Thank you for purchasing our T-Link Communications Card OPC-G1-TL.
The communications card is used to connect our general-purpose inverter series FRENIC-MEGA to a T-Link
network. Mounting this communications card on your FRENIC-MEGA allows you to connect the FRENIC-MEGA
to a Fuji MICREX series of programmable logic controllers (T-Link module) and control it as a slave unit using
run and frequency commands, and accessing function codes.
This instruction manual does not contain inverter handling instructions. Read through this instruction manual in
conjunction with the FRENIC-MEGA Instruction Manual and be familiar with proper handling and operation of
this product. Improper handling might result in incorrect operation, a short life, or even a failure of this product.
Keep this manual in a safe place.
Related Publications
Listed below are the other materials related to the use of the T-Link communications card "OPC-G1-TL." Read
them in conjunction with this manual as necessary.
RS-485 Communication User's Manual
FRENIC-MEGA Instruction Manual
The materials are subject to change without notice. Be sure to obtain the latest editions for use.
Read through this instruction manual and be familiar with the T-Link communications card before
proceeding with installation, connections (wiring), operation, or maintenance and inspection.
Improper handling might result in incorrect operation, a short life, or even a failure of this product as
well as the motor.
Deliver this manual to the end user of this product. Keep this manual in a safe place until this product
is discarded.
Safety precautions
Read this manual thoroughly before proceeding with installation, connections (wiring), operation, or
maintenance and inspection. Ensure you have sound knowledge of the device and familiarize yourself with all
safety information and precautions before proceeding to operate the inverter.
Safety precautions are classified into the following two categories in this manual.
Failure to heed the information indicated by this symbol may lead to
dangerous conditions, possibly resulting in death or serious bodily
injuries.
Failure to heed the information indicated by this symbol may lead to
dangerous conditions, possibly resulting in minor or light bodily injuries
and/or substantial property damage.
Failure to heed the information contained under the CAUTION title can also result in serious consequences.
These safety precautions are of utmost importance and must be observed at all times.
1
Page 5
Installation and wiring
Before starting installation and wiring, turn OFF the power and wait at least five minutes for inverters
with a capacity of 22 kW or below, or at least ten minutes for inverters with a capacity of 30 kW or
above. Make sure that the LED monitor and charging lamp are turned OFF. Further, make sure,
using a multimeter or a similar instrument, that the DC link bus voltage between the terminals P(+)
and N(-) has dropped to the safe level (+25 VDC or below).
Qualified electricians should carry out wiring.
Otherwise, an electric shock could occur.
Do not use the product that is damaged or lacking parts.
Doing so could cause a fire, an accident, or injuries.
Prevent lint, paper fibers, sawdust, dust, metallic chips, or other foreign materials from getting into
the inverter and the communications card.
Otherwise, a fire or an accident might result.
Incorrect handling in installation/removal jobs could cause a failure.
A failure might result. Noise may be emitted from the inverter, motor and wires. Implement appropriate measure to prevent
the nearby sensors and devices from malfunctioning due to such noise.
Otherwise, an accident could occur.
Operation
Be sure to install the front cover before turning the inverter's power ON. Do not remove the cover
when the inverter power is ON.
Otherwise, an electric shock could occur.
Do not operate switches with wet hands.
Doing so could cause an electric shock.
If you configure the function codes wrongly or without completely understanding FRENIC-MEGA
Instruction Manual and the FRENIC-MEGA User's Manual, the motor may rotate with a torque or at a
speed not permitted for the machine. Confirm and adjust the setting of the function codes before
running the inverter.
Otherwise, an accident could occur.
Maintenance and inspection, and parts replacement
Before proceeding to the maintenance/inspection jobs, turn OFF the power and wait at least five
minutes for inverters with a capacity of 22 kW or below, or at least ten minutes for inverters with a
capacity of 30 kW or above. Make sure that the LED monitor and charging lamp are turned OFF.
Further, make sure, using a multimeter or a similar instrument, that the DC link bus voltage between
the terminals P(+) and N(-) has dropped to the safe level (+25 VDC or below).
Otherwise, an electric shock could occur.
Maintenance, inspection, and parts replacement should be made only by qualified persons.
Take off the watch, rings and other metallic objects before starting work.
Use insulated tools.
Otherwise, an electric shock or injuries could occur.
2
Page 6
Disposal
Treat the communications card as an industrial waste when disposing of it.
Otherwise injuries could occur.
Others
Never modify the communications card.
Doing so could cause an electric shock or injuries.
Icons
The following icons are used throughout this manual.
This icon indicates information which, if not heeded, can result in the product not operating to full
efficiency, as well as information concerning incorrect operations and settings which can result in
accidents.
This icon indicates information that can prove handy when performing certain settings or operations.
