Hybrid Flex Submittal
AOU24RLXFZ
Hybrid Flex Inverter System Heat Pump
Job Name:_______________________________
Location: ________________________________
Engineer:________________________________
Submitted to:_____________________________
Submitted by:_____________________________
Reference:_______________________________
|
|
|
|
|
|
General Data (at 230V) |
||||
Power |
|
|
|
|
208-230VAC-1ph-60Hz |
|||||
Fuse Size, Max. |
|
|
|
25A |
||||||
Minimum Circuit Ampacity(MCA) |
|
17A |
||||||||
Compressor |
Inverter driven variable speed DC Twin Rotary |
|
|
|||||||
No. used |
|
|
|
|
1 |
|
|
|||
Output |
|
|
|
|
1,100W |
|||||
Lubrican Oil |
|
|
|
POE |
||||||
Fan type |
|
|
|
|
Propeller |
|
|
|
|
|
Motor Output |
|
|
|
100W |
||||||
CFM |
Cooling/Heating |
(High) |
|
1,942 / 1,942 |
|
|
|
|||
Refrigerant |
|
|
|
410A |
||||||
Outdoor unit charge |
|
|
|
4lbs 14oz.(2,200g) |
||||||
Contrlol |
|
|
|
Electronic Expansion Valve |
||||||
O.D. Discharge |
|
(in) |
|
1/4”x3(Flare) |
||||||
O.D Suction |
|
(in) |
|
3/8”x2 + 1/2”x1(Flare) |
|
|||||
Dimensions |
|
|
|
H x W x D |
||||||
Uncrated |
|
|
(in) |
|
27-9/16 x 35-7/16 x 13 |
|||||
|
|
|
|
(mm) |
|
(700 x 900 x 330) |
||||
Crated |
|
|
(in) |
32-7/8 x 41-11/32 x 17-17/32 |
||||||
|
|
|
|
(mm) |
|
(835 x 1,050 x 445) |
|
|||
Weight |
|
|
|
|
Outdoor |
|||||
Net |
|
|
|
|
124lbs(56kg) |
|||||
Gross Shipping |
|
|
|
139lbs (63kg) |
|
|||||
Cooling Capacity |
|
|
22,000(6,100~27,000)BTU/h |
|||||||
Rated Power Input |
|
|
|
1.9kW |
||||||
Max. Power Input |
|
|
|
2.72kW |
||||||
Outdoor Sound Rating |
|
|
51dB |
|||||||
Heating Capacity |
|
|
22,000 (6,800-24,400)BTU/h |
|||||||
Rated Power Input |
|
|
|
1.84kW |
||||||
Max. Power Input |
|
|
|
2.09kW |
||||||
Outdoor Sound Rating |
|
|
49dB |
|||||||
Piping Lengths |
|
|
|
|
|
|
|
|
||
Pre-charge length |
|
|
|
98ft |
||||||
Max. Piping Length (Total) |
|
|
164ft |
|||||||
Max. length (each) |
|
|
|
82ft |
||||||
Min. length |
(total) |
|
|
|
49ft |
|||||
Min. length (each) |
|
|
|
16ft |
||||||
Max. Pipe Height Difference |
|
|
|
|
|
|
||||
|
Between condenser and each indoor unit |
49ft |
||||||||
|
Between indoor units |
|
|
33ft |
||||||
Connection method |
|
|
|
(Flared) |
||||||
Operating Range |
|
|
|
14°F~115°F DB |
||||||
Cooling |
|
|
|
|
||||||
Heating |
|
|
|
|
5°F~75°F DB |
Approval:________________________________
Date:___________________________________
Construction: ____________________________
Unit #:__________________________________
Drawing #:_______________________________
|
Non-Ducted |
Ducted & Non- |
Ducted |
|
Ducted |
||
|
|
|
|
|
|
|
|
SEER |
18 |
16.75 |
15.50 |
|
|
|
|
HSPF |
9.50 |
9.25 |
9.0 |
|
|
|
|
EER |
12.50 |
11.55 |
10.60 |
|
|
|
|
Fujitsu General America, Inc. Fairfield, NJ 07004
Toll Free: 1-888-888-3424 Fax: (973) 836-0447 www.fujitsugeneral.com
Fujitsu products are subject to continuous improvements. Fujitsu reserves the right to modify product design, specifications and information in this data sheet without notice and without incuring any obligations.
Note: Specifications are based on the following conditions. Power source of specifications : 230V
Cooling: Indoor temperature of 80°F(26.67°C)DB / 67°F(19.44°C)WB, and outdoor temperature of 95°F(35°C)DB/75°F(23.89°C)WB. Heating: Indoor temperature of 70°F(21.11°C)DB / 60°F(15.56°C)WB, and outdoor temperature of 47°F(8.33°C)DB/43°F(6.11°C)WB. Pipe length : 24ft. 7in.(7.5m),Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit]