Fuji M-UPS050AD2B, M-UPS075AD2B, M-UPS100AD2B User Manual

USERS MANUAL
-
HG5687
Uninterruptible Power Supply GX 200 Series Model
M-UPS075AD2B M-UPS100AD2B
M-UPS050AD2B
For Safe Use
About handling of this manual
This manual describes important information for using this product safely. Please read this manual carefully before using this product. Use this product, after reading and understanding especially "Caution about Safety" and "Caution for Use" in this manual well. Furthermore, this manual should be retained for future reference.
About Use which Requires High Safety
This product is designed and manufactured for the general use, such as general office use and personal use, and is not designed and manufactured for uses (control of nuclear reactions at the nuclear facilities, aircraft flight control, air traffic control, mass transport control, medical life support systems, and missile launch control in weapon systems, etc.) that require a high degree of safety, and can cause death or serious injury if the required safety is not maintained. Do not use this product without carrying out measures to ensure the required safety for such a use. If using this product for such a use, consult with our sales representatives.
About Prevention of Radio Interference
Important
This product is class A information technology equipment based on the standard of Voluntary Control Council for Interference by Information Technology Equipment (VCCI). Using this product in a residential area may cause radio interference. In this case, the user may be requested to take an appropriate measure.
About Prevention of Harmonic Current Interference
M-UPS050AD2B conforms to the Guideline of harmonic restraint measures for general-purpose UPS.
M-UPS075AD2B and M-UPS100AD2B conform to IEC61000-3-12.
Do not reproduce or reprint this manual without notice.
All Rights Reserved, Copyright cFuji Electric Co., Ltd. 2011
Introduction
An uninterruptible power supply is a device for supplying stable electric power to OA devices, FA devices, and computer devices. This manual describes installation, running, daily management, troubleshooting, and maintenance of an uninterruptible power supply. Use an uninterruptible power supply correctly in accordance with this manual. In this manual, an uninterruptible power supply (this product) is described as UPS for short.
Content and organization of this manual
The organization of this manual is as follows:
Caution about Safety and Caution for Use
The cautions about safety are described. If you use the UPS, be sure to read this section.
1 Unpacking
The cautions about taking out the UPS from a box are described.
2 Outline
The name of each part and the operation mode of the UPS are described.
3 Installation
Installation of the UPS and connection of the cable are described.
4 Running
The methods of run and stop of the UPS are described.
5 Inspection
The cautions about daily inspection and rolling blackouts are described.
6 Troubleshooting
Troubleshooting is described.
7 Maintenance
Replacement of battery and cooling fan and method of storage of the UPS are described.
8 Appendix
Rated specification and the cautions in UL standard are described.
Due to the purpose to use, the chapters which should be referred to especially are as follows.
For installation personnel Caution about Safety, Caution for Use,
Chapters 1, 2, 3, and 4
For users Caution about Safety, Caution for Use,
Chapters 2, 4, 5, and 6
For maintenance personnel Caution about Safety, Caution for Use,
Chapters 2, 4, 5, and 7
i
Introduction
About warning display
In this manual, the following warning displays are described so that user or the people around the UPS do not suffer damage to the body and property.
Warning
Caution
Important
"Warning" indicates that death or serious injury may result, if the UPS is not used correctly.
"Caution" indicates that slight or moderate injury may result or the UPS or users property may be damaged, if the UPS is not used correctly.
"Important" indicates caution about the use of the UPS.
About marks in this manual
Marks in this manual have the following meanings:
The state of the UPS is described.
About symbols of LED
The states of LED are indicated by the following symbols:
Have a look if necessary. How to deal with, the reference place, etc. are described.
: Lighting
: Blinking
: Not lighting
Attention
Information in this manual is subject to change without notice.
ii
Caution about Safety
List of important warnings
The important warnings described in this manual are as follows.
Warning
Electric shock Do not remove the cover of the UPS.
"Warning" indicates that death or serious injury may result, if the UPS is not used correctly.
Since there are some portions with high voltage in the inside of the UPS, there is fear of an electric shock.
Caution
Electric shock Injury
Electric shock Perform the battery and cooling fan replacement by
The UPS should be connected to ground. (more than
Electric shock Failure
When inspecting or maintaining the connection device (a
"Caution" indicates that slight or moderate injury may result or the UPS or users property may be damaged, if the UPS is not used correctly.
Put neither a stick nor a finger into the cooling fan or the vent hole.
There is fear of an electric shock or an injury.
maintenance personnel.
There is fear of an electric shock.
class D grounding) When connecting to an input power supply, connect the grounding wire to the ground terminal.
There is fear of an electric shock.
When connecting the UPS to an input power supply, connect the electric wire of hot-line side to the AC input terminals L1/R and L2/S, and connect the grounding wire to the input ground terminal. Likewise, in the connections between the output of the UPS and the connection device, connect the electric wire of hot-line side to the AC output terminals l1/U and l2/V, and connect the grounding wire to the output ground terminal.
If connected by mistake, there is fear of the malfunction by noise, the failure, or an electric shock.
device getting connected to the UPS) or the UPS, turn off power of the connection device and stop the operation of UPS. And turn off the breaker of the distribution board and cut off connection of AC input terminal.
There is fear of an electric shock.
 iii
Caution about Safety
Injury Do not ride on or put an object on the UPS.
Injury Damage
Fire Damage
There is fear of an injury or an overturn.
The UPS is heavy. Pay enough attention to handling the UPS.
Take out the UPS in a level and flat place. If you lift the UPS alone or carry it, there is fear of hurting arms, legs or hip, or dropping the UPS. Work by a suitable number of persons. And pay enough attention to prevent an accident such as an overturn or a drop. The weight of the UPS is as follows:
M-UPS050AD2B : 63kg (without battery : 29kg) M-UPS075AD2B : 127kg (without battery : 59kg) M-UPS100AD2B : 127kg (without battery : 59kg)
This UPS can be installed laying down. If installing laying the UPS down, tilt it only to the right side, seeing from the front. Never tilt the UPS to the left side.
If tilting the UPS to the left side, the liquid leak of a battery may occur, there is fear of a fire or the UPS failure in the case. If installing laying the UPS down, be sure to tilt it to the right side.
iv
Caution about Safety
Damage Do not use the UPS for the uses that may hurt the human
body or exert an important influence on the society and public.
Do not put an object (display or floppy disk etc.)
Confirm that the voltage set up by the switch of voltage
Do not operate the switch of voltage setting during
Replace the battery periodically.
Medical instrument affecting human life directly Device that may hurt the human body Socially and publicly important computer system
vulnerable to magnetism around the UPS.
There is fear of exerting a bad influence on the object.
setting is within the range of input voltage of the connection device.
There is fear of damaging the connection device.
operation of the UPS.
There is fear of damaging the connection device, since the changed voltage is outputted at the restart. And even if operating the switch during operation of the UPS, the output voltage cannot be changed.
If continuing to use the UPS that the battery life ended, there is fear of a liquid leak of battery, a smoking, and an ignition.
Replace the battery with one specified by our company and a new one.
If using the un-specified battery or mixing an old battery and a new battery, it becomes the cause of a liquid leak of battery, a smoking, an ignition, and the UPS failure and trouble.
When performing the rolling blackouts or when cutting off an input power supply, perform them after stopping the operation of the UPS, with reference to Chapter 4.2 "Turning off the UPS". The stop of operation can be confirmed by slow blink (in the cycles of approximately
1.6 sec.) of the RUN LED (green).
If cutting off an input power supply when the UPS is operating (the RUN LED is lighting), the UPS switches to the battery operation since it will be in the same state as a power failure. Performing such unnecessary battery operation leads to a shortening of a cycle of battery replacement.
Warning label
Warning labels are attached to the UPS. Never remove the labels.
v
Caution for Use
Be careful about the following when using the UPS.
Important
Do not install and store the UPS in the following places:
In an outdoor location  A place exposed to the elements  An extremely humid place and a dusty place  A place with corrosive gas or salinity  A place subjected to direct sunlight  A place near sparks or heating element  An extremely hot or cold place or place where the temperature fluctuates
greatly
A place where vibration and a shock are added
Do not perform the battery check in succession.
When the battery check is performed, the UPS temporarily switches to the battery operation. If the battery check is performed in succession, there is fear of the battery deterioration or a shortening of a cycle of battery replacement since the battery becomes an over-discharge state.
If the UPS is not used for a long time, charge the battery every two months.
The battery is charged by operating the UPS. For the battery charging time, refer to Chapter 8.1 "Rated Specification". If the UPS is left without operating for a long time, there is a possibility that the UPS get unusable since the battery becomes an over-discharge state due to self-discharge.
This UPS is recyclable.
This UPS uses the small sealed lead storage battery. The small sealed lead storage battery uses expensive and rare resources. However, these precious resources are able to recycle. Cooperate in recycling without disposing of the used battery.
Do not block the vent hole and cooling fan or use the UPS in a stuffy place.
The vent hole and cooling fan are equipped in order to cool the inside of the UPS. There is a possibility that the inside and ambient temperature of the UPS may get out of the rated specification.
Replace the cooling fan periodically.
If continuing to use the UPS that the cooling fan life ended, there is a possibility that the inside temperature of the UPS may get out of the rated specification.
Do not use 5 to 9 of the switch of voltage setting.
It becomes impossible for the UPS to start up normally.
"Important" indicates caution about the use of the UPS.
 vi
Caution for Use
The permissible voltage between the input electric cable of the UPS and the ground is 250V AC.
If the voltage more than 250V AC is applied, the filter circuit of the input part may be damaged.
The permissible input surge voltage of the UPS is 5kV peak (1.2 50µs). However, if the model of the UPS is "-UC" and "-C", it is 2kV peak (1.2
50µs).
