This manual is updated as new information and models are released. Visit our website for the latest manual.
FOR YOUR SAFETY
Do Not Store or use gasoline or other
flammable vapors and liquids in the vicinity
of this or any other appliance.
*8197443*
Part Number: FRY_SM_8197443 02/2018
NOTICE
IF, DURING THE WARRANTY PERIOD, THE CUSTOMER USES A PART FOR THIS FRYMASTER EQUIPMENT
OTHER THAN AN UNMODIFIED NEW OR RECYCLED PART PURCHASED DIRECTLY FROM FRYMASTER
DEAN, OR ANY OF ITS FACTORY AUTHORIZED SERVICERS, AND/OR THE PART BEING USED IS MODIFIED
FROM ITS ORIGINAL CONFIGURATION, THIS WARRANTY WILL BE VOID. FURTHER, FRYMASTER DEAN
AND ITS AFFILIATES WILL NOT BE LIABLE FOR ANY CLAIMS, DAMAGES OR EXPENSES INCURRED BY THE
CUSTOMER WHICH ARISE DIRECTLY OR INDIRECTLY, IN WHOLE OR IN PART, DUE TO THE
INSTALLATION OF ANY MODIFIED PART AND/OR PART RECEIVED FROM AN UNAUTHORIZED SERVICER.
NOTICE
This appliance is intended for professional use only and is to be operated by qualified personnel
only. A Frymaster Authorized Servicer (FAS) or other qualified professional should perform
installation, maintenance, and repairs. Installation, maintenance, or repairs by unqualified
personnel may void the manufacturer’s warranty. See Chapter 1 of this manual for definitions of
qualified personnel.
NOTICE
This equipment must be installed in accordance with the appropriate national and local codes of the
country and/or region in which the appliance is installed. See NATIONAL CODE REQUIREMENTS in
Chapter 2 of this manual for specifics.
NOTICE TO U.S. CUSTOMERS
This equipment is to be installed in compliance with the basic plumbing code of the Building
Officials and Code Administrators International, Inc. (BOCA) and the Food Service Sanitation Manual
of the U.S. Food and Drug Administration.
NOTICE
Drawings and photos used in this manual are intended to illustrate operational, cleaning and
technical procedures and may not conform to onsite management operational procedures.
NOTICE TO OWNERS OF UNITS EQUIPPED WITH CONTROLLERS
U.S.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two
conditions: 1) This device may not cause harmful interference, and 2) This device must accept any
interference received, including interference that may cause undesired operation. While this device
is a verified Class A device, it has been shown to meet the Class B limits.
CANADA
This digital apparatus does not exceed the Class A or B limits for radio noise emissions as set out by
the ICES-003 standard of the Canadian Department of Communications.
Cet appareil numerique n’emet pas de bruits radioelectriques depassany les limites de classe A et B
prescrites dans la norme NMB-003 edictee par le Ministre des Communcations du Canada.
NOTICE
The instructions in this manual for using a bulk oil system for filling and discarding oil are for an RTI
system. These instructions may not be applicable to other bulk oil systems.
WARNING
After installation of a gas fryer and after any maintenance to the gas system of a gas fryer-manifold,
valve, burners, etc. – check for gas leaks at all connections. Apply a thick soapy solution to all
connections and ensure there are no bubbles. There should be no smell of gas.
DANGER
Improper installation, adjustment, maintenance or service, and unauthorized alterations or
modifications can cause property damage, injury, or death. Read the installation, operating, and
service instructions thoroughly before installing or servicing this equipment.
DANGER
Adequate means must be provided to limit the movement of this appliance without depending upon
the gas line connection. All fryers equipped with casters must be stabilized by installing restraining
chains. If a flexible gas line is used, an additional restraining cable must be connected at all times
when the fryer is in use.
DANGER
The front ledge of this appliance is not a step! Do not stand on the appliance. Serious injury can
result from slips or contact with the hot oil.
DANGER
Do not store or use gasoline or other flammable liquids or vapors in the vicinity of this or any other
appliance.
DANGER
This product contains chemicals known to the state of California to cause cancer and/or birth
defects or other reproductive harm.
Operation, installation, and servicing of this product could expose you to airborne particles of
glasswool or ceramic fibers, crystalline silica, and/or carbon monoxide. Inhalation of airborne
particles of glasswool or ceramic fibers is known to the State of California to cause cancer.
Inhalation of carbon monoxide is known to the State of California to cause birth defects or
other reproductive harm.
WARNING
Use caution and wear appropriate safety equipment to avoid contact with hot oil or surfaces that
may cause severe burns or injury.
