Fujitsu AOU24RLX, AOU42RLX, AUU42RCLX, AUU24RCLX, AOU18RLX User Manual

...
SPLIT TYPE ROOM AIR CONDITIONER
CASSETTE
INSTRUCTION
Models Indoor unit Outdoor unit
AUU18RCLX AUU24RCLX AUU36RCLX AUU42RCLX
type
INVERTER
AOU18RLX AOU24RLX AOU36RLX AOU42RLX
R410A
CONTENTS
1. DESCRIPTION OF EACH CONTROL OPERATION
1. COOLING OPERATION..............................................................................................
2. HEATING OPERATION..............................................................................................
3. DRY OPERATION......................................................................................................
4. AUTO CHANGEOVER OPERATION.........................................................................
5. INDOOR FAN CONTROL...........................................................................................
6. OUTDOOR FAN CONTROL.......................................................................................
7. LOUVER CONTROL...................................................................................................
8. COMPRESSOR CONTROL........................................................................................
9. TIMER OPERATION CONTROL................................................................................
10. ELECTRONIC EXPANSION VALVE CONTROL........................................................
11. TEST OPERATION CONTROL..................................................................................
12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )................................
13. 4-WAY VALVE EXTENSION SELECT.......................................................................
14. AUTO RESTART........................................................................................................
15. PUMP DOWN ( Refrigerant collecting operation )......................................................
16. COMPRESSOR PREHEATING..................................................................................
DEFROST OPERATION CONTROL..........................................................................
17.
18. DRAIN PUMP OPERATION.......................................................................................
19. ENERGY SAVE FUNCTION.......................................................................................
20. VARIOUS PROTECTIONS.........................................................................................
01-01 01-02 01-03 01-04 01-05 01-07 01-08 01-09 01-10 01-12 01-12 01-12 01-12 01-12 01-13
01-13 01-13
01-15 01-15 01-16
2. TROUBLE SHOOTING
2-1 ERROR DISPLAY......................................................................................................
2-1-1 WIRED REMOTE CONTROLLER DISPLAY......................................................
2-1-2 OUTDOOR UNIT DISPLAY................................................................................
2-2 TROUBLE SHOOTING WITH ERROR CODE..........................................................
2-3 TROUBLE SHOOTING WITH NO ERROR CODE....................................................
2-4 SERVICE PARTS INFORMATION............................................................................
02-01 02-01 02-03
02-04 02-24
02-29
3. REPLACEMENT PARTS
1 REPLACEMENT PARTS ( For OUTDOOR UNIT ).......................................................
1-1 For AOU18/ 24/ 36RLX...........................................................................................
1-1-1 PARTS LAYOUT DRAWING...............................................................................
1-1-2 WIRING................................................................................................................
1-1-3 DISASSEMBLY PROCESS.................................................................................
1-1-4 ASSEMBLY PROCESS of INVERTER UNIT......................................................
1-2 For AOU42RLX.......................................................................................................
1-2-1 PARTS LAYOUT DRAWING...............................................................................
1-2-2 WIRING................................................................................................................
1-2-3 DISASSEMBLY PROCESS.................................................................................
1-2-4 ASSEMBLY PROCESS of INVERTER UNIT......................................................
2 REPLACEMENT PARTS ( For INDOOR UNIT )...........................................................
2-1 PARTS LAYOUT DRAWING...................................................................................
03-01 03-01 03-01 03-03 03-04 03-09
03-15 03-15 03-17 03-19 03-25
03-30 03-30
CASSETTE type
INVERTER
R410A
1 . DESCRIPTION OF EACH
CONTROL OPERATION
1. COOLING OPERATION
1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor.
* If the room temperature is 3.6 degF(2 degC) higher than a set temperature,
the compressor operation frequency will attain to maximum performance.
* If the room temperature is 3.6 degF(2 degC) lower than a set temperature, the compressor
will be stopped.
* When the room temperature is between +3.6 degF(+2 degC) to -3.6 degF(-2 degC) of
the setting temperature, the compressor frequency is controlled within the range shown in Table1. However, the maximum frequency is limited in the range shown in Figure 1 based on the fan speed mode and the outdoor temperature.
( Table 1 : Compressor Frequency Range )
minimum frequency
AUU18RCLX 20Hz AUU24RCLX AUU36RCLX AUU42RCLX
20Hz 20Hz 25Hz
maximum frequency
63Hz 80Hz 90Hz 92Hz
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
Outdoor air temperature
87.8°F (31°C)
66.2°F (19°C)
51.8°F (11°C)
A zone
B zone
C zone
D zone
AUU18RCLX
AUU24RCLX
AUU36RCLX
AUU42RCLX
Fan speed mode
A zone 63Hz Bzone C zone D zone Azone Bzone Czone D zone Azone Bzone C zone D zone Azone Bzone C zone D zone
Hi Me Lo
45Hz 45Hz 35Hz 35Hz 80Hz 55Hz 45Hz 45Hz 90Hz 75Hz 70Hz 63Hz 92Hz 72Hz 60Hz 60Hz
35Hz
35Hz 35Hz
30Hz
55Hz
45Hz
45Hz
35Hz
75Hz
70Hz
63Hz
55Hz
72Hz
60Hz
60Hz
53Hz
45Hz 35Hz
30Hz 55Hz 45Hz 45Hz 35Hz 75Hz 70Hz 63Hz 55Hz 72Hz 60Hz 60Hz 53Hz
01-01
2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor.
