2) Electrical
I DANGER: Electrical shock hazard. Turn OFF electric power at the fuse box or service panel before making any I
electrical connections and ensure a proper ground connection is made before connecting line voltage. Failure to do
Iso can result in property damage, personal injury and/or death.
A. Grounding
,_. CAUTION: The unit must be electrically wired and grounded inaccordance with all state and local codes, national electric
code, and NFPA 70. Unit and controls will NOT operate unless properly grounded. Aground lug is provided for ground
connection. Use only approved copper wire and connectors from unit to service panel.
B. Power Supply
NOTE: Line voltage circuit is completelyfactory wired. Make allline voltage connections inside circuit breakerjunction box.
ThecircuitbreakersorfusesusedforbranchcircuitprotectionshouldbeULrecognized. Ifcircuit breakers are used, the circuit
breakerfor the compressorcircuit must havea UL HACRrating. Iffuses are used, thefuseforthecompressorcircuitMUST
be time delay type.
CAUTION: Units are dual voltage rated 208-230/1/60. The 24V control transformer must be connected for either 208V
or 240V power source for proper operation. Line voltage must not exceed 253V or go below 197V. The transformer
connection must be changed for 208V operation.
Depending on auxiliary heater size, unit must be supplied with 2 or 3 separate 208V or 240V circuits from structure's fuse
box or service panel. Each circuit is internally connected to a circuit breaker located in the unit control box located at the
front center of the unit. Refer to Table 4 and Table 5for required circuits and recommended wire size for each circuit.
Table 4
Minimum Circuit Maximum Fuse2or
= Model Compressor Amps Outdoor Fan Amps Indoor Fan Amps Ampacity Minimum Wire Size 1 Breaker Size Amps
u. _ V(E,H)B18 7.9 1.7 1.7 14.0 12 20
m_ V(E,H)B24 9.3 1.7 1.7 16.7 12 25
_- V(E,H)B30 15.0 2.2 1.8 22.8 10 30
t33
._= ,_ V(E,H)B36 17.9 3.0 2.5 27.9 8 40
oo'o V(E,H)B42 20.4 4.7 3.0 34.0 8 50
O V(E,H)B49 22.1 4.6 3.0 41.0 6 60
V(E,H)B60 32.1 4.6 3.1 49.0 6 60
Table 5
Heater Size Chassis Ckt#1 Ckt #1 Wire Ckt #1 Max. Ckt #2 &3 3 Ckt#2&3 3 Ckt #2 &3 3 Ckt#2& 3s
(KIN) Available Ckt #1 Amps Arn pacity Size _ Fuse 2 Amps Am pacity Wire Size _ Max. Fuse 2
Q 5.0 18/24 20 8 26.0 I O 30 N/A KVA N/A N/A
O.
10.0 18/24/30/36/42 416 52.0 6 60 N/A NVA N/A N/A
69 15,0 30/36/42/48 208 26.0 10 30 41.6 52.0 6 60
o_ 20,0 48/60 41 6 52.0 6 60 41.6 52.0 6 60
i
25,0 60 208 26.0 10 30 41.6 52.0 6 60
1 if wire is apptied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70) The ampacity of nonmetalic-sheathed cable (NM), trade
name ROMEX, shalt be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70)Article 336-30. If other than uncoated (non-plated), 60°C or 75°C (140°F or
167°F) insulation, copper wire (solid wire for 10 AWG and smalter, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
2 Time-delay fuse.
3
Circuit #3 is only used for 25kw heater
Auxiliary
(Field
Heat Pump
(Field Wiring)
Heat Pump
Auxiliary
Heater#1
Ground
(Field
Auxiliary
Heater#2
(Field Wiring)
Line Voltage And Ground Connections
AUXILIARY HEATER #I
POWER WIRING
(FIELD WIRING)
= AUXILIARY HEATER #I
GROUND LUG •AUXILIARY HEATER #2
(FIELD WIRING) t60A, PARALLEL WIRING)
Unit Wiring with VPDB1 Distribution Block
12