DANGER
Keep all items out of drains. Closing actuators may cause damage or injury.
Table of Contents
Section 1: Service Procedures
1.1 FQ4000 Menu Summary Trees ......................................................................................................... 1-1
1.1.1 FQ4000 Menu Tree General Market/Burger King ................................................................. 1-1
1.1.2 FQ4000 Information Statistics Menu Tree General Market/Burger King .......................... 1-2
1.1.3 FQ4000 Menu Tree Taco Bell ................................................................................................... 1-3
1.1.4 FQ4000 Information Statistics Menu Tree Taco Bell ............................................................ 1-4
1.24.7 Full Vat Direct Spark Wiring Diagram with Optional OIB Sensor .............................. 1-67
1.24.8 Dual Vat Direct Spark Wiring Diagram with Optional OIB Sensor ............................ 1-68
FQGLA-T SERIES FILTERQUICK GAS FRYERS
CHAPTER 1: SERVICE PROCEDURES
1.1 FQ4000 Menu Summary Trees
1.1.1 FQ4000 Menu Tree General Market/Burger King
Reflected below are the major programming sections in the FQ4000 and the order in which the headings will be found
in the controller.
Filtration Menu
Quick Filter
Clean and Filter (with OQS)
OQS-Filter
Dispose
Fill Vat from Pan
Fill Vat from Bulk (Bulk Only)
Pan to Waste (Bulk Only)
Drain to Pan
Clean
Polish
Home Button
Crew Mode (Cooking Mode)
Menus (1650)
Create New
Recipes (1650)
Product Name
Temp
Cook Time
Sensitivity
Hold Timer
Shake 1
Shake 2
Filter
Settings
Manager (1656)
Language
Date & Time
F° to C°/ C° to F° (Toggles Temperature Scale)
Sound
Filter Attributes
Energy Savings (Enabled, Temperature, Time)
Lane Assignments (# of Baskets)
Brightness
Screen Saver
Alarm Attributes
Temperature
Oil Dragout
Basket Lift
Service (3000)
Locale (CE / Non-CE)
Energy Type (Gas / Electric)
Vat Type (Full / Split)
Oil System Type (JIB / Bulk)
Waste Oil (None / Bulk/Front Dispose)
Auto Top Off Vat (On / Off)
ATO Delay Time
ATO Type (Auto, Push Button, Both)
Filtration Time Settings
OQS Setup
Basic Auto Filter (Enable/Disable)
Primary
Secondary
Volume
Tone
Filter After (Cooks)
Filter Time (Hours)
Filter Off Time
Filtration Off Settings
Clean (Cold/Hot)
Shake Alarm Mode (Auto / Manual)
Hold Alarm Mode (Auto / Manual)
Alarm Timer (Shake Timer / Hold Timer)
Basket Configuration
OQS (Enable/Disable)
Oil Type (Oil Curve)
Display Type (Number/Text)
Discard Now (TPM Value)
Discard Soon (TPM Offset Value)
Dispose Delay Timer
Factory Menu (Resets Product Recipes)
Bad CRC (Resets Alert)
Recovery Fault Call Service (Resets Alert)
Reset Factory Resets (Resets to Factory Default)
Reset Report Card (Resets Report Card)
F° to C°/ C° to F° (Toggles Temperature Scale)
Filter Stats Data (Clears Filter Stats)
E-Log (Clears E-Log Errors)
1-1
1.1.2 FQ4000 Information Statistics Menu Tree General Market/Burger King
Reflected below are the information statistics in the FQ4000 and the order in which the headings will be found in the
controller.
1-2
1.1.3 FQ4000 Menu Tree Taco Bell
Reflected below are the major programming sections in the FQ4000 and the order in which the headings will be found
in the controller.
1-3
1.1.4 FQ4000 Information Statistics Menu Tree Taco Bell
Reflected below are the information statistics in the FQ4000 and the order in which the headings will be found in the
controller.
1-4
1.2 FQ4000 Password Codes
Press the HOME button to enter MENUS, RECIPES, SETTINGS or SERVICE menus.
1650 – MENUS, RECIPES,
1656 – SETTINGS (MANAGER), SERVICE (MANAGER)
3000 – SETTINGS (SERVICE), SERVICE (SERVICE) Enter Tech Mode
9000 – Component Check [SETTINGS (SERVICE), SERVICE (SERVICE) Enter Tech Mode]
The following code is entered when prompted to do so.
1111 – Reset SERVICE REQUIREDMessage – Enter when the issue is fixed and prompted to enter
code.