* If the room temperature is lower 5.4 degF(3 degC) than a set temperature,
the compressor operation frequency will attain to maximum performance.
* If the room temperature is higher 3.6 degF(2 degC) than a set temperature, the compressor
will be stopped.
* When the room temperature is between +3.6 degF(+2 degC) to -5.4 degF(-3 degC) of
the setting temperature, the compressor frequency is controlled within the range shown in Table2. However, the maximum frequency is limited in the range shown in Figure 2 based on the outdoor temperature.
( Table 2 : Compressor Frequency Range )
minimum frequency
AUU18RCLX 20Hz AUU24RCLX AUU36RCLX AUU42RCLX
20Hz 20Hz 23Hz
maximum frequency
87Hz 87Hz 95Hz 92Hz
( Fig.2 : Limit of Maximum Frequency based on Outdoor Temperature )
Outdoor air temperature
68°F
(20°C)
60.8°F (16°C)
53.6°F (12°C)
41°F
(5°C)
E zone
D zone
C zone
B zone
A zone
AUU18RCLX
AUU24RCLX
AUU36RCLX
AUU42RCLX
A zone 87Hz Bzone C zone Dzone E zone Azone Bzone Czone Dzone Ezone Azone Bzone Czone D zone Ezone Azone B zone C zone D zone Ezone
Limit of Maximum
Frequency
85Hz 70Hz 70Hz 60Hz 87Hz 85Hz 70Hz 70Hz 60Hz 95Hz 95Hz 90Hz 80Hz 80Hz 92Hz 92Hz 90Hz 80Hz 80Hz
01-02
3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to set temperature and room temperature variation which the room temperature sensor of the indoor unit has detected as shown in the Table 3.
( Table 3 : Compressor frequency )
Operating frequency
AUU18RCLX 25Hz AUU24RCLX AUU36RCLX AUU42RCLX
( Fig.3 : Compressor Control based on Room Temperature )
Room temperature
Compressor ON
Ts+1.8 degF
(1 degC)
Compressor OFF
30Hz 45Hz 30Hz
Room temperature
Ts+2.7 degF
(1.5 degC)
Ts : Setting temperature
( Fig.4 : Indoor Fan Control )
Compressor
ON
OFF
Indoor fan
air flow mode
ON
OFF
Air flow mode : Lo
30 5 30 120 5 (sec)
180 180
01-03
4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum mode from among the HEATING, COOLING and MONITORING modes. During operation, the optimum mode is automatically swiched in accordance with temperature changes. The temperature can be set between 64°F(18°C) and 88°F(30°C) in 2 degF(1 degC) steps.
When operation starts, only the indoor fan is operated for 1 minute. (Air flow mode: S- Lo)
1
After 1 minute, depends on the room temperature and outdoor unit's operarion mode, the operation mode is selected in accordance with the table below.
( Table 4 : Operation mode selection table )
Room temperature :TR
TR>Ts+3.6degF
=
(2 degC)
Ts +3.6 degF > TR > Ts-3.6 degF
(2 degC) (2 degC)
Ts +3.6 degF>TR
(2 degC)
Ts : Setting temperature
2
When COOLING was selected at , the same operation as COOLING OPERATION is performed.
3
When HEATING was selected at , the same operation as HEATING OPERATION is performed.
4
When the compressor was stopped for 6 consecutive minutes by the temperature control function after the COOLING or HEATING operation mode was selected at above, operation is switched to MONITORING and the operation mode is selected again.
=
Operation mode
Cooling
Monitoring
Heating
1
1
1
01-04
5. INDOOR FAN CONTROL
1. Fan speed
( Table 5 : Indoor Fan Speed )
AUU18RCLX
Operation mode Air flow mode Speed (rpm)
Heating
Cooling
Hi 400
Me
Lo
S-Lo
Hi 450
Me
Lo
S-Lo
350 310 250
390 330 250
AUU36RCLX
Operation mode Air flow mode Speed (rpm)
Heating
Cooling
Hi 580
Me
Lo
S-Lo
Hi 580
Me
Lo
S-Lo
510 440 300
510 440 300
AUU24RCLX
Operation mode Air flow mode Speed (rpm)
Heating
Cooling
Hi 440
Me
Lo
S-Lo
Hi 490
Me
Lo
S-Lo
380 330 250
430 360 250
AUU42RCLX
Operation mode Air flow mode Speed (rpm)
Heating
Cooling
Hi 620
Me
Lo
S-Lo
Hi 620
Me
Lo
S-Lo
550 470 300
550 470 300
2. FAN OPERATION
The airflow can be switched in 4 steps such as AUTO, LOW, MED, HIGH, while the indoor fan only runs.
When [AUTO] is selected, the indoor fan motor runs LO and OFF at 1 minute intervals.
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, asshowninFigure5. On the other hand, if switched in [HIGH] [LOW], the indoor motor will run at a constant airflow of [COOL] operation modes LOW, MED, HIGH,as shown in Table 5.
( Fig.5 : Airflow change - over ( Cooling : AUTO ) )
*1
When the room temperature rises
TR : Room temperature Ts : Setting temperature
TR-Ts > 3.6 degF
=
(2 degC)
3.6 degF > TR-Ts > 1.8 degF (2 degC) (1 degC)
=
1.8 degF > TR-Ts (1 degC)
HIGH mode
MED mode
LOW mode
When the room temperature drops
TR-Ts > 5.4 degF
=
(3 degC)
5.4 degF > TR-Ts > 3.6 degF (3 degC) (2 degC)
3.6 degF > TR-Ts (2 degC)
*1 : Contains a condition to the following
When the operation mode is set to AUTO mode at the start of operation. When the setting temperature was changed. When the operation mode was changed to COOLING mode. When the airflow mode was changed to AUTO mode.