This icon indicates a reference to more detailed information.
Unpack the package and check the following:
(1) A communications card, two screws (M3 8), and the T-Link Communications Card Instruction Manual (this
document) are contained in the package.
(2) The communications card is not damaged during transportation--no defective parts, dents or warps.
(3) The model name "OPC-G1-TL" is printed on the communications card. (See Figure 2.1.)
If you suspect the product is not working properly or if you have any questions about your product, contact the
shop where you bought the product or your local Fuji branch office.
No terminating resistor comes with this communications card.
A pair of resistors with the following specifications must be used: 100 ohm, 1 watt
1.2 Applicable Inverters
The T-Link communications card is applicable to the following inverters and ROM version.
(The terminating resistors that come with the T-Link module of the MICREX series can be used.)
Table 1.1 Applicable Inverters and ROM Version
Series Inverter type Applicable motor rating ROM version
FRENIC-MEGA FRNG1 -All capacities 0500 or later
* The boxes replace alphanumeric letters depending on the nominal applied motor, enclosure, power supply voltage, etc.
To check the inverter's ROM version, use Menu #5 "Maintenance Information" on the keypad. (Refer to the
Inverter's ROM versionShows the inverter's ROM version as a 4-digit code.
5
Page 9
Chapter 2 NAMES AND FUNCTIONS
2.1 Parts Names
Figure 2.1 shows the names of the parts on the T-Link communications card.
Screw hole (left)
(Front) (Back)
Positioning
cutout
Model name
RSW1 RSW2
Station address switches
T-Link terminal
block (TB11)
Figure 2.1 Names of Parts on T-Link Communications Card
2.2 Station Address Switches (RSW1 and RSW2)
Release knob
Screw hole (right)
Connector CN1
The station address switches on the communications card are rotary ones (RSW1 and RSW2) that are used to
configure the station address of the communications card on a T-link. The setting range is from 00 to 99.
The station address switches should be accessed when the inverter power is OFF. Access with the
inverter power ON will result in a communications error.
RSW1: Upper digit (x10)
RSW2: Lower digit (x1)
Note 1: When two or more communications cards are used on the same T-Link network,
the same station address should not be double assigned.
Figure 2.2 Station Address Switches (RSW1 and RSW2)
2.3 T-Link Terminal Block (TB11)
Connect the T-Link communications cable to the T-Link terminal block.
For details about wiring, refer to Chapter 4 "WIRING AND CABLING."
6
Page 10
Chapter 3 INSTALLATION AND REMOVAL OF THE COMMUNICATIONS CARD
Before starting installation and wiring, turn OFF the power and wait at least five minutes for inverters with a
capacity of 22 kW or below, or at least ten minutes for inverters with a capacity of 30 kW or above. Make
sure that the LED monitor and charging lamp are turned OFF. Further, make sure, using a multimeter or a
similar instrument, that the DC link bus voltage between the terminals P(+) and N(-) has dropped to the safe
level (+25 VDC or below).
Otherwise, an electric shock could occur.
Do not use the product that is damaged or lacking parts.
Doing so could cause a fire, an accident, or injuries.
Prevent lint, paper fibers, sawdust, dust, metallic chips, or other foreign materials from getting into
the inverter and the communications card.
Otherwise, a fire or an accident might result.
Incorrect handling in installation/removal jobs could cause a failure.
A failure might result.
3.1 Installing the Communications Card
Before mounting the communications card, perform the wiring for the main circuit terminals and control
circuit terminals.
(1) Remove the front cover from the inverter and expose the control printed circuit board (control PCB). As
shown in Figure 3.1, the communications card can be connected to the A-port only, out of three option
connection ports (A-, B-, and C-ports) on the control PCB.
To remove the front cover, refer to the FRENIC-MEGA Instruction Manual, Chapter 2, Section 2.3.
For inverters with a capacity of 30 kW or above, open also the keypad enclosure.
(2) Insert connector CN1 on the back of the communications card (Figure 1.1) into the A-port (CN4) on the
inverter's control PCB. Then secure the communications card with the two screws that come with the card.
(Figure 3.3)
Check that the positioning cutout (shown in Figure 2.1) is fitted on the tab ( in Figure 3.2) and
connector CN1 is fully inserted ( in Figure 3.2). Figure 3.3 shows the communications card
correctly mounted.
(3) Perform wiring to the communications card.
For details, refer to Chapter 4 "WIRING AND
CABLING."
(4) Put the front cover back into place.
To put back the front cover, refer to the FRENIC-MEGA
Instruction Manual, Chapter 2, Section 2.3.
For inverters with a capacity of 30 kW or above, close
also the keypad enclosure.
Figure 3.1 In the case of 0.4 kW
7
Page 11
Tab
Fit the positioning cutout of the communications
card over the tab on the inverter to determine
the mounting position.