1.3 Service Required Errors
A SERVICE REQUIRED error with a description of the error displays on the controller. After YES is pressed the
alarm is silenced. The controller displays an error message from the list below three times with the location of the
error. Then the controller displays SYSTEM ERROR FIXED? YES/NO. If yes is chosen, enter code 1111. If NO
is chosen, the system returns to cook mode if possible for 15 minutes, then redisplays error until issue is fixed.
1.4 Error Log Codes
To access the error log, press the home button. Press the service button. Press the manager button. Enter 1656 and
press the check button. Press the E-log button. The ten most recent errors are listed from top to bottom, with the
top error being the most recent error. A “G” indicates a global error such as a filtration error. Side specific errors
in split vats are indicated by L for left or R for right. Pressing the left down arrow allows scrolling through the
errors. If no errors are present the screen will be blank.
Code ERROR MESSAGE EXPLANATION
E13
E16
E17
E18
E19
E25
E27
E28
E29
E32
E33
E34
E35
E36
E37
E39
E41
TEMPERATURE PROBE FAILURE TEMP Probe reading out of range
HIGH LIMIT 1 EXCEEDED High limit temperature is past more than 410°F
(210°C), or in CE countries, 395°F (202°C)
HIGH LIMIT 2 EXCEEDED High limit switch has opened.
HIGH LIMIT PROBLEM
DISCONNECT POWER
Vat temperature exceeds 460°F (238°C) and the
high limit has failed to open. Immediately
disconnect power to the fryer and call service.
HEATING FAILURE – XXX F or XXX C Heating Control latch circuit failed.
Heat Contactor failed to latch.
HEATING FAILURE - BLOWER The air pressure switch(s) failed to close.
HEATING FAILURE - PRESSURE SWITCH -
The air pressure switch has failed closed.
CALL SERVICE
HEATING FAILURE – XXX F or XXX C The fryer has failed to ignite and has locked out the
ignition module.
TOP OFF PROBE FAILURE - CALL SERVICE ATO RTD reading out of range
DRAIN VALVE NOT OPEN - FILTRATION AND
TOP OFF DISABLED - CALL SERVICE
DRAIN VALVE NOT CLOSED - FILTRATION
AND TOP OFF DISABLED - CALL SERVICE
RETURN VALVE NOT OPEN - FILTRATION
AND TOP OFF DISABLED - CALL SERVICE
RETURN VALVE NOT CLOSED - FILTRATION
AND TOP OFF DISABLED - CALL SERVICE
VALVE INTERFACE BOARD FAILURE -
FILTRATION AND TOP OFF DISABLED -
Drain valve was trying to open and confirmation is
missing
Drain valve was trying to close and confirmation is
missing
Return valve was trying to open and confirmation is
missing
Return valve was trying to close and confirmation is
missing
Valve Interface Board connections lost or board
failure.
CALL SERVICE
AUTOMATIC INTERMITTENT FILTRATION
AIF (VIB Probe) RTD reading out of range.
PROBE FAILURE - FILTRATION DISABLED CALL SERVICE
CHANGE FILTER PAD 25 hour timer has expired or dirty filter logic has
activated.
OIL IN PAN ERROR The system detects that oil may be present in the
filter pan.
1-5
Code ERROR MESSAGE EXPLANATION
E42
E43
E44
E45
E46
E51
E52
E53
E55
E62
E63
E64
E65
E66
E67
E68
E69
E70
E71
E72
E73
E74
E75
E76
E81
CLOGGED DRAIN (Gas) Vat did not empty during filtration
OIL SENSOR FAILURE - CALL SERVICE Oil level sensor may have failed.
RECOVERY FAULT Recovery time exceeded maximum time limit.
RECOVERY FAULT – CALL SERVICE Recovery time exceeded maximum time limit for two
or more cycles.
SYSTEM INTERFACE BOARD 1 MISSING CALL SERVICE
DUPLICATE BOARD ID - CALL SERVICE Two or more controllers have the same location ID.
USER INTERFACE CONTROLLER ERROR CALL SERVICE
CAN BUS ERROR - CALL SERVICE Communications are lost between boards.
SYSTEM INTERFACE BOARD 2 MISSING CALL SERVICE
SLOW HEATING FAILURE XXXF OR XXXC CHECK ENERGY SOURCE - CALL SERVICE
RATE OF RISE Rate of rise error occurred during a recovery test.
FILTRATION INTERFACE BOARD FAILURE -
FILTRATION AND TOP OFF DISABLED CALL SERVICE
CLEAN OIB SENSOR – XXX F OR XXX C CALL SERVICE
DRAIN VALVE OPEN – XXXF OR XXXC Drain valve is opened during cooking.