If the surge voltage more than 5kV peak ("-UC" and "-C" are 2kV peak) is applied, the filter circuit of the input part may be damaged.
The input voltage of the UPS is 160 to 288V AC.
When input voltage is different from the rated specification (400V AC etc.), install a transformer at the outside of the UPS to convert voltage. If the voltage more than the range of the input voltage is applied, the UPS may be damaged.
Pay attention to an input voltage.
This UPS can operate up to 288V AC. However, an input voltage of the general device is 200V AC ±10%. Therefore, if switching to the bypass operation when applying the voltage of 220V AC to the UPS, the voltage exceeding specification is applied to the connection device. Adjust the input voltage to the specification of connection device.
Do not apply single-line grounding on the output side.
Between the input and output of the UPS is not insulated. Therefore, do not apply single-line grounding on the output side. There is fear of becoming the cause of the trouble of connection device by noise or the failure.
When connecting the UPS to the electrical power equipment with the earth leakage breaker, select the earth leakage breaker not to trip due to current leakage.
When connecting the UPS to the electrical power equipment with the earth leakage breaker, select the earth leakage breaker in consideration of total number of current leakage of the UPS plus current leakage of the connection device.
When connecting the UPS to a three-phase power supply system, be sure to connect the grounding phase of the three-phase power supply system to the electrode of a grounding side of the AC input of the UPS.
If connecting to an un-grounding power supply, there is fear of becoming the cause of the malfunction.
vii
Caution for Use
50Hzor60Hz
Illegalzerocross
When using a generator temporarily during the rolling blackouts, use a generator satisfying the following specification.
If connecting a generator not satisfying the following specification to the input part of the UPS, there is a possibility of becoming the cause of the malfunction or damage of the UPS.
Voltage regulation: depend on the input specification of the connection device  Frequency variation: within rated frequency ± 5% (frequency does not change
rapidly)
Voltage waveform distortion: within 5%  Voltage zero-cross condition: Zero-cross must not occur twice or more in 1
cycle.
viii
Index
Introduction.......................................................................................................i
Caution about Safety .....................................................................................iii
Caution for Use..............................................................................................vii
1 Unpacking
1.1 Opening the Packing ...........................................................................1
Opening the packing  Confirming the contents of the packing
2 Outline
2.1 Name and Main Function of Each Part ...............................................2
2.2 Mechanism of the UPS.........................................................................5
At the normal operation  At the battery operation (In the event of an input power failure)  At the automatic bypass operation  At the manual bypass operation
3 Installation
3.1 Installing the UPS.................................................................................7
Caution about installation  Determining an installation location  Determining the installation method  Installation method
3.2 Connecting the Cable ........................................................................12
Caution about connecting the cable  Preparation before connecting the cable  Connecting the output cable  Connecting the input cable
3.3 Interface Port......................................................................................16
CN1 (No-voltage contact signal interface)  CN2 (RS-232C interface)
3.4 Setting up the Output Voltage...........................................................18
The setup procedures of the rated output voltage
4 Running
4.1 Turning on the UPS............................................................................ 20
Confirming cable connection  Turning on the UPS  Turning on the connection device
4.2 Turning off the UPS............................................................................23
Turning off the connection device  Turning off the UPS
5 Inspection
5.1 Care and Daily Inspection .................................................................25
How to care for the UPS  Daily inspection
ix
5.2 Caution and Measures for the Rolling Blackouts.............................27
Operation before the rolling blackouts  Operation after the rolling blackouts
5.3 Inspecting the Battery (Battery Check).............................................29
Confirming the state of the UPS  Using the manual check function  Charging the battery
6 Troubleshooting
6.1 If a Warning Beep Sounds.................................................................34
6.2 Operation Mode List...........................................................................35
Types of blink of LED  Types of warning beep  Operation mode list
7 Maintenance
Replacing the Battery ........................................................................40
Timing of the battery replacement  The method of battery replacement  Disposal and storage of battery
7.2 Replacing the Cooling Fan ................................................................43
Timing of the cooling fan replacement  The method of cooling fan replacement
7.3 When Not Using the UPS (Storage)...................................................45
Work before storage  If a storage period exceeds two months
8 Appendix
8.1 Rated Specification ............................................................................46
8.2 Additional Description for UL Type...................................................48
x
1 Unpacking
1.1 Opening the Packing
Opening the packing
Injury Damage
1. Open the packing box and take out the UPS. Confirming the contents of the packing
2. Confirm that there is no damage in the appearance of the UPS.
The UPS is heavy. Pay enough attention to handling the UPS.
Take out the UPS in a level and flat place. If you lift the UPS alone or carry it, there is fear of hurting arms, legs or hip, or dropping the UPS. Work by a suitable number of persons. And pay enough attention to prevent an accident such as an overturn or a drop. The weight of the UPS is as follows:
M-UPS050AD2B : 63kg (without battery: 29kg)  M-UPS075AD2B : 127kg (without battery: 59kg)  M-UPS100AD2B : 127kg (without battery: 59kg)
Caution
3. Confirm that all accessories are contained.
UPS model Accessories No. of pcs
M-UPS050AD2B
(5kVA)
M-UPS075AD2B
(7.5kVA)
M-UPS100AD2B
(10kVA)
If the UPS got damaged, or accessories are missing:
Contact an agent from which you purchased the UPS.
Users manual (this document) Guarantee (this document) Stabilizer (with 6 setscrews) Users manual (this document) Guarantee (this document) Stabilizer (with 6 setscrews) Users manual (this document) Guarantee (this document) Stabilizer (with 6 setscrews)
1 copy
1set
1 copy
1set
1 copy
1set
- 1 -
2 Outline
(14)
(18)
(6)
(19)
(17)
2.1 Name and Main Function of Each Part
This chapter describes the name and main function of each part of the UPS.
M-UPS050AD2B
(1)
(2)
(3)
(4)
(5)
(9)
N
U
R
M
R
A
L
A
D
A
O
L
R
E
V
O
S
S
A
P
Y
B
Y
R
N
E
T
O
I
T
T
I
A
D
B
N
O
C
(7)
T
E
S
E
R
T
T
K
A
C
B
E
H
C
S
P
U
(8)
(10)
(15)
(12) (16)
(11)
(13)
- 2 -
(10)
(11)
(12)
(13)
(14)
2.1 Name and Main Function of Each Part
M-UPS075AD2B, M-UPS100AD2B〉
(2)
(3)
(4)
(1)
(7)
(6)
(5)
(9)
(8)
(16)
(19)
(18)
(17)
(15)
- 3 -
2 Outline
(1) (2)
(3)
(4)
LED
Name Main function
RUN It lights up (green) while the UPS is operating normally. ALARM
OVER LOAD
BYPASS
It lights up (orange) when the abnormalities occurred inside the UPS. It lights up (orange) when the load capacity of the connection device exceeded the rated specification. It lights up (orange) while the UPS is performing the bypass operation. When the battery is normal, it indicates the amount of battery
(5)
BATTERY CONDITION
charge according to the sort of lighting (green). (Not lighting:0 to 50%, Blinking:50 to 80%, Lighting:80 to 100%) When the battery is abnormal, it lights up (orange). It is the switch for performing operation and stop of the UPS.
(6)
RUN/STOP
RUN and STOP are switched every time this switch is pressed for approximately 1 second. Press this switch when stopping the warning beep. Also, if this
(7)
RESET
switch is pressed for approximately 3 seconds after the failure is restored, the ALARM LED goes out. It is the switch for performing the battery check manually. By
(8)
BATT CHECK
Switch
pressing the switch for approximately 2 seconds, the battery check is performed. Press switch (7) and (8) for approximately 3 seconds simultaneously when switching to the bypass operation forcibly
BYPASS
(manually) while the UPS is operating normally. When the switches are pressed for approximately 3 seconds simultaneously again, the UPS returns to the normal operation.
(9) Vent hole (cooling fan)
The inside of the UPS is ventilated and cooled. The direction of air is intake.
(10) Cooling fan The inside of the UPS is cooled. The direction of air is exhaust.
(11) Input terminal block Connect to an input power supply. (12) Input breaker It is the breaker for protecting the input circuit. (13) Output terminal block Connect to an output system. (14) Ground terminal Connect a grounding wire. (15) Switch of voltage setting Set up the output voltage.
(16) Dummy board Mount various option outlets. (-U, -UC type is no option)
(17) Interface slot Mount various interface cards.
(18) Contact signal (CN1) Output a no-voltage contact signal. (19) RS-232C (CN2) It is RS-232C interface.
- 4 -
2.2 Mechanism of the UPS
2.2 Mechanism of the UPS
At the normal operation
While the UPS is operating normally, the UPS operates an AC power supply as an input, and supplies the output of constant voltage to connection device. Simultaneously, the UPS charges an internal battery and prepares for the battery operation. Output frequency synchronizes with input frequency.
[UPS]
Bypass
AC/ACconverter
Boostchopper
BatteryCharger
Inputpowersupply
:Powerisfed
:Powerisnotfed
Output Toconnectiondevice
Electricity flow during normal operation
At the battery operation (In the event of an input power failure)
When the power failure or the abnormalities of voltage or frequency of an input power supply occur while the UPS is operating, the UPS starts the electric discharge from the battery, and continues to supply the stable electric power to the connection device. In addition, the changeover to the battery operation is performed without instantaneous power interruption. If the input power supply returns (the voltage of the input power supply returns within the rated specification), the UPS will return to the above normal operation automatically.
[UPS]
Bypass
AC/ACconverter
Boostchopper
BatteryCharger
Theabnormalities
occurataninput
powersupply.
WhiletheUPSisoperating,
-Powerfailure
-Theabnormalitiesofvoltageorfrequency etc.