Insert connector CN1 on the communications
card into the corresponding port on the
inverter's control PCB.
Note: Be sure to follow the order of and .
Inserting CN1 first may lead to insufficient
insertion, resulting in a contact failure.
Figure 3.2 Mounting the Communications Card
(Release knob)
Figure 3.3 Mounting Completed
3.2 Removing the Communications Card
Remove the two screws that secure the communications card and pull the release knob (shown above) to take
the communications card out of the inverter.
8
Page 12
Chapter 4 WIRING AND CABLING
Before starting installation and wiring, turn OFF the power and wait at least five minutes for inverters with
a capacity of 22 kW or below, or at least ten minutes for inverters with a capacity of 30 kW or above.
Make sure that the LED monitor and charging lamp are turned OFF. Further, make sure, using a
multimeter or a similar instrument, that the DC link bus voltage between the terminals P(+) and N(-) has
dropped to the safe level (+25 VDC or below).
Qualified electricians should carry out wiring.
Otherwise, an electric shock could occur.
In general, the covers of the control signal wires are not specifically designed to withstand a high voltage
(i.e., reinforced insulation is not applied). Therefore, if a control signal wire comes into direct contact with
a live conductor of the main circuit, the insulation of the cover might break down, which would expose the
signal wire to a high voltage of the main circuit. Make sure that the control signal wires will not come into
contact with live conductors of the main circuit.
Failure to observe this precaution could cause an electric shock or an accident.
Noise may be emitted from the inverter, motor and wires. Take appropriate measures to prevent the nearby
sensors and devices from malfunctioning due to such noise.
An accident could occur.
4.1 Basic Connection Diagram
FRENIC-MEGA
L1/R
L2/S
L3/T
OPC-G1-TL
T-Link
terminal block
Station address switches
T1
T2
SD
U
V
W
Motor
G
Terminating
resistor
Terminating
resistor
T1
MICREX series
T2
processor
T1
T2
module
Station
address
Station
address
SD
T1
T2
SD
SD
G
G
Figure 4.1 Basic Connection Diagram
9
Page 13
4.2 Wiring for T-Link Terminal Block (TB11)
(1) Use either of the following cables as a T-Link communications cable.
- Twisted pair cable CPEV-SB 0.9 dia. x 1 pair (manufactured by Furukawa Electric)
- Twisted pair cable KPEV-SB 0.5 mm2 x 1 pair (manufactured by Furukawa Electric)
(2) Wiring to T-Link terminal block (TB11)
The pin assignment on the T-Link terminal block, the terminal functions, and the terminal specifications are
shown in Figure 4.2, Tables 4.1 and 4.2, respectively.
T1 T2SD
Figure 4.2 Pin Assignment on T-Link Terminal Block
Table 4.1 Functions of T-Link Terminals
Symbol Name Functions
T1
T-Link terminals Terminals for connecting the T-Link communications line
T2
SD Shield Terminal for connecting the cable shield
Table 4.2 Terminal Specifications
Item Specifications
Terminal screw size M3
Tightening torque 0.5 N m
(3) Terminating resistor
T-Link requires a terminating resistor to be mounted externally on each end of the trunk line. Check that the
trunk line is terminated on both ends; if it is not terminated, mount a terminating resistor(s) on the missing
end(s).
No terminating resistor comes with this communications card.
A pair of resistors with the following specifications must be used: 100 ohm, 1 watt
(The terminating resistors that come with the T-Link module of the MICREX series can be used.)
10
Page 14
4.3 Wiring to Inverter
Route the T-Link communications cable as far from the wiring of the main circuit as possible.
For inverters with a capacity of 22 kW or below
Otherwise electric noise may cause malfunctions.
Pass the T-Link communications cable between the control circuit terminal block and the front cover.
In the case of 0.4 kW
For inverters with a capacity of 30 kW or above
In the case of 75 kW
Figure 4.3 Examples of Wiring
11
Page 15
Chapter 5 CONFIGURING INVERTER'S FUNCTION CODES FOR T-Link
COMMUNICATION
5.1 Inverter's Function Codes
Before running the inverter for practical operation, configure the inverter's function codes listed in Table 5.1. It is
recommended to configure them before starting T-Link communication, since a T-Link network break could
occur immediately after the start of communication.
Table 5.1 Inverter's Function Code Settings Required for T-Link Communication
Function
codes
o27
o28
o30
y98
Select error processing for
T-Link network breaks
Set the operation timer to be
used in error processing for
network breaks
Specify T-link communications
format
Select run/frequency
command sources
Description
Changing o30 data may cause an option error (T-Link communications error) . If it occurs, reset
the MICREX.