SYSTEM INTERFACE BOARD NOT
CONFIGURED - CALL SERVICE
OIB FUSE TRIPPED – CALL SERVICE The VIB board OIB fuse has tripped and didn’t
RECIPES NOT AVAILABLE The controller has not been programmed with
OQS TEMP HIGH Oil temperature is too high for a valid OQS reading.
OQS TEMP LOW Oil temperature is too low for a valid OQS reading.
TPM RANGE LOW The TPM is too low for a valid OQS reading. This
TPM RANGE HIGH The TPM reading is too high for a valid OQS
OQS ERROR The OQS has an internal error. If issue continues
OQS AIR ERROR The OQS is detecting air in the oil. Check the O-
OQS ERROR The OQS sensor has a communication error. Check
SAFE MODE FAILURE ERROR The system has detected the fryer is not heating
SIB board 1 connection lost or board failure.
The controller has an unknown error.
SIB board 2 connection lost or board failure.
The vat is not heating properly.
Filtration Interface Board connections lost or board
failure.
Gas -The oil is back sensor does not detect oil.
Clean optional oil sensor.
Controller is turned on when the SIB board is not
configured.
reset.
product recipes. Replace controller with factory
programmed controller.
Filter at a temperature between 300ºF (149ºC) and
375ºF (191ºC).
Filter at a temperature between 300ºF (149ºC) and
375ºF (191ºC).
may also be seen with fresh new oil. The incorrect
oil type may be selected in the setup menu. The
sensor may not be calibrated for the oil type. See oil
type chart in instruction document 8197316. If issue
continues contact an FAS.
reading. Dispose the oil.
contact an FAS.
rings and check/tighten prescreen filter to ensure no
air is entering the OQS sensor. If issue continues
contact an FAS.
connections to the OQS sensor. Power cycle the
entire fryer battery. If issue continues contact an
FAS.
properly due to low oil conditions. Ensure the fryer
has oil to the bottom fill line or higher. If not, add oil
to the bottom fill line.
1-6
1.5 Component Check
The FQ4000 controller has a function to check the major components and their status.
With the controller soft powered OFF, press the HOME button. Select Service, Service, Enter 9000, Select Tech
Modes, scroll down and select Component Check.
The component name is above each button. The status of the component is below the function. Pressing the
button will change the status of the function to what is stated on the button. If the button is shaded that function is
not available unless that function is enabled (such as bulk). The JIB reset button and Waste Tank full only
displays the status of the switch.
Pressing the home button to exit the function will display driving valves to ensure all valves return to home state.
Once completed the controller will display FILL VAT FROM DRAIN PAN? YES NO. Press YES to ensure that
any oil in the filter pan is returned to the vat.
1-7
1.6 Functional Description
FQGLA-T Series gas fryers contain a welded stainless steel frypot that is directly heated by a high efficiency
infrared burner system, requiring approximately 43% less energy than conventional burners to cook the same
volume.
Self-contained combustion chambers (referred to as “burners”) are fitted into rails attached to the sides of the
frypot, one on each side. Each combustion chamber is fitted with special ceramic tiles that are heated by the
burning of a forced air/gas mixture. The tiles transfer heat to the frypot by means of infrared radiation,
providing much more constant and uniform heat dispersion over the surface of the frypot than do
conventional burners. Because less heat is lost to the atmosphere in the process, compared to “open-burner”
designs, less fuel is required to achieve and maintain a given frypot temperature.
In full-vat units, gas flow to both of the burners is regulated by one electromechanical gas valve. In dual-vat
units, each burner has its own valve. All fryers in this series are equipped with 24 VAC gas valve systems,
and all are configured with electronic ignition.
1.7 The Electronic Ignition System
An ignition module mounted below the component box (located
behind the control panel) is connected to an ignitor assembly at
the burner. The ignition module performs four important
functions: it provides fuse protection for the 24-volt circuit,
provides an ignition spark, supplies voltage to the gas valve, and
proofs the burner flame. The module contains a four second
Out to Oil
Level Sensor
and Gas Valve
To Alarm
Inside the Ignition
Module
time delay circuit and a coil that activates the gas valve. All full
and dual vat fryers use two single-spark modules
.
The ignitor assembly consists of a spark rod, an enrichment
tube, and a flame sensor
.
