Friedrich Ms36y3f, Mr36y3f Installation Instruction

Refrigerant
R410A
Ceiling Suspension Type
CONNECTION PIPE REQUIREMENT
ELECTRICAL REQUIREMENT
••
••
Electric wire size:
Decide the mounting position with the customer as follows:
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks. Use heat insulation with heat resistance above 248 °F. (Reverse cycle model only) In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat insulation around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that is 15 mm (19/32 in.) or thicker and if the expected humidity exceeds 80%, use heat insulation that is 20 mm (3/4 in.) or thicker. If heat insulation is used that is not as thick as specified, condensation may form on the surface of the insulation. In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 68 °F).
••
••
Use pipe with water-resistant heat insulation.
INDOOR UNIT
(1) Install the indoor unit level on a strong wall which is not subject to vibration. (2) The inlet and outlet ports should not be obstructed : the air should be able to
blow all over the room. (3) Do not install the unit where it will be exposed to direct sunlight. (4) Install the unit where connection to the outdoor unit is easy. (5) Install the unit where the drain pipe can be easily installed. (6) Take servicing, etc., into consideration and leave the spaces shown in the
figure. Also install the unit where the filter can be removed.
WARNING
Select installation locations that can properly support the weight of the indoor and outdoor units. Install the units securely so that they do not topple or fall.
CAUTION
1 Do not install where there is the danger of combustible gas leakage.
2 Do not install the unit near heat source of heat, steam, or flammable gas.
3 If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
[FOR HALF CONCEALED INSTALLATION]
Diameter
Gas
15.88 mm (5/8 in.)
Liquid
9.52 mm (3/8 in.)
MIN.
1.0
Connection cord (mm )
MAX.
2.5
••
••
Install all electrical works in accordance to the standard.
••
••
Install the disconnect device with a contact gap of at least 3 mm (1/8") in all poles nearby the units. (Both indoor unit and outdoor unit)
••
••
Install the circuit breaker nearby the units.
2
SPLIT TYPE AIR CONDITIONER
INSTALLATION INSTRUCTION SHEET
(PART NO. 9364488028)
For authorized service personnel only.
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all danger, warning, and caution notices given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury and the potential for product or property damage.
Hazel alerting symbols
Electrical
Safety / alert
If Necessary, Get Help
These instructions are all you need for most installation sites and mainte­nance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
Ground the unit following local electrical codes.
Connect all wiring tightly. Loose wiring may cause overheating at con­nection points and a possible fire hazard.
WARNING:
CAUTION:
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing...
...In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
...In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
...In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnor­mal vibration.
...In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
...In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
Keep all tubing runs as short as possible.
Use the flare method for connecting tubing.
Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion the refrigerant tubing for your particular model is specified as either “small” or “large” rather than as “liquid” or “gas”.
When Servicing
Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring.
Keep your fingers and clothing away from any moving parts.
Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
After installation, explain correct operation to the customer, using the operating manual.
GENERAL
This INSTALLATION INSTRUCTION SHEET briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
Ceiling panel
Ceiling panel
INDOOR UNIT
80 mm (3-1/8")
or over
150 mm (6")
or over
10 mm (3/8") or over
2,400 mm (94")
or more
Floor
Ceiling
INDOOR UNIT
80 mm (3-1/8")
or over
Ceiling
150 mm (6")
or over
10 mm (3/8") or over
2,400 mm (94")
or more
Floor
This air conditioner uses new refrigerant HFC (R410A).
The basic installation work procedures are the same as conventional refrigerant models. However, pay careful attention to the following points:
1 Since the working pressure is 1.6 times higher than that of conventional refrigerant models, some of the piping and
installation and service tools are special. (See the table below.) Especially, when replacing a conventional refrigerant model with a new refrigerant R410A model, always replace the conventional piping and flare nuts with the R410A piping and flare nuts.
2 Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with
conventional refrigerant and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is 1/2 UNF 20 threads per inch.]
3 Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant models. Also, when
storing the piping, securely seal the openings by pinching, taping, etc.
4 When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases, and
always charge from the liquid phase side whose composition is stable.
