97 4.76
90.00 4.61 2.95 70.00 0.89 4.92 70.00 1.65 4.79
95.00 3.97 3.13 75.00 0.76 4.93 75.00 1.39 4.83
100.00 3.43 3.30 80.00 0.65 4.94 80.00 1.18 4.85
105.00 2.98 3.45 85.00 0.56 4.95 85.00 1.00 4.87
110.00 2.59 3.60 90.00 0.48 4.96 90.00 0.85 4.89
115.00 2.26 3.73 95.00 0.41 4.96 95.00 0.73 4.91
120.00 1.99 3.85 100.00 0.36 4.97 100.00 0.63 4.92
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
0.00 10.00 20.00 30.00 40.00 50.00 60.00
0.00
20.00
40.00
60.00
80.00
100.00
120.00
140.00
160.00
180.00
0.00 20.00 40.00 60.00 80.00
0.00
20.00
40.00
60.00
80.00
100.00
120.00
140.00
160.00
180.00
0.00 20.00 40.00 60.00 80.00 100.00 120.00
0.00
10.00
20.00
30.00
40.00
50.00
-20.00 0.00 20.00 40.00 60.00 80.00
0.00
20.00
40.00
60.00
80.00
100.00
120.00
-20.00 0.00 20.00 40.00 60.00
Thermistor resistance values
Room temperature thermistor
Temp ( C)
Resistance(k )
Voltage(V)
Indoor heat exchanger thermistor
Temp ( C)
Resistance(k )
Voltage(V)
Characteristics of room temperature thermistor
Resistance (k )
Temperature ( C)
Characteristics of heat exchanger thermistor (Indoor)
Resistance (k )
Temperature ( C)
Discharge thermistor
Temp ( C)
Resistance(k )
Voltage(V)
Outdoor heat exchanger thermistor
Temp ( C)
Resistance(k )
Voltage(V)
Temp ( C)
Resistance(k )
Voltage(V)
Outdoor temperature thermistor
Characteristics of discharge thermistor
Resistance (k )
Temperature ( C)
Resistance (k )
Temperature ( C)
Characteristics of heat exchanger thermistor (Outdoor)
Resistance (k )
Temperature ( C)
Characteristics of outdoor temperature thermistor
08-08
ASYA09LCC Capacity/Input data (1/2)
< Capacity >
<Input>
*Defrosting operation is performed when temperature is less than 5.5 degrees C. Frost appears on an outdoor unit heat exchanger at 5.5 or less degrees C. *Solid line:Integral capacity/Input containing the defrosting cycle. *Dotted line:Capacity/Input which does not contain the defrosting cycle.
Heating
40%
50%
60%
70%
80%
90%
100%
110%
120%
130%
140%
150%
160%
170%
180%
-15 -10 -5 0 5 10 15 20 25
Capacity(%)
70%
80%
90%
100%
110%
120%
130%
140%
150%
160%
170%
180%
190%
200%
210%
220%
-15 -10 -5 0 5 10 15 20 25
Input(%)
Rated operation
24
24
Maximum
operation
5.5
5.5
Rated operation
Maximum
operation
Without Frost
Without Frost
With Frost
Without Frost
With Frost
Without Frost
IndoorDB:20 C
Outdoor DB( C)
Outdoor DB( C)
IndoorDB:20 C
08-09
(2/2)
< Capacity >
<Input>
Cooling
60%
70%
80%
90%
100%
110%
120%
130%
140%
150%
10 15 20 25 30 35 40 45
Capacity(%)
30%
40%
50%
60%
70%
80%
90%
100%
110%
120%
10 15 20 25 30 35 40 45
Input(%)
43
43
Indoor:27/19 C
Outdoor DB( C)
Indoor:27/19 C
Outdoor DB( C)
08-10
ASYA12LCC Capacity/Input data (1/2)
< Capacity >
< Input >
*Defrosting operation is performed when temperature is less than 5.5 degrees C. Frost appears on an outdoor unit heat exchanger at 5.5 or less degrees C. *Solid line:Integral capacity/Input containing the defrosting cycle. *Dotted line:Capacity/Input which does not contain the defrosting cycle.
Heating
40%
50%
60%
70%
80%
90%
100%
110%
120%
130%
140%
150%
-15 -10 -5 0 5 10 15 20 25
)
Capacity(%)
70%
80%
90%
100%
110%
120%
130%
140%
150%
160%
170%
180%
-15 -10 -5 0 5 10 15 20 25
Input(%)
Rated operation
24
24
5.5
Maximum
operation
5.5
Without Frost
Without Frost
With Frost
Rated operation
Maximum operation
Without Frost
With Frost
Without Frost
IndoorDB:20 C
IndoorDB:20 C
Outdoor DB( C
Outdoor DB( C)
08-11
(2/2)
< Capacity >
< Input >
*Both capacity and input decrease when temperature is 19 or less degrees C, for compressor frequency restrictions operate. *Both capacity and input decrease when temperature is 43 or more degrees C, as compressor speed is decreased due to current release protection.
