Vert-I-Pak®
SinglePackageVerticalAirCenditieningSystem
A-Series
9,000 I 12,000 I 18,000 BTU/h
Installation& OperationManual
920-075-07 (10-03)

920-075-07(10-03)
TableofContents
GeneralSpecifications
InstallationRecommendations.......................................................................................................................................... 3
Model NumberIdentification Guide ................................................................................................................................... 4
VERT-I-PAKChassisSpecifications .................................................................................................................................... 4
IL
III.
IV.
V.
Installation
1. UtilityClosetDimensions................................................................................................................................................... 5
2. WallPlenum&ArchitecturalLouverInstallation................................................................................................................ 6
3. ElectricalInformation ..................................................................................................................................................... 7-9
4. IndoorReturnAirGrillelnstallation .................................................................................................................................. 10
5. DuctworkPreparationandCFM....................................................................................................................................... 11
6. ChassisInstallation.......................................................................................................................................................... 11
7. ChassisFinalConnections (Electrical,Duct,Drain& WallThermostat) ............................................................................ 12
8. FinalInstallationChecklist............................................................................................................................................... 12
ChassisOperation
9. ThermostatControl .......................................................................................................................................................... 13
10. LowAmbientProtection for Compressor& Fan................................................................................................................ 13
11. HeatingDefrost(HeatPumpModelsonly)........................................................................................................................ 13
12. FreshAirDoor................................................................................................................................................................... 13
13. CondensateDisposalSystem .......................................................................................................................................... 13
Service& Warranty
14. Servicing/ ChassisQuickChangeouts............................................................................................................................. 13
15. Warranty.......................................................................................................................................................................... 14
Ver_l-PakAccessories .................................................................................................................................................... 15
Please read this manual thoroughly prior to equipment installation or operation, it is the installer's
responsibility to properly apply and install the equipment, installation must be in conformance
with the NFPA 70-2002 National Electric Code or current edition and Universal Mechanical Code
current edition and applicable local or national codes.
Proper installation is not difficult but it is essential.
2

920-075-07 (10-03)
Vert-I-Pak Installation Recommendations
Forproperunitperformanceandmaximumoperatinglifepleaserefertothe minimuminstallationclearancesbelow.
Figure I
VERT-I-PAK ® units must be installed on an outside wall. Confined spaces and/or covered areas should be
avoided. Units should be installed no closer than 12" apart when two units are side by side. If three of more
units are to operate next to one another allow a minimum of 60" between units or pairs of units. Also, a vertical
clearance of 60" should be maintained between units. Units installed on the bottom floor should be mounted
at least 6" off of the ground.
SMALL RECESS OK 60" 60"
D D D
60" E
60" E
D D D
J
6" 7_
Figure2
Any time obstructions are present use
the following guidelines for proper
spacing from the VERT-I-PAK louver:
• For minor obstructions such as lamp
poles or small shrubbery aclearance
of 24" from the outdoor louver should
be maintained.
• For major obstructions such as a solid
fence, wall or other heat rejecting
device like a condensing unit, a mini-
mum distance of 72" should be kept.
6" 3
D D
D D
_A_
LARGER RECESS OK IF A> 5xB
\
D
D
60'_
D
D
BUILDING
OUTDOOR "72"
UNIT
MAJOR OBSTRUCTION
FENCE
H
12"
The above suggestions are for reference only and do not represent all possible installations. Please contact the factory
for information regarding affects of other installation arrangements.
By following these simple recommendations you can be confident that your Friedrich Vert-I-Pak ®will provide years
of worry-free operation.
3