5 When moving, if the compressor stops during pump down, close the valve immediately.
Special tools for R410A
Copper pipes
Contents of change
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing of other refrigerants, the diameter of each port has been changed. It is recommended the gauge with seals –0.1 to 5.3 MPa (–76 cmHg to 53 kgf/cm
2
) for high pressure. –0.1 to
3.8 MPa (–76 cmHg to 38 kgf/cm
2
) for low pressure. To increase pressure resistance, the hose material and base size were changed. A conventional vacuum pump can be used by installing a vacuum pump adapter. Special gas leakage detector for HFC refrigerant R410A.
Tool name
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
Thicknesses of Annealed Copper Pipes (R410A)
STANDARD PARTS
The following installation parts are furnished. Use them as required.
INDOOR UNIT ACCESSORIES
Q’ty
1
2
1
2
1
1
2
1
Name and Shape
Remote control unit
Battery (penlight)
Remote control unit holder
Tapping screw (ø3 × 12)
Drain hose insulation
VT wire
Coupler heat insulator (large)
Coupler heat insulator (small)
Nylon fastener
Special nut A (large flange)
Special nut B (small flange)
Installation template
Auxiliary pipe assembly
Application
Use for air conditioner operation
For remote control unit
For mounting the remote control unit
For remote control unit holder installation
Adhesive type 70 × 230
For fixing the drain hose L 280 mm
For indoor side pipe joint (Gas pipe)
For indoor side pipe joint (Liquid pipe)
For fixing the coupler heat insulator
For installing indoor unit
For installing indoor unit
For positioning the indoor unit
For connecting the piping
Large
4
Small
4
4
4
1
1
OPTIONAL PARTS
The following options are available.
••
••
DRAIN PUMP UNIT: UTR-DPB241 (P/N 9034087001)
••
••
WIRED REMOTE CONTROLLER UNIT: UTB-UUB (P/N 9075887004)
It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants. As an air conditioner using R410A incurs pressure higher than when using conventional refrigerant, it is necessary to choose adequate materials. Thicknesses of copper pipes used with R410A are as shown in the table. Never use copper pipes thinner than that in the table even when it is available on the market.
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
0.80 mm (0.0315 in.)
0.80 mm (0.0315 in.)
0.80 mm (0.0315 in.)
1.00 mm (0.0394 in.)
Pipe outside diameter
Thickness
1
INSTALLATION PROCEDURE
2
PREPARING INDOOR UNIT
INSTALLATION
REMOVE THE INTAKE GRILLE AND SIDE COVER
(1) Remove the two Air filters. (2) Remove the two Intake grilles.
For 4 Left rear drain and 5 Left drain: Remove air filters and intake
grilles at three places. (Refer to “2 INDOOR UNIT INSTALLATION”.)
(3) Remove the Side cover A (Right side) and Side cover B (Right and
Left side).
For 5 Left drain : Remove both the Side cover A (Right and Left
side). (Refer to “2 INDOOR UNIT INSTALLATION”.)
(4)
This air conditioner can be set up to intake fresh air. For information about how to install for fresh-air intake, refer to “= FRESH-AIR INTAKE”.
INDOOR UNIT INSTALLATION
You can use the accessory template to help you install the indoor unit. The template helps you determine the appropriate locations for suspen­sion bolts and pipe opening (drain pipe and connection cord).
[For Half-Concealed Installation]
••
••
Suspension-bolt pitch should be as shown in the figure.
2. SELECT PIPING DIRECTION
Select connection piping and drain piping directions.
[FOR 4 Left rear piping, 5 Left piping]
••
••
Transfer the Drain cap and Drain cap seal.
Drain cap seal
Drain cap
Indoor unit Drain pan
Drain cap seal
Drain cap
Push cap all the way on (as far as it will go).
[If using anchor bolts]
(1) Drill holes for anchor bolts at the locations at which you will set the
suspension bolts. Note that anchor bolts are M10 bolts (to be ob­tained locally).
(2) Install the anchor bolts, then temporarily attach special nut “B” (in-
cluded) and a locally-procured M10 nut to each of the bolts.
Anchor-Bolt Strength 980 to 1470 N (100 to 150 kgf)
4. INSTALLING THE INDOOR UNIT
(1) Lift unit so that suspension bolts pass through the suspension fittings
at the sides (four places), and slide the unit back.