5.2 Error Processing for T-Link Network Breaks
Factory
default
setting
0 0 to 15
0.0 s0.0 to 60.0 s
Select one of the following:
0: G11 standard format
0
2: G9 compatible format
1, 3 to 255: (Not allowed)
Select from the following choices:
Frequency
y98
command source
0
0
1
2
3
Function code data Remarks
For details about
function codes o27
and o28, see Table
5.2.
For details about
communications
format, refer to
Chapter 7.
Inverter's function codes o27 and o28 define error processing that the inverter should perform when it detects a
T-Link network break, as listed in Table 5.2.
If no run or frequency command via the communications link is enabled, the inverter does not issue ,
performing no error processing.
Table 5.2 Error Processing for T-Link Network Breaks, Defined by Function Codes o27 and o28
o27 o28
0, 4 to 9 Invalid Immediately coast to a stop and trip with .
1 0.0 to 60.0 s After the time specified by o28, coast to a stop and trip with .
2 0.0 to 60.0 s
3,
13 to 15
10 Invalid Immediately decelerate to a stop. After the stop, trip with . The inverter's
11 0.0 to 60.0 s
12 0.0 to 60.0 s
Invalid Continue to run, ignoring the error (No trip).
If the communications link is restored within the time specified
by o28, ignore the communications error. If a timeout occurs,
coast to a stop and trip with .
After the time specified by o28, decelerate to a stop. After the
stop, trip with .
If the communications link is restored within the time specified
by o28, ignore the communications error. If a timeout occurs,
decelerate to a stop and trip with .
after Detection of T-Link Network Break
Error Processing
Remarks
function code F08
specifies the
deceleration time.
Same as above.
Same as above.
12
Page 16
Chapter 6 ESTABLISHING A T-Link COMMUNICATIONS LINK
6.1 Starting Procedure
After confirming that wiring to the T-Link has been completed, establish a T-Link communications link between
the MICREX and the inverter and start T-Link communication, using the procedure given in this chapter.
T-Link communication enables the MICREX to issue run commands and monitor the inverter's operation.
For details, refer to Chapter 7 "COMMUNICATIONS FORMAT."
(1) Configure the MICREX.
- Set a station address of the T-Link communications card (e.g., 00) using the MICREX loader. The relay
area should not be double assigned by any other T-Link station address.
- Allocate read and write areas on the T-Link communications card. Each of those areas is 4 words in
length, regardless of the format.
- In the I/O group setting, register the T-Link communications card as both input and output devices.
For details about the relay area to be occupied, refer to Chapter 6, Section 6.2 "I/O Relay Area
Occupied."
For details about configuring MICREX, refer to the MICREX user's manual.
(2) Configure the station address switches (RSW1 and RSW2) on the communications card. (Refer to Section
2.2.)
- Before accessing the station address switches, make sure that both the inverter power and the T-Link
communications card power are turned OFF.
- Set the station address switches to the station address that matches the one specified by the loader.
(3) Turn the inverter power ON and configure the inverter's function codes.
- Select the communications format with the inverter's function code o30.
- Configure the inverter's function codes o27, o28, and y98, if necessary.
For details about the communications format, refer to Chapter 7 "COMMUNICATIONS FORMAT."
(4) Power ON the MICREX and send a T-Link connection request to the inverter.
For details about how to send a connection request from the MICREX, refer to the MICREX user's
manual.
(5) Start I/O data exchange.
In response to the connection request from the MICREX, the T-Link communications link will be established
if the MICREX and the T-Link communications card have been properly configured and wiring between
them is correct.
The MICREX exchanges data with the inverter in accordance with the communications format selected,
making it possible to control the inverter.
When the error LED on the MICREX T-Link module is ON, no T-Link communication is possible.
13
Page 17
6.2 I/O Relay Area Occupied
T-Link communication uses a consecutive eight-word area per inverter in the I/O relay area as shown below.
The two-digit address (** in WB00**) should be configured with rotary switches RSW1 and RSW2 on the
communications card.
WB0000
WB00**
(Inverter MICREX) data
RSW1
RSW2
(MICREX Inverter) data
WB00**+7
WB0099
6.3 Address Configuration Example
In the case of G11 standard format, 4 W + 4 W
Station address 50: RSW1 = 5, RSW2 = 0
WB0050
WB0051
WB0057
Output frequency monitor (Motor speed monitor)
(4 words)
(4 words)
Running status monitor
Selecting data
I/O relay area
For details about communications format, refer to Chapter 7 "COMMUNICATIONS FORMAT."
14
Page 18
Chapter 7 COMMUNICATIONS FORMAT
7.1 About Communications Format
The T-Link communications card supports two types of communications formats: G11 standard format and G9
compatible format.
Use of the G11 standard format is recommended since the G9 compatible format may not be supported in the
future.
