Hybrid Flex Submittal
AOU24RLXFZ
Hybrid Flex Inverter System Heat Pump
Job Name:_______________________________
Location: ________________________________
Engineer:________________________________
Submitted to: _____________________________
Submitted by:_____________________________
Reference:_______________________________
Power 208-230VAC-1ph-60Hz
Fuse Size, Max. 25A
Minimum Circuit Ampacity(MCA) 17A
Compressor Inverter driven variable speed DC Twin Rotary
No. used 1
Output 1,100W
Lubrican Oil
Fan type Propeller
Motor Output 100W
CFM Cooling/Heating (High)
Refrigerant 410A
Outdoor unit charge 4lbs 14oz.(2,200g)
Contrlol Electronic Expansion Valve
O.D. Discharge (in) 1/4”x3(Flare)
O.D Suction (in)
Dimensions H x W x D
Uncrated (in) 27-9/16 x 35-7/16 x 13
Crated (in) 32-7/8 x 41-11/32 x 17-17/32
(mm) (835 x 1,050 x 445)
Weight Outdoor
Net 124lbs(56kg)
Gross Shipping
Cooling Capacity 22,000(6,100~27,000)BTU/h
Rated Power Input 1.9kW
Max. Power Input 2.72kW
Outdoor Sound Rating
Heating Capacity 22,000 (6,800-24,400)BTU/h
Rated Power Input 1.84kW
Max. Power Input 2.09kW
Outdoor Sound Rating
Piping Lengths
Pre-charge length 98ft
Max. Piping Length (Total) 164ft
Max. length (each) 82ft
Min. length (total) 49ft
Min. length (each) 16ft
Max. Pipe Height Difference
Between condenser and each indoor unit 49ft
Between indoor units 33ft
Connection method (Flared)
Operating Range
Cooling 14°F~115°F DB
Heating 5°F~75°F DB
(mm) (700 x 900 x 330)
51dB
General Data (at 230V)
POE
1,942 / 1,942
3/8”x2 + 1/2”x1(Flare)
139lbs (63kg)
49dB
Approval:________________________________
Date:___________________________________
Construction: ____________________________
Unit #:__________________________________
Drawing #:_______________________________
Non-Ducted
SEER 18 16.75 15.50
HSPF 9.50 9.25 9.0
EER 12.50 11.55 10.60
Fujitsu General America, Inc.
Fairfield, NJ 07004
Toll Free: 1-888-888-3424
Fax: (973) 836-0447
www.fujitsugeneral.com
Note: Specifications are based on the following conditions.
Power source of specifications : 230V
Cooling: Indoor temperature of 80°F(26.67°C)DB / 67°F(19.44°C)WB, and outdoor temperature of 95°F(35°C)DB/75°F(23.89°C)WB.
Heating: Indoor temperature of 70°F(21.11°C)DB / 60°F(15.56°C)WB, and outdoor temperature of 47°F(8.33°C)DB/43°F(6.11°C)WB.
Pipe length : 24ft. 7in.(7.5m),Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit]
Ducted & Non-
Ducted
Fujitsu products are subject to continuous improvements. Fujitsu reserves
the right to modify product design,
specifications and information in this
data sheet without notice and without
incuring any obligations.
Ducted