Fujitsu AOU12RL2, AOU09RL2, ASU12RL2 User Manual

SPLIT TYPE ROOM AIR CONDITIONER
WALL MOUNTED
INVERTER
SERVICE
INSTRUCTION
Models Indoor unit Outdoor unit
ASU09RL2 ASU12RL2
type
AOU09RL2 AOU12RL2
CONTENTS
1. DESCRIPTION OF EACH CONTROL OPERATION
1. COOLING OPERATION................................................................................................
2. HEATING OPERATION.................................................................................................
3. DRY OPERATION.........................................................................................................
4. AUTO CHANGEOVER OPERATION............................................................................
5. INDOOR FAN CONTROL..............................................................................................
6. OUTDOOR FAN CONTROL..........................................................................................
7. LOUVER CONTROL.....................................................................................................
8. COMPRESSOR CONTROL..........................................................................................
9. TIMER OPERATION CONTROL...................................................................................
10. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST ).................................
11. FOUR-WAY VALVE EXTENSION SELECT................................................................
12. AUTO RESTART.........................................................................................................
13. MANUAL AUTO OPERATION ( Indoor unit body operation ).....................................
14. FORCED COOLING OPERATION..............................................................................
15. COMPRESSOR PREHEATING..................................................................................
16. ECONOMY OPERATION............................................................................................
17. POWERFUL OPERATION.......................................................................................... 01-12
01-01
01-02
01-02
01-03
01-04
01-06
01-07
01-08
01-09
01-11
01-11
01-11
01-11
01-12
01-12
01-12
18. DEFROST OPERATION CONTROL........................................................................... 01-13
19. OFF DEFROST OPERATION CONTROL...................................................................
20. VARIOUS PROTECTIONS.......................................................................................... 01-16
2. TROUBLE SHOOTING
2-1 ERROR DISPLAY.......................................................................................................
2-2 TROUBLE SHOOTING WITH ERROR CODE............................................................
2-3 TROUBLE SHOOTING WITH NO ERROR CODE.....................................................
2-4 SERVICE PARTS INFORMATION.............................................................................. 02-26
01-15
02-01
02-02
02-21
3. APPENDING DATA
3-1 FUNCTION SETTING.................................................................................................
3-1-1 INDOOR UNIT....................................................................................................
3-1-2 Procedures to change the Function Setting for wireless RC..............................
3-2 Thermistor Resistance Values.....................................................................................
3-2-1 INDOOR UNIT....................................................................................................
3-2-2 OUTDOOR UNIT................................................................................................
03-01
03-01
03-03
03-06
03-06
03-06
WALL MOUNTED type
INVERTER
R410A
1 . DESCRIPTION OF EACH CONTROL OPERATION
1. COOLING OPERATION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor.
* If the room temperature is 2°C(4°F) higher than a set temperature, the compressor operation frequency will attain to maximum performance.
* If the room temperature is some degrees lower than a set temperature, the compressor will be stopped.
* When the room temperature is between +2°C(4°F) to -2.5°C(-5°F) of the setting temperature, the compressor frequency is controlled within the range shown in Table1. However, the maximum frequency is limited in the range shown in Fig.1 based on the indoor fan mode and the outdoor temperature.
( Table 1 : Compressor frequency range )
AOU09RL2 AOU12RL2
Minimum frequency
18rps
Maximum frequency
57rps 80rps
Maximum frequency
80rps 96rps
When the compressor operates for 30 minutes continuously at over the maximum frequency , the maximum frequency is changed from Maximum Frequency to Maximum Frequency.