Table 7.1 Details of Function Code o31
Data for o30 Function Occupied Words
0 G11 standard format 4 W + 4 W
2 G9 compatible format 4 W + 4 W
Other than the above *
(1, 3 to 255)
* Do not set the o30 data to any values other than "0" and "2" with the T-Link
communications card connected.
Disable --
7.2 Data Allocation Addresses in I/O Relay Area
(1) G11 Standard Format
(MSB)(LSB)
WB00**
+0
+1
+2
+3
+4
+5
+6
+7
Polling communications #
Selecting communication #
(2) G9 Compatible Format
Output frequency monitor (Motor speed monitor)
Frequency command (Motor speed command)
Running status monitor
Polling data
Run command, Di, RESET input
Selecting data
Empty (All fixed at 0)
Polling communication #
Inverter
MICREX
MICREX
Inverter
(MSB)(LSB)
WB00**
+0
+1
+2
+3
+4
+5
+6
+7
Running status monitor, Extended data read
Output frequency
Read/write function code monitor
Read function code data monitor
Run command, Extended data written
Frequency command
Read/write function code
Written function code data
Inverter
MICREX
MICREX
Inverter
15
Page 19
7.3 Descriptions of Communications Formats
(1) G11 standard format: o30 = 0 (factory default)
The G11 standard format is common to the G11 and FRENIC-MEGA series of inverters. Note that there are
some differences in the function codes between those series of inverters; therefore, be sure to confirm
function codes that are used for reading/writing before replacing the G11 series with the FRENIC-MEGA
series.
For details about the different function codes, refer to the FRENIC-MEGA User's Manual, App. G
"Replacement Information."
MICREX Inverter
Word 0 1 2 3 4 5 6 7 8 9 A B CDE F
4 RST XR XF - - X9X8X7X6X5X4X3X2X1REV FWD
5 Frequency command (100% = 20000 p.u.)
6 Selecting communication number Polling communication number
7 Selecting data
FWD: Run forward command
REV: Run reverse command
X1 to X9: General-purpose input (whose functions are specified by E01 to E09)
XF: General-purpose input (whose function is specified by E98)
XR: General-purpose input (whose function is specified by E99)
RST: Reset signal (Turning RST from "1" to "0" releases an inverter alarm.)
(This data should be "0" in ordinary operation.)
Frequency command: Frequency command to be specified, assuming that the maximum frequency (e.g.,
F03) is 20000 (=100%)
Frequency com mand
Frequency com mand [Hz]
Maxim um frequency (F03) [Hz]
Polling communication number: Can be read from FRENIC-MEGA's major function codes
Selecting communication number: Can be written into FRENIC-MEGA's major function codes
Selecting data: Can be written into the function code specified by the "Selecting
communication number"
For details about the communication number, refer to Table 7.2. The inverter's function code data is subject to the data format of each function code. For details about
the data format, refer to the RS-485 Communication User's Manual, Chapter 5, Section 5.2 "Data
Formats."
The RST signal received via the communications card cannot be checked in "I/O Checking" on
the keypad.
20000
16
Page 20
Inverter MICREX
Word 0 1 2 3 4 5 6 7 8 9 A B C D E F
0 BUSY ERR 1 R/L ALM DEC ACCILVLTLNUV BRKINT EXT REV FWD
1 Output frequency monitor (100% = 20000 p.u.)
2 Polling communication number Empty data
3 Polling data
(Each item is ON when its data is "1.")
FWD: Running forward
REV: Running reverse
EXT: During DC braking or pre-exciting
INT: Inverter shutdown
BR: Braking
NUV: DC link bus voltage established
TL: Torque limiting
VL: Output voltage limiting
IL: Output current limiting
ACC: During acceleration
DEC: During deceleration
ALM: Alarm relay output
R/L: Link enabled/disabled (When either one of run and frequency commands can be specified via the
communications card, the link becomes enabled and the R/L is turned ON.)
ERR: Selecting or polling error *
BUSY: Selecting or polling
Output frequency monitor: Output frequency under monitoring, assuming that the maximum
frequency (e.g., F03) is 20000 (=100%)
Polling communication number: Value specified by the polling communication number
Polling data: Data specified by the polling communication number
* If the ERR bit is "1" during polling or selecting, an error has occurred so that reading or writing of a function code is
not completed. Check your specification conditions such as: whether a communication number having no function
code assignment (EMPTY in Table 7.2) is specified or a function code having the attribute of "writing not allowed
during running" is specified when the inverter is running. Then try reading/writing again.
17
Page 21
The table below lists the correspondence between the communication numbers (COM#) and
FRENIC-MEGA function codes in the G11 standard format.
Accessing any of the EMPTY COM numbers other than 0 will cause a communications error.