:Powerisfed
:Powerisnotfed
Output Toconnectiondevice
Electricity flow during battery operation
- 5 -
2 Outline
At the automatic bypass operation
When the abnormalities occurred in the UPS during the normal operation, the UPS switches to the bypass operation automatically. During the bypass operation, the UPS sends the input voltage to the output directly and supplies the electric power to the connection device. In this operation state, even if the power failure occurs, the UPS becomes the power failure state without switching to the battery operation.
[UPS]
Bypass
:Powerisfed
BatteryCharger
:Powerisnotfed
Output Toconnectiondevice
Inputpowersupply
AC/ACconverter
Anerror
occursinside
Boostchopper
theUPS
-TheabnormalitiesinsidetheUPS
Electricity flow during automatic bypass operation
At the manual bypass operation
It is possible to switch to the bypass operation manually during the normal operation. Press the RESET switch and the BYPASS switch for approximately 3 seconds simultaneously to switch to the bypass operation. When the switches are pressed for approximately 3 seconds simultaneously again, the UPS returns to the normal operation. In this operation state, even if the power failure occurs, the UPS becomes the power failure state without switching to the battery operation.
[UPS]
Bypass
AC/ACconverter
Inputpowersupply
Boostchopper
BatteryCharger
Switchingtothebypass
operationmanually
:Powerisfed
:Powerisnotfed
Output Toconnectiondevice
Electricity flow during manual bypass operation
- 6 -
3 Installation
3.1 Installing the UPS
Caution about installation
Injury Do not ride on or put an object on the UPS.
Damage Do not put an object (display or floppy disk etc.) vulnerable to
Determining an installation location
Do not install the UPS in the following places:
In an outdoor location A place exposed to the elements An extremely humid place and a dusty place A place with corrosive gas or salinity A place subjected to direct sunlight A place near sparks or heating element An extremely hot or cold place or place where the temperature fluctuates
A place where vibration and a shock are added
Do not use the UPS in a residential area or its adjacent area.
This UPS is class A information technology equipment based on the standard of Voluntary Control Council for Interference by Information Technology Equipment (VCCI). Using this UPS in a residential area may cause radio interference. In this case, the user may be requested to take an appropriate measure.
Do not block the vent hole and cooling fan or use the UPS in a stuffy place.
The vent hole and cooling fan are equipped in order to cool the inside of the UPS. There is a possibility that the inside and ambient temperature of the UPS may get out of the rated specification.
There is fear of an injury or an overturn.
magnetism around the UPS.
There is fear of exerting a bad influence on the object.
greatly
Caution
Important
- 7 -
3 Installation
The following spaces are required for an installation location.
The UPS takes in air through the vent hole on the front of the UPS and
exhausts air through the cooling fan on the back of the UPS. Therefore, the space of 10cm or more is required in the front and rear of the UPS.
Frontside
Intake
air
10cm
or more
Right side
When performing maintenance of the UPS:
The space of approximately 1m is required in the front and rear of the UPS.
Spaceforcooling fanandbattery maintenance
Approx.1m
Frontside
UPS
UPS
Rearside
Exhaust
air
10cm
or more
Spacefor coolingfan maintenance
Approx.1m
Rearside
Right side
Confirm the environment of the installation location. The recommended environment in consideration of the battery life etc. is as follows.
Item Recommended environment
Temperature 15 to 25 degrees C Humidity 30 to 70% (no condensation)
- 8 -
3.1 Installing the UPS
Determining the installation method
Caution
Fire Damage
This UPS can be installed laying down. If installing laying the UPS down, tilt it only to the right side, seeing from the front. Never tilt the UPS to the left side.
If tilting the UPS to the left side, the liquid leak of a battery may occur, there is fear of a fire or the UPS failure in the case. If installing laying the UPS down, be sure to tilt it to the right side.
This UPS can be put in a 19-inch rack using the optional rack mount
attachment kit.
- 9 -
3 Installation
Installation method
Injury Damage
1.
When using the UPS as the self-standing type, tilt the UPS to the right tenderly and attach the attached stabilizer to the bottom of the UPS with 6 screws. (refer to the following figure)
M-UPS050AD2B
The UPS is heavy. Pay enough attention to handling the UPS.
Take out the UPS in a level and flat place. If you lift the UPS alone or carry it, there is fear of hurting arms, legs or hip, or dropping the UPS. Work by a suitable number of persons. And pay enough attention to prevent an accident such as an overturn or a drop. The weight of the UPS is as follows:
M-UPS050AD2B : 63kg (without battery: 29kg)  M-UPS075AD2B : 127kg (without battery: 59kg)  M-UPS100AD2B : 127kg (without battery: 59kg)
Caution
M-UPS075AD2B, M-UPS100AD2B〉
- 10 -
338 189.5
251.5
330
3.1 Installing the UPS
2. After attaching the stabilizer to the UPS, be sure to fix the stabilizer to the floor.
M-UPS050AD2B
212 197 330 181
M-UPS075AD2B, M-UPS100AD2B
- 11 -
3 Installation
3.2 Connecting the Cable
Caution about connecting the cable
Electric shock
The permissible voltage between the input electric cable of the UPS and the ground is 250V AC.
If the voltage more than 250V AC is applied, the filter circuit of the input part may be damaged.
The permissible input surge voltage of the UPS is 5kV peak (1.2 50µs). However, if the model of the UPS is "-UC" and "-C", it is 2kVpeak (1.2
50µs).
If the surge voltage more than 5kV peak ("-UC" and "-C" are 2kV peak) is applied, the filter circuit of the input part may be damaged.
The input voltage of the UPS is 160 to 288V AC.
When input voltage is different from the rated specification (400V AC etc.), install a transformer at the outside of the UPS to convert voltage. If the voltage more than the range of the input voltage is applied, the UPS may be damaged.
Pay attention to an input voltage.
This UPS can operate up to 288V AC. However, an input voltage of the general device is 200V AC ±10%. Therefore, if switching to the bypass operation when applying the voltage of 220V AC to the UPS, the voltage exceeding specification is applied to the connection device. Adjust the input voltage to the specification of connection device.
Do not apply single-line grounding on the output side.
Between the input and output of the UPS is not insulated. Therefore, do not apply single-line grounding on the output side. There is fear of becoming the cause of the trouble of connection device by noise or the failure.
The UPS should be connected to ground. (more than class D grounding) When connecting to an input power supply, connect the grounding wire to the ground terminal.
There is fear of an electric shock.
Caution
Important
- 12 -
50Hzor60Hz
Illegalzerocross
3.2 Connecting the Cable
Preparation before connecting the cable
Important
When connecting the UPS to the electrical power equipment with the earth leakage breaker, select the earth leakage breaker not to trip due to current leakage.
When connecting the UPS to the electrical power equipment with the earth leakage breaker, select the earth leakage breaker in consideration of total number of current leakage of the UPS plus current leakage of the connection device.
When connecting the UPS to a three-phase power supply system, be sure to connect the grounding phase of the three-phase power supply system to the electrode of a grounding side of the AC input of the UPS.
If connecting to an un-grounding power supply, there is fear of becoming the cause of the malfunction.
When using a generator temporarily during the rolling blackouts, use a generator satisfying the following specification.
If connecting a generator not satisfying the following specification to the input part of the UPS, there is a possibility of becoming the cause of the malfunction or damage of the UPS.
Voltage regulation: depend on the input specification of the connection
device
Frequency variation: within rated frequency ± 5% (frequency does not
change rapidly)
Voltage waveform distortion: within 5%  Voltage zero-cross condition: Zero-cross must not occur twice or more in 1
cycle.
1. Confirm the input power supply. The input power supply which can connect with
this UPS is as follows.
UPS model
M-UPS
050AD2B
(5kVA) M-UPS
075AD2B
(7.5kVA)
M-UPS
100AD2B
(10kVA)
Breaker
capacity
40A or
more
50A or
more
75A or
more
Input
capacity
5kVA or
more
7.5kVA or more
10kVA or
more
- 13 -
Input
voltage
160 to 288V
AC
Input
frequency
50/60Hz
± 5% (Note)
Number of
phase
Single-phase
two-wire
3 Installation
Remarks If the input voltage and the frequency are out of this range, the UPS will
become the following state or be damaged.
When the UPS is turned on:
The UPS will become the "input error at startup". In this case, the UPS cannot be started up.
While the UPS is operating:
"Abnormalities of input voltage" is detected and the battery operation is performed. If the UPS is connected to an input power supply which gets out of this range frequently, by repeating the charge and discharge of the battery, the battery will be in an empty state or will become the cause of deterioration.
Note) The input frequency of the using area is chosen automatically.
2.
The specification of the terminal block is as follows. Select the crimp contact which is suitable for specification.
M-UPS050AD2B
UPS side Specification Connect with
Input and
output
terminal block
Terminal
marking
L1/R
L2/S
PE(G)
l1/U
l2/V
Connection Figuration
AC input (un-grounding side) AC input (un-grounding side) Ground (protective grounding) AC output (un-grounding side) AC output (un-grounding side)
5 pole
screw
terminal
(M5)
Input power supply and output system
M-UPS075AD2B, M-UPS100AD2B
UPS side Specification Connect with
Input and
output
terminal block
Terminal
marking
L1/R
L2/S
PE(G)
PE(G)
Connection Figuration
AC input (un-grounding side) AC input (un-grounding side) Ground (protective grounding) Ground (protective
6 pole
screw
terminal
(M8)
Input power supply and output system
grounding)
l1/U
l2/V
AC output (un-grounding side)
AC output (un-grounding side)
- 14 -
3.2 Connecting the Cable
Connecting the output cable
Remove the input and output terminal block cover on the back of the UPS, and connect the AC output cable to the output terminal block. Confirm that the ground is connected.
