Friedrich MR36TQY3JM User Manual

Multi Zone Air Conditioner SVC MANUAL(Exploded View)
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.
MODEL : MR36TQY3JM
960-920-04
1. Specification
Capacity(*)
Btu/h Class
34,000
Power Input (Min.~Rated~ Max.)
Cooling kW
0.77~2.72~ 3.92
Heating kW
1.12~3.58~4.1
Running Current
Cooling A
3.3~11.8~17.0
Heating A
4.9~15.5~17.8
Starting Current
Cooling/Heating
A
-
Power Supply
Ø / V / Hz
1/208 - 230/60
Power Supply Cable (Outdoor)
No.x AWG
3 × 12
Transmission Cable (Outdoor to Indoor unit )
No.x AWG
4 x 18 (Including Earth)
900 x 1,165 x 370
(35 7/16 x 45 7/8 x 14 9/16)
Net Weight
kg(lbs)
95(209.4)
Max. Number of Connectable Indoor Units
4
Compressor
Type
Twin-Rotary
Qty x Model
GPT425DBA
Motor type
BLDC
Oil charge volume
cc
1300
Oil Type
FVC68D
Refrigerant
Cycle A Charge (at 7.5m)
g(oz)
3,500(123.46)
Cycle B Charge (at 7.5m)
g(oz)
-
Type
R410A
Control
EEV
Heat Exchanger
(Rows x Column x FPI) x No.
(2R x 26C x 17) x 2
Coil tube dia.
mm(inch)
7(0.276)
Defrosting Method
Reversing cycle
Fan motor
Capacitor
μF/Vac
-
Drive
Direct (DC)
Discharge Direction(Side/Top)
Side
Air Flow Rate x No. of Fan
CMM(CFM)
60(2,118) x 2EA
Sound Level(H)
Sound Pressure
dB(A)+3
57
Piping Connections
Liquid(Cycle A)
mm(inch)
6.35(1/4) × 4EA
Gas(Cycle A)
mm(inch)
9.52(3/8) × 4EA
Liquid(Cycle B)
mm(inch)
-
Gas(Cycle B)
mm(inch)
-
Piping length spec.
Max. total piping
m(ft.)
75(246.1)
Max. OD~ID piping
m(ft.)
25(82.0)
Piping length(no add'l refrigerant)
m(ft.)
30(123.0)
Max. Elevation Difference
Outdoor Unit~Indoor Unit
m(ft.)
15(49.2)
Indoor Unit~Indoor Unit
m(ft.)
7.5(24.6)
Operation Range
Cooling °C(°F)
-10 ~ 46 (14~114.8)
Heating °C(°F)
-15 ~ 24 (5~75.2)
Outdoor Unit
Dimensions
Outdoor Unit
W x H x D
mm(inch)
MR36TQY3JM
(Outdoor)
Note:
1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27C(80.6F) DB/19C(66.2F) WB
Heating: - Indoor Temperature 20C(68F) DB/15C(59F) WB Piping Length - Interconnecting Pipi ng Lengt h 7.5m
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
- Outdoor Temperature 35C(95F) DB/24C(75.2F) WB
- Outdoor Temperature 7C(44.6F) DB/6C(42.8F) WB
- Level Difference of Zero
Conversion Formula
kW = Btu/h x 0.0002931 cfm = CMM x 35.3
- 2 -
2. Function Table
Defrost / Deicing
O
High Pressure Switch
X
Low Pressure Switch
X
Phase protection
X
Restart Delay (3-minutes)
O
Self Diagnosis
O
Soft Start
O
Test Function
X
Auto operation(Artificial intelligence) O
Auto Restart Operation
O
Central control(LGAP)
X
PDI(Power Distribution Indicator)
X
PI485
X
Special function kit
Low ambient operation
O
Others
Thermistor
-
Category
Reliability
Convenience
CAC Network Function
Note :

• O: Applied, • X: Not applied, • - : No relation,

• Option: Model name & price are different according to options, and assembled in factory with main unit.
• Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Function
A4UW363FA2 [MR36TQY3JM]
- 3 -