Model VPDP1
Installation Instructions
DRAIN PAN
For Vert-I-Pak A Series 24,000 Btuh units only.
Please read these instructions completely before attempting installation.
Note: This drain pan must be installed with all VEA24 and VHA24 units.
STEP 1: CUT OPENING IN GASKET
Remove an 8" portion of the weather seal gasket from the bottom left surface of the plenum.
To remove: Cut the gasket in the lower left corner of the plenum. Then make a second cut 8" from the left
corner. The gasket should peel away from the plenum leaving a clean mounting surface (See detail A).
A
8.00
DETAIL A
STEP 2: SEAL AND SET PAN
Prior to placing the drain pan into the opening run a 1/4" bead of sealant the entire width of the removed
gasket. The secondary overflow lip must extend into the plenum to prevent water leaks. The pan should be
mounted against the 3/4" flange of the plenum, refer to view A.
2.00
A
Sealant
920-150-00 (1-05)
B

STEP 3: INSTALL DRAIN PAN
Attach the drain pan to the closet floor with the appropriate field supplied hardware.
IMPORTANT - To prevent water leaks use only the factory supplied mounting holes. NEVER make penetrations in the
drain pan itself.
STEP 4: INSTALL DRAIN PLUG
The drain pan comes with both left and right-hand drain connections locations. Determine which of the two connections will be used to drain the condensate. Then, with the factory supplied drain plug, plug the unused opening.
NOTE - proper sealant must be applied to the connection to prevent leaks.

STEP 5: INSTALL DRAIN LINE
Condensate line routing options are shown below. Choose the one that best suits your installation. Never run
the condensate line as shown in Option 4 below, as the drain line will come into contact with the factory-installed
isolators beneath the unit.
Option 1
Run condensate line
to right of unit
Option 2
Run condensate line
beneath unit platform
Option 3
Run condensate line
to left of unit
IMPORTANT - The drain pan and line must be kept free from debris. Prior to installing the chassis ensure that
there are no blockages in the drain pan or line.
Option 4
Do not run
condensate line
back toward unit