=
01-05
4. HEATING OPERATION
When the airflow is set to [AUTO], the indoor fan motor operates [MED] mode. Then the indoor fan motor will run according to a room temperature, as shown in Figure 6.
On the other hand, if switched in [HIGH] [LOW], the indoor motor will run at a constant airflow of [COOL] operation modes LOW, MED, HIGH, as shown in Table 5.
( Fig.6 : Airflow change - over ( Heating : AUTO ) )
Indoor heat exchanger temperature
116.6°F
Go up one-step
(47°C)
Hold
105.8°F (41°C)
Go down one-step
5. COOL AIR PREVENTION CONTROL (Heating mode)
The maximum value of the indoor fan speed is set as shown in Figure 7, based on the detected temperature by the indoor heat exchanger sensor on heating mode.
( Fig.7 : Cool Air Prevention Control )
Indoor heat exchanger temperature
SETTING
91.4°F (33°C)
FAN MODE
LO mode
86°F
(30°C)
S-LOW mode
Indoor heat exchanger temperature
86°F
(30°C)
6. DRY OPERATION
Refer to the Figure 4. During the dry mode operation, the fan speed setting can not be changed.
01-06
6. OUTDOOR FAN CONTROL
1. Outdoor Fan Motor
Following table shows the fan speed of the outdoor unit.
( Table 6 : Fan speed of the outdoor unit )
Cooling Heating
AUU18RCLX AUU24RCLX AUU36RCLX
AUU42RCLX
AUU42RCLX has two fan motors.
*
The outdoor fan speed changs in the range mentioned avobe depending on the compressor
*
frequency and outdoor temperature. (When the compressor frequency and outdoor temperature increase, the outdoor fan speed
also changes to the higher speed. When the compressor frequency and outdoor temperature decrease, the outdoor fan speed also changes to the lower speed.)
For AUU18RCLX
*
It runs at 250rpm for 20 seconds after starting up the outdoor fan. When the outdoor heat exchanger tenperature is lower than 35.6°F (2°C), the fan speed switches to 780rpm on heating mode.
For AUU24RCLX / AUU36RCLX
*
It runs at 250rpm for 20 seconds after starting up the outdoor fan. When the outdoor heat exchanger tenperature is lower than 35.6°F (2°C), the fan speed switches to 900rpm on heating mode.
For AUU42RCLX
*
It runs at 500rpm for 20 seconds after starting up the outdoor fan. When the outdoor heat exchanger tenperature is lower than 35.6°F (2°C), the fan speed switches to 900rpm(Upper fan) and 850rpm(Lower fan) on heating mode.
Upper fan Lower fan
780/ 400/ 250/ 220/ 200 rpm
900/ 850/ 780/ 400/ 250/ 220/ 200 rpm 900/ 780/ 400/ 250/ 220/ 200 rpm
850/ 780/ 400/ 350/ 300 rpm
780/ 750/ 350/ 0 rpm
780/ 400/ 250/ 220/ 200 rpm
900/ 850/ 780/ 350/ 200/ 170/ 150 rpm
850/ 780/ 750/ 350/ 200/ 170/ 150 rpm
01-07
7. LOUVER CONTROL
1. VERTICAL LOUVER CONTROL
(Function Range)
Each time the button is pressed, the air direction range will change as follows:
(Operation Range)
Cooling / Dry mode Heating mode Fan mode
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry / Fan mode Heating mode Downward flow
For AUU18/ 24RCLX At the start of operation if the setting louver position is ,the setting position is set to after the louver moves from totally-enclosed position to . (Positioning Control)
Horizontal flow
(Fig.8 : Air Direction Range)
1
2
3
4
For AUU36/ 42RCLX At the start of operation if the setting louver position is or ,the setting position is set to or after the louver moves from totally-enclosed position to . (Positioning Control)
The indoor fan motor starts after the louver reaches to the setting position.
2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing. The range of swing depends on the set airflow direction.
(Swinging Range)
Airflow direction set Range of swing
to to to to
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position. ( Stop mode means Operation stop.)
01-08
8. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as shown in Table 7.
(Table 7 : Compressor Operation Frequency Range)
