1-2-4 ASSEMBLY PROCESS of INVERTER UNIT......................................................
2 REPLACEMENT PARTS ( For INDOOR UNIT )...........................................................
2-1 PARTS LAYOUT DRAWING...................................................................................
03-01
03-01
03-01
03-03
03-04
03-09
03-15
03-15
03-17
03-19
03-25
03-30
03-30
CASSETTE type
INVERTER
R410A
1 .DESCRIPTION OF EACH
CONTROL OPERATION
1. COOLING OPERATION
1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 3.6 degF(2 degC) higher than a set temperature,
the compressor operation frequency will attain to maximum performance.
* If the room temperature is 3.6 degF(2 degC) lower than a set temperature, the compressor
will be stopped.
* When the room temperature is between +3.6 degF(+2 degC) to -3.6 degF(-2 degC) of
the setting temperature, the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Figure 1 based on the
fan speed mode and the outdoor temperature.
( Table 1 : Compressor Frequency Range )
minimum
frequency
AUU18RCLX20Hz
AUU24RCLX
AUU36RCLX
AUU42RCLX
20Hz
20Hz
25Hz
maximum
frequency
63Hz
80Hz
90Hz
92Hz
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
Outdoor air
temperature
87.8°F
(31°C)
66.2°F
(19°C)
51.8°F
(11°C)
A zone
B zone
C zone
D zone
AUU18RCLX
AUU24RCLX
AUU36RCLX
AUU42RCLX
Fan speed mode
A zone63Hz
Bzone
C zone
D zone
Azone
Bzone
Czone
D zone
Azone
Bzone
C zone
D zone
Azone
Bzone
C zone
D zone
A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower 5.4 degF(3 degC) than a set temperature,
the compressor operation frequency will attain to maximum performance.
* If the room temperature is higher 3.6 degF(2 degC) than a set temperature, the compressor
will be stopped.
* When the room temperature is between +3.6 degF(+2 degC) to -5.4 degF(-3 degC) of
the setting temperature, the compressor frequency is controlled within the range shown in Table2.
However, the maximum frequency is limited in the range shown in Figure 2 based on
the outdoor temperature.
( Table 2 : Compressor Frequency Range )
minimum
frequency
AUU18RCLX20Hz
AUU24RCLX
AUU36RCLX
AUU42RCLX
20Hz
20Hz
23Hz
maximum
frequency
87Hz
87Hz
95Hz
92Hz
( Fig.2 : Limit of Maximum Frequency based on Outdoor Temperature )
Outdoor air
temperature
68°F
(20°C)
60.8°F
(16°C)
53.6°F
(12°C)
41°F
(5°C)
E zone
D zone
C zone
B zone
A zone
AUU18RCLX
AUU24RCLX
AUU36RCLX
AUU42RCLX
A zone87Hz
Bzone
C zone
Dzone
E zone
Azone
Bzone
Czone
Dzone
Ezone
Azone
Bzone
Czone
D zone
Ezone
Azone
B zone
C zone
D zone
Ezone
The compressor rotation frequency shall change according to set temperature and room
temperature variation which the room temperature sensor of the indoor unit has detected
as shown in the Table 3.
( Table 3 : Compressor frequency )
Operating frequency
AUU18RCLX25Hz
AUU24RCLX
AUU36RCLX
AUU42RCLX
( Fig.3 : Compressor Control based on Room Temperature )
Room
temperature
Compressor ON
Ts+1.8 degF
(1 degC)
Compressor OFF
30Hz
45Hz
30Hz
Room
temperature
Ts+2.7 degF
(1.5 degC)
Ts : Setting temperature
( Fig.4 : Indoor Fan Control )
Compressor
ON
OFF
Indoor fan
air flow mode
ON
OFF
Air flow mode : Lo
305301205(sec)
180180
01-03
4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum
mode from among the HEATING, COOLING and MONITORING modes. During operation, the
optimum mode is automatically swiched in accordance with temperature changes. The temperature
can be set between 64°F(18°C) and 88°F(30°C) in 2 degF(1 degC) steps.
When operation starts, only the indoor fan is operated for 1 minute. (Air flow mode: S- Lo)
1
After 1 minute, depends on the room temperature and outdoor unit's operarion mode,
the operation mode is selected in accordance with the table below.
( Table 4 : Operation mode selection table )
Room temperature :TR
TR>Ts+3.6degF
=
(2 degC)
Ts +3.6 degF > TR > Ts-3.6 degF
(2 degC)(2 degC)
Ts +3.6 degF>TR
(2 degC)
Ts : Setting temperature
2
When COOLING was selected at, the same operation as COOLING OPERATION is performed.
3
When HEATING was selected at, the same operation as HEATING OPERATION is performed.
4
When the compressor was stopped for 6 consecutive minutes by the temperature control function
after the COOLING or HEATING operation mode was selected atabove, operation is switched
to MONITORING and the operation mode is selected again.
=
Operation mode
Cooling
Monitoring
Heating
1
1
1
01-04
5. INDOOR FAN CONTROL
1. Fan speed
( Table 5 : Indoor Fan Speed )
AUU18RCLX
Operation modeAir flow modeSpeed (rpm)
Heating
Cooling
Hi400
Me
Lo
S-Lo
Hi450
Me
Lo
S-Lo
350
310
250
390
330
250
AUU36RCLX
Operation modeAir flow modeSpeed (rpm)
Heating
Cooling
Hi580
Me
Lo
S-Lo
Hi580
Me
Lo
S-Lo
510
440
300
510
440
300
AUU24RCLX
Operation modeAir flow modeSpeed (rpm)
Heating
Cooling
Hi440
Me
Lo
S-Lo
Hi490
Me
Lo
S-Lo
380
330
250
430
360
250
AUU42RCLX
Operation modeAir flow modeSpeed (rpm)
Heating
Cooling
Hi620
Me
Lo
S-Lo
Hi620
Me
Lo
S-Lo
550
470
300
550
470
300
2. FAN OPERATION
The airflow can be switched in 4 steps such as AUTO, LOW, MED, HIGH, while the indoor
fan only runs.
When [AUTO] is selected, the indoor fan motor runs LO and OFF at 1 minute intervals.
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
asshowninFigure5.
On the other hand, if switched in [HIGH][LOW], the indoor motor will run at a constant airflow of [COOL]
operation modes LOW, MED, HIGH,as shown in Table 5.
( Fig.5 : Airflow change - over ( Cooling : AUTO ) )
*1
When the room
temperature rises
TR : Room temperature
Ts : Setting temperature
TR-Ts > 3.6 degF
=
(2 degC)
3.6 degF > TR-Ts > 1.8 degF
(2 degC)(1 degC)
=
1.8 degF > TR-Ts
(1 degC)
HIGH mode
MED mode
LOW mode
When the room
temperature drops
TR-Ts > 5.4 degF
=
(3 degC)
5.4 degF > TR-Ts > 3.6 degF
(3 degC)(2 degC)
3.6 degF > TR-Ts
(2 degC)
*1 : Contains a condition to the following
When the operation mode is set to AUTO mode
at the start of operation.
When the setting temperature was changed.
When the operation mode was changed to COOLING mode.
When the airflow mode was changed to AUTO mode.
=
01-05
4. HEATING OPERATION
When the airflow is set to [AUTO], the indoor fan
motor operates [MED] mode.
Then the indoor fan motor will run according
to a room temperature, as shown in Figure 6.
On the other hand, if switched in [HIGH][LOW],
the indoor motor will run at a constant airflow
of [COOL] operation modes LOW, MED, HIGH,
as shown in Table 5.
( Fig.6 : Airflow change - over ( Heating : AUTO ) )
Indoor heat exchanger
temperature
116.6°F
Go up one-step
(47°C)
Hold
105.8°F
(41°C)
Go down one-step
5. COOL AIR PREVENTION CONTROL (Heating mode)
The maximum value of the indoor fan speed is set as shown in Figure 7, based on the detected
temperature by the indoor heat exchanger sensor on heating mode.
( Fig.7 : Cool Air Prevention Control )
Indoor heat exchanger
temperature
SETTING
91.4°F
(33°C)
FAN MODE
LO mode
86°F
(30°C)
S-LOW mode
Indoor heat exchanger
temperature
86°F
(30°C)
6. DRY OPERATION
Refer to the Figure 4.
During the dry mode operation, the fan speed setting can not be changed.