At start-up, the power switch on the touchscreen controller is
placed in the ON position, supplying approximately 24 VAC to
24 V +
GND
Coil
TD
H
V
the heat-control circuitry in the Smart Interface Board and to one
side of the heat relay coils on the Smart Interface Board. If the
Ignition WireFlame Sensor
resistance in the temperature probe indicates the temperature in
the frypot is below 180ºF (82ºC), the melt cycle function is activated where a timer activates for six seconds
and deactivates for 24 seconds. If the temperature is 180ºF (82ºC) or above, the melt cycle is bypassed. In
either case, ground is supplied to the other leg of the heat relay coils, which closes electronic switches in the
24 VAC circuit to provide current to the ignition module. Circuitry in the ignition module sends 24 VAC to
the gas valve via a normally closed high-limit switch, and an oil level sensor which is controlled by
electronics inside an egg shaped housing and a 7 second time delay relay board. Simultaneously, the module
causes the ignitor to spark for four seconds to light the burner. A flame sensor verifies the burner ignition by
measuring the flow of micro amps through the flame. If the burner does not light (or is extinguished), current
to the ignition module is cut, the gas valve closes, and the ignition module “locks out” until the power switch
is turned off and then back on. A probe monitors the temperature in the frypot. When the programmed
setpoint temperature is reached, resistance in the probe causes the heat cycle circuitry in the SIB board to cut
off current flow through the heat relay. This in turn cuts off the 24 VAC to the ignition module, causing the
gas valve to close.
1-8
1.8 Smart Interface Board (SIB)
All fryers in this series have a smart interface board
(SIB) located in the component box behind the
controller panel. The SIB board provides a link
between the controller and the fryer’s individual
components without requiring excessive wiring, and
executes commands from one central point.
SMART INTERFACE BOARD LED
DIAGNOSTIC LIGHTS
LED 1
LED 2
LED 3
LED 4
LED 6
LED 7
24VAC Heat Relay
12VDC to Controller
24VAC Latch Relay
5VDC to probes and switches
3.3VDC to Micro Processor
Communication to/from Micro Processor
K2 is a single-pole-double throw (SPDT) relay that
supplies 24VAC to the ignition and gas valve circuits. The relays on this board are soldered to the board. If a
relay fails, the board must be replaced. K1 is a single-pole-double throw (SPDT) relay that supplies voltage
through the high limit and the optional air pressure switch.
The SIB LEDs (labeled LED1 through LED7) are arrayed around the board to assist in troubleshooting.
12VDC should be lit and bright at all times.
If LED is dim then something is pulling
voltage down. Short to ground on 12VDC
circuit will cause dim LED.
5VDC should be lit and bright at all
times. If LED is dim then something is
pulling voltage down. Short to ground
on 5VDC circuit will cause dim LED.
When UI is soft
powered on this
Latch Relay LED
will come on first
confirming high
limit is closed.
The blower will
then come on
and prove the air
switch. The relay
is a true latch
circuit and when
broken or turned
off the heat relay
will also turn off.
When UI calls for HEAT this LED will
come on with the heat relay only after
latch relay has been latched in and
AIR switch has been proven. This LED
Blinking red LED, (Heart Beat).
This LED should be blinking and
bright at all times when board is
powered. The other green LED’s
being dim or off will cause this
LED to be off.
3.3VDC LED should be lit and
bright at all times. If dim then
something is pulling voltage
down. Short to ground on
3.3VDC circuit will cause dim
LED.
NOTE: Refer to Section 1.16.1 for troubleshooting flowchart.
The charts on pages 1-8 and 1-9 illustrate current flow through the board, and the table at the top of page 1-10
identifies frequently used test points.
1-9
1.8.1 Full Vat flow through the SIB board
MVPV
GAS VALVE
ST
IGNITION
1
Pin 3
VALVE
Pin 11
SPARK
MODULE
Pin 8
24V Pin 6
SENSE
GND Pin 5
MODULE GROUND
st
HEAT 24VAC OUT
1
1
2
Optional
ALARM Pin 7
MODULE GAS VALVE 24VAC
MODULE ALARM 24VAC
st
st
AIR OUT 24VAC
1
1
34567
AIR PROVER
SWITCH
AIR IN 24VAC
10111214151720
nd
MODULE POWER 24VAC
2
nd
ND
MODULE GAS VALVE 24VAC
2
IGNITION
MODULE
2
nd
MODULE GROUND
2
Pin 11
SPARK
13
-12VDC AC BLOWER RELAY
21
Pin 3
VALVE
Pin 8
SENSE
24V Pin 6
GND Pin 5
+12VDC AC BLOWER RELAY
22
J2
HEAT
RELAY
FULL VAT
IGNITION MODULES
TWO SINGLE SPARK
LATCH
CIRCUIT
1345678
24VAC
HIGH
LIMIT
AIR OUT 24VAC
HIGH LIMIT 24VAC
HIGH LIMIT RETURN 24VAC
AIR BYPASS
AIR IN 24VAC
JUMPER IF AIR
PROVER SWITCH IS
BOARD
(SIB)
SMART
INTERFACE
SENSORS
J1
101112
9
HOOD RELAY 12VDC
NOT INSTALLED
14
16
JUMPER
20
17
18
JUMPER
1-10
1.8.2 Split Vat flow through the SIB board
1-11
1.8.3 Frequently Used Test Points for SIB (Smart Interface Board)
NOTE: DO NOT CHECK WITH HARNESSES UNPLUGGED AS SHORTING THE PINS MAY
OCCUR WHICH WILL DAMAGE THE BOARD.
