Fujitsu ASU18RLF, ASU24RLF, AOU18RLXFWH, AOU24RLXFWH Design & Technical Manual

Page 1
AIR CONDITIONER
Wall mounted type
DESIGN & TECHNICAL MANUAL
For Extra Cold Climate Area
INDOOR
ASU18RLF ASU24RLF
OUTDOOR
DR_AS014EF_04
2017.03.10
Page 2
Notices:
• Product specifications and design are subject to change without notice for future improvement.
• For further details, please check with our authorized dealer.
Copyright © 2016, 2017 Fujitsu General Limited. All rights reserved.
Page 3
CONTENTS
Part 1. INDOOR UNIT....................................................................... 1
1. Specifications............................................................................................2
2. Dimensions................................................................................................3
2-1. Models: ASU18RLF and ASU24RLF .......................................................................... 3
3. Wiring diagrams ........................................................................................5
3-1. Models: ASU18RLF and ASU24RLF .......................................................................... 5
4. Capacity table............................................................................................6
4-1. Cooling capacity.......................................................................................................... 6
4-2. Heating capacity .........................................................................................................8
5. Fan performance .......................................................................................9
5-1. Air velocity distributions............................................................................................... 9
5-2. Airflow....................................................................................................................... 12
6. Operation noise (sound pressure)......................................................... 14
6-1. Noise level curve....................................................................................................... 14
6-2. Sound level check point............................................................................................ 15
7. Safety devices ......................................................................................... 16
8. External input and output.......................................................................17
8-1. External input............................................................................................................ 17
8-2. External output.......................................................................................................... 19
9. Remote controller ...................................................................................20
9-1. Wireless remote controller ........................................................................................ 20
10. Function settings .................................................................................... 22
10-1.Function settings by using remote controller............................................................ 22
11. Accessories.............................................................................................29
12. Optional parts..........................................................................................30
12-1.Controllers ............................................................................................................... 30
12-2.Others...................................................................................................................... 30
Page 4
Part 2. OUTDOOR UNIT................................................................. 31
1. Specifications..........................................................................................32
2. Dimensions..............................................................................................33
2-1. Models: AOU18RLXFWH and AOU24RLXFWH....................................................... 33
3. Installation space ....................................................................................34
3-1. Models: AOU18RLXFWH and AOU24RLXFWH....................................................... 34
4. Refrigerant circuit ................................................................................... 37
4-1. Models: AOU18RLXFWH and AOU24RLXFWH....................................................... 37
5. Wiring diagrams ......................................................................................38
5-1. Model: AOU18RLXFWH ........................................................................................... 38
5-2. Model: AOU24RLXFWH ........................................................................................... 39
6. Capacity compensation rate for pipe length and height difference....40
6-1. Models: AOU18RLXFWH and AOU24RLXFWH....................................................... 40
7. Additional charge calculation ................................................................ 41
7-1. Models: AOU18RLXFWH and AOU24RLXFWH....................................................... 41
8. Airflow......................................................................................................42
8-1. Model: AOU18RLXFWH ........................................................................................... 42
8-2. Model: AOU24RLXFWH ........................................................................................... 42
9. Operation noise (sound pressure)......................................................... 43
9-1. Noise level curve....................................................................................................... 43
9-2. Sound level check point............................................................................................ 44
10. Electrical characteristics........................................................................45
11. Safety devices ......................................................................................... 46
12. Accessories.............................................................................................47
CONTENTS (continued)
Page 5
Part 1. INDOOR UNIT
WALL MOUNTED TYPE:
ASU18RLF ASU24RLF
Page 6
1. Specifications
Type
Wall mounted
Inverter heat pump
Model name ASU18RLF ASU24RLF
Power supply 208/230 V ~ 60 Hz Available voltage range 187—253 V
Capacity
Cooling
Rated
kW 5.28 6.44
Btu/h 18,000 22,000
Min.—Max.
kW 2.05—6.74 2.90—8.00
Btu/h 7,000—23,000 9,900—27,300
Heating
Rated
kW 6.30 7.38
Btu/h 21,600 25,200
Min.—Max.
kW 2.05—8.50 2.20—10.61
Btu/h 7,000—29,000 7,500—36,200
Input power
Cooling
Rated
kW
1.35 1.76
Min.—Max. 0.50—3.01 0.58—3.42
Heating
Rated 1.75 1.94 Min.—Max. 0.48—3.23 0.50—3.53
Current
Cooling
Rated A
6.2 7.9
Heating 7.8 8.6
EER Cooling
kW/kW 3.90 3.66 Btu/hW 13.3 12.5
COP Heating
kW/kW 3.62 3.80
Btu/hW 12.3 13.0 SEER Cooling Btu/hW 20.0 19.5 HSPF Heating Btu/hW 10.4 10.5
Power factor
Cooling
%
95.0 97.0
Heating 97.6 98.1
Moisture removal pints/h (L/h) 5.9 (2.8) 6.3 (3.0)
Maximum operating current *1
Cooling
A
13.5 15.0
Heating 14.5 15.5
Fan
Airflow rate
Cooling
HIGH
CFM (m3/h)
541 (920) 659 (1,120) MED 435 (740) 530 (900) LOW 365 (620) 435 (740) QUIET 306 (520) 365 (620)
Heating
HIGH 541 (920) 677 (1,150) MED 435 (740) 530 (900) LOW 365 (620) 435 (740) QUIET 318 (540) 365 (620)
Type × Q'ty Cross flow fan × 1 Motor output W 53
Sound pressure level *2
Cooling
HIGH
dB (A)
43 49 MED 37 42 LOW 33 37 QUIET 28 33
Heating
HIGH 44 49 MED 37 42 LOW 33 37 QUIET 28 33
Heat exchanger type
Dimensions (H × W × D) in (mm)
Main: 14-7/8 × 32-3/4 × 1-1/16 (378 × 832 × 26.6)
Sub: 3-5/16 × 32-3/4 × 1/2 (84 × 832 × 13.3) Fin pitch FPI Main: 21, Sub: 18 Rows × Stages Main: 2 × 18, Sub: 1 × 4 Pipe type Copper tube Fin type Aluminum
Enclosure
Material Polystyrene
Color
White
Approximate color of Munsell N 9.25/
Dimensions (H × W × D)
Net
in 12-5/8 × 39-5/16 × 9
mm 320 × 998 × 228
Gross
in 12-9/16 × 42-15/16 × 16-7/8
mm 319 × 1,090 × 429
Weight
Net
lb (kg)
31 (14)
Gross 40 (18)
Connection pipe
Size
Liquid
in (mm)
Ø 3/8 (Ø 9.52)
Gas Ø 5/8 (Ø 15.88)
Method Flare
Drain hose
Material PVC Size in (mm) Ø 15/32 (Ø 12) (I.D.), Ø 5/8 (Ø 16) (O.D.)