01-06
6. OUTDOOR FAN CONTROL
1. Outdoor Fan Motor
Following table shows the fan speed of the outdoor unit.
( Table 6 : Fan speed of the outdoor unit )
CoolingHeating
AUU18RCLX
AUU24RCLX
AUU36RCLX
AUU42RCLX
AUU42RCLX has two fan motors.
*
The outdoor fan speed changs in the range mentioned avobe depending on the compressor
*
frequency and outdoor temperature.
(When the compressor frequency and outdoor temperature increase, the outdoor fan speed
also changes to the higher speed.
When the compressor frequency and outdoor temperature decrease, the outdoor fan
speed also changes to the lower speed.)
For AUU18RCLX
*
It runs at 250rpm for 20 seconds after starting up the outdoor fan.
When the outdoor heat exchanger tenperature is lower than 35.6°F (2°C),
the fan speed switches to 780rpm on heating mode.
For AUU24RCLX / AUU36RCLX
*
It runs at 250rpm for 20 seconds after starting up the outdoor fan.
When the outdoor heat exchanger tenperature is lower than 35.6°F (2°C),
the fan speed switches to 900rpm on heating mode.
For AUU42RCLX
*
It runs at 500rpm for 20 seconds after starting up the outdoor fan.
When the outdoor heat exchanger tenperature is lower than 35.6°F (2°C),
the fan speed switches to 900rpm(Upper fan) and 850rpm(Lower fan) on heating mode.
Each time the button is pressed, the air direction range will change as follows:
(Operation Range)
Cooling / Dry mode
Heating mode
Fan mode
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation
selected.
Cooling / Dry / Fan mode
Heating modeDownward flow
For AUU18/ 24RCLX
At the start of operation if the setting louver position is,the setting position is set to
after the louver moves from totally-enclosed position to. (Positioning Control)
Horizontal flow
(Fig.8 : Air Direction Range)
1
2
3
4
For AUU36/ 42RCLX
At the start of operation if the setting louver position isor,the setting position is set toor
after the louver moves from totally-enclosed position to. (Positioning Control)
The indoor fan motor starts after the louver reaches to the setting position.
2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing.
The range of swing depends on the set airflow direction.
(Swinging Range)
Airflow direction setRange of swing
to
to
to
to
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted
and the louver stops at the memorized position.
( Stop mode means Operation stop.)
01-08
8. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in Table 7.
(Table 7 : Compressor Operation Frequency Range)
AUU18RCLX
AUU24RCLX
AUU36RCLX
AUU42RCLX
CoolingHeating
MinMaxMinMax
20Hz
20Hz
20Hz
25Hz
63Hz
80Hz
90Hz
92Hz
20Hz
20Hz
20Hz
23Hz
87Hz
87Hz
95Hz
92Hz
Dry
25Hz
30Hz
45Hz
30Hz
2. OPERATION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in Figure 9.
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
2. WEEKLY TIMER
2-1. WEEKLY TIMER
Use this timer function to set operating time for each day of the week.
The weekly timer allows up to two ON and OFF time to set up per day.
Operation mode
Stop mode
Set time
The operating time can be set in 30 min increments only.
The OFF time can be carried over to next day.
The ON timer and the OFF timer functions cannot be set with using the weekly timer.
Both ON and OFF time must be set.
Operation mode
Stop mode
Set timeSet timeSet time
Operation mode
Stop mode
01-10
2-2. DAY OFF setting
The DAY OFF setting is only available for days for which weekly settings already exist.
If the operating time carries over to the next day (during a next day setting), the effective
DAY OFF range will be set as shown below.
Normal
DAY OFF
Operation mode
Operation mode
Stop mode
Stop mode
Preceding dayNext day
Setting day
Stop mode
Next day setting
DAY OFF
Stop mode
Operation mode
Stop mode
Preceding dayNext daySetting day
Operation mode
Stop mode
The DAY OFF setting can only be set one time. The DAY OFF setting is cancelled automatically
after the set day has passed.
3. TEMPERATURE SET BACK TIMER
The SET BACK timer only changes the set temperature for 7 days, it cannot be used to start or stop
air conditioner operation.
The SET BACK timer can be set to operate up to two times per day but only one temperature setting
can be used.
During the COOL/DRY mode, the air conditioner will operate at a minimum of 64°F(18°C) even if
the SET BACK temperature is set to 62°F(17°C) or lower.
Case of SET BACK timer on the Cooling operation.
( Setting temperature :72°F(22°C), SET BACK temperature :80°F(26°C))
SET BACK setting
Operation
temperature
*1
Operation
temperature
*1: During the SET BACK function,
the setting temperature is changed.
80°F(26°C)
72°F(22°C)
80°F(26°C)
76°F(24°C)
72°F(22°C)
ONOFFOFFON
Chenge the setting temperature:
72°F(22°C)76°F(24°C)
01-11
10. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the
present operating condition based on the following values.
The compressor frequency, the temperatures detected by the discharge temperature sensor
and the outdoor temperature sensor.
The pulse range of the electronic expansion valve control is between 50 to 480 pulses.
At the time of supplying the power to the outdoor unit, the initialization of the electronic
expansion valve is operated (1000 pulses are input to the closing direction).
11. TEST OPERATION CONTROL
With Wired Remote Controller
Under the condition where the air conditioner stops, press the MASTER CONTROL button and
the FAN CONTROL button simultaneously for 5 seconds or more, and the test operation control
mode will appear.
During test running, "" will display on the remote controller display.
Set the test operation mode, and the compressor will continue to run regardless of whatever
the room temperature sensor detects.
The test operation mode is released if 60 minutes have passed after setting up the test operation.
12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
The compressor won't enter operation status for 3 minutes after the compressor is stopped,
even if any operation is given.
13. 4-WAY VALVE EXTENSION SELECT
At the time when the air conditioner is switched from the cooling mode to heating mode,
the compressor is stopped, and the 4-way valve is switched in 3 minutes later
after the compressor stopped.
14. AUTO RESTART
When the power was interrupted by a power failure, etc. during operation, the operation contents
at that time are memorized and when power is recovered, operation is automatically resumed with
the memorized operation contents.
When the power is interrupted and recovered during timer operation, timer operation is canceled,
but only setting time is memorized.
[Operation contents memorized when the power is interrupted]
Operation mode
Set temperature
Set air flow
Timer mode and timer time
Air flow Direction
Swing
Thermistor detected position
01-12
15. PUMP DOWN ( Refrigerant collecting operation )
Perform the following procedures to collect the refrigerant when moving the indoor unit or the outdoor unit.
When the product is stopped:
1. Press the PUMP DOWN switch (SW2) on the outdoor unit.
(The LED on the outdoor unit circuit board flickers every 1second.)
2. The pump down operation (cooling operation) begins right away.
After operation starts, close the 3-way valve (liquid).
3. After 2-3minutes, operation stops. Close the 3-way valve (gas) within 1minute after operations stops.
4. The LED will go out 3minutes after it stops. Disconnect the power supply after confirming that the LED has gone out.
When the product is operating:
1. Press the PUMP DOWN switch (SW2) on the outdoor unit. The LED on the outdoor unit circuit board flickers
every 1second, and operation stops.
At this point, recovery has not been completed, so do not close the 2 and 3-way valves.
2. The pump down operation (cooling operation) begins after 3minutes.
Close the 3-way valve (liquid) after operation starts.
3. After 2-3minutes, operation stops. Close the 3-way valve (gas) within 1minute after operations stops.
4. The LED will go out 3minutes after it stops. Disconnect the power supply after confirming that the LED has gone out.
16. COMPRESSOR PREHEATING
When the outdoor heat exchanger temperature is lower than Operation temperature (Refer to Table 8) and the heating
operation has
(By heating the compressor, warm air is quickly discharged when operation is started.)
When operation was started, and when the outdoor temperature rises to Release temperature or greater,
preheating
Defrost Indicator:
[Operation lamp]
9 sec ON / 1 sec OFF
3 sec later Compressor OFF
3 sec later Outdoor fan motor OFF
28 sec later 4-way valve OFF
34 sec later compressor ON
Outdoor heat exchanger temperature: Over 53.6°F(12°C)
Compressor ON time: Over 15 minutes
(Frequency : 92 Hz)
or
Defrost Indicator:
[Operation lamp]
9 sec ON / 1 sec OFF
Compressor : 30 Hz
Outdoor fan motor OFF
4-way valve OFF
Compressor ON
(Frequency : 92 Hz)
Defrost end
01-14
18. DRAIN PUMP OPERATION
During Cooling / Dry operation
1. When the compressor starts, the drain pump starts simultaneously.
2. The drain pump operates continuously for 3 minutes after the compressor is turned off.
3. When the compressor stops by the "Indoor heat exchanger de-icing function", the drain pump is turned off in 1 hour
after the compressor stops.