AUU18RCLX AUU24RCLX AUU36RCLX AUU42RCLX
Cooling Heating
Min Max Min Max
20Hz 20Hz
20Hz 25Hz
63Hz 80Hz 90Hz
92Hz
20Hz 20Hz 20Hz 23Hz
87Hz 87Hz 95Hz 92Hz
Dry
25Hz 30Hz 45Hz 30Hz
2. OPERATION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in Figure 9.
(Fig.9 : Compressor Control at Start-up)
Frequency
1
2
Frequency
Hold
(Frequency)
AUU18RCLX AUU24RCLX AUU36RCLX AUU42RCLX
(Time)
AUU18RCLX AUU24RCLX AUU36RCLX AUU42RCLX
Time A Time B Time C
Time E
For AUU18/ 24/ 36RCLX
Frequency
40Hz
56Hz
Time A Time B Time C Time D Time E
180sec
180sec
Frequency
56Hz
70Hz
60sec
80sec
120sec
180sec
1 Discharge pipe temp. > 50°F (10°C) ,86°F (30°C)
2 Discharge pipe temp. < 50°F (10°C) ,86°F (30°C)
For AUU42RCLX 1 Discharge pipe temp. > 50°F (10°C) ,95°F (35°C)
2 Discharge pipe temp. < 50°F (10°C) ,95°F (35°C)
120sec
180sec
Time D
720sec
720sec
=
(Cooling) (Heating)
(Cooling) (Heating)
=
(Cooling) (Heating)
(Cooling) (Heating)
01-09
9. TIMER OPERATION CONTROL
9-1 Wired Remote Controller
AR-3TA14
ON / TIMER OFF / TIMER
WEEKLY TIMER
TEMPERATURE SET BACK TIMER
1. ON / OFF TIMER
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
2. WEEKLY TIMER
2-1. WEEKLY TIMER
Use this timer function to set operating time for each day of the week. The weekly timer allows up to two ON and OFF time to set up per day.
Operation mode
Stop mode
Set time
The operating time can be set in 30 min increments only. The OFF time can be carried over to next day. The ON timer and the OFF timer functions cannot be set with using the weekly timer.
Both ON and OFF time must be set.
Operation mode
Stop mode
Set time Set time Set time
Operation mode
Stop mode
01-10
2-2. DAY OFF setting
The DAY OFF setting is only available for days for which weekly settings already exist. If the operating time carries over to the next day (during a next day setting), the effective
DAY OFF range will be set as shown below.
Normal
DAY OFF
Operation mode
Operation mode
Stop mode
Stop mode
Preceding day Next day
Setting day
Stop mode
Next day setting
DAY OFF
Stop mode
Operation mode
Stop mode
Preceding day Next daySetting day
Operation mode
Stop mode
The DAY OFF setting can only be set one time. The DAY OFF setting is cancelled automatically after the set day has passed.
3. TEMPERATURE SET BACK TIMER
The SET BACK timer only changes the set temperature for 7 days, it cannot be used to start or stop air conditioner operation.
The SET BACK timer can be set to operate up to two times per day but only one temperature setting can be used.
During the COOL/DRY mode, the air conditioner will operate at a minimum of 64°F(18°C) even if the SET BACK temperature is set to 62°F(17°C) or lower.
Case of SET BACK timer on the Cooling operation. ( Setting temperature :72°F(22°C), SET BACK temperature :80°F(26°C))
SET BACK setting
Operation temperature
*1
Operation temperature
*1: During the SET BACK function,
the setting temperature is changed.
80°F(26°C)
72°F(22°C)
80°F(26°C)
76°F(24°C)
72°F(22°C)
ON OFF OFFON
Chenge the setting temperature: 72°F(22°C) 76°F(24°C)
01-11
10. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the following values. The compressor frequency, the temperatures detected by the discharge temperature sensor and the outdoor temperature sensor.
The pulse range of the electronic expansion valve control is between 50 to 480 pulses.
At the time of supplying the power to the outdoor unit, the initialization of the electronic expansion valve is operated (1000 pulses are input to the closing direction).
11. TEST OPERATION CONTROL
With Wired Remote Controller
Under the condition where the air conditioner stops, press the MASTER CONTROL button and the FAN CONTROL button simultaneously for 5 seconds or more, and the test operation control mode will appear. During test running, " " will display on the remote controller display. Set the test operation mode, and the compressor will continue to run regardless of whatever the room temperature sensor detects. The test operation mode is released if 60 minutes have passed after setting up the test operation.
12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
The compressor won't enter operation status for 3 minutes after the compressor is stopped, even if any operation is given.
13. 4-WAY VALVE EXTENSION SELECT
At the time when the air conditioner is switched from the cooling mode to heating mode, the compressor is stopped, and the 4-way valve is switched in 3 minutes later after the compressor stopped.
14. AUTO RESTART
When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically resumed with the memorized operation contents. When the power is interrupted and recovered during timer operation, timer operation is canceled, but only setting time is memorized.
[Operation contents memorized when the power is interrupted]
Operation mode Set temperature
Set air flow
Timer mode and timer time Air flow Direction
Swing
Thermistor detected position
01-12
15. PUMP DOWN ( Refrigerant collecting operation )
Perform the following procedures to collect the refrigerant when moving the indoor unit or the outdoor unit.
When the product is stopped:
1. Press the PUMP DOWN switch (SW2) on the outdoor unit. (The LED on the outdoor unit circuit board flickers every 1second.)
2. The pump down operation (cooling operation) begins right away. After operation starts, close the 3-way valve (liquid).
3. After 2-3minutes, operation stops. Close the 3-way valve (gas) within 1minute after operations stops.
4. The LED will go out 3minutes after it stops. Disconnect the power supply after confirming that the LED has gone out.
When the product is operating:
1. Press the PUMP DOWN switch (SW2) on the outdoor unit. The LED on the outdoor unit circuit board flickers every 1second, and operation stops. At this point, recovery has not been completed, so do not close the 2 and 3-way valves.
2. The pump down operation (cooling operation) begins after 3minutes. Close the 3-way valve (liquid) after operation starts.
