Friedrich VRPXEMWRT2 Instruction Manual

VRPXEMWRT2
Wireless VRP® Energy Management Wall Controller with an Occupancy Sensor
INSTRUCTION MANUAL
PART NO. 95200303 Rev 00
3
Table of Contents
Introduction ............................................................................................................ 5
Before you begin ................................................................................................... 7
Wall Controller Installation ..................................................................................... 9
Pairing the Wall Controller and the Receiver .........................................................9
Mounting the Wall Controller to the wall ................................................................ 9
Installing the Wireless Receiver ..................................................................... 10-11
Wall Controller Wiring Installation .............................................................................12-14
Wall Controller Conguration ...............................................................................15
Setting the Wall Controller Clock ................................................................................... 16
Entering the Room Number ........................................................................................... 17
Conguring the Energy Saving Settings ....................................................................... 18
Testing the Wall Controller .............................................................................................19
Custom Energy Savings Settings .................................................................................. 20
Using the Wall Controller Settings Screens .........................................................21
01 – FAN CONTROL MODE ...............................................................................22
02 – 1ST STAGE DIFFERENTIAL - HEAT ............................................................ 23
03 – 2ND STAGE DIFFERENTIAL - HEAT ............................................................ 24
04 – 1ST STAGE DIFFERENTIAL - COOL .........................................................25
05 – INCIDENTAL OCCUPANCY THRESHOLD ................................................. 26
06 – NIGHT OCCUPANCY THRESHOLD ........................................................... 27
07 – NA ................................................................................................................ 28
08 – NIGHT OCCUPANCY START ..................................................................... 29
09 – NIGHT OCCUPANCY END ......................................................................... 30
10 – NA ................................................................................................................ 31
11 – NA ................................................................................................................ 32
12 – TEMPERATURE SETBACK DELAY - HEAT ............................................... 33
13 – MINIMUM SETBACK TEMPERATURE ...................................................... 34
14 – TEMPERATURE SETBACK DELAY - COOL .............................................. 35
15 – MAXIMUM SETBACK TEMPERATURE...................................................... 36
16 – NA ................................................................................................................ 37
17 – MINIMUM SET POINT.................................................................................38
18 – MAXIMUM SET POINT ...............................................................................39
4
Table of Contents
19 – TEMPERATURE CONTROL MODE ........................................................... 40
20 – AUTO CHANGEOVER SET POINT OFFSET (DEAD BAND) ..................... 41
21 – SETBACK SET POINTS / AUTO-RESTORE .............................................. 42
22 – AUTOMATIC HUMIDITY CONTROL† .......................................................... 43
23 – TEMPERATURE CALIBRATION ................................................................. 44
Wall Controller Maintenance ...............................................................................45
Replacing Wall Controller Batteries ..................................................................... 46
Troubleshooting ................................................................................................... 47
Error Codes ......................................................................................................... 47
Wall Controller is not controlling the VRP unit. .................................................... 48
APPENDIX 1 - Energy Saving Presets................................................................ 49
APPENDIX 2 - Glossary ...................................................................................... 50
Technical Specications ...................................................................................... 51
5
Introduction
Friedrich VRPXEMWRT2 Energy Management Wall Controllers for the hospitality industry deliver unprecedented energy savings without compromising guest comfort. Integrated occupancy sensor uses a combination of motion and thermal sensing technologies for accurate occupancy detection. Reliable occupancy detection allows saving energy when rooms are unoccupied.
Energy saving presets eliminate the guesswork and make it easy to adjust the
energy saving settings. (Patent Pending) Fully congurable energy saving settings allow customizing the Wall Controller energy saving settings to t any
situation.
Large buttons with international symbols make it easy to adjust the temperature in ±1° °F or °C and control the fan speed.
Built-in wireless mesh-networking enables optional remote management. For installation of a networking Wall Controller with remote management, refer to the “Network Installation” manual.