( Fig.1 : Outdoor temperature zone )
When the outdoor
When the outdoor temperature drops
34°C
A zone
temperature rises
(93°F)
30°C
B zone
(86°F)
19°C
C zone
(66°F)
10°C
D zone
(50°F)
0°C
E zone
36°C (97°F)
32°C (90°F)
21°C (70°F)
12°C (54°F)
2°C (36°F)
( Table 2 : Limit of maximum speed based on outdoor temperature )
Indoor fan mode
Hi
Me Lo Quiet
ASU09RL2
ASU12RL2
Outdoor temp. zone
A zone 80rps 49rps 42rps 32rps B zone 80rps 49rps 42rps 32rps C zone 80rps 49rps 42rps 32rps D zone 49rps 44rps 40rps 29rps E zone 49rps 44rps 40rps 29rps F zone 49rps 44rps 40rps 29rps
A zone 96rps 61rps 51rps 33rps B zone 96rps 61rps 51rps 33rps C zone 96rps 61rps 51rps 33rps D zone 73rps 57rps 45rps 33rps E zone 73rps 57rps 45rps 33rps F zone 73rps 57rps 45rps 33rps
(32°F)
F zone
01-01
2. HEATING OPERATION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor.
* If the room temperature is lower by 3°C (6°F) than a set temperature, the compressor operation frequency will attain to maximum performance.
* If the room temperature is some degrees higher than a set temperature, the compressor will be stopped.
* When the room temperature is between +2.5°C (+5°F) to -3°C (-6°F) of the setting temperature, the compressor frequency is controlled within the range shown in Table 3. However, the maximum frequency is limited shown in Table 4 based on the fan mode.
( Table 3 : Compressor frequency range )
Minimum frequency
AOU09RL2
AOU12RL2
18rps
( Table 4 : Limit of maximum speed based on outdoor temperature )
Indoor fan mode
Hi
AOU09RL2
AOU12RL2
Maximum frequency
80rps
120rps
Me Lo Quiet Auto
80rps
120rps
3. DRY OPERATION
The compressor frequency shall change according to the temperature, set temperature, and room temperature variation which the room temperature sensor of the indoor unit body has detected as shown in the Table 5. However, after the compressor is driven, the indoor unit shall run at operation frequency of (09 : 52 rps, 12 : 61 rps) for 60 seconds.
( Table 5 : Compressor frequency in Dry mode)
Operating frequency
AO09RL2
X zone
J zone
Y zone
30rps
28rps
0rps
AO12RL2
( Fig.2 : Compressor control based on room temperature )
When the room
When the room
temperature rises
temperature drops
Ts+0.5°C (Ts+1°F)
Ts -1.5°C (Ts-3°F)
X zone
J zone
X zone 33rps
J zone
Y zone
Ts+1.5°C (Ts+3°F)
Ts -0.5°C (Ts-1°F)
Operating frequency
25rps
0rps
Y zone
01-02
4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum mode from among the Heating, Cooling, Dry and Monitoring modes. During operation, the optimum mode is automatically switched in accordance with temperature changes. The temperature can be set between 18°C (64°F) and 30°C (88°F) in 1°C (2°F) steps.
(Fig. 3 : Operation flow chart in Auto changeover)
START
YES
YES
Room temp.
>Ts+2°C (4°F) ?
NO
or operation command other than
Room temp.
<Ts- 2°C(4°F) ?
HEATING OPERATION
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
auto changeover operation?
NO
YES
NO
YES
TS : Setting temperature
or operation command other than
COOLING OPERATION
Thermostat remains
in OFF state for 6 minutes or
longer?
NO
System stops
auto changeover operation?
YES
YES
NO
NO
01-03
5. INDOOR FAN CONTROL
1. Fan speed
( Table 6 : Indoor fan speed )
Operation mode Air flow mode
Heating
Cooling/ Fan
Dry
Powerful 1420
Hi 1360
Me+ 1290
Me 1120
Lo 900
Quiet 700
Cool air prevention 600
S-Lo 480
Powerful 1400
Hi 1320
Me 1120
Lo 840 860
Quiet 700
* Soft Quiet 600
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs. (Hi > Me, Me > Lo, Lo > Quiet, Quiet > Soft Quiet)
ASU09RL2
X zone: 700
J zone: 600
Speed (rpm)
ASU12RL2
1420 1360 1290 1120
900 700 600
480 1400 1320 1120
700
600
X zone: 700
J zone: 600
2. FAN OPERATION
The airflow can be switched in 5 steps such as Auto, Quiet, Lo, Me, Hi, while the indoor fan only runs. When fan mode is set at [Auto], it operates on [Me] fan Speed.