Cooling
60%
70%
80%
90%
100%
110%
120%
130%
140%
150%
10 15 20 25 30 35 40 45
Capacity(%)
30%
40%
50%
60%
70%
80%
90%
100%
110%
120%
10 15 20 25 30 35 40 45
Input(%)
43
19
19
43
Indoor:27/19 C
Outdoor DB( C)
Indoor:27/19 C
Outdoor DB( C)
08-12
ASYA18LCC Capacity/Input data (1/2)
Heating
*Defrosting operation is performed when temperature is less than 5.5 degrees C. Frost appears on an outdoor unit heat exchanger at 5.5 or less degrees C. *Solid line:Integral capacity/Input containing the defrosting cycle. *Dotted line:Capacity/Input which does not contain the defrosting cycle.
< Capacity >
< Input >
60%
70%
80%
90%
100%
110%
120%
130%
140%
150%
160%
170%
180%
-15 -10 -5 0 5 10 15 20 25
Outdoor DB( C)
Input(%)
5.5 2417
12
Current release works
30%
40%
50%
60%
70%
80%
90%
100%
110%
120%
130%
140%
-15 -10 -5 0 5 10 15 20 25
Capacity(%)
24
12
17
Current release works
Rated operatio
Without Frost
Without Frost
Without Frost
Rated operation
Without Frost
With Frost
With Frost
Maximum operation Current release works
5.5
Maximum operation Current release works
Indoor DB:20 C
Outdoor DB( C)
Indoor DB:20 C
08-13
(2/2)
Cooling
*Both capacity and input decrease when temperature is 19 or less degrees C, for compressor frequency restrictions operate. *Both capacity and input decrease when temperature is 40 or more degrees C, as compressor speed is decreased due to current release protection. *Both capacity and input change largely when temperature is 10 or less degrees C, as outdoor fan speed is decreased due to low ambient temperature cooling control. *Both capacity and input change more largely at less than 0 degrees C of ambient temperature as outdoor fan speed is decreased further.
<Capacity>
< Input >
60%
70%
80%
90%
100%
110%
120%
130%
140%
150%
-10 0 10 20 30 40
Capacity(%)
19
43
20%
30%
40%
50%
60%
70%
80%
90%
100%
110%
120%
-10 0 10 20 30 40
Input(%)
19
43
Indoor : 27/19 C
Outdoor DB( C)
Indoor : 27/19 C
Outdoor DB( C)
08-14
ASYB09LDC Capacity/Input data (1/2)
< Capacity >
< Input >
*Defrosting operation is performed when temperature is less than 5.5 degrees C. Frost appears on an outdoor unit heat exchanger at 5.5 or less degrees C. *Solid line:Integral capacity/Input containing the defrosting cycle. *Dotted line:Capacity/Input which does not contain the defrosting cycle.
Heating
40%
50%
60%
70%
80%
90%
100%
110%
120%
130%
140%
150%
160%
170%
180%
-15-10-5 0 5 10152025
)
Capacity(%)
70%
80%
90%
100%
110%
120%
130%
140%
150%
160%
170%
180%
190%
200%
210%
220%
-15 -10 -5 0 5 10 15 20 25
Input(%)
Rated operatio
24
24
Maximum operation
5.5
5.5
Rated operatio
Maximum
operation
Without Frost
Without Frost
With Frost
Without Frost
With Frost
Without Frost
IndoorDB:20 C
Outdoor DB( C
IndoorDB:20 C
Outdoor DB( C)
08-15
(2/2)
< Capacity >
< Input >
*Both capacity and input change more largely at less than 0 degrees C of ambient temperature as
outdoor fan speed is decreased further.
*Both capacity and input change largely when temperature is 10 or less degrees C, as outdoor fan speed
is decreased due to low ambient temperature cooling control.
60%
70%
80%
90%
100%
110%
120%
130%
140%
150%
-100 10203040
Capacity(%)
30%
40%
50%
60%
70%
80%
90%
100%
110%
120%
-10 0 10203040
Input(%)
43
43
Indoor:27/19 C
Outdoor DB( C)
Indoor:27/19 C
Outdoor DB( C)
08-16
ASYB12LDC Capacity/Input data (1/2)
< Capacity >
< Input >
*Defrosting operation is performed when temperature is less than 5.5 degrees C. Frost appears on an outdoor unit heat exchanger at 5.5 or less degrees C. *Solid line:Integral capacity/Input containing the defrosting cycle. *Dotted line:Capacity/Input which does not contain the defrosting cycle.