Operation range
Cooling
°F (°C) 64 to 90 (18 to 32)
%RH 80 or less
Heating °F (°C) 88 (30) or less
Remote controller type Wireless (Wired [option])
NOTES:
• Specifications are based on the following conditions: – Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) /67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB). – Heating: Indoor temperature of 70 °FDB (21.11 °CDB) /59 °FWB (15 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) /43 °FWB (6.11 °CWB). – Pipe length: 24 ft 6 in (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum current is maximum value when operated within the operation range.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 2 -
WALL MOUNTED
ASU18, 24RLF
Page 7
2. Dimensions
2-1. Models: ASU18RLF and ASU24RLF
Unit: in (mm)
39-5/16 (998)
17-5/16 (439)
17-1/4 (438)
15-5/8 (397)
12-5/8 (320): Unit size
10-9/16 (269)
13/16 (20)
1-7/16 (37)
1 x 7/16 (26 x 11) hole
3/16 x 11/16 (5 x 18): 14 holes
13/16 x 3/16 (21 x 5): 14holes
3/16 x 1-15/16 (5 x 50): 3 holes
1/2 x 3/16 (13 x 5): 4 holes
ø3-1/8 (80) hole
ø3/16 (5): 65 holes
39-3/8 (1,000): Unit size
Piping inlet
for tapping screw
11/16 x 7/16 (18 x 11) hole
11/16 x 7/16 (18 x 11) hole
4-13/16 (122)
6-3/4 (172)
2-15/16 (75)
15-1/4 (387)
6-11/16 (170)
5/8 (16)
15-3/4 (400)
Unit center
4-15/16 (126)
5-1/4 (133)
5-1/8 (130)
4-7/16 (113)
2-15/16 (75)
9-9/16 (243)
9 (228)
12-5/8 (320)
20-1/2 (520)
23-1/4 (590)
28-3/8 (721)
ø3-1/8 (80) hole
Piping inlet
1-3/16 (30)
1-3/16 (30)
5-7/8 (149)
7-3/4 (197)
10-11/16 (272)
1-1/8 (44)
1/2
(12)
1/2 (13)
1 x 7/16 (26 x 11) hole
1 (25)
ø1-1/4 (32)
ø5/8 (16)
ø1/2 (12)
- 3 -
WALL MOUNTED
ASU18, 24RLF
Page 8
¢
Installation space requirement
Provide sufficient installation space for product safety.
Unit: in (mm)
3 (63) or more
4 (80) or more
3 (52) or more 3 (53) or more
4 (80) or more
Outline of unit
5 (120) or more
60 (1,500) or more
71 (1,800) or more
- 4 -
WALL MOUNTED
ASU18, 24RLF
Page 9
3. Wiring diagrams
3-1. Models: ASU18RLF and ASU24RLF
- 5 -
WALL MOUNTED
ASU18, 24RLF
Page 10
4. Capacity table
Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR):
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP)
4-1. Cooling capacity
¢
Model: ASU18RLF
AFR CFM 541
Indoor temperature °FDB 64 70 75 80 85 90 °FWB 54 60 63 67 71 73
Outdoor temperature
°FDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kBtu kW kBtu kW kBtu kW kBtu kW kBtu kW kBtu kW
-5 17.81 11.45 0.29 19.85 11.51 0.29 21.88 12.56 0.29 22.55 13.56 0.30 23.89 13.52 0.30 25.27 14.39 0.30 5 17.80 11.47 0.36 19.83 11.54 0.36 21.86 12.58 0.36 22.53 13.59 0.37 23.87 13.54 0.37 25.24 14.42 0.37
14 17.77 11.20 0.42 19.79 11.27 0.43 21.84 12.29 0.43 22.49 13.28 0.44 23.85 13.23 0.44 25.19 14.09 0.44 23 17.77 11.43 0.49 19.77 11.50 0.50 21.82 12.54 0.50 22.49 13.55 0.51 23.85 13.48 0.51 25.17 14.36 0.52 32 17.74 11.64 0.56 19.77 11.71 0.57 21.82 12.77 0.57 22.47 13.80 0.58 23.82 13.75 0.58 25.14 14.65 0.59 41 17.74 11.18 0.62 19.75 11.27 0.63 21.80 12.27 0.64 22.47 13.26 0.65 23.82 13.21 0.65 25.14 14.07 0.66 50 17.70 11.41 0.71 19.70 11.50 0.72 21.75 12.54 0.73 22.40 13.55 0.73 23.75 13.48 0.74 25.07 14.36 0.74 59 17.37 11.16 0.78 19.35 11.23 0.79 21.33 12.25 0.80 21.97 13.24 0.81 23.30 13.17 0.81 24.60 14.02 0.82 67 16.65 10.85 0.92 18.56 10.92 0.93 20.47 11.91 0.95 21.09 12.86 0.95 22.35 12.83 0.96 23.61 13.65 0.97 77 15.90 10.54 1.06 17.74 10.61 1.07 19.55 11.57 1.09 20.13 12.49 1.09 21.36 12.45 1.11 22.55 13.27 1.12 87 15.12 10.20 1.19 16.82 10.27 1.21 18.56 11.19 1.23 19.14 12.11 1.23 20.27 12.04 1.25 21.43 12.83 1.26
95 14.23 9.86 1.30 15.87 9.93 1.32 17.47 10.82 1.34 18.02 11.67 1.35 19.11 11.63 1.36 20.16 12.39 1.38 104 13.58 9.59 1.45 15.12 9.66 1.47 16.65 10.54 1.49 17.16 11.36 1.50 18.22 11.33 1.51 19.24 12.08 1.53 115 12.39 9.14 1.62 13.78 9.18 1.65 15.22 10.03 1.67 15.66 10.82 1.68 16.62 10.78 1.70 17.57 11.50 1.72
AFR
m3/h
920
Indoor temperature
°CDB 17.8 21.1 23.9 26.7 29.4 32.2
°CWB 12.2 15.6 17.2 19.4 21.7 22.8
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW
-20.6 5.22 3.36 0.29 5.82 3.37 0.29 6.41 3.68 0.29 6.61 3.97 0.30 7.00 3.96 0.30 7.41 4.22 0.30
-15.0 5.22 3.36 0.36 5.81 3.38 0.36 6.41 3.69 0.36 6.60 3.98 0.37 7.00 3.97 0.37 7.40 4.23 0.37
-10.0 5.21 3.28 0.42 5.80 3.30 0.43 6.40 3.60 0.43 6.59 3.89 0.44 6.99 3.88 0.44 7.38 4.13 0.44
-5.0 5.21 3.35 0.49 5.79 3.37 0.50 6.40 3.68 0.50 6.59 3.97 0.51 6.99 3.95 0.51 7.38 4.21 0.52
0.0 5.20 3.41 0.56 5.79 3.43 0.57 6.40 3.74 0.57 6.59 4.05 0.58 6.98 4.03 0.58 7.37 4.29 0.59
5.0 5.20 3.28 0.62 5.79 3.30 0.63 6.39 3.60 0.64 6.59 3.89 0.65 6.98 3.87 0.65 7.37 4.12 0.66
10.0 5.19 3.34 0.71 5.77 3.37 0.72 6.37 3.68 0.73 6.56 3.97 0.73 6.96 3.95 0.74 7.35 4.21 0.74
15.0 5.09 3.27 0.78 5.67 3.29 0.79 6.25 3.59 0.80 6.44 3.88 0.81 6.83 3.86 0.81 7.21 4.11 0.82