920-075-07 (10-03)
Section I. GeneralSpecifications
MODEL NUMBER
SERIES
V=Vertical Series
E=Cooling with or without electric heat
H=Heat Pump
DESIGN SERIES
A = 32" Cabinet
NOMINAL CAPACITY
A-Series (Btu/h)
09 = 9,000
12 = 12,000
18 = 18,000
VOLTAGE
K = 208/230V-1Ph-60Hz
MODEL:
Voltage (V)
Refrigerant
Chassis Width
Chassis Depth
Chassis Height **
Shipping Wx D x H
Supply Duct Cellar***
Drain Connection
Min. Circuit Amps
CFM Indoor
Max. Duct ESP
V A
V(E,H)A09
230 / 208
R-22
23.125"
23.125"
32.25"
25,00" x 28,50" x35.00"
10"
3/4" FPT
.3 in. water
ENGINEERING CODE
OPTIONS
RT = Standard Remote Operation
SP = Seacoast Protected
ELECTRIC HEATER SIZE
A-Series
00 = No electric heat
25 = 25 KW
34 = 3.4 KW
50 = 5.0 KW
V(E,H)A12
230 /208
R-22
23.125"
23.125"
32,25"
26.00" x 28.50" x 35.00"
10"
3/4" FPT
See Chassis Nameplate
See Charts 2 & 3 (Page 10)
,3in.water
V(E,H)A18
230 /208
R-22
23,125"
23,125"
32.25"
26.00" x 28.50" x 35.00"
10"
3/4" FPT
,3 in. water
NOTES:
** Height includes 2" ductcollar & isolatorsunder unit.
*** Factory collar accepts 10" flex duct.
4

920-075-07(10-03)
II. Installation
1) UtilityClosetDimensions
Recommended utilityclosetdimensions anda typical indoorinstallationareillustrated inFigure 3. Three inches minimumclearance on
three sides of the unit must be allowed for return airflow, installationaccess and service access. See Figures 3 and 4 for clearances
and referencedimensions.
Figure3
25"x 20" Filter
(Field Supplied)
Typical Utility Closet
VPRG4 Access Panel and
Return Air Filter Grille
See Figure 8, Page 10
for return air options
Chassis Shownin Closet, on Optional Platform
Rigid Ductwork
Electrical
Connection
Flexible Ductwork
,VPAWP1-8/1-14
Wall Plenum
Plenum Divider
Wiring
Power
Disconnect
3/4" FPT Drain
Connection
• Vert-I-Pak Chassis dimensions:
23 _/e"wide x 23 _/_'deep x32 V4"high.
• VPAWP1-8/1-14 WallPlenumcut-out
dimensions24 SlY'wide x307/j, high.
• VPRG4 Access Panel cutoutdimensions:
27"wide by 553/4"high.
• See Figure9 (Pg11)for properchassis
installation.
Figure4
Top View f
7 tl
•2 wl
Optional
Platform
Chassis installs
23/e'' into Plenum
3" Clearance on all three sides
minimum for service and installation•
f
6t_
5

920-075-07(10-03)
2) Wall PlenumandArchitecturalLouverInstallation
A, Install the wall plenum (VPAWP1-8/1-14) components in accordance with the installation instructions provided with each accessory,
O IMPORTANT REMINDER: FRIEDRICH WALL PLENUM IS NOT DESIGNED TO CARRY STRUCTURAL
B, Ensure that the divider is adjusted propedy for the depth of the wail in accordance with the accessory installation manual
LOADS. PROPER WALL HEADER CONSTRUCTION IS REQUIRED. THE PLENUM REQUIRES
PROPER FLASHING, SHIM AND CAULK FOR A WEATHER RESISTANT INSTALLATION.
Figure5
WallPlenum& OutdoorLouverInstallation
Proper Header Caulk all 8
flange corners
Proper Flashing
InsideWall Plenum
Proper Caulking_
(Part B)
ProperCaulking
Architectural louver VPAL2 mounted
on the outside wall plenum (PartA)
• Rough opening dimension 24 %" wide x 307/8"high,
• Ensure that the bottom of the plenum is 3/4"fromthe floor of the closet,
• For proper airflow, maintain a minimum distance of 12" between Vert-I-Pak units (see Figure 1,page 3),
Consult the factory for any installation or application questions.
6
Proper Flashing