4.When the water level in the drain pan rises up and then the float switch functions:
The compressor, indoor and outdoor fan motor operation are stopped.
1
2
Drain pump operates continuously for 3 minutes after the float switch is turned off.
(Almost condensing water may be drained)
5. When the float switch turns ON continuously for 3 min., "FAILURE INDICATION" operates.
6. When the float switch turns OFF within 3 min., the unit starts cooling operation.
During Heating / Fan / Stop operation
1.When the water level in the drain pan rises up and then the float switch functions:
Drain pump operates continuously for 3 minutes after the float switch is turned off.
1
(Almost condensing water may be drained)
2. When the float switch turns ON continuously for 3 min., "FAILURE INDICATION" operates.
19. ENERGY SAVE FUNCTION
1. During Cooling / Dry operation:
The thermostat temperature setting increases by 1.8 degF (1 degC) as soon as the ENERGY SAVE button is pressed,
and then increases by 1.8 degF (1 degC) after 1 hour later.
Afterwards, energy consumption is saved by continuing to cool or dry at a thermostat temperature of 3.6 degF (2 degC)
higher than setting temperature.
ENERGY
SAVE ON
1hour.
1.8 degF
(1 degC)
3.6 degF(2degC)
Setting
temperature
2. During Heating operation:
The thermostat temperature setting decreases by 1.8 degF (1 degC) as soon as the ENERGY SAVE button is pressed,
and then decreases by another 1.8 degF (1 degC) every 30 minutes.
Afterwards, energy consumption is saved by continuing to heat at a thermostat temperature of 7.2 degF (4 degC)
lower than setting temperature.
ENERGY
SAVE ON
1.8degF
(1degC)
30min.
1 hour.
1 hour
30 min.
3.6degF
(2degC)
5.4degF
(3degC)
7.2degF
(4degC)
Setting
temperature
01-15
20. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVER RISE PREVENTION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas
temperature.
When the discharge temperature becomes higher than Temperature ,the compressor frequency
is decreased 10 Hz, and it continues to decrease the frequency for 10 Hz every 120 seconds until
the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature ,the control of the compressor
frequency is released.
When the discharge temperature becomes higher than Temperature,the compressor stops.
When the discharge temperature becomes lower than Temperature,the compressor operates.
(Table 11 : Discharge Temperature Over Rise Prevention Control / Release Temperature)
TemperatureTemperatureTemperatureTemperature
AUU18RCLX
AUU24RCLX
AUU36RCLX
AUU42RCLX
221°F (105°C)212°F (100°C)239°F(115°C)176°F(80°C)
2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit value that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
(Table 12 : Current Release Operation Value / Release Value)
The compressor frequency decreases on cooling mode when the indoor heat exchanger
temperature sensor detects the temperature lower than 37.4°F(3°C).
Then, the anti-freezing control is released when it becomes higher than 42.8°F(6°C).
Compressor OFF : Hold
Compressor ON : Release of protection
Release of protection
When the compressor frequency becomes lower than minimum frequency,
the compressor operates at minimum frequency.
If the indoor heat exchanger temperature sensor detects the temperature lower than
37.4°F(3°C) after 2minutes upon operating the compressor at minimum frequency,
the compressor stops.
4. COOLING PRESSURE OVER RISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to
158.9°F (70.5°C) or greater,
the compressor is stopped and error display is indicated.
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the
detection value of the indoor heat exchanger temperature sensor.
(Fig 11 : Heating Overload Protection Control)
Indoor heat exchange
temperature
Compressor is OFF
145.4°F
(63°C)
129.2°F
(54°C)
122°F
(50°C)
The compressor frequency is
decreased 10Hz every 60seconds.
Hold
Compressor OFF :
Release of protection
Compressor ON :
The compressor frequency is
increased 10Hz every 60seconds.
01-19
CASSETTE type
INVERTER
R410A
2 .TROUBLE SHOOTING
2. TROUBLESHOOTING
2-1 ERROR DISPLAY
2-1-1 WIRED REMOTE CONTROLLER DISPLAY
1. SELF - DIAGNOSIS
When the error indication "E:EE" is displayed, inspection of the air conditioning system is necessary.
Please consult authoilzed servise personnel.
Run [Self-Diagnosis] if [E:EE] flashes on the clock display of the remote controller.
Display
SUMOTUWETH FR
SA
SUMOTUWETH FR
Ex. Self-diagnosis
CLOCK ADJUST
SET BACK
DELETESET
DAY
DAY OFF
ENERGY
SAVE
CLOCK ADJUST
SET BACK
DAYOFF
DELETESET
DAY
SET
ENERGY
SAVE
THERMO
SENSOR
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttonsandsimultaneously for 5 seconds or more
to start the self-diagnosis.
3. Press the SET TEMPERATURE buttonsandsimultaneously for 5 seconds or more
or there is no key input for 20 seconds to stop the self-diagnosis.
Error code
Error contents
Communication error (indoor unitremote control)
Communication error (Serial reverse transfer error)
Room temperature sensor open
Room temperature sensor short-circuited
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor short-circuited
Outdoor heat exchanger temperature sensor error
Water drain abnormal
Outdoor temperature sensor error
Outdoor discharge pipe temperature sensor error
Indoor EEPROM abnormal (Model No.)
Indoor fan motor abnormal
Outdoor communication signal error (Forward transfer signal error)
Up to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons,and the START/STOP buttonsimultaneously
for 5 seconds or more to start the self-diagnosis.
DAY
SUMOTUWETH FR
SA
3. Press the START/STOP button.
Error code
Error history number
DAY
SUMOTUWETH FR
SA
4. Press the SET TEMPERATURE button to select the error history number.
Lower
DAY
Raise
01234 567
FEdcbA98
ı
ı
5. Press the SET TEMPERATURE buttons,and START/STOP buttonsimultaneously
for 5 seconds or more or there is no key input for 20 seconds to stop the display.
02-02
2-1-2 OUTDOOR UNIT DISPLAY
1. ERROR DISPLAY
Error contents
Outdoor communication signal error
(Forward transfer signal error)
Outdoor discharge pipe temperature sensor error
Outdoor heat exchanger temperature sensor error
Outdoor temperature sensor error
Compressor temperature sensor error
Heat sink temperature sensor error
Pressure switch abnormal
IPM error
Compressor rotor location cannot detect
Compressor Start-up error
Outdoor unit fan motor error (upper fan)
Outdoor unit fan motor error (lower fan)
LED Flashing
Pattern
1timeflash
2 times blink
3 times blink
4 times blink
7 times blink
8 times blink
9 times blink
12 times blink
13 times blink
14 times blink
15 times blink
16 times blink
2. ERROR DISPLAY METHOD
Outdoor LED Blink (1 to 16 times) 0.5sec ON / 0.5sec OFF blinking
0.5sec0.5sec2sec
ON
Display
priority
1
2
3
4
5
6
7
8
9
10
11
12
Trouble
shooting
11
8
5
7
12
19
13
14
17
20
18
OFF
3. NORMAL OPERATION DISPLAY
OperationLED Blinking Pattern
Normal operationContinuously lighting
Protected operation
Pump down operation
5sec ON / 1sec OFF
1sec ON / 1sec OFF
02-03
2-2 TROUBLE SHOOTING WITH ERROR CODE
Trouble shooting 1
INDOOR UNIT Error Method:
Communication Error
(Indoor unitRemote control)
Detective Actuators:
Indoor unit controller PCB circuit
Wired Remote Control
Indicate or Display:
Indoor Unit: No LED
Outdoor Unit : No indication
ERROR CODE : E : 00
Detective details:
When the indoor unit cannot receive the signal from Wired Remote
more than 10seconds after power ON, or the indoor unit cannot receive
the signal more than 1minute during normal operation.
After turning off the power, check & correct the followings.
Check the connection of terminal between remote control and Indoor unit,
and check if there is a disconnection of the cable.