Heating
40%
50%
60%
70%
80%
90%
100%
110%
120%
130%
140%
150%
-15 -10 -5 0 5 10 15 20 25
Capacity(%)
70%
80%
90%
100%
110%
120%
130%
140%
150%
160%
170%
180%
-15 -10 -5 0 5 10 15 20 25
Input(%)
Rated operation
24
24
5.5
IndoorDB:20 C
Maximum
operation
5.5
Without Frost
Without Frost
With Frost
Rated operatio
Maximum
operation
Without Frost
With Frost
Without Frost
Outdoor DB( C)
IndoorDB:20 C
Outdoor DB( C)
08-17
(2/2)
< Capacity >
< Input >
decreased due to current release protection.
Cooling
*Both capacity and input decrease when temperature is 40 or more degrees C, as compressor speed is
*Both capacity and input decrease when temperature is 19 or less degrees C, for compressor frequency restrictions operate.
Both capacity and input change largely when temperature is 10 or less degrees C, as outdoor fan speed
is decreased due to low ambient temperature cooling control.
Both capacity and input change more largely at less than 0 degrees C of ambient temperature as
outdoor fan speed is decreased further.
60%
70%
80%
90%
100%
110%
120%
130%
140%
150%
-10 0 10203040
Capacity(%)
30%
40%
50%
60%
70%
80%
90%
100%
110%
120%
-10 0 10 20 30 40
Input(%)
43
19
19
43
Indoor:27/19 C
Outdoor DB( C)
Indoor:27/19 C
Outdoor DB( C)
08-18
9 . REPLACEMENT PARTS
R410A
WALL MOUNTED type
INVERTER
REPLACEMENT PARTS
09-01
Models : ASYA07LCC
ASYA09LCC
INVERTER
REPLACEMENT PARTS
09-02
Models : ASYA07LCC
ASYA09LCC
REPLACEMENT PARTS
09-03
Models : AOYR07LCC
AOYR09LCC
REPLACEMENT PARTS
09-04
Models : AOYR07LCC
AOYR09LCC
REPLACEMENT PARTS
09-05
Models : AOYR07LCC
AOYR09LCC
REPLACEMENT PARTS
09-06
Models : ASYA12LCC
INVERTER
REPLACEMENT PARTS
09-07
Models : ASYA12LCC
REPLACEMENT PARTS
09-08
Models : AOYR12LCC
REPLACEMENT PARTS
09-09
Models : ASYA14LCC
ASYA18LCC
INVERTER
REPLACEMENT PARTS
09-10
Models : ASYA14LCC
ASYA18LCC
REPLACEMENT PARTS
09-11
Models : AOYR14LCC
AOYR18LCC
REPLACEMENT PARTS
09-12
Models : AOYR14LCC
AOYR18LCC
REPLACEMENT PARTS
09-13
Models : ASYB09LDC
ASYB12LDC
INVERTER
REPLACEMENT PARTS
09-14
Models : ASYB09LDC
ASYB12LDC
REPLACEMENT PARTS
09-15
Models : AOYS09LDC
AOYS12LDC
PROCESS
MODEL:AOYR07/09LCC
Wiring lead wire
REGULATIONS
Like a rough sketch, wire COMP lead wire and REACTOR lead wire.
Like a rough sketch, pass each lead wire to guide for the lead wire of HOLDER(PWB).
Each lead wire are wired without sag and twist ,and must be in the ditch of HOLDER(PWB).
Like a rough sketch, Assemble the WIRE.
VIEW A
VIEW A
DB
PWB
Less than 12.5mm
REACTOR lead wire
COMP lead wire
Through the Comp. lead upper side of the reactor lead.
REPLACEMENT PARTS
09-16
Process
Model:AOYR07/09LCC
Connection of leads to inverter assy
REPLACEMENT PARTS
09-17
Process
Model:AOYR07/09LCC
Shaping of leads to inverter assy
REPLACEMENT PARTS
09-18
Model : AOYR07/09LCC
09-19
REPLACEMENT PARTS
09-20
PROCESS
Model : AOYR14/18LCC
ATTACHMENT OF INVERTER ASSY
INVERTER ASSY
Tap tight screw
(TERMINAL BRACKET)
Do not run up the terminal board mounting metal on 2 location of hook.
THERMISTOR (OUT TEMP) is passed here.
(SEPARATER)
1
1
2
2
A
A
REPLACEMENT PARTS
09-21
PROCESS
Model : AOYR14/18LCC
1
6
5
4
3
2
1
2
3
4 5
6
7
The leads are connected with INVERTER ASSY
MOTOR LEAD
THERMISTOR ASSY (COND, DIS)
THERMISTOR (OUT TEMP)
SOLENOID LEAD
COIL (EXP VLV) LEAD
COMP LEAD
WIRE CLAMPER
A
A
B
4
is fixed to HOLDER
PWB side
SOLENOID side
is fix ed to WAIRE CLAMPER
C
C
4
6
7
7
7
4
5~15mm
20~30mm
Loading...