RECOMMENDED BRANCH
CIRCUIT WIRE SIZES
*AWG- AMERICAN WIRE GAUGE
14121010101064
ELECTRICAL DATA
VHA18RVHA24R
HEATER WATTS2500340050005000750010000
VOLTAGE265
ELECTRIC HEATING BTU 85001160017000170002560034100
HEAT CURRENT (AMPS)9.412.818.918.928.337.7
HEATING AMPS HP6.96.96.98.18.18.1
MINIMUM CIRCUIT AMPACITY12.316.624.227.138.950.7
BRANCH CIRCUIT FUSE (AMPS)152030304055
LRA-COMPRESSOR (AMPS)424242464646
COOLING CURRENT (AMPS)7.67.67.69.79.79.7
BASIC HEATER SIZE2.5KW3.4KW5.0KW5.0KW7.5KW10.0KW
POWER CONNECTION HARD WIREDHARD WIRED
RECOMMENDED BRANCH
CIRCUIT WIRE SIZES
*AWG- AMERICAN WIRE GAUGE
1412101064
Due to continuing research in new energy-saving technology, specications are subject to change without notice.
10
Page 11
Application and Installation
Installation Guidelines
• Chassis is to be installed against an exterior wall. Wall
cutout dimensions will be 24 5/8" w x 30 7/8" h.
• Clos et sho uld al low for a mini mum of thre e inch es on th ree
sides of the unit for return air, drain connections and change
outs.
• Minimum recommended access door rough-in measure-
ments 27" wide by 55
3
/4" high (for VPRG4/VPRG4R).
• Friedrich recommends the use of a platform between 24"
an d 36" above the oo r, for ea se of in stal l ati on and ser vice -
ability.
• Duct outlet designed for external static pressures up to .3"
on 9,000, 12,000, and 18,000 Btu models; and .4" on 24,000
Btu models.
• Wall plenum allows chassis to be inserted 2
3
/8" into
plenum, thereby minimizing closet dimensions.
• Quick connect drain coupling ships standard to make
installation and removal easier.
Application and Accessories (All models)
• The use of a Friedrich wall plenum is required for installation. Plenum opening is 3/4" above the oor for 9,000 &
12,000 models, and 11/2" for 18,000 & 24,000 Btu models.
(V PAW P1-8 / VPAWP1-14).
• Return air is accommodated with a return air lter attached
to the unit or through the use of a return air lter grille.
(VPRG4/ VPRG4R).
• Exterior louvers are available in anodized aluminum (VPAL2)
or in custom painted colors (VPSC2).
• Unit is controlled by a remote wall-mounted thermostat.
Fr i edric h mod el W R T1 w i rele s s digi tal th ermos t at, RT6 wi red
digital thermostat, RT6P wired programmable thermostat,
or EMRT1/EMWRT1 Energy Management Stats are recommended.
• Central desk control ready.
Typical Closet Arrangement
Cutaway of a typical closet shown with Vert-I-Pak® chassis
installed in the wall sleeve. The unit has the thermostat, eld
wiring, internal drain and ex duct attached. VPRG4 return air
lter holder and access panel are shown below.
The closet access panel may be instal led in the fr ont (as sh own
below) or to the left or right side of th e un it. Al l thr ee in stal l ati on
options will allow easy access to the unit for removal and
replacement.
Application and Accessories (24K Models only)
• 18K and 24K utilize drain pan (VPDP1) that can be installed
prior to chassis for simplied installation and removal.
• 18K and 24K utilize the same wall plenum as other units to
give consistent exterior appearance. VHA24 plenum must
be installed 1
1
/2" above chassis platform.
10"
10"
23
1
/
8
"
9,000 & 12,000 Btu
23
1
/4"
47
32 1/4"
1
8
"
/
23
1
/
8
"
23
1
"
8
/
18,000 & 24,000 Btu
11
Page 12
ACCESSORIES
ARCHITECTURAL LOUVER
VPAL2 and VPSC2
Extruded aluminum grille that attaches to the outdoor section of the wall
plenum. Takes in fresh air and returns condensed air. VPSC2 can be ordered in
custom colors.
DIMENSIONS: 25 9/16" W x 31 1/16" H
WALL PLENUM
VPAWP1-8, VPAWP1-14
Two-part sleeve that telescopes in and out. Sits inside the exterior wall
penetration.
VPAWP1-8 telescopes from 5 1/2”–8”
VPAWP1-14 telescopes from 8”–14”
DIMENSIONS: 24 1/8” W x 30 3/8” H
CUTOUT DIMENSIONS: 24 5/8” W x 30 7/8” H
RETURN AIR GRILLE/ACCESS PANEL
VPRG4 / VPRG4R
Hinged panel allows access to unit and return air lter.
