Friedrich VPAWP1, VPAWP2 Installation Instruction

INSTALLATION
INSTRUCTIONS
WALL PLENUM AND LOUVER
For Use With Vert-I-Pak
NOTE: These instructions apply to Vert-I-Pak A Series Units ONLY. Refer to Chassis Installation/Operation Manual for additional information.
Please read these instructions completely
before attempting installation.
VPAWP1 VPAWP2
VERY IMPORTANT!
YOUR WALL PLENUM WILL WORK ONLY IF INSTALLED CORRECTLY. TAKE NOTICE TO INSTALL IT IN THE CORRECT ORIENTATION AS SHOWN IN THE ILLUSTRATIONS.
Step 1: Included Parts
There are two parts to a Wall Plenum:
A) 1-Outside Assembly (Part A) B) 1-Inside Assembly (Part B)
Step 2: Field Supplied Parts:
Caulk, Attachment screws and Flashing are field supplied. Silicone caulk is
recommended.
VPAWP1 adjusts for walls 5.5 - 8.0" thick. VPAWP2 adjusts for walls 8 - 14.0" thick.
45° Drip
Ledge
PART A CORRECT ORIENTATION:
●●
LOUVER ATTACHMENT
●●
FLANGES TOWARD THE BUILDING OUTSIDE, 45° DRIP LEDGE AT THE BOTTOM.
Part A
Outside Plenum
PART B CORRECT ORIENTATION:
LARGE OPENING TO BOTTOM
3/4" FLANGE TOWARD THE INSIDE OF THE BUILDING.
Part B
Inside
Plenum
Both installations are similar.
Flashing
Caulk
Header materials / wall studs
1" –3" Screws to attach the plenum assembly to the wall studs
Shim
920-069-04 (7/01)
Step 3: Measure and frame out the outside wall plenum opening
Measure your outside wall as shown in the illustration. Cut, frame, and square rough opening. The Wall plenum has a 3/4" break all the way around to cover the rough cut opening or required shim.
IMPORTANT: THE WALL PLENUM IS NOT DESIGNED TO CARRY STRUCTURAL LOADS. A PROPER HEADER OPENING MUST BE BUILT INTO THE ROUGH OPENING. THE PLENUM REQUIRES FLASHING, SHIM AND CAULK FOR A WEATHER-RESISTANT INSTALLATION.
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROPERLY INSTALL THE PLENUM AND MEET BUILDING CODE REQUIREMENTS.
Step 4: Install Architectural Louver on the Outside Plenum
The VPAL2 Architectural Louver is best installed onto the Outside Plenum (Part A) prior
NOTE:
to Wall Plenum installation. Louver installation is easier at this point, and it will help keep the Wall Plenum square during installation.
Page 2
Step 5: Plenum Installation
Note: Proper header and wall penetration must conform to all
national and local building codes.
Proper Flashing
Proper Caulking
Caulk all 8 flange corners
Proper Header
Inside Wall Plenum
(Part B)
Architectural louver VPAL2 mounted on the outside wall plenum (Part A)
Outside Wall
Proper Flashing
Proper Caulking
After the rough cut opening is prepared, you are ready to assemble the two wall plenum parts. Before caulking and permanent attachment, dry fit the outside plenum into the rough opening and check for fit and level. Caulk (silicone recommended ) the parts well and insert them into the wall as shown.
A) Apply caulk and insert Outside Part A into the hole.
B) Apply caulk and insert Inside Part B into Part A. Be sure that Part A does not back out
of the wall hole.
IMPORTANT: DO NOT RUN SCREWS THROUGH THE TOP OR
BOTTOM OF THE WALL PLENUM.
Page 3
Step 6 - Adjust the Divider
Adjustment A:
Ensure that the plenum divider is located in the proper slot. The divider has a label indicating the proper placement as follows:
Top Position: 18,000 Btuh models prior to the E-suffix.
Middle Position: All E-suffix Vert-I-Pak Models 9,000, 12,000, and 18,000 Btuh.
Lower Position: 9,000 and 12,000 Btuh models prior to the E-suffix.
NOTE: The plenum is shipped with the
divider in the middle position for all E-suffix models.
A
Adjustment B
Loosten the two screws located on the top side of the divider. Slide the top part of the divider toward the outside until the sealing strip makes contact with the outdoor louver. Tighten the divider screws to complete the adjustment.
NOTE: Let the caulk cure completely
before installing the chassis. This completes the plenum installation.
B
FRIEDRICH AIR CONDITIONING CO.
Post Office Box 1540 4200 N. Pan Am Expressway San Antonio, Texas 78295-1540 (210) 357-4400 FAX (210) 357-4480
Page 4
920-069-04 (7/01)
Loading...