OKOK
Check Point 2 : Check Remote Control and Controller PCB
Check Voltage at CN17 of Controller PCB. (Power supply to Remote Control)
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal)>> Replace Remote Control
>> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
Upon correcting the removed connector or mis-wiring, reset the power.
02-04
Trouble shooting 2
OUTDOOR UNIT Error Method:
Communication Error
(Serial Reverse Transfer Error)
Indicate or Display:Indicate or Display:
Indoor Unit: No LED
Outdoor Unit : No indication
ERROR CODE : E : 01
Detective Actuators:
Detective details:
Outdoor Unit Main PCB Circuit
Active Filter Module
Forecast of Cause:
1. Connection failure 2. External cause 3. Main PCB failure 4. Active Filter Module failure
Check Point 1-1 : Reset the power and operate
Does Error indication show again?
YESYES
Check Point 2 : Check Connection
Check any loose or removed connection line of
Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check connection between Outdoor Unit Main PCB
and Filter PCB.
(If there is loose connector or open cable)
When the indoor unit cannot receive the serial signal from Outdoor unit
more than 10seconds.
NO
Check Point 1-2:
Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
OK
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC208 - 230V appears at Outdoor Unit Terminal L - N.
OK
Check Point 4 : Check Serial Signal (Reverse Transfer Signal)
Check Serial Signal (Reverse Transfer Signal)
>> Check if Indicated value swings between AC70V and AC130V at Outdoor Unit Terminal 1 - 3.
>> If it is abnormal, Check Active Filter Module. (PARTS INFORMATION 3)
>>If Active Filter Module is abnormal, replace it.
>>If Active Filter Module is normal, replace Main PCB.
WHITE
BLACK
RED
WHITE
BLACK
N
L
3
2
1
+
-
02-05
Trouble shooting 3
INDOOR UNIT Error Method:
INDOOR UNIT
Room Temperature Sensor Error
Indicate or Display:
Indoor Unit: No LED
Outdoor Unit : No indication
ERROR CODE : E : 02 / 03
Detective Actuators:
Indoor Unit Controller PCB Circuit
Room Temperature Thermistor
Detective details:
When Room Temperature Thermistor open or short-circuit is
detected at power ON.
Check operation of float switch. (any blocking by dust, etc.)
Remove Float switch and check ON/OFF switching operation
by using a meter.
>>If Float switch is detective, replace it.
OKOK
Check Point 2 :Check Point 2 : Check Connector (CN15) / Wire
Check loose contact of CN15 /shorted wire (pinched wire).
>>Replace Float switch if the wire is abnormal
ONONOFFOFF
OKOK
Check Point 3 : Replace Controller PCB
If Check Point 1&2donotimprovethesymptom, change Controller PCB.
02-09
Trouble shooting 7
OUTDOOR UNIT Error Method:
INDOOR UNIT
Outdoor Temperature Sensor Error
Indicate or Display:
Indoor Unit: No LED
Outdoor Unit : LED 4 times blink
ERROR CODE : E : 0A
Detective Actuators:
Outdoor Unit Main PCB Circuit
Outdoor Temperature Thermistor
Detective details:
When Outdoor Temperature Thermistor open or short-circuit is
detected at power ON or while running the compressor.
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
Temperature
-4°F
(-20°C)
86°F
(30°C)
14°F
(-10°C)
104°F
(40°C)
23°F
(-5°C)
122°F
(50°C)
32°F
(0°C)
140°F
(60°C)
41°F
(5°C)
158°F
(70°C)
50°F
(10°C)
59°F
(15°C)
16.1
68°F
(20°C)
12.620.726.935.246.662.3115Resistance Value (k )
5.187.97
If Thermistor is either open or shorted, replace it and reset the power.
3.452.361.65Resistance Value (k )
OKOK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
THERMISTOR
THERMISTOR
(DISCHARGE)
1212121212
(PIPE)
BROWN
THERMISTOR
(OUTDOOR)
BLACK
THERMISTOR
(COMPRESSOR)
BLUE
THERMISTOR
(HEAT SINK)
BROWN
BLACK
CN21CN22CN23CN26CN25
If the voltage does not appear, replace Main PCB.
02-10
Trouble shooting 8
OUTDOOR UNIT Error Method:
INDOOR UNIT
Outdoor Discharge Pipe Temperature
Sensor Error
Indicate or Display:
Indoor Unit: No LED
Outdoor Unit : LED 2 times blink
ERROR CODE : E : 0C
Detective Actuators:
Outdoor Unit Main PCB Circuit
Discharge Pipe Temperature Thermistor
Detective details:
When Discharge Pipe Temperature Thermistor open or short-circuit
is detected at power ON or while running the compressor.
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
32°F
(0°C)
41°F
(5°C)
50°F
(10°C)
59°F
(15°C)
68°F
(20°C)
86°F
(30°C)
41.164.581.8105135176Resistance Value (k )
Temperature
158°F
(70°C)
176°F
(80°C)
194°F
(90°C)
212°F
(100°C)
248°F
(120°C)
284°F
(140°C)
104°F
(40°C)
320°F
(160°C)
122°F
(50°C)
18.126.9
356°F
(180°C)
140°F
(60°C)
12.5
1.211.983.434.616.318.78Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
0.77
0.51
OKOK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
THERMISTOR
THERMISTOR
(DISCHARGE)
1212121212
(PIPE)
BROWN
THERMISTOR
(OUTDOOR)
BLACK
THERMISTOR
(COMPRESSOR)
BLUE
THERMISTOR
(HEAT SINK)
BROWN
BLACK
CN21CN22CN23CN26CN25
If the voltage does not appear, replace Main PCB.
02-11
Trouble shooting 9
INDOOR UNIT Error Method:
Indoor EEPROM abnormal
(Model No.)
Indicate or Display:
Indicate or Display:
Indoor Unit: No LED
Outdoor Unit : No indication
ERROR CODE : E : 11
Detective Actuators:
Indoor Unit Controller PCB circuit
Detective details:
When the model information being read from EEPROM has
an apparent error.
Forecast of Cause:
1. External cause 2. Defective connection of electric components 3. Controller PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
YESYES
Check Point 2 :
Check Indoor Unit electric components
Check all connectors.
(loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
Check Point 3 : Replace Controller PCB
Change Controller PCB.
NO
Check Point 1-2 :
Check external cause at Indoor and Outdoor
(Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus
in the same circuit.
Momentary power failure : Check if there is a defective contact
or leak current in the power supply
circuit.
Noise : Check if there is any equipment causing harmonic
wave near electric line.(Neon bulb or electric
equipment that may cause harmonic wave)
Check the complete insulation of grounding.
02-12
Note : EEPROM
EEPROM(Electronically Erasable and
Programmable Read Only Memory) is a nonvolatile memory which keeps memorized
information even if power is turned off. It can
change the contents electronically.
To change the contents, it uses higher
voltage than normal, and it can not change a
partial contents. (Rewriting shall be done
upon erasing the all contents.)
There is a limit in a number of rewriting.
Trouble shooting 10
INDOOR UNIT Error Method:
Indoor Fan Motor abnormal
Indicate or Display:
Indoor Unit: No LED
Outdoor Unit : No indication
ERROR CODE : E : 12
Detective Actuators:
Detective details:
Indoor Unit Controller PCB Circuit
Indoor Fan Motor
Forecast of Cause:
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise
4. Capacitor failure5. Control PCB failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check Motor winding
Check Indoor Fan motor. (PARTS INFORMATION 5)
>>If Fan motor is abnormal, replace it.
OK
When the condition that actual frequency of Indoor Fan is
below 1/3 of target frequency is continued more than 56 seconds.
Check Point 3 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
OK
Check Point 4 : Check Motor Capacitor
Check continuity of motor capacitor
>>If it is shorted, replace the capacitor.
Check Point 5 : Check Output Voltage of Control PCB
Check indoor unit circuit diagram
and the output voltage (between 2 (White) and 3 (Red)) of CN5.
AUU18RCLX : 77% of Input AC voltage (Cooling, Airflow[HIGH])
73% of Input AC voltage (Heatling, Airflow[HIGH])
AUU24RCLX : 93% of Input AC voltage (Cooling, Airflow[HIGH])
81% of Input AC voltage (Heatling, Airflow[HIGH])
AUU36RCLX : 91% of Input AC voltage (Cooling, Airflow[HIGH])
91% of Input AC voltage (Heatling, Airflow[HIGH])
AUU42RCLX : 98% of Input AC voltage (Cooling, Airflow[HIGH])
98% of Input AC voltage (Heatling, Airflow[HIGH])
If the voltage is not correct, replace Controller PCB.