A eld-supplied lter (25” x 20”) should be mounted on the inside grille. Panel
can be mounted with return air openings high or low on the door for optimum
sound attenuation.
DIMENSIONS: 29” W x 58” H
CUTOUT DIMENSIONS: 27” W x 55 3/4” H
VPAL2
VPAWP1-8
VPRG4
FIRST COMPANY SLEEVE ADAPTER
VPAS A1
Single piece, welded adapter allows retrot into existing First Company SPXRseries single package ver tical unit wall sleeve and louver. Easy connection to
Friedrich small chassis VERT-I-PAK.
SINGLE STAGE THERMOSTATS
RT6P
Wired, single stage, wall-mounted programmable thermostat has two fan
speeds and backlight. Controls Friedrich VERT-I-PAK.
RT6
Wired, single stage, wall-mounted digital thermostat with two fan speeds and
backlight for control of Friedrich VERT-I-PAK.
WRT1
Wireless, single stage, wall-mounted digital thermostat with two fan speeds
and backlight for control of Friedrich VERT-I-PAK.
ENERGY MANAGEMENT THERMOSTATS
EMRT1
Wired thermostat with occupancy sensor.
EMWRT1
Wireless thermostat with occupancy sensor.
EMOCT EMRAF EMRHCF
Online connection kit. Remote access fee. Remote humidity control fee.
VPASA1
RT6, RT6P WRT1
DRAIN PAN
VPDP1
For VHA18 and VHA24 models. May be installed prior to chassis for easy installation/
removal.
12
EMRT1, EMWRT1
VPDP1
Page 13
HVAC Engineering Specications
A-Series Vertical Packaged Heat Pumps
Cooling: 9400 – 23000 Btu
Heating: 8400 – 20000 Btu (Heat Pump)
All units shall be factory assembled, piped, wired and fully
charged with R-410A. All units shall be certied in accordance
with ARI Standard 390 for Single Packaged Vertical Heat Pumps.
Units shall be ETL listed and carry a ETL label. All units shall
be factory run-tested to check operation and be manufactured
by Friedrich or equivalent.
The basic unit shall not exceed 23
height of the unit from the bottom of the isolators to the top of the
duct collar shall not exceed 32 ¼" for models up to 12,000 Btu and
47 ¼" for models up to 24,000 Btu. The unit shall be designed so
that the unit will insert into a factory supplied wall plenum 2
to mini miz e room intr usio n. Fac t ory su ppli ed wal l plenums shal l
allow for installation through walls from 4 ½" – 14" in thickness.
Wall plenums will be adjustable to minimize installation clearances. Unit shall draw in ambient air through upper portion of
an outside architectural louver measuring 25
high and shall exhaust heated air out through the lower portion
of the louver. The unit shall be secured to the architectural lou-
ver by means of a two part, weather-resistant wall plenum. The
unit shall be capable of left, right or straight-in installations into
mechanical closet without eld modications.
REFRIGERATION SYSTEM – The refrigeration system shall be
hermetically sealed and consist of a rotary compressor that is
externally mounted on vibration isolators no smaller than 1 ¾"
diameter x 1 ½" high; condenser and evaporator coils constructed of
co pper tube s an d al uminum plate ns; and cap illa r ies as ex p ans ion
devices. Unit shall have a fan slinger ring to increase efciency
and condensate disposal. A primary condensate removal system
consisting of ¾" FTP ttings on multiple locations shall exist. A
secondary overow from the primary drain pan shall expel water
to the outside of the building through the wall plenum and louver
in the event that the primary drain line clogs.
AIR HANDLING SECTION – The condenser fan shall be driven by
a single, totally enclosed, ball bearing, permanently lubricated
split capacitor fan motor for models up to 12,000 Btu. 18,000
and 24,000 Btu models shall utilize a separate motor for both
the indoor and outdoor air sections. Airow shall be directed
ver t ical ly up throu gh a stan dard 10" ex duct sta r ter collar and
into e xib le or rigid ducts to be distrib ute d int o the conditioned
area. Starter collar shall have both crimped edge to ease ex
du c t inst allation and a wai stli ne to pr even t duc t from loose ning .
The chassis shall have a built-in damper capable of providing
at least 60 CFM of fresh air into the conditioned area. A ne
mesh screen shall lter the incoming fresh air. The damper
can be controlled by a slide lever located on the front of the unit.