3. After 2-3minutes, operation stops. Close the 3-way valve (gas) within 1minute after operations stops.
4. The LED will go out 3minutes after it stops. Disconnect the power supply after confirming that the LED has gone out.
16. COMPRESSOR PREHEATING
When the outdoor heat exchanger temperature is lower than Operation temperature (Refer to Table 8) and the heating operation has (By heating the compressor, warm air is quickly discharged when operation is started.) When operation was started, and when the outdoor temperature rises to Release temperature or greater, preheating
(Table 8 : Preheating Operation / Release Temperature)
been stopped for 3 hours, power is applied to the compressor and the compressor is heated.
is over.
Before 24 hour After 24 hour
Operation temperature
Release temperature
Operation temperature
Release temperature
AUU18RCLX AUU24RCLX AUU36RCLX
37.4°F (3°C)
44.6°F (7°C)
32°F (0°C)
39.2°F (4°C)
AUU42RCLX
17. DEFROST OPERATION CONTROL
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor detects the temperature lower than the values shown in Table 9.
(Table 9 : Condition of starting Defrost Operation)
Compressor integrating operation :45min and over
Less than 6 min. *1
or 10min. *2
Above 20min. Select 10min.
After 6 min. *1
or 10min. *2
°F(-8°C) *3
17.6 14
°F (-10°C) *4
AUU18RCLX AUU24RCLX AUU36RCLX AUU42RCLX
Compressor integrating operation :Less than 45min.
Does not operate
*1. It means contiguous operation time. *2. Compressor stop time: Below 20min. Select 6min.
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table 10.
(Table 10 : Defrost Release Condition)
Release Condition
AUU18RCLX
AUU24RCLX
AUU36RCLX
AUU42RCLX
Outdoor heat exchanger temperature sensor value is higher than 53.6°F(12°C) or Compressor operation time has passed 15 minutes.
01-13
Outdoor temp. ­Outdoor heat exchanger temp.
21.6 degF (12
Outdoor heat exchanger temp.
degC)
-4
°F (-20°C)
*3. Outdoor temp. > 30.2°F (-1°C) *4. Outdoor temp. < 30.2°F (-1°C)
=
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time and outdoor heat exchanger temperature as follows.
Heating operation start : Compressor ON
(Not defrosted for 6 or 10 minutes)
Compressor integrating operation: 45 minutes and over
Outdoor temp. > 30.2°F
Outdoor heat exchanger temperarure: Below 17.6°F (-8°C)
=
(-1°C)
Defrost start
AUU18/ 24/ 36RCLX
Outdoor temp. < 30.2°F
(-1°C)
Outdoor heat exchanger temperarure: Below 14°F (-10°C)
Outdoor temp. > 30.2°F
Outdoor heat exchanger temperarure: Below 17.6°F (-8°C)
=
(-1°C)
Outdoor temp ­Outdoor heat exchanger temperature: Above 21.6 degF(12degC)
AUU42RCLX
Compressor integrating operation: 45 minutes and over
Outdoor temp. < 30.2 F
(-1°C)
Outdoor heat exchanger temperarure: Below 14°F (-10°C)
Outdoor heat exchanger temperarure: Below - 4°F (-20°C)
Defrost start
Defrost Indicator: [Operation lamp] 9 sec ON / 1 sec OFF
3 sec later Compressor OFF
3 sec later Outdoor fan motor OFF 28 sec later 4-way valve OFF 34 sec later compressor ON
Outdoor heat exchanger temperature: Over 53.6°F(12°C)
Compressor ON time: Over 15 minutes
(Frequency : 92 Hz)
or
Defrost Indicator: [Operation lamp] 9 sec ON / 1 sec OFF
Compressor : 30 Hz Outdoor fan motor OFF 4-way valve OFF Compressor ON (Frequency : 92 Hz)
Defrost end
01-14
18. DRAIN PUMP OPERATION
During Cooling / Dry operation
1. When the compressor starts, the drain pump starts simultaneously.
2. The drain pump operates continuously for 3 minutes after the compressor is turned off.
3. When the compressor stops by the "Indoor heat exchanger de-icing function", the drain pump is turned off in 1 hour after the compressor stops.
4.When the water level in the drain pan rises up and then the float switch functions: The compressor, indoor and outdoor fan motor operation are stopped.
1
2
Drain pump operates continuously for 3 minutes after the float switch is turned off. (Almost condensing water may be drained)
5. When the float switch turns ON continuously for 3 min., "FAILURE INDICATION" operates.
6. When the float switch turns OFF within 3 min., the unit starts cooling operation.
During Heating / Fan / Stop operation
1.When the water level in the drain pan rises up and then the float switch functions: Drain pump operates continuously for 3 minutes after the float switch is turned off.
1
(Almost condensing water may be drained)
2. When the float switch turns ON continuously for 3 min., "FAILURE INDICATION" operates.
19. ENERGY SAVE FUNCTION
1. During Cooling / Dry operation:
The thermostat temperature setting increases by 1.8 degF (1 degC) as soon as the ENERGY SAVE button is pressed, and then increases by 1.8 degF (1 degC) after 1 hour later. Afterwards, energy consumption is saved by continuing to cool or dry at a thermostat temperature of 3.6 degF (2 degC) higher than setting temperature.
ENERGY SAVE ON
1hour.
1.8 degF (1 degC)
3.6 degF(2degC)
Setting temperature
2. During Heating operation:
The thermostat temperature setting decreases by 1.8 degF (1 degC) as soon as the ENERGY SAVE button is pressed, and then decreases by another 1.8 degF (1 degC) every 30 minutes. Afterwards, energy consumption is saved by continuing to heat at a thermostat temperature of 7.2 degF (4 degC) lower than setting temperature.
