Fujitsu AOU24RLXFZ Installation Manual

Hybrid Flex Submittal
AOU24RLXFZ Hybrid Flex Inverter System Heat Pump
Job Name:_______________________________ Location: ________________________________ Engineer:________________________________ Submitted to: _____________________________ Submitted by:_____________________________ Reference:_______________________________
Power 208-230VAC-1ph-60Hz Fuse Size, Max. 25A Minimum Circuit Ampacity(MCA) 17A Compressor Inverter driven variable speed DC Twin Rotary No. used 1 Output 1,100W Lubrican Oil Fan type Propeller Motor Output 100W CFM Cooling/Heating (High)
Refrigerant 410A Outdoor unit charge 4lbs 14oz.(2,200g) Contrlol Electronic Expansion Valve O.D. Discharge (in) 1/4”x3(Flare) O.D Suction (in)
Dimensions H x W x D Uncrated (in) 27-9/16 x 35-7/16 x 13
Crated (in) 32-7/8 x 41-11/32 x 17-17/32
(mm) (835 x 1,050 x 445)
Weight Outdoor Net 124lbs(56kg) Gross Shipping
Cooling Capacity 22,000(6,100~27,000)BTU/h Rated Power Input 1.9kW Max. Power Input 2.72kW Outdoor Sound Rating
Heating Capacity 22,000 (6,800-24,400)BTU/h Rated Power Input 1.84kW Max. Power Input 2.09kW Outdoor Sound Rating
Piping Lengths
Pre-charge length 98ft Max. Piping Length (Total) 164ft Max. length (each) 82ft Min. length (total) 49ft Min. length (each) 16ft Max. Pipe Height Difference
Between condenser and each indoor unit 49ft Between indoor units 33ft
Connection method (Flared)
Operating Range
Cooling 14°F~115°F DB Heating 5°F~75°F DB
(mm) (700 x 900 x 330)
51dB
POE
1,942 / 1,942
3/8”x2 + 1/2”x1(Flare)
139lbs (63kg)
49dB
Approval:________________________________ Date:___________________________________ Construction: ____________________________ Unit #:__________________________________ Drawing #:_______________________________
Non-Ducted
SEER 18 16.75 15.50
HSPF 9.50 9.25 9.0
EER 12.50 11.55 10.60
Fujitsu General America, Inc. Fairfield, NJ 07004 Toll Free: 1-888-888-3424 Fax: (973) 836-0447 www.fujitsugeneral.com
Note: Specifications are based on the following conditions. Power source of specifications : 230V Cooling: Indoor temperature of 80°F(26.67°C)DB / 67°F(19.44°C)WB, and outdoor temperature of 95°F(35°C)DB/75°F(23.89°C)WB. Heating: Indoor temperature of 70°F(21.11°C)DB / 60°F(15.56°C)WB, and outdoor temperature of 47°F(8.33°C)DB/43°F(6.11°C)WB. Pipe length : 24ft. 7in.(7.5m),Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit]
Ducted & Non-
Ducted
Fujitsu products are subject to continu­ous improvements. Fujitsu reserves the right to modify product design, specifications and information in this data sheet without notice and without incuring any obligations.
Ducted
Loading...