02-13
Trouble shooting 11
INDOOR UNIT Error Method:
Outdoor Communication Signal Error
(Forward Transfer Signal Error)
Indicate or Display:Indicate or Display:
Indoor Unit: No LED
Outdoor Unit : LED 1 time blink
ERROR CODE : E : 13
Detective Actuators:
Indoor Unit Controller PCB Circuit
Forecast of Cause:
1. Connection failure 2. External cause 3. Controller PCB failure
Check Point 1-1 : Reset the power
Does Error indication reappear?
YESYES
Check Point 2 : Check Connection
Check any loose or removed connection line of
Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check connection between Indoor Unit Controller PCB
and Filter PCB.
(If there is loose connector or open cable)
Detective details:
When the outdoor unit cannot receive the serial signal from Indoor unit
more than 10seconds.
NO
Check Point 1-2:
Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
OK
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC208 - 230V appears at Outdoor Unit Terminal L - N.
OK
Check Point 4 : Check Serial Signal (Forward Transfer Signal)
Check Serial Signal (Forward Transfer Signal)
>> Check if Indicated value swings between AC70V and AC130V at Outdoor Unit Terminal 2 - 3.
>> If it is abnormal, Controller PCB is failure. >> Replace Controller PCB
WHITE
BLACK
RED
WHITE
BLACK
N
L
3
2
1
+
-
02-14
Trouble shooting 12
OUTDOOR UNIT Error Method:
Compressor Temperature Sensor Error
Indicate or Display:
Indoor Unit: No LED
Outdoor Unit : LED 7 times blink
ERROR CODE : E : 15
Detective Actuators:
Outdoor Unit Main PCB Circuit
Compressor Temperature Thermistor
Detective details:
When Compressor Temperature Thermistor open or short-circuit is
detected at power ON or while running the compressor.
Forecast of Cause :
1. Connector connection failure 2. T hermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature
32°F
(0°C)
41°F
(5°C)
50°F
(10°C)
59°F
(15°C)
68°F
(20°C)
86°F
(30°C)
41.164.581.8105135176Resistance Value (k )
Temperature
158°F
(70°C)
176°F
(80°C)
194°F
(90°C)
212°F
(100°C)
248°F
(120°C)
284°F
(140°C)
104°F
(40°C)
320°F
(160°C)
122°F
(50°C)
18.126.9
356°F
(180°C)
140°F
(60°C)
12.5
1.211.983.434.616.318.78Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
0.77
0.51
OKOK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
THERMISTOR
THERMISTOR
(DISCHARGE)
1212121212
(PIPE)
BROWN
THERMISTOR
(OUTDOOR)
BLACK
THERMISTOR
(COMPRESSOR)
BLUE
THERMISTOR
(HEAT SINK)
BROWN
BLACK
CN21CN22CN23CN26CN25
If the voltage does not appear, replace Main PCB.
02-15
Indicate or Display:
Trouble shooting 13
OUTDOOR UNIT Error Method:
INDOOR UNIT
Pressure Switch Error
Detective Actuators:
Outdoor Unit Main PCB Circuit
Pressure Switch
Indicate or Display:
Indoor Unit: No LED
Outdoor Unit : LED 9 times blink
ERROR CODE : E : 16
Detective details:
When pressure switch open is detected in 10 seconds
after the power is turned on.
Check Point 3 :Check Point 2 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage
at Pressure Switch. (DC5.0V)
HIGH PRESSURE SW
RED
1
CN37
If the voltage does not appear, replace Main PCB.
2
1
2
3
RED
BLACK
BLACK
4WV
OK
Check Point 3 : Check Pressure Switch
Check if connector is loose or cable is open.
>> If no abnormal connection is found,
replace Pressure Switch.
After replacing Pressure Switch, check operating
condition and pressure in operation.
02-16
Trouble shooting 14
OUTDOOR UNIT Error Method:
IPM error (Permanent Stop)
Indicate or Display:
Indoor Unit: No LED
Outdoor Unit : LED 12 times blink
ERROR CODE : E : 17
Detective Actuators:
Outdoor Unit Main PCB Circuit
Compressor
Detective details:
When more than normal operating current to IPM in Main PCB flows,
the compressor stops.
After the compressor restarts, if the same operation is repeated within 40sec,
the compressor stops again.
Ifandrepeats 5 times, the compressor stops permanently.
Forecast of Cause :
1. Defective connection of electric components 2. Outdoor Fan Operation failure
3. Outdoor Heat Exchanger clogged4. Compressor failure5. Main PCB failure
Check Point 1 : Check connections of Outdoor Unit Electrical Components
Check if the terminal connection is loose.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Check Outdoor Fan, Heat Exchanger
Is there anything obstructing the air distribution circuit?
Is there any clogging of Outdoor Heat Exchanger?
Is the Fan rotating by hand when operation is off ?
>> If the Fan Motor is locked, replace it.
Check Outdoor Fan Motor. (Refer to Trouble shooting 18)
>> If the Fan Motor is failure, replace it.
OK
Check Point 3 : Check Compressor
Check Compressor.
(PARTS INFORMATION 2)
OKOK
Check Point 4 : Replace Main PCB
If Check Point 1, 2, 3 do not improve the symptom, change Main PCB.
02-17
Trouble shooting 15
OUTDOOR UNIT Error Method:
CT error
Indicate or Display:
Indoor Unit: No LED
Outdoor Unit : No indication
ERROR CODE : E : 18
Detective Actuators:
Outdoor Unit Main PCB Circuit
Outdoor Unit Filter PCB Circuit
(Input current sensor unit)
Detective details:
When Input Current Sensor has detected lower than 0.5A
while Inverter Compressor is operating at higher than 56Hz,
after 1minute upon starting the Compressor.
(Except during the defrost operation)
Forecast of Cause :
1. Defective connection of electric components 2. External cause 3. Filter PCB failure 4. Main PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
NO
YES
Check Point 2 :
Check connections of Outdoor Unit Electrical Components
Check if the terminal connection is loose.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring,
reset the power.
OK
Check Point 1-2 :
Check external cause at Indoor and Outdoor
(Voltage drop or Noise)
Instant drop : Check if there is a large load electric
apparatus in the same circuit.
Momentary power failure : Check if there is a defective
contact or leak current in the
power supply circuit.
Noise : Check if there is any equipment causing harmonic
wave near electric line.(Neon bulb or electric
equipment that may cause harmonic wave)
Check the complete insulation of grounding.
Check Point 3 : Check Filter PCB and Main PCB
Check DC voltage of CN1 (between 2 (Brown) and 3 (Red)) on Filter PCB.
>> After 40seconds upon starting the Compressor,
If it is higher than 0.2V, Main PCB is failure. (Filter PCB is normal) >> Replace Main PCB
>> If it is lower than 0.2V, F ilter PCB is failure.>> Replace Filter PCB
If it does not improve the symptom, change Main PCB.
02-18
Trouble shooting 16
OUTDOOR UNIT Error Method:
INDOOR UNIT
Active Filter Module (AFM) error
Indicate or Display:
Indoor Unit: No LED
Outdoor Unit : No indication
ERROR CODE : E : 19
Detective Actuators:
Outdoor Unit Main PCB Circuit
Active Filter Module
Detective details:
When inverter input DC voltage is higher than 467V or
lower than 237V.
When a momentary power cut off occurred on low voltage.
Forecast of Cause :
1. External cause 2. Connector connection failure 3. Active Filter Module failure˴㧠. Main PCB failure
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OKOK
Check Point 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 3 : Check Active Filter Module
Check Active Filter Module. (PARTS INFORMATION 3)
>>If Active Filter Module is abnormal, replace it.
OKOK
Check Point 4 : Replace Main PCB
If Check Point 1, 2 do not improve the symptom, change Main PCB.
Indoor Unit: No LED
Outdoor Unit : LED 13 times blink
ERROR CODE : E : 1A
Detective Actuators:
Outdoor Unit Main PCB Circuit
Detective details:
While running the compressor, if the detected rotor location is out of
phase with actual rotor location more than 90 degrees,
the compressor stops.