Wall
Ceiling
Ceiling
M10 Anchor Bolt (Obtained locally)
Special nut B (Included)
M10 Nut (Obtained locally)
10 to 15 mm
(3/8" to 19/32")
1. LOCATION OF CEILING SUSPENSION BOLTS
Suspension bolt pitch 1600 mm (63")
Dimensions (Space Required for Installation)
30 mm (1-3/16")
10 mm (3/8") 155 mm (6-3/32")
300 mm (12")
INDOOR UNIT (TOP VIEW)
INDOOR UNIT
Suspension bolt should extend outward 30 to 75 mm. (1-3/16" to 2-31/32")
30 mm (1-3/16")
3. DRILLING THE HOLES AND ATTACHING THE SUSPENSION BOLTS
(1) Drill ø25 mm holes at the suspension-bolt locations. (2) Install the bolts, then temporarily attach Special nuts A and B and a
normal M10 nut to each bolt. (The two special nuts are provided with the unit. The M10 nut must be obtained locally.) Refer to the figure.
Bolt Strength 980 to 1470 N (100 to 150 kgf)
Ceiling panel
Special nut A (Included)
Special nut B (Included)
M10 Nut (Obtained locally)
10 to 15 mm
(13/32" to 19/32")
INDOOR UNIT
Wall
Ceiling panel
(2) Fasten the indoor unit into place by tightening-up the special “B” bolts
and the M10 nuts. Make sure that unit is secure and will not shift back and forth.
[For Half-Concealed Installation]
When installing the indoor unit in a semi-concealed orientation, make sure to reinforce the insulation of the unit on all sides. Drops of water may fall from the unit if it is not thoroughly insulated.
Glass wool insulate (10 to 20 mm (3/8" to 3/4") thick)
INDOOR UNIT
(Top view)
Wall
Ceiling panel
CAUTION
Install the drain pipe in accordance with the instructions in this installation instruction sheet and keep the area warm enough to prevent condensation. Problems with the piping may lead to water leaks.
••
••
Install the drain pipe with downward gradient (1/50 to 1/100) and so
there are no rises or traps in the pipe.
••
••
Use general hard polyvinyl chloride pipe (VP25) [outside diameter
38 mm (1-1/2")].
••
••
During installation of the drain pipe, be careful to avoid applying
pressure to the drain port of the indoor unit.
••
••
When the pipe is long, install supporters.
••
••
Do not perform air bleeding.
••
••
Always heat insulate (8 mm (5/16") or over thick) the indoor side of the
drain pipe.
GOOD
BAD BAD
Drain pipe
Arrange the drain pipe lower than this portion.
Lifted up
Wave
End in water
Supporter
1.5 to 2 m
(5 to 6.5 ft)
(1) Install insulation for the drain pipe.
Cut the included insulation material to an appropriate size and adhere it to the pipe.
Drain pipe
Insulation for drain pipe (To be obtained locally. Length should be at least 8 mm (5/16").)
Drain pipe insulation (accessories)
Indoor unit (drain port)
(2) If “1 Right rear piping” : fasten the drain pipe with VT wire so that the
pipe slopes correctly within the indoor unit.
Indoor unit (rear view)
VT wire
Drain hose
Drain pipe insulation
Drain pipe
No gap
10 mm (3/8") or over
Indoor unit
1 Right rear piping
5 Left piping
(Drain pipe only)
4 Left rear piping
(Drain pipe only)
2 Top piping
(Connection pipe only)
3 Right
piping
Cut off the piping outlet cutting groove with a hacksaw, etc.
INDOOR UNIT (TOP VIEW)
Air filter
Intake grille
Tapping screw
INDOOR UNIT
Side cover A (Right side)
Side cover B
(Left side)
Side cover B (Right side)
Drilling position for Suspension bolt
Ceiling
Wall
Template
Drilling position for piping
Ceiling Opening: 1580 mm (62") 40 mm (1-9/16")
Ceiling panel
Ceiling Opening: 640 mm (25-3/16")
15 mm (19/32")
Suspension bolt should extend outward 30 to 50 mm. (1-3/16" to 1-31/32")
INDOOR UNIT
Ceiling panel
40 mm (1-9/16")
CAUTION
In order to check the drainage, be sure to use a level during installation of the indoor unit. If the installation site of the indoor unit is not level, water leakage may occur.
5. DRAIN PIPING
Loading...
+ 5 hidden pages