19.4 4.88 3.18 0.92 5.44 3.20 0.93 6.00 3.49 0.95 6.18 3.77 0.95 6.55 3.76 0.96 6.92 4.00 0.97
25.0 4.66 3.09 1.06 5.20 3.11 1.07 5.73 3.39 1.09 5.90 3.66 1.09 6.26 3.65 1.11 6.61 3.89 1.12
30.6 4.43 2.99 1.19 4.93 3.01 1.21 5.44 3.28 1.23 5.61 3.55 1.23 5.94 3.53 1.25 6.28 3.76 1.26
35.0 4.17 2.89 1.30 4.65 2.91 1.32 5.12 3.17 1.34 5.28 3.42 1.35 5.60 3.41 1.36 5.91 3.63 1.38
40.0 3.98 2.81 1.45 4.43 2.83 1.47 4.88 3.09 1.49 5.03 3.33 1.50 5.34 3.32 1.51 5.64 3.54 1.53
46.1 3.63 2.68 1.62 4.04 2.69 1.65 4.46 2.94 1.67 4.59 3.17 1.68 4.87 3.16 1.70 5.15 3.37 1.72
- 6 -
WALL MOUNTED
ASU18, 24RLF
Page 11
¢
Model: ASU24RLF
AFR CFM 659
Indoor temperature °FDB 64 70 75 80 85 90 °FWB 54 60 63 67 71 73
Outdoor temperature
°FDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kBtu kW kBtu kW kBtu kW kBtu kW kBtu kW kBtu kW
-5 19.12 11.45 0.30 21.30 11.51 0.30 23.48 12.56 0.31 24.19 13.56 0.31 25.64 13.52 0.32 27.11 14.39 0.32 5 19.10 11.47 0.37 21.28 11.54 0.38 23.46 12.58 0.38 24.17 13.59 0.39 25.62 13.54 0.39 27.09 14.42 0.39
14 19.06 11.37 0.45 21.23 11.44 0.45 23.42 12.46 0.46 24.13 13.45 0.46 25.56 13.40 0.47 27.04 14.29 0.47 23 19.06 11.60 0.52 21.20 11.67 0.52 23.39 12.72 0.53 24.13 13.73 0.54 25.56 13.66 0.54 27.02 14.57 0.54 32 19.03 11.81 0.59 21.20 11.88 0.60 23.39 12.95 0.60 24.11 13.98 0.61 25.53 13.93 0.61 26.99 14.86 0.62 41 19.03 11.35 0.65 21.18 11.44 0.66 23.37 12.44 0.67 24.11 13.43 0.68 25.53 13.38 0.68 26.99 14.27 0.69 50 18.98 11.58 0.74 21.12 11.67 0.75 23.32 12.72 0.76 24.03 13.73 0.77 25.46 13.66 0.77 26.92 14.57 0.78 59 18.63 11.33 0.82 20.74 11.40 0.83 22.86 12.42 0.84 23.58 13.41 0.85 24.98 13.34 0.85 26.41 14.23 0.86 67 17.91 11.05 0.95 19.96 11.12 0.97 21.97 12.15 0.98 22.66 13.10 0.99 24.02 13.07 1.00 25.39 13.92 1.01 77 19.31 11.57 1.37 21.50 11.63 1.39 23.71 12.69 1.41 24.43 13.72 1.42 25.90 13.65 1.43 27.36 14.54 1.44 87 18.36 11.23 1.53 20.47 11.29 1.55 22.55 12.32 1.58 23.27 13.31 1.58 24.63 13.24 1.60 26.03 14.13 1.61
95 17.37 10.88 1.70 19.35 10.92 1.72 21.33 11.94 1.75 21.97 12.86 1.76 23.30 12.83 1.78 24.60 13.65 1.80 104 16.24 10.47 1.86 18.08 10.54 1.89 19.93 11.50 1.92 20.54 12.42 1.93 21.77 12.35 1.95 23.00 13.17 1.97 115 12.35 9.21 1.56 13.75 9.28 1.58 15.18 10.13 1.61 15.63 10.92 1.61 16.58 10.88 1.63 17.50 11.60 1.65
AFR
m3/h
1,120
Indoor temperature
°CDB 17.8 21.1 23.9 26.7 29.4 32.2
°CWB 12.2 15.6 17.2 19.4 21.7 22.8
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW
-20.6 5.60 3.36 0.30 6.24 3.37 0.30 6.88 3.68 0.31 7.09 3.97 0.31 7.51 3.96 0.32 7.95 4.22 0.32
-15.0 5.60 3.36 0.37 6.24 3.38 0.38 6.88 3.69 0.38 7.08 3.98 0.39 7.51 3.97 0.39 7.94 4.23 0.39
-10.0 5.59 3.33 0.45 6.22 3.35 0.45 6.86 3.65 0.46 7.07 3.94 0.46 7.49 3.93 0.47 7.93 4.19 0.47
-5.0 5.59 3.40 0.52 6.21 3.42 0.52 6.86 3.73 0.53 7.07 4.02 0.54 7.49 4.00 0.54 7.92 4.27 0.54
0.0 5.58 3.46 0.59 6.21 3.48 0.60 6.86 3.80 0.60 7.07 4.10 0.61 7.48 4.08 0.61 7.91 4.36 0.62
5.0 5.58 3.33 0.65 6.21 3.35 0.66 6.85 3.65 0.67 7.07 3.94 0.68 7.48 3.92 0.68 7.91 4.18 0.69
10.0 5.56 3.39 0.74 6.19 3.42 0.75 6.83 3.73 0.76 7.04 4.02 0.77 7.46 4.00 0.77 7.89 4.27 0.78
15.0 5.46 3.32 0.82 6.08 3.34 0.83 6.70 3.64 0.84 6.91 3.93 0.85 7.32 3.91 0.85 7.74 4.17 0.86
19.4 5.25 3.24 0.95 5.85 3.26 0.97 6.44 3.56 0.98 6.64 3.84 0.99 7.04 3.83 1.00 7.44 4.08 1.01
25.0 5.66 3.39 1.37 6.30 3.41 1.39 6.95 3.72 1.41 7.16 4.02 1.42 7.59 4.00 1.43 8.02 4.26 1.44
30.6 5.38 3.29 1.53 6.00 3.31 1.55 6.61 3.61 1.58 6.82 3.90 1.58 7.22 3.88 1.60 7.63 4.14 1.61
35.0 5.09 3.19 1.70 5.67 3.20 1.72 6.25 3.50 1.75 6.44 3.77 1.76 6.83 3.76 1.78 7.21 4.00 1.80
40.0 4.76 3.07 1.86 5.30 3.09 1.89 5.84 3.37 1.92 6.02 3.64 1.93 6.38 3.62 1.95 6.74 3.86 1.97
46.1 3.62 2.70 1.56 4.03 2.72 1.58 4.45 2.97 1.61 4.58 3.20 1.61 4.86 3.19 1.63 5.13 3.40 1.65
- 7 -
WALL MOUNTED
ASU18, 24RLF
Page 12
4-2. Heating capacity
¢
Model: ASU18RLF
AFR CFM 541
Indoor temperature
°FDB 60 65 70 72 75
Outdoor temperature
°FDB °FWB
TC IP TC IP TC IP TC IP TC IP
kBtu kW kBtu kW kBtu kW kBtu kW kBtu kW
-15 -17 18.80 1.76 18.37 1.80 17.91 1.83 17.46 1.87 17.02 1.90
-5 -7 20.67 2.28 20.20 2.33 19.70 2.37 19.19 2.42 18.72 2.46 5 3 22.67 2.65 22.13 2.70 21.60 2.75 21.06 2.80 20.53 2.85
14 12 23.46 2.82 22.89 2.88 22.37 2.93 21.80 2.99 21.24 3.04 23 19 24.70 3.01 24.12 3.07 23.51 3.13 22.93 3.19 22.35 3.25 32 28 27.47 3.02 26.82 3.08 26.17 3.14 25.52 3.20 24.87 3.26 41 37 29.31 2.84 28.59 2.90 27.91 2.96 27.23 3.02 26.51 3.08 47 43 30.47 2.87 29.72 2.93 29.00 2.99 28.29 3.05 27.57 3.11 50 47 30.98 2.85 30.26 2.91 29.51 2.97 28.76 3.03 28.05 3.09 59 50 29.24 2.48 28.56 2.53 27.84 2.58 27.16 2.63 26.44 2.68
AFR
m3/h
920
Indoor temperature
°CDB 15.6 18.3 21.1 22.2 23.9
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-26.1 -27.2 5.51 1.76 5.38 1.80 5.25 1.83 5.12 1.87 4.99 1.90