3. COOLING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Fig4. On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow of [Cool] operation modes Quiet, Lo, Me, Hi, as shown in Table 6.
( Fig.4 : Airflow change - over ( Cooling : Auto ) )
When the room
When the room temperature drops
TR-Ts > 2°C (4°F)
2°C (4°F) > TR-Ts > C (2°F)
1°C (2°F) > TR-Ts
=
Hi mode
Me mode
Lo mode
temperature rises
TR-Ts > 2.5°C (5°F)
=
2.5°C (5°F) > TR-Ts > 1.5°C (3°F)
1.5°C (3°F) > TR-Ts
=
TR : Room temperature Ts : Setting temperature
4. DRY OPERATION
Refer to the Table 6. During the dry mode operation, the fan speed setting can not be changed.
01-04
5. HEATING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Fig. 5 On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow of [Heat] operation modes Quiet, Lo, Me, High, as shown in Table 6.
( Fig.5 : Airflow change - over ( Heating : Auto ) )
When the room temperature rises
TR-Ts > -1°C (-2°F)
=
-1°C (-2°F) > TR-Ts > -2°C (-4°F)
=
Lo mode
Me mode
When the room temperature drops
TR-Ts > -1.5°C (-3°F)
=
-1.5°C (3°F) > TR-Ts > -2.5°C (-5°F)
TR : Room temperature Ts : Setting temperature
=
-2°C (-4°F) > TR-Ts
Me+ mode
-2.5°C (-5°F) > TR-Ts
6. COOL AIR PREVENTION CONTROL (Heating mode)
The maximum value of the indoor fan speed is set as shown in Fig.6 based on the detected temperature by the indoor heat-exchanger sensor on heating mode.
( Fig.6 : Cool air prevension control )
<Powerful operation>
When the Indoor heat exchanger temp. rises
42°C (108°F)
39°C (102°F)
37°C (99°F)
30°C (86°F)
<Normal operation>
When the Indoor heat exchanger temp. drops
* Hi or setting Fan mode
* Me+ or setting Fan mode
* Lo or setting Fan mode
Cool air prevention
S-Lo
* Lower speed is selected.
37°C (99°F)
34°C (93°F)
32°C (90°F)
28°C (82°F)
When the Indoor heat exchanger temp. rises
42°C (108°F)
39°C (102°F)
37°C (99°F)
30°C
(86°F)
When the Indoor heat exchanger temp. drops
Powerful
Hi
Lo
Cool air prevention
S-Lo
* Lower speed is selected.
37°C (99°F)
34°C (93°F)
32°C (90°F)
28°C (82°F)
7. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
Switch the airflow [Auto] at cooling mode, and the indoor fan motor will run as shown in Fig.7.
( Fig.7 : Indoor fan control )
Compressor
ON
OFF
Indoor fan Setting air flow
Indoor fan (as shown in Table 7)
S-Lo
OFF
10 30 60 180 60 180 60 10 30
( Table 7 : Indoor fan speed )
ASU09/12RL2
Dry
X zone J zone
700rpm 600rpm
Y zone
0 480rpm 700rpm
Cooling
(sec)
01-05
6. OUTDOOR FAN CONTROL
1. Outdoor Fan Motor
Following table shows the type of the outdoor fan motor. The control method is different between AC motor and DC motor.