After the compressor restarts, if the same operation is repeated
within 40sec, the compressor stops again.
Ifandrepeats 5 times, the compressor stops permanently.
Forecast of Cause :
1. Defective connection of electric components 2. Main PCB failure
Check Point 1 : Check connection of around the Compressor components
For Compressor Terminal, Main PCB
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
(Refer to PARTS INFORMATION 2)
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 : Replace Main PCB
If Check Point 1 do not improve the symptom, change Main PCB.
02-20
Trouble shooting 18
OUTDOOR UNIT Error Method:
Outdoor Unit Fan Motor Error
Indicate or Display:
Indoor Unit: No LED
Outdoor Unit : LED 15 (Fan motor 1)/ 16(Fan motor 2) times blink
ERROR CODE : E : 1b
Detective Actuators:
Outdoor Unit Main PCB Circuit
Outdoor Fan Motor
Detective details:
When outdoor fan rotation speed is less than 100rpm in 20 seconds
after fan motor starts, fan motor stops.
After fan motor restarts, if the same operation within 60sec is repeated
3 times in a row, compressor and fan motor stops.
Ifandrepeats 5 times in a row, compressor and fan motor stops
permanently.
Forecast of Cause:
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Main PCB failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
OK
Check Point 3 : Check Output Voltage of Main PCB
Check outdoor unit circuit diagram and the voltage. (Measure at Main PCB side connector)
AUU18/ 24/ 36RCLXAUU42RCLX
FAN MOTOR 1
FM
CN802
RED
1
2
BLACK
3
WHITE
4
YELLOW
5
BLUE
6
Read wireDC voltage
Red - Black
White - Black
If the voltage is not correct, replace Main PCB.
㨪
150380V
15 1.5V
CN802
CN803
RED
1
2
BLACK
3
WHITE
4
YELLOW
5
BLUE
6
RED
1
2
BLACK
3
WHITE
4
YELLOW
5
BLUE
6
FAN MOTOR 1
FM
FAN MOTOR 2
FM
02-21
Trouble shooting 19
OUTDOOR UNIT Error Method:
Heat Sink Temperature Sensor Error
Indicate or Display:
Indoor Unit: No LED
Outdoor Unit : LED 8 times blink
ERROR CODE : No indication
Detective Actuators:
Outdoor Unit Main PCB Circuit
Heat Sink Temperature Thermistor
Detective details:
When Heat Sink Temperature Thermistor open or short-circuit is
detected at power ON or while running the compressor.
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
Temperature
32°F
(0°C)
140°F
(60°C)
41°F
(5°C)
158°F
(70°C)
50°F
(10°C)
176°F
(80°C)
59°F
(15°C)
7.67
194°F
(90°C)
68°F
(20°C)
6.109.7312.416.1Resistance Value (k )
212°F
(100°C)
86°F
(30°C)
230°F
(110°C)
104°F
(40°C)
2.623.95
248°F
(120°C)
122°F
(50°C)
1.79
1.250.89Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
0.65
0.48
0.36
0.27
0.21
OKOK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
Indoor Unit: No LED
Outdoor Unit : LED 14 times blink
ERROR CODE : No indication
Detective Actuators:
Outdoor Unit Main PCB Circuit
Detective details:
On start-up the compressor, when detected rotor position is out of phase
with actual rotor position more than 90 degrees,the compressor stops.
After the compressor restarts, if the same operation is repeated
within 40sec, the compressor stops again.
Ifandrepeats 5 times, the compressor stops permanently.
Forecast of Cause :
1. Defective connection of electric components 2. Main PCB failure
Check Point 1 : Check connection of around the Compressor components
For Compressor Terminal, Main PCB
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
(Refer to PARTS INFORMATION 2)
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 : Replace Main PCB
If Check Point 1 do not improve the symptom, replace Main PCB.
02-23
2-3 TROUBLE SHOOTING WITH NO ERROR CODE
Trouble shooting 21
Indoor Unit - No Power
Forecast of Cause:
1. Power Supply failure 2. External cause
3. Electrical Components defective
Check Point 1 : Check Installation Condition
Isn’t the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring
to Installation Manual or Data & Technical Manual.
OKOK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in
the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OKOK
Check Point 3 : Check Electrical Components
Check Voltage of power supply.
>> Check AC208 - 230V appears at Indoor Unit Terminal 1 - 2 (Power Supply).
YESYES
Check Fuse (F101) in Filter PCB.
>> If Fuse is open, check if the wiring between Terminal and Filter PCB
is loose, and replace Fuse.
Check Varistor (VA101, VA102) in Filter PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply.
Check the correct power supply and replace Varistor.
OKOK
If the symptom does not change by above Check3, replace Filter PCB.
NO
02-24
Trouble shooting 22
Outdoor Unit - No Power
Forecast of Cause:
1. Power Supply failure 2. External cause
3. Electrical Components defective
Check Point 1 : Check Installation Condition
Isn’t the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring
to Installation Manual or Data & Technical Manual.
OKOK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OKOK
Check Point 3 : Check Electrical Components
Check the voltage of power supply.
>> Check if AC208 - 230V appears at Outdoor Unit Terminal L - N.
YESYES
Check Fuse (F2, F4) in Main PCB.
>> If Fuse is open, check loose terminal or removed connector (C
Check Varistor in Main PCB (VA103).
>> If Varistor is defective, there is a possibility of an abnormal power supply.
Check the correct power supply and replace Varistor.
Upon checking the normal power supply, replace Varistor.
N1) , and replace Fuse.
YESYES
Check Active Filter Module. (PARTS INFORMATION 3)
>>If Active Filter Module is abnormal, replace it.
OK
If the symptom does not change by above Check 3, replace Main PCB.
NO
02-25
Trouble shooting 23
Forecast of Cause:
1. Setting/ Connection failure 2. External cause
No Operation (Power is ON)
3. Electrical Component defective
Check Point 1 : Check indoor and outdoor installation condition
Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control, or terminals between Indoor Units.
Or, check if there is an open cable connection.
Are these Indoor Unit, Outdoor Unit, and Remote Control suitable model numbers to connect?
>> If there is some abnormal condition, correct it by referring to Installation manual and
Data & Technical Manual.
OK
Turn off Power and check/ correct followings.
Is there loose or removed communication line of Indoor Unit and Outdoor Unit?
OK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OKOK
Check Point 3 : Check Electrical Components at Indoor and Outdoor
Check Voltage at CN17 of Controller PCB. (Power supply to Remote Control)
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal)>> Replace Remote Control
>> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
>> If the symptom does not change by above Check 1, 2, 3, replace Main PCB of Outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data & Technical
Manual.
OKOK
psipsi
Check Point 5 : Check Refrigeration Cycle
Check if Strainer is clogged (Refer to the figure at right).
Measure Gas Pressure and if there is a leakage, correct it.
>> When recharging the refrigerant, make sure to perform
vacuuming, and recharge the specified amount.
Check EEV (PARTS INFORMATION 4)
Check Compressor (PARTS INFORMATION 1,2)
Attention
Strainer normally does not have temperature difference
between inlet and outlet as shown in, but if there is a
difference like shown in, there is a possibility of inside
clogged. In this case, replace Strainer.
Pipe (In)Pipe (Out)
Pipe (In)Pipe (Out)
02-27
Trouble shooting 25
Abnormal Noise
Forecast of Cause :
1. Abnormal installation (Indoor/ Outdoor) 2. Fan failure(Indoor/ Outdoor)
3. Compressor failure (Outdoor)
Diagnosis method when Abnormal Noise is occurred
Abnormal noise is coming from Indoor Unit.
(Check and correct followings)
Abnormal noise is coming from Outdoor Unit.
(Check and correct followings)
Is Main Unit installed in stable condition?
Is the installation of Air suction grille and
front panel normal?
OK
Is Fan broken or deformed?
Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
Trouble shooting 26
Forecast of Cause:
Water Leaking
Diagnosis method when water leak occurs
Is Main Unit installed in stable condition?
Is Fan Guard installed normally?
OK
Is Fan broken or deformed?
Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
OK
Check if vibration noise by loose bolt or contact noise
of piping is happening.
Is Main Unit installed in stable condition?
Is Main Unit broken or deformed at the time of
transportation or maintenance?
OKOK
Is Drain Hose connection loose?
Is there a trap in Drain Hose?
Is Drain Hose clogged?
OKOK
Is Fan rotating?