Connecting the input cable
Remove the input and output terminal block cover on the back of the UPS, and connect the AC input cable to the input terminal block. Confirm that the ground is connected.
- 15 -
3 Installation
3.3 Interface Port
The interface port (D-sub 9 pins) is mounted on the back of the UPS and can take out the following signals. Use as necessary.
CN1 (No-voltage contact signal interface)
Pin
No.
1-4
1-6
2-5
2-7
3-9
3-8
Use the contact output in the range of the voltage and current in the following graph.
Classification
of signal
"Open"
at operation
"Close"
at operation
"Open"
at operation
"Close"
at operation
"Open"
at operation
"Close"
at operation
1 2 543
6 987
D-sub9pins,male
(3mmscrew)
Name of
signal
UPS failure
signal
Input power
supply
abnormal signal
Battery voltage
drop signal
Content
It is the no-voltage contact signal which operates when the abnormalities occur inside the UPS, when the abnormalities occur in the battery, or when the recommendation time of battery replacement comes.
It is the no-voltage contact signal which is outputted when the abnormalities, such as the power failure, occur at an input power supply. (In the power failure for 1.5 seconds or less, it does not operate.)
It is the no-voltage contact signal which is outputted approximately 2 minutes before (at the rated load) the end of battery discharge during the battery operation.
Contactrating
Contactrating
①:AC Contactrating Contactrating
Contactrating
1.0
1.0
0.5
0.5
0.2
0.2
Contactcurrent(A)
Contactcurrent(A)
0.1
0.1
0.05
0.05 30 6010 120
30 6010 120
Contactvoltage(V)
Contactvoltage(V)
②:DC Contactrating
200
200
- 16 -
3.3 Interface Port
CN2 (RS-232C interface)
125 4 3
69 8 7
D-sub9pins,female
(#4-40inchscrew)
Pin No.
2-3
1-3
8-7 AC output stop
6-7 Serial data
9-7 Serial data
*1 Refer to the graph of the previous page for contact capacity.
*2 In the case of Windows 2000 and XP, although the shutdown of OS can be
*3 When performing the RS-232C serial communication, contact your maintenance
Classification
of signal
"Close"
at operation
"Close"
at operation
at H’ signal
reception
RS-232C serial
signal
7
When using the UPS monitoring function (using the above contact signal) preinstalled in the following OS, contact your maintenance staff, since the dedicated cable for contact signal which corresponds to each OS is needed separately. For more detail on the UPS monitoring function preinstalled in each OS, refer to an instructions manual, an on-line manual, etc. of each OS.
performed during the power failure, a subsequent UPS automatic shutdown cannot be performed.
staff, since the dedicated cable for RS-232C communication is needed separately.
(*3)
Windows NT/2000/XP:FiFH/WS9 (the dedicated cable for contact signal)
FiFA/WS9 (the dedicated cable for RS-232C communication)
Name of
signal
Input power
supply
abnormal signal
(*1)
Battery voltage
drop signal
(*1)
UPS automatic
shutdown signal
(*2)
input (RX)
output (TX)
Signal ground
(SG)
Content
It is the no-voltage contact signal which is outputted when the abnormalities, such as the power failure, occur at an input power supply. (In the power failure for 1.5 seconds or less, it does not operate)
It is the no-voltage contact signal which is outputted approximately 2 minutes before (at the rated load) the end of battery discharge during the battery operation.
It is the signal which is inputted into the UPS when stopping the AC output of the UPS.
(1) The stop of the AC output is possible
only during the battery operation.
(2) Input this signal (5 to 25V DC)
approximately 0.6 seconds or more. [Communication system] Baud rate : 2400 bps Data length : 8 bits Stop bit : 1 bit Parity : non Character type : ASCII
- 17 -
0 200V AC
1 208V AC
2 220V AC
3
230V AC
4 240V AC
5-9 They are not used.
3 Installation
3.4 Setting up the Output Voltage
This UPS can change the rated output voltage by the switch of voltage setting on the back of the UPS.
Damage Confirm that the voltage set up by the switch of voltage
setting is within the range of input voltage of the connection device.
Do not operate the switch of voltage setting during operation
Do not use 5 to 9 of the switch of voltage setting.
It becomes impossible for the UPS to start up normally.
There is fear of damaging the connection device.
of the UPS. There is fear of damaging the connection device, since the changed
voltage is outputted at the restart. And even if operating the switch during operation of the UPS, the output voltage cannot be changed.
Important
Caution
The setup procedures of the rated output voltage
1.
Turn off the connection device.
2.
Press the RUN/STOP switch on the front of the UPS for approximately 1 second. The buzzer will sound if the switch is received.
3.
An output stops. The RUN LED (green) on the front of the UPS blinks slowly (in the cycles of approximately 1.6 sec.).
4.
Turn off the input breaker on the back of the UPS.
5.
After confirming that all LEDs on the front of the UPS have gone out, operate the switch of voltage setting on the back of the UPS. The rated output voltage corresponding to a setup of the switch of voltage setting is shown below.
Setup of the switch of voltage setting Rated output voltage
6.
Turn on the input breaker on the back of the UPS. The RUN LED (green) on the front of the UPS blinks slowly (in the cycles of approximately 1.6 sec.).
- 18 -
3.4 Setting up the Output Voltage
7. Press the RUN/STOP switch on the front of the UPS for approximately 1 second.
The buzzer will sound if the switch is received.
8. AC voltage set up is outputted from the output terminal block. The RUN LED
(green) on the front of the UPS lights up.
9. Turn on the connection device, if the normal operation is started with the rated
voltage set up.
- 19 -
4 Running
4.1 Turning on the UPS
Damage
Confirming cable connection
1. Confirm that the UPS is connected to an input power supply and the connection
device. When turning on the input breaker on the back of the UPS, the RUN LED (green) on the front of the UPS blinks slowly (in the cycles of approximately 1.6 sec.).
〈M-UPS050AD2B〉 〈M-UPS075AD2B, M-UPS100AD2B〉
Confirm that the voltage set up by the switch of voltage setting is within the range of input voltage of the connection device.
There is fear of damaging the connection device.
Caution
N
U
R
M
R
A
L
A
D
A
O
L
R
E
V
O
S
S
A
P
Y
B
T
T
A
B
N
O
C
T
E
S
E
R
Y
R
E
O
I
T
I
D
T
N
T
K
A
C
B
E
H
C
S
P
U
If the UPS is not connected:
Refer to Chapter 3.2 "Connecting the Cable".
- 20 -
4.1 Turning on the UPS
Turning on the UPS
2. Press the RUN/STOP switch on the front of the UPS for approximately 1 second.
The buzzer will sound if the switch is received.
〈M-UPS050AD2B〉 〈M-UPS075AD2B, M-UPS100AD2B〉
Press the RUN/STOP switch for approximately 1 second.
N
U
R
M
R
A
L
A
D
A
O
L
R
E
V
O
S
S
A
P
Y
B
T
T
A
B
N
O
C
T
E
S
E
R
Y
R
E
O
I
T
I
D
T
N
T
K
A
C
B
E
H
C
S
P
U
3. AC voltage is outputted from the output terminal block.
The RUN LED (green) on the front of the UPS lights up. The BATTERY CONDITION LED (green) on the front of the UPS indicates the amount of battery charge according to the sort of lighting.
〈M-UPS050AD2B〉 〈M-UPS075AD2B, M-UPS100AD2B〉
The RUN LED(green)lights up.
N
U
R
M
R
A
L
A
D
A
O
L
R
E
V
O
S
S
A
P
Y
B
T
T
A
B
N
O
C
T
E
S
E
R
Y
R
E
O
I
T
I
D
T
N
T
K
A
C
B
E
H
C
S
P
U
The indication (green) of the amount of battery charge
Lighting:80 to 100%  Blinking:50 to 80%  Not lighting:0 to 50%
- 21 -
4 Running
4.
The battery check is performed automatically. The BATTERY CONDITION LED (orange) on the front of the UPS blinks (in the cycles of approximately 1.6 sec.).
〈M-UPS050AD2B〉 〈M-UPS075AD2B, M-UPS100AD2B〉
N
U
R
M
R
A
L
A
D
A
O
L
R
E
V
O
S
S
A
P
Y
B
T
T
A
B
N
O
C
T
E
S
E
R
Y
R
E
O
I
T
I
D
T
N
T
K
A
C
B
E
H
C
S
P
U
5.
The battery check is performed for approximately 5 seconds. Then, if the battery is normal, the BATTERY CONDITION LED (green) on the front of the UPS indicates the amount of battery charge again, and the UPS returns to the normal operation.
If the normal operation is not started:
Refer to Chapter 6 "Troubleshooting".
Turning on the connection device
6.
Turn on the connection device if the normal operation is started.
- 22 -
4.2 Turning off the UPS
4.2 Turning off the UPS
Also when the rolling blackouts are performed, be sure to perform the following operation. (For details, refer to Chapter 5.2 "Caution and Measures for the Rolling Blackouts")
Caution
Damage When performing the rolling blackouts or when cutting off an
input power supply, perform them after stopping the operation of the UPS, with reference to Chapter 4.2 "Turning off the UPS". The stop of operation can be confirmed by slow blink (in the cycles of approximately 1.6 sec.) of the RUN LED (green).
Turning off the connection device
1. Turn off the connection device.
If cutting off an input power supply when the UPS is operating (the RUN LED is lighting), the UPS switches to the battery operation since it will be in the same state as a power failure. Performing such unnecessary battery operation leads to a shortening of a cycle of battery replacement.
Turning off the UPS
2. Press the RUN/STOP switch on the front of the UPS for approximately 1 second.
The buzzer will sound if the switch is received.