3) Electrical Data
Electrical Data
Model
Voltage (V)
LRA - Comp. (A)
Cooling Current (A)
MIN. Ckt. Amps (A)
Power Connection
Sample Nameplate (see your chassis nameplate)
230/208 230/208 230/208
21 21 21
4.4/4.9 4.4/4.9 4.4/4.9
15 20 30
HARD WIRED
920-075-07(10-03)
/
230/208 230/208 230/208
24.0 24.0 24.0
5.5/6.1 5.5/6.1 5.5/6.1
15 20 30
HARD WIRED
230/208 230/208 230/208
47 47 47
9.2/10.2 9.2/10.2 9.2/10.2
15 20 30
HARD WIRED
MODEL NO 1
SERIAL NO *
FRIEDRICH AIR CONDITIONING CO.
SAN ANTONIO r TEXAS
VOLTS: 24,33,34
VOLTAGE RANGE: 255-197
REFRIG CHARGE: 70ZS. R22
DESIGN PRESSURE: 575 PSIG HS/150 PSIG LS
COOLING: BTU/HR 8
SEER: 10 COP: 16
HEAT PUMP BTUIRR: 14
TOTAL COOLING AMPS: 9
TOTAL ELEC. HEAT AMPS: 15
ELECTRIC HEAT WATTS: 18
FOR PERMANENTLY CONNECTED UNITS ON
COMP'. PLA 11 LRA 12
MOTOR: FLA 13 RP 19
HEATER AMPS: 17
MIN. CKT AMP ~0 US
OR HACR TYPE CIRCUIT BREAKER.
GENERAL UNIT INFORMATION:
MAX OUTLET AIR TEMPERATURE: 2OO'F
MAX EXTERNAL STATIC PRESSURE ELECTRIC
HEAT'..5 IN. WATER
"O" CLEARANCE TO COMBUSTIBLE MATERIAL
USE ON SINGLE OUTLET CIRCUIT ONLY
WARNING
ELECTRICAL SHOCK AND
MOVING PARTS HAZARD
CAN CAUSE INJURY OI
PUL
BEFORE
SERVICING.
LISTED
120524
HEATING AND
COOLING EQUIPMENT
APPLICABLE PATENTS:
US 6,065,296
NY MEA NO.: 295-00-E
USE ONE OF THE
FOLLOWING ITEMS
TO COMPLETE THE
ASSEMBLY
WALL PLENUM:
VPAWP1 -8
VPAWPI -14
OUTDOOR GRILLE
VPAL2
INDOOR GRILLE
VPRGI
VPRG2
VPRG5
Important: all 208/230v chassis must be hard wired withproperly sized breaker. See nameplate for specific chassis
electrical requirements. See page 8- Figure 5 for unitwiring and wall thermostat wiring. See page 8for wire size. Use
HACR type breakers to avoid nuisancetrips. All field wiring must be done in accordance with nec and local codes.

3) ElectricalData (continued)
920-075-07 (10-03)
Figure6
Electrical Requirements
Note:All field wiring must complywith NEC andlocal codes.It
is the responsibilityof the installerto insurethat the electrical
codes are met.
Wire Size
Fuse/Circuit breaker indicated on unit'srating plate (See sample
Breaker on page 6), Proper current protection to the unit is
Grounding unit, orthrough separate ground wire provided on
Wire Sizing with local and national codes, NOTE: Use copper
Use ONLY wiring size recommended for single
outlet branch circuit.
Use ONLY type and size fuse or HACR circuit
the responsibility of theowner.
Unit MUST be grounded from branch circuit to
permanently connected units. Be sure that branch
circuit or general purpose outlet is grounded,
Use recommended wire size given in tables and
installa singlebranchcircuit. Allwidng mustcomply
conductors only.
Electrical RatingTables
NOTE: Use copper conductors ONLY, Wire sizes are per
NEC Check local codes for overseas applications
Recommended branch circuit wire sizes*
Nameplate AWG Wire size**
maximum circuit
breaker size
15A 14
20A 12
30A 10
AWG --American Wire Gauge
* Single circuitfrom main box
** Basedon copperwire, single insulatedconductor at 60°C
Electricshock hazard.
Turn OFF electric power before service
or installation.
All electricalconnectionsandwiringMUST
be installedby a qualified electrician and
conformtotheNationalElectricalCodeand
all local codes which havejurisdiction.
Failure to do so can result in property
damage, personal injury and/or death.
8

