Specifications:
Inverter Side:
Digital Inputs: 4 DC inputs (24VDC)
Input : 24VDC, 12mA per channel
Parameters 4DC Inputs (24VDC)
Input Impedance: 2.88K ohm
Min. ON voltage: 18VDC
Max. OFF voltage:1.2VDC
Turn ON time: 10msec max
Turn OFF time: 5msec max
Digital Outputs: 8 Relay outputs
Output: 24VDC, 20mA per channel
General:
Operating Temp.: 0 to 60°C
Storage Temp.: -20 to 80°C
Operating Humidity:10% to 90% (Non condensing)
Dimensions and Panel Mounting:
145mm
2. Din rail installation:
a. Mount the DIN rail to your mounting surface.
b. Align the unit to the mounting plate and snap the
unit into place.
c. Hook the top slot of the mounting plate over the
DIN rail.
d. While pressing the unit against the rail, snap the
unit into place.
BACK VIEW
e-Frontrunners
OPC-ALL-115VPART#:
S/N.: CIWWYYXXXXX
Made in India
User Side:
Digital Inputs: 8 AC inputs (115V)
Input: 115VAC, 8mA per channel
92mm
Parameters 8 AC Inputs (115V)
Input Impedance: 6.5K ohm
Min. ON voltage: 96VAC
Max. OFF voltage: 36VAC
Turn ON time: 15msec max
Turn OFF time: 10msec max
Digital Outputs: 4 Relay outputs.
Output: 250VAC, 5A / 24VDC, 5A per
Channel
This unit can be mounted on DIN rail slider as well as
can be rest on mounting plate:
1. For mounting plate installation:
A) Drill hole into your mounting surface (#36 drill
BACK VIEW
e-Frontrunners
OPC-ALL-115VPART#:
S/N.: CIWWYYXXXXX
Made in India
recommended).
B) Align the unit to the mounting plate.
C) Fasten the mounting plate to your surface with
four screws.
Quick Start Manual Doc. No.: ; Ver.: 1.00QS-OPC-ALL-115-1010 Renu Electronics Pvt. Ltd. Pub.: 10/2010
Inverter Side:User Side:
I1
I2
I3
I4
I5
I6
I7
I8
N
COM1
NO1
L
O
A
D
COM2
COM3
NO2
L
O
A
D
COM4
NO3
NO4
L
L
O
O
A
A
D
D
115 VAC
Input:
User can connect 8 AC Inputs (115VAC) as input to
respective relay coil.
I1 to I8 stands for Input 1 to 8 (Phase) where as N
stands for Neutral that is common for all Inputs
Each Relay can be trigger by applying minimum
96VAC.
Input (115VAC) Status LED Output
RED
I1 L5 X1
I2 L6 X2
I3 L7 X3
I4 L8 X4
I5 L9 X5
I6 L10 X6
I7 L11 X7
I8 L12 X8
A red LED indication is provided for each Relay
status.
Note: Status LED's will glow only if load is
connected to X1-X8, as LED's are connected in
series with load at each AC relay output side.
Y3
Y4
Y2Y1+24V
24VDC
INVERTER OUTPUT
+
-
COM
COM
INVERTER SIDE
-
24VDC
+
COM
COM
X8
X7
X4 X3
X5
X6
INVERTER INPUT
X1
X2
I/P1I/P3I/P5I/P7
I/P2I/P4I/P6I/P8
Input:
Inverter outputs can be applied to 4 DC Inputs
(24VDC) as input to respective relay coil.
Y1 to Y4 stands for Input 1 to 4 (Negative) where as
+24V is common for all four Inputs.
Each Relay can be trigger by applying minimum
18VDC.
A green LED indication is provided for each Relay
status.
Input (24VDC) Status LED Output
GREEN
Y1 L1 COM1: NO1
Y2 L2 COM2: NO2
Y3 L3 COM3: NO3
Y4 L4 COM4: NO4
Output:
X1 to X8 are Inputs for Inverter, which has +24VDC
as Inputs for Inverter side. Where as three COM
terminals are provides as a common at Inverter side.
Technical Support:
For Technical support please contact factory along
with the unit serial number and revision number
written on the address sticker of the unit.
Also provide information of the application used.
MANUAL REVISIONS:
Output:
User can connect load to 4 Relay outputs.
This 4 Relay can be driven by Inverter output
(24VDC).
Quick Start Manual
ELECTRONICS PVT. LTD.
Doc. No.: ; Ver.: 1.00QS-OPC-ALL-115V-1010
Rev. No. Doc. No. Date Description
1.00 QS-OPC-ALL-115-1010 08/10/10 First Draft
Renu Electronics Pvt. Ltd.
Pub.: 10/2010