Table 7.2 Correspondence Between the COM# and Function Codes in the G11 Standard Format
This format has been designed to minimize software modification required in the MICREX for replacement
of the G11 series with the FRENIC-MEGA series. Note that this format is not fully compatible. For
restrictions, see the table below.
Replacing the G9 series with the FRENIC-MEGA series, using the G9 compatible format
Function Compatibility Description
Running status monitor,
Extended data read
Yes No extended data read is used.
Output frequency Yes
In the M code group, only M01 (Output current
Function code data read No
monitor), M02 (Output voltage monitor), and M03
(Calculated torque value monitor) are available
(full-compatible).
Run command,
Extended data written
Yes No extended data written is used.
Frequency command Yes
Function code data written No
MICREX Inverter
Word 0 1 2 3 4 5 6 7 8 9 A B CD E F
- - - - - - - X5X4X3X2X1RDT BX REV FWD
4
5 Frequency command (Hz)
6 Function code number Function code group Request code
7 Selecting data
In G9 format, X6 to X9 are not available.
FWD: Run forward command
REV: Run reverse command
X1 to X5: General-purpose input (to be specified by E01 to E05)
BX: Coast to a stop command
RST: Reset signal (Changing the data from "1" to "0" clears the inverter alarm) *1
Frequency command: Speed command value [Hz] (in increments of 0.01 Hz) *2
Function code number: Specifies the function code number from/into which data is read/written. (BCD)
Function code group: Specifies the function code group to be read or written
Request code: Depending on the specified data (see the table below), reading/writing data
from/into the inverter is enabled or disabled.
Table 7.3 Request Codes
BCD
Request Code (binary)Processing
000b Disable
001b Write
010b Read
BCD: Switches the frequency command format between binary and BCD. (1: BCD, 0: Binary)
Selecting data: Specifies the data to be written into the selecting function code
*1 This data should be "0" in ordinary operation.
*2 If specified in BCD, the data is expressed in increments of 0.1 Hz.
Example) If BCD data is "0": 50.00 Hz = 1368 hex.
If BCD data is "1": 50.00 Hz = 0500 hex.
The RST signal received via the communications card cannot be checked in "I/O Checking" on
the keypad.
Function code number Function code group Response code BCD
Polling data
Y1 to Y5: General-purpose output (to be specified by E20 to E24)
30: General-purpose output (to be specified by E27)
R/L: Link enabled or disabled (When either one of run and frequency commands can be entered via the
communications card, the link is regarded as enabled and the R/L is turned ON.)
Output frequency: Output frequency in Hz (in increments of 0.01 Hz) *
Function code number: Numeral part of an inverter's function code (BCD)
Function code group: Group code of a function code listed in Table 7.5
Response code: Returns a response related to the requested function code
Table 7.4 Response Codes
Response Codes (binary)Status
000b Accessed to a nonexistent function code
010b - Writing or reading normally completed
- No request
011b Writing or reading in progress (BUSY)
100b Selecting data out of range error
110b Parameter protection error
BCD: Indicates whether the motor output frequency is monitored in BCD format
(1: BCD, 0: binary)
Polling data: Data part of a function code read
* If monitored in BCD, the data is expressed in increments of 0.1 Hz.
Example) If BCD data is "0": 50.00 Hz = 1368 hex.
If BCD data is "1": 50.00 Hz = 0500 hex.
20
Page 24
Configuring inverter's function codes in G9 compatible format
Configure a function code data by specifying the function code number in binary-coded decimal and the code
group in binary (listed in Table 7.5).
Function code group (see Table 7.5)
Function code number (BCD)
Table 7.5 Function Code Group
Group Group Code Function Code GroupGroup CodeFunction Code
F * 0 0000b Fundamental function H 6 0110bHigh performance function
O 1 0001b Option function A 7 0111bMotor 2 parameters
M 2 0010b Monitored data J 8 1000bApplication function 1
E 3 0011b Terminal function y 9 1001bLink function
C 4 0100b Control function d 10 1010bApplication function 2
P 5 0101b Motor 1 parameters
Example: For E27, E 0011 (binary)
27 0010 0111 (binary)
"0010 0111 0011"
* Function code response F00 (0000 0000 0000b) may mean "function code disabled" or "waiting for response."
M codes in G9 compatible format
Accessed in the G9 compatible format, each of the following M codes serves as a special function code to
read the corresponding value. (Writing is not allowed.)
Table 7.6 M Codes
Function
Code
M01 Output current monitor 0.00 to 2000 A
M02 Output voltage monitor 0 to 500 V
M03 Calculated torque value monitor 0 to 255 %
Name Range Unit Data Format
[2]
[1]
[1]
Given below are the data formats for M codes in the G9 compatible format.