>> Check Fan Motor (PARTS INFORMATION 5)
OKOK
Is Float Switch defective?
>> Check Float Switch (Refer to Trouble Shooting 6)
Is the filter clogged?
OKOK
psipsi
Check Gas Pressure and correct it
if there was a gas leak.
02-28
2-4 SERVICE PARTS INFORMATION
SERVICE PARTS INFORMATION 1
Compressor
Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting )
Does not start up
Is there open or loose connection
cable?
Check Filter PCB, Main PCB,
connection of Compressor,and winding
resistance. (Refer to the next page).
>> If there is no failure, the defect of
Compressor is considered (Locked
compressor due to clogged dirt or
less oil)
Replace Compressor
Stops soon after starting up
Is there open or loose connection
cable?
Is Gas Pipe Valve open?
(Low Pressure is too low)
psipsi
Check if Refrigerant is leaking.
(Recharge Refrigerant)
Abnormal noise
Check if vibration noise by
loose bolt or contact noise
of piping is happening.
Defective Compressor
can be considered.
(due to inside dirt clogging
or broken component)
Replace Compressor
Check if Strainer is clogged.
(PARTS INFORMATION 4)
Check Filter PCB, Main PCB,
connection of Compressor,and winding
resistance. (Refer to the next page).
>> If there is no failure, the defect of Compressor can be
considered. (Compression part broken or valve defective.)
02-29
Replace Compressor
SERVICE PARTS INFORMATION 2
Inverter Compressor
Check Point 1 : Check Connection
Check terminal connection of Compressor
(loose or incorrect wiring)
Terminal cover opened
UU(RED)(RED)
VV (WHITE)(WHITE)WW
(BLACK)(BLACK)
Check Point 2 : Check Winding Resistance
Check winding resistance of each terminal
If the resistance value is 0or infinite, replace Compressor.
U
Check connection of Main PCB
(Loose or incorrect wiring)
MAIN PCB
RED
WHITE
W304
W305W303
Compressor
BLACK
Resistance Value :
0.88(For AUU18/ 24/ 36RCLX)
0.188 (For AUU42RCLX)
at 68°F(20°C)
W
V
Check Point 3 : Replace Main PCB
If the symptom does not change with above Check 1, 2, replace Main PCB.
02-30
SERVICE PARTS INFORMATION 3
Active Filter Module
Check Point 1 : Check Open or Short-circuit and Diode (D1)
Remove connector, check the open or short-circuit and the diode in the module
Check the open or short-circuit
Tester(+)Tester(-)
(+)
()
L2L1
Power factor control
D1
P
N1
N2
Io
Check the diode
Tester(+)Tester(-)
If it is abnormal,replace ACTIVE FILTER MODULE
Check Point 2 : Check the Output DC voltage (between P and N1)
(+)
()
P
L1
P
L1,L2
L2
L2
P
Terminal
Control Box
Terminal
()
N1
(+)
L2
N1
N2
P
L2
Resistance value
360k
0
720k
5.4M (approx.)
360k
5.8M (approx.)
Resistance value
5.3M (approx.)
5.4M (approx.)
Check the Output DC voltage (between P and N1) of compressor stopping and operating.
>> If the output voltage of compressor operating is less than the output voltage of compressor stopping,
Active Filter Module is detective. >> Replace Active Filter Module
02-31
SERVICE PARTS INFORMATION 4
Outdoor unit Electronic Expansion Valve
( EEV )
Check Point 1 : Check Connections
Check connection of connector (CN27)
( Loose connector or open cable )
4
EXPANSION
VALVE COIL
EV
Check Point 3 : Check Voltage from Main PCB.
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Main PCB.
Check Point 4 : Check Noise at start up
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Main PCB.
RED
1
BROWN
2
BLUE
3
4
5
6
ORANGE
YELLOW
WHITE
CN27
Check Point 2 : Check Coil of EEV
Remove connector, check each winding
resistance of Coil.
Read wire
Resistance value
White - Red
Yellow - Brown
Orange - Red
46
at 68°F(20°C)
Blue - Brown
If Resistance value is abnormal, replace EEV.
Check Point 5 : Check Opening and Closing Operation of Valve
When Valve is closed,
it has a temp. difference between Inlet and Outlet.
CLOSE
Example : Hot Gas
If it is open,
it has no temp. difference between Inlet and Outlet.
OPEN
Example : Hot Gas
DC
Pipe (In)
Hi TEMP.
Pipe (Out)
Normal TEMP.
Pipe (In)
Hi TEMP.
Pipe (Out)
Hi TEMP.
Check Point 6 : Check Strainer
Strainer normally does not have temperature difference between inlet and outlet as shown in,
but if there is a difference as shown in, there is a possibility of inside clogged. In this case, replace Strainer.
Remove the 7 mounting screws.
Remove the TOP PANEL upward.
FRONT VIEWREAR VIEW
03-04
3. INVERTER BOX removal
Remove the 4 mounting screws.
Remove the connectors and cords. (Refer to VIEW -C,-D)
Remove the INVERTER BOX upward.
C
FRONT VIEW
Remove the connectors
VIEW - C
D
Remove power supply &
Connection cord.
REAR VIEW
Remove the connectors
Terminal
GG
Choke coil
VIEW - D
INVERTER BOX
03-05
Remove the 1 mounting screw.
Remove the INVERTER BOX COVER upward.
F
INVERTER BOX COVER
Hook (2 places)
E
Remove the connector and cords.
CN1 (Black/Brown/Red)
Twist W6 and W7
4 times or more.
Twist W4 and W5
2 times or more.
W8 (Black)
W9 (White)
W6 (Black)
03-06
W7 (White)
W200 (Red)
VIEW - E
W4 (Black)
W5 (White)
Remove the connector and cords.
Twist 4 times or more2 turn the Wire this way
" - " (Black)
" L2 " (Brown)
"+"(Red)
CN407
" N1 " (Blue)
VIEW - F
Thermistor (Heat sink)
" L1 " (White)
" P " (Yellow)
BIND
W12 / "P" (Yellow)
W13 / "N1"(Blue)
CN407
DETAIL
03-07
Remove the 6 mounting screws.
Remove the INVERTER BOX A upward.
INVERTER BOX A
5
6
1
2
4
3
3
4
REAR VIEW
6
5
Main PCB
Remove the 1 mounting screw.
Remove the Main PCB upward.
Hook (3 places)
LEFT SIDE VIEW
Filter PCB
Remove the 2 mounting screws.
Remove the Filter PCB upward.
Hook (2 places)
Main PCBFilter PCB
ScrewScrew
03-08
1-1-4 ASSEMBLY PROCESS of INVERTER UNIT (For AOU18/ 24/ 36RLX)
1. FILTER PCB
As shown in Fig.1, assemble FILTER PCB to INVERTER BOX A.
As shown in Fig.2, pull out the wires of FILTER PCB.
Hook (2 places)
Screw (2 places)
FILTER PCBINVERTER BOX A
Fig.1
2. MAIN PCB
As shown in Fig.3, temporarily fix MAIN PCB to INVERTER BOX A.
After it is temporary fix of MAIN PCB, As shown in the Fig 4 - 7,
pull out the wires of MAIN PCB.
Fig.4
W12(Yellow)
W13(Blue)
Fig.2
Fig.5
Hook (3 places)
MAIN PCB
Screw
Fig.3
Fig.6/ 7
03-09
As shown in Fig.4, pull out the wires.
W16 (Red)
W17 (Black)
W303 (Black)
W304 (White)
W305 (Red)
CN407
Thermistor
(Heat sink)
Fig. 4
As shown in Fig.5, pull out the wires and fix them.
Hook (2 places)
W303 (Black)
W304 (White)
W305 (Red)
Fig. 5
W12 (Yellow)
W13 (Blue)
W17 (Black)
W16 (Red)
03-10
As shown in Fig.6, pull out the wires.
W200 (Red)
CN1
Fig. 6
As shown in Fig.7, pull out the wires.
A
W200 (Red)
CN1 wire with connector
HYIC1
Fig. 7
03-11
Don't come in contact with HYIC1.
DETAIL - A
For AOU18/ 24RLX
As shown in Fig.8, connect wires.
CN34 (Yellow)
CN1 (White)
Fig. 8
As shown in Fig.9, connect wires.
Through this hole.