3) ElectricalData (continued)
Figure7
Electrical & Thermostat Wiring Diagrams
920-075-07 (10-03)
FOR 208VOLT MODELS ONLY:
MOVE THE WHITE WIRE AS
SHOWN BELOW
THERMOSTAT CONNECTIONS
(REAR)
RT2
THERMOSTAT
(FRONT)
DEFROST
COOL RELAY
COM. 208V 240V
TRANSFORMER
24V
T-STAT
HEATER
1
Note: the diagram above illustratesthe typical thermostat wiring and 208volt transformer wiring.
See the unitcontrol panel for the actual unit wiring diagram and schematic,
9

920-075-07(10-03)
4) IndoorReturnAirGrilleInstallation
There are three Indoor Return Air Grille options as shown in Figure 8, Choose the optionthat best suits your needs. Use the installation
instructions providedwith accessories for installation details,
Figure8
ReturnAir GrilleOptions
Option I
VPRG4
ReturnAir Grille with AccessPanel
A field-supplied(25"x 20")filteris
mountedinsidethehingedaccessdoor.
All Vert-I-Pak chassis are shipped with a
14x 20 filter installed. If an accessory filter
holder is to be used, you MUST remove the
VPRG2
_ ....... ReturnAir Grille
Unitrequiresa field-supplied
I
_ _ _\_ _÷ 16"x20" filter.
Notes:
A. These are the Friedrich recommended returnair grine /filter / access panel arrangements. Consultthe factory on other
arrangements. Improper return airarrangements will cause performance problems.
B. Return air arrangements areshown from the front, butcan also be installedfrom the right orleft sideof the unit.
accessdoororpanelanda
factory shipped filter from the chassis. Do
NOT use two filters
10

920-075-07(10-03)
5) DuctworkPreparation
1) Duct ESP:
To determine your system's indoorexternal static pressure
(ESE in inches of water) use a duct calculator (as provided
by your duct supplier). Include all flex duct transitions and
discharge grille(s). If flex duct is used, be sure all the slack
is pulled out of the flex duct. Flex duct ESP can increase
considerably when not fully extended. DO NOT EXCEED a
total of .30 ESP, as this is the MAXIMUM design limit for the
VERT-I-PAK A-Series unit.
2) Determining the Indoor CFM: Chart A - CFM
18000 12000/9000
.00 520 420
.10 510 410
.20 500 370
30 490 330
6) ChassisInstallation
Install the followingcomponents asshown in Figure 5.
A,
Ensurethat the wallplenumis installedinaccordance with
the VPAWP1-8/1-14 Installation Manual,
B.
Place the chassis intothe closet with the outdoor side
facing thewall plenum opening.
C.
Slide the chassis intothe wall plenum until the plenum
divider seal isestablished. (See Figure 9)
Figure9
Slide-in View/Chassis Installation
/
3) Correct CFM (if needed):
Chart B - Correction Multipliers
230V 1.00
208V 0.97
Heating 1.00
Cooling 0.95
TheVert-I-Pakchassismustbeinsertedintothewailplenumsothatthe
plenumdividergasketmakescontactwiththeplasticcondenserbaffleon
the unit.The chassiswill fit approximately23H' intothe wall plenum.
11