-20.6 -21.7 6.06 2.28 5.92 2.33 5.77 2.37 5.63 2.42 5.49 2.46
-15.0 -16.1 6.64 2.65 6.49 2.70 6.33 2.75 6.17 2.80 6.02 2.85
-10.0 -11.1 6.87 2.82 6.71 2.88 6.56 2.93 6.39 2.99 6.22 3.04
-5.0 -7.2 7.24 3.01 7.07 3.07 6.89 3.13 6.72 3.19 6.55 3.25
0.0 -2.2 8.05 3.02 7.86 3.08 7.67 3.14 7.48 3.20 7.29 3.26
5.0 2.8 8.59 2.84 8.38 2.90 8.18 2.96 7.98 3.02 7.77 3.08
8.3 6.1 8.93 2.87 8.71 2.93 8.50 2.99 8.29 3.05 8.08 3.11
10.0 8.3 9.08 2.85 8.87 2.91 8.65 2.97 8.43 3.03 8.22 3.09
15.0 10.0 8.57 2.48 8.37 2.53 8.16 2.58 7.96 2.63 7.75 2.68
¢
Model: ASU24RLF
AFR CFM 677
Indoor temperature
°FDB 60 65 70 72 75
Outdoor temperature
°FDB °FWB
TC IP TC IP TC IP TC IP TC IP
kBtu kW kBtu kW kBtu kW kBtu kW kBtu kW
-15 -17 20.71 3.09 20.24 3.16 19.73 3.22 19.23 3.28 18.75 3.34
-5 -7 23.66 3.30 23.12 3.36 22.54 3.43 21.97 3.50 21.43 3.56 5 3 26.47 3.45 25.86 3.52 25.21 3.59 24.57 3.66 23.96 3.73
14 12 28.20 3.47 27.53 3.54 26.87 3.61 26.21 3.68 25.51 3.75 23 19 30.78 3.42 30.06 3.49 29.31 3.56 28.59 3.63 27.84 3.70 32 28 33.81 3.42 32.99 3.48 32.21 3.55 31.39 3.62 30.61 3.69 41 37 36.88 3.29 36.00 3.36 35.14 3.43 34.26 3.49 33.37 3.56 47 43 37.98 3.25 37.09 3.32 36.17 3.38 35.28 3.45 34.36 3.52 50 47 38.69 3.24 37.77 3.31 36.85 3.37 35.93 3.44 35.01 3.51 59 50 36.85 2.85 36.00 2.91 35.11 2.97 34.22 3.03 33.37 3.09
AFR
m3/h
1,150
Indoor temperature
°CDB 15.6 18.3 21.1 22.2 23.9
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-26.1 -27.2 6.07 3.09 5.93 3.16 5.78 3.22 5.64 3.28 5.50 3.34
-20.6 -21.7 6.94 3.30 6.78 3.36 6.61 3.43 6.44 3.50 6.28 3.56
-15.0 -16.1 7.76 3.45 7.58 3.52 7.39 3.59 7.20 3.66 7.02 3.73
-10.0 -11.1 8.26 3.47 8.07 3.54 7.88 3.61 7.68 3.68 7.48 3.75
-5.0 -7.2 9.02 3.42 8.81 3.49 8.59 3.56 8.38 3.63 8.16 3.70
0.0 -2.2 9.91 3.42 9.67 3.48 9.44 3.55 9.20 3.62 8.97 3.69
5.0 2.8 10.81 3.29 10.55 3.36 10.30 3.43 10.04 3.49 9.78 3.56
8.3 6.1 11.13 3.25 10.87 3.32 10.60 3.38 10.34 3.45 10.07 3.52
10.0 8.3 11.34 3.24 11.07 3.31 10.80 3.37 10.53 3.44 10.26 3.51
15.0 10.0 10.80 2.85 10.55 2.91 10.29 2.97 10.03 3.03 9.78 3.09
- 8 -
WALL MOUNTED
ASU18, 24RLF
Page 13
5. Fan performance
5-1. Air velocity distributions
¢
Model: ASU18RLF
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
2
1
0
1
2
(m)
(m)
Unit: ft/s (m/s)
012345678
(ft)
7142027
7
3
0
3
7
(ft)
7 (2) 3 (1) 2 (0.5)
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
3
2
1
0
1
2
3
(m)
(m)
Unit: ft/s (m/s)
012345678
(ft)
7142027
10
7
3
0
3
7
10
(ft)
2 (0.5)
2 (0.5)
3 (1)
3 (1)
7 (2)
7 (2)
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
3
2
1
0
(m)
(m)
Unit: ft/s (m/s)
012345678
(ft)
7142027
10
7
3
0
(ft)
7 (2)
3 (1)
2 (0.5)
- 9 -
WALL MOUNTED
ASU18, 24RLF
Page 14
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
3
2
1
0
(m)
(m)
Unit: ft/s (m/s)
012345678
(ft)
7142027
10
7
3
0
(ft)
7 (2)
3 (1)
2 (0.5)
- 10 -
WALL MOUNTED
ASU18, 24RLF
Page 15
¢
Model: ASU24RLF
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
2
1
0
1
2
(m)
(m)
Unit: ft/s (m/s)
012345678
(ft)
7142027
7
3
0
3
7
(ft)
7 (2) 3 (1)
2 (0.5)
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
3
2
1
0
1
2
3
(m)
(m)
Unit: ft/s (m/s)
012345678
(ft)
7142027
10
7
3
0
3
7
10
(ft)
2 (0.5)
2 (0.5)
3 (1)
3 (1)
7 (2)
7 (2)
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
3
2
1
0
(m)
(m)
Unit : ft/s (m/s)
012345678
(ft)
7142027
10
7
3
0
(ft)
7 (2)
3 (1)
2 (0.5)
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
3
2
1
0
(m)
(m)
Unit: ft/s (m/s)
012345678
(ft)
7142027
10
7
3
0
(ft)
7 (2)
3 (1)
2 (0.5)
- 11 -
WALL MOUNTED
ASU18, 24RLF
Page 16
5-2. Airflow
¢
Model: ASU18RLF
Cooling
Fan speed Airflow
HIGH
m3/h
920
l/s 256
CFM 541
MED
m3/h
740
l/s 206
CFM 435
LOW
m3/h
620
l/s 172
CFM 365
QUIET
m3/h
520
l/s 144
CFM 306
Heating
Fan speed Airflow
HIGH
m3/h
920
l/s 256
CFM 541
MED
m3/h
740
l/s 206
CFM 435
LOW
m3/h
620
l/s 172
CFM 365
QUIET
m3/h
540
l/s 150
CFM 318
- 12 -
WALL MOUNTED
ASU18, 24RLF
Page 17
¢
Model: ASU24RLF
Cooling
Fan speed Airflow
HIGH
m3/h
1,120
l/s 311
CFM 659
MED
m3/h
900
l/s 250
CFM 530
LOW
m3/h
740
l/s 206
CFM 435
QUIET
m3/h
620
l/s 172
CFM 365
Heating
Fan speed Airflow
HIGH
m3/h
1,150
l/s 319
CFM 677
MED
m3/h
900
l/s 250
CFM 530
LOW
m3/h
740
l/s 206
CFM 435
QUIET
m3/h
620
l/s 172
CFM 365
- 13 -
WALL MOUNTED
ASU18, 24RLF
Page 18
6. Operation noise (sound pressure)
6-1. Noise level curve
¢
Model: ASU18RLF
Cooling
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
HIGH
QUIET
Heating
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000 8,000
HIGH
QUIET
¢
Model: ASU24RLF
Cooling
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
HIGH
QUIET
Heating
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
HIGH
QUIET
- 14 -
WALL MOUNTED
ASU18, 24RLF
Page 19
6-2. Sound level check point
2 ft 7
-5/8
in (0.8 m)
3 ft 3
-3/8
in (1 m)
Microphone Microphone
NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated
above.