ENERGY SAVE ON
1.8degF (1degC)
30min.
1 hour.
1 hour 30 min.
3.6degF (2degC)
5.4degF (3degC)
7.2degF (4degC)
Setting temperature
01-15
20. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVER RISE PREVENTION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature.
When the discharge temperature becomes higher than Temperature ,the compressor frequency is decreased 10 Hz, and it continues to decrease the frequency for 10 Hz every 120 seconds until
the temperature becomes lower than Temperature . When the discharge temperature becomes lower than Temperature ,the control of the compressor frequency is released.
When the discharge temperature becomes higher than Temperature ,the compressor stops. When the discharge temperature becomes lower than Temperature ,the compressor operates.
(Table 11 : Discharge Temperature Over Rise Prevention Control / Release Temperature)
Temperature Temperature Temperature Temperature
AUU18RCLX AUU24RCLX AUU36RCLX AUU42RCLX
221°F (105°C) 212°F (100°C) 239°F(115°C) 176°F(80°C)
2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds the current limit value that was set up with the outdoor temperature. The compressor frequency returns to the designated frequency of the indoor unit at the time when the frequency becomes lower than the release value.
(Table 12 : Current Release Operation Value / Release Value)
[ Heating ]
AUU18RCLX
T0 > 68°F (20°C)
=
T0 < 68°F (20°C)
T0: Outdoor temperature
AUU24RCLX
T0 > 68°F (20°C)
=
T0 < 68°F (20°C)
T0: Outdoor temperature
780 rpm 400 rpm 250 rpm 220, 200 rpm
10.0A / 9.5A
12.0A / 11.5A
900, 780 rpm 400 rpm 250 rpm 220, 200 rpm
10.0A / 9.5A
12.0A / 11.5A
Outdoor unit fan speed
10.0A / 9.5A 8.0A / 7.5A 6.0A / 5.5A
Outdoor unit fan speed
10.0A / 9.5A 8.0A / 7.5A 6.0A / 5.5A
AUU36RCLX
T0 > 53.6°F (12°C)
=
53.6°F > T0 > 41°F
(12°C) (5°C)
T0 < 41°F (5°C)
T0: Outdoor temperature
=
Outdoor unit fan speed
780 rpm900 rpm 400 rpm 250 rpm 220 ,200 rpm
15.0A / 14.5A 15.0A / 14.5A 13.0A / 12.5A 10.0A / 9.5A 8.0A / 7.5A
18.0A / 17.5A
18.0A / 17.5A 18.0A / 17.5A 18.0A / 17.5A 18.0A / 17.5A
01-16
AUU42RCLX
Upper fan
Lower fan
T0 > 53.6°F (12°C)
=
T0 < 53.6°F (12°C)
T0: Outdoor temperature
[ Cooling ]
AUU18RCLX
T0 > 113°F (45°C)
= 113°F > T0 > 77°F
(45°C) (25°C)
77°F > T0 > 66.2°F
(25°C) (19°C)
66.2°F > T0 > 55.4°F
(19°C) (13°C)
55.4°F > T0 > 44.6°F
(13°C) (7°C)
44.6°F > T0 > 32°F
(7°C) (0°C)
T0 < 32°F (0°C)
T0: Outdoor temperature
=
=
=
=
=
Outdoor unit fan speed
900 ,850 ,780 ,350 rpm 200 rpm 170 rpm 150 rpm
850 ,780 ,750 ,350 rpm 200 rpm 170 rpm 150 rpm
20.0A / 19.5A
20.0A / 19.5A 20.0A / 19.5A 20.0A / 19.5A 20.0A / 19.5A
Outdoor unit fan speed
780 rpm 400 rpm 250 rpm 220, 200 rpm
8.0A / 7.5A 8.0A / 7.5A 5.0A / 4.5A 4.0A / 3.5A
10.0A / 9.5A
12.0A / 11.5A 12.0A / 11.5A
15.0A / 14.5A 12.0A / 11.5A 12.0A / 11.5A
7.0A / 6.5A
8.0A / 7.5A
8.5A / 8.0A
9.0A / 8.5A
5.0A / 4.5A
6.5A / 6.0A
7.5A / 7.0A
AUU24RCLX
T0 > 113°F (45°C)
= 113°F > T0 > 100.4°F
(45°C) (38°C)
100.4°F > T0 > 77°F
(38°C) (25°C)
77°F > T0 > 66.2°F
(25°C) (19°C)
66.2°F > T0 > 55.4°F
(19°C) (13°C)
55.4°F > T0 > 44.6°F
(13°C) (7°C)
44.6°F > T0 > 32°F
(7°C) (0°C)
T0 < 32°F (0°C)
T0: Outdoor temperature
=
=
=
=
=
=
Outdoor unit fan speed
900 ,850 rpm 780 rpm 400 rpm 250 rpm 220, 200 rpm
8.0A / 7.5A 8.0A / 7.5A 8.0A / 7.5A 5.0A / 4.5A 4.0A / 3.5A
10.0A / 9.5A 10.0A / 9.5A
12.0A / 11.5A
12.0A / 11.5A 12.0A / 11.5A
7.0A / 6.5A
8.0A / 7.5A
8.5A / 8.0A
9.0A / 8.5A
5.0A / 4.5A
6.5A / 6.0A
7.5A / 7.0A
01-17
AUU36RCLX
T0 > 113°F (45°C)
= 113°F > T0 > 100.4°F
(45°C) (38°C)
100.4°F > T0 > 66.2°F
(38°C) (19°C)
66.2°F > T0 > 55.4°F
(19°C) (13°C)
55.4°F > T0 > 44.6°F
(13°C) (7°C)
44.6°F > T0 > 32°F
(7°C) (0°C)
=
=
=
=
=
T0 < 32°F (0°C)
T0: Outdoor temperature
Outdoor unit fan speed
900 ,850 rpm 780 rpm 400 rpm 250 rpm 220, 200 rpm
10.0A / 9.5A 10.0A / 9.5A 10.0A / 9.5A 7.0A / 6.5A 5.5A / 5.0A
14.0A / 13.5A
14.0A / 13.5A
18.0A / 17.5A
