Fujitsu AOU24RLXFZ Installation Manual

Fujitsu AOU24RLXFZ Installation Manual

Hybrid Flex Submittal

AOU24RLXFZ

Hybrid Flex Inverter System Heat Pump

Job Name:_______________________________

Location: ________________________________

Engineer:________________________________

Submitted to:_____________________________

Submitted by:_____________________________

Reference:_______________________________

 

 

 

 

 

 

General Data (at 230V)

Power

 

 

 

 

208-230VAC-1ph-60Hz

Fuse Size, Max.

 

 

 

25A

Minimum Circuit Ampacity(MCA)

 

17A

Compressor

Inverter driven variable speed DC Twin Rotary

 

 

No. used

 

 

 

 

1

 

 

Output

 

 

 

 

1,100W

Lubrican Oil

 

 

 

POE

Fan type

 

 

 

 

Propeller

 

 

 

 

Motor Output

 

 

 

100W

CFM

Cooling/Heating

(High)

 

1,942 / 1,942

 

 

 

Refrigerant

 

 

 

410A

Outdoor unit charge

 

 

 

4lbs 14oz.(2,200g)

Contrlol

 

 

 

Electronic Expansion Valve

O.D. Discharge

 

(in)

 

1/4”x3(Flare)

O.D Suction

 

(in)

 

3/8”x2 + 1/2”x1(Flare)

 

Dimensions

 

 

 

H x W x D

Uncrated

 

 

(in)

 

27-9/16 x 35-7/16 x 13

 

 

 

 

(mm)

 

(700 x 900 x 330)

Crated

 

 

(in)

32-7/8 x 41-11/32 x 17-17/32

 

 

 

 

(mm)

 

(835 x 1,050 x 445)

 

Weight

 

 

 

 

Outdoor

Net

 

 

 

 

124lbs(56kg)

Gross Shipping

 

 

 

139lbs (63kg)

 

Cooling Capacity

 

 

22,000(6,100~27,000)BTU/h

Rated Power Input

 

 

 

1.9kW

Max. Power Input

 

 

 

2.72kW

Outdoor Sound Rating

 

 

51dB

Heating Capacity

 

 

22,000 (6,800-24,400)BTU/h

Rated Power Input

 

 

 

1.84kW

Max. Power Input

 

 

 

2.09kW

Outdoor Sound Rating

 

 

49dB

Piping Lengths

 

 

 

 

 

 

 

 

Pre-charge length

 

 

 

98ft

Max. Piping Length (Total)

 

 

164ft

Max. length (each)

 

 

 

82ft

Min. length

(total)

 

 

 

49ft

Min. length (each)

 

 

 

16ft

Max. Pipe Height Difference

 

 

 

 

 

 

 

Between condenser and each indoor unit

49ft

 

Between indoor units

 

 

33ft

Connection method

 

 

 

(Flared)

Operating Range

 

 

 

14°F~115°F DB

Cooling

 

 

 

 

Heating

 

 

 

 

5°F~75°F DB

Approval:________________________________

Date:___________________________________

Construction: ____________________________

Unit #:__________________________________

Drawing #:_______________________________

 

Non-Ducted

Ducted & Non-

Ducted

 

Ducted

 

 

 

 

 

 

 

SEER

18

16.75

15.50

 

 

 

 

HSPF

9.50

9.25

9.0

 

 

 

 

EER

12.50

11.55

10.60

 

 

 

 

Fujitsu General America, Inc. Fairfield, NJ 07004

Toll Free: 1-888-888-3424 Fax: (973) 836-0447 www.fujitsugeneral.com

Fujitsu products are subject to continuous improvements. Fujitsu reserves the right to modify product design, specifications and information in this data sheet without notice and without incuring any obligations.

Note: Specifications are based on the following conditions. Power source of specifications : 230V

Cooling: Indoor temperature of 80°F(26.67°C)DB / 67°F(19.44°C)WB, and outdoor temperature of 95°F(35°C)DB/75°F(23.89°C)WB. Heating: Indoor temperature of 70°F(21.11°C)DB / 60°F(15.56°C)WB, and outdoor temperature of 47°F(8.33°C)DB/43°F(6.11°C)WB. Pipe length : 24ft. 7in.(7.5m),Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit]