Follett equipment enjoys a well-deserved reputation for excellent performance, long-term reliability and outstanding
after-the-sale support. To ensure that this product delivers that same degree of service, we ask that you take a
moment to review this manual before beginning the installation. Should you have any questions or require technical
help at any point, please call our technical service group at (877) 612-5086 or +1 (610) 252-7301.
Before you begin
After uncrating and removing all packing material, inspect the equipment for concealed shipping damage. If damage
is found, notify the shipper immediately and contact Follett Corporation so that we can help in the ling of a claim, if
necessary.
Check your paperwork to determine which con guration you have. Follett con guration numbers are designed to
provide information about the type of refrigerator you are receiving. Following is an explanation of the different item
numbers.
Casters(4) dual-wheel swiveling casters with toe locks
Insulation2.75" (7cm) thick, CFC-free foam insulation throughout
Lighting(2) full length side LED lights
Air circulation systemDucted air through 12 back plenum openings with front face return
Temperature probeStainless steel RTD (resistance temperature detectors) top, bottom probe standard
on - BB models, available as option on -LB, -PH models, immersible with panel quickdisconnect
Ambients
Intended for indoor use where ambient temperature typically does not exceed 80 F (27 C) and ambient relative
humidity does not exceed 60% RH. A heated door is recommended for higher humidity ambients.
Clearances
The top of the refrigerator must have 10 inches (25.4cm) of clear space above the refrigerator to ensure proper
ventilation of the refrigeration system.
The back of the refrigerator should have 1 inch (2.5cm) of clearance to allow for power cord clearance on unit and
an additional 1 inch (2.5cm) if the unit is to be plugged in directly behind the refrigerator.
Electrical specifications
115V, 60Hz, 1 phase
Running load amps: 8.4 amps without heated door; max 9.7 amps with door heater energized 100% (adjustable).
Full load amps (90% maximum continuous current per UL 471 at 40 C): 10.5 amps
Maximum size of branch circuit overcurrent device: 15 amp dedicated circuit
Refrigeration specifications
Refrigerant R134a, 11.4 oz (322g)
Detail drawing
76.75"
(195cm)
79.5"
(202cm)
29.75"
(76cm)
4 Installation 00926170 – REF20/25 LB, PH, BB
REF20
30.5" (78cm)
REF25
36.5" (93cm)
Installation
DANGER
• Do not tilt any unit further than 30° off vertical during
uncrating or installation
• Refrigeration module area contains mechanical, moving
parts. Keep hands and arms clear of this area at all
times. If access to this area is required, power to unit
must be disconnected rst.
1. Remove key taped to side of refrigerator cabinet and unlock door.
2. Remove casters from box packed inside refrigerator.
Note: California facilities requiring wall and oor anchors – refer to wall anchor
kit instructions (#00938241) packed with seismic kit before proceeding with
caster installation.
3. Unbolt refrigerator from pallet.
4. Rotate refrigerator on pallet to install casters (Fig. 1.1).
5. Install casters by hand one at a time using channel locks to tighten, until
caster meets against the bottom of cabinet (Fig. 1.2).
6. Peel protective lm from exterior walls of stainless cabinet.
Fig. 1
2
1
Adjust self-closing door
1. Roll refrigerator to desired location and lock as many casters as
possible (Fig 2.1).
2. Check door for sagging and, if necessary, turn sag adjustment screw
(Fig. 2.2) to align door squarely with refrigerator cabinet.
3. Check door for closing tension and adjust if necessary. To check closing
tension, open door 1" and turn screw (Fig. 2.3) counterclockwise until
you achieve positive close. (Light will go out) Then, turn another half
turn counterclockwise.
Install shelves (if equipped) and power up
1. If refrigerator is equipped with shelves, remove bag containing shelf
supports and position them in desired locations on each pilaster and
insert shelves (Fig. 3).
2. Plug refrigerator into a 115V 60Hz 15 amp dedicated outlet.
Fig. 2
Fig. 3
1
3
2
1
2
3
00926170 – REF20/25 LB, PH, BB Installation 5
Fill product bottle
1. Remove probe and cap from the top bottle and ll with solution used at
your facility (e.g., 50% glycerine and 50% water) (Fig. 4). Replace cap
and reinsert probe sensor.
2. If equipped with a bottom probe, perform same procedure for bottom
bottle.
ATTENTION INSTALLER
It is imperative that the top probe bottle be lled with a solution that your
facility uses to ensure proper operation of unit.
3. Press lower left corner of front facade door to access power switch
Remote communication connections are located on back side of top facade
(Fig.7).
Dry contacts
• Connection to NO or NC contacts provides remote alarming capability
• No temperature data is communicated
RS-485 port
• Connection provides real-time data streaming
– Temperature
– Alarms
– Refrigeration operation
• MODBUS protocol
• Uses 6 pin, 4 conductor RJ11 jack (not supplied)
Fig. 7
Hotkey
Common
N/O
N/C
Alarm Contacts
RS485 Port
00926170 – REF20/25 LB, PH, BB Operation 7
Operation
4.0C
1
Quick setup checklist
• Set time/date
• Change temperature display from factory default Celsius to Fahrenheit (if desired)
• Set high/low temperature alarms
• Select password access (if required)
• Setup chart recorder (if equipped)
• Verify solution is in bottle
DANGER
• Do not extend all of the drawers or baskets when
fullyloaded to avoid the possibility of the refrigerator
tipping forward
• Refrigeration module area contains mechanical, moving
parts. Keep hands and arms clear of this area at all
times. If access to this area is required, power to unit
must be disconnected rst.
Fig. 8
Interior LED lights
Interior lighting of refrigerator with door closed is controlled by light switch
(Fig 8.1) on interface.
Lights will be on whenever door is open regardless of light switch selection.
ATTENTION
• The time/date are not retained in the event of a power interruption or if the batteries are dead.
• Change batteries with the unit powered up. Change one battery at a time to retain time/date. Failure to follow this
procedure will result in loss of time & date and will not provide accurate time and date stamping for high or low
temperature alarms.
ottom Temp 3.5C
Fig. 9
Set time & date
Set time and date for stamping of minimum and maximum temperatures.
1. Press Menu button (Fig. 9).
4.0C
Bottom Temp 3.5C
Menu
8 Operation 00926170 – REF20/25 LB, PH, BB
Fig. 10
2. Use
to scroll and highlight Set time/date and press Enter to
select (Fig. 10).
3. Adjust the year using
and press NEXT.
4. Adjust the month using and press NEXT.
5. Adjust the day using and press NEXT.
6. Adjust the hour using and press NEXT. (24 HR Clock)
7. Adjust the minute using .
8. Press Enter to select values.
9. Press Back until the main temperature display screen is displayed.
Set time/date
Set Alarm Volume
Alarm Silence
Fig. 11
Set year: 2009
2009 10/19 16:13
4.0C
Back Enter
3.4C
Next Enter
Change temperature display to show degrees
Fahrenheit (if desired)
Follett has pre-set the temperature display to read in degrees Celsius. If
degrees Fahrenheit display is preferred:
1. Press Menu button (Fig. 12).
2. Use to scroll and highlight Display Settings and press Enter to
select (Fig. 13).
3. Use to scroll and highlight Degrees F/C and press Enter to
select.
4. Use to scroll and highlight F and press Enter to select.
5. Press Back button until the main temperature display screen is
The high alarm is set to a default of 40 C (104 F) from the factory. This
default setting is used so that the alarm will not sound while the unit is
pulling down to temperature. The low alarm default setting is 1.0 C (33.8 F).
After the unit has been installed and the system has stabilized
(approximately 1 hr), the high and low alarm set points should be adjusted
to desired settings.
1. Press Menu button (Fig. 14).
2. Alarm Settings will be highlighted. Press Enter to select (Fig. 15).
Fig. 14
4.0C
Bottom Temp 3.5C
Menu
Fig. 15
3. Use
select (Fig. 16).
to scroll and highlight High Alarm Set and press Enter to
4. Use to change set point and press Enter to accept (Fig. 17).
High Alarm Setpoint4.0C
40.0C
Back Enter
10 Operation 00926170 – REF20/25 LB, PH, BB
Fig. 18
5. Use
to scroll and highlight Low Alarm Set and press Enter to
select (Fig. 18).
6. Use
to change set point and press Enter to accept (Fig. 19).
7. Press Back until the main temperature display screen is displayed.
High Alarm Set
Low Alarm Set
Fig. 19
Low Alarm Setpoint4.0C
1.0C
4.0C
Back Enter
Back Enter
00926170 – REF20/25 LB, PH, BB Operation 11
Alarms
The refrigerator has several alarms that will sound an audible and visual alarm. Alarm type is shown on the top
line of the alarm display and multiple alarms will show progressively on the display. A red LED, to the right of the
display, accompanies all alarms.
All active alarms are conveyed to remote alarm relays. Remote alarm relay provides a choice of either a normally
closed (NC) or normally open (NO) contact. It is recommended for use at 24V 1A (relay is rated for 250V 10A).
Alarm displayed
Temp AlarmOnly top product temperature probe activates this alarm. Bottom product temperature probe,
if installed, is for display reference only.
Top Probe ErrorActivates with loss of signal from top probe (open or short circuit).
Bottom Probe ErrorActivates with loss of signal from bottom probe (open or short circuit).
Door Ajar AlarmActivates with door open longer than 1 minute.
AC Power AlarmActivates after 2 min delay with loss of AC power.
Display backlight will turn off to conserve battery life, but pressing any button will brighten
display for 30 seconds.
Low Battery AlarmsDisplay activates when (2) 9V controller back-up batteries decrease to 7.5V (maximum 4 hr
back-up time remaining.) This alarm will audibly chirp every 5 minutes.
Chart recorder – LED ashes green.
All batteries should be changed at same time. Replace batteries one at a time with AC
power on to keep correct time/date.
Evap Probe ErrorActivates with loss of signal from refrigeration control evaporator probe (open or short circuit).
Refrigerator goes into a xed on/off cycle until corrected. Default settings are 4 minutes
compressor on time and 8 minutes compressor off time. Cycle on time and off time are
adjustable in faulty probe cycle sub-menu of refrigeration controls menu.
Alarm muting
All audible alarms can be muted for up to 60 minutes in 5 minute
increments by pressing the MUTE button. The desired mute period will
display, and count down, in the window adjacent the MUTE label (Fig.20).
Conditions
Fig. 20
Door Ajar Alarm
4.0C
MENUMUTE
12 Operation 00926170 – REF20/25 LB, PH, BB
15 min
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.