920-075-07(10-03)
7) ChassisFinalConnections
With the chassis in place,you are nowready to begin chassis
connections:
A. Move the thermostat switches to "OFF" and "AUTO." This
will keep the thermostat from cycling the chassis until final
connections arecomplete.
B. Connecttheductworkontothel0"coilar. Plasticwireties(field
supplied)are suggested to securethe ductworkinplace. Use
2 wire ties, onefor each inner and outer flex duct sleeve.
C. Using the two 3/4" plugs supplied with the unit,plug two of
the condensate drain holes. Connect a drain to the third
condensate exit location. Be sure to use teflon tape or
approved pipe sealant on all drain connections and plugs.
(See Figure 10.)
D. For208Voltpoweronly: youmustmovethetransformerwire
as shown inFigure 7, Page 9.
Electricalshockand moving parts hazard cancause injury
or death. Ifyou havenot done so, pull out the disconnect
headfound onthe front of chassis beforecontinuing instal-
lation! Disconnect external power at the breaker.
E. Review the Final Installation Checklist on Page 12 before
replacing the power quick disconnect, reconnecting power
tothe chassis, plugging inthe remote thermostat harness, or
operating the chassis.
Figure10
Drain Connection and Location
3*'
CAUTION
[] The unit basepan has three (3) provisions (left, right, and
rear) for connecting an external condensate drain.
[] A field supplied condensate drain system must be
connected to one of the three (left, right, or rear) 3/4"
FPT connections on the unit basepan. Use of rear fitting
may result in staining of the outside wall.
[] The remaining b,vo connections must be plugged using
the two 3/4" pipe plugs (provided) and field supplied
teflon tape or pipe joint compound.
[] The addition of a secondary drain pan may be required.
Follow all applicable codes.
[] Failure to follow these procedures may result in serious
property damage.
RT2 DigitalThermostat
8) FinalInstallationChecklist
[] Correct line voltage?
[] Chassis decklevel?
[] Plenum divider baffle installed?
[] Wall plenumcaulked? Level?Flashing?
[] HACR type breaker/fuse?
[] Single circuit only?
[] Ductwork connected?
[] Chassis weather seal in place?
[] Wall thermostatwired correctly?
[] Chassis insertedinto plenum?
12