〈M-UPS050AD2B〉 〈M-UPS075AD2B, M-UPS100AD2B〉
Press the RUN/STOP switch for approximately 1 second.
N
U
R
M
R
A
L
A
D
A
O
L
R
E
V
O
S
S
A
P
Y
B
T
T
A
B
N
O
C
T
E
S
E
R
Y
R
E
O
I
T
I
D
T
N
T
K
A
C
B
E
H
C
S
P
U
- 23 -
4 Running
3.
An output stops. The RUN LED (green) on the front of the UPS blinks slowly (in the cycles of approximately 1.6 sec.).
〈M-UPS050AD2B〉 〈M-UPS075AD2B, M-UPS100AD2B〉
N
U
R
M
R
A
L
A
D
A
O
L
R
E
V
O
S
S
A
P
Y
B
T
T
A
B
N
O
C
T
E
S
E
R
Y
R
E
O
I
T
I
D
T
N
T
K
A
C
B
E
H
C
S
P
U
If an output does not stop normally:
Refer to Chapter 6 "Troubleshooting".
4.
Turn off the input breaker on the back of the UPS.
- 24 -
5 Inspection
5.1 Care and Daily Inspection
In order to use the UPS safely over the long term, perform the following care and daily inspection regularly.
Warning
Electric Do not remove the cover of the UPS. shock Since there are some portions with high voltage in the inside of the UPS,
there is fear of an electric shock.
Caution
Electric shock
Failure
Electric shock
Damage When performing the rolling blackouts or when cutting off an
When inspecting or maintaining the connection device (a device getting connected to the UPS) or the UPS, turn off power of the connection device and stop the operation of UPS. And turn off the breaker of the distribution board and cut off connection of AC input terminal.
There is fear of an electric shock.
Perform the battery and cooling fan replacement by maintenance personnel.
There is fear of an electric shock.
input power supply, perform them after stopping the operation of the UPS, with reference to Chapter 4.2 "Turning off the UPS". The stop of operation can be confirmed by slow blink (in the cycles of approximately 1.6 sec.) of the RUN LED (green).
If cutting off an input power supply when the UPS is operating (the RUN LED is lighting), the UPS switches to the battery operation since it will be in the same state as a power failure. Performing such unnecessary battery operation leads to a shortening of a cycle of battery replacement.
- 25 -
5 Inspection
How to care for the UPS
1.
Turn off the UPS after turning off the connection device, and remove the dust adhering to the vent hole and cooling fan of the UPS with a cleaner, etc.
2.
Wipe the surface of the UPS with a dry and soft cloth.
Daily inspection
Confirm that the dust is not adhering to the vent hole and the cooling fan.
When the dust is adhering:
Refer to "How to care for the UPS".
Confirm that the surface of UPS, the electric cables, and the outlets are not heating
unusually.
When they are heating:
Confirm the state, and contact an agent from which you purchased the UPS or a maintenance company.
Confirm that a loud abnormal sound or a nasty smell is not occurring during the
operation of the UPS.
When abnormalities have occurred:
Confirm the state, and contact an agent from which you purchased the UPS or a maintenance company.
- 26 -
50Hzor60Hz
Illegalzerocross
5.2 Caution and Measures for the Rolling Blackouts
5.2 Caution and Measures for the Rolling Blackouts
Important
When using a generator temporarily during the rolling blackouts, use a generator satisfying the following specification.
If connecting a generator not satisfying the following specification to the input part of the UPS, there is a possibility of becoming the cause of the malfunction or damage of the UPS.
Voltage regulation: depend on the input specification of the connection
device
Frequency variation: within rated frequency ± 5% (frequency does not
change rapidly)
Voltage waveform distortion: within 5% Voltage zero-cross condition: Zero-cross must not occur twice or more in 1
cycle.
Operation before the rolling blackouts
Turn off the connection device and the UPS before performing the rolling blackouts (Note).
1. Turn off the connection device.
2. Press the RUN/STOP switch on the front of the UPS for approximately 1 second.
The buzzer will sound if the switch is received.
3. An output stops.
The RUN LED (green) on the front of the UPS blinks slowly (in the cycles of approximately 1.6 sec.).
If the rolling blackouts are performed without turning off the UPS, the UPS will be in the same state as an ordinary power failure. Electric power is supplied to the connection device from the internal battery of the UPS until the rolling blackouts are completed. Electric power is not supplied to the connection device until an input power supply returns after the electric discharge is completed.
Note) The rolling blackouts mean the blackouts to which the date and hour, such as
the safety inspection of electricity, is informed beforehand.
- 27 -
5 Inspection
Operation after the rolling blackouts
1.
Confirm that the UPS is connected to an input power supply and the connection device. The RUN LED (green) on the front of the UPS blinks slowly (in the cycles of approximately 1.6 sec.).
2.
Press the RUN/STOP switch on the front of the UPS for approximately 1 second. The buzzer will sound if the switch is received.
3.
AC voltage is outputted from the output terminal block, and the RUN LED (green) on the front of the UPS lights up.
4.
Turn on the connection device if the normal operation is started.
For details, refer to Chapter 4.1 "Turning on the UPS". When a warning beep sounds:
Refer to Chapter 6.1 "If a Warning Beep Sounds".
- 28 -
5.3 Inspecting the Battery (Battery Check)
5.3 Inspecting the Battery (Battery Check)
Inspection of the battery is performed using a battery check function. There are two kinds of battery check functions, an automatic check and a manual check. The manual check is not necessary ordinarily since automatic check is performed while the UPS is operating. Automatic check is performed in the following cases:
When the operation of UPS is started up Every two weeks in an operation continuation state When the UPS has switched to the normal operation from the bypass operation
Perform manual check in the following cases:
When a warning beep sounds due to the abnormalities in a battery When performing the battery check other than the automatic check
Important
Do not perform the battery check in succession.
When the battery check is performed, the UPS temporarily switches to the battery operation. If the battery check is performed in succession, there is fear of the battery deterioration or a shortening of a cycle of battery replacement since the battery becomes an over-discharge state.
Confirming the state of the UPS
1. Confirm that the UPS is operating normally.
〈M-UPS050AD2B〉 〈M-UPS075AD2B, M-UPS100AD2B〉
Confirm that the RUN LED (green) is lighting.
N
U
R
M
R
A
L
A
D
A
O
L
R
E
V
O
S
A
P
Y
B
A
B
C
T
E
S
E
R
S
Y
R
E
T
T
T
I
D
N
O
T
N
T
O
I
K
A
C
B
E
H
C
S
P
U
When the UPS is in a stop state (all LED on the front of the UPS goes
out):
Turn on the UPS, and proceed to Procedure 2. For details, refer to Chapter 4.1 "Turning on the UPS".
When the normal operation cannot be confirmed in states other than a
stop:
Proceed to Procedure 2 after reading Chapter 6 "Troubleshooting" and dealing with the trouble.
- 29 -
5 Inspection
Using the manual check function
2. Press the BATT CHECK switch on the front of the UPS for approximately 2 seconds.
M-UPS050AD2B〉 〈M-UPS075AD2B, M-UPS100AD2B〉
N
U
R
M
R
A
L
A
D
A
O
L
R
E
V
O
S
A
P
Y
B
A
B
O
C
T
E
S
E
R
S
Y
R
E
T
T
T
I
D
N
T
N
T
O
I
K
A
C
B
E
H
C
S
P
U
Press the BATT CHECK switch for approximately 2 seconds.
M-UPS050AD2B
R
A
L
A
E
V
O
Y
B
Pi
A buzzer sounds.
The buzzer sounds, and the BATTERY CONDITION LED (orange)
blinks (in the cycles of approximately 1.6 sec.). The buzzer sounds again approximately 5 seconds later and the battery check is completed.
N
U
M
R
D
A
O
L
R
S
S
A
P
T
T
A
B
N
O
C
T
E
S
E
R
Y
R
E
O
I
T
I
D
T
N
T
K
A
C
B
E
H
C
P
U
(Not sound)
S
The BATTERY CONDITION LED (orange) blinks.
N
U
R
M
R
A
L
A
D
A
O
L
R
E
V
O
S
S
A
P
Y
B
T
T
A
B
N
O
C
T
E
S
E
R
Y
R
E
O
I
T
I
D
T
N
T
K
A
C
B
E
H
C
S
P
U
Pi
U
R
M
R
A
L
A
R
E
V
O
A
P
Y
B
B
A buzzer sounds.
N
D
A
O
L
S
S
T
T
A
N
O
C
T
E
S
E
R
Y
R
E
O
I
T
I
D
T
N
T
K
A
C
B
E
H
C
S
P
U
- 30 -
5.3 Inspecting the Battery (Battery Check)
M-UPS075AD2B, M-UPS100AD2B
A buzzer sounds.
Pi
The BATTERY CONDITION LED (orange) blinks.
(Not sound)
Pi
A buzzer sounds.
- 31 -
5 Inspection
sound)
3.
As a result of the battery check, the UPS will be in the following state.
If the battery is fully charged:
The RUN LED (green) on the front of the UPS lights up, and the UPS
returns to the normal operation.
〈M-UPS050AD2B〉 〈M-UPS075AD2B, M-UPS100AD2B〉
The RUN LED(green)lights up.
N
U
R
M
R
A
L
A
D
A
O
L
R
E
V
O
S
A
P
Y
B
A
B
C
T
E
S
E
R
S
Y
R
E
T
T
T
I
D
N
O
T
N
T
O
I
K
A
C
B
E
H
C
S
P
U
If the battery is not fully charged:
A warning beep sounds and the BATTERY CONDITION LED (orange)
on the front of the UPS blinks. Proceed to Procedure 4.