Data format [1]
(MSB) (LSB)
0 1 2 3 4 5 6 7 8 9 A B C D E F
Function data x 1 16-bit data
Data format [2]
(MSB) (LSB)
0 1 2 3 4 5 6 7 8 9 A B C D E F
Current data (BCD) Exponent part
Actual Current Significand Exponent Part
0.00 to 9.99 001 to 999 0
10.0 to 99.9 100 to 999 1
100 to 999 100 to 999 2
1000 to 2000 100 to 200 3
21
Page 25
7.4 Example of Communication Data
This section shows an example of communication data in the G11 standard format (factory default). The
example assumes that the maximum frequency (F03) is 60 Hz.
(1) Example of operation pattern
Figure 7.1 shows an example of an inverter's operation pattern. To drive the inverter according to this
operation pattern, the communication data should be as shown in item (2) below.
Commands: Run forward command, Speed command 1800 r/min (= 2710h)
WB00** +4 00 01
+5 27 10
+6 00 00 +7 00 00
Response: Running forward during acceleration, Output speed increasing
WB00** +0 32 21
+1 ** **
+2 00 00 +3 00 00
22
Page 26
Commands: Run forward command, Speed command 1800 r/min (= 2710h)
WB00** +4 00 01
+5 27 10
+6 00 00 +7 00 00
Response: Running forward, Arrived at the reference speed
WB00** +0 30 21
+1 27 10
+2 00 00 +3 00 00
Commands: Run command OFF, Speed command 1800 r/min (= 2710h)
WB00** +4 00 00
+5 27 10
+6 00 00 +7 00 00
Response: Running forward during deceleration, Output speed decreasing
WB00** +0 34 21
+1 ** **
+2 00 00 +3 00 00
Commands: Run command OFF, Change the speed command to 300 r/min (1667 p.u. = 0683h)
WB00** +4 00 00
+5 06 83
+6 00 00 +7 00 00
Response: Being stopped, Inverter ready
WB00** +0 30 28
+1 00 00
+2 00 00 +3 00 00
23
Page 27
Chapter 8 LIST OF INVERTER ALARM CODES
Through T-Link, the MICREX can monitor the information on alarms that have occurred in the inverter. Their
alarm codes are stored in the inverter's communication-dedicated function codes M16 to M19 (latest, last, 2nd
last, and 3rd last alarm codes), as listed below.
(COM port 1)
11 (0BH) Input phase loss 44 (2CH) Overload of motor 3
14 (0EH) Fuse blown 45 (2DH) Overload of motor 4
16 (10H) Charger circuit fault 46 (2EH) Output phase loss
Problem A communications error occurred between the T-Link communications card and the inverter.
Possible Causes What to Check and Suggested Measures
(1) There was a problem with the
connection between the
communications card and the
Check whether the connector on the communications card is properly
engaged with that on the inverter.
Reload the communications card into the inverter.
inverter.
(2) Strong electrical noise. Check whether appropriate noise control measures have been
implemented (e.g. correct grounding and routing of signal wires,
communications cables, and main circuit wires).
Implement noise control measures.
(3) More than one communications
card of the same type is
mounted.
(4) More than one communications
card of different types is
mounted.
Check the type of the communications cards mounted on the inverter.
Mount only one communications card of the same type on the inverter.
Check whether any other type of the communications card (e.g.,
DeviceNet) is mounted.
Mount only one communications card on the inverter.
If the inverter does not display o codes (option functions) even if the communications card is mounted,
check whether the connector on the communications card is properly engaged with that on the inverter
although does not appear.
Option error (T-Link communications error) ()
Problem An error detected by the communications card.
Possible Causes What to Check and Suggested Measures
(1) Mismatch of T-Link station
address.
Check whether the station address specified on the T-Link
communications card matches with the one specified at the MICREX.
Configure the station address of the T-Link communications card
properly using the station address switches (RSW1 and RSW2).
(2) T-Link data area double
assigned.
Check whether the T-Link station address is double assigned by any
other device on the same T-Link network.
Review the T-Link station address settings.
For details, refer to the MICREX user's manual.
(3) Incorrect wiring of T-Link
communications cable
Check the cable specifications and wiring.
Replace the cable if broken and correct the wiring.
(4) Strong electrical noise. Check whether appropriate noise control measures have been
implemented (e.g. correct grounding and routing of signal wires,
communications cables, and main circuit wires).
Implement noise control measures.
(5) Improper terminating
resistors.
(6) Error that has occurred in any
other option card.
Check whether the terminating resistors are mounted as specified.
Mount the terminating resistors as specified.
Find out the option card causing an error.
Refer to the instruction manual of the option card that has caused
.