( Table 8 : Type of Motor )
AC motor DC motor
AOU09RL2 AOU12RL2
2. Fan Speed
( Table 9 : Outdoor fan speed )
Zone
Y 730 / 650 / 470
AOU09RL2 900 / 650 / 470 730 / 470
AOU12RL2 900 / 760 / 680 / 470 760 / 470
Refer to Fig.8
Z F G Y Z F G
Cooling Heating
730 / 470 / 360
360 / 150
210 / 150 860 / 760 / 470 860 / 470 / 380
380 / 280 280 / 200
Dry
( Fig.8 : Outside air temperature zone selection )
Outside air temperature
21°C (70°F)
12°C (54°F)
2°C (36°F)
Y zone
Z zone
F zone
G zone
Outside air temperature
19°C (66°F)
10°C (50°F)
0°C (32°F)
*The outdoor fan speed mentioned adove depends on the compressor frequency. (When the compressor frequency increases, the outdoor fan speed also changes to the higher speed. When the compressor frequency decreases, the outdoor fan speed also changes to the lower speed.)
*After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed as table 10 without relating to the compressor frequency.
( Table 10 : Outdoor fan speed after the defrost )
AOU09RL2 AOU12RL2
900 rpm
01-06
7. LOUVER CONTROL
1. VERTICAL LOUVER CONTROL
(Function Range)
Each time the button is pressed, the air direction range will change as follow:
Types of Air flow Direction Setting:
, , , : During Cooling/Dry modes , , , : During Heating
The Remote Controller's display does not change.
Use the air direction adjustments within the ranges shown above. The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode Horizontal flow Heating mode Downward flow
If you set the angle to position ~ for more than 30 minutes in Cooling or Dry mode, they automatically return to position . In Cooling or Dry mode, if the angle is set to position ~ for many hours, condensation may be formed, and the drips may wet your property.
Fig.8 : Air Direction Range
1
2
3
4
5
6
7
2. ADJUST THE RIGHT-LEFT LOUVERS
Move the Right-Left louvers to adjust air flow in the direction you prefer.
Right-Left Louvers
Knob
Knob (2 places)
3. SWING OPERATION
To select Vertical Airflow Swing Operation
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Table10 : Swinging Range)
Range
Cooling / Dry mode Fan mode ( )
de
Heating Fa
mo
)
(
e
od
m
n
The SWING operation may stop temporarily when the air conditioner’s fan is not operating, or when operating at very low speeds.
To select Horizontal Airflow Swing Operation
(No function)
01-07
8. COMPRESSOR CONTROL
1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as shown in the Table 11.
(Table 11 : Compressor frequency range)
Cooling / Dry Heating
Minimum Maximum Minimum Maximum
AOU09RL2
AOU12RL2
18rps
2. OPEARTION FREQUENCY CONTROL AT NORMAL START UP
The compressor frequency soon after the start-up is controlled as shown in the Fig.9.
(Fig.9 : Compressor control at start-up)
Frequency Frequency Frequency Frequency Frequency Frequency
80rps 96rps
18rps 120rps
Time
6
Frequency
78rps
Time
6
(Frequency)
AOU09RL2
AOU12RL2
(Time)
AOU09RL2
AOU12RL2
Time
Frequency
56rps 67rps 75rps
56rps 74rps 87rps 97rps 108rps 119rps
Time
80sec 140sec 200sec
60sec 100sec 140sec 200sec 410sec350sec
Time Time Time
Frequency
Time Time Time
Frequency Frequency
78rps 78rps
380sec 440sec440sec
Time
Frequency
Time
3. LIMITATION OF COMPRESSOR FREQUENCY BY OUTDOOR TEMPERATURE
The minimum compressor frequency is limited by outdoor temperature as shown in the Table12.
(Table12 : Limitation of Compressor Frequency)
[ Cooling/ Dry ]
10°C (50°F) 14°C (59°F) 40°C (104°F)
Under Over Under Over Under Over
AOU09RL2
AOU12RL2
35rps 23rps
45rps 27rps
30rps-------
[ Heating ]
AOU09RL2
AOU12RL2
- 3°C (26°F) 7°C (45°F) 14°C (59°F) 40°C (104°F)
Under Over Under Over Under Over Under Over
34rps 22rps 27rps
36rps 27rps 27rps
30rps-------
01-08
9. TIMER OPEARTION CONTROL
9-1 WIRELESS REMOTE CONTROLLER
The Table 13 shows the available timer setting based on the product model.