〈M-UPS050AD2B〉 〈M-UPS075AD2B, M-UPS100AD2B〉
T
A
B
H
C
S
P
T
K
C
E
Pip-pip­pip-pip・・・ (continuous
The BATTERY CONDITION LED (orange) blinks.
N
U
R
M
R
A
L
A
D
A
O
L
R
E
V
O
S
S
A
P
Y
B
T
T
A
B
N
O
C
T
E
S
E
R
Y
R
N
E
O
I
T
I
D
U
- 32 -
5.3 Inspecting the Battery (Battery Check)
Charging the battery
4. Put out the BATTERY CONDITION LED (orange) by pressing the RESET switch on
the front of the UPS for approximately 3 seconds, and operate the UPS 12 hours or more to charge the battery.
When pressing the RESET switch, once the BATTERY CONDITION
LED (orange) on the front of the UPS goes out, and is switched to the indication (green) of the amount of battery charge.
〈M-UPS050AD2B〉 〈M-UPS075AD2B, M-UPS100AD2B〉
Press the RESET switch.
N
U
R
M
R
A
L
A
D
A
O
L
R
E
V
O
A
P
Y
B
A
B
C
T
E
S
E
R
S
S
Y
R
E
T
I
T
T
I
D
N
O
T
N
T
O
K
A
C
B
E
H
C
S
P
U
Remarks. In this state, even if a power failure occurs, the battery operation may not
be performed.
5. Return to Procedure 2, and perform the battery check again manually.
When the UPS will be in the state of Procedure 3 If the battery is not
fully charged again:
The battery is out of order (end of battery life). Replace the battery. For details, refer to Chapter 7.1 "Replacing the Battery".
- 33 -
6 Troubleshooting
6.1 If a Warning Beep Sounds
1. Confirm the state of LED on the front of the UPS, and the type of a warning beep.
2. Refer to the "Operation mode list", and deal with it according to directions.
If the UPS is not connected to an input power supply, connect. For details, refer to Chapter 3.2 "Connecting the Cable".
How to stop a warning beep:
A warning beep can be stopped by pressing the RESET switch on the front of the UPS for approximately 1 second. (Note) However, if a warning beep does not stop even if pressing the RESET switch, stop a warning beep by the following procedures. For details, refer to Chapter 4.2 "Turning off the UPS".
(1) Turn off the connection device. (2) Press the RUN/STOP switch on the front of the UPS for approximately 1
second.
(3) An output stops.
The RUN LED (green) on the front of the UPS blinks slowly (in the cycles of approximately 1.6 sec.).
(4) Turn off the input breaker on the back of the UPS.
Note) In the output overload state, even if pressing the RESET switch, a warning
beep does not stop. Reduce the capacity of the connection device to less than the rated value of the UPS.
- 34 -
6.2 Operation Mode List
6.2 Operation Mode List
When it seems that the abnormalities occur inside the UPS or the connection device stops, confirm the LED and a warning beep by the following lists, and deal with the trouble in accordance with the remarks in the "Operation mode list".
Types of blink of LED (The symbols correspond to the symbols
in the "Operation mode list".)
Symbol
Blink pattern
(a)
(b)
Fast blink (in the cycles of approximately 0.4 sec.)
Slow blink (in the cycles of approximately 1.6 sec.)
OFF
ON
Approximately0.4sec.
OFFON
Approximately1.6sec.
Types of warning beep (The symbols correspond to the
symbols in the "Operation mode list".)
Symbol
(1)
(2)
Pip-pip-pip-pip・・・ (continuous sound)
Pip-pip-pip-pip (a stop for approximately 2 sec.) Pip-pip-pip-pip (four times every approximately 3 sec.)
Warning beep
OFF
ON
Approximately0.2sec.
OFFON
Approximately0.2sec.
Approximately
3sec.
(3)
(4)
Pi (continuance)
Pi (a stop for approximately 4 sec.) Pi
- 35 -
ONcontinuously
OFFON ON
Approximately1sec.
Approximately5sec.
6 Troubleshooting
Operation mode list
Symbols of LED:
The BATTERY CONDITION LED (green) indicates the amount of battery charge
No.
RUN
(green)
1 Lighting
2
3 (b)
Slow blink
····Lighting
········· Not lighting ········ Blinking
according to the sort of lighting as follows:
(Not lighting)········· 0 to 50% : The battery is not fully charged. Even if a
power failure occurs, the UPS may not be able to back up.
(Blinking)·············· 50 to 80% : The battery is charged to some extent,
however, an adequate backup time cannot be assured.
(Lighting) ·············· 80 to 100% : The battery is fully charged. There is backup
time at full.
LED
ALARM
(orange)
OVER LOAD
(orange)
BYPASS (orange)
BATTERY
CONDITION
(green/
orange)
Indication
of the
amount of
battery charge
(green)
Warning
beep
Operational
status
- Normal operation
- Stopping
(without an input power
supply)
- Stopping
(with an input power supply)
Remarks
The UPS is operating normally.
The output of the UPS is stopping. If an input power supply returns, the UPS will become the stopping (No.3). If the UPS does not become the stopping (No.3) even if an input power supply returns, check whether or not the input breaker has tripped. If the breaker has tripped, reset it. If the UPS still does not become the stopping (No.3), contact an agent from which you purchased the UPS or a maintenance company. When the UPS stopped since the input power failure continued and electric discharge of a battery was completed, the UPS will return to the normal operation (No.1) automatically if an input power supply returns. The output of the UPS is stopping. The UPS will return to the normal operation (No.1) by pressing the RUN/STOP switch for approximately 1 second.
- 36 -
6.2 Operation Mode List
LED
No.
RUN
(green)
4
5 Lighting
6
7 (b)
Slow blink
8 Lighting
ALARM
(orange)
Lighting
(a)
Fast
blink
OVER LOAD
(orange)
Lighting
BYPASS (orange)
Lighting
(b) Slow blink
Lighting
BATTERY
CONDITION
(green/
orange)
Indication
of the
amount of
battery charge (green)
Indication
of the
amount of
battery charge (green)
Warning
beep
Operational
status
(1) Bypass
operation due
to UPS failure
(3) Abnormality
in cooling fan
- Manual bypass
operation
(1) Input error at
startup
(1) Bypass
operation due
to an output
overload
during the
normal
operation
Remarks
The UPS became the failure state and switched to the bypass operation. Evacuate important connection device from the UPS. In this state, even if an input power failure occurs, the battery operation cannot be performed. Confirm ambient temperature and ventilation, and press the RESET switch on the front of the UPS for approximately 3 seconds after approximately 10 minutes have passed. If there is no problem, the UPS will return to the normal operation (No.1). If the ALARM LED does not go out or lights up again, even after the above operation is performed, contact an agent from which you purchased the UPS or a maintenance company. Abnormalities have occurred in the cooling fan. If this state continues for approximately 2 minutes or the inside temperature of the UPS rises, the UPS will become the
failure state of No.4. The UPS has been switched to the bypass operation manually. In this state, even if an input power failure occurs, the battery operation cannot be performed.
Since the abnormalities occur at an
input power supply, the UPS
cannot be started up.
Stop the UPS once, and restart after
confirming that an input power
supply is within the range of the
following conditions.
Input voltage: 160 to 288V AC
Input frequency: 47.5 to 52.5 Hz
or 57 to 63 Hz
Since the capacity of the
connection device exceeded the
rated value and the UPS became
the overload state, the UPS has
switched to the bypass operation
automatically. Reduce the capacity
of the connection device to less
than the rated value of the UPS. If
the capacity of the connection
device become below the rated
value, the UPS will return to the
normal operation (No.1). In the
state of the continuation of
overload, even if pressing the
RESET switch, the warning beep
does not stop. Although it may
become the overload temporarily
by inrush current at the time of a
load injection, it is no matter since
it is canceled automatically.
- 37 -
6 Troubleshooting
No.
RUN
(green)
9
10 Lighting
11
12 Lighting
13 Lighting
14 Lighting
ALARM
(orange)
Lighting
LED
OVER LOAD
(orange)
Lighting
Lighting
Lighting
BYPASS (orange)
(b) Slow blink
BATTERY
CONDITION
(green/
orange)
Indication
of the
amount of
battery charge
(green)
Indication
of the
amount of
battery charge
(green)
Indication
of the
amount of
battery charge
(green)
(b)
Slow blink
(orange)
Warning
beep
Operational
status
(1) Output
overload
during the
bypass
operation
(1) Output
overload
during the
battery
operation
(1) A Stop due to
an output
overload
(2) Battery
operation
(1) Battery
voltage drop
due to
continuing the
battery
operation
(4)
(at the
Battery
checking
manual
check)
Remarks
During the bypass operation, the capacity of the connection device exceeds the rated value. Reduce the capacity of the connection device to less than the rated value of the UPS. In this state, even if pressing the bypass switch (pressing the RESET switch and the BATT CHECK switch for approximately 3 seconds simultaneously), the UPS will not return to the normal operation (No.1). During the battery operation, the capacity of the connection device exceeds the rated value. Reduce the capacity of the connection device to less than the rated value of the UPS. If this state continues for 100 seconds, the UPS will stop. Evacuate important connection device from the UPS. Since the UPS continued to be used even after the capacity of the connection device had exceeded the rated value of the UPS, the UPS stopped. Reduce the capacity of the connection device to less than the rated value of the UPS, and restart the UPS. Since the abnormalities occurred at an input power supply, the UPS started to supply the electric power to the connection device from the battery. It is not necessary to deal with it especially. If an input power supply returns, the UPS will return to the normal operation (No.1) automatically. The battery voltage has dropped since the battery operation continued. In the rated load, the battery operation will be completed approximately 2 minutes later. Evacuate important connection device from the UPS. If an input power supply returns, the UPS will return to the normal operation (No.1) automatically. The battery check is performed. At the manual battery check, a buzzer sounds at the start and end of the battery check. After the battery check is performed for approximately 5 seconds, the UPS will return to the normal operation (No.1) if there is no problem.