CONTROLS – The unit shall be factory equipped with terminal
strip for connection to a standard 24-volt single-stage heat/
cool thermostat. A 24-volt transformer shall be included and
factory wired. Low voltage inputs will include: C (common), R
(2 4V pow er), Y (cooling), G (fan) , W (he at) and B (r eversi ng valve
on VHA he at pumps on ly).T he uni t shal l be hard -wire d and ha ve
a quick-disconnect to disable power for control box service.
1
/8" wide x 23 1/8" deep. Overall
9
/16" wide x 31 1/16"
3
/8"
Friedrich Models: VHA – Heat Pump with electric heat
An emergency heat override switch must be available to allow
operation of the resistance heater in the event of a compressor
failure on heat pump models.
GENERAL CONSTRUCTION – The unit shall be constructed of
18-gauge galvanized zinc-coated steel. The unit shall feature
½" foil backed insulation for sound and thermal efciency.
The wall plenum (required factor y accessor y) shall be shipped
separately and constructed of 20-gauge galvanized zinc-coated
steel; pretreated with zinc-phosphate and sealed with a chromate rinse, then powder-coated for maximum coverage and
protection. The plenum shall be black in color for minimal
visibility of unit from exterior of building. The plenum shall be
shipped with a protective weatherboard for use prior to nal
installation of the louver and chassis.
The architectural louver (required factory accessor y) shall
be shipped separately and fabricated from extruded anodized
aluminum with louvers in the horizontal plane.
The unit shall include vibration isolators mounted under the
chassis and a nonrigid plenum-to-chassis connection to isolate
vibrations to the building.
The unit shall have a plastic fan, fan shroud, and drain pan; and
aluminum outdoor coil endplates for corrosion protection and to
help prevent rust on the side of the building below the outdoor
louver.
The unit shall be shipped with return air lter brackets and a 14"
x 20" lter afxed directly on to the unit chassis. Optional return
air grilles and access panels shall be available as factory acces-
sories for installation in the wall or door of the mechanical closet.
CORROSION PROTECTION - The unit shall feature corrosion
-resistant materials and nish to help prevent deterioration.
The outdoor coil shall have Diamonblue advanced corrosion pro-
tection consisting of hydrophilic-coated ns to prolong the life of
the coil in all applications including seacoast protection.
ACCE SSORY ACCE SS PANEL - An optional factor y-supplied access
panel shall be available to provide access to the unit and adequate
return air. The panel shall feature a lter holder to accept a eld
supplied 25” x 20” x 1” lter. Kit shall contain a hinge bracket for
mounting the door with the return air openings high or low on
the door for optimal sound attenuation. For 9,000 and 12,000 Btu
mo dels it is r ecom mended to inst all the d oor wi th th e hin ge on the
right side and the return air openings high on the door. For 18,000
and 24,000 Btu models it is recommended to install the hinge on
the left with the openings low on the door.
WARRANT Y – The warranty is one year on all parts and labor
and 5 years on the sealed system, parts and labor, including
compressor, indoor and outdoor coils and refrigerant tubing.
13
Page 14
Vert-I-Pak
Single Package Heat Pumps
PURCHASERP.O. #DATE
PROJECTLOCATION
ENGINEERARCHITECT
SUBMITTED BYFOR APPROVALFOR REFERENCE
ITEMPLAN DESIGNATIONQUANTITYCOOLING BtuVOLTAGEFRIEDRICH MODEL
A-SERIES ACCESSORIES (Wall Plenum and Outdoor Louver are required)
®
VPAWP1-8 Adjustable Wall Plenum (5 ½"- 8")Qty
VPAWP1-14 Adjustable Wall Plenum (8"-14")Qty
VPAL2 Architectural Louver Qty
VPSC2 Architectural Louver (color matched)Qty
VPASA1 Sleeve adapter for exact t in existing
First Company SPXR-series
VPRG4 Return Air Grille/Access PanelQty
VPDP1 Drain Pan for all A Series 18,000 and
24,000 Btu
Qty
Qty
RT6 Wired Digital Wall ThermostatQty
RT6P Wired Programmable Wall ThermostatQty
WRT1 Wireless Digital Wall ThermostatQty
EMRT1 Wired Thermostat with Occupancy SensorQty
EMWRT1 Wireless Thermostat with Occupancy
Sensor
EMOCT Online Connection KitQty
EMRAF Remote Access FeeQty
EMRHCF Energy Management Remote
Humidity Control Fee
MODEL IDENTIFICATION GUIDE
MODEL NUMBER V H A 09 K 34 RT N
Series
VHA=Vertical Heat Pump
Nominal Capacity
A Series (Btu)
09 = 9,000 18 = 18,000
12 = 12,000 24 = 24,000
Refer to electrical data chart for heater/unit compatibility.