FREQUENTLY USED TEST POINTS FOR INTERFACE BOARD 1085980
Meter
Test
24VAC Power to SIB 50VAC Scale 1 on J1 and GROUND 22-28
12VDC Power to Controller 50VDC Scale 7 and 8 on J6 12-18
24VAC Power to Right Module 50VAC Scale 1 on J2 and GROUND 22-28
24VAC Power to Left Module (if present) 50VAC Scale 12 on J2 and GROUND 22-28
120 VAC Power 250VAC Scale Blower Connections 110-125
120 VAC Power to Blowers 250VAC Scale Blower Connections 110-125
24VAC Power to High-Limit 50VAC Scale 3 on J1 and GROUND 22-28
Probe Resistance R x 1000 OHMS Disconnect and test across probe leads **
Probe Isolation R x 1000 OHMS 2 on Probe Connector and GROUND ***
High-Limit Continuity R x 1 OHM 3 on J1 and 4 on J1 0
** See Probe Resistance Chart in section 1.17.
*** 5 mega-Ohms or greater.
Pins Results Setting
1.8.4 SIB (Smart Interface Board) Troubleshooting
Problem Probable Causes Corrective Action
A. J1 connection unplugged
No power to SIB board
SIB BOARD 1
MISSING displayed on
the controller.
SIB BOARD 2
MISSING displayed on
the controller.
SIB NOT
CONFIGURED
displayed on the
controller.
B. Fuse blown.
C. Transformer malfunction
A. Loose wire connection.
A. Loose wire connection. A. Ensure all wiring harnesses are securely
A. SIB board not configured A. Replace the SIB board.
A. Check to ensure J1 on front of SIB board
is fully locked into connector.
B. Ensure fuse located at the bottom of the
control box is not blown and cap is
securely tightened.
C. Check that proper voltage is present at
transformer. See table in section 1.8.3.
A. Ensure the connector is securely attached
to plug J6 on the SIB board.
connected between J9 and J10 between
SIB boards.
1-12
1.8.5 SIB (Smart Interface Board) Pin Positions and Harnesses
NOTE: DO NOT CHECK WITH HARNESSES UNPLUGGED (except ATO and Temp Probes) AS SHORTING THE PINS
MAY OCCUR WHICH WILL DAMAGE THE BOARD.
Connector From/To Harness #
From Transformer
To High Limit
From High Limit
To Air Switch Jumper
From Air Switch Jumper
J1
From Drain Switch Jumper
J2
J3 ATO Probe 8263286
J6 Controller
J7
J8
P-Bus Power Communication
J9
P-Bus Power Communication
J10
To Hood Relay
Left SIB Jumper
Left SIB Jumper
To Drain Switch Jumper
To 24VAC Ignition Module
From Gas Valve
From Gas Valve
From Gas Valve
To Air Switch
From Air Switch
To 2nd Ignition Module
From 2nd Ignition Module
From 2nd Ignition Module
Valve
To AC Blower Relay
To AC Blower Relay
C-Bus Harness
C-Bus Harness or
Network Resistor
(pins 2 & 3)
from SIB to VIB or between
SIB’s
RJ11
from SIB to VIB or between
SIB’s
RJ11
8075888 Full
8075886 Split
8075549 or
8075551
8075549 or
8075551 or
(8075632
Resistor)
8075555 or
8075553
8075555 or
8075553
Pin
# Function Voltage
1 24VAC Input
2 Ground 3 24VAC Out
4 24VAC Input
5 24VAC Out
6 24VAC Input
9 12VDC Out
10
11
14 24VAC Input
16
17 Ground 18 5VDC Out
20 24VAC Out
1 24VAC Out
2 Ground
3 Alarm In
4 24VAC In
5 24VAC Out
6 2VAC In
11
12 24VAC Out
13 Ground
14 24VAC In
15
21 AC Blower Relay
22 AC Blower Relay
1 Ground Yellow
2 RTD 3.3VDC Red
3
1 C-BUS + 5VDC
2 C-BUS - 5VDC
3 5VDC 5VDC
4 RS485 - 5VDC
5 RS485 + 5VDC
6 Signal Ground
7 12VDC 12VDC
8 Signal Ground
1 5VDC+ +5VDC
2 CAN High
3 CAN Low
4 Ground
1 5VDC+ +5VDC
2 CAN High
3 CAN Low
4 Ground
1 Ground
2 P-BUS power +5VDC
3 Modbus RS485 B
4 Modbus RS485 A
5 Signal ground
6 P-BUS power +12VDC
1 Ground
2 P-BUS power +5VDC
3 Modbus RS485 B
4 Modbus RS485 A
24VAC Orange
Blue
24VAC Orange
24VAC Blue
24VAC Gray
24VAC Gray
12VDC Purple
Yellow
Brown
24VAC Blue
Blue
Purple
5VDC Purple
24VAC Orange
24VAC Red
Green
24VAC Yellow
24VAC Orange
24VAC Orange
24VAC Blue
Blue
24VAC Red
Green
24VAC Orange
Orange
-12VDC Black
+12VDC Yellow