- 38 -
6.2 Operation Mode List
LED
No.
RUN
(green)
15 Lighting
16 Lighting
17 (b)
Slow blink
18 (b)
Slow blink
ALARM
(orange)
(a)
Fast
blink
OVER LOAD
(orange)
BYPASS (orange)
BATTERY
CONDITION
(green/
orange)
(a)
Fast blink
(orange)
Lighting
(orange)
(b)
Slow blink
(green)
Warning
beep
Operational
status
(1) Battery check
error
(1) End of battery
life
(1) Setting error
of rated output
voltage
- Waiting for restart
Remarks
There is possibility that the battery is not fully charged. Perform the battery check manually after operating the UPS 12 hours or more to charge the battery. Since an adequate backup time cannot be assured, evacuate important connection device from the UPS. If the UPS becomes this state again, the battery is out of order. Since it is necessary to replace the battery, contact an agent from which you purchased the UPS or a maintenance company. The recommendation time of battery replacement has come. Since it is necessary to replace the battery, contact an agent from which you purchased the UPS or a maintenance company. Although the alarm (indication and warning beep) can be stopped by pressing the RESET switch for 3 seconds, the alarm (warning beep) is issued again 24 hours later or at the restart. When only the warning beep is stopped by pressing the RESET switch 1 second or more, the alarm (warning beep) of the end of battery life will be issued again at the automatic battery check which is performed every two weeks. A setup of the switch of voltage setting on the back of the UPS is wrong. Use 0 to 4 of the switch of voltage setting. For details on a setup, refer to Chapter 3.4 "Setting up the Output Voltage". The output of the UPS has stopped by setup of the RS-232C communication. After a time specified at the setup passes, the UPS will start automatically, and return to the normal operation (No.1). Also, the UPS can be started up with the RUN/STOP switch.
- 39 -
7 Maintenance
sound)
7.1 Replacing the Battery
Timing of the battery replacement
Damage Replace the battery periodically.
In the following cases, it is the end of battery life. Replace the battery.
When the BATTERY CONDITION LED (orange) on the front of the UPS lights
〈M-UPS050AD2B〉 〈M-UPS075AD2B, M-UPS100AD2B〉
If continuing to use the UPS that the battery life ended, there is fear of a liquid leak of battery, a smoking, and an ignition.
up and a warning beep sounds
Pip-pip­pip-pip・・・
N
U
R
M
R
A
L
A
D
A
O
L
R
E
V
O
A
P
Y
B
B
T
E
S
E
R
S
S
Y
R
E
T
T
A
D
N
O
C
T
N
T
O
I
T
I
K
A
C
B
E
H
C
S
P
U
(continuous
Caution
The BATTERY CONDITION LED (orange) lights up.
When the backup time of the battery has been lowered to 3 minutes or less (at the
rated load)
Battery life is influenced greatly by ambient temperature and the conditions of connection device. If using the UPS in the standard environment and conditions (an ambient temperature of 25 degrees C, and the rated load), replace the battery in approximately 3 years.
)
r
8
a
e
y
(
5
t
4
n
e m
3
e
c
2
a
l
p e
r y
1
r
e
t
t a B
0
25 30 35 40
Ambient temperature of the UPS ()
Relation between the ambient temperature
and the timing of the battery replacement
- 40 -
7.1 Replacing the Battery
The method of battery replacement
Caution
Electric Perform the battery replacement by maintenance personnel. shock There is fear of an electric shock.
Damage Replace the battery with one specified by our company and a
new one.
If using the un-specified battery or mixing an old battery and a new battery, it becomes the cause of a liquid leak of battery, a smoking, an ignition, and the UPS failure and trouble.
Important
This UPS is recyclable.
This UPS uses the small sealed lead storage battery. The small sealed lead storage battery uses expensive and rare resources. However, these precious resources are able to recycle. Cooperate in recycling without disposing of the used battery.
The battery of this UPS can be replaced (hot-swap) without turning off the UPS and connection device (Note). For details, consult with an agent from which you purchased the UPS or a maintenance company.
Note) The UPS performs the bypass operation during hot swapping. In the state of
the bypass operation, even if the abnormalities, such as a power failure, occur at an input power supply, the battery operation cannot be performed.
Use the battery shown in the following list. For the method of purchasing the battery unit, consult with an agent from which you purchased the UPS or a maintenance company.
UPS
model
M-UPS
050AD2B
(5kVA) M-UPS
075AD2B
(7.5kVA)
M-UPS
100AD2B
(10kVA)
UPS
model
Battery for
M-UPS
050AD2B
Battery for
M-UPS
075AD2B
Battery for
M-UPS
100AD2B
Type of
battery unit
RRABU-GX31
Number of
units (Note)
(per UPS)
2 units
Approximately
4 units
Battery unit
Mass
(a unit)
17kg
Battery
capacity
12V, 5Ah
8
Note) It is necessary to replace the battery by the unit.
- 41 -
7 Maintenance
Disposal and storage of battery
Pay enough attention to disposal and storage of the battery. Prevent mixing with a
dry cell, etc. after taking a measure (for example, stick the insulating tape on the terminal) to prevent a short circuit, when taking out the battery in order to discard.
This UPS uses the small sealed lead storage battery as battery. The small sealed lead
storage battery uses expensive and rare resources. However, these precious resources are able to recycle. Cooperate in recycling without disposing of the used battery. If you have any questions, consult with an agent from which you purchased the UPS or a maintenance company.
This mark is the recycle mark of small sealed lead storage battery.
Pb
- 42 -
(continuous sound)
(continuous sound)
7.2 Replacing the Cooling Fan
7.2 Replacing the Cooling Fan
Timing of the cooling fan replacement
Important
Replace the cooling fan periodically.
If continuing to use the UPS that the cooling fan life ended, there is a possibility that the inside temperature of the UPS may get out of the rated specification.
In the following cases, it is the end of cooling fan life. Replace the cooling fan.
When the ALARM LED (orange) and the BYPASS LED (orange) light up, after a
warning beep sounded for 120 seconds
M-UPS050AD2B
The ALARM LED (orange) lights up.
Pi―― (continuance)
M-UPS075AD2B, M-UPS100AD2B
Pi―― (continuance)
N
U
R
M
R
A
L
A
D
A
O
L
R
E
V
O
S
S
A
P
Y
B
T
T
A
B
N
O
C
T
E
S
E
R
Y
R
E
O
I
T
I
D
T
N
T
K
A
C
B
E
H
C
S
P
U
Pip-pip­pip-pip・・・
The BYPASS LED (orange) lights up.
N
U
R
M
R
A
L
A
D
A
O
L
R
E
V
O
S
S
A
P
Y
B
T
T
A
B
N
O
C
T
E
S
E
R
Y
R
E
O
I
T
I
D
T
N
T
K
A
C
B
E
H
C
S
P
U
The ALARM LED (orange) lights up.
Pip-pip­pip-pip・・・
The BYPASS LED (orange) lights up.
At the second battery replacement It is necessary to replace the cooling fan with new one periodically, since the cooling fan
has a life by wear of the bearing. However, since the life of cooling fan may become short according to the use environment, replace the cooling fan early.
- 43 -
7 Maintenance
The method of cooling fan replacement
Caution
Electric shock Injury
Electric shock Perform the cooling fan replacement by maintenance
The cooling fan of this UPS can be replaced (hot-swap) without turning off the UPS and connection device (Note). For details, consult with an agent from which you purchased the UPS or a maintenance company.
Note) Replacement by hot swapping should be performed in a short time. The UPS
starts the bypass operation, if the internal temperature of the UPS rises (out of the rated specification). In the state of the bypass operation, even if an input power failure occurs, the battery operation cannot be performed.
Use the following cooling fan. For the method of purchasing the cooling fan, consult with an agent from which you purchased the UPS or a maintenance company.
Type of cooling fan : Fan for M-UPS050AD2B (RRAF-GX11×1 / RRAF-GX12×1)
Fan for M-UPS075AD2B (RRAF-R1×2 / RRAF-GX12×2) Fan for M-UPS100AD2B (RRAF-R1×2 / RRAF-GX12×2)
Put neither a stick nor a finger into the cooling fan or the vent hole.
There is fear of an electric shock or an injury.
personnel.
There is fear of an electric shock.
- 44 -
7.3 When Not Using the UPS (Storage)
7.3 When Not Using the UPS (Storage)
Work before storage
Important
Do not store the UPS in the following places:
In an outdoor location A place exposed to the elements An extremely humid place and a dusty place A place with corrosive gas or salinity A place subjected to direct sunlight A place near sparks or heating element An extremely hot or cold place or place where the temperature fluctuates
greatly
A place where vibration and a shock are added
1. Charge the battery by operating the UPS 12 hours or more. After charging the
battery, perform the battery check using a battery check function (manual check). For details, refer to Chapter 5.3 "Inspecting the Battery (Battery Check)". The period that can store the battery used for this UPS is approximately 2 months from the state charged fully.
2. Turn off the UPS after turning off the connection device, and turn off the input
breaker on the back of the UPS. For details, refer to Chapter 4.2 "Turning off the UPS".
3. Put the UPS in a box (the box, etc. which was packing the UPS) and store it. If a storage period exceeds two months
Important
If the UPS is not used for a long time, charge the battery every two months.
The battery is charged by operating the UPS. For the battery charging time, refer to Chapter 8.1 "Rated Specification". If the UPS is left without operating for a long time, there is a possibility that the UPS get unusable since the battery becomes an over-discharge state due to self-discharge.
