Horizon Elite™ Ice Machine Installation Instructions
HCD/HMD/HCF/HMF1010R _ _
HCD/HMD/HCF/HMF1410R _ _
for Remote Condensing Unit
801 Church Lane • Easton, PA 18040, USA
Toll free (877) 612-5086 • +1 (610) 252-7301
www.follettice.com
01113356R03
Horizon Elite 1010 series Horizon Elite 1410 series
W1 Width 36.25" (91.4 cm) – AJA7490ZXDPN and
AWA9490ZXTPN
38.10" (96.8 cm) – all others
D1 Depth 25.50" (64.8 cm) – AJA7490ZXDPN and
AWA9490ZXTPN
21.50" (54.6 cm) – all others
H1 Height 26.10" (66.3 cm) – AJA7490ZXDPN and
AWA9490ZXTPN
28.50" (20.3 cm) – all others
Electrical single phase – 208-230/60/1
three phase – 208-230/60/3
Minimum circuit ampacity single phase – 10.7A
three phase – 9.9A
Maximum overcurrent
protection
Outdoor condensing unit
operating limits
(air temperature)
Maximum refrigerant line run
length
Maximum line rise above
evaporator
Evaporator mounting above
condenser
Maximum refrigeration line
drop without oil trap
Refrigerant charge 12.5 lb required at installation 12.5 lb – single phase (Tecumseh)
Approximate ship weight 260 lb (118 kg) – All others
Approximate net weight 250 lb (114 kg) – All others
single phase – 15A
three phase – 15A
min –20 F (–29 C)
max 120 F (49 C)
100' (30.5 m) 100' (30.5 m)
35' (10.7 m) 35' (10.7 m)
15' (4.6 m) 15' (4.6 m)
15' (4.6 m) 15' (4.6 m)
212 lb (96 kg) – Tecumseh ASFS9516ZNAMC1
232 lb (105 kg) – Tecumseh AJA7490ZXDPN
180 lb (82 kg) – Tecumseh AJA7490ZXDPN
200 lb (91 kg) – Tecumseh ASFS9516ZNAMC1
36.25" (90.1 cm) – single phase (Tecumseh)
37.75" (95.9 cm) – three phase (Larkin)
25.50" (64.8 cm) – single phase (Tecumseh)
28.25" (71.6 cm) – three phase (Larkin)
26.10" (66.3 cm) – single phase
19.75" (50.2 cm) – three phase (Larkin)
single phase – 208-230/60/1 (Tecumseh)
three phase – 208-230/60/3 (Larkin)
single phase – 19.3A (Tecumseh AWA9513ZXDPN)
single phase – 16.4A
three phase – 14.2A (Tecumseh AWA9517ZXDPN)
three phase – 15A (Larkin)
single phase – 30A (Tecumseh AWA9513ZXDPN)
single phase – 25A
three phase – 25A (Tecumseh AWA9517ZXDPN)
three phase – 15A (Larkin LZT015M6CFIM)
three phase – 20A (Larkin LCH0015MCACZ)
min –20 F (–29 C)
max 120 F (49 C)
10 lb – three phase (Larkin)
required at installation
270 lb (122 kg) –
234 lb (106 kg) − Tecumseh ASFS9516ZNAMC1
230 lb (104 kg) – three phase (Larkin)
260 lb (118 kg) – Tecumseh AWA9513ZXDPN
202 lb (92 kg) – Tecumseh ASFS9516ZNAMC1
210 lb (95 kg) – three phase (Larkin)
(Tecumseh ASFS9516ZNAMC1)
(Tecumseh ASFS9516ZNAMC1)
Tecumseh AJA7490ZXDPN
2
REMOTE CONDENSING UNIT
Prior to installation, carefully unpack and inspect the
contents of your condensing unit!
Site preparation
To ensure proper performance, ease of service and warranty coverage, it is critical that you follow
the requirements detailed in this manual. If you cannot meet these requirements or have questions,
call our technical service group at 877.612.5086 for installation support.
1
2.1
1. 1
Condenser Unit Clearances
min. 36.00"
(91.4 cm)
exhaust
24.00"
(61.0 cm)
air in
48.00"
(121.9 cm)
24.00"
(61.0 cm)
• Position condenser unit as shown.
Required clearances:
§ Mininum 48” (121.9 cm) front and back
§ Minimum 24” (61.0 cm) left and right
§ Minimum 36” (91.4 cm) above
REMOTE CONDENSING UNIT
48.00"
(121.9 cm)
3
2.1
1. 2
Condenser installation specications
S-trap
required
Easton Pennsylvania
CORPORATION
PART NO
SERIAL NO
MODEL
SINGLE
FULL LOAD AMPS
HZ
VOLTS
PHASE
MOTOR COMPRESSOR THERMALLY PROTECTED
OZ
CHARGE
REFRIGERANT
PSIG
DESIGN PRESSURE HIGH SIDE
LOW SIDE
208264
MIN. BRANCH CIRCUIT AMPACITY
AMPS
Stock Module Identification Plate
MADE IN
ULU
NSF
THE USA
L
RR
Module No.
MAX. BRANCH CIRCUIT FUSE SIZE
AMPS
C
Product
Service No.
EVAPORATOR
UNIT
➊
100' max.
(30.5 m)
➍
➊
P-trap
required
EVAPORATOR UNIT LEVEL
CONDENSER UNIT
maximum
line rise
CONDENSER UNIT
maximum
line drop
➋
+35'
(+10.7 m)
+20'
(+6.1 m)
–15'
(–4.6 m)
100' max.
(30.5 m)
➌
➍
Site layout:
• Outdoor ambient temperature range: –20 F to 120 F (–29 C to 49 C)
• Installation with condenser unit elevations above 20' (6.1 m) require an S-trap at the midpoint
of the rise and a P-trap at the top of the rise
➊
• Maximum line rise must not exceed 35' (10.7 m) ➋
• Maximum line set length must not exceed 100' (30.5 m)
• Maximum line drop must not exceed 15' (4.6 m)
➍
➌
4
REMOTE CONDENSING UNIT