Follett REF User Manual

Order parts online www.follettice.com
REF Series
Undercounter Refrigerator
Installation, Operation and Service Manual
Service numbers B59000 and above
Following installation, please forward this manual
801 Church Lane • Easton, PA 18040, USA Toll free (800) 523-9361 • (610) 252-7301 Fax (610) 250-0696 • www.follettice.com
00128892R02
Table of contents
Welcome to Follett 3 Before you begin 3
Specifications 3
Installation procedures 4
Installing legs 4 Installing shelves 4 Installing controller faceplate 4 Changing controller settings 4
Reversing door 5
Controller 6 Controller operation 6 Programming the controller 6
Operation 10
How the refrigerator works 10 Temperature control 10 Defrosting 10 Cleaning 10
Service information 11 Latch adjustment 11 Gasket replacement 11 Slide-out compressor tray 11 Controller replacement 12 Wiring diagram 12 Refrigeration system diagram 13 Troubleshooting guide 14
Accessory information 15 Temperature alarm 15 Pyxis 16
Replacement parts 17
2
Welcome to Follett
Follett equipment enjoys a well-deserved reputation for excellent performance, long-term reliability and outstanding after-the-sale support. To ensure that this product delivers that same degree of service, we ask that you take a moment to review this manual before beginning the installation. Should you have any questions or require technical help at any point, please call our technical service group at (800) 523-9361 or (610) 252-7301.
Before you begin
After uncrating and removing all packing material, inspect the equipment for concealed shipping damage. If damage is found, notify the shipper immediately and contact Follett Corporation so that we can help in the filing of a claim, if necessary.
Specifications
Series specifications
REF4-ADA 31.25" height fits below 34" high ADA-compatible counter 4.0 cu ft capacity REF5 34.00" height fits below standard 36" high counter 4.8 cu ft capacity
Electrical specifications
115V, 60Hz, 1 phase
Full load amps: 8.0
Minimum circuit ampacity: 15 amp
Maximum size of branch circuit overcurrent device: 15 amp
Refrigeration specifications
Refrigerant – R404A
Charge size – 8 oz
Maximum design pressures:
High side – 375psi Low side – 174psi
Installation specifications
Ambient temperature must not exceed 100°F (38°C).
The front louvered panel must be kept free of any cabinet trim or obstructions to ensure proper ventilation of the refrigeration system.
Important cautions
• Equipment must be wired according to local and NEC codes.
• Always disconnect power before servicing refrigerator.
3
Installation
Installing legs – required
1. Remove legs from plastic bag packed inside refrigerator.
2. Tip refrigerator back and screw legs in all the way to stop (they will extend 1/8" below base of REF).
3. Adjust legs as needed to level REF in both directions. To access legs, remove the lower front panel. Turn legs clockwise to extend legs.
Fig. 1
Installing shelves – required
1. Remove shelves and shelf brackets packed inside refrigerator. (If ordered, find cut-out upper shelf accessory in separate box.)
2. Install shelf brackets in pilasters (insert top tab, squeeze and push in lower tab).
3. If ordered, position cut-out upper shelf accessory below evaporator with cut-out around drain.
Installing controller faceplate – required
1. Remove °F and °C faceplates from plastic bag packed inside refrigerator.
2. Snap appropriate faceplate in place over controller face.
3. If °C display is desired, resetting of temperature controller is required. See below.
Fig. 2
2
1
3
Fig. 3
Changing temperature controller settings – optional
Follett’s temperature controller is pre-programmed with a 34°F set point and °F display. The 34° set point delivers a temperature range of 34°F – 38°F that may not meet the needs of your specific application. Follett’s controller set point can be changed to deliver the required range in either °F or °C. Refer to page 6 for instructions on changing set point and/or display to °C.
4
Fig. 4
Reversing the door swing – optional
1. Remove screws and latch from refrigerator cabinet. (Fig. 5.1).
2. Use flat screwdriver to carefully remove (do not scratch) hinge covers (Fig. 6.1).
3. Support door and remove screws attaching hinge to refrigerator cabinet (Fig. 6.2).
4. Cover hinge screw holes with screw hole plugs removed from opposite side.
5. Reverse door and reinstall hinge screws.
6. Reinstall latch on opposite side.
7. Remove screws and handle from door (Fig. 7.1).
8. Rotate handle (Fig. 7.2).
9. Reinstall handle screws (application of 242 blue Loctite® to handle screws recommended).
Fig. 5
1
2
Fig. 6
Fig. 7
2
1
1
1
2
Loctite is a registered trademark of Henkel Corporation in the United States and other countries.
5
Controller operation
In normal operation the controller displays cabinet temperatures in °F (default) or user-selected °C. °C temperatures are displayed to 1 decimal point.
Fig. 8
UP arrow rocker button
DOWN arrow rocker button
*
An LED located below the snowflake icon flashes when the compressor is running.
38
˚F
Rocker buttons to the right of the temperature display control all programming functions.
The controller is pre-programmed with a 34°F set point which provides a compressor cut-in at 38°F and cut-out at 34°F. This may not meet your specific application needs. For example, many pharmaceutical manufacturers recommend that their refrigerated medications be stored between 36°F and 46°F. Instructions for changing the set point are found below.
Refer to the chart below for the set point for your application’s required temperature range:
Set point Cut-in/ Cut-in/ Normal display °F/°C Cut- out °F Cut-out °C range temperature °F/°C
prg
SET
*
SET rocker button
34° / 1.1° 38° / 34° 3.3° / 1.1° 32° - 38° / 0° - 3.3°
35° / 1.7° 39°/ 35° 3.9° / 1.7° 33° - 39° / .6° - 3.9°
36° / 2.2° 40° / 36° 4.4° / 2.2° 34° - 40° / 1.1° - 4.4°
37° / 2.8° 41° / 37° 5° / 2.8° 35° - 41° / 1.7° - 5°
38° / 3.3° 42° / 38° 5.6° / 3.3° 36° - 42° / 2.2° - 5.6°
39° / 3.9° 43° / 39° 6.1° / 3.9° 37° - 43° / 2.8° - 6.1°
40° / 4.4° 44° / 40° 6.7° / 4.4° 38° - 44° / 3.3° - 6.7°
41°/ 5° 45° / 41° 7. 2 °/ 5° 39° - 45°/ 3.9° - 7.2°
All set points have a 4°F differential (HY setting on the controller). The 4°F differential means that with a 34°F set point, for example, the compressor will turn off at 34°F and turn on when it reaches 38°F.
Caution: Do NOT change the differential (HY setting) except as indicated below in instructions for changing the °C or °F display. Changes to the HY setting can cause short-cycling and failure of the compressor.
Because there is still refrigerant in the evaporator, there can be an additional 1° - 1.5°F of downward “drift” in temperature after the compressor turns off. The temperature may momentarily display as low as 32°F (32.9°F and below rounds down to 32°F) before beginning to rise again.