* 24000 Btu only.
VERT-I-PAK® SUBMITTAL_2017
14
Page 15
Friedrich Air Conditioning Company
10001 Reunition Place, Suite 500
San Antonio, Tx 78216
800.541.6645
www.friedrich.com
VERT-I-PAK® A SERIES
SINGLE PACKAGE VERTICAL AIR CONDITIONERS
LIMITED WARRANTY
SAVE THIS CERTIFICATE. It gives you specic rights. You may also have other rights which may vary from state to state and province to province.
In the event that your unit needs servicing, contact your nearest authorized service center. If you do not know the nearest service center, ask the com-
pany that installed your unit or contact use - see address and telephone number above. To obtain service and/or warranty parts replacement, you must
notify an authorized FRIEDRICH Air Conditioning Co. service center, distributor, dealer, or contractor of any defect within the applicable warranty period.
When requesting service: please have the model and serial number from your unit readily available.
Unless specied otherwise herein, the following applies:
FRIEDRICH VERT-I-PAK A SERIES HEAT PUMPS & AIR CONDITIONERS
LIMITED WARRANTY - FIRST YEAR (Twelve (12) months from the date of installation). Any part found to be defective in the material or workman-
ship will be repaired or replaced free of charge by our authorized service center during the normal working hours; and
LIMITED WARRANTY - SECOND THROUGH FIFTH YEAR (Sixty (60) months from the date of installation). ON THE SEALED REFRIGERATION
SYSTEM. Any part of the sealed refrigeration system that is defective in material or workmanship will be repaired or replaced free of charge (excluding
freight charges) by our authorized service center during normal working hours. The sealed refrigeration system consists of the compressor, metering
device, evaporator, condenser, reversing valve, check valve, and the interconnecting tubing.
These warranties apply only while the unit remains at the original site and only to units installed inside the continental United States, Alaska,
Hawaii, Puerto Rico, Mexico and Canada. The warranty applies only if the unit is installed and operated in accordance with the printed instructions and in compliance with applicable local installation and building codes and good trade practices. For international warranty information,
contact the Friedrich Air Conditioning Company - International Division.
Any defective part to be replaced must be made available to FRIEDRICH in exchange for the replacement part. Reasonable proof must be presented to
establish the date of install, otherwise the beginning date of this certicate will be considered to be our shipment date plus sixty days. Replacement parts
can be new or re-manufactured. Replacement parts and labor are only warranted for any unused portion of the unit’s warranty.
We will not be responsible for and the user will pay for:
1. Service calls to:
A) Instruct on unit operation. B) Replace house fuses or correct house wiring. C) Clean or replace air lters. D) Remove the unit from
its installed location when not accessible for service required. E) Correct improper installations.
2. Parts or labor provided by anyone other than an authorized service center.
3. Damage caused by:
A) Accident, abuse, negligence, misuse, riot, re ood or acts of God. B) Operating the unit where there is a corrosive atmosphere containing
chlorine, uorine, or any damaging chemicals (other than in a normal residential environment). C) Unauthorized alteration or repair of the unit,
which in turn affects its stability or performance. D) Failing to provide proper maintenance and service. E) Using and incorrect power source. F)
Faulty installation or application of the unit.
We shall not be liable for any incidental, consequential, or special damages or expenses in connection with any use or failure of this unit. We
have not made and do not make any representation or warranty of tness for a particular use or purpose and there is no implied condition of
tness for a particular use or purpose. We make no expressed warranties except as stated in this certication No one is authorized to change
this certicate or to create for us any other obligation or liability in connection with this unit. Any implied warranties shall last for one year
after the original purchase date. Some states and provinces do not allow limitations on how long an implied warranty or condition lasts, so the above
limitation or exclusions may not apply to you. The provisions of this warranty are in addition to and not a modication of or subtraction from the statutory
warranties and other rights and remedies provided by law.
Performance of Friedrich’s Warranty obligation is limited to one of the following methods:
1. Repair of the unit
2. A refund to the customer for the prorated value of the unit based upon the remaining warranty period of the unit.
3. Providing a replacement unit of equal value
The method of fulllment of the warranty obligation is at the sole discretion of Friedrich Air Conditioning.
In case of any questions regarding the provisions of this warranty, the English version will govern.
(11-10)
15
Page 16
Friedrich Air Conditioning Co. l 10001 Reunion Place, Suite 500 l San Antonio, TX 78216 l 877.599.5665 l www.friedrich.com
PRPRF_VPAK_2018 9521 4200_01
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.