FOR INSTALLATION OF NETWORKING WALL CONTROLLERS WITH REMOTE MANAGEMENT, REFER TO THE NETWORK INSTALLATION” MANUAL. LOGIN TO THE REMOTE MANAGEMENT WEBSITE TO CONFIRM THE SERVER IS CONNECTED TO THE INTERNET BEFORE INSTALLING WALL CONTROLLERS. DO NOT INSTALL WALL CONTROLLERS IF THE SERVER IS NOT CONNECTED TO THE INTERNET. STOP THE INSTALLATION AND CONTACT TECHNICAL SUPPORT. START BY FIRST INSTALLING A WALL CONTROLLER IN THE ROOM CLOSEST TO THE SERVER. LOG IN TO REMOTE MANAGEMENT WEBSITE TO CONFIRM THAT THE WALL CONTROLLER IS ON THE REMOTE MANAGEMENT WEBSITE WITH THE CORRECT ROOM NUMBER. CONTINUE BY INSTALLING ADDITIONAL WALL CONTROLLERS IN ADJACENT ROOMS ONLY AFTER CONFIRMING THAT INSTALLED WALL CONTROLLER(S) HAVE CONNECTED TO THE WIRELESS NETWORK AND THE REMOTE MANAGEMENT WEBSITE . IF INSTALLED WALL CONTROLLER(S) ARE NOT CONNECTING TO THE NETWORK AND DO NOT APPEAR ON THE REMOTE MANAGEMENT WEBSITE WITH THE CORRECT ROOM NUMBER, STOP THE INSTALLATION AND CONTACT TECHNICAL SUPPORT THE ROOMS FURTHEST AWAY FROM THE SERVER SHOULD BE INSTALLED LAST.
6
7
Before You Begin
• Determine the appropriate installation location for the Wall Controller. The Wall Controller should face the bed area of the room.
• Wall Controller MUST NOT BE INSTALLED NEAR OR ON METAL
STRUCTURES OR SURFACES INCLUDING METAL AIR DUCTING
THAT MAY BE IN THE WALL. METAL STRUCTURES AND SURFACES SIGNIFICANTLY REDUCE THE RANGE OF THE WIRELESS SIGNAL
8
Wall Controller Installation
Pairing the Wall Controller and the Receiver
Wall Controller and Receiver must be paired in order to operate together. Once paired, the Wall Controller cannot be used with another wireless Receiver without repeating the pairing procedure. Friedrich Wall Controllers are pre-linked with the card in the box.
In case of Network Installation with Remote Management, the Wall Controller and
the Receiver must be paired with a Network Programmer specic to the property
before the installation.
Wall Controller and Receiver must not be powered during the pairing procedure ­remove batteries from the Wall Controller and unplug the Receiver from the VRP unit during the pairing procedure.
• Plug one programmer connector into the Wall Controller;
• Plug the other programmer connector into the Receiver;
• Push the black button on the programmer. The red light on the programmer should turn on and remain steadily lit;
If the red light on the programmer is blinking or is not steadily lit, unplug the programmer from the Wall Controller and the Receiver and repeat the steps above.
• Unplug the programmer from the Wall Controller and the Receiver;
9
Mounting the Wall Controller to the wall
• Remove the Wall Controller cover;
• Use the supplied wall anchors and mounting screws to secure the Wall Controller to the wall;
• Insert two (2) AA-cell batteries (not-supplied) into the Wall Controller battery compartment;
Follow the “Wall Controller Conguration” instructions;
• Replace the Wall Controller cover and screw in the locking screw;
Wall Controller Installation
10
Installing the Wireless Receiver
• Unplug the VRP® unit from power supply.
• Connect the low voltage wires to screw terminals on the VRP® unit low voltage terminal block - refer to the Wiring Table to determine proper connections.
• Ensure that the Wireless Receiver antenna is not touching any metal components of the VRP® unit.
• Ensure that the Wireless Receiver antenna is facing the Wall Controller on the wall and is oriented so that any metal parts of the VRP® unit do not obstruct the wireless communication to the Wall Controller and, in case of a network installation, to other wireless Receivers and the server.
• Plug the VRP® unit to power supply.
Wall Controller Installation
Receiver
11
Wall Controller Installation
Installing the Wireless Receiver
Mount the Receiver as high as possible. It MUST be higher than the VRP unit (top)
To maximize the wireless signal strength from the Receiver to the VRPXEMWRT2 Wall Controller, the Receiver MUST NOT be installed on the VRP unit.