- 15 -
WALL MOUNTED
ASU18, 24RLF
Page 20
7. Safety devices
Type of protection Protection form
Model
ASU18RLF ASU24RLF
Circuit protection Current fuse (PCB*) 250 V, 3.15 A Terminal protection Current fuse 250 V, 3 A
Fan motor protection
Thermistor protection
Activate
More than 185°F (85°C)
Fan motor speed down
Reset
Less than 185°F (85°C)
Fan motor speed recover
Power IC thermal shutdown protection
Activate
302±27°F (150±15°C)
Fan motor stop
Reset
Less than 275°F (135°C)
Fan motor restart
*PCB: Printed Circuit Board
- 16 -
WALL MOUNTED
ASU18, 24RLF
Page 21
8. External input and output
With using external input and output functions, this product can be operated inter-connectedly with an external device.
Connector Input Output Remarks
CN14 Control input
See external input/output
settings for details.
CN16 Operation status output
8-1. External input
With using external input function, some functions on this product can be controlled from an exter­nal device.
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m).
• The wire connection should be separate from the power cable line.
¢
Control input (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work. Unit operation is started at the following contents by adding the contact input of a commercial
on/off switch to a connector on the external control PCB and turning it on.
Unit operation Initial setting after power is on
Starting mode other than initial
setting
Operation mode Auto changeover Mode at previous operation Set temperature 76 °F (24 °C) Temperature at previous operation
Airflow mode AUTO Mode at previous operation
Air direction (swing) Standard air direction (swing OFF) Air direction at previous operation
- 17 -
WALL MOUNTED
ASU18, 24RLF
Page 22
Circuit diagram example
Indoor unit
control PCB
Example: Switch
Locally purchased
Connected unit
1
3
Signal
Connector
*33 ft. (10 m)
• Contact capacity: DC 24 V or more, 10 mA or more.
• *: Make the distance from the PCB to the con­nected unit within 33 ft (10 m).
• Use non-polar relays and switches.
• When function setting is "Operation/Stop" mode
Operation
Stop
On
Off
Input signal
Indoor unit
• When function setting is "Forced stop" mode
Remote controller
On On On
Input signal
Indoor unit
Command
Remote control operation invalidity
On
Off
Operation
Stop
Forced stop
Normal
Optional part
Part name Model name Exterior
External connect kit UTY-XWZX
External input wire
- 18 -
WALL MOUNTED
ASU18, 24RLF
Page 23
8-2. External output
With using external output function, operating status of this product can be transmitted to the ex­ternal device, and also, this product can be inter-connected with the external device.
¢
Operation status output
Air conditioner operation status signal can be output.
Circuit diagram example
Locally purchased
Indoor unit
control PCB
Connected unit
Example: Display
Example: Relay unit
Relay power supply
DC 24 V
1
2
Signal
V
Connector
*33 ft (10 m)
• *: Make the distance from the PCB to the connected unit within 33 ft (10 m).
• Relay spec: Max. DC 24 V, 10 mA to less than 500 mA.
On
Off
Operation
Stop
Indoor unit
Output signal
Optional part
Part name Model name Exterior
External connect kit UTY-XWZX
External output wire
- 19 -
WALL MOUNTED
ASU18, 24RLF
Page 24
9. Remote controller
9-1. Wireless remote controller
¢
Overview
o
p
j
k
l
n
m
b
d
e
a
f
i
g
h
c
Display panel
q
r
s
t
u
v
w
x
NOTE:
Functions may differ by type of the in­door unit. For details, refer to the oper­ation manual.
a
FAN button
Selects the fan speed (AUTO, HIGH, MED, LOW, and QUIET).
b START/STOP button
Starts and stops operation.
c SET button (vertical)
Adjusts the vertical airflow direction.
d SET button (horizontal)
Adjusts the horizontal airflow direction.
e SWING button
Sets the automatic swing operation and selects swing mode (Up/down, Left/right, Up/down/left/right, and Stop swing).
f RESET button
Used when replacing batteries.
g Timer set (- / +) button
Sets the current time and on-off time.
h TEST RUN button
Only used for the initial test in the unit installation.
i CLOCK ADJUST button
Used for adjusting the clock.
j TIMER MODE button
Selects the timer mode (off timer, on timer, program timer, and timer reset).
k SLEEP button
Pressed to select sleep timer.
l ECONOMY button m MIN. HEAT button
n
SET TEMP. (temperature) (
/ ) button
• Sets desired temperature.
• Sets remote controller custom code.
o MODE button
• Switches operation mode (AUTO, COOL, DRY, FAN, and HEAT).
• Starts/ends the remote controller custom code (max. 4 types) change.
p
Signal transmitter
q Signal transmit indicator r Fan speed indicator s Swing indicator t Timer mode indicator u Clock indicator v Sleep indicator w Operating mode indicator x Temperature indicator
- 20 -
WALL MOUNTED
ASU18, 24RLF
Page 25
¢
Specifications
Controller
Unit: in (mm)
Front view Side view Rear view
6-11/16 (170)
3/4 (19)
2-3/16 (56)
Top view
Size (H × W × D) in (mm) 6-11/16 × 2-3/16 × 3/4 (170 × 56 × 19) Weight oz (g) 3 (85) (without batteries)
NOTE: Actual number of buttons might be different from the figure above.
Holder
Unit: in (mm)
Front view Side view Bottom view
2-3/8 (60.4)
1-3/16 (30.2)
Ø1/8 (3.5)
1/8 x 1/4 (3.5 x 6.5)
(hole)
(hole)
1-1/16
1
3-3/4 (95)
6-1/16 (154.7)
(25.5)
(26.2)
Size (H × W × D) in (mm) 6-1/16 × 2-3/8 × 1-1/16 (154.7 × 60.4 × 26.2) Weight oz (g) 10 (28)
- 21 -
WALL MOUNTED
ASU18, 24RLF
Page 26
10. Function settings
To adjust the functions of this product according to the installation environment, various types of function settings are available.
NOTE:
Incorrect settings can cause a product malfunction.
10-1. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting pro­cedure and the content of each function setting, select appropriate functions for your installation environment.
NOTE: Incorrect settings can cause a product malfunction.
¢
Setting procedure by using wireless remote controller
The function number and the associated setting value are displayed on the LCD of the remote controller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
Before connecting the power supply of the indoor unit, reconfirm following items:
• Piping air tight test and vacuuming have been performed firmly.
• There is no wiring mistake.
Then, connect the power supply of indoor unit.
Entering function setting mode:
While pressing the FAN button and SET TEMP. ( ) button simultaneously, press the RESET button to enter the function setting mode.
STEP 1: Setting the remote controller custom code
Use the following steps to select the custom code of the remote controller. (Note that the air con­ditioner cannot receive a custom code if the air conditioner has not been set for the custom code.)
The custom codes that are set through this process are applicable only to the signal in the func­tion setting.
For details on how to set the custom codes through the normal process, refer to "Custom code
setting for wireless remote controller" on page 28.