15.0A / 14.5A 15.0A / 14.5A
7.0A / 6.5A
12.0A / 11.5A
9.5A / 9.0A
AUU42RCLX
Upper fan
Lower fan
T0 > 113°F (45°C)
= 113°F > T0 > 87.8°F
(45°C) (31°C)
87.8°F > T0 > 77°F
(31°C) (25°C)
77°F > T0 > 66.2°F
(25°C) (19°C)
66.2°F > T0 > 55.4°F
(19°C) (13°C)
=
=
=
=
T0 < 55.4°F (13°C)
T0: Outdoor temperature
Outdoor unit fan speed
850 rpm 780 rpm 350 rpm 400 rpm 350, 300 rpm
750 rpm 780 rpm 350 rpm 0 rpm 0 rpm
12.0A / 11.5A 12.0A / 11.5A 12.0A / 11.5A 12.0A / 11.5A 12.0A / 11.5A
20.0A / 19.5A 20.0A / 19.5A
18.0A / 17.5A
18.0A / 17.5A
20.0A / 19.5A
15.0A / 14.5A
18.0A / 17.5A
01-18
3. ANTI-FREEZING CONTROL (Cooling mode)
The compressor frequency decreases on cooling mode when the indoor heat exchanger temperature sensor detects the temperature lower than 37.4°F(3°C). Then, the anti-freezing control is released when it becomes higher than 42.8°F(6°C).
(Fig 10 : Anti-freezing Protection Operation / Release Temperature)
Indoor heat exchanger temperature
The compressor frequency is
37.4°F (3°C)
42.8°F (6°C)
53.6°F (12°C)
decreased 10Hz every 120seconds.
Hold
Compressor OFF : Hold Compressor ON : Release of protection
Release of protection
When the compressor frequency becomes lower than minimum frequency, the compressor operates at minimum frequency. If the indoor heat exchanger temperature sensor detects the temperature lower than
37.4°F(3°C) after 2minutes upon operating the compressor at minimum frequency,
the compressor stops.
4. COOLING PRESSURE OVER RISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to
158.9°F (70.5°C) or greater,
the compressor is stopped and error display is indicated.
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the detection value of the indoor heat exchanger temperature sensor.
(Fig 11 : Heating Overload Protection Control)
Indoor heat exchange temperature
Compressor is OFF
145.4°F (63°C)
129.2°F (54°C)
122°F
(50°C)
The compressor frequency is decreased 10Hz every 60seconds.
Hold
Compressor OFF :
Release of protection
Compressor ON :
The compressor frequency is increased 10Hz every 60seconds.
01-19
CASSETTE type
INVERTER
R410A
2 . TROUBLE SHOOTING
2. TROUBLESHOOTING
2-1 ERROR DISPLAY
2-1-1 WIRED REMOTE CONTROLLER DISPLAY
1. SELF - DIAGNOSIS
When the error indication "E:EE" is displayed, inspection of the air conditioning system is necessary. Please consult authoilzed servise personnel.
Run [Self-Diagnosis] if [E:EE] flashes on the clock display of the remote controller.
Display
SUMOTUWETH FR
SA
SUMOTUWETH FR
Ex. Self-diagnosis
CLOCK ADJUST
SET BACK
DELETE SET
DAY
DAY OFF
ENERGY
SAVE
CLOCK ADJUST
SET BACK
DAY OFF
DELETE SET
DAY
SET
ENERGY
SAVE
THERMO SENSOR
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons and simultaneously for 5 seconds or more to start the self-diagnosis.
3. Press the SET TEMPERATURE buttons and simultaneously for 5 seconds or more or there is no key input for 20 seconds to stop the self-diagnosis.
Error code
Error contents
Communication error (indoor unit remote control)
Communication error (Serial reverse transfer error)
Room temperature sensor open
Room temperature sensor short-circuited
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor short-circuited
Outdoor heat exchanger temperature sensor error
Water drain abnormal
Outdoor temperature sensor error
Outdoor discharge pipe temperature sensor error
Indoor EEPROM abnormal (Model No.)
Indoor fan motor abnormal
Outdoor communication signal error (Forward transfer signal error)
Compressor temperature sensor error
Pressure switch error
IPM error
CT error
Active filter module (AFM) error
Compressor rotor location cannot detect (permanent stop)
Outdoor unit fan motor error
Trouble shooting
1 2
3
4
5 6 7 8
9 10 11 12 13 14 15
16 17 18
Error code
SA
02-01
2. ERROR CODE HISTORY DISPLAY
Up to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons , and the START/STOP button simultaneously for 5 seconds or more to start the self-diagnosis.