Note: Depending upon the closet size, an appropriate length of Field Supplied CAT 6 cable will be required.
12
Wall Controller Wiring Installation
There are four sets of connections for the VRPXEMWRT2 Wall Controller. The supplied cable from the VRPXEMWRT2 Receiver as shown in Figure 1, has four color coded wires. Each of these wires must be connected to two Cat6 wires as shown in Figure 2. Each connection is made with a lever type connector. Four connectors will be needed to complete unit wiring. Each connector is capable of connecting three wires.
Figure 1
Figure 2
WIRE COLOR LABEL
Orange
Connection 1
V+ Orange
Green/White
Brown
Connection 2
D+ Brown
Blue/White
Blue
Connection 3
D­Blue
Brown/White
Green
Connection 4
V­Green
Orange/White
Ground Shield Wire
GND
13
Wall Controller Wiring Installation
General Connection Procedure:
1. Remove 2” of the outer sheath of the CAT6 cable including the shield and
strip the wires.
2. Insert the specied wire from the Receiver into a slot of the lever connector as shown in Figure 3 and close lever as shown in Figure 4.
3. Insert two specied twisted, paired wires from the CAT6 cable into the remaining lever connector slot as shown in Figure 4. Each twisted, paired wire should be inserted into its own separate slot in the lever connector.
4. Close the orange lever on the lever connector as shown in Figure 5. Make sure the levers seat properly.
Figure 3.
Figure 4.
Figure 5.
14
Connection 1 Insert the Orange (V+) wire from the Receiver into a lever connector slot and close the orange lever on the connector.
Insert the twisted Orange and Green/White Cat 6 wires into the remaining lever connector slot and close the orange lever on the connector.
Connection 2 Insert the Brown (D+) wire from the Receiver into a lever connector slot and close the orange lever on the connector.
Insert the twisted Brown and Blue/White Cat 6 wires into the remaining lever connector slot and close the orange lever on the connector.
Connection 3 Insert the Blue (D-) wire from the Receiver into a lever connector slot and close the orange lever on the connector.
Insert the twisted Blue and Brown/White Cat 6 wire into the remaining lever connector slot and close the orange lever on the connector.
Connection 4 Insert the Green (V-) wire from the Receiver into a lever connector slot and close the orange lever on the connector.
Insert the twisted Green and Orange/White Cat 6 wire into the remaining lever connector slot and close the orange lever on the connector.
WIRE COLOR LABEL
Orange
Connection 1
V+ Orange
Green/White
Brown
Connection 2
D+ Brown
Blue/White
Blue
Connection 3
D­Blue
Brown/White
Green
Connection 4
V­Green
Orange/White
Ground Shield Wire
GND
Wall Controller Wiring Installation
NOTE: You can access Wall
Controller Conguration settings
at any time by pressing the
“Conguration” button.
NOTE: If the Wall Controller is connected to a network, the equipment and the
energy saving settings congured on the Wall Controller will be ignored and the settings congured on the Remote Management
Website will be applied.
CONFIGURATION BUTTON
15
Wall Controller Conguration
Once the Wall Controller is powered, Wall Controller conguration settings will
appear on the Wall Controller screen.
In order to properly operate the VRP unit:
• Set the Wall Controller clock;
• Enter the room number;
• Select Energy Savings Preset;
The Wall Controller conguration screens have a 3-minute time-out. If no action is taken within three (3) minutes, the Wall Controller will exit conguration
settings.
NOTE: If the Wall Controller is connected to a network, the equipment settings
congured on the Wall Controller will be ignored and the Wall Controller settings congured through the network will be applied.
16
Wall Controller Conguration
Setting the Wall Controller Clock
Set the Wall Controller clock to current time in 24h (Military Time) format.
• Use the “Up” and “Down” buttons to set the hours;
• Press the “Fan” button to advance to the minutes setting;
• Use the “Up” an “Down” buttons to set the minutes;
• Press the “F/C” button to advance to the next menu;
Setting the clock correctly is crucial for proper operation of the Wall Controller.
HOURS MINUTES
Loading...
+ 36 hidden pages