( Table 13 : Timer Setting )
ON TIMER / OFF TIMER PROGRAM TIMER SLEEP TIMER
ASU09RL2 ASU12RL2
1. OPEARTION FREQUENCY RANGE
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
2. PROGRAM TIMER
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation mode
Stop mode
Set time Set time Set time Set time
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest to the clock's current timer setting. The order of operations is indicated by the arrow in the remote control unit's display.
SLEEP timer operation cannot be combined with ON timer operation.
Operation mode
Operation mode
Stop mode
Stop mode
01-09
3. SLEEP TIMER
If the sleep is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON.
In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 1°C (2°F). It increases the setting temperature another 1°C (2°F) after 1 hour. After that, the setting temperature is not changed and the operation is stopped at the time of timer setting.
Set temperature rises
( Ts : Set temperature )
+2°C (4°F) +1°C (2°F)
Ts
Stop of operation
Set
60min
In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 1°C (2°F). It decreases the setting temperature another 1°C (2°F) every 30 minutes. Upon lowering 4°C (8°F), the setting temperature is not changed and the operation stops at the time of timer setting.
Set temperature lowers
( Ts : Set temperature )
Ts
-1°C (-2°F)
-2°C (-4°F)
-3°C (-6°F)
-4°C (-8°F)
Stop of operation
Set
30min
30min
30min
01-10
10. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
The compressor won't enter operation status for 2 minutes and 20 seconds after the compressor is stopped, even if any operation is given.
11. FOUR-WAY VALVE EXTENSION SELECT
At the time when the air conditioner is switched from the cooling mode to heating mode, the compressor is stopped, and the four-way valve is switched in 2 minutes and 20 seconds later after the compressor stopped.
12. AUTO RESTART
When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically started with the memorized operation contents. When the power is interrupted and recovered during timer operation, since the timer operation time is shifted by the time the power was interrupted, an alarm is given by blinking (7 sec ON/2 sec OFF) the indoor unit body Timer lamp.
[ Operation contents memorized when the power is interrupted ]
Operation mode Set temperature Set air flow Timer mode and set time Set air flow Direction Swing ECONOMY operation
13. MANUAL AUTO OPERATION (Indoor unit body operation)
When the remote control is lost or battery power dissipated, this function will work without the remote control. When MANUAL AUTO button is set more than 3seconds and less than 10seconds, MANUAL AUTO OPERATION will be started as shown in Table14. To stop operation, press the MANUAL AUTO button for 3seconds.
(Table14 : MANUAL AUTO OPERATION)
Manual auto operation OPERATION MODE Auto changeover FAN CONT. MODE Auto TIMER MODE Continuous SETTING TEMP. 24°C (75°F) SETTING LOUVER Standard
SWING ECONOMY
OFF OFF
(No timer setting available)
Press and hold MANUAL AUTO button for 3 ~ 10seconds
01-11
14. FORCED COOLING OPERATION (TEST OPERATION)
When FORCED COOLING OPERATION is set, the operation is controlled as shown in Table15.
( Table15 : FORCED COOLING OPERATION )
Forced cooling operation OPERATION MODE FAN CONT. MODE TIMER MODE
SETTING TEMP. SETTING LOUVER
SWING ECONOMY
Cooling Hi
­Room Temp is not controlled Horizontal
(It is changed follow as setting of remote controller) OFF
-
Forced cooling operation is started when press MANUAL AUTO button for 10 seconds or more. During the forced cooling operation, it operates regardless of room temperature sensor. Operation lamp and Timer lamp blink at the same time during the forced cooling operation. They blink for 1 second ON and 1 second OFF on both Operation lamp and Timer lamp (same as test operation). Forced cooling operation is released after 60 minutes of starting operation or pressing MANUAL AUTO button
for 3 seconds or pressing START/STOP button on the remote controller.