Wire
Color
1-13
Connector From/To Harness #
J11 Cooking Probe 8263285
1.9 Thermostats
Pin
# Function Voltage
5 Signal ground
6 P-BUS power +12VDC
1 Ground Yellow
2 Probe 3.3VDC Red
Wire
Color
The fryers are equipped with temperature probes located on the front centerline of each frypot (dual-vat frypots
have two probes, one in each vat). In this type of thermostat, the probe resistance varies directly with the
temperature. That is, as the temperature rises, so does resistance, at a rate of approximately 2 ohms for every 1º
F. Circuitry in the controller monitors the probe resistance and controls burner firing when the resistance
exceeds or falls below programmed temperatures (set points).
The fryers are also equipped with a high-limit thermostat. In the event that the fryer fails to properly control the
oil temperature, the high-limit thermostat prevents the fryer from overheating to the flash point. The high-limit
thermostat acts as a normally closed power switch that opens when exposed to temperatures above 425ºF to
450ºF (218ºC to 232ºC). The different types of high limit thermostats have different part numbers for CE and
Non-CE models, and are not interchangeable.
1.10 Accessing Fryers for Servicing
DANGER
Moving a fryer filled with oil may cause spilling or splattering of the hot liquid. Follow
the Drain to Pan instructions in Chapter 5 of the FQGLA-T Installation and Operation
Manual before attempting to relocate a fryer for servicing.
1. Shut off the gas supply to the unit. Unplug the power cords. Disconnect the unit from the gas supply.
2. Remove any attached restraining devices and relocate the fryer for service accessibility.
3. After servicing is complete, reconnect the unit to the gas supply and turn on gas supply, reattach restraining
devices, and plug in the electrical cords. NOTE: To ensure the safe and efficient operation of the fryer
and hood, the electrical plug for the 100-120 volt line, which may power the hood, must be fully
engaged and locked in its pin and sleeve socket.
1.11 Cleaning the Gas Valve Vent Tube
1. Set the fryer power switch and the gas valve to the OFF position.
2. Carefully unscrew the vent tube from the gas valve. NOTE: The vent tube may be straightened for ease of
removal.
3. Pass a piece of ordinary binding wire (.052 inch diameter) through the tube to remove any obstruction.
4. Remove the wire and blow through the tube to ensure it is clear.
5. Reinstall the tube and bend it so that the opening is pointing downward.
1-14
1.12 Checking the Burner Manifold Gas Pressure
1. On non-CE fryersonly ensure that the gas valve knob is in the OFF position.
Honeywell
ON
OFF
2.Remove the pressure tap plug from the gas valve assembly.
Pressure Tap Plug
Typical Non-CE
Valve Assembly
Typical CE Valve
Assembly
3. Insert the fitting for a gas pressure-measuring device into the pressure tap hole.
4. On non-CE fryers only, place the gas valve in the ON position
5. Place the fryer power switch in the ON position. When the burner has lit and burned steadily for at least
one minute, compare the gas pressure reading to the pressure for the corresponding gas in the appropriate
table on the following page. The tables on the following page list the burner manifold gas pressures for each
of the gas types that can be used with this equipment.
6. To adjust the burner gas pressure, remove the cap from the gas valve regulator and adjust to the correct
pressure.
Non-CE
Valve
GAS VALVE REGULATOR CAP
7. Place the fryer power switch (and the gas valve in non-CE fryers) in the OFF position. Remove the fitting
from the pressure tap hole and reinstall the pressure tap plug.