1. Press the SET TEMP. (
) ( ) buttons to change the custom code between → → → . Match the code on the display to the air conditioner custom code. (Initially set to
.) If the custom code does not need to be selected, press the MODE button, and proceed to STEP 2.
2. Press the TIMER MODE button and check that the indoor unit can receive signals at the displayed custom code.
3. Press the MODE button to accept the custom code, and proceed to STEP 2.
4. After completing the function setting, be sure to disconnect the power supply and then reconnect it.
NOTES:
The air conditioner custom code is set to “ ” prior to shipment.
The remote controller resets to custom code “ ” when the batteries on the remote controller are replaced. If you use a custom code other than code “ ”, reset the custom code after re-
placing the batteries.
If you do not know the air conditioner custom code setting, try each of the custom codes ( →
→ → ) until you find the code that operates the air conditioner.
- 22 -
WALL MOUNTED
ASU18, 24RLF
Page 27
STEP 2: Selecting the function number and setting value
1. Press the SET TEMP. ( ) ( ) buttons to select the function number. To switch between the left and right digits, press the MODE button.
2. Press the FAN button to proceed the setting value. To return the function number selection, press the FAN button again.
3. Press the SET TEMP. ( ) ( ) buttons to select the setting value. To switch between the left and right digits, press the MODE but­ton.
4. Press the TIMER MODE button, and START/STOP button, in the order listed to confirm the settings.
5. Press the RESET button to cancel the function setting mode.
6. After completing the function setting, be sure to disconnect the power supply and then reconnect it.
Function number
Setting value
CAUTION
After disconnecting the power supply, wait 30 seconds or more before reconnecting it. The func­tion setting will not become active unless the power supply is disconnected and then reconnect­ed.
- 23 -
WALL MOUNTED
ASU18, 24RLF
Page 28
¢
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ­ment.
NOTE:
Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no. Functions
1) 11 Filter sign
2) 30/31 Room temperature control for indoor unit sensor
3) 40 Auto restart
4) 42 Room temperature sensor switching
5) 44 Remote controller custom code
6) 46 External input control
7) 48 Room temperature sensor switching (Aux.)
8) 92/93 Room temperature control for wired remote controller sensor
9) 94 Fixed operation mode switching
10) 95 Heat insulation condition (building insulation)
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the esti­mated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number Setting value Setting description Factory setting
11
00 Standard (400 hours) 01 Long interval (1,000 hours) 02 Short interval (200 hours) 03 No indication
- 24 -
WALL MOUNTED
ASU18, 24RLF
Page 29
2) Room temperature control for indoor unit sensor
NOTE: Before performing this setting, refer to Function 95.
Depending on the installed environment, correction of the room temperature sensor may be re­quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufac­turer’s recommended value).
*When Function 95-01 (High insulation) is set, the Standard setting "00" will be the same as "No correction 0.0 °F (0.0 °C)" (01).
Function number Setting value Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00 Standard setting* ♦ 01 No correction 0.0 °F (0.0 °C) 02 -1 °F (-0.5 °C)
More cooling Less heating
03 -2 °F (-1.0 °C) 04 -3 °F (-1.5 °C) 05 -4 °F (-2.0 °C) 06 -5 °F (-2.5 °C) 07 -6 °F (-3.0 °C) 08 -7 °F (-3.5 °C) 09 -8 °F (-4.0 °C) 10 +1 °F (+0.5 °C)
Less cooling
More heating
11 +2 °F (+1.0 °C) 12 +3 °F (+1.5 °C) 13 +4 °F (+2.0 °C) 14 +5 °F (+2.5 °C) 15 +6 °F (+3.0 °C) 16 +7 °F (+3.5 °C) 17 +8 °F (+4.0 °C)
3) Auto restart
Enables or disables automatic restart after a power interruption.
Function number Setting value Setting description Factory setting
40
00 Enable ♦ 01 Disable
NOTE:
Auto restart is an emergency function such as for power outage etc. Do not attempt to use this function in normal operation. Be sure to operate the unit by remote controller or external device.
4) Room temperature sensor switching
(Only for wired remote controller) When using the wired remote controller temperature sensor, change the setting to "Both" (01).
Function number Setting value Setting description Factory setting
42
00 Indoor unit ♦ 01 Both
00: Sensor on the indoor unit is active. 01: Sensors on both indoor unit and wired remote controller are active.
NOTE: Remote controller sensor must be turned on by using the remote controller.
- 25 -
WALL MOUNTED
ASU18, 24RLF
Page 30
5) Remote controller custom code
(Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code.
Function number Setting value Setting description Factory setting
44
00 A ♦ 01 B 02 C 03 D
6) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function number Setting value Setting description Factory setting
46
00 Operation/Stop mode ♦ 01 (Setting prohibited) 02 Forced stop mode
7) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01). When the setting value is set to "Both" (00), more suitable control of the room temperature is pos-
sible by setting function setting 30 and 31 too.
Function number Setting value Setting description Factory setting
48
00 Both ♦ 01 Wired remote controller
- 26 -
WALL MOUNTED
ASU18, 24RLF
Page 31
8) Room temperature control for wired remote controller sensor
NOTE: Before performing this setting, refer to Function 95.
Depending on the installed environment, correction of the room temperature sensor may be re­quired. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to "Both" (01). Ensure that the thermo sensor icon is displayed on the remote controller screen.
Function number Setting value Setting description
Factory
setting
92
(For cooling)
93
(For heating)
00 No correction 0.0 °F (0.0 °C) ♦ 01 No correction 0.0 °F (0.0 °C) 02 -1 °F (-0.5 °C)
More cooling Less heating
03 -2 °F (-1.0 °C) 04 -3 °F (-1.5 °C) 05 -4 °F (-2.0 °C) 06 -5 °F (-2.5 °C) 07 -6 °F (-3.0 °C) 08 -7 °F (-3.5 °C) 09 -8 °F (-4.0 °C) 10 +1 °F (+0.5 °C)
Less cooling
More heating
11 +2 °F (+1.0 °C) 12 +3 °F (+1.5 °C) 13 +4 °F (+2.0 °C) 14 +5 °F (+2.5 °C) 15 +6 °F (+3.0 °C) 16 +7 °F (+3.5 °C) 17 +8 °F (+4.0 °C)
9) Fixed operation mode switching
Sets the operation mode to heat pump, heating only, or cooling only.
Function number Setting value Setting description Factory setting
94
00 Heat pump ♦ 01 Heating only 02 Cooling only
10) Heat insulation condition (building insulation)
Heat insulation conditions differ according to the installed environment. "Standard insulation" (00) allows system to rapidly respond to the cooling or heating load
changes. "High insulation" (01) is when the heat insulation structure of the building is high and does not re-
quire system to rapidly respond to cooling or heating load changes. When "High insulation" (01) is selected:
• Overheating (overcooling) is prevented at the start-up.
• All room-temperature control settings (Function 30, 31, 92, and 93) will reset to "No correction
0.0 °F (0.0 °C)".
Function number Setting value Setting description Factory setting
95
00 Standard insulation ♦ 01 High insulation
NOTE:
When changing Function 95, perform this setting before other room-temperature control settings (Function 30, 31, 92, and 93). If Function 95 is not set first, room-temperature control settings (Function 30, 31, 92, and 93) will be reset and you must re-do them again.
- 27 -
WALL MOUNTED
ASU18, 24RLF
Page 32
¢
Custom code setting for wireless remote controller
To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required.
NOTE:
Air conditioner cannot receive a custom code if the air conditioner has not been set for the custom code.