920-075-07(10-03)
III. ChassisOperation
9) Remote Thermostat Control
Thechassisrequiresa simplesinglestageheat-coolwall thermostat.
Each chassis comes with a terminal strip located inthe electrical
control box. All internalchassiswiring (low&highvoltage) isfactory
ready for 230 Volt operation. For 208 Volt operation a singlewire
MUSTBE CHANGED ONTHE TRANSFORMER. Referto Figure
7 on page9.
10) LowAmbientProtection
Eachchassis isequippedwithLowAmbient Protectionintheform of
a suction linethermostat.This thermostat will prevent compressor
operation at low suction line temperatures. Each chassis is also
equipped with afactory installed bellows thatwill drainwater from
the base panto preventthe fan slinger fromfreezing during winter
weather.
11) HeatingDefrost (Heat PumpModels Only)
All Heat Pumps have a passive heating defrost system. Defrost
occursas neededand automaticallyswitchestoelectricheat during
defrost.When theoutdoor ambienttemperaturedropsbelowa 45°F
factory setting,the chassis automaticallyswitches to electric heat.
As outdoor ambient temperatures rise above 45°F, the chassis
returns to the heat pump mode. The changeover temperature
is user adjustable from approximately 32°F - 55°E The defrost
thermostat may also be used to lock out the compressor in an
emergency heat situation.
IV.Service& Warranty
14) Servicing/Chassis QuickChangeouts
The chassis isdesigned for quick disconnect and change out. For
minor electrical service, the control boxcover lifts straight upafter
the screws & disconnect headare removed. For major electrical,
refrigeration and fan service the chassis must be removed from
utility closet.
ToRemovethe Chassis from the Closet:
A Switch the wail thermostat off.
B Pullthe power disconnect located inthe frontof the chassis.
C Turnoff all powerto the unit at the main breaker or
disconnect.
D Disconnectthe thermostat wiring.
E Disconnectthe electrical connection.
F Disconnectthe ductwork.
G Disconnectthe drain connection.
H Slide the chassisout of thewall plenum.
I Lift the chassisout of the utility closet.
15) Warranty
All service work must be done by a qualified servicer. See
Warranty on the next page, and consult your dealer or contractor
for details.
12) FreshAir Door
The Fresh Air Door is an "intake" system. The fresh air door is
opened via a slide on the front of the chassis located just above
the indoorcoil. Move the slide left to open and right to close the
fresh airdoor. The system iscapable of upto 60 CFM of freshair
@ ~.3" H20internalstatic pressure.
13) CondensateDisposalSystem
The internal drain connections are 3/4" FPT fittings on the right,left
and outdoorside oftheunit.See Figure10onpage 12.The chassis
is designed with a condensate drain systemthat has 3 parts. The
three parts work asfollows:
Part 1: The system's first stage increasesenergy efficiency
utilizing a factoryinstalled fan that slings the cold
condensate ontothe hotoutdoor coil.
Part2: When high outdoor humidity preventsthe slinger from
disposing ofall the condensate, the excess condensate
overflows into the internaldrain connection.
Part3:
If Parts 1& 2 failfor any reason, excess condensate
overflows from aspillway directly intothe wall plenum
to the outside ofthe building. IF THIS OCCURS, THIS
ISYOUR WARNING THAT THE CHASSIS OR DRAIN
NEEDS SERVICING.
Electricalshock andmoving parts hazardcan causeinjury
or death. Pull out the disconnect headfound on the front
ofthe chassis before servicing.
Followall codes when working with the condensate drain
system. A secondary drain pan may be placed beneath the
chassis to preventcondensated spillage due to improper
installation or unit malfunction.
13