15. COMPRESSOR PREHEATING
When the outdoor heat exchanger temperature is lower than 5°C and the all operation has been stopped for 30 minutes, power is applied to the compressor and the compressor is heated. (By heating the compressor, warm air is quickly discharged when operation is started.) When operation was started, and when the outdoor temperature rises to 7°C (44.6°F) or greater, preheating is ended.
16. ECONOMY OPERATION
The ECONOMY operation functions by pressing ECONOMY button on the remote controller. At the maximum output, ECONOMY Operation is approximately 70% of normal air conditioner operation for cooling and heating. The ECONOMY operation is almost the same operation as below settings.
( Table 16 )
Mode Cooling/ Dry
Heating
Target temperature Setting temp.+1°C (2°F) Setting temp.-1°C (-2°F)
17. POWERFUL OPERATION
The POWERFUL OPERATION functions by pressing POWERFUL button on the remote controller. The indoor unit & outdoor unit will operate at maximum power as shown in Table17.
(Table17)
Powerful operation
COMPRESSOR FREQUENCY Maximum
FAN CONT. MODE Powerful
SETTING LOUVER Cooling/ Dry : 3, Heating : 5
Release Condition is as follows. [Cooling / Dry]
- Room temperature < Setting temperature - 1.5°C (-3°F) or Operation time has passed 20 minutes. =
[Heating]
- Room temperature > Setting temperature +1.5°C (+3°F) or Operation time has passed 20 minutes.
=
01-12
18. DEFROST OPERATION CONTROL
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts as shown in the following Table 18.
(Table 18 : Condition of starting Defrost Operation)
Normal defrost
Less than 25 minutes More than 25 minutes
Compressor integrating operation time
Outdoor heat exchanger temp. < -17°C (1.4°F) (at outside air temp. > -10°C (14°F))
Outdoor heat exchanger temp. < Outside air temp.
- 7°C (-44.6°F) or Outdoor heat exchanger temp. < - 20°C (-13°F) (at outside air temp. < -10°C (14°F))
More than 213 minutes (For continuous operation)
Outdoor heat exchanger
temperature below -5°C (-10°F)
=
Integrating defrost
Does not operate
Compressor integrating operation time
More than 240 minutes (For continuous operation)
Outdoor heat exchanger
temperature below -3°C (-6°F)
If the compressor continuous operation time is less than 10 minutes, the OFF number of the compressor is counted. If any defrost operated, the compressor OFF count is cleared.
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table 19.
(Table 19 : Defrost Release Condition)
Release Condition
=
=
=
Less than 10 minutes ( For intermittent operation )
OFF count of the compressor
40 times
Outdoor heat exchanger temperature sensor value is higher than +16°C (60.8°F) or Compressor operation time has passed 15 minutes.
01-13
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature and outdoor heat exchanger temperature as follows.
Heating operation start : Compressor ON
(Not defrosted for 10 minutes)
Normal defrost
Outside air temp. > -10°C Outside air temp. < -10°C
Outdoor HEX temp. Below - 17°C(1.4°F)
=
Outdoor HEX temp.
- Outside air temp. Below - 7°C(-44.6°F) or Outdoor HEX temp. Below - 20°C(-4°F)
(14°F)(14°F)
Defrost start
Defrost Indicator: [Operation lamp] 7 sec ON / 2 sec OFF
Integrating defrost
Intermittent operation Continuous operation
Compressor OFF count : 40 times (Less than 10min.)
Compressor integrating operation: Over 240 min.
Outdoor heat exchanger temperature: Below - 3°C (26.6°F)
Compressor integrating operation: Over 213 min.
Outdoor heat exchanger temperature: Below - 5°C (23°F)
Outdoor fan : OFF Compressor speed : 0 rps 4-way valve : OFF Compressor speed : 90rps
Outdoor HEX temp.: Over 16°C (60.8°F)
or
Compressor ON time: Maximum 15 minutes
Defrost end
01-14