1. Press the START/STOP button until only the clock is displayed on the remote controller dis­play.
2. Press the MODE button for at least 5 seconds to display the current custom code. (Initially set to
.)
3.
Press the SET TEMP. (
or ) button to change the custom code between → → → .
Match the code on the display to the air conditioner custom code.
4. Press the MODE button again to return to the clock indicator. The custom code will be changed.
NOTES:
• If no button is pressed within 30 seconds after the custom code is displayed, the system re­turns to the original clock indicator. In this case, start again from step 1.
• The air conditioner custom code is set to prior to shipment. To change the custom code, contact your retailer.
• The remote controller resets to custom code when the batteries in the remote controller are replaced. If you use a custom code other than code , reset the appropriate custom code af-
ter replacing the batteries. If you do not know the assigned code for the air conditioner, try each of the custom code ( → → → ) until you find the code which operates the air condi-
tioner.
- 28 -
WALL MOUNTED
ASU18, 24RLF
Page 33
11. Accessories
Part name Exterior Q’ty Part name Exterior Q’ty
Operating manual 1 Drain hose insulation 1
Installation manual 1 Cloth tape 1
Wall hook bracket 1
Tapping screw (large), M4 × 25 mm
8
Remote controller 1
Tapping screw (small), M3 × 12 mm
2
Battery 2 Air cleaning filter 2
Remote controller holder
1 Air cleaning filter frame 2
- 29 -
WALL MOUNTED
ASU18, 24RLF
Page 34
12. Optional parts
12-1. Controllers
Exterior Part name Model name Summary
Mode
Menu
Cool
Monitor
Set temp.
Fan
High
°
F
80
Mo
10:00
AM
Icon check:
Wired remote
controller
UTY-RVNUM
Large and full-dot liquid crystal screen, wide and large keys easy to press, user-intuitive arrow key. Wire type: Polar 3-wire
Wired remote
controller
UTY-RNNUM
Room temperature can be controlled by detecting the temperature accurately with built-in thermo sensor. Wire type: Polar 3-wire
Simple remote
controller
UTY-RSNUM
Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, temperature setting, and operation mode. Wire type: Polar 3-wire
NOTE:
Available functions may differ by the remote controller. For details, refer to the operation manual.
12-2. Others
Exterior Part name Model name Summary
External
connect kit
UTY-XWZX
Use to connect with various peripheral devices and air conditioner PCB.
- 30 -
WALL MOUNTED
ASU18, 24RLF
Page 35
Part 2. OUTDOOR UNIT
SINGLE TYPE: AOU18RLXFWH AOU24RLXFWH
Page 36
1. Specifications
Type Inverter heat pump
Model name AOU18RLXFWH AOU24RLXFWH
Power supply 208/230 V ~ 60 Hz Available voltage range 187—253 V Starting current A 8.0 10.5
Fan
Airflow rate
Cooling
CFM (m3/h)
1,489 (2,530) 2,001 (3,400)
Heating 1,489 (2,530) 2,119 (3,600) Type × Q'ty Propeller fan × 1 Motor output W 100
Sound pressure level *1
Cooling
dB (A)
47 54
Heating 50 55
Heat exchanger type
Dimensions
(H × W × D)
in 31-7/16 × 35-7/16 × 1-7/16
mm 798 × 900 × 36.4 Fin pitch FPI 20 Rows × Stages 2 × 38 Pipe type Copper
Fin type
Type (Material) Corrugate (Aluminum) Surface treatment Corrosion resistance (Blue fin)
Compressor
Type × Q'ty Hermetic motor compressor × 1 Motor output W 2,100
Refrigerant
Type R410A
Charge
lb oz 4 lb 10.1 oz
g 2,100
Refrigerant oil
Type POE (RB68) Amount
in3 (cm3)
48.8 (800)
Enclosure
Material Steel sheet
Color
Beige
Approximate color of MUNSELL 10YR7.5/1.0
Dimensions (H × W × D)
Net
in 32-11/16 × 35-7/16 × 13
mm 830 × 900 × 330
Gross
in 39-3/8 × 41-5/16 × 17-1/2
mm 1,000 × 1,050 × 445
Weight
Net
lb (kg)
135 (61)
Gross 152 (69)
Connection pipe
Size
Liquid
in (mm)
Ø 3/8 (Ø 9.52)
Gas Ø 5/8 (Ø 15.88)
Method Flare Pre-charge length
ft (m)
66 (20) Max. length 164 (50) Max. height difference 98 (30)
Operation range
Cooling
°F (°C)
-5 to 115 (-20 to 46)
Heating -15 to 75 (-26 to 24)
Drain hose
Material LDPE Size mm Ø 13.0 (I. D.), Ø 16.0 to Ø 16.7 (O. D.)
NOTES:
• Specifications are based on the following conditions: – Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) / 67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB). – Heating: Indoor temperature of 70 °FDB (21.11 °CDB) / 59 °FWB (15 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) / 43 °FWB (6.11 °CWB). – Pipe length: 24 ft 6 in (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level – Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 32 -
OUTDOOR UNIT
AOU18, 24RLXFWH
Page 37
2. Dimensions
2-1. Models: AOU18RLXFWH and AOU24RLXFWH
Unit: in (mm)
Top view
Front view
Side view
Bottom view
3(77)
35-3/8 (900)
32-3/4 (830)
17-3/8 (440)
7/8 (21)
15-3/4 (400)
13 (330)
7-3/4 (196)
5-3/4 (147)
6-3/4 (170)
14-5/8 (370)
25-5/8 (650)
Airflow
1-1/4 (31)
1/2 (12)
3-7/8
(99)
3/8
(9)
- 33 -
OUTDOOR UNIT
AOU18, 24RLXFWH
Page 38
3. Installation space
3-1. Models: AOU18RLXFWH and AOU24RLXFWH
¢
Space requirement
Provide sufficient installation space for product safety.
Single outdoor unit installation
When the upper space is open:
Unit: in (mm)
When there are obstacles at the rear only. When there are obstacles at the rear and
sides.
4 (100) or more
10 (250) or more
12 (300) or more
4 (100) or more
When there are obstacles at the front only. When there are obstacles at the front and
rear.
24 (600) or more
24 (600) or more
4 (100) or more
When there is an obstruction in the upper space:
Unit: in (mm)
When there are obstacles at the rear and above.
When there are obstacles at the rear, sides, and above.
12 (300) or more
Max. 19 (500)
24 (600) or more
40 (1,000) or more
4 (100) or more
10 (250) or more
20 (500) or more
Max. 19 (500)
- 34 -
OUTDOOR UNIT
AOU18, 24RLXFWH
Page 39
Multiple outdoor unit installation
When the upper space is open:
Unit: in (mm)
When there are obstacles at the rear only. When there are obstacles at the front only.
12 (300)
10 (250) or more
or more
60 (1,500) or more
10 (250) or more
When there are obstacles at the front and rear.
20 (500) or more
60 (1,500) or more
10 (250) or more
When there is an obstruction in the upper space:
Unit: in (mm)
When there are obstacles at the rear and above.
60 (1,500) or more
20 (500) or more
10 (250) or more
10 (250) or more
Max. 11 (300)
60 (1,500) or more
- 35 -
OUTDOOR UNIT
AOU18, 24RLXFWH
Page 40
Outdoor unit installation in multi-row
Unit: in (mm)
Single parallel unit arrangement Multiple parallel unit arrangement
6 (150) or more
24 (600) or more
40 (1,000) or more
79 (2,000) or more
20 (500) or more
24 (600) or more
60 (1,500) or more
10 (250) or more
119 (3,000) or more
10 (250) or more
60 (1,500) or more
20 (500) or more
10 (250) or more
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no obstacle.