DAY
SUMOTUWETH FR
SA
3. Press the START/STOP button.
Error code
Error history number
DAY
SUMOTUWETH FR
SA
4. Press the SET TEMPERATURE button to select the error history number.
Lower
DAY
Raise
01234 567
FEdcbA98
ı
ı
5. Press the SET TEMPERATURE buttons , and START/STOP button simultaneously for 5 seconds or more or there is no key input for 20 seconds to stop the display.
02-02
2-1-2 OUTDOOR UNIT DISPLAY
1. ERROR DISPLAY
Error contents
Outdoor communication signal error (Forward transfer signal error)
Outdoor discharge pipe temperature sensor error
Outdoor heat exchanger temperature sensor error
Outdoor temperature sensor error
Compressor temperature sensor error
Heat sink temperature sensor error
Pressure switch abnormal
IPM error
Compressor rotor location cannot detect
Compressor Start-up error
Outdoor unit fan motor error (upper fan)
Outdoor unit fan motor error (lower fan)
LED Flashing
Pattern
1timeflash
2 times blink
3 times blink
4 times blink
7 times blink
8 times blink
9 times blink
12 times blink
13 times blink
14 times blink
15 times blink
16 times blink
2. ERROR DISPLAY METHOD
Outdoor LED Blink (1 to 16 times) 0.5sec ON / 0.5sec OFF blinking
0.5sec 0.5sec 2sec
ON
Display priority
1
2 3 4 5 6 7 8
9
10 11
12
Trouble shooting
11
8
5
7 12 19 13 14 17 20
18
OFF
3. NORMAL OPERATION DISPLAY
Operation LED Blinking Pattern Normal operation Continuously lighting Protected operation Pump down operation
5sec ON / 1sec OFF 1sec ON / 1sec OFF
02-03
2-2 TROUBLE SHOOTING WITH ERROR CODE
Trouble shooting 1
INDOOR UNIT Error Method:
Communication Error (Indoor unit Remote control)
Detective Actuators:
Indoor unit controller PCB circuit Wired Remote Control
Indicate or Display:
Indoor Unit : No LED
Outdoor Unit : No indication
ERROR CODE : E : 00
Detective details:
When the indoor unit cannot receive the signal from Wired Remote more than 10seconds after power ON, or the indoor unit cannot receive the signal more than 1minute during normal operation.
Forecast of Cause:
1. Terminal connection abnormal 2. Wired Remote Control failure 3. Controller PCB failure
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Check the connection of terminal between remote control and Indoor unit, and check if there is a disconnection of the cable.
OKOK
Check Point 2 : Check Remote Control and Controller PCB
Check Voltage at CN17 of Controller PCB. (Power supply to Remote Control)
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control >> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
Upon correcting the removed connector or mis-wiring, reset the power.
02-04
Trouble shooting 2
OUTDOOR UNIT Error Method:
Communication Error (Serial Reverse Transfer Error)
Indicate or Display:Indicate or Display:
Indoor Unit : No LED Outdoor Unit : No indication
ERROR CODE : E : 01
Detective Actuators:
Detective details:
Outdoor Unit Main PCB Circuit Active Filter Module
Forecast of Cause:
1. Connection failure 2. External cause 3. Main PCB failure 4. Active Filter Module failure
Check Point 1-1 : Reset the power and operate
Does Error indication show again?
YESYES
Check Point 2 : Check Connection
Check any loose or removed connection line of Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check connection between Outdoor Unit Main PCB and Filter PCB. (If there is loose connector or open cable)
When the indoor unit cannot receive the serial signal from Outdoor unit more than 10seconds.
NO
Check Point 1-2:
Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
OK
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC208 - 230V appears at Outdoor Unit Terminal L - N.
OK
Check Point 4 : Check Serial Signal (Reverse Transfer Signal)
Check Serial Signal (Reverse Transfer Signal)
>> Check if Indicated value swings between AC70V and AC130V at Outdoor Unit Terminal 1 - 3.
>> If it is abnormal, Check Active Filter Module. (PARTS INFORMATION 3)
>>If Active Filter Module is abnormal, replace it.
>>If Active Filter Module is normal, replace Main PCB.
WHITE
BLACK
RED
WHITE
BLACK
N
L
3
2
1
+
-
02-05
Trouble shooting 3 INDOOR UNIT Error Method:
INDOOR UNIT
Room Temperature Sensor Error
Indicate or Display:
Indoor Unit : No LED Outdoor Unit : No indication
ERROR CODE : E : 02 / 03
Detective Actuators:
Indoor Unit Controller PCB Circuit Room Temperature Thermistor
Detective details:
When Room Temperature Thermistor open or short-circuit is detected at power ON.
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 :Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
Temperature
32°F (0°C)
104°F (40°C)
41°F (5°C)
113°F (45°C)
50°F (10°C)
122°F (50°C)
59°F (15°C)
68°F (20°C)
77°F (25°C)
10.012.515.820.225.933.6Resistance Value (k )
86°F (30°C)
8.04
95°F (35°C)
6.51
3.594.355.30Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 :Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
THERMISTOR (PIPE TEMP.)
THERMISTOR
GRAY
GRAY
BLACK
BLACK
(ROOM TEMP.)
12 12 12 12
CN7 CN8
If the voltage does not appear, replace Controller PCB.
02-06
Loading...
+ 67 hidden pages