920-075-07 (10-03)
FRIEDRICH AIR CONDITIONING CO.
Post Office Box 1540 • San Antonio, Texas 78295-1540
(210) 357-4400. FAX (210) 357-4480
VERT- I-PAK ®A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONERS
LIMITED WARRANTY
SAVE THIS CERTIFICATE. it gives you specific rights, you may also have other rights which may vary from state to state and province
to province.
Inthe event that your unit needs servicing, contact your nearest authorized service center. If you do not know the nearest service center,
ask the company that installed your unit or contact us- see address and telephone number below. To obtain service and/or warranty parts
replacement, you must notify an authorized FRIEDRICH Air Conditioning Co. service center, disf_butor, dealer, or contractor of any defect
within the applicable warranty pedod.
When requesting service: please have the model and serial number from your unit readily available.
Unless specified otherwise herein, the following applies:
FRIEDRICH VERT-I-PAK A SERIES VERTICAL AIR CONDITIONERS AND HEAT PUMPS
LIMITED WARRANTY- FIRST YEAR (Twelve (12) months from the date of installation). Any part found to be defective in the material
or workmanship will be repaired or replaced flee of charge by our authodzed service center durleg the normal working hours; and
LIMITED WARRANTY - SECOND THROUGH FIFTH YEAR (Sixty (69) months from the date of installation). ON THE SEALED
REFRIGERATION SYSTEM. Any part of the sealed refdgeratiee system that is defective in material or workmanship wiUbe repaired or
replaced free of charge (excluding freight charges) by our authodzed service center dudng normal working hours. The sealed reffigerafiee
system consists of the compressor, metering device, evaporator, condenser, reversing valve, check valve, and the interconnecting tubing.
These warranties apply only while the unit remains at the original site and only to units installed inside the continental United
States, Alaska, Hawaii, Puerto Rico and Canada. The warranty applies only if the unit is installed and operated in accordance with
the printed instructions and in compliance with applicable local installation and building codes and good trade practices.
For international warranty information, contact the Friedrtch Air Conditioning Company - International Division.
Any defective part to be replaced must be made available to FRIEDRICH in exchange for the replacement part. Reasonable proof must
be presented to establish the dste of install, otherwise the beginning date of this certificate will be considered to be our shipment date plus
sixty days. Replacement parts can be new or remanufactured. Replacement parts and labor are only warranted for any unused portion
ofthe unit's warranty.
We will not be responsible for and the user will pay for:
1. Service ceils to:
A) Instruct on unit operation. B) Replace house fuses or correct house wiring. C) Clean or replace air filters. D) Remove the unit
from its installed location when not accessible for service required. E) Correct improper installations.
2. Parts or labor provided by anyone other than an authorized service center.
3. Damage caused by:
A) Accident, abuse, negligence, misuse, riot, fire, flood, or acts ofGod. B) Operating the unit where there is a corrosive atmosphere
containing chlorine, fluorine, or any damaging chemicals (other than in a normal residential environment). C) Unauthorized altera-
tion or repair of the unit, which in turn affects its stability or performance. D) Failing to provide proper maintenance and service. E)
Using other than a "Seacoast Protected" unit in a coastal environment. F) Using an incorrect power source. G) Faulty install_ee
or application of the unit.
We shall not be liable for any incidental, consequential, or special damages or expenses in connection with any use or failure
of this unit. We have not made and do not make any representation or warranty of fitness for a particular use or purpose and
there is no implied condition of fitness for a particular use or purpose. We make no expressed warranties except as stated in
this certificate. No one is authorized to change this certificate or to create for us any other obligation or liability in connection
with this unit. Any implied warranties shall last for one year after the original purchase data. Some states and provincesdo not
allow limitations on how long an implied warranty or condition lests, so the above limitations or exclusions may not apply to you. The provi-
sions of this warranty are in addition to and not a modification of or subtraction from the statutory warranties and other rights and remedies
provided by law.
In case of any questions regarding the provisions of this warranty, the English version will govern.
Rev 9-03
14

V. Vert-I-Pak Accessories
MODEL DESCRIPTION PHOTO
WALL PLENUM Two-part sleeve that telescopes inand
out from 5_/2"to 8" in depth. The wall plenum sits inside
VPAWP1-8
the exterior wall penetration.
DIMENSIONS: 303&"high x 24W' wide.
CUTOUT DIMENSIONS: 30W' high x 24_&"wide.
920-075-07(10-03)
VPAWP1-14
VPAL2
VPSC2
RT2
VPRG4
Same as VPAWP1-8, but telescopes 8" to 14" as required.
ARCHITECTURAL LOUVER Extruded aluminum louver
that attaches to the outdoor section of the wall plenum.
DIMENSIONS: 31 _/_6"high x 259h6"wide.
Same as VPAL2 but can be ordered in a special color to
match the exterior wall.
DIGITAL THERMOSTAT Digital electronic thermostat with
"one touch" adjustment. Mounts to wall for control of unit.
ACCESS PANEL / RETURN AIR GRILLE - Serves as
an access panel to chassis and interiorreturn air grille.
A field-supplied (25" x 20") filter is mounted insidethe
hinged access door.
DIMENSIONS: 58" high x 29" wide.
CUTOUT DIMENSIONS: 553/4" high x 27" wide.
VPRG2
RETURN AIR GRILLE - Interior return air grille that
hinges to allow a field supplied (16" x 20") filter to slip
inside. Must be used when an access door / panel
already exists in closet.
DIMENSIONS: 187h6"high x 223/8''wide.
_iqilf
15

FriedrichAirConditioningCo.
PostOfficeBox15401SanAntonio,TX78295-1540
4200N,PanAmExpresswayLSanAntonio,TX78218-5212
(210)357-4400fax(210)357-4480www,friedrich.com
Printed in the U.S.A. 920-075-07 (10-03)