• Height above the floor level should be 2 in (50 mm) or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better opera­tion efficiency.
CAUTION
• Do not install the outdoor unit in two-stage where the drain water could freeze. Otherwise the drainage from the upper unit may form ice and cause a malfunction of the lower unit.
• When the outdoor temperature is 32 °F (0 °C) or less, do not use the accessory drain pipe and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it might become difficult to get warm, and it is likely to cause product malfunction. Construct a canopy and a pedestal, or place the unit on a high stand that is locally installed.
- 36 -
OUTDOOR UNIT
AOU18, 24RLXFWH
Page 41
4. Refrigerant circuit
4-1. Models: AOU18RLXFWH and AOU24RLXFWH
3-way valve
(small)
3-way valve
(large)
Muffler
Pressure switch
4-way valve
Strainer
Expansion valve
Strainer
Heat exchanger
(INDOOR)
Heat exchanger
(OUTDOOR)
Sub-accumulator
Compressor
Cooling Heating
- 37 -
OUTDOOR UNIT
AOU18, 24RLXFWH
Page 42
5. Wiring diagrams
5-1. Model: AOU18RLXFWH
- 38 -
OUTDOOR UNIT
AOU18, 24RLXFWH
Page 43
5-2. Model: AOU24RLXFWH
- 39 -
OUTDOOR UNIT
AOU18, 24RLXFWH
Page 44
6. Capacity compensation rate for pipe length and height difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH
6-1. Models: AOU18RLXFWH and AOU24RLXFWH
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length
m
5 7.5 10 20 30 40 50
ft 16 24 32 65 98 131 164
Height difference H
Indoor unit is higher than
outdoor unit *1
30 98 - - - - 0.932 0.929 0.924 20 65 - - - 0.945 0.947 0.945 0.940 10 32 - - 0.984 0.961 0.963 0.960 0.956
7.5 24 - 0.988 0.988 0.965 0.967 0.964 0.959 5 16 0.992 0.992 0.992 0.968 0.971 0.968 0.963 0 0 0.998 1.000 1.000 0.976 0.979 0.976 0.971
Indoor unit is lower than outdoor
unit *2
-5 -16 0.998 1.000 1.000 0.976 0.979 0.976 0.971
-7.5 -24 - 1.000 1.000 0.976 0.979 0.976 0.971
-10 -32 - - 1.000 0.976 0.979 0.976 0.971
-20 -65 - - - 0.976 0.979 0.976 0.971
-30 -98 - - - - 0.979 0.976 0.971
HEATING
Pipe length
m
5 7.5 10 20 30 40 50
ft 16 24 32 65 98 131 164
Height difference H
Indoor unit is higher than
outdoor unit *1
30 98 - - - - 0.816 0.756 0.686 20 65 - - - 0.872 0.816 0.756 0.686 10 32 - - 0.991 0.872 0.816 0.756 0.686
7.5 24 - 1.000 0.991 0.872 0.816 0.756 0.686 5 16 0.986 1.000 0.991 0.872 0.816 0.756 0.686 0 0 0.986 1.000 0.991 0.872 0.816 0.756 0.686
Indoor unit is lower than outdoor
unit *2
-5 -16 0.981 0.995 0.986 0.868 0.812 0.752 0.683
-7.5 -24 - 0.993 0.983 0.866 0.810 0.750 0.681
-10 -32 - - 0.981 0.864 0.808 0.748 0.679
-20 -65 - - - 0.855 0.799 0.740 0.672
-30 -98 - - - - 0.791 0.733 0.665
- 40 -
OUTDOOR UNIT
AOU18, 24RLXFWH
Page 45
7. Additional charge calculation
7-1. Models: AOU18RLXFWH and AOU24RLXFWH
Refrigerant type R410A
Refrigerant amount
lb oz 4 lb 10.1 oz
g 2,100
¢ Refrigerant charge
Total pipe length
ft 66 or less 98 131 164 (Max.)
0.43 oz/ft (40 g/m)
m 20 or less 30 40 50 (Max.)
Additional charge
oz 0 14.1 28.2 42.3
g 0 400 800 1,200
- 41 -
OUTDOOR UNIT
AOU18, 24RLXFWH
Page 46
8. Airflow
8-1. Model: AOU18RLXFWH
Cooling
m3/h
2,530
l/s 703
CFM 1,489
Heating
m3/h
2,530
l/s 703
CFM 1,489
8-2. Model: AOU24RLXFWH
Cooling
m3/h
3,400
l/s 944
CFM 2,001
Heating
m3/h
3,600
l/s 1,000
CFM 2,119
- 42 -
OUTDOOR UNIT
AOU18, 24RLXFWH
Page 47
9. Operation noise (sound pressure)
9-1. Noise level curve
¢
Model: AOU18RLXFWH
Cooling
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
¢
Model: AOU24RLXFWH
Cooling
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
- 43 -
OUTDOOR UNIT
AOU18, 24RLXFWH
Page 48
9-2. Sound level check point
39-3/8 in (1 m)
MicrophoneMicrophone
Rear
A
irflow
Rear view
Side view
NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrat-
ed above.
- 44 -
OUTDOOR UNIT
AOU18, 24RLXFWH
Page 49
10. Electrical characteristics
Model name AOU18RLXFWH AOU24RLXFWH
Power supply
Voltage V 208/230~
Frequency Hz 60 MCA *1 A 17.0 18.0 Starting current A 7.8 8.6
Wiring spec. *2
MAX. CKT. BKR *3 A 20
Power cable AWG 12
Connection cable *4 AWG 14
Limited wiring length ft (m) 167 (51)
*1: Minimum Circuit Ampacity (Calculation based on UL1995) *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
As the regulations of wire size and circuit breaker differ in each country or region, select appropri­ate devices complied to the regional standard.
*3: Maximum Circuit Breaker *4: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor
size.
- 45 -
OUTDOOR UNIT
AOU18, 24RLXFWH
Page 50
11. Safety devices
Type of
protection
Protection form
Model
AOU18RLXFWH AOU24RLXFWH
Circuit protection
Current fuse (Filter PCB) 250 V, 5 A × 2
Current fuse (Main PCB)
250 V, 3.15 A
250 V, 5 A
Current fuse (Out of PCB) 250 V, 5 A
Fan motor protection
Thermal protection
Activate
302±27 °F (150±15 °C)
Fan motor stop
Reset
248±27 °F (120±15 °C)
Fan motor restart
Compressor protection
Terminal protection program (Compressor temp.)
Activate
226 °F (108 °C)
Compressor stop
Reset
176 °F (80 °C)
Compressor restart
Thermal protection program (Discharge temp.)
(COOL or DRY mode)
Activate
230 °F (110 °C)
Compressor stop
Reset
After 7 minutes
Compressor restart
High pressure protection
Pressure switch
Activate
4.2±0.1 MPa
Compressor stop
Reset
3.2±0.15 MPa
Compressor restart
- 46 -
OUTDOOR UNIT
AOU18, 24RLXFWH
Page 51
12. Accessories
Part name Exterior Q’ty Part name Exterior Q’ty
Installation manual 1
Adapter,
12.7 (1/2)→15.88 (5/8) [mm (in)] (Only for 18 model)
1
Drain pipe 1
Adapter,
6.35 (1/4)→9.52 (3/8) [mm (in)]
1
Drain cap 5
- 47 -
OUTDOOR UNIT
AOU18, 24RLXFWH
Loading...