25
Page 29
Chapter 10 SPECIFICATIONS
10.1 Operating Environment
Table 10.1 lists the environmental requirements for the inverter equipped with the communications card. For the
items not covered in this section, the specifications of the inverter itself apply.
Table 10.1 Environmental Requirements
Item Specifications
Site location Indoors
Surrounding temperature Refer to the FRENIC-MEGA Instruction Manual, Chapter 2.
Relative humidity 5 to 95% (No condensation)
Atmosphere
Altitude 1,000 m max.
Atmospheric pressure 86 to 106 kPa
Vibration Refer to the FRENIC-MEGA Instruction Manual, Chapter 2.
(Note) Do not install the inverter in an environment where it may be exposed to lint, cotton waste or moist dust or dirt which will
clog the heat sink of the inverter. If the inverter is to be used in such an environment, install it in a dustproof panel of your
system.
The inverter must not be exposed to dust, direct sunlight, corrosive gases, flammable
gases, oil mist, vapor or water drops.
Pollution degree 2 (IEC60664-1) (Note)
The atmosphere can contain a small amount of salt. (0.01 mg/cm2 or less per year)
The inverter must not be subjected to sudden changes in temperature that will
cause condensation to form.
26
Page 30
10.2 T-Link Specifications
Table 10.2 lists the T-Link specifications for this communications card. For the items not covered in this section,
the specifications of the T-Link apply.
Table 10.2 T-Link Specifications
ItemSpecifications
Name T-Link communications card
Model nameOPC-G1-TL
Applicable inverters FRENIC-MEGA series of inverters, ROM Ver. 0500 or later
Applicable controllerMICREX series
Transmission specifications T-Link slave I/O transmission
Number of words occupied
in transmission
T-Link communications
cable
Number of units connectable Max. 12 units
Transmission speed 500 kbps
Run command Run forward and reverse commands, Alarm reset command,
Reference frequency,
output frequency
monitor
Running status monitor The following signals can be monitored:
Function codes Able to read and write data from/to major function codes.
Recovery from T-Link
network breaks
Checking alarms
Protective functions
Total 8 words
(MICREX Inverter: 4 W, Inverter MICREX: + 4 W)
Furukawa Electric twisted pair cable CPEV-SB 0.9 dia. x 1 pair or
Furukawa Electric twisted pair cable KPEV-SB 0.5 mm2 x 1 pair
X1 to X9, XF, and XR commands
(G11 standard format)
Run forward and reverse commands, Alarm reset command,
X1 to X5, and BX commands
(G9 compatible format)
Reference frequency 20000 Maximum frequency (F03) 16-bit data
(G11 standard format)
Running forward, Running reverse, During DC braking, Inverter shutdown, Braking,
DC link bus voltage established, Torque limiting, Output voltage limiting, Output
current limiting, During acceleration, During deceleration, Alarm relay output, Link
enabled/disabled, Write/read error from the T-Link, and Data writing in progress
(G11 standard format)
The following signals can be monitored:
General-purpose output signals on terminals Y1 to Y5 (such as inverter running,
frequency arrival signal, and frequency detected), Alarm relay output, Link
enabled/disabled
(G9 compatible format)
For function codes that can be read/written by the T-Link communications card, refer
to Chapter 7, Table 7.2 "Correspondence Between the COM# and Function Codes in
the G11 standard format."
(G11 standard format)
Able to read and write data from/to the following function codes:
F, o, E, C, P, H, A, J, y, and d codes. Also, it can read the output current, output
voltage, and calculated torque value of the M codes.
(G9 compatible format)
o27 defines error processing that the inverter should perform when it detects a T-Link
network break.
If the inverter causes an alarm due to the error processing selected, removing the
alarm factor and issuing a Reset command resumes the inverter operation.
Able to check the alarm contents using M codes. (G11 standard format t only)
(A communications error between the communications card and the inverter)
: Option error (T-Link communications error)
(A communications error between the MICREX and the communications card)
27
Page 31
28
Page 32
T-Link Communications Card
"OPC-G1-TL"
Instruction Manual
First Edition, July 2008
Fourth Edition, April 2011
Fuji Electric Co., Ltd.
The purpose of this manual is to provide accurate information in the handling, setting up and operating of the
T-Link Communications Card for the FRENIC-MEGA series of inverters. Please feel free to send your comments
regarding any errors or omissions you may have found, or any suggestions you may have for generally
improving the manual.
In no event will Fuji Electric Co., Ltd. be liable for any direct or indirect damages resulting from the application of
the information in this manual.
Page 33
URL http://www.fujielectric.co.jp/
Fuji Electric Co., Ltd.
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo, 141-0032, Japan
Phone: +81 3 5435 7283 Fax: +81 3 5435 7425
URL http://www.fujielectric.com/
2011-04 (D11c/G08) 1CM
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.