CE
Valve
1-15
Non-CE Standard for Gas Pressure
Fryer Model FQGLA30-T
Gas Type Nat
(Natural)
Incoming Min Pressure
6/1.49/14.9311/2.74/27.37
LP
(Propane)
WC/kPa/mbar
Incoming Max Pressure
14/3.48/34.8414/3.48/34.84
WC/kPa/mbar
Orifice Size (mm)
Number of Orifices
Burner Manifold
3.182.10
22
3.00/0.738.25/2.5
Pressure WC/kpa
(1) mbar = 10,2 mm H2O
Korea Standard for Gas Pressure
Fryer Model FQGLA30-T
Gas Type LNG
(Natural)
Incoming Min Pressure
4/1.00/10.009.2/2.30/23.00
LPG
(Propane)
WC/kpa/mbar
Incoming Max Pressure
10/2.50/25.0013.2/3.30/33.00
WC/kpa/mbar
Orifice Size (mm)
Number of Orifices
Burner Manifold
3.182.10
22
3.00/0.738.25/2.5
Pressure WC/kPa
(1) mbar = 10,2 mm H2O
Japan Standard for Gas Pressure
Fryer Model FQGLA30-T
CE Standard for Gas Pressure
Fryer Model FQGA30-T
Gas Type G20
Natural
Gas
Lacq
Incoming Min
20 20 28/30 37
G25
Natural
Gas
Groniqu
Pressure (mbar)
Incoming Max
20 25 50 50
Pressure (mbar)
Orifice Size (mm)
Number of
3.18 3.18 1.95 1.95
2 2 2 2
Orifices
Regulator
7 10 17 20.6
Pressure Full Vat
(mbar)
Regulator
8 11.2 17 20.6
Pressure Dual Vat
(mbar)
Burner Manifold
7 10 17 20.6
Pressure (mbar)
Full Vat
Burner Manifold
8 11.2 17 20.6
Pressure (mbar)
e
G30
Butane
/Propane
G31
Propane
Gas Type
Incoming Min Pressure
WC/kpa/mbar
Incoming Max Pressure
WC/kpa/mbar
Orifice Size (mm)
Number of Orifices
Burner Manifold
Pressure WC/kPa
(1) mbar = 10,2 mm H2O
13A
4/1.00/10.009.2/2.30/23.00
10/2.50/25.0013.2/3.30/33.00
3.181.95
22
3.00/0.738.25/2.5
Propane
(LP)
1-16
1.13 Measuring Flame Current
Flame Sensor
When the burner flame is properly adjusted, it will produce a current between
2.0A and 2.5A on Fenwal modules. Lockouts can occur at currents 0.5A or
below on Fenwal modules. Flame current is measured by placing a microamp (not
milliamp) meter in series with the sensing wire on the ignitor. This is
accomplished as follows:
1. Place the controller power switch in the OFF position.
2. Disconnect the sensing wire from one of the burner ignitors (see Figure 1) and
connect it to the positive lead of the meter. Connect the negative lead of the
meter to the terminal from which the sensing wire was removed.
3. Place the controller power switch in the ON position to light the burners. After
Figure 1
the frypot temperature reaches 200F (93C), wait at least one minute before
checking the reading. NOTE: The closer the unit is to normal operating temperature, the more accurate the
reading will be.
1.14 Replacing Fryer Components
1.14.1 Replacing the Controller or the Controller Wiring Harnesses
1. Disconnect the fryer from the electrical power supply. The fuse located at the bottom of the control
box can be removed to remove power from individual control boxes.
2. The controller is held in place by two screws in upper corners.
3. Remove the two screws from the upper corners of the controller.
4. Slide the controller up and it and will swing open from the top.
5. Disconnect the RJ45 cable from the SIB board first.
6. Disconnect the other cables from the connectors on the back of the controller marking their position for
reassembly.
7. Disconnect the lanyard tether.
8. Remove the controller.
RJ-45 Power /
Communication
Ground Wire
Lanyard Tether
Wire
Speaker
Harness
Locator Wire
USB Harness
Figure 2
5. With the replacement controller face down resting in the control box, reattach the lanyard tether first.
Failure to reinstall lanyard could result in damage to the SIB board.
6. Reinstall the controller by reversing steps 1 thru 6.
7. Setup the controller following the instructions in section 4.7 of the FQGLA-T Installation and Operation
manual. If the controller being replaced is in the far left position the current date and time will need to be
setup following the instruction in section 4.8 of the Installation and Operation manual. Setup MUST be
performed prior to reset.
8. Once setup is complete on all replaced controllers, CYCLE POWER TO ENTIRE FRYER SYSTEM. See
section 1.19.2 to reset control power.
1-17
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.