Charge the battery by operating the UPS 12 hours or more every two months. After charging the battery, perform the battery check using a battery check function (manual check). For details, refer to Chapter 5.3 "Inspecting the Battery (Battery Check)". Even if the UPS is not used, the battery is discharged by itself inside the UPS. If leaving the UPS two months or more, there is a possibility that the UPS gets unusable since the battery becomes an over-discharge state.
- 45 -
Peak value: 300% or more of rated effective value (bearing the load
measures for
8 Appendix
8.1 Rated Specification
Model M-UPS050AD2B Rating capacity 5000VA/4000W Voltage 200/208/220/230/240V ± 2% Frequency 50/60Hz (automatic changeover inside the UPS)
At the normal operation Depend on input frequency Frequency
accuracy Number of phase Single-phase two-wire (with a ground terminal) Load condition Linear load or rectified load with a crest factor of up to three times Voltage waveform
distortion factor Overcurrent
AC output
protection Grounding system Un-grounding
Straightforward bypass circuit
Voltage *1 *2 160 to 288V Frequency 50/60Hz ±5% Number of phase Single-phase two-wire (with a ground terminal) Capacity Grounding system Un-grounding or Line to line on a center-earthed
AC input
Power factor 0.97 or more (at the rated operation) Input harmonic current Type Small sealed lead storage battery (long-life battery) Backup time *3 (initial value)
Battery
Nominal voltage 192V Ambient temperature Relative humidity 20 to 95% (no condensation) Noise 50dB(A) max. (at 1m from the front of the UPS)
Others
Cooling method Forced air cooling
Outside dimension W D H Mass Standard UL1778 (-U, -UC type) Applicable standard VCCI CLASS A,
Input Terminal block (L1/R, L2/S : M5 screws)
At the battery operation Within ±0.1%
At the resistance load: 4% or less At the rectified load: 6% or less Effective value: 100% or more
of the crest factor of three)
Thyristor system (changeover time : without instantaneous power interruption) Changeover is impossible at the time of a power failure.
5000VA or less
Based on the Guideline of harmonic restraint general-purpose UPS
Approximately 5 minutes (4000W)
0 to +40C
130 718 434mm 63 (without battery: 29 )
Comply with IEC62040
Ground Terminal block (PE(G) : M5 screw)
External
Output Terminal block (l1/U, l2/V : M5 screws)
connection
- 46 -
Peak value: 300% or more of rated effective value (bearing the load of
8.1 Rated Specification
Model M-UPS075AD2B M-UPS100AD2B Rating capacity 7500VA/6000W 10000VA/8000W Voltage 200/208/220/230/240V ± 2% Frequency 50/60Hz (automatic changeover inside the UPS)
At the normal operation Depend on input frequency Frequency
accuracy
At the battery operation Within ±0.1%
Number of phase Single-phase two-wire (with a ground terminal) Load condition Linear load or rectified load with a crest factor of up to three times Voltage waveform distortion factor Overcurrent
AC output
At the resistance load: 4% or less At the rectified load: 6% or less Effective value: 100% or more
protection
the crest factor of three)
Grounding system Un-grounding Straightforward
bypass circuit
Thyristor system (changeover time : without instantaneous power interruption) Changeover is impossible at the time of a power failure.
Voltage *1 *2 160 to 288V Frequency 50/60Hz ±5% Number of phase Single-phase two-wire (with a ground terminal) Capacity
7500VA or less 10000VA or less
Grounding system Un-grounding or Line to line on a center-earthed
AC input
Power factor 0.97 or more (at the rated operation) Input harmonic
Based on IEC61000-3-12
current Type Small sealed lead storage battery (long-life battery) Backup time *3 (initial value)
Battery
Nominal voltage 192V Ambient
Approximately 8 minutes (6000W)
0 to +40C
Approximately 5 minutes (8000W)
temperature Relative humidity 20 to 95% (no condensation) Noise 55dB(A) max. (at 1m from the front of the UPS)
Others
Cooling method Forced air cooling
Outside dimension
130 718 434mm
W D H Mass
127 (without battery: 59 )
Standard UL1778 (-U, -UC type) Applicable standard VCCI CLASS A,
Comply with IEC62040
Input Terminal block (L1/R, L2/S : M8 screws) Ground Terminal block (PE(G) : M8 screw)
External
Output Terminal block (l1/U, l2/V : M8 screws)
connection
*1 Operation of UPS according to an input voltage
Low voltage detection : 144V return : 154V
Overvoltage detection : 300V return : 290V *2 Rated voltage of UL standard product is 200, 208, 220, 230, or 240V. *3 The backup time is the test result and is not a guaranteed value.
- 47 -
8 Appendix
8.2 Additional Description for UL Type
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for UPS GX200 series Models that should be followed during installation and maintenance of the UPS and batteries.
Internal battery voltage is 192 V dc. This unit intended for installation in a controlled environment and
maximum temperature is 40 (temperature controlled, indoor area free of conductive contaminants).
Servicing of batteries should be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
This UPS is intended for use in Japan-domestic. For All Models, field wiring connection must be made by a UL and CSA
Listed closed-loop terminal connector sized for the wire gauge involved and fully insulated up to terminals. Connector must be fixed using the crimp tool specified by the connector manufacturer. Closed-loop terminal is shown in table 1 and table 2 (made by Japan Solderless Terminal).
Use 75 Copper conductors. Wire size and tightening torque are shown in table 1 and table 2. Circuit diagrams are shown by figure 1 and figure 2. Circuit Breaker (UL Listed Inverse-time Circuit Breaker) is not provided
on the UPS as shipped. All Models must connect Circuit Breakers for use with the UPS. The rated tripping current of the Circuit Breaker (2 pole type) is as follows:
Table 1. Input rating, wire size, torque, external input circuit breaker size
INPUT & GROUND
MODEL
M-UPS050AD2B-U M-UPS075AD2B-U M-UPS100AD2B-U
Table 2. Output rating, wire size, torque, external output circuit breaker size
MODEL
Vin(V) Iin(A)
200,208 220,230
240
Vout(V) Iout(A)
25 10 R5.5-5 2.0 AC240 40
37.5 8 R8-8 5.5 AC240 60 50 6 R14-8 5.5 AC240 75
WIRE
SIZE
AWG
OUTPUT
WIRE
SIZE AWG
Type of
Closed-loop
Terminal
Type of
Closed-loop
Terminal
TIGHTENING
TORQUE
(Nm)
TIGHTENING
TORQUE
(Nm)
2POLE CIRCUIT
BREAKER
V A
2POLE CIRCUIT
BREAKER
V A
M-UPS050AD2B-U M-UPS075AD2B-U M-UPS100AD2B-U
200,208,
220,230
240
25 10 R5.5-5 2.0 AC240 40
37.5 8 R8-8 5.5 AC240 60 50 6 R14-8 5.5 AC240 75
- 48 -
8.2 Additional Description for UL Type
AC Input/Output
Terminal Block
L1/R
L2/S
PE(G)
Figure 1 - Circuit diagram of Models M-UPS050AD2B-U
AC Input/Output
Terminal Block
L1/R
S1
S1
Boost Chopper
Dual Conveter
Dual Conveter
AC Input/Output
Terminal Block
l1/U
l2/V
AC Input/Output
Terminal Block
l1/U
L2/S
PE(G)
Boost Chopper
Figure 2 - Circuit diagram of Models M-UPS075AD2B-U and
Models M-UPS100AD2B-U
l2/V
- 49 -
8 Appendix
DANGER
Risk of electric shock Do not touch uninsulated battery terminal.
WARNING
Risk of electric shock
Do not remove the cover for any reason. There are no user-serviceable parts
inside the UPS. Refer servicing to qualified service personnel.
CAUTION
■Dont use this equipment in life support applications where failure of this
equipment can reasonably be expected to cause the failure of the life support equipment or to significantly effect its safety or effectiveness.
■Risk of electric shock
Battery and cooling fan replacement should be performed only authorized
servicing personnel.
The UPS has an internal energy source (the battery). The output may be
energized when the unit is not connected to an AC power line.
Terminal marked PE(G) is intended for connection of the Protective
Earthing (Grounding) conductor(s). This earth connection is essential before connecting supply conductors. Also ensure the reliability of this connection during any servicing, including connection of protective earthing (grounding) conductors to the output (load).
Capacitor stores hazardous energy. Do not remove cover until 7 minutes
after disconnecting all sources of supply.
For M-UPS050AD2B, 2 pole circuit breaker is not provided on this UPS. If
this UPS installs, removes or does any services, for disconnecting all sources of supply, be off the external input circuit breaker.
■For ALL Models, to reduce the risk of fire,
・
Need to provide External Disconnect / Overcurrent Protective Device for the AC input and the AC output. -for example ,an UL Listed branch circuit breaker with suitable ratings could provide both functions (disconnect and overcurrent protection).
・
Suitable rating of input and output circuit breakers are shown in Table1 and Table2.
■Risk of explosion if battery is replaced by an incorrect type. Dispose of
used batteries according to the instructions.
■Do not dispose of batteries in a fire. The batteries may explode.
■Do not open or mutilate batteries. Released electrolyte is harmful to the
skin and eyes. It may be toxic.
- 50 -
8.2 Additional Description for UL Type
■A battery can present a risk of electrical shock and high short-circuit
current. The following precautions should be observed when working on batteries:
a) Remove watches, rings, or other metal objects. b) Use tools with insulated handles. c) Wear rubber gloves and boots. d) Do not lay tools or metal parts on top of batteries. e) Disconnect charging source prior to connecting or
disconnection battery terminals.
f) Determine if battery is inadvertently grounded.
If inadvertently grounded, remove source from ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance (applicable to equipment and remote battery supplies not having a grounded supply circuit).
- 51 -