TM102 (White line)TM101 (Black line)
Fig. 9
03-12
For AOU36RLX
As shown in Fig.8, connect wires.
CN1 (White)CN34 (Yellow)
As shown in Fig.9, connect wires.
W21 (Orange)
W22 (Orange)
Through this hole.
Fig. 8
PTC Thermistor
Fig. 9
03-13
TM102 (White line)TM101 (Black line)
As shown in Fig.10, fix the wire to INVERTER BOX A.
Thermistor (Heat sink)
Hook (3 places)
Pull out the wire
through this opening
CN407
Fig. 10
As shown in the figures, set wire with connector and bind it to INVERTER BOX A.
Remove the 7 mounting screws.
Remove the TOP PANEL upward.
FRONT VIEWREAR VIEW
03-20
3. INVERTER BOX removal
Remove the 4 mounting screws.
Remove the connectors and cords. (Refer to VIEW -C,-D)
Remove the INVERTER BOX upward.
C
FRONT VIEW
Remove the connectors
VIEW - C
D
Remove power supply &
Connection cord.
REAR VIEW
Remove the connectors
Terminal
GG
Choke coil
VIEW - D
INVERTER BOX
03-21
Remove the 1 mounting screw.
Remove the INVERTER BOX COVER upward.
F
INVERTER BOX COVER
Hook (2 places)
E
Remove the connector and cords.
Twist W6 and W7
2 times or more.
W6 (Black)
W7 (White)
VIEW - E
03-22
W200 (Red)
W1 (Black)
W2 (White)
Remove the connector and cords.
" - " (Black)
"+"(Red)
CN407
"" (White)
D,Power (Bridge)
"" (Gray)
" L2 " (Brown)
" L1 " (White)
Thermistor (Heat sink)
BIND
"P" (Yellow)
"N1"(Blue)
CN407
" N1 " (Blue)
VIEW - F
" P " (Yellow)
03-23
Remove the 6 mounting screws.
Remove the INVERTER BOX A upward.
INVERTER BOX A
5
6
1
2
4
3
3
4
REAR VIEW
6
5
Main PCB
Remove the 1 mounting screw.
Remove the Main PCB upward.
Hook (3 places)
LEFT SIDE VIEW
Filter PCB
Remove the 2 mounting screws.
Remove the Filter PCB upward.
Hook (2 places)
Main PCBFilter PCB
ScrewScrew
03-24
1-2-4 ASSEMBLY PROCESS of INVERTER UNIT (For AOU42RLX)
1. FILTER PCB
As shown in Fig.1, assemble FILTER PCB to INVERTER BOX A.
As shown in Fig.2, pull out the wires of FILTER PCB.
Hook (2 places)
Screw (2 places)
FILTER PCBINVERTER BOX A
Fig.1
Fig.2
2. MAIN PCB
As shown in Fig.3, temporarily fix MAIN PCB to INVERTER BOX A.
After it is temporary fix of MAIN PCB, As shown in the Fig 4 - 6,
pull out the wires of MAIN PCB.
Fig.4
Fig.5
W14(Yellow)
W15(Blue)
Hook (3 places)
MAIN PCB
Screw
03-25
Fig.6
Fig.3
As shown in Fig.4, pull out the wires.
Thermistor
(Heat sink)
CN407
Fig. 4
As shown in Fig.5, pull out the wires and fix them.
Hook (2 places)
W107 (White)
W303 (Black)
W304 (White)
W305 (Red)
W303 (Black)
W304 (White)
W305 (Red)
W108 (Violet)
CN407
Fig. 5
03-26
Thermistor
(Heat sink)
As shown in Fig.6, pull out the wires.
A
W200 (Red)
As shown in Fig.7, connect wires.
CN34 (Yellow)CN1 (White)
CN1 wire with connector
Fig. 6
HYIC1
Don't come in contact with HYIC1.
VIEW - A
Fig. 7
03-27
As shown in Fig.8, connect wires.
W108 (Violet)
W107 (White)
Twist 5 times or more.
Gray line
Make White line
on Black line
Through this hole.
TM102 (White line)TM101 (Black line)
Fig. 8
03-28
As shown in Fig.9, fix the wire to INVERTER BOX A.
Thermistor (Heat sink)
Hook (3 places)
Pull out the wire
through this opening
CN407
Fig. 9
As shown in the figures, set wire with connector and bind it to INVERTER BOX A.
Bind wire to
INVERTER BOX A.
Through the guide
W303 (Black)
W304 (White)
W305 (Red)
Fig. 10
03-29
Through the hole
2. REPLACEMENT PARTS (For INDOOR UNIT)
2-1 PARTS LAYOUT DRAWING
1. INTAKE GRILLE removal
Push the INTAKE GRILLE pushbuttons (2 places).
Open the INTAKE GRILLE
PUSH
OPEN
PUSH
Pushbotton
(2 places)
Remove the GRILLE hinge wire.
INTAKE GRILLE
Pull up while pressing the B section.
B
Remove the INTAKE GRILLE.
03-30
A
GRILLE hinge wire
Part A detail view
Part B section view
2. FILTER removal
Remove the FILTER.
FILTER
Hook
(3 places)
3. CONTROL BOX COVER removal
Remove the 5 mounting screws.
Remove the CONTROL BOX COVER upward.
CONTROL BOX COVER
03-31
4. Wiring and Parts layout
Thermistor(Room temp.)
CLAMP
(PWB wire (For Power Supply PCB))
(Wire with connector (For Float SW))
(Wire with connector (For Remocon))
CLAMP
(Wire with connector (For Float SW))
(Wire with connector (For Remocon))
Terminal-3P
CN17
(Remocon)
CN15
(Float SW)
CN8
Thermistor
(Room temp.)
CN1
(Power Supply PCB)
Capacitor,Plastic
BIND
(Wire with connector (For Capacitor,Plastic))
(PWB wire (For Power Supply PCB)X2)
(Wire with connector (For Float SW))
(Wire with connector (For Remocon))
Power Supply PCBController PCB
BLACK
CN6
(Drain Pump)
WHITE
RED
CN7
Thermistor
(Heat Exchanger temp.)
CN10
(Stepping motor)
CN16
(MOTOR Feed Back)
Detail View
CN5
(FAN MOTOR)
03-32
CN4
(Capacitor)
Detail View
5. PANEL FRAME removal
Pull up the corner section (A) of the PANEL FRAME as shown in
figure (4 locations).
A
PANEL FRAME
A
B
A
A
Part A detail view
Pull up in the direction of the arrow while holding down
the C section of figure (4 locations).
C
Part B detail view
PANEL FR A M E
PANEL BASE
03-33
5. PANEL BASE removal
Remove the 4 mounting bolts.
Remove the PANEL BASE upward.
PANEL BASE
6. CONTROL UNIT removal
Remove the 3 mounting bolts and 1 mouting screw.
Remove the CONTROL UNIT upward.
SCREW
BOLT
(3places)
CONTROL UNIT
03-34
7. DRAIN PAN removal
Remove the DRAIN PAN ASSY.
DRAIN PAN ASSY
03-35
8. TURBO FAN removal
Remove the M8 NUT and Washer(TURBO FAN).
Remove the TURBO FAN ASSY.
For AUU18/ 24RCLX
For AUU36/ 42RCLX
M8 NUT
Washer(TURBO FAN)
TURBO FAN ASSY
The M8 special NUT should
be tightened with a torque of
1.96-7.84Nm.
M8 NUT
Washer(TURBO FAN)
TURBO FAN ASSY
The M8 special NUT should
be tightened with a torque of
1.96-7.84Nm.
03-36
9. FAN MOTOR removal
For AUU18/ 24RCLX
Remove the 3 mounting nuts.
Remove the FAN MOTOR ASSY.
Special NUT M6
(3 places)
FAN MOTOR ASSY
Rubber
(Vibration-proof) -B
(3 places)
For AUU36/ 42RCLX
Remove the 4 mounting nuts.
Remove the FAN MOTOR ASSY.
Special NUT M6
(4 places)
Rubber
(Vibration-proof) -A
(3 places)
FAN MOTOR ASSY
03-37
10. DRAIN PUMP removal
Remove the 2 mounting screws.
Remove the DRAIN PUMP UNIT.
DRAIN PUMP UNIT
DRAIN HOSE
03-38
1116,Suenaga,Takatsu-ku,Kawasaki 213-8502,Japan
Apr. 2006 Printed in Japan
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.